苏州博图制冷设备有限公司用户操作使用说明书BCQ-2600FC-380V工业机柜空调说明书
目录1.安全注意事项·······················································································12.安装要求·····························································································12-1安装位置·························································································22-2安装方法·························································································32-3电器配线························································································62-4机器排水·························································································63.启动与运转···························································································63-1运行前后注意事项···········································································632机器操作说明··················································································74.维护与保养·························································································104-1定期清洁·······················································································104-2长时间停用时注意··········································································105.故障排除·····························································································10附录一······································································································11附录二······································································································11
1.安全注意事项⑴当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册中所提到的注意事项,以避免出现意外情况;⑵请勿用湿手操作,以免引起触电;⑶当需要保养或维护时,请先切断所有电源以免引起触电事故;⑷空调器上不易放置任何物品,以免滑落造成人员伤害;⑸当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受伤或机器损坏;⑹本机器不宜露天放置以免雨水进入机体内,并且也不适宜于安装在振动较大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;⑺本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;⑻禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发生。2.安装要求本空调器为侧挂式系列,侧挂式(图一),为使机组能在理想的状况下工作,在安装上请注意以下要求:图一侧挂式
空调器电控箱回风(热)出风(冷)2-1安装位置⑴空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装空调器,则一定要每天做好空调器的清洁和保养工作。⑵空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、排风口离墙面的间距应大于500mm;⑶空调器周围请勿放置杂物,以保持空气畅通流通;⑷本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。⑸请安装本空调器于周围温度在45℃以下的范围之内高温系列55℃以下;⑹本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜角不大于5°如图四所示;⑺控制箱内正对出风口的电器元件与出风口的最小距离应大于200mm,因距离太近电器元件表面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。
