Introduction
EBSl series products have alarge flow capacity, with maximum discharge current of 60-lookA for single pole module, and are suitable for B-level protection in low-voltage distribution systems. Different combination wiring methods are chosen based on different power supply systems.
High energy varistor, nanosecond response speed;
Equipped with overheating and overcurrent protection;
Local indicationl) and remote alarm contact2);
1) It visually displays the working status of the protector on the protector
2) It provides contacts for remote monitoring of protector status, which requires external wiring.
Pluggable in charged condition, module replaceable in case of failure.
Performance parameter
| Model | EBS1-60voltage limited type | EBS1-80voltage limited type | EBS1-100voltage limited type |
| Maximum continuous operating voltage1) Uc(V) | 385 | 385 | 385 |
| Nominal discharge current In 8/20μs(kA) | 30 | 40 | 50 |
| Maximum discharge current 8/20μs(kA) | 60 | 80 | 100 |
| Voltage protection level Up(kV) | 2.0 | 2.5 | 3.0 |
| Back-up protective device (fuse) | 63 | 100 | 125 |
| Local failure indication | Window in green: normal, window in red: failure | ||
| Remote alarm contact | A normally open contact | ||
| Wiring capacity | 1.5~35mm2 | ||
| Overall dimension | 90×27×62 | ||
| Shell material | It complies with UL 94V-0 | ||
| Shell protection class | IP20 | ||
| Installation mode It is installed with TH35-7.5 (DIN35mm) standard guide rail | |||
Model and specification
| No. Model | Number ofpoles | Uc(M) | In(kA) | Imax(kA) | Up(kV) | Usage |
| 1 EBS1-60/3-320 | 3 | 320 | 30 | 60 | 2.0 | For TN-C, IT and TN-S system |
| 2 EBS1-80/3-320 | 3 | 320 | 40 | 80 | 2.0 | |
| 3 EBS1-100/3-320 | 3 | 320 | 60 | 100 | 2.5 | |
| 4 EBS1-60/3N-320 | 3 | 320 | 30 | 60 | 2.0 | $\mathsf { F o r } ^ { * } 3 + 1 ^ { * }$ combination and full-module combination |
| 5 EBS1-80/3N-320 | 3 | 320 | 40 | 80 | 2.0 | |
| 6 EBS1-100/3N-320 | 3 | 320 | 60 | 100 | 2.5 | |
| 7 EBS1-60/4-320 | 4 | 320 | 30 | 60 | 2.0 | For three-phase system of TN-S system |
| 8 EBS1-80/4-320 | 4 | 320 | 40 | 80 | 2.0 | |
| 9 EBS1-100/4-320 | 4 | 320 | 60 | 100 | 2.5 | |
| 10 EBS1-60/3N-385 | 3 | 385 | 30 | 60 | 2.0 | $\mathsf { F o r } ^ { * } 3 + 1 ^ { * }$ combination |
| 11 EBS1-80/3N-385 | 3 | 385 | 40 | 80 | 2.5 | |
| 12 EBS1-100/3N-385 | 3 | 385 | 60 | 100 | 3.0 | |
| 13 EBS1-60/4-385 | 4 | 385 | 30 | 60 | 2.0 | For TT system |
| 14 EBS1-80/4-385 | 4 | 385 | 40 | 80 | 2.5 | |
| 15 EBS1-100/4-385 | 4 | 385 | 50 | 100 | 3.0 |
Overall dimension and schematic diagram
Wiring diagram for remote communication termina
Remote sound alarm
1。
Remote alarm light turns on
2°-
3-220V
20
3-220V
Installation schematic diagram
Scope of application
HD series and HS series knife switches (hereinafter referred to as switches) are suitable for complete sets of power distribution equipment with frequency of AC 50Hz,rated operatingvoltage up to380V and rated operating current up to 3000A. They are used as infrequent manual connection and disconnection circuits or as disconnectors. In which:
1.1 The central handle type knife switch is mainly used for power stations and does not cut off circuits with current, serving as an disconnector.
1.2 The side front lever operating mechanism switch is mainly used in front operation and front maintenance switchgear, and the operating mechanism can be installed on both sides of the cabinet.
1.3 The central front lever operating mechanism switch is mainly used in front operation and rear maintenance switchgear, with the operating mechanism installed in the front.
1.4 Side operated handle type switch is mainly used in the power box.
1.5 Switches equipped with arc extinguishing chambers can cut offappropriate current loads, while other series of knife switches are only used as disconnectors. The product complies with the GB/T 14048.3 standard.
Model and meaning
For the 11 series,"B" represents product with protective cover
"0"represents product with no arc extinguishing chamber, "1"
represents product with arc extinguishing chamber
For the 11 series,"8"represents front-panel wiring
"9" represents back-panel wiring
Number of poles (2,3, 4)
Agreed heating current(A)
-Additional code: For the 11 series,"F"represents disconnector (see HD11Fdisconnector selection for details) For 13 series,"BX" represents rotary operation, and it represents lever operation without "BX"
Design code:"11" represents the central handle type
"12"represents the side frontlever operating mechanism type
"13" representsthe central frontlever operating mechanism type
"14" represents the side operating handle type
"HD" represents open type knife switch, and "HS" represents a double-throw knife change-over switch.
Main parameters and technical performance
| Conventional heatingcurrent (A) | 100 | 200 | 400 | 600 | 1000 | 1500 | 2000 | 3000 |
| Rated operatingcurrent (A) | 100 | 200 | 400 | 600 | 1000 | 1500 | 2000 | 3000 |
| On-off capacity (A)AC 380V | 100 | 200 | 400 | 600 | 1000 | 1500 | - | |
| Mechanical life (time) | 10000 | 10000 | 10000 | 5000 | 5000 | 5000 | 3000 | 3000 |
| Electrical life (time) | = | 1000 | 1000 | 500 | 500 | 500 | 300 | 300 |
| 1S short-time withstandcurrent (kA) | 5 | 10 | 15 | 20 | 25 | 30 | 30 | 50 |
| Operating force (N) | ≤300 | ≤300 | ≤400 | ≤400 | ≤450 | ≤450 | ≤450 | ≤450 |
Table 3 (mm)
Overall andinstallation dimension
| specification | 100A | 200A | 400A | 600A | 1000A | 1500A | ||||||||||||
| 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | |
| A | 85 | 140 | 190 | 190 | 190 | 260 | 190 | 210 | 300 | 240 | 260 | 360 | 280 | 320 | 440 | 300 | 350 | 480 |
| B | 200 | 200 | 200 | 210 | 210 | 230 | 270 | 270 | 300 | 350 | 330 | 330 | 380 | 360 | 360 | 410 | 390 | 390 |
| C | - | 50 | 100 | 140 | 70 | 140 | 160 | 80 | 160 | 200 | 100 | 200 | 240 | 120 | 240 | 260 | 130 | 260 |
| D | 140 | 140 | 140 | 140 | 140 | 140 | 190 | 190 | 190 | 140 | 140 | 140 | 140 | 140 | 140 | 140 | 140 | 140 |
| E | 50 | 50 | 50 | 70 | 70 | 70 | 80 | 80 | 80 | 100 | 100 | 100 | 120 | 120 | 120 | 130 | 130 | 130 |
| F | 160 | 160 | 160 | 162 | 162 | 162 | 210 | 210 | 210 | 274 | 274 | 274 | 284 | 284 | 284 | 330 | 330 | 330 |
| H | 210 | 220 | 220 | 220 | 220 | 235 | 270 | 270 | 270 | 330 | 310 | 310 | 380 | 360 | 360 | 390 | 370 | 370 |
| h | 120 | 120 | 120 | 120 | 120 | 120 | 135 | 135 | 135 | 140 | 125 | 125 | 175 | 160 | 160 | 175 | 160 | 160 |
| J | 110 | 110 | 110 | 110 | 110 | 110 | 146 | 146 | 146 | 234 | 234 | 234 | 208 | 208 | 208 | 230 | 230 | 230 |
| K | - | - | - | - | - | - | - | 1 | 1 | 40 | 40 | 40 | 50 | 50 | 50 | 70 | 70 | 70 |
| M | 8 | 8 | 8 | 8 | 8 | 8 | 12 | 12 | 12 | 16 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 |
| φ | 6 | 6 | 6 | 7 | 7 | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 9 | 9 | 11 | 11 | 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | ||||||||||
| 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | |
| A | 200 | 200 | 270 | 200 | 220 | 300 | 240 | 270 | 370 | 280 | 330 | 450 | 300 | 380 | 510 |
| B | 230 | 230 | 250 | 280 | 280 | 310 | 340 | 320 | 320 | 380 | 360 | 360 | 410 | 390 | 390 |
| C | 140 | 70 | 140 | 160 | 80 | 160 | 200 | 100 | 200 | 240 | 120 | 240 | 260 | 130 | 260 |
| D | 160 | 160 | 160 | 190 | 190 | 190 | 220 | 220 | 220 | 260 | 260 | 260 | 300 | 300 | 300 |
| E | 70 | 70 | 70 | 80 | 80 | 80 | 100 | 100 | 100 | 120 | 120 | 120 | 130 | 130 | 130 |
| F | 190 | 190 | 190 | 215 | 215 | 215 | 240 | 240 | 240 | 290 | 290 | 290 | 340 | 340 | 340 |
| H | 220 | 220 | 240 | 270 | 270 | 300 | 330 | 310 | 310 | 380 | 360 | 360 | 390 | 370 | 370 |
| h | 120 | 120 | 120 | 135 | 135 | 145 | 140 | 125 | 125 | 175 | 160 | 160 | 175 | 160 | 160 |
| I | 35 | 35 | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 36 | 36 | 40 | 40 | 40 |
| J | 60 | 60 | 60 | 70 | 70 | 70 | 140 | 140 | 140 | 160 | 160 | 160 | 180 | 180 | 180 |
