Power Management
98 / huyuelectric.com
FM2S
Single Phase Smart Meter
3. Measurement
Energy Pulse
Active energy pulse is output to relevant LED for accuracy verification. By default the meter constants
are configured as 1000imp/kWh, which are also configurable based on application.
Energy Values
Electric meter can measure and store the following energy quantities:
-Import active energy (+A),
-Export active energy (-A),
-Absolute active energy (|+A| + |-A|),
-Algebraic sum active energy (|+A| - |-A),
-Multi- tariff energy
After the energy value reaches the maximum display limit, which is 999999.9 [kWh], it will overflow and
reset to zero, meanwhile the overflow counter increments by one.
Demand
The method used for demand calculation of the meter could be either average demand or sliding demand.
By default it’s configured as average demand.
For sliding demand the interval “T” used for demand calculation is determined by the two parameters:
period and number_of_period, illustrated below:
For average demand, it can be regarded as a special type of “sliding demand” where the number of period is always 1.
Through the configuration of the above two parameters, the demand interval of the meter is defined.
The following table shows the value range of the parameters.
Maximum demand is captured based on corresponding demand register value.
The meter has the following demand/maximum demand registers:
Instantaneous Values
The meter measures the following instantaneous values:
- Instantaneous current: 1-digit decimal, unit: A.
-Instantaneous voltage: 1-digit decimal, unit: V.
-Import active power (A+): 2-digit decimal, unit: kW.
-Export active power (A-): 2-digit decimal, unit: kW.
Calculation method
Sliding
Interval
period(min)
1~60
1~60
Demand internal (min)
1~60
1~60
Number of period
1~60
1
Demand type
Import active demand (A+)
Export active demand (A-)
Measurement content
Current demand register (1.4.0)
Demand of last interval register (1.5.0)
Maximum demand registers - total and per tariff (1.6.x)
Current demand register (2.4.0)
Demand of last interval register (2.5.0)
Maximum demand registers - total and per tariff (2.6.x)
Power Management
99 / huyuelectric.com
FM2S
Single Phase Smart Meter
Optical Interface
Optical front view
-Compliant to ANSI C12.18 optical communication physical interface
-Conform to IEC62056-21 standards (mode C)
-Configured as 300bps, 7 bits, 1 even parity by default
-Communication speed up to 9600bps
-PC software and HHU can be used for local data exchange through optical interface.
Uplink Communication Interface
-Configured as 8 bits, no parity by default
-IEC62056-21 protocols
-Various communication options including RF/Lora/Bluetooth
5. Time of Use(Optional)
General Description
The meter offers up to 4 tariff operations, which feature is driven by its internal real time clock. The time table used for the tariff switching consists of the
season tables, the day tables and the special day tables.
Real Time Clock
1. RTC features
-Automatic leap year switching
-Accuracy at 23°C less than 0.5s/day
-24-hour clock format
-If the real-time clock stops, a predefined tariff can be designated for tariff energy registration
2. RTC Backup Power
One lithium battery with 1200mAh capacity, 3.6V supply voltage battery provides backup power to the RTC
TOU Time Table
The meter has 2 sets of TOU time tables, capable of up to 4 tariff operations. Each table consists of up to 12 season entries, associated to 12 week tables
respectively, and up to 8 day tables, each with up to 10 day entries. Besides, the meter can define up to 50 special days.
4. Communication
The meter offers 2 independent communication interfaces, which include an optical port, and a
modular communication unit used for uplink communication.
Power Management
100 / huyuelectric.com
Time Table Programming
The time table programming is always applied on the passive time table. The activation time of the passive time table is configurable. When the meter gets
to the activation time the active and passive time table will swap. The names of active and passive time table are both configurable but cannot be the same.
The time table switching can be done remotely through a communication command.
FM2S
Single Phase Smart Meter
6. Billing
There is a billing profile in the meter to store the billing values. The maximum demand registers reset and a record is generated in the billing profile either the
predefined billing time is due or a comunication billing operation is detected.
Billing on Predefined Schedule
By default the billing schedule is configured to trigger the billing operation at midnight on the first day of each month. The number of captured objects for
each billing entry can be up to 30.
The virgin startup of the meter generates a billing entry in the profile.
If a power outage or a time adjustment skips the billing time, the meter will complement the missed billing entry either after the meter is re-powered up or
after the time adjustment is completed.
Operations associated to billing
When a billing operation is conducted, the meter will do the following:
- Generate an entry in the billing profile
- Reset maximum demand resisters,
- Generate MD reset event log.
7. Load Profile(Optional)
Interval of each load profile is configurable, and independent from each other
What values can be stored in each load profile is configurable
Power Management
101 / huyuelectric.com
FM2S
Single Phase Smart Meter
8. Event(Optional)
The meter detects and records events. The event log is identified with unique event number. The generated event signal will be directed to generate alarm or
error indication based on relevant configuration.
Event logs, alarm and error generation:
Event Logs
The meter defines and records the following 10 type of event logs:
Type
Power outage
Over voltage
Under voltage
Over current
Over load
Meter programming
Clock setting
Battery low
Current reversal
System reset
Description
When the power grid is out of power, all phase voltage is lower than the working
voltage of the meter. When the power grid occurs, any phase voltage is higher than
the working voltage of the meter, and it lasts more than 4s; 20 items can be recorded.
The overvoltage starts as the default voltage greater than 1.2Un, and lasts more
than 60 seconds; The default voltage of overvoltage is less than 1.2Un, and lasts
more than 60 seconds; 20 items can be recorded.
The default voltage is less than 0.78Un and lasts more than 60 seconds. The
default voltage is greater than 0.78Un and lasts more than 60 seconds. 20 items can
be recorded.
The overcurrent starts with the default voltage greater than 1.2IMAX, and lasts
more than 60 seconds; The default voltage is less than 1.2imax and lasts more than
60 seconds. 20 items can be recorded.
Overload started as the default voltage greater than 1.2IMAX*Un, and lasted more
than 60 seconds; Overload end default voltage is less than 1. 2IMAX*Un, and
lasts more than 60 seconds; 20 items can be recorded.
Programming event for a meter; There are 10 records.
Save the time before and after the setup; 20 items can be recorded.
The battery is lower than the reasonable valve value; There are 10 records.
The current reverse starting condition is the reverse of the current and the apparent
power is greater than the starting power. The reverse end condition is the current is
not reversed and lasts more than 60 seconds; 20 items can be recorded.
Abnormal reset of the meter, such as the reposition of watchdog, etc.; There are 10 records.
OBIS
0-0:99.98.0.255
0-0:99.98.1.255
0-0:99.98.2.255
0-0:99.98.3.255
0-0:99.98.4.255
0-0:99.98.5.255
0-0:99.98.6.255
0-0:99.98.7.255
0-0:99.98.8.255
0-0:99.98.9.255
Event Code
Power on: 1
Power off: 2
Start: 79
Over: 204
Start: 76
Over: 201
Start: 95
Over: 220
Start: 99
Over: 224
47
The time before set:4 After:5
8
Start: 91
Over: 216
15
Event Alarming
The alarm indication includes the alarm LED, the alarm symbol on the LCD and the display on LCD.
- Alarm LED
When an alarm event occurs, the alarm LED will flash continuously.
- Alarm symbol of LCD(By defult)
9. Data Security
The meter offers different categories of users the following 2 access levels which are protected by access password:
- Public Reading
- Meter Reading and Configuration
Power Management
102 / huyuelectric.com
It is recommended to refer to the wiring diagram for connecting the meter to the power network. If appropriate a meter cabinet can be used to protect the
meter. Preferably the meter should be installed in a ventilated and environment.
1. Installation Procedures and Cautions
Installation Procedures
To ensure proper operation of the meter, follow the procedures below when install a meter:
- Pressure the meter, make sure the terminals are inserted into the socket.Make sure the meter is firmly in place, power on the meter
Cautions
Improper installation could damage the meter. Relevant verification must be done to ensure the meter is properly installed:
- Verify the operating voltage of the meter is within the range
- Verify the current range is proper for the application at the installation site
- Verify there is no visible mechanical or electrical damage on the meter
- Verify the factory seals of the meter have not been broken
2. Acceptance after Installation
After the meter is installed and power is connected, the following checking should be done on the meter:
- The phase voltage symbol on the LCD should be present
- If any load is applied on the meter the pulse LED should be flashing and the quadrant indicator should correctly indicated
3. Safety Regulations
Relevant national and international safety regulations must be complied with during the course of the meter installation. The installation must be conducted
by qualified personnel.
Do not touch any of the live parts of the meter at any time when the power is on. Be aware that personal injury or equipment damage could result from
improper wiring procedures.
FM2S
Single Phase Smart Meter
Transportation and storage
- The meter should be transported and unpacked violently. Do not apply power on when the case has been damaged or violently dropped during handling,
access and installation. Contact the supplier as soon as possible .