⑻当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿度能控制在较为理想的状态下。图三电控箱冷气机图四错误正确错误正确2-2安装方法⑴当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;⑵为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;⑶空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备损坏,当安装在电气柜门上时,最好该扇箱门能固定不
动,当需要打开时请先确认好加在门上的重量不会使整个电气柜倾倒;⑷电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;⑸箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;⑹当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而损坏;⑺具体的安装方式如下:
C.用升降车安全的把空调器从安装面安装到电控箱上,注意安装时把电线先从电线孔伸入到电箱内,再在电控箱内侧螺栓上垫好垫圈,并用螺帽拧紧。D.d.在机组底部出水口连接好排水管,用抱箍固定好,另一端请引入排水沟或蓄水桶内,检测电源是否与机组匹配,然后接上电源即可开机使用。b.卸下机组背后安装螺钉上的螺帽与垫圈,控制好螺栓的伸出长度约15mm2-3电器配线:⑴机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若所提供的电压在额定值±10%以内,本机组可正常使用;排水管蓄水桶螺帽与垫片进风口送风口a.首先在电控柜上开好与所选空调相对应的安装孔电控箱电控箱机柜开孔电源线机柜侧面或门
经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意.⑵空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;⑶在机组的电器回路上请自行安装断路器或漏电保护装置;⑷请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负载,引发事故。2-4机器排水:本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:⑴请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;⑵根据实际情况排水软管长度适当即可,过长部分请切除;⑶排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水严重时产生外溢,引起空调器或者电气柜故障。3.启动与运行3-1运行前后注意事项⑴启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开始工作;⑵当在运转中需重新启动空调器时,请间隔3分钟以上,倘若频繁启动且间隔时间过短会引起机器损伤;⑶当空调器倾斜时请勿开启,避免漏水、触电等情况发生;⑷空调器在出厂时温度点已经设定好为30℃,若需重新设定时请控制在允许范围之内设定,以免引起机器运行不正常;如果空调器有加热功能,出厂时设置为5℃⑸当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并
请专业人员进行检查维修。使用说明V1.0.0简介:BTW-289+系列温控器采用小型化、IP65等级面板防护设计,体积小重量轻,操作简捷安装方便。适用于小型机柜空调系统的温度控制。主要功能1.制冷,风机自动控制2.压缩机智能保护3.多种故障告警,超高温,低温告警,系统高压报警,缺氟报警4.外部开关量输入检测,继电器输出告警,常开,常闭点自由配置5.标准RS485通讯接口,ModbusRTU通讯协议规格尺寸1.前面板尺寸:长78x宽34.5(毫米)2.安装开孔尺寸:长71x宽29(毫米)3.整机尺寸:长78x宽34.5x深71(毫米)4.传感器线长:1米(含探头长度)主要技术指标感温元件:NTC3435/10K电源电压:交流型:AC220V±20%50HZ设定范围:0~50℃接线端子:连接2*1.5mm2显示范围:40~99℃或1*2.5mm2的导线工作环境:-10~45℃负载电流:压缩机16A,风机10A,告警5A存储温度:-30~70℃外壳:PC+ABS阻燃湿度:5~85%RH(不结露)防护等级:IP65(前面板)操作指南显示说明显示屏信号说明图标功能亮灭闪烁压缩机启动停止准备制冷,压缩机正在延时保护电加热运行加热延时开启风机运行停止风机延时开启set设置参数设置状态测控状态----+强启动强制启动压缩机退出强启动面板数码管说明3位彩色数码管显示测量温度值和告警代码;告警代码序号显示代码说明1“E01”温控传感器故障(短路或断路)3“E02”蒸发器传感器故障(短路或断路)3“E03”系统缺氟保护4“Hi”高温告警5“Lo”低温告警
