YR SERIES SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
www.onerealenergy.com 002
YRLB6-63 DC SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
R
DC SERIES
001 www.onerealenergy.com
Product trip characteristics
YRLB6 DCT-63 series small DC circuit breaker is mainly suitable for ratedworking
voltage DC100ov or below, rated current DC63A or below newenergy DC power
generation, energy storage, user customized powersystem,digital and computer center,
communication system, smartcity (building,municipal and public facilities),smart
home,Lowvoltage terminal distribution system in the field of transportation andmicrogrid.
comply with the standard: GB/T 14048.2,IEC 60947-2.
-63 series small DC circuit breaker compact size,simplestructure, high
reliability.This series of circuit breakers are equippedwith auxiliary contact,alarm
contact,shunt trip and other richfunctional accessories. The width of auxiliary contact
and alarmauxiliary contact is 9mm, and the width of shunt trip is 18mm.
YRLB6DCT
Model and Meaning
YR LB 6 - DC / T 63 63A
Corporate logo MCB
Design
serial
number
Direct
current
Standard
code
Rated
shell
current
Rated
current
Main technical parameters
Rated shell current: 63A
Product standard: GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 500V
Rated impact tolerance voltage Uimp: 4kV
Rated current (A): 1,2,3,4,6,10,16, 20,25,32,40,50,63
Rated voltage: DC250V (1P), DC500V (2P), DC800V (3P),DC1000V(4P)
lnstantaneous tripping curve: 10ln 20%
Pole number: 1P, 2P, 3P,4P
Scope of application
4P
Number
of poles
Monopole width :18mm
Rated short circuit breaking capacity :6kA
Base temperature: 30℃
Use category.A
Mechanical life: 20, 000 times
Electrical life: 1500 times
Protection class: IP20
Wiring capacity (mm2): 25
Wiring mode: up and down into the line can be
Rated current(A)
ln≤63
ln>63
1.05In Agreed non-trip
time H (cold state)
1
2
1.30ln Agreed trip
time H (hot state)
1
2
lnstantaneous trip
characteristics(A)
B(4In~7In)
C(7In~15In)
YRLB6-125 DC SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
YRLB6 DCT-125 series small DC circuit breaker is a high performancesmall Dc circuit
breaker with high current and high speed breaking. ltis mainly suitable for overload and
short circuit protection of DCdistribution system and electrical equipment with rated
workingvoltage of DC1000v and rated working current of 125A and below.Theseries of
circuit breakers have been widely used in the DC powerdistribution system in power,
post, transportation, mining enterprisesand other places.The circuit breaker has isolation
function and canalso be used for infrequent circuit on-off operation.This SERIES
ofcircuit breaker rated shell current and rated short circuit breakingcapacity and other
important characteristics of the circuit breaker is inthe domestic similar products in the
leading position, is a rare highperformance small circuit breaker products.
Comply with the standard: GB/T 14048.2,IEC 60947-2.
YRLB6DCT-125 series small DC circuit breaker single pole width 27mm,rated current
up to 125A, rated short circuit breaking capacity up to15kA, a variety of technical
parameters leading in China.
Scope of application
Model and Meaning
YR LB 6 - DC / T 125 125A
Corporate logo MCB
Design
serial
number
Direct
current
Standard
code
Rated
shell
current
Rated
current
4P
Number
of poles
Main technical parameters
Rated shell current: 125A
Product standard :GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 1000V
Rated impact tolerance voltage Uimp: 6kV
Rated current: 32A, 40A, 50A,63A, 80A,100A,125A
Rated voltage: DC250V (1P),500V(2P),750V (3P),1000V(4P)
Tripping curve :10In±20%
Pole number:1P, 2P, 3P,4P
Monopole width: 27mm
Limit short circuit breaking capacity Icu:10kA(In 100 a or less),
15 ka (= In 125 a)
Short circuit breaking capacity lcs:7.5kA(In 100 a or less),
10 ka (=In 125 a)
Base temperature: 30°℃
Use category.A
Mechanical life: 20, 000 times
Electrical life: 300 times
Protection class: lP20
Product trip characteristics
Rated current(A)
ln≤63
ln>63
1.05In Agreed non-trip
time H (cold state)
1
2
1.30ln Agreed trip
time H (hot state)
1
2
Instantaneous trip
characteristics (A)
10ln±20%
Overload trip characteristics
Appearance and installation dimensions
Appearance and installation dimensions
YR SERIES SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
www.onerealenergy.com 002
YRLB6-63 DC SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
R
DC SERIES
001 www.onerealenergy.com
Product trip characteristics
YRLB6 DCT-63 series small DC circuit breaker is mainly suitable for ratedworking
voltage DC100ov or below, rated current DC63A or below newenergy DC power
generation, energy storage, user customized powersystem,digital and computer center,
communication system, smartcity (building,municipal and public facilities),smart
home,Lowvoltage terminal distribution system in the field of transportation andmicrogrid.
comply with the standard: GB/T 14048.2,IEC 60947-2.
-63 series small DC circuit breaker compact size,simplestructure, high
reliability.This series of circuit breakers are equippedwith auxiliary contact,alarm
contact,shunt trip and other richfunctional accessories. The width of auxiliary contact
and alarmauxiliary contact is 9mm, and the width of shunt trip is 18mm.
YRLB6DCT
Model and Meaning
YR LB 6 - DC / T 63 63A
Corporate logo MCB
Design
serial
number
Direct
current
Standard
code
Rated
shell
current
Rated
current
Main technical parameters
Rated shell current: 63A
Product standard: GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 500V
Rated impact tolerance voltage Uimp: 4kV
Rated current (A): 1,2,3,4,6,10,16, 20,25,32,40,50,63
Rated voltage: DC250V (1P), DC500V (2P), DC800V (3P),DC1000V(4P)
lnstantaneous tripping curve: 10ln 20%
Pole number: 1P, 2P, 3P,4P
Scope of application
4P
Number
of poles
Monopole width :18mm
Rated short circuit breaking capacity :6kA
Base temperature: 30℃
Use category.A
Mechanical life: 20, 000 times
Electrical life: 1500 times
Protection class: IP20
Wiring capacity (mm2): 25
Wiring mode: up and down into the line can be
Rated current(A)
ln≤63
ln>63
1.05In Agreed non-trip
time H (cold state)
1
2
1.30ln Agreed trip
time H (hot state)
1
2
lnstantaneous trip
characteristics(A)
B(4In~7In)
C(7In~15In)
YRLB6-125 DC SOLAR DC MINI CIRCUIT BREAKER (DC MCB)
YRLB6 DCT-125 series small DC circuit breaker is a high performancesmall Dc circuit
breaker with high current and high speed breaking. ltis mainly suitable for overload and
short circuit protection of DCdistribution system and electrical equipment with rated
workingvoltage of DC1000v and rated working current of 125A and below.Theseries of
circuit breakers have been widely used in the DC powerdistribution system in power,
post, transportation, mining enterprisesand other places.The circuit breaker has isolation
function and canalso be used for infrequent circuit on-off operation.This SERIES
ofcircuit breaker rated shell current and rated short circuit breakingcapacity and other
important characteristics of the circuit breaker is inthe domestic similar products in the
leading position, is a rare highperformance small circuit breaker products.
Comply with the standard: GB/T 14048.2,IEC 60947-2.
YRLB6DCT-125 series small DC circuit breaker single pole width 27mm,rated current
up to 125A, rated short circuit breaking capacity up to15kA, a variety of technical
parameters leading in China.
Scope of application
Model and Meaning
YR LB 6 - DC / T 125 125A
Corporate logo MCB
Design
serial
number
Direct
current
Standard
code
Rated
shell
current
Rated
current
4P
Number
of poles
Main technical parameters
Rated shell current: 125A
Product standard :GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 1000V
Rated impact tolerance voltage Uimp: 6kV
Rated current: 32A, 40A, 50A,63A, 80A,100A,125A
Rated voltage: DC250V (1P),500V(2P),750V (3P),1000V(4P)
Tripping curve :10In±20%
Pole number:1P, 2P, 3P,4P
Monopole width: 27mm
Limit short circuit breaking capacity Icu:10kA(In 100 a or less),
15 ka (= In 125 a)
Short circuit breaking capacity lcs:7.5kA(In 100 a or less),
10 ka (=In 125 a)
Base temperature: 30°℃
Use category.A
Mechanical life: 20, 000 times
Electrical life: 300 times
Protection class: lP20
Product trip characteristics
Rated current(A)
ln≤63
ln>63
1.05In Agreed non-trip
time H (cold state)
1
2
1.30ln Agreed trip
time H (hot state)
1
2
Instantaneous trip
characteristics (A)
10ln±20%
Overload trip characteristics
Appearance and installation dimensions
Appearance and installation dimensions
001 www.onerealenergy.com
R
Product Application
YRM3 DC series Moulded Case Circuit Breaker is designed to distribute power and protect the circuit and power equipment
against overload in solar system. It is apply to rating current 1250A or less, direct current rating voltage 1500V or less.Products according
IEC60947-2, GB14048.2 standard.
Application conditions
Model YRM3 DC-125 YRM3 DC-250 YRM3 DC-400 YRM3 DC-630 YRM3 DC-800 YRM3 DC-1250
Rated Continuous
Current 125 250 400 630 1250
Rated Current
ln (A)
16、20、25、
32、40、
50、63、80、
100、125
100、125、
140、160、
180、200、
225、250
250、315、
350、400
400、500、
630
800
630、700、
800
800、
1000、
1250
Rated Operating
Voltage Ue (V) DC
550V
750V
1000V
1500V
550V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
Rated Insulation
Voltage Ui (V) 1500V 1500V 1500V 1500V 1500V 1500V
Uimp (kV) 8kV 8kV 8kV 8kV 8kV 8kV
Test Voltage One
Minute (V) 3550 3550 3550 3550 3550 3550
Breaking
Capacity
(kA) Icu
(1cs=
75% Icu)
L M H L M H L M H L M H L M H L M H
250V 25 35 50 35 50 65 35 50 65 35 50 65 50 65 80 50 65 80
500V 25 25 50 35 35 65 35 35 65 35 35 65 50 50 80 50 50 80
750V 25 15 50 35 25 65 35 25 65 35 25 65 50 35 80 50 35 80
1000V 25 10 50 35 15 65 35 15 65 35 15 65 50 20 80 50 20 80
Mechanical
Life Times 7000 7000 4000 4000 2500 2000
Electrical
Life Times 2000 2000 1000 1000 800 600
Breaking Times (ms) 20 20 20 20 20 20
Installation Location Any place
Isolator Capacity Yes
Standard IEC 60947-2、IEC60947-1、GB 14048.1、GB 14048.2
Temperature (℃) -25℃~+50℃
Protection Degree IP20
Accessory OF/SD/MX
Arcing Distance
(mm) ≥50
Altitude : less than 2000m ( please specify
when it's higher than 2000m).
Ambient temperature : -40~+70
Dampproof Moisture-resistant
Technical Data
DC SERIES
YRM3 DC SOLAR DC MOULDED CASE CIRCUIT BREAKER (DC MCCB) YRM3 DC SERIES PV DC MOULDED CASE CIRCUIT BREAKER
YRM3 DC series PV DC moudled case circuit breaker protects the battery systems and energy storage systems,with over load protection
and shortcircuit protection.Rated voltage is 500VDC.Rated current up to 250A.Ensure thesolar PV systems including batteries operating
well and high efficiency.A IP66 and Uvresistance PC enclosure is optional.
Y R M
DC MOULDED CASE CIRCUIT BREAKER
3
High Breaking Capacity, relaiable insulating
Over load protection and short-circuit protection
Frequency operating and isolating
Rated voltage 500VDC
Max Rated Current 250A
Code Name Description
001 www.onerealenergy.com
R
Product Application
YRM3 DC series Moulded Case Circuit Breaker is designed to distribute power and protect the circuit and power equipment
against overload in solar system. It is apply to rating current 1250A or less, direct current rating voltage 1500V or less.Products according
IEC60947-2, GB14048.2 standard.