| K | 20 | 20 | 20 | 30 | 30 | 30 | 40 | 40 | 40 | 50 | 50 | 50 | 70 | 70 | 70 |
| Mφ | 8 | 8 | 8 | 12 | 12 | 127 | 169 | 16 | 16 | 12 | 12 | 129 | 1211 | 12 | 12 |
| 7 | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 11 | 11 | |||||
| specification | 200A | 400A | 600A | 1000A | 1500A | ||||||||||
| 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | |
| A | 160 | 190 | 265 | 200 | 220 | 300 | 240 | 270 | 370 | 280 | 330 | 450 | 300 | 380 | 510 |
| B | 330 | 330 | 370 | 395 | 395 | 455 | 500 | 460 | 460 | 560 | 520 | 520 | 580 | 540 | 540 |
| C | 140 | 70 | 140 | 160 | 80 | 160 | 200 | 100 | 200 | 240 | 120 | 240 | 260 | 130 | 260 |
| D | 220 | 220 | 220 | 260 | 260 | 260 | 220 | 220 | 220 | 220 | 220 | 220 | 260 | 260 | 260 |
| E | 70 | 70 | 70 | 80 | 80 | 80 | 100 | 100 | 100 | 120 | 120 | 120 | 130 | 130 | 130 |
| F | 245 | 245 | 245 | 285 | 285 | 285 | 354 | 354 | 354 | 374 | 374 | 374 | 434 | 434 | 434 |
| H | 240 | 240 | 240 | 280 | 280 | 300 | 390 | 370 | 370 | 450 | 430 | 430 | 470 | 450 | 450 |
| h | 100 | 100 | 100 | 110 | 110 | 110 | 100 | 95 | 95 | 150 | 145 | 145 | 160 | 150 | 150 |
| I | 35 | 35 | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 36 | 36 | 40 | 40 | 40 |
| J | 170 | 170 | 170 | 216 | 216 | 216 | 320 | 320 | 320 | 304 | 304 | 304 | 340 | 340 | 340 |
| K | 20 | 20 | 20 | 30 | 30 | 30 | 40 | 40 | 40 | 50 | 50 | 50 | 70 | 70 | 70 |
| N | - | - | - | - | - | - | 30 | 30 | 30 | 40 | 40 | 40 | 46 | 46 | 46 |
| M | 8 | 8 | 8 | 12 | 12 | 12 | 16 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 |
| φ | 7 | 7 | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 9 | 9 | 11 | 11 | 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | ||||||||||
| 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | |
| A | 170 | 200 | 270 | 200 | 220 | 300 | 240 | 270 | 370 | 280 | 330 | 450 | 300 | 380 | 510 |
| B | 330 | 330 | 370 | 395 | 395 | 455 | 500 | 460 | 460 | 560 | 520 | 520 | 580 | 540 | 540 |
| C | 140 | 70 | 140 | 160 | 80 | 160 | 200 | 100 | 200 | 240 | 120 | 240 | 260 | 130 | 260 |
| D | 220 | 220 | 220 | 260 | 260 | 260 | 300 | 300 | 300 | 340 | 340 | 340 | 390 | 390 | 390 |
| E | 70 | 70 | 70 | 80 | 80 | 80 | 100 | 100 | 100 | 120 | 120 | 120 | 130 | 130 | 130 |
| F | 245 | 245 | 245 | 285 | 285 | 285 | 340 | 340 | 340 | 390 | 390 | 390 | 450 | 450 | 450 |
| H | 240 | 240 | 240 | 280 | 280 | 300 | 330 | 310 | 310 | 380 | 360 | 360 | 390 | 370 | 370 |
| h | 120 | 120 | 120 | 135 | 135 | 145 | 140 | 125 | 125 | 175 | 160 | 160 | 175 | 160 | 160 |
| I | 35 | 35 | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 36 | 36 | 40 | 40 | 40 |
| J | 120 | 120 | 120 | 140 | 140 | 140 | 220 | 220 | 220 | 250 | 250 | 250 | 285 | 285 | 285 |
| K | 20 | 20 | 20 | 30 | 30 | 30 | 40 | 40 | 40 | 50 | 50 | 50 | 70 | 70 | 70 |
| N | - | - | - | - | - | - | 30 | 30 | 30 | 40 | 40 | 40 | 46 | 46 | 46 |
| M | 8 | 8 | 8 | 12 | 12 | 12 | 16 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 |
| φ | 7 | 7 | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 9 | 9 | 11 | 11 | 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | ||||||||||
| 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | 2P | 3P | 4P | |
| A | 200 | 280 | 360 | 220 | 310 | 400 | 250 | 330 | 430 | 300 | 400 | 520 | 330 | 440 | 570 |
| B | 200 | 200 | 200 | 210 | 210 | 210 | 294 | 294 | 294 | 318 | 318 | 318 | 354 | 354 | 354 |
| C | 160 | 80 | 160 | 180 | 90 | 180 | 200 | 100 | 200 | 240 | 120 | 240 | 260 | 130 | 260 |
| D | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 |
| E | 80 | 80 | 80 | 90 | 90 | 90 | 100 | 100 | 100 | 120 | 120 | 120 | 130 | 130 | 130 |
| G | 40 | 40 | 40 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| H | 80 | 80 | 80 | 90 | 90 | 90 | 95 | 95 | 95 | 110 | 110 | 110 | 110 | 110 | 110 |
| J | 130 | 130 | 130 | 166 | 166 | 166 | 254 | 254 | 254 | 242 | 242 | 242 | 254 | 254 | 254 |
| K | 1 | - | - | - | - | - | 40 | 40 | 40 | 50 | 50 | 50 | 70 | 70 | 70 |
| L | 75 | 75 | 75 | 75 | 75 | 75 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 |
| R | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 180 | 230 | 230 | 230 | 230 | 230 | 230 |
| M | 8 | 8 | 8 | 12 | 12 | 12 | 16 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 |
| ① | 7 | 7 | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 9 | 9 | 11 | 11 | 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | |||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| A | 280 | 360 | 310 | 400 | 330 | 430 | 400 | 520 | 440 | 570 |
| B | 280 | 280 | 305 | 305 | 394 | 394 | 434 | 434 | 485 | 485 |
| C | 80 | 160 | 90 | 180 | 100 | 200 | 120 | 240 | 130 | 260 |
| D | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 260 | 260 |
| E | 80 | 80 | 90 | 90 | 100 | 100 | 120 | 120 | 130 | 130 |
| G | 40 | 40 | 30 | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
| H | 80 | 80 | 90 | 90 | 95 | 95 | 110 | 110 | 110 | 110 |
| I | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 40 | 40 |
| J | 210 | 210 | 256 | 256 | 354 | 354 | 362 | 362 | 385 | 385 |
| K | 20 | 20 | 30 | 30 | 40 | 40 | 50 | 50 | 70 | 70 |
| L | 75 | 75 | 75 | 75 | 70 | 70 | 60 | 60 | 70 | 70 |
| N | - | - | - | - | 30 | 30 | 40 | 40 | 46 | 46 |
| R | 180 | 180 | 180 | 180 | 180 | 180 | 230 | 230 | 230 | 230 |
| M | 8 | 8 | 12 | 12 | 16 | 16 | 12 | 12 | 12 | 12 |
| φ | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 11 | 11 |
| specification | 200A | 400A | 1000A 3P | 1500A 4P | 3000A | |||||
| 3P 4P | 3P | 600A 3P 4P | 4P 3P | 2000A 3P 4P | 3P 4P | |||||
| A | 210 | 300 245 | 4P 335 | 260 370 | 310 | 440 | 340 480 | 480 | 660 | 580 780 |
| B | 200 | 200 | 210 210 | 294 | 294 | 318 318 | 354 354 | 360 | 360 | 400 400 |
| C | 80 | 160 | 90 180 | 100 | 200 120 | 240 | 130 260 | 180 | 360 200 | 400 |
| D | 160 | 160 | 160 160 | 160 | 160 160 | 160 | 160 160 | 160 | 160 160 | 160 |
| E | 80 | 80 | 90 90 | 100 | 100 120 | 120 | 130 130 | 180 | 180 | 200 200 |
| H | 160 | 160 | 185 | 185 190 | 190 | 230 230 | 235 235 | 230 | 230 | 235 235 |
| J | 130 | 130 | 166 | 166 254 | 254 | 242 242 | 254 254 | 250 | 250 | 280 280 |
| K | - | - | - - | 40 | 40 | 50 50 | 70 70 | 100 | 100 | 120 120 |
| L | 75 | 75 | 75 75 | 80 | 80 | 80 80 | 80 80 | 80 | 80 | 80 80 |
| R | 180 | 180 | 180 180 | 180 | 180 | 230 230 | 230 230 | 280 | 280 | 280 280 |
| M | 8 | 8 | 12 12 | 16 | 16 | 12 12 | 12 12 | 12 | 12 | 16 16 |
| φ | 7 | 7 | 7 | 7 9 | 9 | 9 9 | 11 11 | 11 | 11 | 11 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | 2000A | 3000A | |||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| A | 210 | 300 | 240 | 335 | 270 | 370 | 330 | 450 | 370 | 500 | 500 | 680 | 600 | 800 |
| B | 280 | 280 | 300 | 300 | 394 | 394 | 434 | 434 | 485 | 485 | 480 | 480 | 540 | 540 |
| C | 80 | 160 | 90 | 180 | 100 | 200 | 120 | 240 | 130 | 260 | 180 | 360 | 200 | 400 |
| D | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 260 | 260 | 260 | 260 | 260 | 260 |
| E | 80 | 80 | 90 | 90 | 100 | 100 | 120 | 120 | 130 | 130 | 180 | 180 | 200 | 200 |
| H | 160 | 160 | 185 | 185 | 190 | 190 | 235 | 235 | 255 | 255 | 235 | 235 | 260 | 260 |
| I | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 40 | 40 | 48 | 48 | 50 | 50 |
| J | 210 | 210 | 256 | 256 | 354 | 354 | 362 | 362 | 385 | 385 | 370 | 370 | 404 | 404 |
| K | - | - | - | 一 | 40 | 40 | 50 | 50 | 70 | 70 | 100 | 100 | 120 | 120 |
| L | 75 | 75 | 70 | 70 | 70 | 70 | 60 | 60 | 70 | 70 | 60 | 60 | 70 | 70 |
| N | - | - | - | - | 30 | 30 | 30 | 30 | 46 | 46 | 50 | 50 | 50 | 50 |
| R | 180 | 180 | 180 | 180 | 180 | 180 | 230 | 230 | 280 | 280 | 280 | 280 | 280 | 280 |
| M | 8 | 8 | 12 | 12 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 | 16 | 16 |
| φ | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 11 | 11 | 11 | 11 | 11 | 11 |
table10
