| Circuit breaker model | E1 | E2 | E3 | E4 |
| Frame current range (A) | 800~1250 | 1250~2000 | 1250~3200 | 3200~4000 |
| Rated current In (A) | 250、400、800、1250 | 1250、1600、2000 | 2000、2500、3200 | 3200、4000 |
| Rated voltage (V) | 690 | |||
| Poles | 3P、4P | |||
| Overload setting current (A) | J1=0.4~1×|n | |||
| Short circuit protection (A) | In=1、2、3、4、6、8、10×1n | |||
| Breaking capacity | Type B 40kA | Type B 40kAN-type 65kA | N-type 65kAS-type 75kA | S-type 100kA H |
| Control unit | PR111、PR112 etc | |||
| Overall dimensions | Fixed width | Fixed width | ||
| W* D* H (mm) | Fixed width 296 (3P), 386 (4P) | 404(3P)、530(4P) | 566(3P)、656(4P) | |
| Fixed - width * 302 *418 | The width of the drawer type is 324 (3P), 414 (4P) | The width of the drawer type is | The width of the drawer type is | |
| Drawer type - width * 396.5 * 461 | 432(3P)、558(4P) | 594(3P)、684(4P) | ||
| Manufacturer | ABB Company | |||
| Circuit breaker model | S1 | S2 | S3 | S5 | S6 |
| Frame current level (A) | 125 | 160 | 160、250 | 400 | 630 |
| Rated current In (A) | 16、25、32、40、50、63、80、100、125、160、200、250 | 320、400 | 630 | ||
| Rated voltage (V) | 500 | 690 | |||
| Poles | 3P、4P | ||||
| Overload setting current (A) | |r=0.4~1×|n | ||||
| Short circuit protection (A) | Im=1、2、3、4、6、8、10×1n | ||||
| Breaking capacity | N-type 25kA | N-type 35kAS-type 50kA | N-type 35kAH-type 65kA | N-type 35kA、H-type 65kAL-type 100kA | |
| Control unit | TM、PR211/P、PR212/P etc. | ||||
| Overall dimensions | 78×70×120(3P) | 90×70×120(3P) | 105×103.5×170(3P) | 140×103.5×254(3P) | 210×103.5×268(3P) |
| W* D* H(mm) | 103×70×120(4P) | 120×70×120(4P) | 140×103.5×170(4P) | 184×103.5×254(4P) | 280×103.5×268(4P) |
| Manufacturer | ABB Company | ||||
| Circuit breaker model | GTW1 | GTW1 | GTW1 |
| Rated current In (A) | 630、800、1000、1250、1600、2000 | 2000、2500、2900、3200 | 3200、3600、4000 |
| Rated voltage (V) | 400、690 | ||
| Poles | 3P、4P | ||
| Overload setting current (A) | |r=0.4~1×|n | ||
| Short circuit protection (A) | Im=0.4、15×1n | ||
| Breaking capacity | 50kA/80kA | 65kA/100kA | 80kA/100kA |
| Control unit | ZDT-3 Electronic Intelligent Controller | ||
| Overall dimensionsW* D* H(mm) | Drawer type 375×421×432(3P)470×421×432(4P)362×333×402(3P)Fixed type 457×333×402(4P) | Drawer type 375×421×432(3P)470×421×432(4P)362×333×402(3P)Fixed type 457×333×402(4P) | Drawer type 550×559×432(3P)812×569×452(4P) |
| Manufacturer | Jubang Group Co., Ltd. | ||
| Circuit breaker model | GTM1 | GTM1 | GTM1 | GTM1 | GTM1 | GTM1 |
| Frame current level (A) | 63 | 125 | 250 | 400 | 630 | 800 |
| Rated current In (A) | 6、10、16、20、32、40、50.63 | 16、20、32、40、50、63、80、100、125 | 100、125、140、160、180、200、225、250 | 225、250、315、350、400 | 400、500、630 | 630、700.800 |
| Rated voltage (V) | 400 | 400、690 | ||||
| Poles | 3P、4P | |||||
| Overload setting current (A) | 1.01、1.05、1.2、1.3、1.5、7.2×ln | |||||
| Short circuit protection (A) | 10×In、12×In | 5×|n、10×In、12×In | ||||
| Breaking capacity | L-type 25kAM-type 50kA | L-type 35kA、M-type 50kAH-type 85kA | L-type 50kA、M-type 65kAH-type 100kA | L-type 75kAM-type 100kA | ||
| Control unit | Thermal electromagnetic type | |||||
| Arcing distance | 0 | 0 or ≤ 50mm | ||||
| Overall dimensions | 75×135×98.5(3P) | 90×155×863P) | 105×65×104(3P) | 140×257×155 | 210×275×155(3P) | |
| W* D * H(mm) | 103×135×98.5(4P) | 120×155×86(4P) | 140×165×104(4P) | 140×103.5×254(3P) | 280×275×155(4P) | |
| Manufacturer | Jubang Group Co., Ltd. | |||||
04![]() | ||||||||||||||||||||||||||||
| 平 | ||||||||||||||||||||||||||||
| Use | Receiving power (upperincoming line) | Receiving power (lowerincoming line) | Receiving power (cableincoming) | Liaison | ||||||||||||||||||||||||
| Specification NO. | A | B | C | D | E | F | G | A | B | C | D | E | F | G | A | B | C | D | E | F | G | A | B | C | D | E | F | G |
| Short-time withstandcurrent/peakwithstand current (kA) | 80/176 | 80/176 | 80/176 | |||||||||||||||||||||||||
| 50/105 | 50/105 | 50/105 | 50/105 | |||||||||||||||||||||||||
| 30/63 | 30/63 | 30/63 | 30/63 | |||||||||||||||||||||||||
| Rated current (A) | 40003 | 150 | 2500 | 2000 | 1600 | 1000 | 630 | 4000 | 3150 | 2500 | 2000 | 1600 | 1000 | 630 | 2500 | 2000 | 1600 | 1000 | 630 | 4000 | 3150 | 2500 | 2000 | 1600 | 1000 | 630 | ||
| Cabinet width (mm) | 800(1000) | 600 | 800(1000) | 600 | 800 | 600 | 1000 | 800 | ||||||||||||||||||||
| Cabinet depth (mm) | 1000 | 800 | 1000 | 800 | 800 | 1000 | 800 | |||||||||||||||||||||
| Width of occupiedcompartment (mm) | ||||||||||||||||||||||||||||
| Main electricalcomponents | The GTW1 type is the main circuit breaker, and other MT and E series circuit breakers with similar or imported performance can also beselected.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | |||||||||||||||||||||||||||