Application conditions
Model YRM3 DC-125 YRM3 DC-250 YRM3 DC-400 YRM3 DC-630 YRM3 DC-800 YRM3 DC-1250
Rated Continuous
Current
125 250 400 630 1250
Rated Current
ln (A)
16、20、25、
32、40、
50、63、80、
100、125
100、125、
140、160、
180、200、
225、250
250、315、
350、400
400、500、
630
800
630、700、
800
800、
1000、
1250
Rated Operating
Voltage Ue (V) DC
550V
750V
1000V
1500V
550V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
750V
1000V
1500V
Rated Insulation
Voltage Ui (V)
1500V 1500V 1500V 1500V 1500V 1500V
Uimp (kV) 8kV 8kV 8kV 8kV 8kV 8kV
Test Voltage One
Minute (V)
3550 3550 3550 3550 3550 3550
Breaking
Capacity
(kA) Icu
(1cs=
75% Icu)
L M H L M H L M H L M H L M H L M H
250V 25 35 50 35 50 65 35 50 65 35 50 65 50 65 80 50 65 80
500V 25 25 50 35 35 65 35 35 65 35 35 65 50 50 80 50 50 80
750V 25 15 50 35 25 65 35 25 65 35 25 65 50 35 80 50 35 80
1000V 25 10 50 35 15 65 35 15 65 35 15 65 50 20 80 50 20 80
Mechanical
Life
Times 7000 7000 4000 4000 2500 2000
Electrical
Life
Times 2000 2000 1000 1000 800 600
Breaking Times (ms) 20 20 20 20 20 20
Installation Location Any place
Isolator Capacity Yes
Standard IEC 60947-2、IEC60947-1、GB 14048.1、GB 14048.2
Temperature (℃) -25℃~+50℃
Protection Degree IP20
Accessory OF/SD/MX
Arcing Distance
(mm)
≥50
Altitude : less than 2000m ( please specify
when it's higher than 2000m).
Ambient temperature : -40~+70
Dampproof Moisture-resistant
Technical Data
DC SERIES
YRM3 DC SOLAR DC MOULDED CASE CIRCUIT BREAKER (DC MCCB) YRM3 DC SERIES PV DC MOULDED CASE CIRCUIT BREAKER
YRM3 DC series PV DC moudled case circuit breaker protects the battery systems and energy storage systems,with over load protection
and shortcircuit protection.Rated voltage is 500VDC.Rated current up to 250A.Ensure thesolar PV systems including batteries operating
well and high efficiency.A IP66 and Uvresistance PC enclosure is optional.
Y R M
DC MOULDED CASE CIRCUIT BREAKER
3
High Breaking Capacity, relaiable insulating
Over load protection and short-circuit protection
Frequency operating and isolating
Rated voltage 500VDC
Max Rated Current 250A
Code Name Description
001 www.onerealenergy.com www.onerealenergy.com 002
YRM3 DC SERIES PV DC MOULDED CASE CIRCUIT BREAKER
Electrical Characteristics
Tripping Type
Service Life/Cycle Operation
lnstallation Environment
YRM3-250 YRM3-250
YRM3-250
YRM3-250 YRM3-250/EL
DC MOULDED CASE CIRCUIT BREAKER
YRSP-40 series surge protective devices have reliable voltage protection level,
supersurge discharge capacity and safety overload capacity, which areused
forlightning protection of photovoltaic power generation system.The producth is
equipped with high-energy mov chip, so when the system Hhhas overvoltage due
tolightning stroke or other reasons, it can introduce the voltage into the earth with
nanosecond response speed, so as to protect the equipment.
E
DC
P: Surge Protector
G:600V N:1000V T:1500V
40:4OkA
2:2P 3:3P
R: with RC Nil: with out RC
D
Product Code
voltage
lmax
Pole
Remote signal
Code Name Description
1
2
3
4
5
6
7
E
YRSP-40 SURGE PROTECTION DEVICE
Y R SP
R
DC SERIES
Type Type
Pole
001 www.onerealenergy.com www.onerealenergy.com 002
YRM3 DC SERIES PV DC MOULDED CASE CIRCUIT BREAKER
Electrical Characteristics
Tripping Type
Service Life/Cycle Operation
lnstallation Environment
YRM3-250 YRM3-250
YRM3-250
YRM3-250 YRM3-250/EL
DC MOULDED CASE CIRCUIT BREAKER
YRSP-40 series surge protective devices have reliable voltage protection level,
supersurge discharge capacity and safety overload capacity, which areused
forlightning protection of photovoltaic power generation system.The producth is
equipped with high-energy mov chip, so when the system Hhhas overvoltage due
tolightning stroke or other reasons, it can introduce the voltage into the earth with
nanosecond response speed, so as to protect the equipment.
E
DC
P: Surge Protector
G:600V N:1000V T:1500V
40:4OkA
2:2P 3:3P
R: with RC Nil: with out RC
D
Product Code
voltage
lmax
Pole
Remote signal
Code Name Description
1
2
3
4
5
6
7
E
YRSP-40 SURGE PROTECTION DEVICE
Y R SP
R
DC SERIES
Type Type
Pole
DC SURGE PROTECTOR
YRSP-40 SURGE PROTECTION DEVICE
Technical Data
001 www.onerealenergy.com www.onerealenergy.com 002
YRSPG40-2(R) YRSPN40-3(R) YRSPT40-3(R)
Appearance lntroduction
YRSP-40 SURGE PROTECTION DEVICE
EDPG40-2(R) YRSPG40-2(R) YRSPN40-3(R),YRSPT40-3(R)
DC SURGE PROTECTOR
DC SURGE PROTECTOR
YRSP-40 SURGE PROTECTION DEVICE
Technical Data
001 www.onerealenergy.com www.onerealenergy.com 002
YRSPG40-2(R) YRSPN40-3(R) YRSPT40-3(R)
Appearance lntroduction
YRSP-40 SURGE PROTECTION DEVICE
EDPG40-2(R) YRSPG40-2(R) YRSPN40-3(R),YRSPT40-3(R)
DC SURGE PROTECTOR
DC SURGE PROTECTOR
YRSP-40 SURGE PROTECTION DEVICE
E
DC
P: Surge Protector
G:600V N:1000V T:1500V
40:40kA
2:2P 3:3P
R: with RC Nil: with out RC
D
Product Code
voltage
lmax
Pole
Remote signal
Code Name Description
1
2
3
4
5
6
7
E
YRSP-40 series surge protective devices have reliable voltage protection level, supersurge discharge capacity and safety overload
capacity, which are used forlightning protection of photovoltaic power generation system.The product isequipped with high-energy mov
chip, so when the system has overvoltage due tolightning stroke or other reasons, it can introduce the voltage into the earth
withnanosecond response speed, so as to protect the equipment.
Product Application
001 www.onerealenergy.com www.onerealenergy.com 002
Y R SP
R
DC SERIES
Technical Data
YRSPG40-2(R) YRSPN40-3(R) YRSPT40-3(R)
YRSP-40 SURGE PROTECTION DEVICE
Location of Use: String box, Inverter
Mode of Protection: (DC+)- PE,(DC-)- PE,(DC+) -(DC-)
Surge Ratings: lTotal=up to 12.5kA(10/350 us)
ITotal=up to 40kA(8/20 us)
IEC/ENUL Category: Class l+ll /Type 1+2
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-31 EN 50539-11+A1
Product mode
lIEC Electrical
Mechanical & Environmental
DC SURGE PROTECTOR
YRSP-40 SURGE PROTECTION DEVICE
E
DC
P: Surge Protector
G:600V N:1000V T:1500V
40:40kA
2:2P 3:3P
R: with RC Nil: with out RC
D
Product Code
voltage
lmax
Pole
Remote signal
Code Name Description
1
2
3
4
5
6
7
E
YRSP-40 series surge protective devices have reliable voltage protection level, supersurge discharge capacity and safety overload
capacity, which are used forlightning protection of photovoltaic power generation system.The product isequipped with high-energy mov
chip, so when the system has overvoltage due tolightning stroke or other reasons, it can introduce the voltage into the earth
withnanosecond response speed, so as to protect the equipment.
Product Application
001 www.onerealenergy.com www.onerealenergy.com 002
Y R SP
R
DC SERIES
Technical Data
YRSPG40-2(R) YRSPN40-3(R) YRSPT40-3(R)
YRSP-40 SURGE PROTECTION DEVICE
Location of Use: String box, Inverter
Mode of Protection: (DC+)- PE,(DC-)- PE,(DC+) -(DC-)
Surge Ratings: lTotal=up to 12.5kA(10/350 us)
ITotal=up to 40kA(8/20 us)
IEC/ENUL Category: Class l+ll /Type 1+2
Protective Elements: High Energy MOV
Housing: Pluggable Design
Compliance: IEC 61643-31 EN 50539-11+A1
Product mode
lIEC Electrical
Mechanical & Environmental
DC SURGE PROTECTOR
001 www.onerealenergy.com www.onerealenergy.com 002
YRSPG40-2(R) YRSPN40-3(R)、YRSPT40-3(R)
YRSP-40 SURGE PROTECTION DEVICE
A range of 14x51mm fuse links specifically designed for protecting photovoltaic strings. These fuselinks are capable of interrupting low ove
rcurrents associated with faulted photovoltaic string arrays(reverse current, multi-array fault).
Structural Characteristics
According to IEC60269-6
Rated current: 1-63A
Rated voltage: DC 1000V
Operating class gPV for Solar protection
Pole 1P
Rated Voltage Ue (V DC) 1000
Rated Current In (A) 4,6,8,10,12,16,20,25,32,40,50,63
Connection(mm2) 2.5 -1 0
Working Temperature(℃ ) -30~+70
Resistance And Damp Hot Class 2
Altitude(m) ≤2000
Relative Humidity ≤95%
Protection Class/Degree IP20
Pollution 3
Installation Environment No obvious shock and vibration
Installation Class/Type Class III/DIN rail
Size/Dimension(mm)
(WxHxL)
W 22
H 66
L 96
Fuse Size 14x51
Fuse holder Weight (kg) 0.11
Fuse link weight(kg) 0.025
Photovoltaic system fuse accord with UL248-1 standard.
Photovoltaic battery dc fuse designed to used for photovoltaic (PV) system.
Main effect is to protect the solar panels. Solar panels points in effective condition is broken.
Fault light cells break points at the same time, does not affect other normal work of light from
the stack.
Technical Data Rated coltage: DC1000V Breaking capacity: 25KA Function level: PV .
Connection and Installation
Size(mm)
PV fuse Description
YRPV-32X SOLAR DC FUSE
R
DC SERIES
DC SURGE PROTECTOR
001 www.onerealenergy.com www.onerealenergy.com 002
YRSPG40-2(R) YRSPN40-3(R)、YRSPT40-3(R)
YRSP-40 SURGE PROTECTION DEVICE
A range of 14x51mm fuse links specifically designed for protecting photovoltaic strings. These fuselinks are capable of interrupting low ove
rcurrents associated with faulted photovoltaic string arrays(reverse current, multi-array fault).
Structural Characteristics
According to IEC60269-6
Rated current: 1-63A
Rated voltage: DC 1000V
Operating class gPV for Solar protection
Pole 1P
Rated Voltage Ue (V DC) 1000
Rated Current In (A) 4,6,8,10,12,16,20,25,32,40,50,63
Connection(mm2) 2.5 -1 0
Working Temperature(℃ ) -30~+70
Resistance And Damp Hot Class 2
Altitude(m) ≤2000
Relative Humidity ≤95%
Protection Class/Degree IP20
Pollution 3
Installation Environment No obvious shock and vibration
Installation Class/Type Class III/DIN rail
Size/Dimension(mm)
(WxHxL)
W 22
H 66
L 96
Fuse Size 14x51
Fuse holder Weight (kg) 0.11
Fuse link weight(kg) 0.025
Photovoltaic system fuse accord with UL248-1 standard.
Photovoltaic battery dc fuse designed to used for photovoltaic (PV) system.
Main effect is to protect the solar panels. Solar panels points in effective condition is broken.
Fault light cells break points at the same time, does not affect other normal work of light from
the stack.
Technical Data Rated coltage: DC1000V Breaking capacity: 25KA Function level: PV .