| specification | 200A | 400A | 600A | 1000A | 1500A | 2000A | 3000A | |||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| A | 210 | 300 | 245 | 335 | 260 | 370 | 310 | 440 | 340 | 480 | 480 | 660 | 580 | 780 |
| B | 200 | 200 | 210 | 210 | 294 | 294 | 318 | 318 | 354 | 354 | 360 | 360 | 400 | 400 |
| C | 80 | 160 | 90 | 180 | 100 | 200 | 120 | 240 | 130 | 260 | 180 | 360 | 200 | 400 |
| D | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 |
| E | 80 | 80 | 90 | 90 | 100 | 100 | 120 | 120 | 130 | 130 | 180 | 180 | 200 | 200 |
| H | 160 | 160 | 185 | 185 | 190 | 190 | 230 | 230 | 235 | 235 | 230 | 230 | 235 | 235 |
| J | 130 | 130 | 166 | 166 | 254 | 254 | 242 | 242 | 254 | 254 | 250 | 250 | 280 | 280 |
| K | - | - | - | - | 40 | 40 | 50 | 50 | 70 | 70 | 100 | 100 | 120 | 120 |
| L | 130 | 130 | 130 | 130 | 135 | 135 | 135 | 135 | 135 | 135 | 135 | 135 | 135 | 135 |
| M | 8 | 8 | 12 | 12 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 | 16 | 16 |
| φ | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 11 | 11 | 11 | 11 | 11 | 11 |
| specification | 200A | 400A | 600A | 1000A | 1500A | 2000A | 3000A | |||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| A | 210 | 300 | 240 | 335 | 270 | 370 | 330 | 450 | 370 | 500 | 500 | 680 | 600 | 800 |
| B | 280 | 280 | 300 | 300 | 394 | 394 | 434 | 434 | 485 | 485 | 480 | 480 | 540 | 540 |
| C | 80 | 160 | 90 | 180 | 100 | 200 | 120 | 240 | 130 | 260 | 180 | 360 | 200 | 400 |
| D | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 240 | 260 | 260 | 260 | 260 | 260 | 260 |
| E | 80 | 80 | 90 | 90 | 100 | 100 | 120 | 120 | 130 | 130 | 180 | 180 | 200 | 200 |
| H | 160 | 160 | 185 | 185 | 190 | 190 | 235 | 235 | 255 | 255 | 235 | 235 | 260 | 260 |
| I | 35 | 35 | 35 | 35 | 36 | 36 | 36 | 36 | 40 | 40 | 48 | 48 | 50 | 50 |
| J | 210 | 210 | 256 | 256 | 354 | 354 | 362 | 362 | 385 | 385 | 370 | 370 | 404 | 404 |
| K | - | - | - | - | 40 | 40 | 50 | 50 | 70 | 70 | 100 | 100 | 120 | 120 |
| L | 75 | 75 | 70 | 70 | 70 | 70 | 60 | 60 | 70 | 70 | 60 | 60 | 70 | 70 |
| N | - | - | - | - | 30 | 30 | 30 | 30 | 46 | 46 | 50 | 50 | 50 | 50 |
| M | 8 | 8 | 12 | 12 | 16 | 16 | 12 | 12 | 12 | 12 | 12 | 12 | 16 | 16 |
| φ | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 9 | 11 | 11 | 11 | 11 | 11 | 11 |
5.11 HD(HS)13BX-2000, 3000/31, 41 overall and installation dimension (see Figure 11, Table 12)
| Product model | A | B | C | D | E | H | J | K | L | M | ① |
| HD13BX-2000/31 | 530 | 318 | 180 | 160 | 180 | 230 | 242 | 50 | 135 | 12 | 11 |
| HD13BX-2000/41 | 710 | 318 | 2-180 | 160 | 180 | 230 | 242 | 50 | 135 | 12 | 11 |
| HD13BX-3000/31 | 710 | 354 | 230 | 160 | 230 | 235 | 254 | 70 | 135 | 12 | 11 |
| HD13BX-3000/41 | 940 | 354 | 2-230 | 160 | 230 | 235 | 254 | 70 | 135 | 12 | 11 |
| HS13BX-2000/31 | 530 | 434 | 180 | 260 | 180 | 235 | 362 | 50 | 115 | 12 | 11 |
| HS13BX-2000/41 | 710 | 434 | 2-180 | 260 | 180 | 235 | 362 | 50 | 115 | 12 | 11 |
| HS13BX-3000/31 | 710 | 485 | 230 | 260 | 230 | 235 | 385 | 70 | 125 | 12 | 11 |
| HS13BX-3000/41 | 940 | 485 | 2-230 | 260 | 230 | 235 | 385 | 70 | 125 | 12 | 11 |
5.11 HD14 overall and installation dimension(see Figure 12 and Table 13)
| specification | 200A | 400A | 600A | 1000A | 1500A | |||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 3P | |
| A | 280 | 360 | 310 | 400 | 330 | 430 | 400 | 440 |
| B | 200 | 200 | 210 | 210 | 294 | 294 | 314 | 354 |
| C | 80 | 160 | 90 | 180 | 100 | 200 | 120 | 130 |
| D | 160 | 160 | 160 | 160 | 160 | 160 | 160 | 160 |
| E | 80 | 80 | 90 | 90 | 100 | 100 | 120 | 130 |
| G | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 |
| H+L | 160+80 | 160+80 | 185+90 | 185+90 | 190+90 | 190+90 | 230+110 | 235+110 |
| L1 | 48 | 48 | 48 | 48 | 48 | 48 | 53 | 53 |
| J | 130 | 130 | 166 | 166 | 254 | 254 | 242 | 254 |
| K | - | - | - | 一 | 40 | 40 | 50 | 70 |
| R | 250 | 250 | 250 | 250 | 250 | 250 | 250 | 250 |
| M | 8 | 8 | 12 | 12 | 16 | 16 | 12 | 12 |
| φ | 7 | 7 | 7 | 7 | 9 | 9 | 9 | 11 |
Scope ofapplication
EBHD11FA series disconnectors are suitable for circuits with rated insulation voltage of 660V, rated operating voltage of 400V and rated operating current from 200A to1600A. They are mainly used in low-voltage complete equipment, and are used for openingand closing circuits and isolating power sources without load. The technical performance of this disconnector complies with the standards of IEC60947-3 and GB/T14048.3.
Model and meaning
3 digits, 3in the first digit represents 3 poles, 8/9 in the second digit representsfront/backpanel wiring,1 in thethirddigit represents product with auxiliarycontact,0 represents product without auxiliary contact,and 0 can be omitted when there is no auxiliary contact Rated operating current
Derived sequence number
Anti-misoperation type
Central handle type
Disconnector
Enterprise code
Main technical parameters
| Ratedoperatingvoltage (V) | Agreed heatingcurrent (A) | Rated short timewithstandcurrent(effective)(kA) | Power factorcosΦ | Ratio ofpeakto effectivevalue | Power-ontime (s) |
| AC400 | 200 | 10 | 0.3 | 1.7 | 1 |
| 400 | 20 | 0.3 | 2.0 | ||
| 630(600) | 20 | 0.3 | 2.0 | ||
| 1000 | 25 | 0.25 | 2.1 | ||
| 1600(1500) | 32 | 0.25 | - |
Overall and installation dimension
| Rated operatingvoltage (V)Overall | Overall dimension | |||||||
| Installation dimension | ||||||||
| A | B | E | F | M | C | D | ① | |
| 200 | 190 | 204 | 70 | 152 | M8 | 70 | 140 | ①7 |
| 400 | 210 | 248 | 80 | 163 | M12 | 80 | 190 | ①7 |
| 630 | 260 | 282 | 100 | 168 | M16 | 100 | 140 | ①9 |
| 1000 | 310 | 304 | 120 | 192 | 2-M12 | 120 | 140 | ①9 |
| 1600 | 350 | 335 | 130 | 210 | 4-M12 | 130 | 150 | ①11 |
Product overview
EBHH15(QSA) series disconnector-fuse group, HH 15A(OA); HH15P(QP) series disconnectors are mainly suitable for distribution circuits and motor circuits with high short-circuit current. They are used as manual and infrequent main switches or master switches, especially suitable for installation in higher withdrawable low-voltage switchgear assemblies. The product complies with GB/T 14048.3 and IEC60947-3 standards.
Model and meaning
Number of auxiliary contacts: 0- no auxiliary contact. 1- with 1 pair of auxiliary
contacts.2-with 2 pairs of auxiliary contacts
Number of poles (3, 4)
Agreed heating current (A)
Single throw: "QA" represents no fuse, series contact structure (double break point); Double throw: QAS
"Qp" represents no fuse, parallel contact structure (single breakpoint);
"QSA" represents product equipped with fuse, series contact structure
(double break point);
Design code
Disconnector-fuse group
Enterprise code
Structural feature
1. The switch adopts a fully enclosed structure to ensure improved reliability and stable performance;
2. It has a unique rolling plug-in contact system. Each phase has two sets of double break point contact systems, either in series orin parallel, which can meet the requirements of circuits with different current levels and different working categories.
3. The contact system allows the current to pass through several rollers separately, resulting in a significant reduction in the electric reaction force on each roller. During the movement, the contact between the roller and the fixed contact has both rolling and sliding friction, which can effectively avoid fusion welding
4. The operating mechanism has energy storage spring, so the movement speed of the moving contact group is independent of the magnitude of the operating force and the operating speed.
5. The actuator consists of handle mounted on the panel, drive coupling that engages with the handle, extension shaft, coupling and drive shaft. The extension shaft and coupling are only used when the drive shaft is not long enough.
6. The depth of installation of switches in complete set of cabinet can be considered according to the needs of the combination installation of various electrical components, with a considerable range of activities.
