目录1.安全注意事项·······················································································12.安装要求·····························································································12-1安装位置·························································································22-2安装方法·························································································32-3电器配线························································································624机器排水·························································································63.启动与运转···························································································631运行前后注意事项···········································································63-2机器操作说明··················································································74.维护与保养·························································································104-1定期清洁·······················································································104-2长时间停用时注意··········································································105.故障排除·····························································································10附录一······································································································11附录二······································································································11
1,安全注意事项⑴当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册中所提到的注意事项,以避免出现意外情况;⑵请勿用湿手操作,以免引起触电;⑶当需要保养或维护时,请先切断所有电源以免引起触电事故;⑷空调器上不易放置任何物品,以免滑落造成人员伤害;⑸当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受伤或机器损坏;⑹本机器露天放置做好外罩密封处理以免雨水进入机体内,并且也不适宜于安装在振动较大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;⑺本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;⑻禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发生。1.安装要求本空调器为半嵌侧挂式系列,半嵌侧挂式(图一),为使机组能在理想的状况下工作,在安装上请注意以下要求:图一侧挂式空调器电控箱回风(热)出风(冷)
2-1安装位置⑴空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装空调器,则一定要每天做好空调器的清洁和保养工作。⑵空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、排风口离墙面的间距应大于500mm;⑶空调器周围请勿放置杂物,以保持空气畅通流通;⑷本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。⑸请安装本空调器于周围温度在45℃以下的范围之内高温系列55℃以下;⑹本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜角不大于5°如图四所示;⑺控制箱内正对出风口的电器元件与出风口的最小距离应大于200mm,因距离太近电器元件表面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。⑻当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿度能控制在较为理想的状态下。图三电控箱冷气机