Connection and Installation
Size(mm)
PV fuse Description
YRPV-32X SOLAR DC FUSE
R
DC SERIES
YR SERIES SOLAR DC FUSE
10000
10A
12A
15A
20A
25A
32A
40A
6
t
(s)
4
2
6
4
2
2
2
10
1.0
0.1
6
6
4
4
1 2 4 6 8 10 2 4 6 8100 2 4 6 8 1000
6
4
1000
100
Dimensions
50.5
13.8
96
30
66
42 22
Installation
Characteristic Curve
www.onerealenergy.com 002
YRPV-32X SOLAR DC FUSE
001 www.onerealenergy.com
YRPV32 SERIES DC LSOLATOR
YR PV
R
DC SERIES
32
Code Name Description
YR SERIES SOLAR DC FUSE
10000
10A
12A
15A
20A
25A
32A
40A
6
t
(s)
4
2
6
4
2
2
2
10
1.0
0.1
6
6
4
4
1 2 4 6 8 10 2 4 6 8100 2 4 6 8 1000
6
4
1000
100
Dimensions
50.5
13.8
96
30
66
42
22
Installation
Characteristic Curve
www.onerealenergy.com 002
YRPV-32X SOLAR DC FUSE
001 www.onerealenergy.com
YRPV32 SERIES DC LSOLATOR
YR PV
R
DC SERIES
32
Code Name Description
DC ISOLATION SWITCH
Rated thermal current Ith A 32
Rated impulse withstand voltage Uimp V 8000
Rated short-time withstand current (1 ms) lcw A 780
Rated short-time making capacity lcw A 1200
Rated insulation voltage ui V 1500 1500 1500 1500 1500
40 55 55 55
Rated Lcurrent A 13 20 25 40 50
Maximum cable cross sections (incl. Jurmper)
Solid or standard
Flexible
Flexible (+ multicore cable end)
Torque
Tghtening torque terminal screws M4
Tightening torque single hole mounting nut M16
Tghteningtorque knob screws M3
Switching on or off torque
Nm 1.2-1.8
Nm 2.0-2.3
Nm
Nm
Actual
Standard
Actual
Standard
0.5-0.7
0.9-1.3
mm² 4-16
mm² 4-16
mm² 4-16
12 o'clock,OFF 3 o'clock,ON 9 o'clock,OFF 12 o'clock,ON
3000Cycles
300 Cycles
10000 Cycles
10000 Cycles
2 or 4 (6/8 geek choice)
8mm
-40℃to+85℃
-40℃to+85℃
3
Knob positions
Electrical Life
Mechanical Life
Number of DC poles
Distance of contacts (per pole)
Operation temperature
Store temperature
Pollu don degree
Overvoltage category
IP rating of shafte and mounting nut
Data according to IEC/EN60947-3,AS60947.3, UL508i, GB/T14048.3. Utilization category DC-PV1/DC-PV2
Ⅱ
IP66
General parameters
Main Parameters
001 www.onerealenergy.com www.onerealenergy.com 002
R
DC SERIES
YRPV32 SERIES DC LSOLATOR YRPV32 SERIES DC LSOLATOR
YEPV32 Voltage / curren (DC-PV1)
YEPV32 Voltage / curren (DC-PV2)
Layers
Layers
DC ISOLATION SWITCH
Rated thermal current Ith A 32
Rated impulse withstand voltage Uimp V 8000
Rated short-time withstand current (1 ms) lcw A 780
Rated short-time making capacity lcw A 1200
Rated insulation voltage ui V 1500 1500 1500 1500 1500
40 55 55 55
Rated Lcurrent A 13 20 25 40 50
Maximum cable cross sections (incl. Jurmper)
Solid or standard
Flexible
Flexible (+ multicore cable end)
Torque
Tghtening torque terminal screws M4
Tightening torque single hole mounting nut M16
Tghteningtorque knob screws M3
Switching on or off torque
Nm 1.2-1.8
Nm 2.0-2.3
Nm
Nm
Actual
Standard
Actual
Standard
0.5-0.7
0.9-1.3
mm² 4-16
mm² 4-16
mm² 4-16
12 o'clock,OFF 3 o'clock,ON 9 o'clock,OFF 12 o'clock,ON
3000Cycles
300 Cycles
10000 Cycles
10000 Cycles
2 or 4 (6/8 geek choice)
8mm
-40℃to+85℃
-40℃to+85℃
3
Knob positions
Electrical Life
Mechanical Life
Number of DC poles
Distance of contacts (per pole)
Operation temperature
Store temperature
Pollu don degree
Overvoltage category
IP rating of shafte and mounting nut
Data according to IEC/EN60947-3,AS60947.3, UL508i, GB/T14048.3. Utilization category DC-PV1/DC-PV2
Ⅱ
IP66
General parameters
Main Parameters
001 www.onerealenergy.com www.onerealenergy.com 002
R
DC SERIES
YRPV32 SERIES DC LSOLATOR YRPV32 SERIES DC LSOLATOR
YEPV32 Voltage / curren (DC-PV1)
YEPV32 Voltage / curren (DC-PV2)
Layers
Layers
DC ISOLATION SWITCH
Drawing Size
001 www.onerealenergy.com www.onerealenergy.com 002
Drawing Size
R
DC SERIES
YRPV32 SERIES DC LSOLATOR YRPV32 SERIES DC LSOLATOR
YRPV7DC/...R YRPV8DC/...R
YRPV7DC/... YRPV8DC/...
YRPV7DBR YRPV8DBR
YRPV7HM YRPV8HM
DC ISOLATION SWITCH
Drawing Size
001 www.onerealenergy.com www.onerealenergy.com 002
Drawing Size
R
DC SERIES
YRPV32 SERIES DC LSOLATOR YRPV32 SERIES DC LSOLATOR
YRPV7DC/...R YRPV8DC/...R
YRPV7DC/... YRPV8DC/...
YRPV7DBR YRPV8DBR
YRPV7HM YRPV8HM
DC ISOLATION SWITCH
Appearance Introduction
Technical Data
YRPV100 DC LSOLATOR(1 S00V) IP66 ENCLOSUREA
Rated insulation voltage
Rated thermal current
Ith
Rated impulse withstand voltage Uimp
Rated short-time withstand current (1s) lcm
Rated short-time making capacity lcm
ui V 1500 1500 1500 1500 1500
40 55 55 55
Rated Lcurrent A 13 20 25 40 50
Maximum cable cross sections (incl. jumper)
Solid or standard
Flexible
Flexible (+ multicore cable end)
Torque
Tightening torque terminal screws M4.
Tightening torque single hole mounting nut M 16
Tightening torque knob screws M3
Switching on or off torque
Nm 1.2-1.8
Nm 2.0-2.3
Nm
Nm
0.5-0.7
0.9-1.3
mm² 4-16
mm² 4-16
mm² 4-16
12 o'clock,OFF 3 o'clock,ON 9 o'clock,OFF 12 o'clock,ON
3000Cycles
300 Cycles
10000 Cycles
10000 Cycles
2 or 4 (6/8 geek choice)
8
-40to+85℃
-40to+85℃
3
Knob positions
Actual
Electrical Life
Standard
Actual
Mechanical Life
Standard
Number of DC poles
Distance of contacts (per pole)
Operation temperature
Store temperature
Pollution degree
Overvoltage category
IP rating of shafte and mounting nut
Ⅱ
General parameters
IP66
A
V
A
32
8000
780
1200A
mm
℃
℃
001 www.onerealenergy.com www.onerealenergy.com 002
DC ISOLATION SWITCH
Number of layers
2/4
4T/B/S
1 As翿h
(€ t
Aluminum box
1 AS翿h
e , (€
Plastic box
600Vdc
32
40
55
I
I
I
I
I
I
I
800Vdc 1000Vdc
26 13
30 20
45 25
50 40
55 50
I 32
I 40
I 55
I I
I I
1200Vdc 1500Vdc
10 5
12 6
15 8
30 20
40 30
26 13
30 20
40 30
I 45
I 50
Voltage/Current(DC-PV1)
Dimension and Mounting
Dimension and Mounting
YRPV100 DC LSOLATOR(1 S00V) IP66 ENCLOSUREA
DC ISOLATION SWITCH
Appearance Introduction
Technical Data
YRPV100 DC LSOLATOR(1 S00V) IP66 ENCLOSUREA
Rated insulation voltage
Rated thermal current
Ith
Rated impulse withstand voltage Uimp
Rated short-time withstand current (1s) lcm
Rated short-time making capacity lcm
ui V 1500 1500 1500 1500 1500
40 55 55 55
Rated Lcurrent A 13 20 25 40 50
Maximum cable cross sections (incl. jumper)
Solid or standard
Flexible
Flexible (+ multicore cable end)
Torque
Tightening torque terminal screws M4.
Tightening torque single hole mounting nut M 16
Tightening torque knob screws M3
Switching on or off torque
Nm 1.2-1.8
Nm 2.0-2.3
Nm
Nm
0.5-0.7
0.9-1.3
mm² 4-16
mm² 4-16
mm² 4-16
12 o'clock,OFF 3 o'clock,ON 9 o'clock,OFF 12 o'clock,ON
3000Cycles
300 Cycles
10000 Cycles
10000 Cycles
2 or 4 (6/8 geek choice)
8
-40to+85℃
-40to+85℃
3
Knob positions
Actual
Electrical Life
Standard
Actual
Mechanical Life
Standard
Number of DC poles
Distance of contacts (per pole)
Operation temperature
Store temperature
Pollution degree
Overvoltage category
IP rating of shafte and mounting nut
Ⅱ
General parameters
IP66
A
V
A
32
8000
780
1200A
mm
℃
℃
001 www.onerealenergy.com www.onerealenergy.com 002
DC ISOLATION SWITCH
Number of layers
2/4
4T/B/S
1 As翿h
(€ t
Aluminum box
1 AS翿h
e , (€
Plastic box
600Vdc
32
40
55
I
I
I
I
I
I
I
800Vdc 1000Vdc
26 13
30 20
45 25
50 40
55 50
I 32
I 40
I 55
I I
I I
1200Vdc 1500Vdc
10 5
12 6
15 8
30 20
40 30
26 13
30 20
40 30
I 45
I 50
Voltage/Current(DC-PV1)
Dimension and Mounting
Dimension and Mounting
YRPV100 DC LSOLATOR(1 S00V) IP66 ENCLOSUREA
R
Application conditions
YRLB6-63 have protective function as overload, and are used in lighting distribution system in industry commerce and dwelling, and protect
fractional electric motors. And they also have many merits of high protective grade(up to IP20), high breaking capacity, reliable sensitive,
action convenient, multi pole assembling, long life ect. The are mainly adapted to the circuit of AC 50Hz, 250V in single pole, 415V in double,
three, four poles for protecting overload and short circuit. Mean while, they are also used in turning on or off the electric apparatus
and lighting circuit under the normal conditions.
Standard
Technical Data
ADC C SSERERIEISES
Rated Voltage 230V/400V AC(1P), 400V AC(2P, 3P, 4P)
EN60B98(EC60e98)MEC60947-2
Rated Current 3,6,10,16,20,25,32,40,50,63A
Rated Breaking Capacity 10KA IEC60898( 3~63A)
Characteristic Curve B, C, D
Max. Fuse That Can Be Connected To 100AGL(>10KA)
Selective Grade 3
Working Ambient Temperature -5℃ ~+40℃
Enclosed Protective Class IP20
Nominal Frequency 50/60Hz
Maximum Operating Voltage(Ue) ≥400V AC
Insulation Voltage(Ui) ≥6KV
Voltage Testing Pulse(Uimp) ≥10KA
Maximum Cutting Capacity(Icu) ≥10KA
Electrical Life Not less than 8000 times
Mechanical Life Not less than 20000 times
Dimensions
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB)
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
a B, C, D 1~63
Cold state
1.13In t 1h Non-tripping
b B, C, D
1~63 Immediately after the
previous test 1.45In t<1h Tripping
The current rise steadily
to a fixed value within 5s
c
B, C, D
In≤32
Cold state
2.55In 1s<t<60s Tripping
In 32 Cold state 2.55In 1s<t<120s Tripping
B 1~63
Cold state
3In t≤0.1s Non-tripping
5In t<0.1s Tripping
C
5In t≤0.1s Non-tripping
10I n t<0.1s Tripping
10In t≤0.1s Non-tripping
10In t<0.1s Tripping
Item Model Rated
Current(A) Initial State
Test
Current
Limited
Time
Remark
Limited
Time
Characteristic Curve
YRLB6-63 Characteristic curve
Over current tripping characteristic
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB)
001 www.onerealenergy.com www.onerealenergy.com 002
R
Application conditions
YRLB6-63 have protective function as overload, and are used in lighting distribution system in industry commerce and dwelling, and protect
fractional electric motors. And they also have many merits of high protective grade(up to IP20), high breaking capacity, reliable sensitive,
action convenient, multi pole assembling, long life ect. The are mainly adapted to the circuit of AC 50Hz, 250V in single pole, 415V in double,
three, four poles for protecting overload and short circuit. Mean while, they are also used in turning on or off the electric apparatus
and lighting circuit under the normal conditions.
