95
QC-S5G Series of Products User Manual V1.0
1001
Mold opened
signal is off
while arm
descending
1.When Y1 falls, mold opened signal
outside Y1 safety zone or in other
places except rising limit is
off(except finding origin)
1.Check the mold openedsignal
2.Check the steps ofprogram
1002
Safety door is
opened when arm
descends.
1. When Y1 falls, safety door opens
in automatic state outside Y1
safety zone or in other places
except rising limit.
2. When pneumatic sub arm
falls,safety door signal is not
detected in internal sub arm rising
limit.(except automatic step)
1.Check the safety doorsignal
2.Check the steps ofprogram
1003
Vertical and
horizontal
signals are
both on
Vertical and horizontal spacing
limit have signals at the same time
Check the horizontallimit switch and
vertical limit switch1004
Z axis origin
signal and
external safety
zone signal are
both on
Z origin switch and external safety
zone switch are on at the same time
Check Z origin switchandexternal safety zoneswitch
1005
Mold opened
signal is off
when Arm descends
in the type
1.In internal area or other places
except external area, main rising
limit is off or sub rising limit is
off, or Y1 is not in safety zone
2.Mold opened signal is off in auto
state
3.When mold locked is allowed in
other states, mold opened signal is
off
1.Check the mold openedsignal
2.Check the steps ofprogram
1006
Posture 1 is
wrong while
descending
internal
1.Press main arm descending button
in manual state. Posture 1 vertical
signal is not detected in internal
safety area or other places except
external safety area
2. In auto state, posture 1 vertical
signal is not detected in internal
safety area, other places except
external safety area or other
places except rising limit
3.Posture 1 vertical signal is not
detected in internal safety area
when pneumatic main arm descends
1.Check whether posture1isvertical
2.Check vertical
limit switch
1007
Arm descends
internal but not
in Z axis
internal safety
zone
When Y1 falls, out of the Y1
internal safety area or in other
places except rising limit,
internal safety zone signal is
detected but the position is not in
the zone
1.Check whether the Z axisinternal safety zone is setcorrect in Function-Mechanicalparam
96
QC-S5G Series of Products User Manual V1.0
1008
Arm descends
external but not
in Z axis
external safety
zone
When Y1 falls, out of the Y1
internal safety area or in other
places except rising limit,
external safety zone signal is
detected but the position is not
in the zone
1.Check whether the Z axisinternal safety zone issetcorrect in
Function-Mechanical param1009
Do not detect
safety zone
signal when
descending
When Y1 falls, out of the Y1
internal safety area or in other
places except rising limit,
internal/external safety zone
signal is not detected
1.Check whether the
descending position isinsafety zone
2.Check Z origin switchandexternal safety zone switch1010
Y1 is not in Z axis
safety zone when
descending
When Y1 falls, in other places
except rising limit,
internal/external safety zone
signal is not detected
1.Check whether the
descending position isinsafety zone
2.Check Z origin switchandexternal safety zone switch1011
Y1 is not in X
axis safety
zone when
descending
When Y1 falls, in other places
except rising limit, X axis
safety zone signal is not
detected
Check whether X axis isset correct in
Function-Mechanical
param
1012
Tow groups of
profile posture
are horizontal at
the same time
Posture 1 and posture 2 are
horizontal at the same time
1.Check whether posture1and posture 2 have
horizontal action at thesame time
2.Check switches of levellimit 1 and level limit21013
Sub forward/
backward limit
is both on
Sub forward/backward limit signal
lamps are on at the same time
Check the sub
forward/backward limitswitch
1014
Sub up/down limit
is both on
Sub up/down limit signal lamps are
on at the same time
Check the sub up/downlimit switch
1015
Main forward/
backward limit
is both on
Main forward/backward limit
signal lamps are on at the same
time
Check the main
forward/backward limitswitch
1016
Main up/down
limit is both on
Main up/down limit signal lamps are
on at the same time
Check the main up/downlimit switch
1017
Safety door opens
when running
Safety door opens when running
automatically
1.Check whether the
safety door is opened2.Check the safety doorsignal
1018
Y2 is not in X2 axis
safety zone when
descending
When Y2 falls, in other places
except rising limit, X2 axis safety
zone signal is not detected
Check whether X2 axisisset correct in
Function-Mechanical param
97
QC-S5G Series of Products User Manual V1.0
1019
The mold
opened signal
is off when
origin is
reset
Mold opened signal is off when
the origin is reset
1.Check signal setting inFunction
2.If checking mold openedasno use in finding origin,thesystem will alarm once whenmold opened signal is off,andit can continue finding originafter removing the alarm1020
The mid-mold
signal is off
when origin is
reset
Mid-mold signal is off when the
origin is reset
1.Check mid-mold signal
2.Check No use of mid-moldinFunction-Signal setting ifnoneed of this function
1021
The posture is
not vertical
when origin is
reset
The vertical limit has no signal
when the origin is reset
1.Check relative limit
switches
2.Check No limit of resetposture in Function-Signalsetting if no need of thisfunction
1022
The posture is
not horizontal
when origin is
reset
The horizontal limit has no signal
when the origin is reset
1023
The posture is
not vertical in
transverse
movement