- Save the energy meter should be in the original packaging, the ambient temperature is -45 ~ +70 , the average relative humidity of not more than 75% of
the air without corrosive gases.
- Meter stored in the warehouse, should be placed on the bench, the stack height of not more than 10 boxes, unboxing, the single package meter stacking
height of not more than 10
Installation
Power Management
DDSU881
Series Guide Rail Table
Item
Accuracy Grade
Voltage Specifications
Current Specifications
Frequency
Operating Voltage Range
Operating Temperature Range
Power Consumption
Display Mode
Standard
Technical Specifications
Active power level 1, level 2
220V
0.25–0.5(60)A, 0.25–0.5(80)A,
other specifications can be customized
50Hz
Rated operating voltage range: 0.9Un~1.1Un,
extended operating voltage range: 0.8Un~1.15Un
Rated operating temperature range: -25℃~+55℃,
extreme operating temperature range: -40℃~+70℃
Approximately 1W
LCD display
GB/T 17215.321-2021, DL/T 645-2007
Application Scope
The DDSU881-4P DIN-rail mounted electronic single-phase energy meter (hereinafter referred to as the meter)
uses microelectronics technology to measure electrical energy. Its technical specifications comply with GB/T
17215.321-2021. It features a fully shielded and sealed structure, offering excellent resistance to electromagnetic
interference, low power consumption, high accuracy, anti-tampering measures, high overload resistance, and a
long lifespan.
Main Functions and Features
1. Accurately measures forward and reverse active energy, with reverse active energy accumulated as forward
energy.
2. The meter utilizes a stable metering chip and low-power industrial-grade components designed using
advanced SMT technology.
3. Long-term use requires no calibration. DIN-rail mounting allows for compact installation and high accuracy.
4. Display: 6+2 LCD.
5. Infrared and RS485 communication interfaces facilitate data exchange.
Main Technical Parameters
Appearance and Installation Dimensions
8
0
1
91
8
6
35
103 / huyuelectric.com
8
0
1
8
6
Power Management
801
86
104 / huyuelectric.com
DDSYU881
Series Guide Rail Table
Item
Accuracy Grade
Voltage Specifications
Current Specifications
Frequency
Operating Voltage Range
Operating Temperature Range
Power Consumption
Display Mode
Standard
Technical Specifications
Active power level 1, level 2
220V
0.25–0.5(60)A,0.25–0.5(80)A,
other specifications can be customized
50Hz
Rated operating voltage range: 0.9Un 1.1Un,
extended operating voltage range: 0.8Un~1.15Un
Rated operating temperature range: -25℃~+55℃,
extreme operating temperature range: -40℃~+70℃
About 1W
LCD display
GB/T17215.321-2021, DL/T645-2007, GB/T18460.3-2001
Application Scope The DDSYU881-4P DIN-rail electronic single-phase prepayment meter (infrared fee control meter) is a new infrared wireless remote control prepayment meter with multiple functions, including energy metering, load control, compact size, and easy installation. It is an ideal product for reforming the electricity consumption system, achieving electricity commercialization, resolving billing difficulties, and regulating grid load conditions. Main Functions and Features 1. Single-phase AC active energy metering, long-term operation without calibration. 2. One electricity purchase remote control per household (meter). Each remote control is encrypted and has a random password to prevent counterfeiting. 3. Expandable RS485 communication enables remote centralized meter reading and remote prepayment top-up. 4. The accompanying prepaid electricity vending management system provides comprehensive electricity vending management and usage monitoring functions. 5. If the load exceeds the set maximum current for a continuous period, the power supply circuit is disconnected and an alarm symbol flashes on the LCD. The meter automatically closes after a delay. 6. Remaining Power Display: The display has 8 digits (6 integers, 2 decimals). When the remaining power reaches the pre-alarm level, the LCD will flash to indicate the user needs to enter a new purchase amount. When the remaining power in the meter reaches zero, the meter automatically trips, interrupting power supply. At this point, the user must present their power purchase card to the electricity sales office to purchase power (the power supply office may allow for overdrafts, and inserting a power purchase card allows the user to use a certain amount of power). Only after inserting a valid power purchase card into the meter can power be restored. When the power shortage reaches a certain level, power is automatically cut off. Power is automatically restored after entering the new purchase amount (minus the overdraft amount). 7. Data is automatically saved during a power outage and restored upon power restoration. 8. A computer, dedicated infrared card reader, and billing management software form the electricity sales management system. 9. The meter can also measure correctly even if the wiring is reversed.
Main Technical Parameters
Appearance and Installation Dimensions 801 91 86
35
Power Management
DTSU881/DSSU881
Series Guide Rail Table
Item
Accuracy Grade
Voltage Specifications
Current Specifications
Frequency
Operating Voltage Range
Operating Temperature Range
Power Consumption
Display Mode
Standard
Technical Specifications
Active power level 1, level 2
3×220/380V, 3×100V, 3×380V, 3×57.7/100V
0.015–0.075(6)A,0.25–0.5(60)A,0.25–0.5(80)A,
other specifications can be customized
50Hz
Rated operating voltage range: 0.9Un~1.1Un,
extended operating voltage range: 0.8Un~1.15Un
Rated operating temperature range: -25℃~+55℃,
extreme operating temperature range: -40℃~+70℃
About 3W
LCD display
GB/T17215.321-2021, DL/T645-2007
Application Scope
This three-phase, four-wire (new DIN-rail type) AC active energy meter (hereinafter referred to as the energy
meter) offers high accuracy and usability. This meter utilizes internationally advanced ultra-low-power largescale integrated circuit technology and SMT manufacturing processes. It is an ideal choice for substations or
power plants, and is also suitable for transmission and distribution, or for network automation. It measures threephase AC active energy in a 50Hz reference frequency grid, and can also measure both forward and reverse
energy.
Main Functions and Features
1. Built-in high-speed, high-precision AC voltage and current acquisition modules, ensuring high sampling
accuracy and real-time, accurate energy measurement.
2. It measures both forward and reverse active energy, boasting a compact size, easy installation, and high
accuracy.
3. Powered by a three-phase power supply, the meter remains operational even if any two phases of the threephase, four-wire system are powered off.
4. It displays ABC three-phase current, voltage, and power factor.
5. The meter maintains data even in the event of a loss of AC power.
6. It has infrared and RS485 communication interfaces to realize remote centralized meter reading function.
Main Technical Parameters
Appearance and Installation Dimensions
9
6
35
158
119
105 / huyuelectric.com
Power Management
96
158 119
106 / huyuelectric.com
DTS881-VAP (D1206)
Single Phase Voltage/Current Protective Energy Meter
Application Scope The DDS238-VAP is a single-phase, two-wire AC active energy meter with over-voltage, under-voltage, and over-current protection. It cuts off the load instantly during faults to protect electrical equipment. Protection thresholds are user-adjustable based on local conditions. The meter offers long service life, high stability, wide voltage range, and low power consumption. Key Features -LCD with backlight: Displays total energy (kWh), real-time current (A), voltage (V), and active power (W). -Protection modes include over-voltage, under-voltage, and over-current with selectable auto or
manual reclosing. -Malignant load protection (pure resistive load limit) designed for dormitories and apartments. -Adjustable protection thresholds to safeguard equipment from voltage instability or faults. -Automatic recovery once line voltage normalizes, preventing false trips caused by transient surges. -LED indicators for all protection modes. -Lightning protection and high overload capacity. -Selectable circuit output cycle switch. -DIN 35 mm rail mounting for easy installation. -Each protection function can be individually enabled or disabled.
Wire connection Outline dimension
Technical Data
D1206
Input working voltage
Overvoltage protection value
Under voltage protection value
Over current protection value
Rated frequency
Delay in switch on after power off
Voltage circuit power consumption
Current circuit power consumption
Active energy display range
Voltage/currentactive power accurate
Active energy accurate
Operating temperature
Storage temperature
Relative humidity
Altitude
Electromagnetic Environment
Mechanical life
85~300V AC
85-300V ( default 270V)
85-300V ( default 170V)
1-63A( default 40A) 1-80A( default 60A special order)
50/60Hz
2-512s ( default 2s)
≤1W
<1VA
0~9999.9kWh
+0.5%
+1% (IEC62053-21)
-25℃ ~+70℃
-40℃ ~+80℃
≤85%
≤2500m
E2
≥100000 cycles
Power Management
Technical Data
DDS881-1(D1102)
Single Phase Din Rail Type Energy Meter
Rate-Rated
Rated Current / Frequency
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
110V, 120V,220V,230,240V (0.8~1.2Un)
5(32)A, 5(40)A, 5(45)A/50Hz or 60Hz ±10%
Application Scope
The meter is designed to measure single phase two wire AC active energy like residential,utility and industrial
application. It is a long life meter with the advantage of high stability, high over load capability, low power loss
and small volume.