HH15 (QSA) series disconnector-fuse group overall and installation dimension
| Specification | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | |
| Number of main poles | 3、4、3+N | 3 | ||||||||
| Rated insulation voltage (V) | $\cup \mathsf { j } = 6 6 0 \mathsf { i f } \cup \mathsf { e } = 3 8 0 . \mathsf { U j } = 1 0 0 0 \mathsf { i f } \cup \mathsf { e } = 6 6 0 .$ | |||||||||
| Rated operating voltage (V) | AC 380、660 | |||||||||
| Rated enclosed heating current (A) | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | |
| Rated operating | 380V AC-23B | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 |
| current (A) | 660V AV-23B | 63 | 100 | 160 | 250 | 315 | 425 | 500 | 630 | 800 |
| Rated limited short circuit current at 380V Y/H (KA) | 100 | 50 | ||||||||
| Rated limited short circuit current at 660V (KA) | 50 | |||||||||
| Mechanical life (time) | 15000 | 15000 | 12000 | 12000 | 12000 | 3000 | 500 | 500 | 500 | |
| Electrical life (time) | 1000 | 1000 | 300 | 300 | 300 | 200 | 100 | 100 | 100 | |
| Rated current of the fuse at 380V/660V (A) | 63/63 | 125/100 | 160/160 | 250/250 | 400/315 | 630/425 | 800/500 | 1000/630 | 1250/800 | |
| Knife contact fuse type | RDT16-00(NT00) | RDT16-1(NT1) R | DT16-2(NT2) | RDT16-3(NT3) | RSO | |||||
| Operating moment (Nm) | 7.5 | 16 | 30 | 40 | ||||||
| Rated heating current of auxiliary contactTH380V/AC-11(A) | 5 | |||||||||
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15-63 | 12 | 6 | 100 | M5 | 2 | 39.5 | 72 | 38.5 | 9 | 199-250 | 250-301 | 301-385 | 180-199 |
| HH15-125 | 15 | 7.5 | 116 | M6 | 3 | 38.5 | 70 | 40.5 | 10 | 199250 | 250301 | 301385 | 180199 |
Hh15 (QSA) series disconnector-fuse group overall and installation dimension
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | o |
| HH15-160 | 20 | 10 | 146 | M8 | 4 | 44 | 107 | 65 | 46 | 226-284 | 284-342 | 342-400 | 120 |
| HH15-250 | 25 | 12.5 | 160 | M10 | 4 | 40 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 160 |
| HH15-400 | 25 | 12.5 | 160 | M10 | 6 | 38 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 160 |
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15-630 | 40 | 20 | 270 | M12 | 6 | 33 | 87 | 87 | 60 | 300-355 | 295-330 | 330-400 | 400-500 |
| Model andspecification | A | B | C | D | E | F | G | H | – | L | L1 | L2 | L3 |
| HH15A-400 | 25 | 12.5 | 160 | M10 | 4 | 40 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 188-238 |
| HH15A-630 | 30 | 15 | 180 | M10 | 6 | 38 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 188-238 |
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 | L4 |
| HH15A-1000 | 40 | 20 | 270 | M12 | 6 | 33 | 87 | 87 | 60 | 300-355 | 295-330 | 330-400 | 400-500 | 225-260 |
HH15P(QP) series disconnector overall and installation dimension
| Specification | 250 | 630 | 1000 | 1250 | 1600 | 2500 | 3150 | |
| Number of main poles | 3 | |||||||
| Rated insulation voltage (V) | $\cup \mathsf { j } = 6 6 0 \mathsf { i f } \cup \mathsf { e } = 3 8 0 . \mathsf { U j } = 1 0 0 0 \mathsf { i f } \cup \mathsf { e } = 6 6 0 .$ | |||||||
| Rated operating voltage (V) | AC 380、660 | |||||||
| Rated enclosed heating current (A) | 250 | 630 | 1000 | 1250 | 1600 | 2500 | 3150 | |
| Rated operatingcurrent (A) | 380V AC-21B | 250 | 630 | 1000 | 1250 | 1600 | 2500 | 3150 |
| 660V AV-22B | 250 | 630 | 630 | 630 | 800 | - | - | |
| 660V AV-23B | 250 | 630 | 1000 | 1250 | 1470 | 2500 | 2500 | |
| Rated short circuit making capacity (peak) (kA) | 17 | 50 | 67.2 | 67.2 | 85 | 130 | 130 | |
| Rated limited short circuit current at 660V (KA) | 10 | 15 | 32 | 32 | 50 | 80 | 80 | |
| Mechanical life (time) | 15000 | 12000 | 12000 | 1000 | 1000 | 300 | 300 | |
| Electrical life (time) | 1000 | 300 | 150 | 100 | 100 | 100 | 100 | |
| Operating moment (Nm) | 7.5 | 16 | 16 | 30 | 30 | 70 | 70 | |
| Rated heating current of auxiliary contactTH380V/AC-11(A) | 5 | |||||||
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15P-250 | 25 | 125 | 143 | M10 | 4 | 37.5 | 66 | 44.5 | 12.5 | 199-250 | 250-301 | 301-385 | 148-199 |
| Model andspecification | A | B1 | B2 | C | D | E | F | G | H | 一 | L | L1 | L2 | L3 |
| HH15-800 | 50 | 18 | 40 | 340 | M12 | 6 | 33 | 87 | 87 | 60 | 300-355 | 295-330 | 330-400 | 400-500 |
| HH15-1000 | 50 | 18 | 40 | 340 | M12 | 7 | 33 | 87 | 87 | 60 | 300-355 | 295-330 | 330-400 | 400-500 |
| Model andspecification | A | B | C | D | E | F | G | H | 一 | L | L1 | L2 | M | N | o |
| HH15-1250-1000A | 70 | 17 | 370 | M10 | 7 | 50 | 120 | 120 | 80 | 395-430 | 495-530 | 560-595 | 400 | 330 | 253 |
| HH15-1250 | 70 | 17 | 370 | M10 | 8 | 50 | 120 | 120 | 80 | 395-430 | 495-530 | 560-595 | 400 | 330 | 253 |
| Specification | 125 | 160 | 200 | 400 | 630 | 1000 | |
| Number of main poles | 3 | ||||||
| Rated insulation voltage (V) | $\cup \mathsf { j } = 6 6 0 \mathsf { i f } \cup \mathsf { e } = 3 8 0 . \mathsf { U j } = 1 0 0 0 \mathsf { i f } \cup \mathsf { e } = 6 6 0$ | ||||||
| Rated operating voltage (V) | AC 380、660 | ||||||
| Rated enclosed heating current (A) | 125 | 160 | 200 | 400 | 630 | 1000 | |
| Rated operatingcurrent (A) | 380V AC-21B | 125 | 160 | 200 | 400 | 630 | 1000 |
| 660V AV-22B | 125 | 160 | 160 | 315 | 425 | 800 | |
| 660V AV-21B | 125 | 160 | 200 | 400 | 630 | 1000 | |
| Rated short circuit making capacity (peak) (kA) | 17 | 17 | 17 | 50 | 50 | 67.2 | |
| Rated limited short circuit current at 660V (KA) | 10 | 10 | 10 | 15 | 15 | 32 | |
| Mechanical life (time) | 15000 | 15000 | 15000 | 12000 | 12000 | 30000 | |
| Electrical life (time) | 1000 | 1000 | 100 | 300 | 300 | 150 | |
| Operating moment (Nm) | 7.5 | 16 | 30 | ||||
| Rated heating current of auxiliary contactTH380V/AC-11(A) | 5 | ||||||
| Model andspecification | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15A-125 | 15 | 7.5 | 116 | M6 | 3 | 38.5 | 70 | 40.5 | 10 | 199-250 | 250-301 | 301-385 | 148-199 |
| HH15A-160 | 20 | 10 | 127 | M8 | 3 | 38.5 | 65 | 45.5 | 13 | 199-250 | 250-301 | 301-385 | 148-199 |
| HH15A-200 | 20 | 10 | 127 | M8 | 3 | 38.5 | 65 | 45.5 | 13 | 199-250 | 250-301 | 301-385 | 148-199 |
| Model andspecification | A | B | C | D | E | F | G | H | 一 | L | L1 | L2 | L3 | M | o |
| HH15P-630 | 30 | 15 | 170 | M10 | 5 | 39 | 107 | 65 | 43.5 | 226-2842 | 84-3423 | 42-4001 | 80-238 | 140 | 119 |
| HH15P-1000 | 40 | 20 | 218 | M12 | 6 | 32 | 117 | 80 | 51 | 226 | -2842284-3423 | 42-4001 | 80-238 | 140 | 125 |
| Model andspecification | A | B | C | D | E | F | G | H | 一 | L | L1 | L2 | L3 | L4 |
| HH15P-1250 | 40 | 20 | 350 | 2×M12 | 10 | 29 | 87 | 87 | 60 | 300-355 | 295-330 | 330-4004 | 00-500 | 225-260 |
| HH15P-1600 | 50 | 20 | 350 | 2×M12 | 10 | 29 | 87 | 87 | 60 | 300-355 | 295-330 | 330400 | -400-500 | 225-260 |
| Model andspecification | A | B | C | D | E | F | G | H | 一 | L | L1 | L2 | L3 | L4 | M | o | T |
| HH15P-2500 | 80 | 20 | 446 | M12 | 12.5 | 171.5 | 100 | 100 | 47 | 480 -510 | 455 -490 | 490 -560 | 560 -600 | 385-420 | 400 | 170 | 40 |
| HH15P-3150 | 100 | 20 | 462 | M12 | 14 | 172.5 | 87 | 87 | 60 | 480 | 455-510 | -490490 | 560-600-560 | 385-420 | 400 | 167.5 | 50 |
Panel cut-out dimension
HH15(QSA)-63\~125
Hh15(AQA)-125\~200
Hh15(PQP)-250
HH15(QSA)-160\~1250; Hh15(AQA)-400\~1000 Hh15(PQP)-630\~3150
Ordering instructions
The HH15 series disconnector must be used together with fuse. The fuse can be provided by the user, but please choose a better fuse to prevent high temperature rise.
The switch price provided by our company do not include fuse. If the user requests it during the order, our company can provide matching fuses, but it isgenerally not installed on the switch body.
When users open the packaging, please check the following accessories:
a) Switch body: 1 set
b) Insulation partition: 5 pieces (dedicated for HH15)
c) Square shaft and handle: 1 set
d) Certificate of conformity and instruction manual: 1 copy
Product overview
HR6 series fuse type disconnector (hereinafter referred to as switch). It is mainly used as power switches, isolation switches, emergency switches and circuit protection in distribution circuits and motor circuits of high short-circuit current with rated voltage of AC 380\~660V (50/60Hz) and agreed heating current up to 800A, but generally it's not used for direct opening and closing of a single motor.
The performance of this product complies with the standards of IEC60947-3 and GB/ T14048.3.