The vertical limit has no signal
in transverse movement
1.Check relative limit
switches
2.Check No limit of transverseposture in Function-Signalsetting if no need of thisfunction
1024
The posture is
not
horizontal in
transverse
movement
The horizontal limit has no signal
in transverse movement
1025
Posture 2 is
wrong while
descending
internal
1.Press main arm descending
button in manual state. Posture
2 vertical signal is not detected
in internal safety area or other
places except external safety
area
2. In auto state, posture 2 vertical
signal is not detected in
internal safety area, other
places except external safety
area or other places except
rising limit
3.Posture 2 vertical signal is
not detected in internal safety
area when pneumatic main arm
descends
1.Check whether posture 2 is
vertical
2.Check vertical limitswitch
98
QC-S5G Series of Products User Manual V1.0
1026
Horizontal 2 limit
and vertical 2
limit ar e bo t h
o n
Horizontal 2 limit and
vertical 2 limit have signal at
the same time
Check vertical limitswitch and horizontallimit switch
1027 Mold locked is not
finished
Mold closed signal is not
detected
1. Check mold closed signal2. Check No use of moldlocked in Function-Signalsetting if no need of thisfunction
1028 Trouble shooting None None
1029
No fully automatic
signal
Automatic signal is off Send the automatic signal1030
Posture 2 is not
vertical in transverse
movement
Vertical 2 signal is off
when the Z axis is moving
transversely
Send a vertical 2 signal1031
Posture 2 is not
horizontal in
transverse movement
Horizontal 2 signal is off
when the Z axis is moving
transversely
Send a horizontal 2 signal1038
Z axis is not in
external area in
Reject
Z axis is not in external area
in Reject period
Check whether the Z axisis set correct
1039
Z axis is not in
external area in
Reject
Z axis is not in external area
in Reject period
Check whether the Z axisisset correct
1040
Previous action is
not Z axis
Reject enable is checked
Remove the check or teachanZ axis before
1052
Spinning in, spinning
out and main rising
limit signals are off
x24,x25,x35,x32 signals are
off
Check main/sub rising limit1054
No X axis but has
X action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1055
No Y axis but has Y
action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1056
No Z axis but has Z
action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1057
No X2 axis but has X2
action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1058
No Y2 axis but has Y2
action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
99
QC-S5G Series of Products User Manual V1.0
1059
No A axis but
has A action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1060
No B axis but
has B action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1061
No C axis but
has C action
Axis is not in Function -
Mechanical parameters - Axis
definition , but there is an
action in mold number program
Delete axis action thatisnot defined
1062
Sequence of X1
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple X1 axes for
sequence of X1 axis back to origin
Delete redundant X1 axesinsequence of returning
1063
Sequence of Y1
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple Y1 axes for
sequence of axis back to origin
Delete redundant Y1 axesinsequence of returning
1064
Sequence of Z
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple Z axes for
sequence of axis back to origin
Delete redundant Z axesinsequence of returning
1065
Sequence of X2
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple X2 axes for
sequence of axis back to origin
Delete redundant X2 axesinsequence of returning
1066
Sequence of Y2
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple Y2 axes for
sequence of axis back to origin
Delete redundant Y2 axesinsequence of returning
1067
Sequence of A
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple A axes for
sequence of axis back to origin
Delete redundant A axesinsequence of returning
1068
Sequence of B
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple B axes for
sequence of axis back to origin
Delete redundant B axesinsequence of returning
1069
Sequence of C
axis back to
origin is set
repeatedly
Function - Mechanical parameters
- Structure - Other definitions,
choose multiple C axes for
sequence of axis back to origin
Delete redundant C axesinsequence of returning
1070
Use returning in
order but order of
X1 axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose X1 axis
Choose X1 axis in sequenceofreturning
100
QC-S5G Series of Products User Manual V1.0
1071
Use returning in
order but order of Y1
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose Y1 axis
Choose X2 axis in sequenceof returning
1072
Use returning in
order but order of Z
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose Z axis
Choose Y1 axis in sequenceof returning
1073
Use returning in
order but order of X2
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose X2 axis
Choose Y2 axis in sequenceof returning
1074
Use returning in
order but order of Y2
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose Y2 axis
Choose X1 axis in sequenceof returning
1075
Use returning in
order but order of A
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose A axis
Choose A axis in sequenceofreturning
1076
Use returning in
order but order of B
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose B axis
Choose B axis in sequenceofreturning
1077
Use returning in
order but order of C
axis is not set