| Remarks | ||||||||||||||||||||||||||||
| Main circuit Scheme No. | 05 | 06 | 07![]() | |||||||||||||||||||||||||
08![]() | ||||||||||||||||||||||||||||
| Main circuit schemediagram | ![]() | ![]() | ||||||||||||||||||||||||||
| Use | Bus transfer | Feed | Manual switching of dual powersupply | Manual switching of dual powersupply | ||||||||||||||||||||||||
| Specification NO. | A | B | C | A | B | C | D | E | F | G | A | B | C | D | E | F | G | |||||||||||
| Short-time withstandcurrent/peakwithstand current (kA) | 50/105 | 50/105 | 50/105 | |||||||||||||||||||||||||
| 30/63 | 30/63 | 30/63 | ||||||||||||||||||||||||||
| Rated current (A) | 1600 | 000 | 630 | 1000 | 630 | 1000 | 630 | |||||||||||||||||||||
| Cabinet width (mm) | 400(600) | 1000 | 1000 | 1000 | ||||||||||||||||||||||||
| Cabinet depth (mm) | 800(1000) | 800(1000) | 800 | 800 | ||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | 640 | |||||||||||||||||||||||||||
| Main electricalcomponents | The GTW1 type is the main circuit breaker, and other MT and E series circuit breakers with similar or imported performance can also beselected. QPS series is selected as the double throw switchThe current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | |||||||||||||||||||||||||||
| Remarks | ||||||||||||||||||||||||||||
| Main circuit Scheme No.Main circuit schemediagram | 09![]() | 10![]() | |||||||||||||||||||||||||||||||||||||||||||||
| 11 | 12![]() | ||||||||||||||||||||||||||||||||||||||||||||||
![]() | |||||||||||||||||||||||||||||||||||||||||||||||
| Use | Dual power switching | Feed | Feed | Current limiting reactor | |||||||||||||||||||||||||||||||||||||||||||
| Specification NO | A | B | A | B | C | D | A | B | C | ||||||||||||||||||||||||||||||||||||||
| Short-time withstandcurrent | 50/105 | 50/105 | 50/105 | ||||||||||||||||||||||||||||||||||||||||||||
| Peak withstandcurrent (kA) | 30/63 | 30/63 | 30/63 | ||||||||||||||||||||||||||||||||||||||||||||
| Rated current (A) | 400 | 250 | 630 | 400 | 250 | 160 | 400 | 200 | 100 | 600 | |||||||||||||||||||||||||||||||||||||
| Cabinet width (mm) | 800(1000) | 1000 | 800(1000) | 600 | |||||||||||||||||||||||||||||||||||||||||||
| Cabinet depth (mm) | 600 | 800(1000) | 800 | 800 | |||||||||||||||||||||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | 480×2 | 480 | 320 | 480 | 320 | 160 | |||||||||||||||||||||||||||||||||||||||||
| Main electricalcomponents | The GTW1 type is the main circuit breaker, and other MT and E series circuit breakers with similar or imported performance can also beselected.The fuse type isolation switch is mainly selected from QSA series; The main selection for AC contactors is the B series.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | ||||||||||||||||||||||||||||||||||||||||||||||
| The feeder scheme can be equipped with zero-sequence protection, and the zero-sequence current transformer can be installed inthe cable compartment. | |||||||||||||||||||||||||||||||||||||||||||||||
| Main circuit Scheme No. | 16 | 17 | 18 | 19![]() | |||||||||||||||||||||||||||||||||||||||||||
| Main circuit schemediagram | ![]() | ![]() | ![]() | ||||||||||||||||||||||||||||||||||||||||||||
| Use | Electric motor (irreversible) | Electric motor (irreversible) | Electric motor (irreversible) | Electric motor (irreversible) | |||||||||||||||||||||||||||||||||||||||||||
| Specification NO. | A | B | C | A | B | A | B | C | |||||||||||||||||||||||||||||||||||||||
| Maximum control motorpower (kW) | 100 | 75 | 55 | 37 | 15 | 7.5 | 100 | 75 | 55 | ||||||||||||||||||||||||||||||||||||||
| Cabinet width (mm) | |||||||||||||||||||||||||||||||||||||||||||||||
| Cabinet depth (mm) | |||||||||||||||||||||||||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | |||||||||||||||||||||||||||||||||||||||||||||||
| Main electricalcomponents | The fuse type isolation switch is mainly selected from QSA series; The main selection for AC contactors is B series, and the mainselection for thermal relays is T series.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | ||||||||||||||||||||||||||||||||||||||||||||||
| Remarks | The feeder scheme can be equipped with zero-sequence protection, and the zero-sequence current transformer can be installed inthe cable compartment. | ||||||||||||||||||||||||||||||||||||||||||||||
| Main circuit Scheme No. | 20 | 21 | 23 | 23 | ||||||||||||||||||||||||
| Main circuit schemediagram | ![]() | ![]() | ![]() | ![]() | ||||||||||||||||||||||||
| Use | Electric motor (reversible | Electric motor (reversible) | Electric motor (irreversible) | Electric motor (irreversible) | ||||||||||||||||||||||||
| Specification NO. | A | B | A | B | C | A | B | C | ||||||||||||||||||||