Model and meaning
"0" represents no fuse signal device
"1" represents fuse signal device type(equipped with micro switch)
Number of poles, 3 means three poles
Rated operating current: 160A, 250A, 400A, 630A, 800A five types
Design code
Fuse type disconnector
Structural feature
The switch consists of base, cover, and arc extinguishing chamber, is completely made of arc resistant plastic and is a fully plastic structure. The fixed contact is directly installed on the base, making the arc extinguishing chamber easy to disassemble and assemble. The arc extinguishing chamber has two parts: an inner chamber and an outer chamber, and multiple metal arc extinguishing grids are used to increase the arc extinguishing ability and improve the contact life.
The NT type fuse link is installed inside the cover, which can rotate in a fan-shaped manner along the support, and has a large electrical isolation to meet the requirements of the disconnector. The cover can be easily removed from the base, making it easy to install and replace the fuse link part. There are two sets of installation holes on the base to meet the requirements for installation inside various switchgear cabinets and on panels. On both sides of the switch, auxiliary contacts can be installed as needed to send signals indicating the opening and closing status of the switch.
Main technical parameters of the fuse
| Model | Rated voltage (V) | Rated current (A) |
| NT00 | 400 | 4、6、10、16、20、25、32、35、40、63、80、100、125、160 |
| 660 | 4、6、10、16、20、25、32、35、40、63、80、100、125、160 | |
| NT1 | 400 | 80、100、125、160、200、224、250 |
| 660 | 80、100、125、160、200、224、250 | |
| NT2 | 400 | 125、160、200、224、250、300、315、355、400 |
| 660 | 125、160、200、224、250、300、315、355、400 | |
| NT3 | 400 | 315、355、400、425、500、630 |
| 660 | 315、335、400、425、500、630 | |
| RT17 | 400 | 800 |
Switch technical parameter
| Model | HR6-160 | HR6-250 | HR6-400 | HR6-630 | HR6-800 | |
| Rated insulation voltage (V) | 1000 | 1000 | 1000 | 1000 | 1000 | |
| Agreed heating current (A) | 160 | 250 | 400 | 630 | 800 | |
| Rated operatingvoltage (V) | 400V | 160 | 250 | 400 | 630 | 800 |
| 660V | 100 | 200 | 315 | 425 | 500 | |
| Rated making andbreaking capacity (A)(at 1.05Ue) | ON400V, COSφ =0.35 AC22BOFF | 1280 | 2000 | 3200 | 5040 | 6400 |
| 960 | 1500 | 2400 | 3780 | 4800 | ||
| ON660V, COSφ =0.65 AC22BOFF | 480 | 750 | 1200 | 1890 | 2400 | |
| 480 | 750 | 1200 | 1890 | 2400 | ||
| Rated fuse short circuit current kA | 50 | 50 | 50 | 50 | 50 | |
| Maximum prospective peak current kA | 100 | 100 | 100 | 100 | 100 | |
| Equipped NT fuse model | 00 | 1 | 2 | 3 | RT17 | |
| Pollution level | 3 | 3 | 3 | 3 | 3 | |
| Installation category | III | III | III | III | III | |
Overall and installation dimension
| Dimension | Specification | ||
| 160A | 250A | 400-800A | |
| A | 215 | 280 | 300 |
| B | 134 | 184 | 244 |
| C | 200 | 260 | 280 |
| D | 80 | 120 | 160 |
| E | 40 | 60 | 60 |
| F | 40 | 62 | 85 |
| G | 139 | 160 | 190 |
| H | 249 | 310 | 360 |
| A | ①7 | ①9 | ①9 |
| B | ①7 | ①9 | ①9 |
BSMJK and BKMJ Series self-healing low-voltage parallel capacitors (economy type)
Mounting dimension
| Type | Rated Voltage(kV) | Rated Frequency(Hz) | Rated output(kvar) | Rated capacitance(MF) | Rated curret(A) | Dimension LxWxH(mm) |
| 0.4-5-3 | 0.4 | 50 | 5 | 99.5 | 7.2 | 145*52*110 |
| 0.4-7.5-3 | 0.4 | 50 | 7.5 | 149 | 10.8 | 145*52*130 |
| 0.4-10-3 | 0.4 | 50 | 10 | 199 | 14.4 | 145*52*130 |
| 0.4-12-3 | 0.4 | 50 | 12 | 239 | 17.3 | 145*52*180 |
| 0.4-14-3 | 0.4 | 50 | 14 | 279 | 20.2 | 145*52*210 |
| 0.4-15-3 | 0.4 | 50 | 15 | 299 | 21.7 | 145*52*210 |
| 0.4-16-3 | 0.4 | 50 | 16 | 318 | 23.1 | 172*70*190 |
| 0.4-20-3 | 0.4 | 50 | 20 | 398 | 28.9 | 172*70*190 |
| 0.4-25-3 | 0.4 | 50 | 25 | 498 | 36.1 | 167*87*200 |
| 0.4-30-3 | 0.4 | 50 | 30 | 597 | 43.3 | 167*87*200 |
| 0.4-40-3 | 0.4 | 50 | 40 | 796 | 57.7 | 240*120*200 |
| 0.4-50-3 | 0.4 | 50 | 50 | 995 | 72.2 | 240*120*220 |
| 0.45-5-3 | 0.45 | 50 | 5 | 79 | 6.4 | 145*52*110 |
| 0.45-7.5-3 | 0.45 | 50 | 7.5 | 118 | 9.6 | 145*52*110 |
| 0.45-10-3 | 0.45 | 50 | 10 | 157 | 12.8 | 145*52*130 |
| 0.45-12-3 | 0.45 | 50 | 12 | 189 | 15.4 | 145*52*130 |
| 0.45-14-3 | 0.45 | 50 | 14 | 220 | 18 | 145*52*180 |
| 0.45-15-3 | 0.45 | 50 | 15 | 236 | 19.2 | 145*52*180 |
| 0.45-16-3 | 0.45 | 50 | 16 | 252 | 20.5 | 145*52*210 |
| 0.45-20-3 | 0.45 | 50 | 20 | 315 | 25.7 | 145*52*210 |
| 0.45-25-3 | 0.45 | 50 | 25 | 393 | 32.1 | 172*70*190 |
| 0.45-30-3 | 0.45 | 50 | 30 | 472 | 38.5 | 172*70*210 |
| 0.45-40-3 | 0.45 | 50 | 40 | 629 | 51.3 | 167*87*250 |
| 0.45-50-3 | 0.45 | 50 | 50 | 786 | 64.2 | 240*120*200 |
| 0.25-5-3YN | 0.25 | 50 | 5 | 255 | 6.7 | 145*52*130 |
| 0.25-10-3YN | 0.25 | 50 | 10 | 510 | 13.3 | 145*52*210 |
| 0.25-15-3YN | 0.25 | 50 | 15 | 764 | 20 | 172*70*190 |
| 0.25-20-3YN | 0.25 | 50 | 20 | 1019 | 26.7 | 172*70*210 |
| 0.25-25-3YN | 0.25 | 50 | 25 | 1274 | 33.3 | 167*87*250 |
| 0.25-30-3YN | 0.25 | 50 | 30 | 1529 | 40 | 167*87*280 |
Low voltage current transformer
Product Overview
The BH(SDH)-0.66 series current transformer casing is made of PA66 alloy material, suitable for AC circuits with a rated frequency of 50Hz and a ratedvoltage of 0.66kV or below for current and energy measurement or relay protection. It is widely used in projects such as photovoltaic (solar power) and wind power. The installation methods include busbar-fixed and base plate-fixed installation methods, making it suitable for any installation. The secondary wiring can be connected via busbars or cables. Standards: GB/T 20840.1, GB/T 20840.2
Model Meaning
Product Parameters
| Current | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH-0.66 20 BH-0.66 30 BH-0.66 40![]() ![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 75/5 | 2.5 | 1 | |||||
| 100/5 | 2.5 | 2.5 | 1 | ||||
| 150/5 | 2.5 | 2.5 | 1 | ||||
| 200/5 | 5 | 5 | 1 | ||||
| 250/5 | 5 | 5 | 1 | ||||
| 300/5 | 5 | 5 | 1 | ||||
| 30/5 | 1 | ||||||
| 40/5 | 1 | ||||||
| 50/5 | 1 | ||||||
| 75/5 | 1 | ||||||
| 100/5 | 2.5 | 2.5 | 1 | ||||
| 150/5 | 2.5 | 2.5 | 1 | ||||
| 200/5 | 5 | 5 | 1 | ||||
| 250/5 | 5 | 5 | 1 | ||||
| 300/5 | 5 | 5 | 1 | ||||
| 400/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
| 150/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 200/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 1 | ||||
| Current | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH-0.66 50 BH-0.66 60136 ![]() BH-0.66 80 BH-0.66 100![]() BH-0.66 120![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 200/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 200/5 | 5 | 2.5 | 1 | ||||
| 250/5 | 5 | 5 | 1 | ||||
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 300/5 | 5 | 5 | 1 | ||||
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 800/5 | 10 | 10 | 1 | ||||
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
Product Overview
The BH(SDH)-0.66 series current transformer is suitable for use in AC circuits with a rated frequency of 50Hz and a rated voltage of 0.66kV and below for current and energy measurement or relay protection. This product is a plastic shell type current transformer, widely used in switchgear assemblies. It can be installed using either busbar-fixed or base-fixed methods and is suitable forinstallation in any direction. The secondary lead can be either busbar or cable.
Standards: GB/T 20840.1, GB/T 20840.2.