Basic Function
-Mechanical step register 5+1 or LCD display 5+2 or 6+1
-Bi-directional total active energy measurement, reverse active energy measure in the total active energy
-For LCD display type meter, Energy data can store in memory chip more than 15 years after power off
-Pulse LED indicates working of meter, Passive pulse output with optical coupling isolation 35mm din
rail installation
-LCD display with backlight (optional function)
Wire connection
Outline dimension
D1102-1
D1102-2
D1102-3
D1102-4
Direct type
<1W/10VA
4000V/25mA for 60s
IP20
-25℃ ~ 70℃
Accuracy class
Start current
Over current withstand
Executive standard
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
107 / huyuelectric.com
Power Management
DDS881-2 (D1201)
Single Phase Din Rail Type Energy Meter
Application Scope
The meter is designed to measure single phase two wire AC active energy like residential, utility and industrial
application. It is a long life meter with the advantage of high stability, high over load capability, low power loss
and small volume.
Basic Function
-LCD display 5+1
-Bi-directional total active energy measurement, reverse active energy measure in the total active energy
-The pulse LED indicates the meter's operation. Passive pulse output is provided with opto-coupler isolation.
-Energy data can store in memory chip more than 15 years after power off
-LCD with backlight and keypad ,resettable interval energy can be reset to zero by keypad in anytime
(optional function)
-35mm din rail installation
Wire connection
Outline dimension
Technical Data
Rate-Rated voltage AC
Rated Current / Frequency
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
110V,120V,220V,230,240V (0.8~1.2Un)
5(65)A, 10(100)A /50Hz or 60Hz±10%
Direct type
<1W/10VA
4000V/25mA for 60s
IP20
-25℃ ~ 70℃
Accuracy class
Start current
Over current withstand
Executive standard
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
D1201-1
D1201-2
108 / huyuelectric.com
Power Management
Technical Data
DDS881-1-W1 (D1107)
Single Phase Din Rail Type Wifi Remote Control Smart Switch(IVAP)
Rated Voltage (AC)
Rated Current / Frequency
Wi-fi
Connection Mode
Power Consumption
Withstand Voltage(AC)
IP Rating
Operating Temperature
Application Scope
The switch is designed to measure single phase two wire AC active energy and variable parameter like
residential, utility and industrial application. It can remote read from WIFI communication (Smart life or Tuya
smart APP). It is a long life meter with the advantage of high stability, high over load capability, low power loss
and small volume.
Basic Function
-Bi-directional active energy measure, import/export active energy display separately on APP
-The switch APP also display real voltage, current, active power, reactive power , power factor,
frequency
-Timing and delay control by APP
-Hour/Day/Month/Year history of total/import/export active energy consumption tracking by APP,
and also can output excel 30 days active energy records by email.P
-Remote control on/off by APP, it also has manual Control on/off by button under lose WIFI
-Prepayment function ,if balance used up, it will cut off automatic. This function can be on/off
by hand.
-It have over-voltage and over load protection, it can set value from APP .Each protection
function can be opened/closed as customer requirement
-It have active power 15minutes interval curve only one day
-Voice control on/off function
-Alarm event records and on/off operation records on APP
-App has password protected setting/Carbon emissions setting/ electric cost fee setting/ reset energy to
zero setting
-35mm din rail installation
Wire connection
Outline dimension
85 ~ 300V (L-N)
63A/50Hz or 60Hz±10%
802.11b/g/n
Direct type
< 2W/10VA
4000V/25mA for60s
IP20
-25°C ~ 70°C
1% or 0.5%
20mA
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse,80±5ms
109 / huyuelectric.com
Accuracy class
Start current
Over current withstand
Executive standard
Led pulse output
D1107
Power Management
DDS881-1-W2 (D1108)
Single Phase Din Rail Type Wifi Remote Control Smart Switch
Application Scope
The switch is designed to remote control on/off in single phase two wire AC power grid . It can remote control
from WIFI communication(Smart life or Tuya smart APP) . It is a long life product with the advantage of high
stability, high over load capability, low power loss and small volume.
Basic Function
-Voice control: once you have this switch, you can connect it with Amazon Alexa(Amazon echo/dot/tap) or
Google Assistant for voice control
-Wi-Fi Remote Control: You can use \"Smart Life\" APP in your smart phone to control the switch wirelessly with Wi-Fi
or 4G network.no hub required
-Timing Function: Take full control of your home or office lights thanks to schedule timer that will allow you to plan
the exact time to turn lights and appliances on/off automatically
-Share Device:This smart switch can have several control sites shared by different family members.one mobile
phone can also control many switches
-Manual Control by button under lose WIFI
-35mm din rail installation
Technical Data
Rate-Rated voltage AC
Rated Current / Frequency
Wi-Fi
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
D1108
110 / huyuelectric.com
85 ~ 300V (L-N)
63A/50Hz or 60Hz±10%
802.11b/g/n
Direct type
< 2W/10VA
4000V/25mA for 60s
IP 20
Magnetic latching
70A
30 Imax for 0.01s
-25°C ~ 70°C
Relay type
Max load
Over current withstand
Work temperature
Wire connection
Outline dimension
DDS881-4 W(D1408)
Single Phase Three Wire Din Rail Type RS485 Energy Meter
Application Scope
The meter is designed to measure single phase two wire AC active energy and variable parameter like residential,
utility and industrial application. It is equipped with an RS485 communication port for remote reading. It is a long
life meter with the advantage of high stability, high over load capability, low power loss and small volume.
Basic Function
-LCD display, keypad for LCD display step by step
-Bi-directional total active energy, reverse active energy measure in the total active energy
-The meter also display real voltage, current, active power, reactive power , power factor, frequency, total
active energy, import active energy, export active energy, reactive energy
-RS485 communication port, MODBUS-RTU protocol
-Remote control on/off with RS485 communication port and have led indication
-The active energy pulse LED indicates meter operation.
-The pulse output is electrically isolated via optical coupling.
-Energy data can store in memory chip more than 15 years after power off
-35mm din rail installation, bottom type wire connection
Wire connection
Outline dimension
Technical Data
Rate-Rated voltage AC
Rated Current/Frequency
Communication port
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
110V,120V,220V,230,240V (0.8~1.2Un)
5(60)A, 20(80)A / 50Hz or 60Hz±10%
RS485 port, baud rate 1200~9600 bps, default is 9600bps, address 1~247, None parity,
stop bits 1, data bits 8.
Direct type
<1W/10VA
4000V/25mA for 60s
IP20
-25℃ ~70℃
Accuracy class
Start current
Over current withstand
Executive standard
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
D1408
Power Management
111 / huyuelectric.com
Power Management
DDS881-4 WIFI(D1415)
Single Phase Din Rail Type WIFI Remote Control Energy Meter(IVAP)
Application Scope
The meter is designed to measure single phase two wire AC active energy and variable parameter like residential,
utility and industrial application. It is equipped with an RS485 communication port for remote reading.(Smart life
or Tuya smart APP). It is a long life meter with the advantage of high stability, high over load capability, low power
loss and small volume.
Basic Function
-LCD screen with step-by-step display using keypad
-Supports two-way energy measurement; imported and exported energy is shown separately on both the
meter and the app
-Displays real-time voltage, current, active power, reactive power, power factor, frequency,
temperature, imported/exported energy, and reactive energy
-Timer and delay functions can be set via the app
-Tracks energy usage history by hour, day, month, and year via the app; also supports exporting 30-day
energy data to Excel by email
-View real-time voltage, current, power, and frequency through the app
-Remote on/off control via the app; manual on/off control is available via a button when Wi-Fi is unavailable
-Prepayment function: the meter will automatically shut off when the balance is used up; this feature can
be manually enabled or disabled
-Built-in over-voltage, overload, and over-temperature protection; limits can be set in the app, and
each function can be turned on or off as needed
-Shows active power curve in 15-minute intervals (for one day only)
-Supports voice control for switching on/off
-Event logs for alarms and on/off actions are viewable in the app
-App features include password protection, carbon emission tracking, electricity cost settings, and energy
reset to zero
-Leakage protection (requires external CT, sold separately upon request)
-35mm DIN rail mounting with bottom-entry wiring
Wire connection
Outline dimension
Technical Data
Rate-Rated voltage AC
Rated Current/ Frequency
WIFI
Communication port
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
90 ~ 300V (L-N)
5(60)A / 50Hz or 60Hz±10%
802.11b/g/n
RS485 port, baud rate 1200 ~ 9600 bps, default is 9600bps, address 1 ~ 247, None parity,
stiop bits 1, data bits 8.
Direct type
<2W/10VA
4000V/25mA for 60s
IP20
-25℃ ~ 70℃
Accuracy class
Start current
Over current withstand
Executive standard
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
D1415
112 / huyuelectric.com
DDS881-4 WIFI(D1413)
Single Phase Three Wire Din Rail Type WIFI Remote Control Energy Meter
Application Scope
The meter is designed to measure single-phase three-wire AC active energy and various electrical parameters,
making it suitable for residential, utility, and industrial applications. It supports remote reading via Wi-Fi using the
Smart Life or Tuya Smart app. This compact meter offers long service life, high stability, strong overload capacity,
and low power consumption.