| Maximum control motorpower (kW) | 37 | 15 | 7.5 | 100 | 75 | 55 | 35 | 15 | 7.5 | |||||||||||||||||||
| Cabinet width (mm) | ||||||||||||||||||||||||||||
| Cabinet depth (mm) | ||||||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | ||||||||||||||||||||||||||||
| Main electricalcomponents | The GTW1 type is the main circuit breaker, and other MT and E series circuit breakers with similar or imported performance canalso be selected.The fuse type isolation switch is mainly selected from QSA series; The main selection for AC contactors is B series, and the mainselection for thermal relays is T series.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | |||||||||||||||||||||||||||
| Remarks | ||||||||||||||||||||||||||||
| Main circuit Scheme No. | 30 | 31 | 32 | |||||||||||||||||||||||||
33![]() | ||||||||||||||||||||||||||||
| Main circuit schemediagram | ![]() | ![]() | ![]() | |||||||||||||||||||||||||
| Use | Y_△ start-up | Y_△ start-up | Y_△ start-up | Y_△ start-up | ||||||||||||||||||||||||
| Specification NO. | A | B | C | A | B | C | A | B | A | B | ||||||||||||||||||
| Short-time withstandcurrent/Peakwithstand current (kA) | 50/105 | 50/105 | 50/105 | 50/105 | ||||||||||||||||||||||||
| Maximumcontrol motorpower (kW) | 30/63 | 30/63 | 30/63 | |||||||||||||||||||||||||
| Cabinetwidth (mm) | 90 | 37 | 15 | 37 | 15 | 37 | 15 | |||||||||||||||||||||
| Cabinet depth (mm) | ||||||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | 1000 | 800(100) | 1000 | 800(100) | ||||||||||||||||||||||||
| Main electricalcomponents | 800(1000) | 600 | 800(1000) | 600 | ||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | 1120 | 960 | 320 | 800 | 320 | |||||||||||||||||||||||
| Main electricalcomponents | The GTW1 type is the main circuit breaker, and other MT and E series circuit breakers with similar or imported performance can also beselected.The main selection for AC contactors is B series, thermal relays are T series, and fuse type isolation switches are QSA series.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | |||||||||||||||||||||||||||
| Main circuit Scheme No. | 34 | 35 | 36 | |||||||||||||||||||||||||
| Main circuit schemediagram | ![]() | ![]() | ![]() | |||||||||||||||||||||||||
| Use | Reactive power compensation(main cabinet) | Reactive power compensation(main cabinet) | Reactive power compensation(main cabinet) | |||||||||||||||||||||||||
| Specification NO. | ||||||||||||||||||||||||||||
| Short-time withstandcurrent/ | ||||||||||||||||||||||||||||
| Peak withstandcurrent (kA) | ||||||||||||||||||||||||||||
| Maximum controlmotor power (kW) | ||||||||||||||||||||||||||||
| Cabinet width (mm) | 1000 | 800 | 800 | |||||||||||||||||||||||||
| Cabinet depth (mm) | 800(1000) | 800 | 800 | |||||||||||||||||||||||||
| Width of occupiedcompartment (mm) | 2200 | 2200 | 2200 | |||||||||||||||||||||||||
| Main electricalcomponents | The fuse type isolation switch is mainly selected from QSA series; The main selection for AC contactors is B series, and the mainselection for thermal relays is T series.The current transformer is mainly selected from the BH-0.66 (or DH-0.66) series, and the zero-sequence current transformer isgenerally used in conjunction with the main circuit breaker. | |||||||||||||||||||||||||||
MNS
LV draw-out switchgear
1 Summary
1.1 Scope of application
This series of LV draw-out switchgear is suitable for power plants, substations, petrochemical industry, steel smelting and rolling, transportation and energy, light industry and textile, factories and mining enterprises, residential communities, high-rise buildings, and other places. Used for energy conversion, distribution, and control of power distribution equipment for AC systems with a rated working voltage of 690V and below at a frequency of 50-60Hz.
1.2 Installation conditions
The upper limit of the ambient air temperature is +40C, and the lower limit is -5C. And the average temperature within 24 hours shall not exceed +35℃;
Atmospheric conditions: The air is clean, and the relative humidity does not exceed 50% at the highest temperature of +40C . Higher relative humidity is allowed at lower temperatures (such as 90% at +20C): However, it should be considered that occasional condensation may occur due to temperature changes;
The altitude does not exceed 2000m;
This device is suitable for transportation and storage processes at the following temperatures:- Within the range of 25℃ to+55℃, it can reach+70℃ in a short period of time (no more than 24 hours). At these extreme temperatures, the device should not suffer any irreparable damage and should be able to operate normally under normal conditions;
If the above usage conditions cannot be meet, it should be resolved through negotiation between the user and the manufacturer.