Function - Mechanical parameters
- Structure - Other definitions,
not choose C axis
Choose C axis in sequenceofreturning
1078
No main up limit
signal when X2 axis
returns to origin
point
No X35 signal when back to the
origin
Check whether main/subuplimit is normal1079
No sub up limit
signal when X2 axis
returns to origin
point
No X32 signal when back to the
origin
Check whether main/subuplimit is normal1080
No main up limit
signal when Z axis
returns to origin
point
No X35 signal when back to the
origin
Check whether main/subuplimit is normal1081
No sub up limit signal
when Z axis returns to
origin point
No X32 signal when back to the
origin
Check whether main/subuplimit is normal1100
Safety zone is not
detected when the
main arm descends
When pneumatic main arm
descends, internal/external
safety zone signal is not
detected
1.Check Z origin switchand external safety zoneswitch
2.Check whether the stepsof program are correct1101
Safety zone is not
detected when the
sub arm descends
When pneumatic sub arm descends,
internal/external safety zone
signal is not detected
1.Check Z origin switchand external safety zoneswitch
2.Check whether the stepsof program are correct1102
Mold-opened signal
is off when main arm
descends
When pneumatic main arm
descends, mold opened signal is
not detected in internal safety
zone
Check mold opened signal
101
QC-S5G Series of Products User Manual V1.0
1103
Mold-opened signal
is off when sub arm
descends
When pneumatic sub arm
descends, mold opened
signal is not detected in
internal safety zone
Check mold opened signal1104
Main up limit is on
after main arm
descended
After pneumatic main arm
descends, main up limit
switch has signal
1.Check whether the mainarmdescends
2.Check main up limit switch1105
Sub up limit is on
after sub arm
descended
After pneumatic sub arm
descends, sub up limit
switch has signal
1.Check whether the sub armdescends
2.Check sub up limit switch1106
Descending limit is
off after main arm
descends
After pneumatic main arm
descends, main down
limit has no signal
1.Check whether the mainarmdescends
2.Check main down limit
switch
3.Choose No use of Main downlimit in Function-Mechanicalparam-Structure if there isnodescending limit
1107
Descending limit is
off after sub arm
descends
After pneumatic sub arm
descends, sub down limit
has no signal
1.Check whether the sub armdescends
2.Check sub down limit switch3.Choose No use of Main downlimit in
Function-Mechanical
param-Structure if there isno descending limit
1108 Mid-mold signal is off
when main arm descends
Mid-mold signal is off
when pneumatic main arm
is descending
1.Check mid-mold signal
2.Check No use of mid-moldinFunction-Signal setting ifnoneed of this function
1109 Mid-mold signal is off
when sub arm descends
Mid-mold signal is off
when pneumatic sub arm is
descending
1.Check mid-mold signal
2.Check No use of mid-moldinFunction-Signal setting ifnoneed of this function
1120
When main arm is
rising,
internal/external
safety zone signal
is not detected
When pneumatic main arm is
rising, Z origin and
external safety zone have
no signal
Check Z origin switch andexternal safety zone switch1121
When sub arm is
rising,
internal/external
safety zone signal
is not detected
When pneumatic main arm is
rising, Z origin and
external safety zone have
no signal
1122
Main arm rises too
fast
When pneumatic main arm is
rising, main up limit
signal can be detected for
a while after the main down
valve is closed
Check whether the main uplimit is normally on
102
QC-S5G Series of Products User Manual V1.0
1123
Sub arm rises
too fast
When pneumatic sub arm is
rising, sub up limit signal
can be detected for a while
after the main down valve is
closed
Check whether the sub up limitisnormally on
1124
Mold-opened
signal is off
when Main Arm
rises
Mold opened signal is off
when pneumatic main arm is
rising
Check the mold opened signal1125
Mold-opened
signal is off
when sub arm
rises
Mold opened signal is off
when pneumatic sub arm is
rising
1126
Main up limit
is off after
main arm rises
After pneumatic main arm
rises, main up limit has no
signal
1.Check whether the main arm rises2.Check main up limit switch
1127
Sub up limit is
off after sub
arm rises
After pneumatic sub arm
rises, sub up limit has no
signal
1.Check whether the sub arm rises2.Check sub up limit switch
1140
Main backward
limit is on
after main
arm moves
forward
Main backward limit has
signal after pneumatic
main arm moves forward
1.Check whether the main arm movesforward
2.Check main backward limit switch3.Choose No use of Main backwardlimit in Function-Mechanical
param-Structure if there is no mainbackward limit
1141
Sub backward
limit is on
after sub
arm moves
forward
Sub backward limit has
signal after pneumatic sub
arm moves forward
1.Check whether the sub arm movesforward
2.Check sub backward limit switch3.Choose No use of Sub backwardlimit in Function-Mechanical
param-Structure if there is nosub backward limit
1142
Main backward
limit is off
after main
arm moves
backward
Main backward limit has no
signal after pneumatic
main arm moves backward
1.Check whether the main arm movesbackward
2.Check main backward limit switch3.Choose No use of Main backwardlimit in Function-Mechanical
param-Structure if there is no mainbackward limit
1143
Sub backward
limit is off
after sub arm
moves backward
Sub backward limit has no
signal after pneumatic
sub arm moves backward
1.Check whether the sub arm movesbackward
2.Check sub backward limit switch3.Choose No use of Sub backwardlimit in Function-Mechanical
