目录1.安全注意事项·······················································································12.安装要求·····························································································12-1安装位置·························································································222安装方法·························································································32-3电器配线························································································62-4机器排水·························································································63.启动与运转···························································································63-1运行前后注意事项···········································································632机器操作说明··················································································74.维护与保养·························································································104-1定期清洁·······················································································104-2长时间停用时注意··········································································105.故障排除·····························································································10附录一······································································································11附录二······································································································11
1,安全注意事项⑴当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册中所提到的注意事项,以避免出现意外情况;⑵请勿用湿手操作,以免引起触电;⑶当需要保养或维护时,请先切断所有电源以免引起触电事故;⑷空调器上不易放置任何物品,以免滑落造成人员伤害;⑸当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受伤或机器损坏;⑹本机器外部结构已做防水处理,请按照我公司给出的正确安装方式安装。此空调不适宜于安装在振动较大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;⑺本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;⑻禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发生。1.安装要求本空调器为侧挂式系列,侧挂式(图一),为使机组能在理想的状况下工作,在安装上请注意以下要求:图一侧挂式空调器电控箱回风(热)出风(冷)
2-1安装位置⑴空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装空调器,则一定要每天做好空调器的清洁和保养工作。⑵空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、排风口离墙面的间距应大于500mm;⑶空调器周围请勿放置杂物,以保持空气畅通流通;⑷本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。⑸请安装本空调器于周围温度在45℃以下的范围之内高温系列55℃以下;⑹本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜角不大于5°如图四所示;⑺控制箱内正对出风口的电器元件与出风口的最小距离应大于200mm,因距离太近电器元件表面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。⑻当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿度能控制在较为理想的状态下。图三电控箱冷气机图四
错误正确错误正确2-2安装方法⑴当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;⑵为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;⑶空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备损坏,当安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的重量不会使整个电气柜倾倒;⑷电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;⑸箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;⑹当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而损坏;⑺具体的安装
1,蒸发风机出风挡板安装示意图:(如不安装出风口有凝结水风险)
2-3电器配线:⑴机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若所提供的电压在额定值±10%以内,本机组可正常使用;L,N,PE,为电源输入引线经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意⑵空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;⑶在机组的电器回路上请自行安装断路器或漏电保护装置;⑷请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负载,引发事故。2-4机器排水:(无水型和户外机型无以下排水管项目)本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:⑴请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;⑵根据实际情况排水软管长度适当即可,过长部分请切除;⑶排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水严重时产生外溢,引起空调器或者电气柜故障。启动与运行3-1运行前后注意事项⑴启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开始工作;(户外机型无排水管,直接在底部有漏水孔)⑵当在运转中需重新启动空调器时,请间隔3分钟以上,倘若频繁启动且间隔时间过短会引起机器损伤;⑶当空调器倾斜时请勿开启,避免漏水、触电等情况发生;⑷空调器在出厂时温度点已经设定好为30℃,若需重新设定时请控制在允许范围之内设定,以免引起机器运行不正常;如果空调器有加热功能,出厂时设置为5℃⑸当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进行检查维修。
操作使用说明书控制箱温度湿度调节机系列使用前请详阅非常感谢您购买本公司控制箱温度湿度调节机系列产品,使用前请仔细阅读本说明书,以便您能正确使用控制箱温度调节机。本说明书内页附有装箱清单及合格证!非常感谢您购买本公司控制箱温度湿度调节机系列产品使用前请仔细阅读本说明书以便您能正确使用控制箱温度湿度调节机装箱单序号123名称单位数量备注控制箱温度调节机台壹使用说明书合格证明书本壹份壹产品合格证明书产品名称:控制箱温度调节机产品型号:出厂编号:本产品按照有关技术标准设计、制造。