8“LA”外部无源数字量输入告警(系统高压告警)10“FrE蒸发器冻结保护按键操作系统参数设置·系统参数设置界面进入:设置温度:测控状态下,长按[set]3s,出现[St],再按[set],出现制冷温度,按〖▲〗或〖▼〗键可对参数进行设置,设置完成后再按[RST]键,或者30s无按键操作,自动保存并回到正常测控状态。设置内部参数:测控状态下,长按[set]3s,出现[St],按〖▲〗出现Po,再按[set],显示0,按〖▲〗或〖▼〗键将Po设置到55,再按[set],返回Po,此时按上下键,即可选择其他参数进行配置。工作参数代码及设置说明如下表所示:参数代码设置功能设定范围说明出厂设定值St制冷温度设定15~50℃30Po密码0~9955固定不可调0管理员参数(需要正确的密码,Po=55)F00温差1~20℃5F01高温报警温度5~60℃高温/低温设定间隔1℃50F02低温报警温度5F03蒸发风机温度设定0~40℃26F04蒸发风机温差1~9℃2F05温控探头校正9~9℃0F06蒸发器探头校正9~9℃0F07高温报警失效0~10:禁用;1:启用1F08低温报警失效0~10:禁用;1:启用1F09系统缺氟失效0~10:禁用;1:启用1F10蒸发器探头使能设定0~10:禁用;1:启用0F11压缩机工作模式0~10:自动模式(启用压缩机)1:禁用模式0F12风机工作模式0~10:温控模式1:常开模式1F13外部输入告警模式0~10:常闭;1:常开0F14蜂鸣器报警0~10:禁用;1:启用1F15压缩机开机延时时间1~5分钟3F16压缩机最短持续运行时间1~5分钟3F17系统开关机0:通电关机,1:通电开机1F18RS485波特率设定0~30:4800bps1:9600bps2:19200bps3:115200bps3F19设备地址1~641查看蒸发器温度在显示当前温度时按一下〖▲〗键,数码管显示制冷设置温度值,1S后恢复显示当前温度值。在显示当前温度时按一下〖▼〗键,数码管显示蒸发器探头温度值,1S后恢复显示当前温度值。控制功能说明:压缩机控制◇当测量温度≥【制冷设定温度】+【温差】,且压缩机停机时间大于【压缩机开机延时时间】,压缩机开启;◇当测量温度≤【设定温度】,且压缩机开机时间大于【压缩机最短持续运行时间】,压缩机关闭;例如:【制冷设定温度】为25度,【温差】为2度,则当温控传感器检测温度高于27度时启动压缩机,温度
低于25度时关闭压缩机,将温度控制在25~27度之间;◇压缩机强制启动:1.在压缩机关闭情况下,按住〖RST〗键5秒不放,可以强制启动压缩机。在压缩机强制启动状态下,按住〖RST〗键5秒不放,可以取消强制启动压缩机,压缩机恢复正常运行。2.压缩机在强制启动状态下持续运行30min后,压缩机恢复正常运行。压缩机延时保护◇运行过程中压缩机停机,必须经过【压缩机开机延时时间】才能再次启动;◇运行过程中压缩机开启,必须经过【压缩机最短持续运行时间】才能以实际情况停机;风机控制:控制器在运行过程中,风机按照如下规则运行:如果风机设定为常开,则送风机始终开启;如果风机设定为温控则风机根据温控传感器温度进行控制。控制条件如下:◇当测量温度≥【蒸发风机设定温度】+【蒸发风机温差】,且风机已经停机时间大于1分钟,风机开启;◇当测量温度≤【蒸发风机设定温度】,且风机开机时间大于1分钟,风机关闭;例如:【蒸发风机设定温度】为23度,【蒸发风机温差】为2度,则当温控传感器检测温度高于25度时启动风机,温度低于23度时关闭风机,将温度控制在23~25度之间蜂鸣器功能每按键一次蜂鸣器鸣叫一声,在参数设置确认时长鸣一次,在进行无效操作时蜂鸣器鸣叫三声;当系统出现故障或有外部报警输入时,如果参数F13=0,关闭蜂鸣器报警功能,蜂鸣器不鸣叫报警;如果参数F13=1,则蜂鸣器连续鸣叫报警;系统恢复正常后,自动消除蜂鸣器报警状态.高温、低温超温告警1.当测量温度≥【高温报警温度】,将产生高温报警,当测量温度≤【高温报警温度】,控制器取消高温告警;2.当测量温度≤【低温报警温度】,将产生低温报警,当测量温度≥【低温报警温度】+2度,控制器取消低温告警;外部输入告警(系统高压告警)外部数字量有以下几种输入方式:;常开:表示在正常情况下外部告警输入信号为开路状态,闭合则产生告警。常闭:表示在正常情况下外部告警输入信号为闭合状态,开路则产生告警。系统高压告警:如果1小时内连续出现3次压力告警,将一直关闭压缩机。手动重新上电可以解除告警。温度值校正功能当测量温度值与传感器安装位置实际温度有误差,可通过【温度修正参数】进行校正,校正范围±9.9℃;按一次〖▲〗或〖▼〗键调整温度校正值增或减0.1℃,按住不放则快速调整;系统缺氟(漏氟)保护:当压缩机启动5分钟后,检测温控传感器、蒸发器传感器温度,,如果温控传感器温度高于蒸发器传感器温度5度以上温差,判定系统正常,否则认定为缺氟保护(漏氟),并显示报警代码“E03”。强制关闭压缩机。如果1小时内连续出现3次缺氟保护,将一直关闭压缩机。手动重新上电可以解除告警。蒸发器冻结保护:当压缩机启动1分钟后,检测蒸发器传感器温度,如果蒸发器传感器温度小于等于1度并保持5