param-Structure if there is nosubbackward limit
103
QC-S5G Series of Products User Manual V1.0
1144
Main forward
limit is off
after main
arm moves
forward
Main forward limit has no
signal after pneumatic
main arm moves forward
1.Check whether the main arm movesforward
2.Check main forward limit switch3.Choose No use of Main forwardlimit in Function-Mechanical
param-Structure if there is no mainfroward limit
1145
Sub forward
limit is off
after sub arm
moves forward
Sub forward limit has no
signal after pneumatic sub
arm moves forward
1.Check whether the sub arm movesforward
2.Check sub forward limit switch3.Choose No use of sub forward limitin Function-Mechanical
param-Structure if there is nosubfroward limit
1146
Main forward
limit is on
after main
arm moves
backward
Main forward limit has
signal after pneumatic
main arm moves backward
1.Check whether the main arm movesbackward
2.Check main forward limit switch3.Choose No use of main forwardlimit in Function-Mechanical
param-Structure if there is no mainfroward limit
1147
Sub forward
limit is on
after sub arm
moves
backward
Sub forward limit has
signal after pneumatic
sub arm moves backward
1.Check whether the sub arm movesbackward
2.Check sub forward limit switch3.Choose No use of sub forward limitin Function-Mechanical
param-Structure if there is nosubfroward limit
1160
Main up limit
signal is not
detected when
Posture 1
changes
1.In internal safety zone,
Posture 1 is vertical when
main up limit signal is off
2.Not in external safety
zone, Posture 1 is
vertical/horizontal when
main up limit signal is off
3.Z position is less than
value set of Z internal
safety zone. Posture 1 is
vertical/horizontal when
main up limit signal is off
Check main up limit switch
104
QC-S5G Series of Products User Manual V1.0
1161
Sub up limit
signal is
not detected
when Posture
1 changes
1.In internal safety zone, Posture 1 is
vertical when sub up limit signal is off
2.Not in external safety zone, Posture 1 is
vertical/horizontal when sub up limit
signal is off
3.Z position is less than value set of Z
internal safety zone. Posture 1 is
vertical/horizontal when sub up limit
signal is off
Check sub up limitswitch
1162
Mold-opened
signal is off
when Posture 1
changes
Posture 1 is vertical in internal safety
zone. Mold opened signal is off when
selecting external standby or horizontal
standby
Check mold openedsignal
1163
Horizontal 1
limit is off
after
Posture 1 is
horizontal
Horizontal 1 limit switch has no signal
after Posture 1 is horizontal
1. Check whether
Posture 1 is
horizontal
2. Check horizontal1limit switch
1164
Vertical 1
limit is off
after
Posture 1 is
vertical
Vertical 1 limit switch has no signal
after Posture 1 is vertical
1. Check whether
Posture 1 is vertical2. Check vertical1limit switch
1165
Not in safety
zone when
posture is
horizontal
Not in Z origin or external safety zone when
posture is horizontal
1. Check Z originswitch and externalsafety zone switch2. Check whethersteps of programarecorrect
1170
Main up
limit signal
is not
detected
when Posture
2 changes
1.In internal safety zone, Posture 2 is
vertical when main up limit signal is off
2.Not in external safety zone, Posture 2
is vertical/horizontal when main up limit
signal is off
3.Z position is less than value set of Z
internal safety zone. Posture 2 is
vertical/horizontal when main up limit
signal is off
Check main up limitswitch
1171
Sub up limit
signal is
not detected
when Posture
2 changes
1.In internal safety zone, Posture 2 is
vertical when sub up limit signal is off
2.Not in external safety zone, Posture 2
is vertical/horizontal when sub up limit
signal is off
3.Z position is less than value set of Z
internal safety zone. Posture 2 is
vertical/horizontal when sub up limit
signal is off
Check sub up limitswitch
105
QC-S5G Series of Products User Manual V1.0
1172
Mold-opened
signal is off when
Posture 2 changes
Posture 2 is vertical in
internal safety zone. Mold
opened signal is off when
selecting external standby or
horizontal standby
Check mold opened signal1173
Horizontal 2
limit is off after
Posture 2 is
horizontal
Horizontal 2 limit switch has no
signal after Posture 2 is
horizontal
1. Check whether Posture2ishorizontal
2. Check horizontal 2 limitswitch
1174
Vertical 2 limit
is off after
Posture 2 is
vertical
Vertical 2 limit switch has no
signal after Posture 2 is
vertical
1. Check whether Posture2isvertical
2. Check vertical 2 limitswitch
1180
Main up limit is off
during pneumatic
transverse in/out
Main up limit point has no
signal during pneumatic
transverse in/out
Check main up limit1181
Sub up limit is off
during pneumatic
transverse in/out
Sub up limit point has no signal
during pneumatic transverse
in/out
Check sub up limit1182
Spin in limit is off
after spin in
Spin in limit has no signal
after pneumatic transverse
entry
1.Check whether transverseentry is carried out
2.Check spin in limit switch1183
Spin out limit is
off after spinning
out
Spin out limit has no signal
after pneumatic transverse exit
1.Check whether transverseexit is carried out
2.Check spin out limit
switch
1184
The posture is not
the same with the
instruction when
spinning out
The posture of fixture is not
the same as taught after
spinning out
Check whether the fixtureisloose
1185
Mold-opened signal
is off when
spinning in
When transverse entry Z
decreases in external
standby, mold opened signal
is off out of external safety
zone or position of Z is less
than external safety area.