Basic Function
-LCD display with button control for step-by-step navigation
-Bi-directional total active energy measurement; reverse energy is included in the total active energy
-The meter displays real-time values such as phase voltage, active power, frequency, and L1/L2 current on
both the LCD and the mobile app
-The app shows total active energy, remaining balance, and supports remote ON/OFF control via a high-capacity
magnetic relay for L1/L2 circuits
-Timing and delay control available through the app
-The app shows total active energy, remaining balance, and supports remote ON/OFF control via a high-capacity
magnetic relay for L1/L2 circuits
-Timing and delay control available through the app
-Hourly, daily, monthly, and yearly tracking of total import/export active energy via the app, with an option
to export the past 30 days of records as an Excel file via email
-Remote ON/OFF control via app; manual ON/OFF control is also available via button if Wi-Fi is unavailable
-Prepayment function: power is automatically cut off when balance is depleted. This function can also
be manually enabled or disabled
-15-minute interval active power curve available for one day
-Voice control for ON/OFF switching
-Event log for alarms and ON/OFF operations viewable in the app
-App supports password protection, carbon emissions tracking, electricity cost settings, and energy reset to zero
-35mm DIN rail mounting design
Wire connection
Outline dimension
Technical Data
Rate-Rated voltage AC
Rated Current / Frequency
WIFI
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
110/220V (L1-L2 90 ~ 300V ) FM2S The meter is designed for L1 and L2 line connection only;
the neutral (N) line does not pass through the meter.
10(100)A / 50Hz or 60Hz±10%
802.11b/g/n
Direct type
<2W/10VA
4000V/25mA for 60s
IP20
-25℃ ~70℃
Accuracy class
Start current
Over current withstand
Executive standard
1% or 0.5%
40mA
30Imax for 0.01s
IEC62053-21 DIN 43880
D1413
Power Management
113 / huyuelectric.com
Power Management
DDS881-4(D1401)
Single Phase Din Rail Type Energy Meter
Application Scope
The meter is designed to measure single-phase, two-wire AC active energy for residential, utility, and industrial
applications. It offers long service life with advantages such as high stability, strong overload capacity, low
power consumption, and compact size.
Basic Function
-Available with mechanical step register (5+1) or LCD display (6+1)
-Bi-directional total active energy measurement; reverse energy is included in total active energy
-For LCD type, energy data is stored in memory and retained for over 15 years after power loss
-Pulse LED indicates meter operation
-Suitable for 35mm DIN rail mounting
Wire connection
Outline dimension
Technical Data
Rate-Rated voltage AC
Rated Current / Frequency
Wiring Method
Power Consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
110V,120V,220V,230,240V (0.8 ~ 1.2Un)
5(60)A, 10(100)A / 50Hz or 60Hz±10%
Direct type
<1W/10VA
4000V/25mA for 60s
IP20
-25℃ ~ 70℃
Accuracy class
Start current
Over current withstand
Executive standard
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
D1401-1
D1401-2
D1401-3
D1401-4
114 / huyuelectric.com
Power Management
DTS881-4 (D3401)
Three Phase Din Rail Type Energy Meter
Application Scope
The meter is used in three phase four wire /three phase three wire /two phase three wire power grid. The meter is
designed to measure AC active energy. All of its functions comply with the relative technical requirement for
class 1 three phase watt hour meter in IEC62053-21. The meter features long service life, high stability, strong
overload capacity, low power consumption, and a compact design.
Basic Function
-LCD display: 6+1 digits (default) or 5+2 digits
-Bi-directional total active energy measurement; reverse energy included in total energy
-Pulse LED indicates meter operation; pulse output is optically isolated
-LED indicators for phase loss and reverse connection
-DIN rail mounting (35 mm) for easy installation
Wire connection
Outline dimension
Technical Data
Rated Voltage AC
Rated Current / Frequency
Connection mode
Power consumption
Withstand Voltage(AC)
IP Rating
Working Temperature
DTS881-4 three phase four wire 3x120/208V, 3x220/380V, 3x230/400V (0.8~1.2Un)
DTS881-4 three phase three wire(two phase three wire) 2x120/208V, 3x220V, 3x380V,
3x400V (0.8~1.2Un)
5A/CT ,1.5(6)A ,5(60)A, 10(100)A / 50Hz or 60Hz±10%
CT or Direct type
<1W/10VA
4000V/25mA for 60s
Ip20
-25℃ ~ 70℃
Accuracy class
Start current
Over current withstand
Standards Compliance
Pulse output
1% or 0.5%
0.004Ib
30Imax for 0.01s
IEC62053-21 DIN 43880
Passive pulse, 80±5 ms
D3401-1
D3401-2 5A/CT
115 / huyuelectric.com
Power Management
DTS881-7 (D3701)
Three Phase Din Rail Type Energy Meter
Application Scope
The meter is used in three phase four wire/three phase three wire /two phase three wire power grid.The meter is
designed to measure AC active energy. It offers long service life with the advantage of high stability, high over
load capability, low power loss and small volume.
Basic Function
-Available with mechanical step register or LCD display
-Bi-directional total active energy measurement; reverse energy is included in total energy
-Pulse LED indicates meter operation; optically isolated pulse output for enhanced reliability
-LED indicators for phase loss and reverse wiring
-For LCD type: energy data stored in memory and retained for over 15 years after power loss
-Compatible with 35 mm DIN rail mounting for quick and easy installation
Technical Data
Rated Voltage Ac
Operating Voltage Range
Rated Current
Frequency
Connection Mode
Display
Accuracy Class
Power Consumption
Start Current
Withstand Voltage(ac)
Impulse Voltage
Ip Rating
Impulse Rate
Pulse Output
Standard Compliance
Working Temperature
Outline Dimension L*M*H
DTS881-7 three phase four wire 3x120/208V, 3x220/380V,3x230/400V, 3x240/415V
DTS881-7 three phase three wire(two phase three wire)
2x120/208V, 2x127/220, 3x220V, 3x380V, 3x400V
0.8~1.2Un
5A/CT, 1.5(6)A, 5(60)A, 10(100)A, or other as required
50Hz or 60Hz
CT type or Direct type
LCD
1.0
<0.5W/5VA/each phase
0.004Ib
4000V/25mA for 60 sec
6kV 1.2 s waveform
IP20
400~6400 imp/kWh
Passive pulse, pulse width is 80土5 ms
DIN 43880, IEC62053-21, IEC62052-11
-30℃~70℃
126x93x65mm
D3701-1
D3701-2 5A/CT
Environment
Operating temperature
Storage temperature
Reference temperature
Relative humidity
Altitude
Warm up time
Mechanical Environment
Electromagnetic Environment
Degree of pollution
-25℃ ~55℃
-40℃ ~80℃
23℃ ±2℃
0 to 95%, non-condensing
Up to 2500m
10s
M1
E2
2
116 / huyuelectric.com
Power Management
Wire connection
Outline dimension
DTS881-7 (D3701)
Three Phase Din Rail Type Energy Meter
117 / huyuelectric.com
Power Management
6L2, 42L6, 85L1, 59L1, 44L1, 99T1
Series current, voltage, frequency, power factor, power
Application Scope
Current, voltage, frequency, power factor, power, series panel meters and other products are suitable for
measuring current, voltage, frequency, phase and power factor in AC and DC circuits.
Main Technical Parameters
Accuracy
Grade 1.5
Grade 2.5
Operating Conditions
-20°C to +40°C
Relative Humidity
25% to 85%
Name
AC ammeter
AC voltmeter
DC ammeter
DC voltmeter
Common Specifications
(Measurement Range)
0A-50A
10A-10kA/5A, 10A-40kA/1A
1V-600V
380V-380kV/100V
50μA-20A
20A-10kA/75mV
1-750V
450V-450kV/1mA,/20mA
1. Basic technical parameters
Mechanical Properties
Withstands acceleration of
30 m/s
Impact frequency of
80-120 times per minute
Two-hour transportation
vibration
Dielectric Strength
AC voltage 50Hz
2kV 1min
Voltage Effect
When the rated
value varies by
±15%, the error in
the indicated
value does not
exceed the basic error.
Working position
Vertical
2. Current and voltage meter measurement range
Notes
Direct connection
Connection via current transformer
Direct connection
Secondary voltage 100V via voltage transformer
Direct connection
External shunt 75mV
Direct connection
Connection via resistor
Name
Frequency meter
Power factor meter
Power meter measurement range
Hz
COSΦ
kW
3. Frequency, power factor (phase) measurement range
Quantity limit
45~55Hz 45~65Hz 55~65Hz 100V 220V 380V
COSΦ=0.5C-1~0.5L 100V 220V 380V 5A
5A-10kV/5A 100V 220V 380V 380V-380kV/100V 5A
Model and Meaning
A represents current, V represents voltage, and Hz represents frequency.
cos represents power factor, kW represents power, and kVar represents reactive power.