秒,判定蒸发器冻结保护,并显示报警代码“FrE”。控制器强制关闭压缩机并开启送风机。当蒸发器的温度上升8度以上,退出冻结保护,控制器恢复正常工作。告警输出告警列表说明故障检测条件推迟持续时间复位操作动作温控传感器故障随时0s2s自动开压缩机、停电加热,温控模式下开蒸发风机;取消缺氟保护告警蒸发温度传感器故障随时0s2s自动取消缺氟保护告警压力保护随时0s5s手动停压缩机缺氟保护压缩机启动5min5s手动停压缩机高温告警随时0s5s自动只告警低温告警随时0s5s自动只告警蒸发冻结保护压缩机启动1min5s自动停压缩机,开始送风机告警接口说明信号名称说明NO故障输出(故障时断开,正常时闭合)NC故障输出(故障时闭合,正常时断开)C公共端控制器接线示意图安装步骤第1步:将控制器嵌入孔中;第2步:通过在设备的导轨方向滑动支架来固定控制器,直到将控制器压实在面板上;电气连接敬告:◆电气接线操作必须由有资质的技术人员来完成。◆使用规定电源类型以外的电源可能会给系统带来严重损害;◆尽可能将传感器、开关量输入信号线与感性负载线、电源线分开排线,以避免电磁干扰。绝不能将电源线(包括电力线)和485通讯协议本产品支持标准ModbusRTU协议,支持标准RS485接口,可与所有支持标准RS485接口的设备通讯。1.通讯参数:默认9600,N,8,1,波特率可选;
2.支持保持寄存器读写,支持03,06,16功能码;3.建议应答超时时间设置大于1000ms;4.建议轮询时间间隔设置大于100ms;5.R:只读,W:只写,R/W:可读可写。6.下表格是具体寄存器参数及说明:地址功能说明預設範圍单位读写0柜温探头温度(实际温度×10)--400~990℃R1蒸发器探头温度(实际温度×10)--400~990℃R2制冷继电器状态0:断开1:闭合R3风机继电器状态0:断开1:闭合R4报警继电器状态0:断开1:闭合R/W5制冷温度设定值3015~50℃R/W6控制回差设定值51~20℃R/W7高温报警温度501~60℃R/W8低温报警温度51~60℃R/W9蒸发风机温度设定260~40℃R/W10蒸发风机温差21~5℃R/W11蒸发器探头使能设定00:禁用1:启用R/W12压缩机工作模式00:自动1:禁用-R/W13风机工作模式10:受控1:常开-R/W14外部输入告警模式00:常闭1:常开R/W15蜂鸣器报警10:禁用1:启用R/W16压缩机开机延时时间31~5MinR/W17压缩机最短持续运行时间31~5MinR/W18系统上电开关机10:通电关机1:通电开机R/W19RS485波特率设定10:48001:96002:192003:115200R/W20从机地址(注意:更改之后,上位机读取软件要相应的更改从机地址)11~64R/W21远程开关机(注意:远程关机状态下,长按[SET]键开机)10:关机1:开机R/W4.维护与保养请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机器上安装的是尼龙滤网的可直接从侧面拔出4-1定期清洁本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,一般每周需清洗一次;⑵请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发生触电事故;4-2长时间停用时注意⑴请切断电源,以防意外;⑵清理冷凝器、过滤网及内部油污;
⑶请对机器采取防尘措施,延长机器使用寿命。4.故障排除故障状况1电源接通后,室内、室外风机不运转可能原因※保险丝熔断※停电或无电源状况排除※更换保险丝※检查电源状况故障状况2在运行中突然停机,电控箱内温度高于设定点温度两度以上可能原因※环境温度过高,导致压缩机热保护※过滤网堵塞或者冷凝器过脏,导致压缩机热保护状况排除※改善周边环境,使散热畅通※对过滤器及冷凝器进行清洗故障状况3机器正常运转,却不制冷可能原因※压缩机损坏※制冷系统泄露※机组蒸发器大面积结霜状况排除※更换压缩机,重新抽真空充注制冷剂※查出泄露处,并重新抽真空加制冷剂※立即停机,把设定温度调高到35℃,十分钟后重新开机◇若上述措施均不能排除故障,请致电本公司咨询!附录1:产品技术参数型号:BCQ-2600FC-380V工作电源:交流380V±10%频率50Hz±4%运行电流:<6.8A功率:1115W制冷剂:R134a制冷量:2600W防护等级:内循环:IP34外循环:IP33允许机柜内温度设定范围:25--38℃(出厂设定30℃)允许使用环境温度范围:-25--45℃循环风量:内循环:1155m³/h外循环:1255m³/h噪音:65dB附录2:电气原理图
室内风机室外风机压缩机M1M2M3C2C3LNPEt℃温控器BCQ-260主0F回C-路380V电路图温控器
苏州博图制冷设备有限公司地址:苏州市吴江区太湖新城镇黄沙路23号联系电话:0512-631728510512-63172852传真:0512-63102853邮编:215223全国统一服务热线:400-920-7382网址:www.botuzl.comEmail:botu@botuzl.com