Check whether mold openedsignal is normal
1186
Main up limit is off
during transverse
movement out of
safety zone
When not in internal/external
safety zone, or Z does
transverse movement between
internal and external area that
has been set, main up limit is
not detected
Check whether main up limitis normal
1187
Sub up limit is off
during transverse
movement out of
safety zone
When not in internal/external
safety zone, or Z does
transverse movement between
internal and external area that
has been set, sub up limit is not
detected
Check whether sub up limitis normal
106
QC-S5G Series of Products User Manual V1.0
1188
Y1 is not in safety
zone during
transverse
movement out of
safety zone
When not in internal/external safety
zone, or Z does transverse movement
between internal and external area
that has been set, position of Y1 is
larger than internal safety zone.
Check setting of Yaxis in
Function-Mechanicalparam
1189
Spin in from
external place
when main/sub up
limit are not both
on
Main/sub up limit are not both on
when Z moves. The current position
is larger than internal safety
area while target position is
less than it.
Check whether
main/sub up limit isnormal
1190
Spin out of
internal place
when main/sub up
limit are not both
on
Main/sub up limit are not both on
when Z moves. The current position
is less than internal safety area
while target position is larger
than it.
Check whether
main/sub up limit isnormal
1191
Rising limit is
not detected
during manual
transverse
movement out of
safety area
Main/sub up limit are not both on or
position of Y1 is larger than internal
safety zone during manual
transverse movement out of safety
area
1.Check whether
main/sub up limitisnormal
2.This alarm occursif Y axis standby
position is 0 or
distance per rotationis 0
1192
Current
position is
less than safety
area allowed
move to
The current position is less than
safety area allowed move to
during manual transverse entry
Check setting of Zaxis in
Function-Mechanicalparam
1193
Current position
is larger than
safety area
allowed move to
The current position is larger than
safety area allowed move to
during manual transverse entry
Check setting of Zaxis in
Function-Mechanicalparam
1194
Y2 axis is not in
rising position
When not in internal/external safety
zone, or Z does transverse movement
between internal and external area
that has been set, position of Y1 is
larger than internal safety zone.
Check setting of Y2axis in
Function-Mechanicalparam
1195
Wait overtime
for Y1,Y2 up
limit signals in
transverse
movement
Wait overtime for signals
Check whether main/subuplimit is normal1200
Clip 1 valve
signal is on;
Clip 1 confirm
signal is off
1.The valve acts when relative
limit has no signal
2.The valve does not act when
relative limit has signal
Check whether the valveand limit point arenormal
107
QC-S5G Series of Products User Manual V1.0
1201
Clip 1 valve signal
is off;
Clip 1 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1202
Clip 2 valve signal
is on;
Clip 2 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1203
Clip 2 valve signal
is off;
Clip 2 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1204
Clip 3 valve signal
is on;
Clip 3 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1205
Clip 3 valve signal
is off;
Clip 3 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1206
Clip 4 valve signal
is on;
Clip 4 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1207
Clip 4 valve signal
is off;
Clip 4 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1208
Suck 1 valve signal
is on;
Suck 1 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1209
Suck 1 valve signal
is off;
Suck 1 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal1210
Suck 2 valve signal
is on;
Suck 2 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether thevalve and limitpoint are normal
108
QC-S5G Series of Products User Manual V1.0
1211
Suck 2 valve
signal is off;
Suck 2 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1212
Clip 7 valve
signal is on;
Clip 7 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1213
Clip 7 valve
signal is off;
Suck 12 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1214
Clip 8 valve
signal is on;
Clip 8 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1215
Clip 8 valve
signal is off;
Clip 8 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1216
Suck 5 valve
signal is on;
Suck 5 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1217
Suck 6 valve
signal is off;
Suck 6 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1218
Suck 7 valve
signal is on;
Suck 7 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1219
Suck 8 valve
signal is off;
Suck 8 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1220
Suck 9 valve
signal is on;
Suck 9 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1221
Suck 10 valve
signal is off;
Suck 10 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal1222
Suck 11 valve
signal is on;
Suck 11 confirm
signal is off
1.The valve acts when relative limit
has no signal
2.The valve does not act when relative
limit has signal
Check whether the valveand limit point are normal
109
QC-S5G Series of Products User Manual V1.0
1223
Suck 12 valve
signal is off;
Suck 12 confirm
signal is on
1.The valve acts when relative limit
has no signal
2.The valve does not act when
relative limit has signal
Check whether the valve andlimit point are normal
1250 X037 signal is
not detected
Wait overtime for signal
1.Check whether the signalwaiting for is normal
2.Set a longer wait limittime1251 X023 signal is
not detected
Wait overtime for signal
1.Check whether the signalwaiting for is normal
2.Set a longer wait limittime1300
Check standby
point posture
Standby posture error
Check vertical/horizontallimit
1301
Check standby
point main arm
up limit
1.Position of standby point is
larger than the max Y1 axis standby
position
2.Main arm is not in Y1 origin and
cannot do transverse movement when
returning to standby point
1.Check whether Y1 axis issetcorrect in
Function-Mechanical param2.Manually move Y1 axis toorigin point
1302
Check standby
point sub arm up
limit
1.Position of standby point is
larger than the max Y2 axis standby
position
2.Main arm is not in Y2 origin and
cannot do transverse movement when
returning to standby point
1.Check whether Y2 axis issetcorrect in
Function-Mechanical param2.Manually move Y2 axis toorigin point
1303
Check standby
point X
position
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step0 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signal instandby point is off, so it is when the cycle ends.