Model Meaning
Category
Window Width
Rated Voltage (KV)
Current Transformer
CGS Low Voltage Withdrawable Switchgear
Product Parameters
| Current | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH(SDH)-0.66 30 (B Type) BH(SDH)-0.66 30 Square Hole Customization BH(SDH)-0.66 40 BH(SDH)-0.66 50![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 50/5 | 5 | 2.5 | 1 | ||||
| 75/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 1 | |
| 100/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 1 | |
| 150/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 1 | |
| 200/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 150/5 | 2.5 | 1 | |||||
| 200/5 | 2.5 | 2.5 | 1 | ||||
| 250/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 150/5 | 5 | 2.5 | 2.5 | 2.5 | 2.5 | 1 | |
| 200/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 200/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| Current | Rated Secondary Load (VA) | ||||||
Number ofTurns through Appearance and InstallationDimensions DiagramCoreBH(SDH)-0.66 60 BH(SDH)-0.66 80 BH(SDH)-0.66100 BH(SDH)-0.66 120 BH(SDH)-0.66 130 ![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 400/5 | 5 | 5 | 5 | 5 | 5 | ||
| 500/5 | 5 | 5 | 5 | 5 | 5 | ||
| 600/5 | 5 | 5 | 5 | 5 | 5 | ||
| 750/5 | 10 | 10 | 10 | 10 | 10 | ||
| 800/5 | 10 | 10 | 10 | 10 | 10 | ||
| 100/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1500/5 | 10 | 10 | 10 | 10 | 10 | ||
| 600/5 | 5 | 5 | 5 | 5 | 5 | ||
| 750/5 | 10 | 10 | 10 | 10 | 10 | ||
| 800/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1000/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1500/5 | 10 | 10 | 10 | 10 | 10 | ||
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 750/5 | 10 | 10 | 10 | 10 | 10 | ||
| 800/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1000/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1500/5 | 10 | 10 | 10 | 10 | 10 | ||
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | ||
| 1000/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1500/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | ||
| 3000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 4000/5 | 30 | 30 | 30 | 30 | 30 | ||
| 800/5 | 10 | 5 | |||||
| 1000/5 | 10 | 5 | 5 | 5 | 5 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1500/5 | 10 | 10 | 10 | 10 | 10 | ||
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | ||
| 3000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 4000/5 | 30 | 30 | 30 | 30 | 30 | ||
| 5000/5 | 30 | 30 | 30 | 30 | 30 | ||
| Current | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH-0.66 150 BH-0.66 180 BH-0.66 200 BH-0.66 220 BH-0.66 260![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 5000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 11 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 11111 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | ||
| 5000/5 | 30 | 30 | 30 | 30 | 30 | ||
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | ||
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 5000/5 | 30 | 30 | 30 | 30 | 30 | 11 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | ||
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 5000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
| 5000/5 | 30 | 30 | 30 | 30 | 30 | 1 | |
Normal Operating Conditions and Installation Conditions
1.Installation Location: Indoor.
2.Ambient Temperature: -5°C to +40°C, with a daily average not exceeding +30°C.
3.Altitude: Not exceeding 1000m.
4.Atmospheric Conditions: When the maximum temperature is +40°C, the relative humidity of the air should not exceed 50%. At lower temperatures, the relative humidity can be up to 80%.
5.The atmosphere should not contain serious pollutants, and there should be no gases or conductive dust that could corrode metals or damage insulation.
6.The installation site should be free from severe vibrations or jolts.
The installation site should not be exposed to direct sunlight, and there should be no rain, snow, or serious mold contamination.
Attachment Outline and Installation Dimensions
Current Transformer Installation Diagram
Ordering Instructions
1.When ordering, please specify the product model, window width, current ratio, rated output, and corresponding accuracy class. For example:
Order description: BH(SDH)-0.66 type, window width 40mm, rated current ratio 200/5A, rated output 5VA, accuracy class 0.2.
Order description: BH-(SDH)0.6640600/5 0.2 class.
2.If the load is not marked in the system, the default parameters are those in the table. If the class is not marked in the system, the default accuracy class is 0.5.
3.If there are other requirements, please specify them in the contract.
Product Overview
The BH-0.661 series current transformer is suitable for use in AC circuits with a rated frequency of 50Hz and a rated voltage of 0.66kV and below for current and energy measurement or relay protection. The product is a plastic-shell current transformer, widely used in complete switchgear. Its installation method can adopt busbar fixation or base plate fixation, and it is suitable for installation in any direction. The primary conductors can be busbars or cables.
Standards: GB/T20840.1, GB/T20840.2
Model Meaning
Product Parameters
| CurrentRatio | Rated Secondary Load (VA) | |||||
Appearance and InstallationDimensions DiagramBH-0.66 Solid BH-0.66 Solid M8![]() BH-0.66 Huge Solid601 ![]() | ||||||
| 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | ||
| 5/5 | 5 | 2.5 | ||||
| 10/5 | 5 | 2.5 | ||||
| 15/5 | 5 | 2.5 | ||||
| 20/5 | 5 | 2.5 | ||||
| 25/5 | 5 | 2.5 | ||||
| 30/5 | 5 | 2.5 | ||||
| 40/5 | 5 | 2.5 | ||||
| 50/5 | 5 | 2.5 | ||||
| 75/5 | 5 | 2.5 | ||||
| 5/5 | 5 | 2.5 | ||||
| 10/5 | 5 | 2.5 | ||||
| 15/5 | 5 | 2.5 | ||||
| 20/5 | 5 | 2.5 | ||||
| 25/5 | 5 | 2.5 | ||||
| 30/5 | 5 | 2.5 | ||||
| 40/5 | 5 | 2.5 | ||||
| 50/5 | 5 | 2.5 | ||||
| 75/5 | 5 | 2.5 | ||||
| 5/5 | 5 | 5 | 5 | 5 | 5 | |
| 10/5 | 5 | 5 | 5 | 5 | 5 | |
| 15/5 | 5 | 5 | 5 | 5 | 5 | |
| 20/5 | 5 | 5 | 5 | 5 | 5 | |
| 25/5 | 5 | 5 | 5 | 5 | 5 | |
| 30/5 | 5 | 5 | 5 | 5 | 5 | |
| 40/5 | 5 | 5 | 5 | 5 | 5 | |
| 50/5 | 5 | 5 | 5 | 5 | 5 | |
| 75/5 | 5 | 5 | 5 | 5 | 5 | |
Product Overview
The BH-0.66I11 series current transformer is mainly used indoors for AC circuits with a rated voltage of 0.66kV and below and a frequency of 50Hz, for current and energy measurement or relay protection. The product is a plastic casing current transformer, widely used in complete switchgear assemblies. Its installation method can be fixed using busbars or base plates and is suitable for installation in any direction. Compared to the 1 and 11 models, it offers advantages such as larger capacity, higher accuracy, fewer accessories, and easier installation.
Standards: GR/T 20840 1.GR/T 20840.2
Standards: GB/T 20840.1, GB/T 20840.2.
Model Meaning
Product Overview
| CurrentRatio | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH-0.66 20III BH-0.66 30III BH-0.66 40III![]() | |||||||
| 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2S Class | |||
| 75/5 | 2.5 | 2.5 | 1 | ||||
| 100/5 | 5 | 5 | 1 | ||||
| 150/5 | 5 | 5 | 1 | ||||
| 200/5 | 5 | 5 | 1 | ||||
| 100/5 | 5 | 5 | 2.5 | 2.5 | 2.5 | 1 | |
| 150/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 200/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 150/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 200/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 250/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
Normal Operating Conditions and Installation Conditions
1.Installation Location: Indoor.
2.Ambient Temperature: -5°C to +40°C, with a daily average not exceeding +30°C.
3.Altitude: No more than 1000m.
4.Atmospheric Conditions: When the maximum temperature is +40°C, the relative humidity of the air should not exceed 50%. At lower temperatures, the relative humidity can be up to 80%.
5.No severe pollution in the atmosphere, and the medium should not contain gases or conductive dust that could corrode metal or damage insulation.
3.If there are any other requirements, please specify them in the contract.
2.For unmarked loads in the system, the default parameters are those in the table. For unmarked accuracy classes, the default is 0.5.
Product Overview
| Current | Rated Secondary Load (VA) | Number ofTurns throughCore | |||||
Appearance and InstallationDimensions DiagramBH-0.66 50IIIFOD BH-0.66 60III BH-0.66 80III![]() BH-0.66 100III![]() BH-0.66 120III![]() ![]() | |||||||
| Ratio | 1.0 Class | 0.5 Class | 0.5S Class | 0.2 Class | 0.2s Class | ||
| 300/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 400/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 1 | |
| 600/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 500/5 | 5 | 5 | 5 | 5 | 5 | 11 | |
| 600/5 | 5 | 5 | 5 | 5 | 5 | ||
| 750/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 800/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 11 | |
| 1000/5 | 10 | 10 | 10 | 10 | 10 | ||
| 1200/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 1500/5 | 10 | 10 | 10 | 10 | 10 | 1 | |
| 2000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 2500/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 3000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
| 4000/5 | 20 | 20 | 20 | 20 | 20 | 1 | |
Ordering Instructions
1.When placing an order, please specify the product model, window width, current ratio, rated output, and corresponding accuracy class. For example: Order BH-0.66l type, window width 60mm, rated current ratio 600/5A, rated output 5VA, accuracy class 0.2. The order description is: BH-0.66 6011600/5 0.2.
Model Meaning
Dimensions and Installation Size
| Specification Model | Outer Diameter Dimensions | Inner Diameter Dimensions | Parameters | |||
| Width | Height | Thickness | Width | Height | ||
| BH-0.66 50P | 92 | 128 | 77 | 33 | 55 | 200/5-800/5 |
| BH-0.66 60P | 92 | 144 | 77 | 33 | 65 | 400/5-1500/5 |
| BH-0.66 80P | 92 | 168 | 77 | 33 | 84 | 600/5-2000/5 |
| BH-0.66 100P | 124 | 200 | 77 | 55 | 104 | 750/5-2500/5 |
| BH-0.66130P | 124 | 230 | 77 | 55 | 134 | 1000/5-4000/5 |
Model Meaning
L MZ (J)1 - 0.5
Voltage Level
Design Sequence Number
Reinforced Type
Cast Resin Insulation
Busbar Type
Current Transformer
Product Overview
This type of transformer is an integral casting structure, primarily suitable for use in power systems with a rated frequency of 50Hz or 60Hz and a rated voltage of 0.66kV and below for current, energy metering, and relay protection, etc.
This product complies with the following standards:
GB20840.1-2010 "Transformers Part 1: General Technical Requirements"
GB20840.2-2014 "Transformers Part 2: Supplementary Technical Requirements for Current Transformers"
JJG313-2010 "Verification Regulations for Measuring Current Transformers"
Operating Environmental Conditions
1.Altitude: Not exceeding 1000 meters.
2.Ambient Temperature: -5°C to +40°C.
3.Relative Humidity: <85%.
4.Installation Location: Indoor.
Operational Parameters
1.Rated Secondary Current: 5A or 1A.
2.Power Factor: cosφ = -0.8 (lagging).
3.Rated Frequency: 50Hz or 60Hz.
4.Rated Primary Current, Rated Output, and Accuracy Class are shown in Table 1.