When this device is used on offshore oil drilling and production platforms and nuclear power plants, a separate technical agreement should be signed
2 Basic technical parameters
2.1 Electrical performance
| Rated insulation voltage | AC690V | |
| Rated working voltage | AC400V | |
| Rated current of main busbar | ≤ 6300A | |
| Rated withstand current of main busbar (1S) | 50kA,80kA | |
| Rated peak withstand current of main busbar | 105kA,176kA | |
| Maximum operating current of distribution busbar (vertical busbar) | 1000A | |
| Distribution busbar (peak current of vertical busbar) | ||
| Standard type | 105kA (maximum)/0.1s | |
| Enhanced type | 176kA (maximum)/0.1s | |
2.2 Protection level
| Comply with IEC529 and DIN40050 standards |
| IP30 for greater thanΦ2.5MM solid protection |
| IP40 for greater thanΦ1.0MM solid protection |
| IP54 provides protection against dust and splashes from any direction |
| (When ordering IP54 protection level, it should be negotiated with the manufacturer) |
3 Cabinet structure
The basic structure of the switchgear cabinet is composed of C-shaped profiles assembled. The C profile is bent from a steel plate with an E=2.5mm module installation hole.
All frames and inner partitions are galvanized and purified. The surrounding door panels and side panels are subjected to high-voltage electrostatic spraying.
The basic structure of the cabinet is shown in Figure 1, and the basic dimensions of the cabinet are shown in Figure 2, Tables 1 and 2.
4 Switchgear type
Power distribution center cabinet (PC): Emax, MT, 3WN, AH, ME series circuit breakers can be used. Motor Control Center Cabinet (MCC): assembled from large and small drawers, each circuit main switch adopts a high breaking molded case circuit breaker or a rotating load switch with a fuse. Power factor automatic compensation cabinet (with manual, automatic, and remote power factor compensation devices)
| H | W | D | Remarks | ||
| H | B | T | T1 | T2 | |
| 2200 | 400 | 1000 | 800 | 200 | Main busbar transfer |
| 2200 | 400 | 1000 | 800 | 200 | F1s-1250-2000 ME630-1605 |
| 2200 | 600 | 1000 | 800 | 200 | F2s-2500 |
| 2200 | 800 | 1000 | 800 | 200 | F3s-3200 ME2000-3200 |
| 2200 | 1000 | 1000 | 800 | 200 | F4s-4000 Me3205 |
| 2200 | 1200 | 1000 | 800 | 200 | ME4005 |
| H | w | D | Remarks | ||||
| H | B | B1 | B2 | T | T1 | T2 | |
| 2200 | 1000 | 600 | 400 | 600 | 400 | 200 | Single sided operation |
| 2200 | 1000 | 600 | 400 | 1000 | 400 | 200 | Double sided operation |
7 Cabinet frame structure composed of C-shaped profiles (Figure 1)
8 Cabinet diagram (Figure 2)
9 Partition design of cabinet body
9.1 Power Distribution Center (PC)
① Divide the PC cabinet into three compartments;
Horizontal busbar compartment: at the rear of the cabinet;
Functional unit compartment: on the upper or left side of the cabinet front
② Split measures:
The horizontal busbar compartment and the functional unit compartment are separated by steel plates; The control circuit compartment and the functional unit compartment are separated by a flame-retardant polyphenylene ether plastic cover.
③ The frame type circuit breakers installed inside the cabinet can be manually operated outside the cabinet when the door is closed. Observe the opening and closing status of the circuit breaker and determine whether the circuit breaker is in the test position or in the working position based on the position relationship between the operating mechanism and the door.
④ A component separation structure is designed between the main circuit and the auxiliary circuit. The auxiliary electrical units composed of instruments, signal lights, and buttons are all installed on a plastic board, and the cover made of flame-retardant polyurethane foam plastic is separated from the main circuit behind the board.
9.2 Withdrawable motor control center and small current power distribution center (MCC)
The withdrawable MCC cabinet is divided into three compartments, namely the horizontal busbar compartment behind the cabinet, the functional unit compartment on the left front of the cabinet, and the cable compartment on the right front of the cabinet. The horizontal busbar compartment and functional unit compartment are separated by functional boards made of flame-retardant foam plastic, and the cable compartment is separated from the horizontal busbar compartment and functional unit compartment by steel plates.
The drawers of MCC (Motor Control Center) are divided into the following 5 types:
8E/4: Height 200 \* Width 150 \* Depth 400mm
8E/2: height 200 \* width 300 \* depth 400mm
8E: Height 200 \* Width 600 \* Depth 400mm
16E: Height 200 \* Width 600 \* Depth 400mm
24E: Height 200 \* Width 600 \* Depth 400mm
9.3 Rear outgoing switchgear structure
The rear outgoing line is designed to reduce the width of the switchgear arrangement. The main busbar of the switchgear is horizontally installed at the top of the switchgear, and the rear half of the cabinet is a cable compartment. The incoming and outgoing cables are all connected in the cable compartment behind the cabinet. The front of the switchgear is a device compartment, which houses the functional units of the switchgear. The system design moves the cable compartment on the side of the switchgear to the rear closing cabinet, greatly reducing the arrangement width of the switchgear to further meet the requirements of the substation space layout. The width of the feeder cabinet is 600mm and the depth is 1000/1200mm. The top is an independent main busbar compartment isolated from the device compartment. The effective installation height of the front device compartment is 72E (E=25mm), which is isolated from the rear cable compartment through a multi-functional board, fully utilizing the installation space of the switchgear. Compact structure and flexible unit configuration. The cable compartment on the back is equipped with a door for easy installation and maintenance.
The width of the incoming cabinet is determined by the frame current of the wiring unit. The recommended width is 400/600/800/1000mm, and the cabinet depth is 1000mm.