图四错误正确错误正确2-2安装方法⑴当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;⑵为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;⑶空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备损坏,当安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的重量不会使整个电气柜倾倒;⑷电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;⑸箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;⑹当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而损坏;⑺具体的安装方式如下
安装示意图:2-3电器配线:⑴机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若所提供的电压在额定值±10%以内,本机组可正常使用;L,N,PE,为电源输入引线经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意⑵空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;⑶在机组的电器回路上请自行安装断路器或漏电保护装置;⑷请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负载,引发事故。2-4机器排水:(户外机型无以下排水管项目)本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:⑴请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;⑵根据实际情况排水软管长度适当即可,过长部分请切除;⑶排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水
严重时产生外溢,引起空调器或者电气柜故障。2.启动与运行3.3-1运行前后注意事项⑴启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开始工作;⑵当在运转中需重新启动空调器时,请间隔3分钟以上,倘若频繁启动且间隔时间过短会引起机器损伤;⑶当空调器倾斜时请勿开启,避免漏水、触电等情况发生;⑷空调器在出厂时温度点已经设定好为32℃,若需重新设定时请控制在允许范围之内设定,以免引起机器运行不正常;如果空调器有加热功能,出厂时设置为5℃⑸当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进行检查维修。安装使用说明A3.0简介:ZL-696温控器采用小型化、IP65等级面板防护设计,体积小重量轻,操作简捷安装方便。适用于小型机柜空调系统的温度控制。主要功能温度测量电加热控制温度显示系统缺氟保护温度校正高温、低温告警压缩机延时保护传感器故障告警蜂鸣器告警输出无源数字量输入RS485通讯规格尺寸1.前面板尺寸:长78x宽34.5(毫米)2.安装开孔尺寸:长71x宽29(毫米)3.整机尺寸:长78x宽34.5x深71(毫米)4.传感器线长:1米(含探头长度)主要技术指标感温元件:NTC3470/10K电源电压:ZL696AR+:AC10V~12V300Ma(外置电源变压器)设定范围:0~50℃ZL696ALR+:DC14V-60V300mA显示范围:40~130℃接线端子:连接2*1.5mm2或1*2.5mm2的导线工作环境:10~45℃负载电流:5~16A/250Vac,(阻性负载)存储温度:-30~70℃外壳:PC+ABS阻燃湿度:5~85%RH(不结露)防护等级:IP65(前面板)操作指南显示说明显示屏信号说明图标功能亮灭闪烁压缩机启动停止准备制冷,压缩机正在延时保护