Design number
T represents AC electromagnetic system, L represents AC rectifier system,
C represents DC system, and D represents AC motor system.
Instrument type
□ □ □ - □
118 / huyuelectric.com
Power Management
6L2, 42L6, 85L1, 59L1, 44L1, 99T1
Series current, voltage, frequency, power factor, power
5. Measurement range of three-phase reactive power meter
Rated current
(via current transformer
with secondary current of 5A)A
5
7.5
10
15
20
30
40
50
75
100
150
200
300
400
600
750
800
1K
1.5K
2K
3K
4K
5K
6K
7.5K
10K
Measuring
range
kVar
mVar
DC access
100
0.6
1
1.2
2
2.5
4
5
6
10
12
20
25
40
50
80
100
100
120
200
250
400
500
600
800
1
1.2
220
1.5
2.5
3
5
6
10
12
15
25
30
50
60
100
120
200
250
250
300
500
600
1
1.2
1.5
2
2.5
3
Accessed via voltage transformer (secondary voltage is 100V)
Rated voltage (V)
380
2.5
4
5
8
10
15
20
25
40
50
80
100
150
200
300
400
400
500
800
1
1.5
2
2.5
3
4
5
3K
20
30
40
60
80
120
150
200
300
400
600
800
1.2
1.5
2.5
3
3
4
6
8
12
15
20
25
30
40
6K
40
60
80
120
150
250
300
400
600
800
1.2
1.5
2.5
3
5
6
6
8
12
15
25
30
40
50
60
80
10K
60
100
120
200
250
400
500
600
1
1.2
2
2.5
4
5
8
10
10
12
20
25
40
50
60
80
100
120
15K
100
150
200
300
400
600
800
1
1.5
2
3
4
6
8
12
15
15
20
30
40
60
80
100
120
150
200
35K
250
400
500
800
1
1.5
2
2.5
4
5
8
10
15
20
30
40
40
50
80
100
150
200
250
300
400
500
110K
800
1.2
1.5
2.5
3
5
6
8
12
15
25
30
50
60
100
120
120
150
250
300
500
600
800
1000
1200
1500
220K
1.5
2.5
3
5
6
10
12
15
25
30
50
60
100
120
200
250
250
300
500
600
1000
1200
1500
2000
2500
3000
380K
2.5
4
5
8
10
15
20
25
40
50
80
100
150
200
300
400
400
500
800
1000
1500
2000
2500
3000
4000
5000
35
80
21.5
7.5
100
70
7.5
56
14.5
1.5
65
17.5
1.5
4. Measurement range of three-phase power meter
Rated current
(via current transformer
with secondary current of 5A)A
5
7.5
10
15
20
30
40
50
75
100
150
200
300
400
600
750
800
1K
1.5K
2K
3K
4K
5K
6K
7.5K
10K
Measuring
range
KW
MW
DC access
100
0.8
1.2
1.5
2.5
3
5
6
8
12
15
25
30
50
60
100
120
120
150
250
300
500
600
800
1
1.2
1.5
200
2
3
4
6
8
12
15
20
30
40
60
80
120
150
250
300
300
400
600
800
1.2
1.5
2
2.5
3
4
Accessed via voltage transformer (secondary voltage is 100V)
Rated voltage (V)
380
3
5
6
10
12
20
25
30
50
60
100
120
200
250
400
500
500
600
1
1.2
2
2.5
3
4
5
6
3K
25
40
50
80
100
150
200
250
400
500
800
1
1.5
2
3
4
4
5
8
10
15
20
25
30
40
50
6K
50
80
100
150
200
300
400
500
800
1
1.5
2
3
4
6
8
8
10
15
20
30
40
50
60
80
100
10K
80
120
150
250
300
500
600
800
1.2
1.5
2.5
3
5
6
10
12
12
15
25
30
50
60
80
100
120
150
15K
120
200
250
400
500
800
1
1.2
2
2.5
4
5
8
10
15
20
20
25
40
50
80
100
120
150
200
250
35K
300
500
600
1.2
2
2
2.5
3
5
6
10
12
20
25
40
50
50
60
100
120
200
250
300
400
500
600
110K
1
1.5
2
3
4
6
8
10
15
20
30
40
60
80
120
150
150
200
300
400
600
800
1000
1200
1500
2000
220K
2
3
4
6
8
12
15
20
30
40
60
80
120
150
250
300
300
400
600
800
1200
1500
2000
2500
3000
3500
380K
3
5
6
10
12
20
25
30
50
60
100
120
200
250
400
500
500
600
1000
1200
2000
2500
3000
4000
5000
6000
119 / huyuelectric.com
Power Management
Appearance and Installation Dimensions
1. 42L6, 42C3 type plate meter
120 13 112
68
35
23
2. 6L2, 6C2 type plate meter
80 10
85.5
77
H (see table)
Models
6L(C)2-A, 6L(C)2-V, 6L2-HZ
6L2-COSφ
6L2-KW, 6L2-KVAR
H Table
H
70
85
102
3. 44L1, 44C2 type plate 4. 59L1, 59C2 type plate meter
100
80
49 14 Φ58.5
70
2×M4
21.5
7.5
120 49 14
100
Φ78.5
90±0.25
70 4×M4
7.5
6L2, 42L6, 85L1, 59L1, 44L1, 99T1
Series current, voltage, frequency, power factor, power
5. 85L1, 85C1, 85L17, 85C17 plate
56
64 51 11 Φ49
52
2×M3
14.5
1.5
6. 69L9, 69C9, 69L17, 69C17 plate
65
80 50 11 Φ59
64±0.5
2×M3
17.5
1.5
7. 72L1, 72C1, 72T1 plate meter 8. 99L1, 99C1, 99T1 plate meter
□72 48.5
5
59.5
66.5
66 □48 40.5
56
45max
5
120 / huyuelectric.com
Accuracy
grade
Application Scope
Main Technical Parameters
BH-0.66
Series Current Transformer
The BH-0.66 series current transformers are designed for indoor use and are suitable for current and energy
measurement and relay protection in AC circuits with a rated voltage of 660V and a rated frequency of 50Hz.
This product complies with GB 20840.1 and GB 20840.2.
Model
BH-0.66 20Φ
BH-0.66 30 Type I
BH-0.66 30 Type IB
BH-0.66 40 Type I
BH-0.66 50 Type
Rated Current
Ratio (A)
75/5
100/5
100/5
150/5
200/5
250/5
300/5
400/5
500/5
50/5
75/5
100/5
150/5
200/5
250/5
300/5
400/5
150/5
200/5
250/5
300/5
400/5
500/5
600/5
750/5
800/5
1000/5
1200/5
1500/5
200/5
300/5
400/5
500/5
600/5
800/5
1000/5
1200/5
1500/5
0.66
Rated voltage
(kV)
0.5
1.5S
0.2
0.2S
Power Management
1. Insulation Requirements: Primary winding to secondary winding and ground, and secondary winding to ground,
withstand power frequency voltage of 3kW for 1 minute. Insulation resistance ≥ 10MΩ.