Standard
Technical Data
ADC C SSERERIEISES
Rated Voltage 230V/400V AC(1P), 400V AC(2P, 3P, 4P)
EN60B98(EC60e98)MEC60947-2
Rated Current 3,6,10,16,20,25,32,40,50,63A
Rated Breaking Capacity 10KA IEC60898( 3~63A)
Characteristic Curve B, C, D
Max. Fuse That Can Be Connected To 100AGL(>10KA)
Selective Grade 3
Working Ambient Temperature -5℃ ~+40℃
Enclosed Protective Class IP20
Nominal Frequency 50/60Hz
Maximum Operating Voltage(Ue) ≥400V AC
Insulation Voltage(Ui) ≥6KV
Voltage Testing Pulse(Uimp) ≥10KA
Maximum Cutting Capacity(Icu) ≥10KA
Electrical Life Not less than 8000 times
Mechanical Life Not less than 20000 times
Dimensions
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB)
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
a B, C, D 1~63
Cold state
1.13In t 1h Non-tripping
b B, C, D
1~63 Immediately after the
previous test 1.45In t<1h Tripping The current rise steadily
to a fixed value within 5s
c
B, C, D
In≤32
Cold state
2.55In 1s<t<60s Tripping
In 32 Cold state 2.55In 1s<t<120s Tripping
B 1~63
Cold state
3In t≤0.1s Non-tripping
5In t<0.1s Tripping
C
5In t≤0.1s Non-tripping
10I n t<0.1s Tripping
10In t≤0.1s Non-tripping
10In t<0.1s Tripping
Item Model Rated
Current(A) Initial State
Test
Current
Limited
Time Remark Limited
Time
Characteristic Curve
YRLB6-63 Characteristic curve
Over current tripping characteristic
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB)
001 www.onerealenergy.com www.onerealenergy.com 002
3A 3.9 3.78 3.69 3.57 3.42 3.3 3.12 3 2.88 2.79 2.64 2.49
6A 7.8 7.56 7.38 7.14 6.84 6.6 6.24 6 5.76 5.64 5.28 4.98
10A 13.2 12.7 12.5 12 11.5 11.1 10.6 10 9.6 9.3 8.9 8.4
16A 21.12 20.48 20 19.2 18.4 17.76 16.96 16 15.36 14.88 14.24 13.44
20A 26.4 25.6 25 24 23 22.2 21.2 20 19.2 18.6 17.8 16.8
25A 33 32 31.25 30 28.75 27.75 26.5 25 24 23.25 22.25 21
32A 42.56 41.28 40 38.72 37.12 35.52 33.93 32 30.72 29.76 28.16 26.88
40A 53.2 51.2 50 48 46.4 44.8 42.4 40 38.4 37.2 35.6 33.6
50A 67 65.5 63 60.5 58 56 53 50 48 46.5 44 41.5
63A 83.79 81.9 80.01 76.86 73.71 73.71 66.78 63 60.48 58.9 55.44 52.29
-35 -30 -20 -10 0 10 20 30 40 50 60 70
Temperature
Temperature
Rated Current (A)
Current correction values used at different ambient temperatures
Current correction factor used at different altitudes
Wire connection terminals
3,6,10,16,20,25,32,40,50,63A 1.0 0.9 0.8
3,6
10
16,20
25
32
48
63
1
1.5
2.5
4
6
10
10
Rated current In(A) Copper wire nominal cross sectional area(mm )
≤2000m 2000~3000m ≥3000m
Different altitude correction factors
Rated Current (A)
R
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB) YRB-63 MINI CIRCUIT BREAKER (AC MCB)
YRB-63 series small circuit breaker has short circuit protection,overload protection, control, isolation and other functions. This seriesof
circuit breakers are suitable for protection of low-voltage terminaldistribution lines in industrial, civil building, energy, communicationand
infrastructure fields with AC frequency 50Hz/60Hz, rated workingvoltage C240/400V and rated working current up to 63A.
Product standard: GB/T 10963.1 IEC 60898-1
YRB-63 series circuit breakers have the characteristics of small size,simple structure and high reliability.The circuit breaker has a varietyof
functional accessories, including auxiliary contact,alarm contact,shunt trip, undervoltage trip, overvoltage trip, overvoltage trip andother
accessories.The width of auxiliary contact and alarm contact inthese accessories is 9mm,and the width of other accessories is18mm.
Application conditions
Model and Meaning
HG B 3 - 63 / C 63 4P
Corporate logo MCB
Design
serial
number
Current she
frame
Tripping
curves
Rated
current
Number
of poles
Main technical parameters
Rated shell current :63A
Product standard :GB/T 10963.1 IEC 60898-1
Rated insulation voltage Ui :500V
Rated impact tolerance voltage Uimp:4kV
Rated current (A):1,2,3,4,6,10,16,20,25,32,40,50,63
Rated voltage :240/400V(1P, 2P),400V(2P, 3P, 4P)
Rated frequency (Hz):50/60
Tripping curve :B(3-5In),C(5-10 in), D(10-20In)
Pole number :1P, 2P, 3P, 3P, 4P
Monopole width: 18mm
Rated short circuit breaking capacity :6kA
Dielectric strength test voltage (l min) :2kV
Reference temperature :30℃
Mechanical life: 20,000 times
Electrical life :4000 times
Protection class :IP20
Wiring capacity (mm2) :25
Line entry mode :top or bottom line can be
ADC C SSERERIEISES YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
001 www.onerealenergy.com www.onerealenergy.com 002
3A 3.9 3.78 3.69 3.57 3.42 3.3 3.12 3 2.88 2.79 2.64 2.49
6A 7.8 7.56 7.38 7.14 6.84 6.6 6.24 6 5.76 5.64 5.28 4.98
10A 13.2 12.7 12.5 12 11.5 11.1 10.6 10 9.6 9.3 8.9 8.4
16A 21.12 20.48 20 19.2 18.4 17.76 16.96 16 15.36 14.88 14.24 13.44
20A 26.4 25.6 25 24 23 22.2 21.2 20 19.2 18.6 17.8 16.8
25A 33 32 31.25 30 28.75 27.75 26.5 25 24 23.25 22.25 21
32A 42.56 41.28 40 38.72 37.12 35.52 33.93 32 30.72 29.76 28.16 26.88
40A 53.2 51.2 50 48 46.4 44.8 42.4 40 38.4 37.2 35.6 33.6
50A 67 65.5 63 60.5 58 56 53 50 48 46.5 44 41.5
63A 83.79 81.9 80.01 76.86 73.71 73.71 66.78 63 60.48 58.9 55.44 52.29
-35 -30 -20 -10 0 10 20 30 40 50 60 70
Temperature
Temperature
Rated Current (A)
Current correction values used at different ambient temperatures
Current correction factor used at different altitudes
Wire connection terminals
3,6,10,16,20,25,32,40,50,63A 1.0 0.9 0.8
3,6
10
16,20
25
32
48
63
1
1.5
2.5
4
6
10
10
Rated current In(A) Copper wire nominal cross sectional area(mm )
≤2000m 2000~3000m ≥3000m
Different altitude correction factors
Rated Current (A)
R
YRLB6-63 MINI CIRCUIT BREAKER (AC MCB) YRB-63 MINI CIRCUIT BREAKER (AC MCB)
YRB-63 series small circuit breaker has short circuit protection,overload protection, control, isolation and other functions. This seriesof
circuit breakers are suitable for protection of low-voltage terminaldistribution lines in industrial, civil building, energy, communicationand
infrastructure fields with AC frequency 50Hz/60Hz, rated workingvoltage C240/400V and rated working current up to 63A.
Product standard: GB/T 10963.1 IEC 60898-1
YRB-63 series circuit breakers have the characteristics of small size,simple structure and high reliability.The circuit breaker has a varietyof
functional accessories, including auxiliary contact,alarm contact,shunt trip, undervoltage trip, overvoltage trip, overvoltage trip andother
accessories.The width of auxiliary contact and alarm contact inthese accessories is 9mm,and the width of other accessories is18mm.
Application conditions
Model and Meaning
HG B 3 - 63 / C 63 4P
Corporate logo MCB
Design
serial
number
Current she
frame
Tripping
curves
Rated
current
Number
of poles
Main technical parameters
Rated shell current :63A
Product standard :GB/T 10963.1 IEC 60898-1
Rated insulation voltage Ui :500V
Rated impact tolerance voltage Uimp:4kV
Rated current (A):1,2,3,4,6,10,16,20,25,32,40,50,63
Rated voltage :240/400V(1P, 2P),400V(2P, 3P, 4P)
Rated frequency (Hz):50/60
Tripping curve :B(3-5In),C(5-10 in), D(10-20In)
Pole number :1P, 2P, 3P, 3P, 4P
Monopole width: 18mm
Rated short circuit breaking capacity :6kA
Dielectric strength test voltage (l min) :2kV
Reference temperature :30℃
Mechanical life: 20,000 times
Electrical life :4000 times
Protection class :IP20
Wiring capacity (mm2) :25
Line entry mode :top or bottom line can be
ADC C SSERERIEISES YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
001 www.onerealenergy.com www.onerealenergy.com 002
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
www.onerealenergy.com 002
FE7-63 MINI CIRCUIT BREAKER (AC MCB)
Appearance and installation dimensions
001 www.onerealenergy.com
R
Application conditions
YRB-125 series mini-circuit breaker is a high-performance mini-circuit breaker with important characteristics such as large ratedcurrent
and high rated short-circuit breaking capability.The circuitbreaker is mainly suitable for distribution lines with rated workingfrequency of
50Hz/60Hz,rated working voltage of AC240/400v andrated current up to 125A. It is used to protect over current and shortcircuit of power
line facilities and important electrical equipment inimportant buildings or similar places. It can also be used forinfrequent on-off
operation.The circuit breaker is also suitable forisolation.Product standard: GB/T 14048.2, IEC 60947-2.
YRB-125 MINI CIRCUIT BREAKER (AC MCB)
Structural characteristics of
High rated short circuit breaking ability, all rated current levels canreach 6kA.
With red green safety indication, higher safety.
With energy storage mechanism operation,contact fast closure,overcome the adverse influence caused by the speed of manualoperation
handle,greatly improve the service life of the product.
The product can be used with a variety of modular accessories,such as AX-1.
Model and Meaning
YR B 3 - 125 / C 125 4P
Corporate logo MCB
Design
serial
number
Product
standard
code
Current
shell
frame
Rated
current
Number
of poles
Main technical parameters
Product shell current :125A
Comply with the standard: GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 1000V
Rated impact tolerance voltage Uimp: 6kV
Rated current In:16A,20A,25A,32A,40A,50A,63A,80A,100A,125A
Rated voltage Ue: 240/400V (1P, 2P),400V(2P,3P,4P)
Rated frequency :50Hz/6OHz
Tripping curve :C:8ln±20%,D:12In±20%
Number: 1 p,2p,3p,4p
Monopole width: 18mm
Limit short-circuit breaking capacity lcu:10kA
Running short circuit breaking capability lcs:7.5kA
Base temperature :30℃
Use category :A
Mechanical life :20,000 times
Electrical life: 6000 times
Tripping characteristics
Rated current (A)
lns≤63
ln>63
Overload trip characteristics
1.13ln Agreed nontiptime H (cold state)
1
2
1.45In Agreed
triptime H (hot state)
1
2
lnstantaneous
tripcharacteristics(A)
B(3-5In),C(5-10ln)
D(10-20In)
Rated residual
operating current
10,30,100,300mA
ADC C SSERERIEISES
Model TH35-7.5 Mounting guide rail dimensions
DZ47LE-63
4P:72+72 3P+N:54+72
3P:54+54 2P: 36+36
1P+N:18+36
DZ47LE-63
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
www.onerealenergy.com 002
FE7-63 MINI CIRCUIT BREAKER (AC MCB)
Appearance and installation dimensions
001 www.onerealenergy.com
R
Application conditions
YRB-125 series mini-circuit breaker is a high-performance mini-circuit breaker with important characteristics such as large ratedcurrent
and high rated short-circuit breaking capability.The circuitbreaker is mainly suitable for distribution lines with rated workingfrequency of
50Hz/60Hz,rated working voltage of AC240/400v andrated current up to 125A. It is used to protect over current and shortcircuit of power
line facilities and important electrical equipment inimportant buildings or similar places. It can also be used forinfrequent on-off
operation.The circuit breaker is also suitable forisolation.Product standard: GB/T 14048.2, IEC 60947-2.
YRB-125 MINI CIRCUIT BREAKER (AC MCB)
Structural characteristics of
High rated short circuit breaking ability, all rated current levels canreach 6kA.
With red green safety indication, higher safety.
With energy storage mechanism operation,contact fast closure,overcome the adverse influence caused by the speed of manualoperation
handle,greatly improve the service life of the product.
The product can be used with a variety of modular accessories,such as AX-1.
