AWT100 wireless communication terminal
General
At present, wireless technology has gradually become an important direction for the
development and application of networks in the industrial Internet in the future due to its
advantages of easy deployment, low construction cost and wide applicable environment.
AWT100 wireless communication terminal is a new wireless data acquisition device launched
by Acrel. The uplink communication includes 2G, 4G, NB, LoRa, LoRaWAN and other
communication modes. The downlink interface provides a standard RS485 data interface,
which can easily connect power meters and RTUs, PLC, industrial computers and other
equipment, only need to complete the initial configuration, you can complete the data
acquisition of MODBUS equipment; at the same time AWT100 series wireless communication
terminal uses a powerful micro-processing chip, with built-in watchdog technology, reliable
performance stable.
Type Description
AWT100-□
2G:2G communication terminal
4G:4G communication terminal
NB:NB-IoTcommunication terminal
Lora:LoRa communication terminal
LW:LoRaWAN communication terminal
Acrel wireless communication terminal
Function Description
■Support data acquisition of serial port MODBUS RTU protocol, and communicate with Acrel
server through Acrel platform protocol.
■Supports data acquisition for up to 30 MODBUS RTU devices.
■Supports the acquisition of 5 register address fields for each MODBUS device, each register
address range does not exceed 64.
■ Supports triggering alarms by preset alarm addresses and alarm values for each MODBUS
address range. Each address domain alarm address currently has a maximum of five.
■Support server MODBUS or LoRa transparent communication.
■Support fixed IP and dynamic domain name resolution to connect to the data center.
■Support transparent transmission protocol, universal mode (active rotation, timed reporting),
MQTT protocol, smart power wireless protocol, prepaid wireless protocol
Negotiation, custom development.
■ The functions of the AWT100-LW wireless communication terminal are still under
development, and data can be uploaded to the server through LoRa communication in the
future.
Note: ①The AWT100-2G/NB/4G wireless communication terminal can communicate with the
Acrelserver through the Encore platform protocol.
Technical Parameter
Parameter
name
AWT100-4G AWT100-NB AWT100-2G
AWT100-LoRa
AWT100-LW
LTE-FDD B1 B3 B5 B8
GSM 850
LTE-TDD B34 B38 B39 B40
H-FDD B1 B3 B8 EGSM 900 LoRa 460 ~
Working
frequency
B41
510MHz
B5 B20 DCS 1800
CDMA B1 B5 B8
PCS 1900
GSM 900/1800M
LTE-FDD Downstream rate
up to 150Mbps
Uplink rate up to
50Mbps
LTE-TDD Downstream rate
Transmission
rate
up to 130Mbps
Uplink rate up to
35Mbps
CDMA Downstream rate
up to 3.1Mbps
Uplink rate up to
Downstream rate
up to 25.2Kbps
Uplink rate up to
15.62Kbps
GPRS
Downstream rate
up to 85.6kbps
Uplink rate up to
85.6kbps
LoRa 62.5kbps
1.8Mbps
GSM Downstream rate
up to 107Kbps
Uplink rate up to
85.6Kbps
Downstream RS485 communication
Uplink 4G communication
NB-IoT
communication
2G
communication
LoRa
communication
SIM card
voltage
3V,1.8V /
Static power
consumption:≤
Working
current
Static power consumption: ≤1W, transient power consumption: ≤3W
0.5W,
transient power
consumption:≤
1W
Antenna
interface
50Ω/SMA(Female head)
Serial port
type
RS-485
Baud rate 4800bps、9600bps、19200bps、38400bps(default 9600bps)
Working
Voltage
DC24V or AC/DC220V①
Working
temperature
-10℃~55℃
Storage
temperature
-20℃~70℃
Humidity
range
0 to 95% non-condensing
Note: ①AC/DC220V power supply requires an external AWT100 power module.
Dimension Drawings
Wiring and Installing
Wiring sample of voltage and current
1.(1)AWT100-2G/NB/4G/LoRa/LW terminals and wiring
Auxiliary power supply (DC24V) RS485 communication
(2) The network port function (the power and RS485 interface) definition
1 2 3 4 5 6 7 8
POWER
(DC12V)
GND NC 485A 485B
(3)AWT100-2G/NB/4G/LoRa/LW side interface definition
1 2 3 4 5
10 9 8 7 6
1 2 3 4 5 6 7 8 9 10
NC +5V GND 485A NC 485B GND +5V NC
Note:
The two interfaces of the network port and the terminal can only be used one by one and cannot be used at the
same time.
2.(1)Terminals and Wiring of AWT100 Power Module (Selected for AC220V Power Supply)
Auxiliary power supply (AC/DC 220V)
(2) AWT100 Power Module side interface definition
1 2 3 4 5
10 9 8 7 6
1 2 3 4 5 6 7 8 9 10
NC GND +5V NC +5V GND NC
Panel light definition
1.AWT100-2G/NB/4G wireless communication terminal panel light definition
LINK RSSI COMM
Green Red Orange
The green indicator light flashes The red indicator flashes The orange indicator blinks to
for 2 seconds. The wireless for 3 seconds. The signal show that there is network
module is being initialized. strength is lower than data communication.
The green indicator blinks for 1 20%.
second and is connecting to the
server.
If the green indicator is steady on,
the server is connected and the
signal strength is greater than
20%.
2.AWT100-LoRa/LW wireless communication terminal panel light definition
RUN LoRa COMM
Green Red Orange
The green indicator light is The red indicator flashes for 1 The orange indicator flashes
steady on, indicating that second when there is a LoRa for 1 second when there is
the meter is working signal receiving and transmitting 485 signal receiving and
properly. data. sending data.
3.Panel Light Definition for AWT100 Power Module
RUN : If the green indicator light is steady on, the power module is working properly. If the
indicator is off, the module is not powered or faulty.
迅捷 PDF 转换器