10 Busbar system
The switchgear can be equipped with two sets of main busbars, installed in the rear busbar compartment of the switchgear. Two sets of busbars can be installed separately in the upper and lower parts of the cabinet. According to the needs of the incoming line, the upper and lower sets of busbars can be made of different or the same crosssection materials. Both can be powered separately, in parallel, or as backup power sources.
The distribution busbar (vertical busbar) can choose "L" type copper bars or rectangular copper bars; When selecting "L" type copper bars for vertical copper bars, the supporting insulation components are functional boards which have good safety performance, small size, and a maximum current of 1000A; When selecting rectangular copper bars for vertical copper bars, the supporting insulation component is the busbar clamp, which has good safety performance, large volume, and a maximum current of 2000A. All frame structural components are connected with self-tapping screws, which has high grounding reliability.
The neutral busbar and neutral protection busbar are installed parallel to the lower part of the functional unit compartment and vertically in the cable compartment. If an insulator is used to separate the N line from the PE line, the N line and the PE line should be used separately. If a conductor is used to short circuit the two lines, they become PE/N lines.
11 Protective earthing system
The protection circuit of the device consists of two parts: a separately decorated PE wire (or PE/N wire) that runs through the entire queue length and a conductive structural component. The metal structural components in the device, except for the exterior doors and sealing plates, are all galvanized. At the connection points of the structure, they are carefully designed to withstand a certain short-circuit current.
12 Auxiliary current and cable tray
An auxiliary circuit cable tray is installed at the top of the functional unit compartment, which can accommodate inter cabinet connecting wires and public power cables.
13 Cable and control line connection
On one side of the withdrawable component, the cable compartment is equipped with wiring devices and terminals for connecting the outgoing cable and the wiring between the control wire and the component. The incoming and outgoing cables and control line wiring devices are arranged on the guide rail on the right side of the cable compartment. The main circuit terminal is located at the rear, and the control line terminal is located in the front 45° direction. The wiring of the control wire terminal can be connected with screws or plug-in wire nose or copper wire. If the main circuit terminal on the adapter of the withdrawable component is less than 65A, it is equipped with PE terminal.
14 Security protection system
Each cabinet does not have one or a set of flame-retardant plastic functional boards, which are installed between the main busbar room and the electrical room. Their function is to effectively prevent accidents caused by arcing and short circuits between the busbar caused by switch components due to faults, and strict isolation measures are taken.
There is a galvanized metal bottom plate with ventilation holes between the upper and lower drawers for isolation. The smaller 8E/4 and 8E/2 drawers are surrounded by flame-retardant engineering plastic parts, so there is a strong insulation and isolation effect between adjacent circuits. Various plastic components are used inside the cabinet to support the live parts, which are halogen-free. And it has anti leakAge performance of CT1300 level or above.
15 Drawer type
There are five standard sizes, all based on a height of 8E (200mm):
8E/4: Assemble 4 drawer units in the height space of 8E.
8E/2: Assemble 2 drawer units in the height space of 8E.
8E: Assemble 1 drawer unit in the height space of 8E.
16E: Assemble 1 drawer unit in a height space of 16E (400mm).
24E: Assemble 1 drawer unit in a height space of 24E (400mm).
Five types of drawer units can be assembled in a single cabinet or as a mixed assembly. The maximum number of drawer units that can be accommodated in a single cabinet assembly is shown in Figure 3.
| Drawer type | 8E/4 | 8E/2 | 8E | 16E | 24E |
| Maximum number ofaccommodating units | 36 | 18 | 9 | 4 | 3 |
16 Electrical and mechanical interlocking of drawers
The drawer unit has a reliable mechanical interlocking position, which is controlled by the operating handle and has clear and accurate closing, testing, extraction, and isolation positions.
The functions of the operating mechanism are shown in Figures 4 and 5.
To enhance safety precautions, a padlock can be added after the operating handle is positioned, with a maximum of three locks.
After the drawer unit is in place, the switch functions and positions listed in Figures 4 and 5 must be strictly followed, otherwise the structural components may be damaged. Please be careful when using it.
17 Schematic diagram of operating switch functions
18 Arrangement and combination of primary plan
① The total height of the functional unit compartment is 72E.
②In the same device, the general arrangement pattern of functional units is that small functional units are above and large functional units are below.
③8E/4 drawers consist of 4 to form an 8E installation unit, 8E/2 drawers consist of 2 to form an 8E installation unit, or 2 8E/4 drawers and 1 8E/2 drawer to form an 8E installation unit
④ The current transformers depicted in the scheme are the maximum installed quantity in this scheme (in schemes 01-19, 21-39, one current transformer can be added for reactive power compensation circuit). In practical use, it can be reduced or not installed according to system needs.
⑤ There are two types of device depths: 600mm (MCC single-sided operation cabinet) and 1000mm (PC and MCC double-sided operation cabinet). It is recommended to arrange and use PC and MCC separately. When using a split function board, it is possible to allow PC and MCC to be mixed and assembled in one cabinet.
⑥ When the PC and MCC devices are arranged adjacent to each other, then:
(1) When the MCC double-sided cabinet (or 600 depth MCC single-sided cabinet) is arranged adjacent to the PC cabinet, an adapter cabinet (with a width of 400mm) must be added between the two cabinets, as shown in Figure 6, Example 1.
(2)When the single-sided operation of the MCC is deepened to 1000mm, no adapter cabinet can be added, as shown in Figure 6, Example 2.