2. Rated secondary current 5A. Rated primary current, rated capacity, and accuracy are shown in the table below.
Rated load
(VA)
2.5
2.5
2.5
2.5
5
5
5
5
5
2.5
2.5
2.5
2.5
5
5
5
5
2.5
5
5
5
5
10
10
10
10
15
20
20
5
5
5
10
10
10
15
20
20
0.2
0.2S
0.5
0.5S
80
11
80
11
98
21
31
98
11
Model and Meaning
Category
Window Width
Rated Voltage (kV)
Current Transformer
Enclosed
B H - 0.66 □ Ⅰ
121 / huyuelectric.com
Power Management
Accuracy
grade
Model
BH-0.66 60 Type I
BH-0.66 80 Type I
BH-0.66 100 Type I
BH-0.66 120 Type I
Rated Current
Ratio (A)
300/5
400/5
500/5
600/5
800/5
1000/5
1200/5
1500/5
2000/5
600/5
800/5
1000/5
1200/5
1500/5
2000/5
2500/5
1000/5
1200/5
1500/5
2000/5
2500/5
3000/5
4000/5
1500/5
2000/5
2500/5
3000/5
4000/5
5000/5
0.66
Rated voltage
(kV)
Rated load
(VA)
5
5
10
10
10
15
20
20
20
10
10
15
20
20
20
20
15
20
20
20
30
40
40
20
20
30
40
40
40
0.2
0.2S
0.5
0.5S
BH-0.66
Series Current Transformer
1. BH-20
Appearance and Installation Dimensions
Nameplate
S1 S2
38
P1
61
Φ22
80
34
2. BH-30
S1 S2
Nameplate
30.5 33
P1
32
Φ23
11
60.5
80
3、BH-30IB 4、BH-40
S1 S2
Nameplate
42
31.5
P1
44
11
75
98
21.5
11
21
31
S1 S2
40
98
Nameplate
P1
Φ31
11
42
43.5
75
122 / huyuelectric.com
BH-0.66
Series Current Transformer
Power Management
Appearance and Installation Dimensions
5. BH-50 6. BH-60
7、BH-80 8、BH-100
9、BH-120
S1 S2
98
Nameplate
P1
Φ37
16
51
82
40
S1 S2
40
126
Nameplate
P1
Φ46
21
50
62
102
S1 S2
46
30.5
Nameplate
P1
Φ52
11
50
60.5
81.5
138
118
S1 S2
46
145
154
Nameplate
22
P1
50
62
82
102
32
42
Φ62
170
S1 S2
46
190
Nameplate
P1
50
126
190
36
136
Φ62
123 / huyuelectric.com
98
16
126
21
30.5
11
138
4
1
6
54
22
32
42
46
36
136
Power Management
BH(SDH)-0.66 II
Series Current Transformer
Accuracy
grade
Application Scope
Main Technical Parameters
BH (SDH) -0.66 series current transformers are used indoors and are suitable for current and energy
measurement and relay protection in AC circuits with a rated voltage of 660V and below and a rated frequency of
50Hz. The product complies with: GB/T 20840.1 GB/T 20840.2
Model
BH-0.66 30 Type II
BH-0.66 40 Type II
BH-0.66 50 Type II
(SDH-0.66 50 II)
BH-0.66 60 Type II
(SDH-0.66 60Ⅱ)
BH-0.66 80 Type II
(SDH-0.66 80Ⅱ)
Rated Current
Ratio (A)
150/5
200/5
250/5
300/5
400/5
500/5
150/5
200/5
250/5
300/5
400/5
500/5
600/5
750/5
800/5
1000/5
1200/5
1500/5
200/5
300/5
400/5
500/5
600/5
800/5
1000/5
1200/5
1500/5
300/5
400/5
500/5
600/5
800/5
1000/5
1200/5
1500/5
2000/5
600/5
800/5
1000/5
1200/5
1500/5
2000/5
2500/5
0.66
Rated voltage
(kV)
0.5
1.5S
0.2
0.2S
Rated load
(VA)
2.5
2.5
5
5
5
5
2.5
5
5
5
5
10
10
10
10
15
20
20
5
5
5
10
10
10
15
20
20
5
5
10
10
10
15
20
20
20
10
10
15
20
20
20
20
0.2
0.2S
0.5
0.5S
Model and Meaning
Category
Window Width
Rated Voltage (kV)
Current Transformer
SD H - 0.66 □ Ⅱ
Category
Window Width
Rated Voltage (kV)
Current Transformer
Enclosed
B H - 0.66 □ Ⅱ
For GCS Low-Voltage
Withdrawable Switchgear
124 / huyuelectric.com
Power Management
BH(SDH)-0.66 II
Series Current Transformer
Accuracy
grade
Model
BH-0.66 100 Type II
(SDH-0.66 100Ⅱ)
BH-0.66 120 Type II
(SDH-0.66 120Ⅱ)
BH-0.66 130 Type II
(SDH-0.66 130Ⅱ)
BH-0.66 150 Type II
(SDH-0.66 150Ⅱ)
Rated Current
Ratio (A)
1000/5
1200/5
1500/5
2000/5
2500/5
3000/5
4000/5
1500/5
2000/5
2500/5
3000/5
4000/5
5000/5
1000/5
1200/5
1500/5
2000/5
2500/5
3000/5
4000/5
5000/5
1500/5
2000/5
2500/5
3000/5
4000/5
5000/5
0.66
Rated voltage
(kV)
Rated load
(VA)
15
20
20
20
30
40
40
20
20
30
40
40
40
5
10
10
20
20
20
20
20
20
20
20
40
40
40
0.2
0.2S
0.5
0.5S
Appearance and Installation Dimensions
H
P1
e
f
W
a
D
a
33
42
52
62
83
102
122
132
153
Models
BH-0.66 30 II
BH-0.66 40 II
BH-0.66 50 II
BH-0.66 60 II
BH-0.66 80 II
BH-0.66 100 II
BH-0.66 120 II
BH-0.66 130 II
BH-0.66 150 II
H
98
104
106
110
118
120
154
160
160
e
31
31
31
31.5
32.5
32
52
61.5
55
W
65
78.5
87
102
122
140
169
179
200
D
44
47
47
47
47
50
50
47
50
f
32
45
54
52.5
60
74
54
48.5
65
P
11
1
47±0.32
86
45±0.47
54
P
21
11
1
31
54±0.32
92
59±0.47
68
125 / huyuelectric.com
H
e
Power Management
BH-0.66III
Series Current Transformer
Application Scope The BH-0.66III series current transformers are designed for indoor use and are suitable for current and energy measurement and relay protection in AC circuits with a rated voltage of 660V or less and a rated frequency of 50Hz or 60Hz. This product complies with: GB20840.1 GB20840.2 Normal Operating Conditions 1. Installation Location: Indoors 2. Ambient Temperature: Minimum -5°C, Maximum +40°C 3. Ambient Humidity: Relative Humidity not exceeding 80% 4. Altitude: Not exceeding 1000m 5. Atmospheric Conditions: No contaminants, corrosive media, or explosive media that could seriously affect the
transformer's insulation
Structural Characteristics The transformer's core is annular or rectangular, with the secondary winding evenly distributed around the core's circumference. The transformer's insulation is made of flame-retardant plastic. A window is provided in the center of the transformer for the primary busbar to pass through. The product's output terminals are marked with P1 for the primary input and P2 for the output, and S1 and S2 for the secondary output terminals. When the primary current flows in through P1 and out through P2, the secondary current flows out through S1 and then flows through the external circuit into S2, resulting in reduced polarity. The core is formed from wound silicon steel sheets, eliminating air gaps and ensuring high magnetic properties. The secondary winding is evenly wound, minimizing magnetic flux leakage, resulting in stable performance, lightweight, and easy installation.
Rated primary current (A)
150-5000
Main Technical Parameters
Rated voltage (V)
660
Rated frequency (Hz)
50
Rated secondary current (A) 5
1. Basic technical parameters
2. Insulation Level: Secondary winding insulation resistance to ground ≥ 10MΩ, short-term power frequency withstand
voltage 3kV for 1 minute
3. Rated Load and Accuracy: cosΦ = 0.8 hysteresis
Accuracy
0.5
0.5S
0.2
Rated primary current (A)
150-250
300-400
500-800
1200-1500
2000-5000
Rated load (VA) 5
10
10
20
40
Appearance and Installation Dimensions 1、BH-0.66 20III 22 P 111 S1 S2 47±0.32 86 41±0.32 64
Φ20
45±0.47
54
2、BH-0.66 30III
11
P
11
1
S1 S2
21
31
2131
54±0.32
49±0.32
92
59±0.47
68
Model and Meaning
B H - 0.66 □ Ⅲ
Classification
Window Width
Rated Voltage (kV)
Current Transformer
Enclosed
126 / huyuelectric.com
Power Management
BH-0.66III
Series Current Transformer
3、BH-0.66 40III 4、BH-0.66 50III
59±0.47
68
11
P
11
1
S1 S2
21
52
41
52
65±0.43
61±0.43
88
107
21
41
11
P
11
1
S1 S2
31
42
31
42
51
59±0.2
84
59±0.47
68
5、BH-0.66 60III 6、BH-0.66 80III
59±0.47
68
62
34
83±0.26
112
S1 S2
90±0.26
123
P1
59±0.47
68
82
54
109±0.5
132
S1 S2
105±0.57
152
P1
7、BH-0.66 100III 6、BH-0.66 120III
59±0.47
68
102
53
108±0.5
152
S1 S2
128±0.64
150
P1
147±0.72
62±0.47
70
122
53
109±0.57
174
S1 S2
151
P1
108
63
10
117
69
10
127 / huyuelectric.com
Power Management
LMZ(J)1-0.5
Series Current Transformer
Application Scope
The LMZ(J)1-0.5 series current transformers are primarily designed for indoor use and are suitable for current
and energy measurement or relay protection in AC circuits with a rated voltage of 0.5 kV or less and a rated
frequency of 50 Hz. These are cast-type current transformers and are installed using a baseplate mounting
method.
They comply with GB/T20840.1 and GB/T20840.2.