Model and Meaning
YR B 3 - 125 / C 125 4P
Corporate logo MCB
Design
serial
number
Product
standard
code
Current
shell
frame
Rated
current
Number
of poles
Main technical parameters
Product shell current :125A
Comply with the standard: GB/T 14048.2,IEC 60947-2
Rated insulation voltage Ui: 1000V
Rated impact tolerance voltage Uimp: 6kV
Rated current In:16A,20A,25A,32A,40A,50A,63A,80A,100A,125A
Rated voltage Ue: 240/400V (1P, 2P),400V(2P,3P,4P)
Rated frequency :50Hz/6OHz
Tripping curve :C:8ln±20%,D:12In±20%
Number: 1 p,2p,3p,4p
Monopole width: 18mm
Limit short-circuit breaking capacity lcu:10kA
Running short circuit breaking capability lcs:7.5kA
Base temperature :30℃
Use category :A
Mechanical life :20,000 times
Electrical life: 6000 times
Tripping characteristics
Rated current (A)
lns≤63
ln>63
Overload trip characteristics
1.13ln Agreed nontiptime H (cold state)
1
2
1.45In Agreed
triptime H (hot state)
1
2
lnstantaneous
tripcharacteristics(A)
B(3-5In),C(5-10ln)
D(10-20In)
Rated residual
operating current
10,30,100,300mA
ADC C SSERERIEISES
Model TH35-7.5 Mounting guide rail dimensions
DZ47LE-63
4P:72+72 3P+N:54+72
3P:54+54 2P: 36+36
1P+N:18+36
DZ47LE-63
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
www.onerealenergy.com 002
YRB-125 MINI CIRCUIT BREAKER ACCESSORIES
Product trip characteristics
Rated current (A)
lns≤125
ln>125
Overload trip characteristics
1
2
1
2
Instantaneous trip
characteristics(A)
10,30,100,300mA
1.05In Agreed non-trip
time H (cold state)
1.30In Agreed trip
time H (hot state)
Appearance and installation dimensions
001 www.onerealenergy.com
R
ADC C SSERERIEISES
Not over altitude 2000m
Ambient temperature is between -5℃ to+40℃
Withstand the influence of moist air;
Withstand the influence of smoke fog,salt mist;
Withstand the influence of fungus;
The max. gradient is 22.5℃;
Working reliable under the condition of normal vibration in ship;
Working reliable under the condition of earth quake(4g);
Working in the medium which not any explosive, no enough dielectric to corrode metal, no gas
to damage insulation and elctric conduction dust.
Working in the place would not be invaded by rain and snow.
According to the pole number of products,it classifles two-pole(100A, 225A), three-pole(no
four-pole for GDM1(YRM1)-800), the neutral pole(N-pole) of the four-pole breakers has four types;
TypeA: N-pole without over-current release unit, it has been connected all along, and does not
act with other three-pole to turn on or off.
Type B: N-pole without over-current release unit, it could act with other three-pole;
Type C: N-pole flxed with over-current release unit, it could act with other three-pole;
Type D: N-pole flxed with over-current release unit, it has been connected all along, and does
not act with other three-pole to turn on and off.
According to rated current of products, ticlassifles:
GDM1(YRM1)-63: (6),10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, (no over-load protection for 6A);
GDM1(YRM1)-125: (10), 10A,16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A,100A, 125A;
GDM1(YRM1)-250: 100A, 125A, 140A, 160A,180A, 200A, 225A, 250A;
GDM1(YRM1)-400: 225A, 250A, 315A, 350A, 400A;
GDM1(YRM1)-630: 400A, 500A, 630A;
GDM1(YRM1)-800: 630A, 700A, 800A;
According to connection mode, it classifles front in wiring,rear in wiring, and plug in type.
According to over-current release type, it classifles the thermodynamic-magnetic (binary) type
and magnetic (instantaneous) releases.
●
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Application conditions
GDM1(YRM1) series moulded case circuit breaker is a new type
product developed and manufactured by Adopting international
advanced technology. It is supplied with rated insulation voltage
800V and used for circuit of AC 50Hz, rated operation voltage AC
400V or below rated operation current up to 1600A for infrequent
changing over and starting of the motors. Equipped with the
protection devices for over-current, short circuit and under voltage,
the product is capable of preventing damage of circuits and supply
units. The product conforms to IEC60947-2 standard.
Working Condition
●
●
●
●
●
●
●
●
●
Working Condition
●
●
●
●
Working Condition
The thermodynamic of a circuit breaker provides the feature of inverse time-delay,while the magnetic release the instantaneous operation
as shown on Table 1 (distribution circuit breaker)and Table 2 (motor protection circuit breaker):
Model TH35-7.5 Mounting guide rail dimensions
YRB SERIES MINI CIRCUIT BREAKER (AC MCB)
www.onerealenergy.com 002
YRB-125 MINI CIRCUIT BREAKER ACCESSORIES
Product trip characteristics
Rated current (A)
lns≤125
ln>125
Overload trip characteristics
1
2
1
2
Instantaneous trip
characteristics(A)
10,30,100,300mA
1.05In Agreed non-trip
time H (cold state)
1.30In Agreed trip
time H (hot state)
Appearance and installation dimensions
001 www.onerealenergy.com
R
ADC C SSERERIEISES
Not over altitude 2000m
Ambient temperature is between -5℃ to+40℃
Withstand the influence of moist air;
Withstand the influence of smoke fog,salt mist;
Withstand the influence of fungus;
The max. gradient is 22.5℃;
Working reliable under the condition of normal vibration in ship;
Working reliable under the condition of earth quake(4g);
Working in the medium which not any explosive, no enough dielectric to corrode metal, no gas
to damage insulation and elctric conduction dust.
Working in the place would not be invaded by rain and snow.
According to the pole number of products,it classifles two-pole(100A, 225A), three-pole(no
four-pole for GDM1(YRM1)-800), the neutral pole(N-pole) of the four-pole breakers has four types;
TypeA: N-pole without over-current release unit, it has been connected all along, and does not
act with other three-pole to turn on or off.
Type B: N-pole without over-current release unit, it could act with other three-pole;
Type C: N-pole flxed with over-current release unit, it could act with other three-pole;
Type D: N-pole flxed with over-current release unit, it has been connected all along, and does
not act with other three-pole to turn on and off.
According to rated current of products, ticlassifles:
GDM1(YRM1)-63: (6),10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, (no over-load protection for 6A);
GDM1(YRM1)-125: (10), 10A,16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A,100A, 125A;
GDM1(YRM1)-250: 100A, 125A, 140A, 160A,180A, 200A, 225A, 250A;
GDM1(YRM1)-400: 225A, 250A, 315A, 350A, 400A;
GDM1(YRM1)-630: 400A, 500A, 630A;
GDM1(YRM1)-800: 630A, 700A, 800A;
According to connection mode, it classifles front in wiring,rear in wiring, and plug in type.
According to over-current release type, it classifles the thermodynamic-magnetic (binary) type
and magnetic (instantaneous) releases.
●
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Application conditions
GDM1(YRM1) series moulded case circuit breaker is a new type
product developed and manufactured by Adopting international
advanced technology. It is supplied with rated insulation voltage
800V and used for circuit of AC 50Hz, rated operation voltage AC
400V or below rated operation current up to 1600A for infrequent
changing over and starting of the motors. Equipped with the
protection devices for over-current, short circuit and under voltage,
the product is capable of preventing damage of circuits and supply
units. The product conforms to IEC60947-2 standard.
Working Condition
●
●
●
●
●
●
●
●
●
Working Condition
●
●
●
●
Working Condition
The thermodynamic of a circuit breaker provides the feature of inverse time-delay,while the magnetic release the instantaneous operation
as shown on Table 1 (distribution circuit breaker)and Table 2 (motor protection circuit breaker):
Model TH35-7.5 Mounting guide rail dimensions
www.onerealenergy.com 002
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Rated current of release(A)
Thermodynamic release(ambient temp:land+40℃ ,marin+45℃ )
current(A) 1.05ln(cold state) Non-action time(h) 1.30ln(Hot state) Action time(h)
10≤ln≤63 1 1
10ln±20%
63≤ln≤100 2 2
100≤ln≤800 2 2
5ln±20%
10ln±20%
Table 1(for distribution)
Table 1(for distribution)
Thermodynamic release(ambient temp:land+40℃ ,marin+45℃ )
10≤ln≤255
2 2
4min 4s<Tp≤10s
12ln±20%
225≤ln≤800 8min 6s<Tp≤20s
Note:No 5ln magnetic release on 100A, 125A or FEM1-160 and FEM1-225.
Technical Data
Model
Overall Dimension
L H A B 4-Φd
GDM1(YRM1)-63L
63 6,10,16,20,
25,32,40,50,63 AC400V AC500V
25 18 135 78 73.5
25 117 Φ3.5
GDM1(YRM1)-63M 50 35 135 78/103 81.5
GDM1(YRM1)-125L
125
10,16,20,25,
32,40,50,63
80,100,125
AC690V AC800V
35 22 150 92 68
GDM1(YRM1)-125M 50 35 03 129 Φ4.5
150 92/122 86
GDM1(YRM1)-125H 85 50
GDM1(YRM1)-250L
250
100,125,140,
160,180,200,
225,250
AC690V AC800V
35 22 165 107 86
GDM1(YRM1)-250M 50 35 35 12 Φ4.5
165 107/142 103
GDM1(YRM1)-250H 85 50
GDM1(YRM1)-400L
400 225,250,315,
350,400 AC690V AC800V
50 35 257 150/198 105 44 194 Φ7
GDM1(YRM1)-400M 65 42
257 150 106.5 44 194 Φ7
GDM1(YRM1)-400H 100 65
GDM1(YRM1)-630L
630 400,500,630 AC690V AC800V
50 35 270 182/240 110
58 200 Φ7
GDM1(YRM1)-630M 65 42 270 182 110
GDM1(YRM1)-630H 100 65 275 210 115.5 70 243 Φ7
GDM1(YRM1)-800M
800 630,700,800 AC690V AC800V
75 50
275 210 115.5 70 243 Φ7
GDM1(YRM1)-800H 100 65
Rated Current
Value 10 16.20 25 32 40.50 63 80 100 125 160 180,220,225 250 315,350 400
Cable(mm²) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 185 240
See Table 4 for sectional area of connecting conductor and the proper rated current:
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Rated current of
release(A) 1.0ln(cold state) Nonaction time(h)
1.20ln(Hot state)
Action time(h)
1.50ln(Hot state)
Action time(h)
7.2ln(cold state)
Nonaction time(h)
Electromagnetic
release action
current(A)
Mounting
Dimension(Front
in Wiring)
W
3P/4P
Rated
Frame
Current
(A)
Rated Current
(A)
Rated
Working
Voltage
(V)
Rated
Insulated
Voltage
(V)
Rated Ultimate
Short-circuit
Breaking
Capacity
KA 400V
Rated Runing
Breaking
Capacity KA
400V
001 www.onerealenergy.com
Rated Current Value
Cable Copper Row
Cable(mm²) Quantitly Dimension(mm) Quantitly
500 150 2 30×5 2
630 185 2 40×5 2
700,800 200 2 40×5 2
Table5
The accessories are fixed into the circuit breaker.
Remote tripping:
MX or MN releases are used to trip the circuit breaker.
This release trips the circuit breaker when the control voltage drops
below the trip-ping threshold:
Tripping threshold between 35% to 70% of the rated voltage
Circuit-breaker closing is possible only if the voltage exceeds
85% of the rated voltage.
Circuit-breaker tripping by an MN release meets the require
ments of standard IEC 60947-2.
Application conditions
●
●
●
●
●
Moulded Case Circuit Breaker Accessories
MX(Shunt Release)
Technical Data
Rated Control Voltage Us(V) 230V, 400V AC
Operating Voltage(V) (0.7-1.1) Us
Indication contacts
These common-point changeover contacts can be used to
remotely indicate circuit-breaker status information for indications,
electrical locking, relays, etc.
They comply with international standard IEC 60947-5.
Functions
OF (ON/OFF): indicates the position of the circuit-breaker contacts.
SD (trip indication): indicates that the circuit-breaker has tripped
due to: • overload, • short-circuit, • operation of a voltage release,
• operation of the “ push-to-trip ” button Returns to de-energised
state when the circuit breaker is reset.
●
●
●
●
●
●
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
www.onerealenergy.com 002
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Rated current of release(A)
Thermodynamic release(ambient temp:land+40℃ ,marin+45℃ )
current(A)
1.05ln(cold state) Non-action time(h) 1.30ln(Hot state) Action time(h)
10≤ln≤63 1 1
10ln±20%
63≤ln≤100 2 2
100≤ln≤800 2 2
5ln±20%
10ln±20%
Table 1(for distribution)
Table 1(for distribution)
Thermodynamic release(ambient temp:land+40℃ ,marin+45℃ )
10≤ln≤255
2 2
4min 4s<Tp≤10s
12ln±20%
225≤ln≤800 8min 6s<Tp≤20s
Note:No 5ln magnetic release on 100A, 125A or FEM1-160 and FEM1-225.