电气部分符合GB4701.1等相关标准的要求。压力容器符合有关使用场合的要求。本产品经过试运行和出厂检查,各项性能参数均符合有关技术要求及规定。经过公司质保部认可,该产品属合格产品,可以交付用户使用。一、适用范围本机组主要用于对各种电气柜内的空气进行冷却、除湿和净化处理,以保证电气元件在安全温度和湿度条件下可靠工作,延长其使用寿命。适用于机械、电力、轻工、仪器仪表、纺织等行业对温湿度有较高要求的各类控制箱、配电柜及其它电气装置,也可用于小空间的温度、湿度调节。二、安装(一)安装要求1、机组应垂直安装在通风良好且远离灰尘处,另外应保证其外侧进出风口与墙壁或其它物体间距离在1m以上。2、机组周围不应存在腐蚀性气体和易燃易爆等危险气体,安装位置附近也不应有高温热源和其它发热物体,并避免阳光直接照射到机组上。3、机组可安装在控制箱正面、侧面(LA-□□B/Q型)或顶部(LA-□□C型),具体位置由用户自行确定。安装部位结构件应能充分承受机组重量。4、用户应按照产品样本规定,预先在控制箱上加工好机组的送回风口和安装孔。送回风口的位置应确保箱内空气流向合理,循环畅通,温度均匀性好。5、机组应使用专用电路供电,电源线截面积应符合相关规定,并在电路上安装规定容量的空气开关或保险装置。6、机组和控制箱应符合有关电气安全标准要求,并可靠接地。7、机组在存贮搬运或安装中,应避免受到撞击而损坏,同时不允许机组倒置或倾一、适用范围四、试运转七、保修条例二、安装五、维护保养八、型号说明三、面板操作六、故障排除九、附录控制箱温度调节机控制面板接水盒
M8×16螺栓弹平垫过滤网外循环控制箱温度调节机控制面板接水盒M8×16螺栓弹平垫过滤网外循环塑料保温层不干胶泡沫塑料保温层不干胶泡沫控制箱控制箱控制箱温湿度调节机M8×16螺栓弹平垫控制箱斜角度大于40°。为此在运输和安装前,应尽量保持原包装,吊装时掌握好重心。8、吊装螺栓长度≤12mm为宜。(二)安装方法机组的安装参见图1、图2、图3所示,具体步骤如下:1、用M8×16螺栓+弹垫/平垫将机组固图1顶装式安装定在控制箱箱体上,注意安装方向要正确;2、按电路图规定在XT1、XT2端子上接线;
3、将排水软管固定在排水管口处(仅限于不带接水盒的机型)并避免其弯曲、上翘。4、带接水盒机型安装时,先将水位开关固定在接水盒上,再将接水盒安装于机组下部,方可开机(见右图水位开关安装示意)。水位开关安装示意图2外挂式安装图3嵌入式安装附录C:外形结构图附录D:制冷系统原理图内部循环空气外部循环空气进风压缩机毛细管过滤器蒸发器风机进风冷凝器出风出风电容器C1M1内循环风机1M2外循环风机压缩机M3(无源触点)1C11C2LN
告警输出XT1FR3过载保护器KL-2K控制板2J13-LJ12-NJ14-COOLAC220V有源开关量输入J16ALR显示板P2(20P)86E1GND7E2温度J5零度J6J4J20-INJ21E1J17-ALRJ3J2J97E3J99绿蓝
黄红注:1、LA-25~32机型有风机2M1及电容2C1,其他机型无此配件;2、LA-32~50机型有继电器KA1,其他机型无继电器KA1,2号点线路直接温控板OUT1,取消9号点。3、无除湿功能机型不带湿度传感器。4、LA-W-B/Q-Y机型无水位开关2M12C1水位开关SL湿度传感器RH4(三)XT1、XT2接线端子接线方法(如图4所示):1、使用刃口宽度为2.5~3.5mm的一字螺丝刀,将端子台内的弹簧线夹用力压下;2、将安装导线去皮5~7mm,捻紧,由侧面插入端子台,注意不要将导线皮插入弹簧夹内;3、抽回一字螺丝刀弹簧线夹复位,自动夹住导线。三、控制面板操作图4接线三步骤(一)控制面板功能说明(面板如图5所示)
1、温度显示:显示箱内温度及报警代码。2、报警指示:出现故障时,该指示灯亮。3、制冷指示:当压缩机制冷运行时,该指示灯亮。延时启动过程,该指示灯闪烁。4、设置键(Set):在正常运行状态下,按下“Set”,进入设置“设定温度”界面,可以通图5控制面板过按增量键(△)或减量键(▽)进行参数调整,按住增量键(△)或减量键(▽)不放,可以进行参数快速调整。在温度设置状态下,再次按下按下“SET”键可进入回差设定,调整参数方式与温度设定一样。5、增量键(△):在设定状态下,向上调节设定温度,按一下增加1℃。在正常运行状态下按一下△键,显示设定温度值。6、减量键(▽):在设定状态下,向下调节设定温度,按一下减少1℃。在正常运行状态下按一下▽键,显示温控回差,再次按下▽键,显示当前压缩机工作电流。7、退出键(Rst):按下并松开“Rst”或15秒内无按键动作则退出设置状态,并保存参数。端子台导线(二)温控条件(三)独立除湿条件(带独立除湿功能机型)在高湿度条件下,当机组湿度传感器检测到的箱内空气相对湿度RH≥75%,且RT1≥20℃时,压缩机和风机周期性运转,对箱内空气进行除湿。当湿度RH<75%或RT1<20℃时,停止除湿。(四)无源触点使用方法机组的电气控制系统具有一组无源触点输出功能,它由继电器的动合触点组成。当机组正常工作时,输出触点为闭合状态;当机组出现故障或机组未上电时,输出触点为断开状态。不论触点是闭合状态还是断开状态,触点输出均不带电。需要使用无源触点时,由用户自行提供电源或电气控制信号。无源触点的负荷能力为DC24V/1A