110
QC-S5G Series of Products User Manual V1.0
1304
Check standby
point Y
position
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step1 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1305
Check standby
point Z
position
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step2 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1306
Check standby
point Clip1
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step3 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
111
QC-S5G Series of Products User Manual V1.0
1307
Check standby
point Clip2
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step4 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partof the arm. Steps are fetching inserts, transverse entry,waiting for mold opened, moving downward and embedding, fetchingproduct, moving upward and allowing mold locked, crossingoutand placing, moving upward. According to these steps, clip/sucksignal in standby point is off, so it is when the cycle ends.1308
Check standby
point Clip3
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step5 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partof the arm. Steps are fetching inserts, transverse entry,waiting for mold opened, moving downward and embedding, fetchingproduct, moving upward and allowing mold locked, crossingoutand placing, moving upward. According to these steps, clip/sucksignal in standby point is off, so it is when the cycle ends.1309
Check standby
point Clip4
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step6 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
112
QC-S5G Series of Products User Manual V1.0
1310
Check standby
point Suck1
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step7 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1311
Check standby
point Suck2
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step8 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1312
Check standby
point A
When teaching, suck/clip action signal of standby point is offbydefault. Insert Clip ON action into step9 standby positionifneeded.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontal partofthe arm. Steps are fetching inserts, transverse entry, waitingformold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
113
QC-S5G Series of Products User Manual V1.0
1313
Check standby
point B
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step10 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1314
Check standby
point C
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step11 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1315
Check standby
point X2
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step12 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
114
QC-S5G Series of Products User Manual V1.0
1316
Check standby
point Y2
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step13 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1333
Check standby
point suck3
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step14 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
1334
Check standby
point suck4
When teaching, suck/clip action signal of standby point isoffby default. Insert Clip ON action into step15 standby positionif needed.
System will return to standby point automatically after a cycle,except for clip/suck actions.
If clip signal is off in standby point, but it is on after a cycleended, the alarm will occur;
If clip signal is on in standby point, but it is off after a cycle,the alarm will also occur.
Internal insert teaching begins from the upper horizontalpartof the arm. Steps are fetching inserts, transverse entry, waitingfor mold opened, moving downward and embedding, fetching product,moving upward and allowing mold locked, crossing out and placing,moving upward. According to these steps, clip/suck signalinstandby point is off, so it is when the cycle ends.
115
QC-S5G Series of Products User Manual V1.0
1400
Do not detect
rising
In auto mode, press the start key,
system do return action and back to
standby point. While reset, the main
and sub arms must be on the up limit
point, or it will alarm
1. Check whethertheauxiliary up limitisnormal
2. Manually move thesub arm to the origin1401
Not internal at
the same time
When reset, the main and sub arms must
be on the up limit point, or it will
alarm
1. Check whethertheauxiliary up limitisnormal
2. Manually move thesub arm to the origin1402
Not external at
the same time
When reset, the main and sub arms must
be on the up limit point, or it will
alarm
1. Check whethertheauxiliary up limitisnormal
2. Manually move thesub arm to the origin1403
Can not check the Y2
up limit
In auto mode, press the start key,
system do return action and back to
standby point. While reset, the main
and sub arms must be on the up limit
point, or it will alarm
1. Check whethertheauxiliary up limitisnormal
2. Manually move thesub arm to the origin1410
Wait overtime for
external descending
safety signal
Wait overtime for signal
1.Check whether thesignal waiting forisnormal
2.Set a longer
limit time of
waiting
1411
Wait overtime for
external descending
safety signal
Wait overtim e for signal
1.Check whether thesignal waiting forisnormal
2.Set a longer
limit time of
waiting
1412
Error in relative
position of shaft
The current running axis is
inconsistent with the teaching axis
Check whether thetaught axis deviationin waiting is correct1420 Servo 1 off-line
Main board cannot contact servo
board 1
Check that the wireof the servo board1is loose
1421 Servo 2 off-line
Main board cannot contact servo
board 2
Check if the wireofthe servo board 2isloose
1422 Servo 3 off-line
Main board cannot contact servo
board 3
Check if the wireofthe servo plate 3isloose
1423 Servo 4 off-line
Main board cannot contact servo
board 4
Check if the wireofthe servo panel 4isloose
116
QC-S5G Series of Products User Manual V1.0
9.4.2 Servo Alarms of QCS5G, QCS3G Series
Rules of servo alarm codes in drive-control series: first two XX represent axis numberand range is(27-38), 27 means in servo board 1, 28 means in servo board 2, 29 meansin servo board 3, 30 means in servo board 4, 31 means X axis, 32 means Y axis, 33 meansZ axis, 34 means X2 axis, 35 means Y2 axis, 36 means A axis, 37 means B axis, 38 meansC axis; The last two XX represent type of servo alarm and if they are same number,itmeans same type of alarm. 0 axis refers to axis in general, not specific one.