5.Insulation Performance: The primary winding to secondary winding and ground, and secondary winding to ground, can withstand a 3kV power-frequency withstand voltage for 1 minute.
Transformation Ratio Parameters
| Model | Rated PrimaryCurrent (A) | Rated Output (VA) | Primary Turns | ||
| 0.2C Class | 0.5C Class | 1C Class | |||
| LMZ1-0.5 | 5 | 5 | 30 | ||
| 10 | 15 | ||||
| 15 | 10 | ||||
| 20 | 5 | 5 | 8 | ||
| 30 | 5 | ||||
| 50 | 3 | ||||
| 75 | 2 | ||||
| 100 | 2 | ||||
| 100 | 5 | 1 | |||
| 150-250 | 5 | 5 | 75 | ||
| 300 | |||||
| 400 | |||||
| LMZ1(J)-0.5 | 500-800 | 10 | 10 | 15 | |
| 1000-1500 | 20 | 20 | 30 | ||
| 2000-3000 | 20 | 20 | 30 | ||
Dimensions and Installation Size
| Rated Primary Current (A) | H | h | ΦD | φd |
| 5-250 | 115 | 68 | 90 | 30 |
| 300 | 118 | 70 | 93 | 36 |
| 400 | 120 | 70 | 93 | 46 |
Model Meaning
LXK- Φ(80、100、120、150、200、260)
Nominal Inner Hole Diameter
Open/Close Type
Zero Sequence
Current Transformer
Technical Parameters
| Application | Zero Sequence ProtectionLXK-Φ(80、100、120、150、200、260) | |||
| Model | ||||
| Transformation Ratio | Relay Model | |||
| 60/1 | DD-11/60 | Series Connection | 15x1 | 2.4-4.5 |
| 30x1 | ||||
| Parallel Connection | 15x1 | 3-5 | ||
| 30x2 | ||||
| DD-11/60 | Series Connection | 15x1 | 3-5 | |
| 30x1 | ||||
| Parallel Connection | 15x2 | 3-5 | ||
| 30x2 | ||||
| Application | Microcomputer Protection | |
| Model | LXK-Φ(80、100、120、150、200、260) | |
| Transformation Ratio | Accuracy Class | Rated Output |
| 60/1 | 5P10 | 1 |
| 75/1 | 5P10 | 1.5 |
| 100/1 | 5P10 | 2.5 |
| 150/1 | 5P10 | 2.5 |
| 200/1 | 5P10 | 3.75 |
| 300/1 | 5P10 | 7.5 |
| 150/1 | 5P10 | 2.5 |
| 200/1 | 5P10 | 2.5 |
| 300/1 | 5P10 | 5 |
| 400/1 | 5P10 | 10 |
| 500/1 | 5P10 | 12.5 |
| 600/1 | 5P10 | 15 |
Overall & Mounting Bolt Dimension Figure
Cutout Device Drawing Of Inside Overpressur
Main Specifications, Enclosure&Installation Dimensions
| Type | Rated Voltage R(kV) | ated frequency(Hz) | Rated output(kvar) | Ratedcapacitance (μF) | Rated curret (A) | DimensionΦ×H(mm) | MountingboltDimension (mm) |
| 0.25-7.5-3N(1) | 0.25 | 50 | 7.5 | 382.2 | 10.0 (30.0) | Φ76×240 | M12×16 |
| 0.25-10-3N(1) | 0.25 | 50 | 10 | 509.6 | 13.3 (40.0) | Φ86×240 | M12×16 |
| 0.25-15-3N(1) | 0.25 | 50 | 15 | 764.4 | 20.0 (60.0) | Φ106×280 | M16×25 |
| 0.25-20-3N(1) | 0.25 | 50 | 20 | 1019.1 | 26.7 (80.0) | Φ116×280 | M16×25 |
| 0.25-25-3N(1) | 0.25 | 50 | 25 | 1273.9 | 33.3 (100) | Φ136×280 | M16×25 |
| 0.4-7.5-3(1) | 0.4 | 50 | 7.5 | 149 | 10.8 (18.8) | Φ76×240 | M12×16 |
| 0.4-10-3(1) | 0.4 | 50 | 10 | 199 | 14.4 (25.0) | Φ76×240 | M12×16 |
| 0.4-15-3(1) | 0.4 | 50 | 15 | 299 | 21.7 (37.5) | Φ86×240 | M16×25 |
| 0.4-20-3(1) | 0.4 | 50 | 20 | 398 | 28.9 (50.0) | Φ116×240 | M16×25 |
| 0.4-25-3(1) | 0.4 | 50 | 25 | 498 | 36.1 (62.5) | Φ116×280 | M16×25 |
| 0.4-30-3(1) | 0.4 | 50 | 30 | 597 | 43.3 (75.0) | Φ116×280 | M16×25 |
| 0.4-7.5-3(1) | 0.45 | 50 | 7.5 | 118 | 9.6 (16.7) | Φ76×240 | M12×16 |
| 0.4-10-3(1) | 0.45 | 50 | 10 | 157 | 12.8 (22.2) | Φ76×240 | M12×16 |
| 0.4-15-3(1) | 0.45 | 50 | 15 | 236 | 19.2 (33.3) | Φ76×240 | M16×25 |
| 0.4-20-3(1) | 0.45 | 50 | 20 | 315 | 25.7 (44.4) | Φ106×240 | M16×25 |
| 0.4-25-3(1) | 0.45 | 50 | 25 | 393 | 35.1 (55.6) | Φ106×280 | M16×25 |
| 0.4-30-3(1) | 0.45 | 50 | 30 | 472 | 38.5 (66.7) | Φ116×280 | M16×25 |
| 0.525-7.5-3(1) | 0.525 | 50 | 7.5 | 87 | 8.2 (14.3) | Φ76×240 | M12×16 |
| 0.525-10-3(1) | 0.525 | 50 | 10 | 116 | 11.0 (19.0) | Φ76×240 | M12×16 |
| 0.525-15-3(1) | 0.525 | 50 | 15 | 173 | 16.5 (28.6) | Φ86×240 | M16×25 |
| 0.525-20-3(1) | 0.525 | 50 | 20 | 231 | 22.0 (38.1) | Φ106×280 | M16×25 |
| 0.525-25-3(1) | 0.525 | 50 | 25 | 289 | 27.5 (47.6) | Φ116×280 | M16×25 |
| 0.525-30-3(1) | 0.525 | 50 | 30 | 347 | 33.0 (57.1) | Φ136×280 | M16×25 |
Model Meaning
EB 19 - □□/ □□
Number of auxiliary contacts, expressed as a number
20: Two normally open (NO) contacts and no normally closed (NC) contacts.
11: One normally open (NO) contact and one normally closed (NC) contact.
02: No normally open (NO) contacts and two normally closed (NC) contacts.(25A-43A)
21: Two normally open (NO) contacts and one normally closed (NC) contact.
12: One normally open (NO) contact and two normally closed (NC) contacts.(63A-95A)
Basic specification code, expressed in terms of conventional heating current
Design Code
AC Contactor
Scope of Application
The EB19 series capacitorswitchingcontactors (hereinafter referred to as "contactors") are primarily used in power circuits with a frequency of 50Hz or 60Hz and a rated operating voltage of up to 380v. They are designed for use in low-voltagereactive power compensation equipment to connect or disconnect lowvoltage parallel capacitors.
The contactors are equipped with an inrush current suppression device, which effectively minimizes the impact of closing inrush current on capacitors and suppresses overvoltage during disconnection.
Normal Working and Installation Conditions
3.1 Ambient Air Temperature:
The surrounding air temperature should be between -5°C and +40°C.
The average temperature within a 24-hour period must not exceed +35°C.
3.2 Altitude:
The installation altitude must not exceed 2000 meters.
3.3 Atmospheric Conditions:
At a maximum temperature of +40°C, the relative humidity must not exceed 50%.
Higher relative humidity is permitted at lower temperatures, e.g., 90% at 20°C.
Special precautions should be taken to prevent condensation caused by occasional temperature changes.
3.4 Pollution Degree:
The pollution degree is classified as Level 3.
3.5 Installation Category:
Installation category: Category III.
3.6 Installation Conditions:
The mounting surface should not be inclined more than ± 5 ^ { \circ } from the vertical plane.
3.7 Shock and Vibration:
The product should be installed and operated in locations free from significant shaking, impact, or vibration.
| Contactormodel | Auxiliarycontact | Quantity | Label | |
| NO | NC | |||
| EB19-25、32、43 | 20E | 2 | - | 12, 14 23.24 - |
| 02E | - | 2 | - 11, 12 21, 22 | |
| 11E | 1 | 1 | 13, 14 21,22 | |
| EB19-63、95 | 21E | 2 | 1 | 13, 14 33.34 21,22 |
| 12E | 1 | 2 | 13.14 21, 22 21, 22 | |
| EB19-115、150、170 | 10E | 1 | - | 13.14 = |
| 01E | - | 1 | - 11, 12 | |
Main Parameters and Technical Performance
| Parameter Name | EB19-25 | EB19-32 | EB19-43 | EB19-63 | EB19-95 | EB19-115 | EB19-150 | EB19-170 | |
| Electrical Lifetime (10,000 times) | 10 | 10 | 10 | 10 | 10 | 2 | 2 | 2 | |
| Rated Current le (380V) A | 17 | 23 | 29 | 45 | 72 | 87 | 115 | 130 | |
| ControllableCapacitor CapacityCapacity (kvar) | 220V | 6 | 8 | 10 | 15 | 25 | 30 | 40 | 45 |
| 380V | 12 | 16 | 20 | 30 | 40 | 60 | 80 | 90 | |
| Rated Insulation Voltage (V) | 660 | 660 | 660 | 660 | 660 | 1000 | 1000 | 1000 | |
| Inrush Current Suppression Capability | 20le | 20le | 20le | 20le | 20le | 20le | 20le | 20le | |
| Operating Conditions | Pick-up voltage: (85%~110%) US; Drop-out voltage: (20%~75%)US | ||||||||
| Coil Power (VA) - Inrush / Holding | 70/8 | 110/11 | 110/11 | 200/20 | 200/20 | 300/22 | 300/22 | 300/22 | |
| Auxiliary Contacts for CapacitorSwitching (Contactor Control) | AC-15 360VA; DC-13 33W | ||||||||
| Weight (kg) | 0.57 | 0.57 | 0.6 | 1.25 | 1.5 | 2.3 | 2.3 | 2.3 | |
Dimensions&Mounting Details
1.EB19-25, 32, 43 contactors can be installed with M4 screws and anti-loosening washers, or with 35mm mounting rails.