Normal Operating Conditions
1. Installation Location: Indoors
2. Ambient Temperature: Minimum -5°C, Maximum +40°C
3. Humidity: Average relative humidity within 24 hours not exceeding 95%, and average relative humidity within
one month not exceeding 90%
4. Altitude: Not exceeding 1000m
5. Ambient air free of significant dust, smoke, corrosive gases, steam, or salt contamination
6. The installation site must be free of severe vibration or turbulence
Primary winding
nominal voltage (kV)
0.5
Main Technical Parameters
Rated primary
current (A)
Rated secondary
current (A)
5
Accuracy
0.2、0.2S、
0.5、0.5S
1. Basic technical parameters
Primary Current (A)
150, 200, 250, 300
400, 500, 600
750, 800
1000, 1200, 1500
2000, 2500, 3000
Appearance and Installation Dimensions
1. LMZ (J) 1-0.5 (rated primary current 150, 200, 250, 300)
59±0.47
68
P
21
11
1
52
65±0.43
107
41
P
31
11
1
42
51
59±0.47
68
59±0.47
68
34
83±0.26
123
59±0.47
68
54
109±0.5
152
59±0.47
68
53
108±0.5
150
62±0.47
70
53
109±0.57
151
Rated
frequency
150, 200, 250, 300, 400, 500, 600, 750 50Hz
800, 1000, 1200, 1500, 2000, 2500, 3000
H
67.5
72
71.5
76.5
90
H
117
125
120
139
165
L
86
86
98
119
152
A
110
110
128
153
185
D
31
42
82
103
154
D
90
97
140
177
230
B
47
48
51
50
50
C
36
36
-
-
-
A
10
10
24
33
35
B
36
52
37
49
70
S1 S2
85 48
110
108
63
32
P1
10
Φ29
2. LMZ (J) 1-0.5S/0.2 pole (rated primary current 150, 200, 250, 300)
S1 S2
62
85
110
117
69
32
P1
10
Φ29
Model and Meaning
Rated voltage (kV)
Design number
Enlarged capacity
Cast insulation type
Busbar type
Current transformer
L M Z (J) 1 - 0.5
128 / huyuelectric.com
Power Management
LMZ(J)1-0.5
Series Current Transformer
3. LMZ (J) 1-0.5 (rated primary current 400, 500, 600)
4. LMZ (J) 1-0.5 (rated primary current 750, 800)
5. LMZ (J) 1-0.5 (rated primary current 1000, 1200, 1500)
6. LMZ (J) 1-0.5 (rated primary current 2000, 2500, 3000)
S1 S2
85
110
124
72
P1
52
10
Φ45
48
136
P1
S1 S2
82
52
100
130
73
51
S1 S2
160
P1
102
52
120
147
85
51
S1 S2
190
P1
130
62
150
165
95
52
111
20
121
24
119
30
125
36
129 / huyuelectric.com
Power Management
LMZ(J)1-0.66
Series Current Transformer
Application Scope
The LMZ(J)1-0.66 series current transformers are primarily designed for indoor use and are suitable for current
and energy measurement or relay protection in AC circuits with a rated voltage of 0.66 kV or less and a rated
frequency of 50 Hz. These are cast-type current transformers and are installed using the busbar mounting
method.
They comply with GB/T20840.1 and GB/T20840.2.
Normal Operating Conditions
1. Ambient Temperature: Minimum -5°C, Maximum +40°C.
2. Humidity: The average relative humidity measured over a 24-hour period shall not exceed 95%, and the
average relative humidity over a month shall not exceed 90%.
3. Altitude: Not exceeding 1000 meters.
4. The ambient air must be free of significant dust, smoke, corrosive gases, vapors, or salt contamination.
5. The installation site must be free of severe vibration or turbulence.
Primary winding
nominal voltage (kV)
0.66
Main Technical Parameters
Rated primary
current (A)
Rated secondary
current (A)
5
Accuracy
0.5/0.2/
0.2S/0.5S
Appearance and Installation Dimensions
1. LMZ (J) 1-0.66 (rated primary current 100, 150,
200, 250, 300)
Rated
frequency
100, 150, 200, 250, 300, 400, 500, 600, 750, 800, 1000 50Hz
1200, 1500, 2000, 2500, 3000, 4000, 5000, 6000
124
72
10
52
130
73
52
147
85
62
165
95
S1 S2
93
111
P1
34
20
85
56 45
2. LMZ (J) 1-0.66 (rated primary current 400, 500, 600,
750, 800, 1000)
56 45
S1 S2
101
121
P1
53
24
85
3. LMZ (J) 1-0.66 (rated primary current 750, 800, 1000,
1200, 1500, 2000)
4. LMZ (J) 1-0.66 (rated primary current 2000, 2500, 3000,
4000, 5000, 6000)
56 45
S1 S2
150 85
119
P1
104
30
S1 S2
85
191
125
P1
142
36
56 45
72
Model and Meaning
Rated voltage (kV)
Design number
Increased capacity
Cast insulation
Busbar type
Current transformer
L M Z (J) 1 - 0.66
130 / huyuelectric.com
Power Management
LFZ1D-GHY3, LMZ(1D-4D)-GHY3
Series Current Transformer
Application Scope
This type of current transformer is cast in resin and is used indoors for current and energy metering, power
measurement, and relay protection in AC 50Hz circuits with a rated voltage of 400V or less.
This product complies with: GB/T20840.1, GB/T20840.2, and Q/GDW1572.
Normal Operating Conditions
1. Installation Location: Indoors
2. Ambient Air Temperature: -5°C to +40°C, with an average temperature not exceeding +35°C.
3. Ambient Humidity: Relative Humidity ≤ 85%.
4. Altitude: Not exceeding 1000 meters.
5. Atmospheric Conditions: Free from contaminants or corrosive agents that could seriously affect the
transformer's insulation.
Main Technical Parameters
Multiplication
0.55 factor
0.2S
1. Accuracy: 0.2S, 0.5S.
2. Rated voltage: 400V
3. Rated frequency: 50Hz
4. Rated primary current, rated secondary current, rated load, and accuracy are shown in Table 2.
5. Insulation performance: The primary winding must withstand a short-term power frequency withstand voltage
of 3kV from the primary winding to the secondary winding and ground, and from the secondary winding to
ground.
6. Insulation resistance measurement: The insulation resistance from the primary winding to the secondary
winding and ground must be ≥ 100MΩ.
7. The current error and phase difference of the transformer must not exceed the limits listed in Table 1.
Table 1 Basic error limits of current transformers
Accuracy
Level
Ratio difference (±)
Percentage value at rated current
1
1.2
0.67
5
0.45
0.27
20
0.3
0.12
100
0.3
0.12
120
0.3
0.12
Multiplication
factor
Percentage value at rated current
Phase difference (±)
1
72
26
5
27
11
20
18
6
100
18
6
120
18
6
Structural Characteristics
The transformer core uses an iron-based nanocrystalline alloy strip with high initial magnetic conductivity
efficiency and low saturation magnetic density as the 0.2S grade magnetic conductive material. The secondary
winding is evenly wound. The middle window is made of engineering plastic, which greatly enhances the
insulation of the product. At the same time, it serves as the positioning of the secondary coil, enhancing the
appearance and insulation strength of the product. The middle window allows you to see through the primary
busbar or wound soft cable.
Installation, Use and Maintenance
1. The instrument transformer can be installed vertically or horizontally.
2. The primary current of the instrument transformer should flow from P1 to the other terminal, and the secondary
current should flow from S1 to S2 through an external circuit. The instrument transformer has a negative
polarity. The copper wire connecting the secondary terminal to the instrument or relay should have a
cross-section of no less than 2.5 mm².
3. When current is flowing through the primary winding, the secondary winding must not be open-circuited to
prevent high voltage.
4. During long-term storage, the instrument transformer should be placed in an environment with an ambient
temperature of -25°C to +40°C, in a well-ventilated area free of corrosive gases and media. If stored for more
than one year, insulation resistance and power frequency withstand voltage tests should be performed. If any
changes are observed, the instrument transformer should be dried.
118
78
36
8.5
148
67
74
36
8.5
148
67
11
54
42
152
71
30
74
36
8.5
148
67
Model and Meaning
Design Number
Low-voltage type for power metering
Structural number, numbered according to the specified drawing
Z - cast resin insulation
M - busbar type; F - multi-turn type; W - outdoor type
Current transformer
L □□□ D-□
131 / huyuelectric.com
Power Management
Appearance and Installation Dimensions
Accuracy
Grade
0.2s, 0.5s
0.2s, 0.5s
0.2s, 0.5s
0.2s, 0.5s
0.2s, 0.5s
Rated primary
current (A)
10-60
75-150
200-500
600-800
1000-1500
Power
factor
0.8
0.8
0.8
0.8
0.8
Notes
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Models and
Specifications
LFZ1D-GHY3
LMZ1D-GHY3
LMZ2D-GHY3
LMZ3D-GHY3
LMZ4D-GHY3
Rated secondary
current (A)
5
5
5
5
5
Rated secondary
load (VA)
5/2.5
5/2.5
5/2.5
10/3.75
10/3.75
Figure 1 LFZ1D-GHY3
LFZ1D-GHY3, LMZ(1D-4D)-GHY3
Series Current Transformer
25
11
118
78
36
8.5
M向
S2
S1
2xφ6
36
54
148
67
M
85
100
74
S2
S1
36
8.5
M向
2xφ6
36
54
148
67
85
110
φ30
P1
150/5
34
11
54
42
S2
S1
M向
152
71
90
140
M
P1
750/5
2xφ6
84
30
54
Figure 2 LMZ1D-GHY3
Figure 3 LMZ2D-GHY3 Figure 4 LMZ3D-GHY3
74
S2
S1
36
8.5
M向
148
67
85
110
36
74
2xφ6
φ30
P1
150/5
34
132 / huyuelectric.com
Power Management
LFZ1D-GHY3, LMZ(1D-4D)-GHY3
Series Current Transformer
Figure 5 LMZ4D-GHY3
11
54
42
S2
S1
M向
164
172
81
90
140
P1
1000/5
2xφ6
104
50
54
M
133 / huyuelectric.com
GTFP-200A/4J
GTFP-200AN/4J
GTFP-200AN/5J
GTFP-125AN/7J
Outline Dimensions
H
412
412
498
429
429
429
360
Features
Specification
GTFP-200
Square Meter Sockets
Durable: Made from 1.2–1.5 mm galvanized steel with a gray powder-coated finish for corrosion resistance. Voltage Rating: Supports up to 600V AC. Spacious Design: Provides ample room for easy wiring. Knockouts Available: Knockouts on the sides, back, and bottom for flexible installation. Easy Connections: Features lay-in terminals with pressure plates. Conduit Sizes: Compatible with 1\" to 2.5\" conduit hubs.