19 Schematic diagram of combination method (Figure 6)
| (1) | (4) | (4) | (4) | (1) | |||||||
| (3) | (3) | (3) | 009 | (3) | |||||||
| 800 | 400 | 1000 | |||||||||
20 Installation, use, and maintenance
① The installation reference diagram is shown in Figures 7 and 8.
② After the device arrives at the destination, the packAging box should be checked for completeness first. If the device is not installed immediately, it should be stored in a dry and clean place
③ The device is recommended to be installed off the wall or against the wall. The installation foundation plane should be flat, and the horizontal error of the foundation channel steel should be 1/1000, with a total length deviation of 3mm.
④At that time, it is recommended to use grade 8.8 and tension washers for the bolt fixation of all conductive parts. The recommended tightening torque values are shown in the table below:
| Bolt specifications | Tightening torque |
| M6 | 9.5 |
| M8 | 25 |
| M10 | 45 |
| M12 | 80 |
| M16 | 200 |
The cable head sheath and a certain number of copper connectors for the secondary circuit provided in the MCC scheme accessories. (To adapt to the cold pressing process of copper joints, it is recommended to use multi-core flexible wires for secondary cables).
After connecting the cables, the bottom of the device should be sealed to prevent small animals from crawling into the cabinet and causing short circuit accidents.
After installation or adjustment, the device needs to undergo the following inspections and tests before being put into operation:
① Check whether the electrical equipment and control wiring installed in the device comply with the factory's drawing requirements.
②Manual operation of various switches should be flexible and free from abnormalities and jamming.
③ Check whether the mechanical interlocking mechanism and electric interlocking device operate correctly and reliably, and should meet the system requirements.
④ Check whether the insulation resistance of the main circuit and control circuit meets the specified requirements.
⑤Check whether the electrical equipment installed in the device has good contact and meets the technical conditions of the electrical appliance itself.。
⑥ Check whether there are any foreign objects inside the device and if the installation screws of each component are loose.
Instructions for operating withdrawable MCC:
① The bottom of the drawer can only be pushed into the cabinet after it enters the guide correctly, otherwise it may cause damage to the drawer or failure to pull it out.
②The symbols and functions on the 8E/4 and 8E/2 drawer panels are shown in Figure 4. The arrow from the breaking position "O" to the working position "I" in the figure represents: first push the operating handle inward, then rotate the handle from "O" to "I". When returning, there is no need to push, as long as the handle "I" is turned towards "O", and after releasing, the handle will automatically pop out.
③ The symbol and function on the 8E-24E drawer panel are shown in Figure 5. When the handle reaches the working position, the mechanism releases the mechanical lock on the main switch. At this time, the main switch can be closed and opened. However, after the main switch is closed, the handle of the interlocking mechanism cannot be operated. There is a plastic small cover on the lower right corner door that meets the logo, which is the unlocking mechanism of the door. The operation process is as follows: when the drawer is in the working position, if you want to open the door, first pull out the small cover, and then use a screwdriver to insert the hole and move the lock buckle downwards to open the door. After opening the door, be sure to cover the plastic small cover, otherwise it will damage the original protection level.
21 Transportation and storage of devices
The device shall not roll over and be violently shaken.
When lifting the device after unpacking, a transportation angle plate should be used, and the angle between the two steel wire ropes should be ≤ 120° . If using a forklift, rolling bars, or prying bars, it is not allowed to be directly carried out on the bottom frame of the device.
If the device needs to be moved at a small distance during installation, it can be pried on the four corners of the chassis.
Electrical products and parts shall not be disassembled in the device.
It should be prevented from rain and moisture, and the Environment temperature should comply with the relevant regulations of this sample.
22 Product completeness
The switchgear is equipped with packing list, product qualification certificate, product user manual, and necessary drawings. The accompanying accessories include door keys and spare parts provided according to the supporting list
Option 1 Welding and installation Option 2 Bolt Installation
24 Installation diagram of busbar structure (Figure 8)
| Scheme number | 01 | 02 | 03 | 04 | 05 | 06 | 07 | 08 | 09 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | 18 | 19 | 20 |
| Primary scheme | ![]() | ![]() | ||||||||||||||||||
| Cabinet width (mm) | 400 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | |
| Equipment roomheight | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | |||||||||