Axis 1:Axis 1 represents Y1, Y2, X1.
Axis 2:Axis 2 represents Z, X2.
If the program cannot recognize the exact axis that alarms, it will send a blank alarmwithout information, but the servo board alarm code will inform the user.
E.g. 2702 Alarm:from Y1 servo in servo board 1;
2803 Alarm: from X2 servo in servo board 2.
Alarm
Number
Alarm
Information
Alarm Reason Alarm Solution
XX01
Emergency stop
alarm
Servo has
emergency stop
signal input
1.T11.Turn out the manual controlleremergency stop knob
2.2.Make the host emergency stopsignal short connected
XX02
1 axis
overcurrent
IPM module over
current
protection
1. Whether the motor is locked2. Pull out power line and brakelineafter power on again. If alarm,itis host failure and replace it;ifnot, check motor and wiring.
XX03
2 axis
overcurrent
IPM module over
current
protection
1. Whether the motor is locked2. Pull out power line and brakelineafter power on again. If alarm,itis host failure and replace it;ifnot, check motor and wiring.
XX04
0 axis external
generatrix
disconnected
No normal generatrix
signal
1. Whether the motor is locked2. Pull out power line and brakelineafter power on again. If alarm,itis host failure and replace it;ifnot, check motor and wiring.
XX05 1 axis overload
Over the maximum load
1.Check the load
2.Whether the motor is shut off,whether the lock is loose
3.Check whether param1 is thecorresponding power
XX06 2 axis overload
Over the maximum load
1.Check the load
2.Whether the motor is shut off,whether the lock is loose
3.Check whether param1 is thecorresponding power
XX07
Initialization
of 2 axis current
sampling module
failed
Drive power on
initialization is not
over
1.Press stop to clear
2.Power on again if can not clear3.Host failure, replace it
117
QC-S5G Series of Products User Manual V1.0
XX08
Initialization of 2
axis current sampling
module failed
Drive power on
initialization
is not over
1.Press stop to clear
2.Power on again if can not clear3.Host failure, replace it
XX09 1 axis UVW phase current
abnormality
Current
exceeds alarm
value
1.Cable sequence error
2.Lack of phase
3.The motor code does not correspondtothe motor
XX10 2 axis UVW phase current
abnormality
Current
exceeds alarm
value
1.Cable sequence error
2.Lack of phase
3.The motor code does not correspondtothe motor
XX11 0 axis DC undervoltage
Voltage
detected above
195v
1.The load is too heavy, the
acceleration is too high, resultingintoo much voltage drop
2.External power into the voltage istoolow
3.Host failure, replace it
XX12
0 axis VDC
overvoltage
Voltage
detected above
405v
1.The load is too heavy, the
acceleration is too high, resultingintoo much voltage drop
2.External input power voltage istoolow
3.Host failure, replace it
XX13 1 axis overspeed Over max speed
1.Internal communication drops, checkwhether the grounding is good
2.The parameter setting of 50 is wrongXX14 2 axis overspeed Over max speed
1.Internal communication drops, checkwhether the grounding is good
2.The parameter setting of 50 is wrongXX15 0 axis drive overheat
The internal
temperature
exceeds 75
degrees
1.Check if the fan is normal
2.Host failure, replace it
XX16 1 axis writes IIC fail
Memory chip
anomaly
Mainframe replacement
XX17 2 axis reads IIC fail
Memory chip
anomaly
Mainframe replacement
XX18
Excessive deviation of
1 axis position
Deviation
between the
command value
and the actual
encoder value
exceeds the
set value of
param49
1.Set 49 servo parameters, increasethedeviation range
2.The acceleration and decelerationsettings are too small
3.The system is abnormal
118
QC-S5G Series of Products User Manual V1.0
XX19
Excessive
deviation of 2 axis
position
Deviation between the
command value and the
actual encoder value
exceeds the set value
of param49
1.Set 49 servo parameters, increasethe deviation range
2.The acceleration and decelerationsettings are too small
3.The system is abnormal
XX20
1 axis encoder
error
Encoder communication
failure
1.Encoder line is abnormal
2.Poor contact at the junctionofencoder
3.Motor encoder is abnormal
XX21
Abnormal 1 axis
velocity
measurement
Abnormal rotation of
motor
1.Motor code setting is wrong
2.The gain parameter is not
reasonable
3.Motor fault causes chaotic
rotation
XX22
1 axis encoder
initializing
Encoder