Technical Data
Model
Overall Dimension
L H A B 4-Φd
GDM1(YRM1)-63L
63
6,10,16,20,
25,32,40,50,63
AC400V AC500V
25 18 135 78 73.5
25 117 Φ3.5
GDM1(YRM1)-63M 50 35 135 78/103 81.5
GDM1(YRM1)-125L
125
10,16,20,25,
32,40,50,63
80,100,125
AC690V AC800V
35 22 150 92 68
GDM1(YRM1)-125M 50 35 03 129 Φ4.5
150 92/122 86
GDM1(YRM1)-125H 85 50
GDM1(YRM1)-250L
250
100,125,140,
160,180,200,
225,250
AC690V AC800V
35 22 165 107 86
GDM1(YRM1)-250M 50 35 35 12 Φ4.5
165 107/142 103
GDM1(YRM1)-250H 85 50
GDM1(YRM1)-400L
400
225,250,315,
350,400
AC690V AC800V
50 35 257 150/198 105 44 194 Φ7
GDM1(YRM1)-400M 65 42
257 150 106.5 44 194 Φ7
GDM1(YRM1)-400H 100 65
GDM1(YRM1)-630L
630 400,500,630 AC690V AC800V
50 35 270 182/240 110
58 200 Φ7
GDM1(YRM1)-630M 65 42 270 182 110
GDM1(YRM1)-630H 100 65 275 210 115.5 70 243 Φ7
GDM1(YRM1)-800M
800 630,700,800 AC690V AC800V
75 50
275 210 115.5 70 243 Φ7
GDM1(YRM1)-800H 100 65
Rated Current
Value
10 16.20 25 32 40.50 63 80 100 125 160 180,220,225 250 315,350 400
Cable(mm²) 1.5 2.5 4 6 10 16 25 35 50 70 95 120 185 240
See Table 4 for sectional area of connecting conductor and the proper rated current:
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
Rated current of
release(A) 1.0ln(cold state) Nonaction time(h)
1.20ln(Hot state)
Action time(h)
1.50ln(Hot state)
Action time(h)
7.2ln(cold state)
Nonaction time(h)
Electromagnetic
release action
current(A)
Mounting
Dimension(Front
in Wiring)
W
3P/4P
Rated
Frame
Current
(A)
Rated Current
(A)
Rated
Working
Voltage
(V)
Rated
Insulated
Voltage
(V)
Rated Ultimate
Short-circuit
Breaking
Capacity
KA 400V
Rated Runing
Breaking
Capacity KA
400V
001 www.onerealenergy.com
Rated Current Value
Cable Copper Row
Cable(mm²) Quantitly Dimension(mm) Quantitly
500 150 2 30×5 2
630 185 2 40×5 2
700,800 200 2 40×5 2
Table5
The accessories are fixed into the circuit breaker.
Remote tripping:
MX or MN releases are used to trip the circuit breaker.
This release trips the circuit breaker when the control voltage drops
below the trip-ping threshold:
Tripping threshold between 35% to 70% of the rated voltage
Circuit-breaker closing is possible only if the voltage exceeds
85% of the rated voltage.
Circuit-breaker tripping by an MN release meets the require
ments of standard IEC 60947-2.
Application conditions
●
●
●
●
●
Moulded Case Circuit Breaker Accessories
MX(Shunt Release)
Technical Data
Rated Control Voltage Us(V) 230V, 400V AC
Operating Voltage(V) (0.7-1.1) Us
Indication contacts
These common-point changeover contacts can be used to
remotely indicate circuit-breaker status information for indications,
electrical locking, relays, etc.
They comply with international standard IEC 60947-5.
Functions
OF (ON/OFF): indicates the position of the circuit-breaker contacts.
SD (trip indication): indicates that the circuit-breaker has tripped
due to: • overload, • short-circuit, • operation of a voltage release,
• operation of the “ push-to-trip ” button Returns to de-energised
state when the circuit breaker is reset.
●
●
●
●
●
●
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
GDM1(YRM1) MOULDED CASE CIRCUIT BREAKER(AC MCCB)
www.onerealenergy.com 002
R
ADC C SSERERIEISES
YRPS1-A40 TYPE 1 AC SURGE PROTECTIVE DEVICE
Large discharge energy
No leakage
No follow current
Modular installation
High safety coeffcient
Long service life
Strong environmental resistance
Voltage protection level is less than 2500V
Main power distribution panel in buildings
Overhead distribution box in buildings
Outdoor distribution cabinet/distribution box
Application conditions
●
●
●
●
●
●
●
●
The scope of products
●
●
●
YRPS1-A40 series voltage limiting type/voltage switching type primary power surge protectors with high flow capacity ,single module impact
current up to 50kA(10/350s),can prevent all kinds of lightning surge.Products are applies to the power supply of the equipment system in the
higher risk area of lightning strike.The first surge protection can be used in single phase/three-phase power supply line.
YRPS1-A40 series voltage limiting type/voltage switching type primary power surge
protectors are designed according to IEC and EN 61643 standars,and applied to surge
protection at the ?rst stage of the power supply system.Products are standard 35mm rail
mounting methods.
Product capability parameter
Model YRPS1-A15 YRPS1-A25 YRPS1-A50
SPD port 2 Poles 3Poles 4Poles
SPD category Voltage limited type
Test category
Un
Uc
Insulation resistance
Iimep(10/350μs)
Up(1.2/50μs)
tA
Size
Sectional area of wires
Installation method
Woeking environment temperature
Sheathing material
Protection level
Autehntication
Voltage limited type Voltage limited type
Class l test Class l test Class l test
220/380VAC; 50/60Hz
275/385/420VAC; 50/60Hz
>100MΩ >100MΩ >100MΩ
15kA 25kA 50kA
1.5kV 1.5kV 1.8kV
≤100ns ≤100ns ≤100ns
144×90×66 144×90×66 144×90×66
6~25mm² 6~25mm ² 6~25mm²
35mm standard rail(EN50022/DIN46277-3)
-40~85℃
Plastic,accord with UL94 V-0
IP20
CQC CE Type test
001 www.onerealenergy.com
YRPS1-40 TYPE 2 AC SURGE PROTECTIVE DEVICE
YRP1-40 series surge protection device (in short SPD,alias:surge suppressor surge arrester)
is suitable for TN-S, TN-C-S, TT, IT etc, power supply system of AC 50/60Hz,<380V, installed
on the joint of LPZ1 or LPZ2 and LPZ3. It's designed according to IEC61643-1, GB18802.1, it
adopts 35mm standard rail, there is a failure release mounted on the module of surge protection
device, When the SPD fails in breakdown for over heat and over-current, the failure release will
help electric equipments separate from the power supply system and give the indication signal,
green means normal, red means abnormal, it also could be replaced for the module when has
operating voltage.
Application conditions
Inside over-current and over-heat protection, temperature control open circuit.
Module design, convenient installation, could be replaced online.
Time of response <25ns
The color of visible window shows operating status, green means normal, red means abnormal
The scope of products
●
●
●
●
Technical Parameters
Pole 1P 2P 3P 4P
Rated Operating Voltage Un(V~) 230V/275V 385V/420V
Maximum Continuous Operating Voltage Uc(V~) 275/385/420VAC
Voltage protection Level Up(V~)kV ≤2.5
Nominal Discharge Current lnμ s kA 5 20 30 40 60
Maximum Discharge Current lmax μs kA 10 40 60 80 100
Response Time (ns) <25
Test Standard IEC61643.1, GB18802.1
Operating Environment(centigrade) -40℃ ~+85℃
Max Connection Line 35mm2 hard wire/35mm2 strand wire copper line
Recommended Connection Line 16mm2 hard wire/25mm2 strand wire copper line
Installation Standard Rail 35mm
Material of Outer Covering Burning-proof Nylon
Specifications
Overall Dimensions
AC SPD SERIES SURGE PROTECTIVE DEVICE
www.onerealenergy.com 002
R
ADC C SSERERIEISES
YRPS1-A40 TYPE 1 AC SURGE PROTECTIVE DEVICE
Large discharge energy
No leakage
No follow current
Modular installation
High safety coeffcient
Long service life
Strong environmental resistance
Voltage protection level is less than 2500V
Main power distribution panel in buildings
Overhead distribution box in buildings
Outdoor distribution cabinet/distribution box
Application conditions
●
●
●
●
●
●
●
●
The scope of products
●
●
●
YRPS1-A40 series voltage limiting type/voltage switching type primary power surge protectors with high flow capacity ,single module impact
current up to 50kA(10/350s),can prevent all kinds of lightning surge.Products are applies to the power supply of the equipment system in the
higher risk area of lightning strike.The first surge protection can be used in single phase/three-phase power supply line.
YRPS1-A40 series voltage limiting type/voltage switching type primary power surge
protectors are designed according to IEC and EN 61643 standars,and applied to surge
protection at the ?rst stage of the power supply system.Products are standard 35mm rail
mounting methods.
Product capability parameter
Model YRPS1-A15 YRPS1-A25 YRPS1-A50
SPD port 2 Poles 3Poles 4Poles
SPD category Voltage limited type
Test category
Un
Uc
Insulation resistance
Iimep(10/350μs)
Up(1.2/50μs)
tA
Size
Sectional area of wires
Installation method
Woeking environment temperature
Sheathing material
Protection level
Autehntication
Voltage limited type Voltage limited type
Class l test Class l test Class l test
220/380VAC; 50/60Hz
275/385/420VAC; 50/60Hz
>100MΩ >100MΩ >100MΩ
15kA 25kA 50kA
1.5kV 1.5kV 1.8kV
≤100ns ≤100ns ≤100ns
144×90×66 144×90×66 144×90×66
6~25mm² 6~25mm ² 6~25mm²
35mm standard rail(EN50022/DIN46277-3)
-40~85℃
Plastic,accord with UL94 V-0
IP20
CQC CE Type test
001 www.onerealenergy.com
YRPS1-40 TYPE 2 AC SURGE PROTECTIVE DEVICE
YRP1-40 series surge protection device (in short SPD,alias:surge suppressor surge arrester)
is suitable for TN-S, TN-C-S, TT, IT etc, power supply system of AC 50/60Hz,<380V, installed
on the joint of LPZ1 or LPZ2 and LPZ3. It's designed according to IEC61643-1, GB18802.1, it
adopts 35mm standard rail, there is a failure release mounted on the module of surge protection
device, When the SPD fails in breakdown for over heat and over-current, the failure release will
help electric equipments separate from the power supply system and give the indication signal,
green means normal, red means abnormal, it also could be replaced for the module when has
operating voltage.
Application conditions
Inside over-current and over-heat protection, temperature control open circuit.
Module design, convenient installation, could be replaced online.