或AC220V/1A。为了提高抗干扰能力,在使用无源触点时,应在无源触点与I/O口之间插入RC滤波器。参考电路图6所示。九、附录附录A:主要技术参数30050080012001500200025003200400050001.31.52.93.33.54.65.56.68.99.729033262569077010101190142019452085225225290410520800810110013001500种类充注量140g±5g210g±5g190g±5g300g±5g380g±5g460g±5g850g±5g600g±5g1200g±5g1400g±5g290×550×200290×570×210290×600×260400×970×230400×970×230400×1300×260400×1350×270450×1420×280485×1580×
290485×1580×310安装形式制冷量(W)电源额定电流内(A)额定功率(W)内部空气循环量(m3/h)无源触点形式温度调节范围(℃)制冷剂噪音dB(A)外形尺寸(宽×高×深)62R134a外挂/嵌入式1P~220V50Hz告警时,继电器常闭触点断开,触点负载能力:AC220V电流1A/DC24V电流1A28~35
注:1、制冷量测试条件(根据DIN3168):箱内回风温度35℃,环境温度35℃。2、本表参数随技术改进而有变更时,恕不另行通知,以产品铭牌为准。制冷控制条件制热控制条件(冷热双制机型)开始制冷停止制冷开始电加热停止电加热RT1传感器工作正常并且RT1≥(TS+2)℃并且延时时间≥3min并且无报警信号在同时满足上述4个条件下,开始制冷。RT1≤(TS-2)℃或RT1传感器工作不正常或有报警信号出现上述任一条件时,停止制冷。RT1传感器工作正常并且RT1≤10℃并且无报警信号在同时满足上述3个条件下,开始制热。RT1传感器工作不正常或RT1≥15℃
或有故障信号出现上述任一条件时,停止电加热。备注RT1—箱内温度TS—温度设定值控制箱温度湿度调节机代号R:冷热型;单制冷型不标注;G:高温制冷型冷却能力(×100W)设计代号--ALH:带冷凝水接水盒;Z:带冷凝水自蒸发器;Y:带排水接头,无接水盒C:带除湿功能;J:环保冷媒S:特殊电源体制;不标注:电源为1P~220V50Hz安装形式-B:外挂式;Q:半嵌入式;CA:顶装式(2)压缩机频繁起动、停止;(3)压缩机工作正常,但箱内、外侧风机有一个或两个同时不工作;(4)箱外侧风机运转正常而压缩机较长时间不启动;(5)机组运行中出现异常响声。七、保修条例1.凡用户在遵守本使用说明书所述各项规定条件下,整机在一年内(以发票开出日期为准)因制造质量而发生故障或损坏时,凭发票由本公司进行免费维修或更换配件。2.凡违反使用说明书有关规定或因外界条件不符合要求(如电源电压波动超出允许范围、环境温度过高、不按规定维护保养等)而造成的机组损坏,均不属保修(换)范围。3.用户自行对产品进行拆解、改装或产品发生故障后未通知本公司而自行拆修者,本公司不负责保修。4.在搬运、安装和使用过程中,由于碰撞、倒置等人为原因造成机组损坏,不属免费修、换范围。5.保修期外或不属保修范围的维修服务,其相关费用包括往返费用等均由用户负责。八、型号说明
冷却机组报警输出无源触点820Ω/2WRC滤波器1μF/250VACC1外接电源DC-24VE100Ω/2WR1R2I/O输入口用户机组图6无源触点接口电路为了提高无源触点的抗干扰能力,用户使用无源触点时,应采用延时判定,采集间隔时间1~3S,排除干扰信号,确认无源触点输出为低电平,则判断报警信号有效。四、试运转(一)运转前检查确认机组固定牢靠,全部安装工作正确无误,供电电源符合要求,控制箱密封情况良好。(二)通电运转1、向机组供电,机组控制面板显示正常,箱内侧风机工作,箱内空气开始循环。2、调整箱内设定温度:(1)按下SET按键,数码管闪烁,显示设定温度;(2)若设定温度需要修改时,按增量按键(△)或减量按键(▽),使设定值改变为所需要的值;(3)再按一下SET或PRG(MC-80)按键,显示箱内实际温度,同时保存设定值。3、按操作说明要求,确认机组运行正常,电器部件工作可靠,无其它异常声音和现象。在机组正常制冷运行20min后,控制箱内侧送回风口温差应大于5~8℃。