AUX电加热运行--------风机运行停止维修有故障无故障报警有报警无报警----通讯正在通讯HACCP压缩机强制强制运行面板数码管说明4位红色数码管显示测量温度值和告警代码;显示代码说明序号显示代码说明1E01温控温度传感器故障(短路或断路)2E02蒸发器温度传感器故障(短路或断路)3Hi高温告警4Lo低温告警5HP系统高压保护6LP系统低压保护7SmK烟感报警8LOF系统缺氟保护9VENT系统换气10Err密码输入错误11UnL恢复默认出厂密码“1111”按键操作制冷、制热参数设置按〖S〗键并保持3秒钟,进入参数设置状态,这时数码管显示『Cool』,用〖▲〗或〖▼〗键选择参数代码,选定一个参数后按〖S〗键显示该参数的设定值,这时再按〖▲〗或〖▼〗键可对参数进行设置,设置完成后再按〖S〗键,回到显示参数代码状态。序号参数代码设置功能设定范围说明出厂设定值01CooL制冷温度设定0~50℃制冷、制热温度设定2202HEAT制热温度设定0~30℃间隔1℃8当参数设置完成后必须长按〖S〗键3秒,系统退出参数设置状态,此次参数设置被保存。在参数设置状态如果连续30秒内无按键操作,系统退出参数设置状态,但此次参数设置无效,控制器仍按原来的参数运行;系统参数设置·系统参数设置界面进入:使用一组密码进入参数设置状态(出厂默认密码为1111),按〖P〗键并保持3秒钟,数码管显示『---0』,按〖▼〗键循环选择密码当前位,按〖▲〗键设置当前位密码值,密码设置完成后按〖S〗键确认。如果密码错误,显示『Err』蜂鸣器响三声后退出参数设置状态;如果密码输入正确,蜂鸣器响一声,进入参数设置状态,这时数码管显示『U00』,用〖▲〗或〖▼〗键选择参数代码,选定一个参数后按〖S〗键显示该参数的设定值,这时再按〖▲〗或〖▼〗键可对参数进行设置,设置完成后再按〖S〗键,回到显示参数代码状态。·系统参数设置界面退出:当参数设置完成后必须长按〖P〗键3秒,系统退出参数设置状态,此次参数设置被保存。在参数设置状态如果连续30秒内无按键操作,系统退出参数设置状态,但此次参数设置无效,控制器仍按原来的参数运行;
工作参数代码及设置说明如下表所示:序号参数代码设置功能设定范围说明出厂设定值1U00制冷启动温度0~50℃222U01制热启动温度0~30℃83U02制冷/制热温差1.0~10.0℃24U03蒸发风机启动温度0~50℃165U04蒸发风机温差1.0~10.0℃36U05高温报警-5.0~90℃高温/低温设定间隔1℃507U06低温报警58U09柜温传感器校正9.9~+9.9℃09U10内盘温度传感器校正9.9~+9.9℃010U16蒸发器温度传感器使能设定0~10:禁用;1:启用111U18电加热工作模式0~11:启用电加热10:禁用模式12U22高压告警输入模式0~10:常闭;11:常开13U23低压告警输入模式0~10:常闭;11:常开14U24烟感告警输入模式0~10:常闭;11:常开15U25蜂鸣器报警0~10:禁用;1:启用116U26压缩机最短停机时间010分钟317U27压缩机最短运行时间010分钟318U29换气周期0-180小时2419U30换气时间0-99分钟520U33系统开关机ON,OFFON:开机,OFF:关机ON21U34RS485波特率设定0~30:2400bps31:4800bps2:9600bps3:19200bps22U35设备地址1~99123U99密码0000~9999111124End设定结束查看蒸发器温度在显示当前温度时按住〖▲〗键,数码管显示蒸发器传感器温度值,松开则恢复显示当前温度值。控制逻辑
■蒸发风机控制(有蒸发风机控制点时有效)系统上电后3秒钟后检测柜内温度是否满足启动蒸发风机的条件:蒸发风机启动条件:1、柜内温度≥[蒸发风机启动温度]2、电加热启动时,蒸发风机同时启动,电加热停止时,蒸发风机延时1分钟停止。3、压缩机启动时,蒸发风机同时启动,压缩机停止时,蒸发风机延时1分钟停止。蒸发风机停止条件:柜内温度≤[蒸发风机启动温度]-[蒸发风机温差].■压缩机控制系统上电后3秒钟后检测柜内温度是否满足启动压缩机的条件:压缩机启动条件:柜内温度≥[制冷温度]压缩机停止条件:柜内温度≤[制冷温度][制冷/制热温差]压缩机开启时开启蒸发风机;当压缩机关闭时,根据蒸发风机温度开启点(默认16度),判断开关蒸发风机。冷凝风机与压缩机同点控制压缩机启停还需要满足如下条件:满足压缩机最短运行时间和最短停机时间的要求。■电加热控制系统上电3秒钟后检测柜内温度是否满足启动电加热的条件:电加热启动条件:柜内温度≤[制热温度]电加热停止条件:柜内温度≥[制热温度]+[制冷/制热温差]电加热开启时开启蒸发风机;当电加热关闭时,延时1分钟停止。■换气阀控制系统缺省为每间隔24小时换气5分钟,参数可设置。当机组运行时间到达[换气间隔]时间后,关闭电加热,压缩机,开启换气阀,机组进行换气,当到达[换气时间]时间后,关换气阀,满足压缩机最短停机时间,开电加热,压缩机,完成一个换气周期。蜂鸣器功能每按键一次蜂鸣器鸣叫一声,在参数设置确认时长鸣一次,在进行无效操作时蜂鸣器鸣叫三声;当系统出现故障或有外部报警输入时,如果参数U28=0,关闭蜂鸣器报警功能,蜂鸣器不鸣叫报警;如果参数U28=1,则蜂鸣器连续鸣叫报警;系统恢复正常后,自动消除蜂鸣器报警状态.温度值校正功能当测量温度值与传感器安装位置实际温度有误差,可通过【温度修正参数】进行校正,校正范围±9.9℃;按一次〖▲〗或〖▼〗键调整温度校正值增或减0.1℃,按住不放则快速调整;系统缺氟(漏氟)保护:当压缩机启动5分钟后,检测温控传感器、蒸发器传感器温度,如果温控传感器温度高于蒸发器传感器温度5度以上温差,判定系统正常,否则认定为缺氟保护(漏氟),并显示报警代码“LOF”。强制关闭压缩机。1小时内如果连续发生3次缺氟保护,需要手动重新上电解除告警。系统防冻结保护:当压缩机启动1min后,检测蒸发器传感器温度,如果蒸发器传感器温度小于等于-1度并保持5sec,判定系冻结保护。系统强制关闭压缩机,当蒸发器温度上升8度以上,系统恢复正常制冷干接点告警输出当发生传感器故障、高温、低温、高压/低压报警、烟感报警、缺氟保护时,干接点继电器动作,输出告警信号;信号名称说明NO故障输出(故障时断开,正常时闭合)NC故障输出(故障时闭合,正常时断开)COM公共端恢复出厂参数与密码:控制器在运行状态下,同时按下〖P〗与〖▲〗键不放并保持5秒后蜂鸣器响一音调声,数码管显示『UnL』,此时再按2次〖▼〗键后,蜂鸣器响一音调声,控制器自动恢复出厂参数与默认密码「1111」;产品信息查询:
控制器在运行状态下,同时按下〖S〗与〖▲〗键不放并保持3秒后蜂鸣器响一音调声,数码管滚动显示产品型号和版本信息;故障检测及保护压缩机保护压缩机除了高压和低压保护之外,还具备如下保护:压缩机最短停机时间为3分钟,压缩机停止后最少要3分钟才能重新启动。故障检测及动作根据系统设置,各故障点常闭表示故障点如果和该排插座的DCOM(公共端)形成回路则表示正常,如果断开则表示故障。没有用到的故障点,请将其设置为常开,以免引起不必要的报警。故障报警时,显示屏故障指示灯点亮,蜂鸣器发出报警声。故障消音可按任意键。序号报警代码故障推迟时间持续时间复位操作备注1E01柜内温度传感器故障0秒5秒自动报警,停压缩机、加热器,开蒸发风机。2E02蒸发器传感器故障0秒5秒自动报警,取消防冻结、缺氟保护。3HP高压报警0秒5秒自动报警,停压缩机4LP低压报警压缩机启动30秒5秒自动报警,停压缩机5SmK烟感报警0秒5秒手动报警,停整机6Hi高温报警0秒5秒自动报警7Lo低温报警0秒5秒自动报警8LOF缺氟报警0秒5秒手动报警、停压缩机9---冻结保护压缩机启动2分自动停压缩机,开蒸发风机故障复位后压机启动需满足压缩机停机时间大于[压缩机最短停机时间];控制器装配敬告:请尽量避免将控制器安装在以下环境中:◆相对湿度大于90%或存在凝露的地方;◆强烈振动或敲击;◆暴露在连续的水雾喷射下;◆暴露在侵蚀性和污染气体下(例如:含有硫和氨的烟气、盐雾、烟雾),以防止侵蚀和氧化;◆含有易爆物品或可燃混合气体的环境;安装步骤第1步:将控制器嵌入孔中;第2步:通过在设备的导轨方向滑动支架来固定控制器,直到将控制器压实在面板上;电气连接敬告:◆电气接线操作必须由有资质的技术人员来完成。◆使用规定电源类型以外的电源可能会给系统带来严重损害;◆尽可能将传感器、开关量输入信号线与感性负载线、电源线分开排线,以避免电磁干扰。绝不能将电源线(包括电力线)和传感器信号线布在同一管道中。不能将传感器线安装在电源设备(接触器、断路器或类似设备)的紧邻区域;◆尽可能的降低传感器接线的长度,并避免在电源设备周围形成螺旋形线路。◆安装时避免直接接触内部电子元件。◆需直接连接到设备以及完成布线和检查布线时,请仔细阅读并遵照下面的指导进行操作,并仔细注意给出的图示:如果连接错误,可能会危害到用户安全,也可能导致连接设备和元件出现故障。请务必为设备配备所有机电安全保护装置,这些装置是为保证设备正常运行和用户的绝对安全而必需配备的。电气接线图
4.维护与保养请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机器上安装的是尼龙滤网的可直接从侧面拔出4-1定期清洁本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,一般每周需清洗一次;⑵请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发生触电事故;4-2长时间停用时注意⑴请切断电源,以防意外;⑵清理冷凝器、过滤网及内部油污;⑶请对机器采取防尘措施,延长机器使用寿命。
4.故障排除故障状况1电源接通后,室内、室外风机不运转可能原因※保险丝熔断※停电或无电源状况排除※更换保险丝※检查电源状况故障状况2在运行中突然停机,电控箱内温度高于设定点温度两度以上可能原因※环境温度过高,导致压缩机热保护※过滤网堵塞或者冷凝器过脏,导致压缩机热保护状况排除※改善周边环境,使散热畅通※对过滤器及冷凝器进行清洗故障状况3机器正常运转,却不制冷可能原因※压缩机损坏※制冷系统泄露※机组蒸发器大面积结霜状况排除※更换压缩机,重新抽真空充注制冷剂※查出泄露处,并重新抽真空加制冷剂※立即停机,把设定温度调高到35℃,十分钟后重新开机◇若上述措施均不能排除故障,请致电本公司咨询!附录1:产品技术参数型号:BCW-500GR工作电源:交流220V±10%频率50Hz±4%运行电流:<2.5A功率:515W制冷剂:R134a制冷量:500W制热量:500W防护等级:内循环:IP45外循环:IP55允许机柜内温度设定范围:30--38℃(出厂设定30℃)允许使用环境温度范围:-25--45℃噪音:55dB
附录2:电气原理图室内风机室外风机压缩机M1M2M3C2C3LNPEt℃温控器BCW-5主00回GR路电路图
苏州博图制冷设备有限公司地址:苏州市吴江区太湖新城镇黄沙路23号电话:0512-631728510512-63172852传真:0512-63102853邮编:215223全国统一服务热线:400-920-7382网址www.botuzl.comEmail:botu@botuzl.com