initialization
1.Encoder line is abnormal
2.Poor contact at the junctionofencoder
3.Motor encoder is abnormal
XX23
0 axis hard
over-pressure
Internal hardware
over-voltage protection
1.The load is too heavy, the
deceleration is too high, resultingin too much voltage rise
2.Brake resistor failure or
non-conductivity
3.Host failure. Replace
XX24
X axis external
Bus ERR
Normal signal from bus is
not received
1. Top 3-pin white terminal is loose2. Host malfunction
XX25
X axis buffer
overflow
System abnormality Replace the host
XX26
X axis buffer
overflow
System abnormality Replace the host
XX27
EEPROM
parameter check
exception
Storage chip abnormality Replace the host
XX28
2 axis encoder
error
Encoder communication
failure
1.Encoder line is abnormal
2.Poor contact at the junctionofencoder
3.Motor encoder is abnormal
XX29
Abnormal 2 axis
velocity
measurement
Abnormal rotation of
motor
1.Motor code setting is wrong
2.The gain parameter is not
reasonable
3.Motor fault causes chaotic
rotation
XX30
2 axis encoder
initializing
Encoder
initialization
1.Encoder line is abnormal
2.Poor contact at the junctionofencoder
3.Motor encoder is abnormal
XX31
0 axis servo driver
alarm
Clear alarm too
frequently
119
QC-S5G Series of Products User Manual V1.0
XX32
0 axis servo driver
alarm
The stored parameters are
verified incorrectly
Write 8051 through Param0, waitfor 10s and power on again to clearXX33
0 axis
communication
timeout
Bus communication
timeout
Replace the host
XX34
1 axis encoder
battery error
The encoder has a battery
dropout marker bit
Make sure the battery is wellconnected, set Param13 as 0toclear
XX35
2 axis encoder
battery error
The encoder has a battery
dropout marker bit
Make sure the battery is wellconnected, set Param13 as 0toclear
XX36
Low battery
voltage for 1
axis encoder
The encoder has a
battery voltage low
marker bit
Encoder voltage is too low
XX37
Low battery
voltage for 2
axis encoder
The encoder has a
battery voltage low
marker bit
Encoder voltage is too low
XX38
1 axis motor code
is not consistent
with the set value
The motor code read from
the encoder is
inconsistent with the
set value
1.Check whether Param2 is thecorrect motor code. If it iscorrect, it can be eliminatedbyrestarting
2.If it is incorrect, set Param4as 1, and then manually set Param2as the correct motor code
XX39
2 axis motor code
is not consistent
with the set value
The motor code read from
the encoder is
inconsistent with the
set value
1.Check whether Param2 is thecorrect motor code. If it iscorrect, it can be eliminatedbyrestarting
2.If it is incorrect, set Param4as 1, and then manually set Param2as the correct motor code
XX40
1 axis illegal
motor code
System does not support
this code
Set Param4 as 1 and manuallysetParam2 as correct motor codeXX41
2 axis illegal
motor code
System does not support
this code
Set Param4 as 1 and manuallysetParam2 as correct motor codeXX42
Position of 1 axis
encoder does not
refresh
No change in encoder
value
Motor encoder abnormal
XX43
Position of 2 axis
encoder does not
refresh
No change in encoder
value
Motor encoder abnormal
XX44
1 encoder
multi-turn value
alarm
Power off, remove the batterytoreset the encoder/Param13 setas0
120
QC-S5G Series of Products User Manual V1.0
XX45
2 encoder
multi-turn value
alarm
Power off, remove the batterytoreset the encoder/Param13 setas0
XX46
1 motor power
section mismatch
Param 1(motor power
section) does not
match with Param
2(motor code)
Check Param2 to confirm whetherthe motor code matches the powerof Param1
XX47
2 motor power
section mismatch
Param 1(motor power
section) does not
match with Param
2(motor code)
Check Param2 to confirm whetherthe motor code matches the powerof Param1
XX48
1 axis parameter
setting error
Parameter setting is
not reasonable
Check if the parameters areinthe rang:5(1, 6000), 6(1,
300),7(1-300), 11(10,
5000),15(10,100), 21(1, 1000),22(0,300), 23(1, 20), 31(20000),32(2000/20000),69(4096), 71(0),72(0), 73(0)
XX49
2 axis parameter
setting error
Parameter setting is
not reasonable
Check if the parameters areinthe rang:5(1, 6000), 6(1,
300),7(1-300), 11(10,
5000),15(10,100), 21(1, 1000),22(0,300), 23(1, 20), 31(20000),32(2000/20000),69(4096), 71(0),72(0), 73(0)
121
QC-S5G Series of Products User Manual V1.0