(三)带自蒸发器机型说明本空调机组将冷凝水集中收集于机组底部的自蒸发器内,当冷凝水液面达到一定高度(高于蒸发启动开关)时,蒸发电路开始工作,将冷凝水蒸发为气体后排出机外。五、注意事项及维护保养1、供电电源和断路器规格必须符合说明书和产品铭牌规定,工作电压允许变化范围为额定电压的±10%。2、机组工作时内、外侧送回风口附近不应有任何障碍物。3、箱内温度设定值要合适,通常情况下建议设定值保持在30℃~35℃左右。4、定期清理外部空气过滤网(每两周一次),清理时将过滤网抽(取)出,用吸尘器清理或用温度不超过40℃的温水和中性洗涤剂清洗。清洗后应擦干水分或在阴凉处晾干,再装回原处。拆卸空气过滤网应在停机状态下进行。5、机组表面脏污时,应采用中性洗涤剂或高品质肥皂水用软布擦洗。注意不得使用石油类、酸类熔剂、磨粉、钢刷等,以防喷塑面破坏。6、长期放置重新使用前或使用较长一段时间(6个月)后,应检查换热翅片、内外侧风扇叶片,并对换热翅片表面和风扇叶片表面污垢予以清理。7、带接水盒机组根据蜂鸣器提示倒水时,应拿掉水盒上的水位检测装置。重装水盒时再按原位置正确安装检测装置,注意防止其损坏。注意!进行上述检查或保养时务必切断电源。六、故障排除1、机组供电后,箱内侧风机不工作。请检查:(1)电源连接是否可靠;(2)电路空气开关或断路器是否良好;(3)电源线是否断路;(4)供电电压是否正常。2、箱内侧风机工作,但压缩机和箱外侧风机不工作。请检查:(1)温度设定是否合适;(2)机组是否处于延时或报警状态;(3)电源电压是否符合要求;(4)冷热双制机组是否处于制热状态;(5)如果温度无显示,请拆下机组盖板,打开电器盒检查保险丝(FU=2A)及变压器是否良好。
(6)接地是否良好。3、机组工作正常,但降温效果不佳。请检查:(1)空气过滤网(内外)是否太脏;内外风机运转是否正常;(2)温度设定是否合适;(3)控制箱是否密封;(4)机组型号选择是否恰当;(5)送回风风道是否有障碍或者箱内侧有无冷气短路现象发生;(6)温度传感器安装位置是否合适;(7)环境温度过高或者周围环境是否有意料之外的热源。4、显示E1故障代码;表示压缩机电流过载,原因及排除方法为:(1)检查空气过滤网,必要时予以清理;(2)内外风机运转是否正常;(3)检查电源电压是否过低,应提供符合规定的电压;(4)环境温度是否过高,热负荷是否过大;(5)压缩机启动电容或启动装置是否损坏,必要时予以更换;(6)压缩机内部故障(如短路,卡死等),必要时予以更换;5、显示E2故障代码:表示机组相序错误(仅限于三相电源供电机组)(1)检查三相电源相序;(2)检查三相电源电压是否缺相;(3)检查三相电源电压是否为额定值。6、显示F1或F2故障代码:表示温度传感器开路或短路,原因及排除方法:请检查温度传感器及接插件连接是否正常。7、显示F3故障代码:表示蒸发器温度过低,零度保护。请检查内循环风机是否正常,内循环过滤网是否堵塞。8、冷凝水自蒸发器底部溢流口有冷凝水流出。请检查冷凝水自蒸发器供电电源是否正常,内部供电保险丝是否断路。注:经上述检查、处理后,机组仍不能正常工作时,请与厂家联系。若出现下列情形时,应立即停止机组工作:1、保险丝或断路器经常断开或报警指示灯频繁报警;4.维护与保养
请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机器上安装的是尼龙滤网的可直接从侧面拔出(户外机型底部有漏水孔)4-1定期清洁本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,一般每周需清洗一次;有的机型为钣金的网孔,直接用气枪清洗即可。⑵请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发生触电事故;4-2长时间停用时注意⑴请切断电源,以防意外;⑵清理冷凝器、过滤网及内部油污;⑶请对机器采取防尘措施,延长机器使用寿命。2.故障排除故障状况1电源接通后,室内、室外风机不运转可能原因※保险丝熔断※停电或无电源状况排除※更换保险丝※检查电源状况故障状况2在运行中突然停机,电控箱内温度高于设定点温度两度以上可能原因※环境温度过高,导致压缩机热保护※过滤网堵塞或者冷凝器过脏,导致压缩机热保护状况排除※改善周边环境,使散热畅通※对过滤器及冷凝器进行清洗故障状况3机器正常运转,却不制冷可能原因※压缩机损坏※制冷系统泄露※机组蒸发器大面积结霜状况排除※更换压缩机,重新抽真空充注制冷剂※查出泄露处,并重新抽真空加制冷剂※立即停机,把设定温度调高到35℃,十分钟后重新开机◇若上述措施均不能排除故障,请致电本公司咨询!附录1:产品技术参数型号:ZHBCQ-3500ZHT-380V
工作电源:交流380V±10%频率50Hz±4%运行电流:<4.8A功率:1950W制冷剂:R134a制冷量:3500W防护等级:IP45允许机柜内温度设定范围:2538℃(出厂设定30℃)允许使用环境温度范围:-25--45℃噪音:65dB附录2:电气原理图室内风机室外风机压缩机M1M2M3C2C3LNPEt℃温控器ZHBCQ主-3回500路ZHT-380V电路图温控器