| Maximum operatingcurrent (A) | 1500 | 1500 | 2300 | 3150 | 1500 | 3200 | 4000 | 1600 | 3200 | 4000 | 2000 | 3200 | 4000 | 2000 | 3000 | 3600 | 1500 | 3200 | 4000 | |
| Main equipment | ||||||||||||||||||||
| Use | Cable Incoming or outgoing | |||||||||||||||||||
| Scheme number | 21 | 22 | 23 | 24 | 25 | 26 | 27 | 28 | 29 | 30 | 31 | 32 | 33 | 34 | 35 | 36 | 37 | 38 | 39 | 40 |
| Primary scheme | ![]() | ![]() | ![]() | |||||||||||||||||
| Cabinet width (mm) | 400 | 800 | 1000 | 400 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | ||
| 600 | 600 | |||||||||||||||||||
| Equipment roomheight | 72E | 72E | 72E | 72E | 72E | 72E | ||||||||||||||
| Maximum operatingcurrent (A) | 1500 | 2300 | 3150 | 1500 | 3000 | 4000 | 1500 | 3200 | 4000 | 2000 | 3200 | 4000 | 2000 | 3000 | 3600 | 3200 | 4000 | |||
| Main equipment | ||||||||||||||||||||
| Use | Cabinet top Incoming and outgoing lines | |||||||||||||||||||
| Scheme number | 41 | 42 | 43 | 44 | 45 | 46 | 47 | 48 | 49 | 50 | 53![]() | 54 55 56 57 58![]() | ||||||||||||||||||
| Primary scheme | ![]() | |||||||||||||||||||||||||||||
| Cabinet width (mm) | 400 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | 600 | 800 | 1000 | |||||||||||
| Equipment room height | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | 72E | |||||||||||||||||||
| Maximum operatingcurrent (A) | 1500 | 1500 | 2300 | 3150 | 1500 | 3200 | 4000 | 1600 | 3200 | 4000 | 2000 | 3200 | 4000 | 2000 | 3000 | 3600 | 1500 | 3200 | 4000 | |||||||||||
| Main equipment | ||||||||||||||||||||||||||||||
| Use | Bus coupler | Bus coupler | ||||||||||||||||||||||||||||
| Scheme number | 61 | 62 | 63 | 64 | 65 | 66 | 67 | 68 | 69 | 70 | 71 | 72 | 73 74 | |||||||||||||||||
| Primary scheme | (×δ )→ | ![]() | ![]() | ![]() | I | I① | ![]() | 申) | ||||||||||||||||||||||
| Cabinet width (mm) | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | ||||||||||||||||
| Equipment room height | 8E/4 | 8E/2 | 8E | 16E | 24E | 8E/4 | 8E/2 | 24E | 8E | 16E | 8E | 16E | 8E | 16E | ||||||||||||||||
| Maximum operatingcurrent (A) | 30 | 50 | 100 | 300 | 800 | 30 | 50 | 200 | 100 | 300 | 100 | 300 | 100 | 200 | ||||||||||||||||
| Main equipment | ||||||||||||||||||||||||||||||
| Use | Feeder | Feeder | ||||||||||||||||||||||||||||
| Scheme number | 75 | 76 | 77 | 78 | 79 | 80 | 81 | 82 | 83 | 84 | 85 | 86 | 87 | 88 | 89 | 90 | 91 | 92 | 93 | 94 |
| Primary scheme | ![]() | ( ×)→ | ![]() | ![]() | ||||||||||||||||
| Cabinet width (mm) | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | |
| Equipment room height | 16E | 16E | 8E/4 | 8E/2 | 8E/4 | 8E/2 | 8E/4 | 8E/2 | 8E | 16E | 24E | 8E/2 | 8E | 16E | 24E | 8E/2 | 8E/2 | 8E | 24E | |
| Maximum operatingcurrent (A) | 300 | 500 | 7.5 | 15 | 7.5 | 15 | 7.5 | 15 | 45 | 75 | 160 | 15 | 37 | 65 | 110 | 7.5 | 15 | 55 | 110 | |
| Main equipment | ||||||||||||||||||||
| Use | Feeder | Irreversibility | Irreversibility | Reversible | Y/△ | |||||||||||||||
| Scheme number | 95 | 96 | 97 | 98 | 99 | 100 | 101 | 102 | 103 | 104 | 105 | 106 | 107 |
| Primary scheme | II口Y | ![]() | ![]() | ||||||||||
| Cabinet width (mm) | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 | 1000 |
| Equipment room height | 8E/4 | 8E/2 | 16E | 24E | 24E | 8E/2 | 8E | 24E | 24E | 8E/2 | 8E | 16E | 16E |
| Maximum operatingcurrent (A) | 7.5 | 22 | 55 | 110 | 160 | 15 | 30 | 65 | 100 | 7.5 | 15 | 55 | 90 |
| Main equipment | |||||||||||||
| Use | Irreversibility | Reversible | Y/△ | ||||||||||
| Scheme number | 132 | 133 | 134 | 135 | 138 139 140 141 142 143![]() ![]() | |||||||
| Primary scheme | ![]() | |||||||||||
| Use | Cable incoming from below, outgoing frombelow | Cable incoming from below, busbar outgoingfrom side | Cable incoming from below, busbar outgoingfrom above | |||||||||
| Device capacity(kVA) | 200-500 | 630-800 | 1000-1600 | 2000-2500 | 200-500 | 630-800 | 1000-1600 | 2000-2500 | 200-500 | 630-800 | 1000-1600 | 2000-2500 |
| Overalldimensions(H* D* W) | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 |
| Main equipment(PowerTransformer) | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 |
| Scheme number | 144 | 145 | 146 | 147 | 151 152![]() ![]() | |||||||
| Primary scheme | ![]() | |||||||||||
| Use | Busbar incoming from side,cable outgoing from below | Busbar incoming from side,outgoing from side | Busbar incoming from side,outgoing from upper | |||||||||
| Device capacity(kVA) | 200-500 | 630-800 | 1000-1600 | 2000-2500 | 200-500 | 630-800 | 1000-1600 | 2000-2500 | 200-500 | 630-800 | 1000-1600 | 2000-2500 |
| Overalldimensions(H* D* W) | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 | 2200×1800×1200 | 2200×2200×1400 | 2400×2400×1600 | 2600×2600×1600 |
| Main equipment(PowerTransformer) | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 | SCB-200/10SCB-250/10SCB-315/10SCB-400/10SCB-500/10 | SCB-630/10SCB-800/10 | SCB-1000/10SCB-1250/10SCB-1600/10 | SCB-2000/10SCB-2500/10 |
① Transformers and incoming and outgoing line methods can be selected separately according to needs.
②When adjusting the pressure device, the external dimensions should be relaxed by 500mm or deepened by 400mm, and the specific details should be negotiated with the manufacturer.
③ The product description and legend are for reference, and may be continuously modified over time without further notice. Please contact our company.