2.EB19-63, 95 contactors can be installed with M6 screws and anti-loosening washers, or with 35mm or 75mm mounting rails.
3. EB19-115, 150, 170 contactors can be installed with M6 screws and anti-loosening washers, or with two 35mm mounting rails, with a center distance of 100mm between the two rails.
4. The external dimensions and installation dimensions of EB19-25, 32, 43 are shown in Figure 2.
5. The external dimensions and installation dimensions of EB19-63, 95 are shown in Figure 3.
6. The external dimensions and installation dimensions of EB19-115, 150, 170 are shown in Figure 4.
Dimensions&Mounting Details
Ordering Instructions
7.1 Order Details:
7.1.1 Complete Name and Model of the Contactor.
7.1.2 Rated Control Voltage and Frequency of the Coil.
7.1.3. Order quantity
7.2 Ordering Example:EB19-43/11 Switching capacitor contactor coil voltage 220V 50Hz 10 units
Model Meaning
EB W 5 - □- □ □ -□
Number of Output Circuits
S Sampling Signal - Three-Phase Sampling
Y Sampling Signal - Three-Phase Sampling
D DC 12V Voltage Output (Unlabeled) - Static Output
B Hole Dimensions: 162 x 102 mm, can replace JKG2B
C Hole Dimensions:113 x 113 mm
Design Serial Number and Feature Code
W Control Physical Quantity - Reactive Power
Low Voltage Reactive Power Automatic Compensation Controller
Main Purpose&Application Scope
EB series intelligent lowvoltage reactive power compensation controller (referred toas controller)is a special device for reactive power compensation in low voltage distribution system, designed according to the industry standard JB/T9663-1999 of the People's Republic of China and the power industry standard DL/T597-1996. Its sampled physical quantity is reactive power, with novel design, multiple functions, good controllability, high reliability and other advantages. It is in a leading position among similar products in China and provides a new equipment for distribution automation.
Operating Conditions
Power Supply Voltage:The rated supply voltage is AC 220V or 380V, with voltage fluctuations allowed up to +10%.
Ambient Temperature:The operating temperature range is -25°C to +55°C.
Relative Humidity:The maximum relative humidity allowed is 90% at 20°C.
Altitude:The device can be used at altitudes up to 2000 meters.
Environmental Conditions:The operating environment must be free of:
1.Explosive or flammable hazardous substances.
2.Corrosive gases that could damage the metal components.
3.Conductive dust that could damage the electrical insulation of the equipment.
Model Meaning
C K □ G
Dry-type (Self-cooling)
D = Single-phase S = Three-phase
Disturbance Generator
Series Connection
Product Overview
When capacitors are used for compensating capacitive reactive power, they are often affected by harmonic currents, inrush currents during switching, and operating overvoltage, which can lead to capacitor damage and a reduction in the power factor. To address this issue, it is necessary to install series reactors in front of the capacitors. These reactors serve to suppress and absorb harmonic waves, thereby protecting the capacitors from the detrimental effects of harmonic voltage and current surges. This improves power quality, enhances the system's power factor, and extends the service life of the capacitors.
Structural Features
Product Types:The product is available in both three-phase and single-phase versions, featuring a core-type design.
Core Material:The core is made of high-quality cold-rolled silicon steel sheets, processed using a high-speed punching press. The core is characterized by minimal burrs, uniform and orderly lamination, and an aesthetically neat appearance, ensuring the reactor operates with low temperature rise and low noise.
Coil Construction:The coils are made using high-quality insulated wire, wound by a dedicated machine, offering good flatness and a neat appearance.
Assembly Process:During the assembly process, all clamping parts undergo corrosion-resistant treatment. Critical clamping components are made of non-magnetic materials. The reactor undergoes a process of pre-baking,vacuum impregnation, and thermal curing, ensuring that the coils and core are securely bonded together. This significantly reduces temperature rise and noise during operation, effectively improving the reactor's quality factor and reducing harmonic effects. Compact Design:The reactor's external dimensions are designed to fit standard cabinet sizes, making it compact, easy to wire, and significantly reducing the cabinet cost investment for the user.
Performance Specifications and Technical Parameters
Applicable Capacitor Voltage:
The product can be used with capacitor voltages of 0.4kV, 0.45kV, 0.48kV, 0.525kV, 0.66kV, and 0.69kV. Inductive Reactance:
The reactance values are available in the following ranges: 1%, 6.67%, 6%, 7%, 12%, 13.8%, and 14%.
Voltage Withstand Rating:
The product has a voltage withstand rating of 5kV/min.
Insulation Class and Other Parameters:
The insulation grades available are Class B, Class F, and Class H.
Noise Level: ≤ 30dB.
Overload Capacity: The device can operate continuously with an overload capacity of up to 1.35 times its rated value.
Operating Environment
Altitude:The maximum altitude for operation is 2000 meters.
Operating Temperature and Humidity:The operating ambient temperature ranges from -25°C to +45°C, with a relative humidity of up to 90%.
Surrounding Environment:The environment should be free from harmful gases and flammable or explosive materials.
Ventilation Conditions:The environment should have good ventilation. If the equipment is installed inside a cabinet, ventilation devices should be added to ensureproper airflow.
| Capacity of matchedcapacitance (KVAR) | Capacity ofreactor (KVAR) | Model | Terminalcurrent (A) | OutlinedimensionL*W*H(mm) | Installationdimension (mm) | Insulation leve |
| Reactance rate 6% | ||||||
| 10 | 0.6 | CKSG-0.6/0.45-6% | 12.8 | 200*125*180 | 160*75 | F/H |
| 15 | 0.9 | CKSG-0.9/0.45-6% | 19.2 | 200*125*180 | 160*75 | F/H |
| 20 | 1.2 | CKSG-1.2/0.45-6% | 25.7 | 200*135*180 | 165*75 | F/H |
| 25 | 1.5 | CKSG-1.5/0.45-6% | 30.1 | 240*155*205 | 200*100 | F/H |
| 30 | 1.8 | CKSG-1.8/0.45-6% | 38.5 | 240*160*205 | 200*100 | F/H |
| 40 | 2.4 | CKSG-2.4/0.45-6% | 51.3 | 250*170*205 | 210*105 | F/H |
| 50 | 3.0 | CKSG-3.0/0.45-6% | 64.2 | 205*175*205 | 210*110 | F/H |
| Reactance rate 7% | ||||||
| 10 | 0.7 | CKSG-0.7/0.45-7% | 12.8 | 200*125*180 | 160*75 | F/H |
| 15 | 1.05 | CKSG-1.05/0.45-7% | 19.2 | 200*125*180 | 160*75 | F/H |
| 20 | 1.4 | CKSG-1.4/0.45-7% | 25.7 | 200*135*180 | 165*75 | F/H |
| 25 | 1.75 | CKSG-1.75/0.45-7% | 30.1 | 240*155*205 | 200*100 | F/H |
| 30 | 2.1 | CKSG-2.1/0.45-7% | 38.5 | 240*160*205 | 200*100 | F/H |
| 40 | 2.8 | CKSG-2.8/0.45-7% | 51.3 | 250*170*205 | 210*105 | F/H |
| 50 | 3.5 | CKSG-3.5/0.45-7% | 64.2 | 205*175*205 | 210*110 | F/H |
| Reactance rate 12% | ||||||
| 10 | 1.2 | CKSG-1.2/0.525-12% | 11 | 200*125*180 | 160*75 | F/H |
| 15 | 1.8 | CKSG-1.8/0.525-12% | 16.5 | 240*160*205 | 200*100 | F/H |
| 20 | 2.4 | CKSG-2.4/0.525-12% | 22 | 240*170*205 | 210*105 | F/H |
| 25 | 3.0 | CKSG-3.0/0.525-12% | 27.5 | 250*175*205 | 210*110 | F/H |
| 30 | 3.6 | CKSG-3.6/0.525-12% | 33 | 250*175*245 | 210*110 | F/H |
| 40 | 4.8 | CKSG-4.8/0.525-12% | 44 | 300*190*280 | 250*110 | F/H |
| 50 | 6.0 | CKSG-6.0/0.525-12% | 55 | 300*190*280 | 250*110 | F/H |
| Reactance rate 14% | ||||||
| 10 | 1.4 | CKSG-1.4/0.525-14% | 11 | 200*125*180 | 160*75 | F/H |
| 15 | 2.1 | CKSG-2.1/0.525-14% | 16.5 | 240*160*205 | 200*100 | F/H |
| 20 | 2.8 | CKSG-2.8/0.525-14% | 22 | 240*170*205 | 210*105 | F/H |
| 25 | 3.5 | CKSG-3.5/0.525-14% | 27.5 | 250*175*205 | 210*110 | F/H |
| 30 | 4.2 | CKSG-4.2/0.525-14% | 33 | 250*175*245 | 210*110 | F/H |
| 40 | 5.6 | CKSG-5.6/0.525-14% | 44 | 300*190*280 | 250*110 | F/H |
| 50 | 7.0 | CKSG-7.0/0.525-14% | 55 | 300*190*280 | 250*110 | F/H |
EBERRY ELECTRIC CO.,LTD.
Add: 66 pu nan Road, Yueqing Economic Development Zone, Zhejiang, China MP: 86-137 3677 9975
Email: sales@vcbbreaker.com
Wechat: 86-13983212540
Whatsapp:86-13736779975
Telegram:86-13983212540
Web:www.vcbbreaker.com
E-catalogue
ZALO





BH-0.66 30
BH-0.66 40

BH-0.66 60136 
BH-0.66 80
BH-0.66 100
BH-0.66 120
BH(SDH)-0.66 30 Square Hole Customization
BH(SDH)-0.66 40
BH(SDH)-0.66 50
BH(SDH)-0.66 80
BH(SDH)-0.66100
BH(SDH)-0.66 120
BH(SDH)-0.66 130

BH-0.66 180
BH-0.66 200
BH-0.66 220
BH-0.66 260
BH-0.66 Solid M8
BH-0.66 Huge Solid601

BH-0.66 30III
BH-0.66 40III
BH-0.66 60III
BH-0.66 80III
BH-0.66 100III
BH-0.66 120III