Time of response <25ns
The color of visible window shows operating status, green means normal, red means abnormal
The scope of products
●
●
●
●
Technical Parameters
Pole 1P 2P 3P 4P
Rated Operating Voltage Un(V~) 230V/275V 385V/420V
Maximum Continuous Operating Voltage Uc(V~) 275/385/420VAC
Voltage protection Level Up(V~)kV ≤2.5
Nominal Discharge Current lnμ s kA 5 20 30 40 60
Maximum Discharge Current lmax μs kA 10 40 60 80 100
Response Time (ns) <25
Test Standard IEC61643.1, GB18802.1
Operating Environment(centigrade) -40℃ ~+85℃
Max Connection Line 35mm2 hard wire/35mm2 strand wire copper line
Recommended Connection Line 16mm2 hard wire/25mm2 strand wire copper line
Installation Standard Rail 35mm
Material of Outer Covering Burning-proof Nylon
Specifications
Overall Dimensions
AC SPD SERIES SURGE PROTECTIVE DEVICE
www.onerealenergy.com 002
GDS1-100 TYPE 1 AC SURGE PROTECTIVE DEVICE
Type 1 + 2 SPD’s have characteris cs of type 1 but also type2, they are capable of
discharging a very high lightning current (T1 10/350μs) and they have as well a low
residual voltage (Up). They are installed in the main distribu on switchboard but also in
subdistribu- on board. Because of their power, Type 1 + 2 SPD’s can let pass through
a too high residual voltage, if the announced Up is not compa ble with the withstand
voltage of the equipment to protect or if the cable length to the equipment is longer than
10m,
Application conditions
Patented QuickSafe ® technology Safety Reserve system
Din rail moun ng
Improved safety Back up protec on up to 160 A Fuse or 125 A Mcb
●
● ●
● ●
● Pluggable
Key characteristics
Protection mode L-N/L-PE/N-PE
Number of protected lines 1-4
Test class I-II
lntegrated thermal disconnector Yes
End of life indicator Yes
Safety reserve Yes
Safety reserve
Electrical characteristics
Nominal discharge current /n (8/20) kA
Maximal discharge current /max (8/20) kA
lmpulse current /imp (10/350) kA
maximal continuous operating voltage Uc
Type of current/frequency
Voltage protection level at ln Up(L-PE)
Voltage protection level at ln Up(L-N)
Voltage protection level at ln Up(N-PE)
Short circuit withstand /SCCR
Total current /TOTAL
Follow current interrupted /fi
Ground residual current /PE
TOV withstand(L-N:5s/N-PE:200 ms) UT
Voltage Combination Wave Uoc
Features
V
Hz
kV
kV
kV
kA
kA
kA
μA
V
kV
20
40
7
275/385/420
a.c.50/60
1,2
-
-
100
20
-/-
<350
337
20
Features
001 www.onerealenergy.com
R
ADC C SSERERIEISES AC SPD SERIES SURGE PROTECTIVE DEVICE
GDS1-100 TYPE 1 AC SURGE PROTECTIVE DEVICE
A
A
HxWxD mm 89×18×69
mm² 2.5...25
mm² 12.5
mm Per 1
piece
m 2000
g 150
ns 25
<V-0
Required thermal/back up protection
Curve B or C Circuit breaker
gG-gL fuse
Comments
Mechanical characteristics
Dimensions
Wire range:Solid wire
Wire range:Stranded wire
Stripping length
Packing quantities
Miscellaneous characteristics
Maximal altitude
Weight
Response time
Fire resistance according to UL 94
≤125
≤160
Product details
Dimensions
www.onerealenergy.com 002
GDS1-100 TYPE 1 AC SURGE PROTECTIVE DEVICE
Type 1 + 2 SPD’s have characteris cs of type 1 but also type2, they are capable of
discharging a very high lightning current (T1 10/350μs) and they have as well a low
residual voltage (Up). They are installed in the main distribu on switchboard but also in
subdistribu- on board. Because of their power, Type 1 + 2 SPD’s can let pass through
a too high residual voltage, if the announced Up is not compa ble with the withstand
voltage of the equipment to protect or if the cable length to the equipment is longer than
10m,
Application conditions
Patented QuickSafe ® technology Safety Reserve system
Din rail moun ng
Improved safety Back up protec on up to 160 A Fuse or 125 A Mcb
●
● ●
● ●
● Pluggable
Key characteristics
Protection mode L-N/L-PE/N-PE
Number of protected lines 1-4
Test class I-II
lntegrated thermal disconnector Yes
End of life indicator Yes
Safety reserve Yes
Safety reserve
Electrical characteristics
Nominal discharge current /n (8/20) kA
Maximal discharge current /max (8/20) kA
lmpulse current /imp (10/350) kA
maximal continuous operating voltage Uc
Type of current/frequency
Voltage protection level at ln Up(L-PE)
Voltage protection level at ln Up(L-N)
Voltage protection level at ln Up(N-PE)
Short circuit withstand /SCCR
Total current /TOTAL
Follow current interrupted /fi
Ground residual current /PE
TOV withstand(L-N:5s/N-PE:200 ms) UT
Voltage Combination Wave Uoc
Features
V
Hz
kV
kV
kV
kA
kA
kA
μA
V
kV
20
40
7
275/385/420
a.c.50/60
1,2
-
-
100
20
-/-
<350
337
20
Features
001 www.onerealenergy.com
R
ADC C SSERERIEISES AC SPD SERIES SURGE PROTECTIVE DEVICE
GDS1-100 TYPE 1 AC SURGE PROTECTIVE DEVICE
A
A
HxWxD mm 89×18×69
mm² 2.5...25
mm² 12.5
mm Per 1
piece
m 2000
g 150
ns 25
<V-0
Required thermal/back up protection
Curve B or C Circuit breaker
gG-gL fuse
Comments
Mechanical characteristics
Dimensions
Wire range:Solid wire
Wire range:Stranded wire
Stripping length
Packing quantities
Miscellaneous characteristics
Maximal altitude
Weight
Response time
Fire resistance according to UL 94
≤125
≤160
Product details
Dimensions
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
Making and Breaking Capacity
Utilization Category
Making and Breaking Test Condition
I/Ie U/Ue CosΦ Electrical time(s) Duration of cycle(min) Number of operating cycles
Ac-B33 6.0 1.05 0.5 0.05 ≤5 12
Note: AC-B33 motor load or combined load inccluding motor and resistance load under infrequent operation condition
Specifications
The inlet and outlet line & neutral line of normal and ready power shall be properly wired according to actual requirement of circuit desige.
The outlet terminals of the two circuit breaker shall be connected in parallel with accordant phase order(refer to the wiring diagram).
As for 3P circuit breaker, the neutral line must be connected to the terminal of neutral line(the normal and reserve neutral line as shown in
the fig. 2 Shall be respectively connected to NO.1 and 2 connection terminal).
Installation
1.Main circuit wiring diagram
2.External power ON indication and fire protection power wiring diagram
3.When manual operation is required for the transfer switch, as for YRQ1(CB级)-63 type, button switch shall be put to manual position first,
then transfer or normal or reseve power can be made by turing the handle, as for YRQ1(CB级)-63 type, transfer or normal or reserve power
ccan be made only by pushing manual/auto button until the manual indicator is on, when the control mode is in automatic position, the
transfer will enter automatic work condition and the normal power will operate preferentially.
4.When the transfer switch is wired according to wiring diagram, after power on, if the normal and reserve power are in good condition, the
indicator(red) of normal or reserve power will be on and the transfer switch will work normally.
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
www.onerealenergy.com 002
YRQ1(CB级)-LKRY Micro-Breaking Dual Power Transfer Switch (hereinafterreferred to
as transfer switch) is suitable for AC 50/60Hz dual power supoly system with rated
operating voltage of 400V amd rated operating current form 16~63A. Optional transfer
of dual power can be made according to requirement,. The product owns short circuit,
overload, under voltage and loss-of-voltage protection function, as well as fire
protection, double-break and output ON signal function. It's especially suitable for
lighting circuit of office building, mall, bank, bus station and high-rise building requiring
fire product complies with GB/T14048.11 standard.
Application conditions
The ambient temperature shall not be higher than+40℃, or lower than-5℃, and the daily average shall not exceed+35℃.
The altitude of installation site shall not exceed 2000m.
Relative humidity shall not exceed 50% at the ambient temperature of +40℃, a higher humidity is allowable at a lower temperature, the
average maxinmum relative is 90% in the wettest month at a monthly average minimum teperature of +25℃, and special measures shall
be taken for the condensation on surface of product due to temperature change
Pollution calss: class III.
In place of no intense vibration and impact, no harmful gas corrosive and disruptive to the insulation, no sever dust, no conducting micro
particle and explosive substance, no high electromagnetic interference.
Working Conditions
Reasonable structure, small volume, nice appearance, with provided with protective shield, safer and more reliable power supply.
Complete protective fun ctions, including short circuit, overload, open phase and loss-of-voltage protection.
Reliable remote double-break with EPS fie protectin power supply interface DC12-24V
Noiseless, energy saving, simple installation, easy operation, raliable and stable performance.
Product Featurres
The transfer switch is composed of two JHAS69-63 Micro-Breaking and motor and mechanical rotating divice, and make detection to daul
power through controller, when abnormality controller, when abnormality occurs to the circuit, the controller will make a logic judgment for
the detection result and drive the operating mechanism to switch on or off according to according to command of controller, ensuring safe
and reliable and stable performance.
Rated short circuit breaking capacity: 3kA
Rated short circuit making capacity: 3kA
transfer time:≤3S
Control voltage of transfer switch: AC230V
Mechanical life of transfer switch(transfer of normal and reserve power): 3000 times, electric life: 1500 times
Rated insulation voltage: U=500V
Rated working current: 10A,16A,20A,32A,40A,50A,63A
The transfer switch has auto throw-in self-restoring function with the normal supply operating preferentially in common confition, the user
shall negotiate with the manufacturer during order placing for any other special requirement such as transfer switch of auto throw-in
nonself-restoring mode.
□
□
□
□
□
□
□
□
□
Product Performance
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
R
ADC C SSERERIEISES
001 www.onerealenergy.com
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
Making and Breaking Capacity
Utilization Category
Making and Breaking Test Condition
I/Ie U/Ue CosΦ Electrical time(s) Duration of cycle(min) Number of operating cycles
Ac-B33 6.0 1.05 0.5 0.05 ≤5 12
Note: AC-B33 motor load or combined load inccluding motor and resistance load under infrequent operation condition
Specifications
The inlet and outlet line & neutral line of normal and ready power shall be properly wired according to actual requirement of circuit desige.
The outlet terminals of the two circuit breaker shall be connected in parallel with accordant phase order(refer to the wiring diagram).
As for 3P circuit breaker, the neutral line must be connected to the terminal of neutral line(the normal and reserve neutral line as shown in
the fig. 2 Shall be respectively connected to NO.1 and 2 connection terminal).
Installation
1.Main circuit wiring diagram
2.External power ON indication and fire protection power wiring diagram
3.When manual operation is required for the transfer switch, as for YRQ1(CB级)-63 type, button switch shall be put to manual position first,
then transfer or normal or reseve power can be made by turing the handle, as for YRQ1(CB级)-63 type, transfer or normal or reserve power
ccan be made only by pushing manual/auto button until the manual indicator is on, when the control mode is in automatic position, the
transfer will enter automatic work condition and the normal power will operate preferentially.
4.When the transfer switch is wired according to wiring diagram, after power on, if the normal and reserve power are in good condition, the
indicator(red) of normal or reserve power will be on and the transfer switch will work normally.
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
www.onerealenergy.com 002
YRQ1(CB级)-LKRY Micro-Breaking Dual Power Transfer Switch (hereinafterreferred to
as transfer switch) is suitable for AC 50/60Hz dual power supoly system with rated
operating voltage of 400V amd rated operating current form 16~63A. Optional transfer
of dual power can be made according to requirement,. The product owns short circuit,
overload, under voltage and loss-of-voltage protection function, as well as fire
protection, double-break and output ON signal function. It's especially suitable for
lighting circuit of office building, mall, bank, bus station and high-rise building requiring
fire product complies with GB/T14048.11 standard.
Application conditions
The ambient temperature shall not be higher than+40℃, or lower than-5℃, and the daily average shall not exceed+35℃.
The altitude of installation site shall not exceed 2000m.
Relative humidity shall not exceed 50% at the ambient temperature of +40℃, a higher humidity is allowable at a lower temperature, the
average maxinmum relative is 90% in the wettest month at a monthly average minimum teperature of +25℃, and special measures shall
be taken for the condensation on surface of product due to temperature change
Pollution calss: class III.
In place of no intense vibration and impact, no harmful gas corrosive and disruptive to the insulation, no sever dust, no conducting micro
particle and explosive substance, no high electromagnetic interference.
Working Conditions
Reasonable structure, small volume, nice appearance, with provided with protective shield, safer and more reliable power supply.
Complete protective fun ctions, including short circuit, overload, open phase and loss-of-voltage protection.
Reliable remote double-break with EPS fie protectin power supply interface DC12-24V
Noiseless, energy saving, simple installation, easy operation, raliable and stable performance.
Product Featurres
The transfer switch is composed of two JHAS69-63 Micro-Breaking and motor and mechanical rotating divice, and make detection to daul
power through controller, when abnormality controller, when abnormality occurs to the circuit, the controller will make a logic judgment for
the detection result and drive the operating mechanism to switch on or off according to according to command of controller, ensuring safe
and reliable and stable performance.
Rated short circuit breaking capacity: 3kA
Rated short circuit making capacity: 3kA
transfer time:≤3S
Control voltage of transfer switch: AC230V
Mechanical life of transfer switch(transfer of normal and reserve power): 3000 times, electric life: 1500 times
Rated insulation voltage: U=500V
Rated working current: 10A,16A,20A,32A,40A,50A,63A
The transfer switch has auto throw-in self-restoring function with the normal supply operating preferentially in common confition, the user
shall negotiate with the manufacturer during order placing for any other special requirement such as transfer switch of auto throw-in
nonself-restoring mode.
□
□
□
□
□
□
□
□
□
Product Performance
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
R
ADC C SSERERIEISES
001 www.onerealenergy.com
SRQ series automatic transfer switch are mainly composed of power conversion
actuator, circuit breaker and controller. This dual power switch with automatic, manual,
power indicator, normal switch indicator, ready switch indicator working state. Switch's
features are small volume, long life, low power consumption, light weight, stable work,
easy to use and so on.