Product Number
GTFP-200A/4J
GTFP-200A/5J
GTFP-200A/7J
GTFP-200AN/4J
GTFP-200AN/5J
GTFP-200AN/7J
GTFP-20AN/13J
Description
1 Phase, 200A.4 jaw, ring type
1 Phase, 200A, 5 jaw, ring type
3 Phase, 200A, 7 jaw, ring type
1 Phase, 200A , 4 jaw, ringless type
1 Phase, 200A, 5 jaw, ringless type
3 Phase, 200A, 7 jaw, ringless type
3 Phase, 20A.13 jaw, ringless type
W
222
222
235
208
208
208
210
D
134
134
136
130
130
130
95
Outline Dimensions
GTFP-200AN/7J GTFP-200A/7J
Power Management
11
54
42
172
81
50
134 / huyuelectric.com
Power Management
GTFP-200
Square Meter Sockets
GTFP-20AN/13J GTFP-200ARN/4J
GTFP-200AN/4J GTFP-200ADN/7J
Replacement Block Assemblies
PB200N-4J
Use on GTFP-200AN/4J, GTFP-200A/7J
PB200-4J
Use on GTFP-200A/4J
PB200N-5J
Use on GTFP-200AN/5J
135 / huyuelectric.com
GYFD-D-125AC
Outline Dimensions
H
465
465
510
465
Features
Specification
GYFD
Combination Meter Sockets
Standard meter sockets are constructed from 1.2-1.5 mm galvanized steel sheets and finished with a baked gray
polyester powder coating for enhanced corrosion resistance.
◆ Suitable for single-phase systems with a service voltage of 120/240VAC.
◆ Ample gutter space allows for easy and organized wiring.
◆ Convenient knockouts on the sides, back, and bottom for flexible conduit entry.
◆ Lay-in type terminals with pressure plates ensure quick and secure connections.
◆ Designed to accommodate conduit hubs ranging from 1“to2-1/2” .
◆ Compatible with GE-type circuit breakers.
Product Number
GYFD-D-125AC
GYFD-D-125A
GCHM2100MR2 125A
GYFD-S-125A
Description
1 Phase, 125A ,4 jaw, ring type
1 Phase, 125A ,4 jaw, ring type
1 Phase, 125A ,4 jaw, ring type
1 Phase, 125A ,4 jaw, ring type
D
114
114
104
104
Matching
Breaker
THQL 2P
THQL 2P
THQL 2P
THQL 2P
Outline Dimensions
PB-GCHM2100MR2 125A PB-GYFD-D-125A
GYFD-D-125A
GYFD-D-125AL
W
188
188
188
188
Power Management
136 / huyuelectric.com
Power Management
Stainless Steel Sealing Ring
GYFD
Combination Meter Sockets
GCHM2100MR2 125A GCHM2100MR2 125A GTFM-125AL/2T
GSR-1 GSR-2 GSR-3 GSR-4
Product Number
GSR-1
GSR-2
GSR-3
GSR-4
Description
Slip lock type
Screw type
Screw type
Screw type
Thickness
0.35mm
0.35mm
0.35mm
1.5mm
1\"
1-1/2\"
1-1/4\"
2\"
Product Number
HUB- 1\"
HUB- 1-1/4\"
HUB-1-1/2”
HUB- 2\"
Description
1\"
1-1/4\"
1-1/2\"
2\"
HUB
137 / huyuelectric.com
Power Management
HUJX-F
Series Stainless Steel Metering Box
HY □□
Series Electricity Metering Box
Application Scope
The HYPX, HYSX, and HYBX series electricity meter boxes (hereinafter referred to as \"meter boxes\") are suitable for
measuring energy in indoor power distribution circuits operating at 50 Hz, with a rated operating voltage of
400/230 V AC and a rated current up to 250 A. Circuit breakers can be installed on incoming or outgoing lines for
overload, leakage, and short-circuit protection.
The HYPX, HYSX, and HYBX series electricity meter boxes comply with national standards: GB 7251.1, GB 7251.3, and
Q/GDW 11008.
Normal Operating Conditions
1. The ambient air temperature must not exceed +60°C, with an average temperature not exceeding +35°C and a
minimum stable temperature not below -25°C.
2. At a maximum temperature of 40°C, the relative humidity must not exceed 75%. At lower temperatures, a higher
relative humidity is permitted.
3. Pollution Degree must not exceed 2.
4. The altitude must not exceed 2000 meters. 3.5 The meter box should be installed vertically in a place without
obvious shaking or vibration, and should be protected from direct sunlight and rain and snow.
Main Technical Parameters
1. Meter boxes are available in polycarbonate (PC) and ABS non-metallic, SMC fiberglass reinforced plastic
(SMC), and stainless steel metal versions. Customized with molded case circuit breakers, electricity meters,
and miniature circuit breakers, these are available.
2. Meter boxes are available in surface-mounted or concealed-mount versions, with enclosure protection ratings
of IP44 (IP20C for the operating surface).
3. A dedicated junction box is used within the meter box for simple wiring and reliable operation.
4. The meter box's incoming wiring can be single-phase or three-phase, with a rated operating voltage of
400/230V AC and a rated operating current of up to 250A.
5. Rated short-time withstand current (ICW): HYPX: 6kA, HYSX: 9kA.
Use and Maintenance
1. If the user installs their own electricity meter in the meter box, it must comply with national standards and be
calibrated. The wiring terminals must be securely fastened.
2. If the meter box is used in areas prone to thunderstorms, lightning protection measures should be implemented
at the installation site to reduce the risk of component damage from lightning strikes.
3. The meter box casing should always be kept clean and dry to minimize dust intrusion.
Application Scope
Application – For indoor power distribution circuits (50 Hz), rated voltage 380/220 V AC, rated current up to 315 A.
Supports installation of circuit breakers on incoming or outgoing lines for overload, leakage, and short-circuit
protection.
Standards – Complies with GB 7251.1 and GB 7251.3.
Normal Operating Conditions
1. Ambient temperature: max 40°C, average ≤ 35°C, min stable ≥-5°C.
2. Relative humidity: ≤ 50% at 40°C; higher humidity allowed at lower temperatures.
3. No persistent conductive contaminants (e.g., conductive dust).
4. Install vertically, away from strong vibration, direct sunlight, rain, and snow.
Main Technical Parameters
1. Construction – Stainless steel enclosure, equipped with molded case circuit breaker (MCCB),
energy meter, and miniature circuit breaker (MCB) as required.
2. Mounting Options – Available in surface-mounted or concealed-mounted versions.
Enclosure rating: IP40; operating surface rating: IP20C.
3. Wiring – Includes a dedicated junction box for simple wiring and reliable operation.
4. Electrical Parameters – Supports single-phase or three-phase wiring; rated voltage 380/220 V AC,
rated current up to 315 A.
Operation and Maintenance
1. If the user installs their own electricity meter in the meter box, it must comply with national standards and be
calibrated. The wiring terminals must be securely tightened.
2. If the meter box is used in areas prone to thunderstorms, lightning protection measures should be implemented
at the installation site to reduce the risk of component damage due to lightning strikes.
3. The meter box casing should always be kept clean and dry to minimize dust intrusion.
Model and Meaning
PX: PC+ABS non-metallic
metering box
SX: SMC non-metallic
metering box
BX: Stainless steel metal
metering box
Company Code
HY □
Model and Meaning
F: Stainless steel housing
Electricity meter box
Company code
HU JX - □
138 / huyuelectric.com
ADD:Wenzhou Bridge Industrial Zone,Yueqing,Zhejiang,China.
Unlock More: Scan Now
WhatsApp/MOB:0086-135 0655 2522 Email:austin@huyu.com.cn huyuelectric.com
Due to the continuous updating of product technology, all data should be based on the latest confirmation of the company's technical departments.
HUYUYB250807