Product Features
Technical Date
Model
Standard
Electrical Characteristic Parameter
Shell Frame Current 63A 125A 250A 400A 630A
Rated Current ln (A) 10,16,20,25,
32,40,50,63
25,32,40,50,
63,80,100,
125
100,125,140,
160,180,200,
225,250
225,250,315,
350,400
400,500,630
Rated Operating
Voltage Ue AC400V 50Hz
Rated Insulation
Voltage Ui
Rated Impulse
Withstand Voltage
Uimp
Switching Poles
Life
Use Category
Electrical Level
Protection Level
Control Characteristic Parameter
Rated Control
Supply Voltage Us
Switching Time
AC500V AC800V AC800V AC800V AC800V
6KV 8KV 8KV 8KV 8KV
3P, 4P
Times 6000 6000 6000 4000 3000
AC-33iB
CB Class
IP30
AC230V 50Hz
≤3s ≤3s ≤3s ≤4s ≤4s
GB/T 14048.11
SRQ-63 SRQ-125 SRQ-250 SRQ-400 SRQ-630
When installing wiring, normal power N should be access to normal power supply circuit breaker QN, ready power R should be access to
ready power supply circuit breaker QR. When QN and QR is 4 poles circuit breaker, wiring mode according to the wiring diagram, which
QN and QR's 1, 3, 5 are three-phase ( A, B, C ) into line terminals, 2, 4, 6 are three-phase outgoing line terminals, 7 is zero line (N) into
line terminal, 8 is zero line outgoing line terminal. If the use of 3 poles circuit breaker, the normal power N's zero line (NN) and ready power
R's zero line (NR) must be respectively received on 3 poles special connection zero line terminal. Specific see wiring diagram. Dual power
transfer switch automatic controller's work power supply circuit breaker QN and QR's into line terminal A and zero line N, in the automatic
power switch installation, wiring process, Do not let the local controller to forget to connect the signal line, touch off or short circuit and so
on, otherwise can not work.
Installation
YRQ2(CB级) MOULDED CASE DUAL POWER TRANSFER SWITCH(CB CLASS)
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
www.onerealenergy.com 002
Dimension
R
ADC C SSERERIEISES
001 www.onerealenergy.com
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
SRQ series automatic transfer switch are mainly composed of power conversion
actuator, circuit breaker and controller. This dual power switch with automatic, manual,
power indicator, normal switch indicator, ready switch indicator working state. Switch's
features are small volume, long life, low power consumption, light weight, stable work,
easy to use and so on.
Product Features
Technical Date
Model
Standard
Electrical Characteristic Parameter
Shell Frame Current 63A 125A 250A 400A 630A
Rated Current ln (A) 10,16,20,25,
32,40,50,63
25,32,40,50,
63,80,100,
125
100,125,140,
160,180,200,
225,250
225,250,315,
350,400 400,500,630
Rated Operating
Voltage Ue AC400V 50Hz
Rated Insulation
Voltage Ui
Rated Impulse
Withstand Voltage
Uimp
Switching Poles
Life
Use Category
Electrical Level
Protection Level
Control Characteristic Parameter
Rated Control
Supply Voltage Us
Switching Time
AC500V AC800V AC800V AC800V AC800V
6KV 8KV 8KV 8KV 8KV
3P, 4P
Times 6000 6000 6000 4000 3000
AC-33iB
CB Class
IP30
AC230V 50Hz
≤3s ≤3s ≤3s ≤4s ≤4s
GB/T 14048.11
SRQ-63 SRQ-125 SRQ-250 SRQ-400 SRQ-630
When installing wiring, normal power N should be access to normal power supply circuit breaker QN, ready power R should be access to
ready power supply circuit breaker QR. When QN and QR is 4 poles circuit breaker, wiring mode according to the wiring diagram, which
QN and QR's 1, 3, 5 are three-phase ( A, B, C ) into line terminals, 2, 4, 6 are three-phase outgoing line terminals, 7 is zero line (N) into
line terminal, 8 is zero line outgoing line terminal. If the use of 3 poles circuit breaker, the normal power N's zero line (NN) and ready power
R's zero line (NR) must be respectively received on 3 poles special connection zero line terminal. Specific see wiring diagram. Dual power
transfer switch automatic controller's work power supply circuit breaker QN and QR's into line terminal A and zero line N, in the automatic
power switch installation, wiring process, Do not let the local controller to forget to connect the signal line, touch off or short circuit and so
on, otherwise can not work.
Installation
YRQ2(CB级) MOULDED CASE DUAL POWER TRANSFER SWITCH(CB CLASS)
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
www.onerealenergy.com 002
Dimension
R
ADC C SSERERIEISES
001 www.onerealenergy.com
YRQ1(CB级)-LKRY DUAL POWER TRANSFER SWITCH(CB CLASS)
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
Product Features
Automatic transfer switch equipment (ATSE), is a device integrated with the switching
function and logic control, truly perform electromechanical integration function, suitable
for operating in the distribution system of AC50Hz, rated voltage AC400V, conventional
thermal current up to 3200A in mineral and other enterprises. It provides the operation
function of voltage detection, forcedly switching off “0” position, manual emergency
operation and etc, widely used to shift between normal power and standby power or two
loading equipment, or perform safe isolation and etc. the control circuit board will
govern the motor through logic commands, then motor will drive the operating
mechanism of main switches, quickly closing or opening or shift the lines, the safe
isolation of main switch is obvious and legible by eye.
YRPS1(PC级) SERIES AUTOMATIC TRANSFER SWITCH EQUIPMENT(PC CLASS)
Technical Parameters
Standard: IEC947-6-1 GB14048.11-2008;
Rated breaking capacity (A Rms): 8Ie;
Control supply voltage: DC24V, 48V, 110V, AC220V.
Rated heating current(A)
Rated insulation voltage Ui (V)
Rated impact withstand
voltage Uimp (kV)
Rated
operating
current Ie (A)
Rated short-time withstand
current Icw(kA)
Rated limit short-circuit
current(kA)
Control supply voltage(V)
Convenrsion time(S)
100
8 12
750 1000
160 250 400 630 1000 1250 1600 2000 2500 3200
AC-31A
AC-35A
AC-33A
100
100
100
160
160
160
250
250
250
400
400
400
630
630
630
1000
1000
1000
1250
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
2500
3200
3200
3200
7 9 13 50 55
100 70 100 120 80
DC24V, 48V, 110V, AC220V
0.5 1 1.1 1.2 1.25 2.45
Wiring Diagram
Rated working voltage (Ue): AC440V;
Rated connecting capacity (A Rms): 10Ie;
www.onerealenergy.com 002
Main circuit wiring diagram
Dimension
Type
External dimensions Installation dimensions
W L H W1 L1
YRQ2(CB级)-63/3P,4P 290×240×135 255×220
YRQ2(CB级)-125/3P,4P 320×240×140 285×220
YRQ2(CB级)-250/3P,4P 370×240×160 335×220
YRQ2(CB级)-400/3P,4P 525×330×190 465×300
YRQ2(CB级)-630/3P,4P 650×330×190 585×300
R
ADC C SSERERIEISES
001 www.onerealenergy.com
YRQ2(CB级) MOULDED CASE DUAL POWER TRANSFER SWITCH(CB CLASS)
DUAL POWER SERIES AUTOMATIC TRANSFER SWITCH(ATS)
Product Features
Automatic transfer switch equipment (ATSE), is a device integrated with the switching
function and logic control, truly perform electromechanical integration function, suitable
for operating in the distribution system of AC50Hz, rated voltage AC400V, conventional
thermal current up to 3200A in mineral and other enterprises. It provides the operation
function of voltage detection, forcedly switching off “0” position, manual emergency
operation and etc, widely used to shift between normal power and standby power or two
loading equipment, or perform safe isolation and etc. the control circuit board will
govern the motor through logic commands, then motor will drive the operating
mechanism of main switches, quickly closing or opening or shift the lines, the safe
isolation of main switch is obvious and legible by eye.
YRPS1(PC级) SERIES AUTOMATIC TRANSFER SWITCH EQUIPMENT(PC CLASS)
Technical Parameters
Standard: IEC947-6-1 GB14048.11-2008;
Rated breaking capacity (A Rms): 8Ie;
Control supply voltage: DC24V, 48V, 110V, AC220V.
Rated heating current(A)
Rated insulation voltage Ui (V)
Rated impact withstand
voltage Uimp (kV)
Rated
operating
current Ie (A)
Rated short-time withstand
current Icw(kA)
Rated limit short-circuit
current(kA)
Control supply voltage(V)
Convenrsion time(S)
100
8 12
750 1000
160 250 400 630 1000 1250 1600 2000 2500 3200
AC-31A
AC-35A
AC-33A
100
100
100
160
160
160
250
250
250
400
400
400
630
630
630
1000
1000
1000
1250
1250
1250
1600
1600
1600
2000
2000
2000
2500
2500
2500
3200
3200
3200
7 9 13 50 55
100 70 100 120 80
DC24V, 48V, 110V, AC220V
0.5 1 1.1 1.2 1.25 2.45
Wiring Diagram
Rated working voltage (Ue): AC440V;
Rated connecting capacity (A Rms): 10Ie;
www.onerealenergy.com 002
Main circuit wiring diagram
Dimension
Type
External dimensions Installation dimensions
W L H W1 L1
YRQ2(CB级)-63/3P,4P 290×240×135 255×220
YRQ2(CB级)-125/3P,4P 320×240×140 285×220
YRQ2(CB级)-250/3P,4P 370×240×160 335×220
YRQ2(CB级)-400/3P,4P 525×330×190 465×300
YRQ2(CB级)-630/3P,4P 650×330×190 585×300
R
ADC C SSERERIEISES
001 www.onerealenergy.com
YRQ2(CB级) MOULDED CASE DUAL POWER TRANSFER SWITCH(CB CLASS)
CONFLUENCE BOX SERIES
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRG9 2 INPUT 1OUTPUT (MC4接头)
YRSP-40
YRPV-32X
YRB1-63
YRG9 5 INPUT 1OUTPUT (MC4接头)
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
Specification
2-1 Wiring diagram
Wiring diagram
Enclosure FCDB-EUS
Environment
Specification
5-1 Wiring diagram
Enclosure FCDB-EUS
Environment
CONFLUENCE BOX SERIES
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRG9 2 INPUT 1OUTPUT (MC4接头)
YRSP-40
YRPV-32X
YRB1-63
YRG9 5 INPUT 1OUTPUT (MC4接头)
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
Specification
2-1 Wiring diagram
Wiring diagram
Enclosure FCDB-EUS
Environment
Specification
5-1 Wiring diagram
Enclosure FCDB-EUS
Environment
001 www.onerealenergy.com www.onerealenergy.com 002
R
YRHA 2 INPUT 1OUTPUT (MC4接头) YRHA 6 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
Specification
2-1 Enclosure
Enclosure FCDB-EUS
Environment
Specification
6-1 Wiring diagram
Enclosure FCDB-EUS
Environment
001 www.onerealenergy.com www.onerealenergy.com 002
R
YRHA 2 INPUT 1OUTPUT (MC4接头) YRHA 6 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
Specification
2-1 Enclosure
Enclosure FCDB-EUS
Environment
Specification
6-1 Wiring diagram
Enclosure FCDB-EUS
Environment
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRHA 4 INPUT 1OUTPUT (MC4接头) YRHA 5 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRHA 4 INPUT 1OUTPUT (MC4接头) YRHA 5 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRHQ 6 INPUT 1OUTPUT (MC4接头)
1
YRHA 1 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRHQ 6 INPUT 1OUTPUT (MC4接头)
1
YRHA 1 INPUT 1OUTPUT (MC4接头)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX
R
001 www.onerealenergy.com www.onerealenergy.com 002
YRKH 4 INPUT 1OUTPUT (MC4接头) YRHA 1 INPUT 1OUTPUT DOUBLE CIRCUIT (WATERPROOF INTERFACE)
CONFLUENCE BOX SERIES
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
YRSP-40
YRPV-32X
YRB1-63
Suitable for PV system, equipped with a surge protector and isolator fuses,provid-ing isolation, leakage and grounding protection.
Max Operation Voltage 1000V;
Standard Compliance with EN50539 Type1+2;
Maximum Discharge Current 40KA;
LED Indicator or without LED indicator;
Rated Working Voltage 1000V;
Fuse Link 10x38mm LITTEL 15A;
DC MCB(Mini circuit breaker)
Rated Insulation Voltage 1200V;
Rated Current 63A;
COMBINER BOX