GTDSVF
Multifunctional variable frequency speed control cabinet
1 Summary
1.1 Scope of application
Our company's multifunctional variable frequency speed control cabinet GTDSVF series provides customized solutions for customers, making it convenient for management and operation, and more suitable for the needs of various industries.
1) The energy-saving effect is significant, with a power saving rate of up to 40%\~85%, especially outstanding for variable load motors such as centrifugal and axial fans, water (oil) pumps, etc.
2) The speed regulation performance is far superior to other speed regulation methods such as thyristor cascade speed regulation and rotor series resistance speed regulation.
3) It has multiple protection functions such as motor overload and overheating, ensuring the safe operation of the motor.
4) It also has the soft start function of asynchronous motors.
5) It has a standard serial interface and can connect multiple frequency converters to PLC or other remote management systems.
1.2 Installation conditions
Widely used:
For various occasions, such as fans, oil fields, oil extraction equipment, domestic water supply and drainage, fire protection, spraying, pressurization, air conditioning cooling circulation, industrial control pumps, sewage discharge
Multiple functions:
It is divided into multiple control methods such as one-driven-one, one-driven-two, and two-driven-two. The main and backup pumps can be selected in any combination, with multiple starting methods and various control forms.
2 Product model and meaning
A (one-driven-one) B (one for use and one for backup)
C (without bypass) D (other)
Power(37kV)
220V 380V 660/690V 1140V
S (Three-phase) D (Single-phase)
V/F (Variable frequency control cabinet)
DS (Multifunctional speed regulation)
GT (Jubang Group Co., Ltd.)
3 Main technical parameters
| Specifications | Parameters |
| Power Supply | Three-phase 380V 50Hz; 690V 50Hz |
| Power | 0.75kW~630kW |
| Working temperature | -30℃~+40℃ |
| Working humidity | ≤ 90%RH(No condensation) |
| Working altitude | ≤ 2000m |
| Seismic parameters | Maximum amplitude ≤ 5.8m/S2(0.6g) |
| Protection level | IP40 |
| Cabinet color | RAL7035 |
4 Description of options and accessory functions
| Components | Cabinet type | ||
| One-driven-One(Type A) | One for use and onefor backup (Type B) | No bypass (Type C) | |
| Frequency converter | |||
| Molded case circuit breaker | |||
| AC contactor | |||
| Ammeter, voltmeter | |||
| CAM switch | |||
| Two position rotary switch (remote/local) | |||
| Three position rotary switch (mains/zero/node) | |||
| Operation panel introduction cabinet door | |||
| Cooling fan for mains power, powersaving, and fault indicator lights | |||
| Cooling fan | |||
| DC reactor | 一 | ||
| Input AC reactor | O | O | O |
| Output AC reactor | O | O | O |
| Input filter | O | O | O |
| Output filter | O | O | O |
| Remote control box | O | O | O |
Standard frequency conversion integrated cabinet with standard components;
Devices can be selected according to user needs;
Standard components for frequency converters of 75G or 90P (including 75G/90P) or above in the standard frequency conversion integrated cabinet.
5 Flexible configurable solution
| Cabinet type | Secondary circuit diagram | Control principle | Application features |
| One-driven-one (cabinet diagram) | Users can achieve frequency conversion switching operation of the motor | The on-site production requirements are high, and the shutdown of the frequency converter can ensure the normal operation of the equipment. | |
| One for use and one for backup (cabinet diagram) | ![]() | Users can achieve frequency conversion switching operation for motors and backup motors | The on-site production requirements are high, that is, the main motor is shut down and can be replaced with a backup motor to ensure normal production operation. |
| No bypass (cabinet diagram) | ![]() | Users can achieve variable frequency operation of the motor | The on-site production requirements are not high, that is, the frequency converter is shut down, and during the repair of the frequency converter, the equipment shutdown does not have a significant impact on production. |
6 Selection guidance
| Voltage (V) | Power (kW) | Output current (A) | Size (H * W * D) | |||||
| 380 | 0.75 | 2.6 | ||||||
| 380 | 1.5 | 3.8 | ||||||
| 380 | 2.2 | 5.5 | ||||||
| 380 | 3.7 | 9 | ||||||
| 380 | 5.5 | 13 | ||||||
| 380 | 7.5 | 17 | ||||||
| 380 | 11 | 25 | ||||||
| 380 | 15 | 32 | ||||||
| 380 | 18.5 | 37 | Depending on the number offrequency converters configured inthe user's cabinet | |||||
| 380 | 22 | 45 | ||||||
| 380 | 30 | 60 | ||||||
| 380 | 37 | 75 | ||||||
| 380 | 45 | 90 | ||||||
| 380 | 55 | 110 | ||||||
| 380 | 75 | 150 | ||||||
| 380 | 90 | 176 | ||||||
| 380 | 110 | 210 | ||||||
| 380 | 132 | 250 | ||||||
| 380 | 160 | 300 | 1800*600*600 | |||||
| 380 | 185 | 340 | ||||||
| 380 | 200 | 377 | ||||||
| 380 | 220 | 420 | ||||||
| 380 | 250 | 480 | 1800*800*600 | |||||
| 380 | 280 | 540 | ||||||
| 380 | 315 | 600 | ||||||
| 380 | 355 | 670 | ||||||
| Voltage(V) | Power(KW) | Output current (A) | Size (H * W * D) |
| 380 | 0.4 | 1.2 | Depending on the number offrequency converters configuredin the user's cabinet |
| 380 | 0.75 | 2.6 | |
| 380 | 1.5 | 3.8 | |
| 380 | 2.2 | 5.5 | |
| 380 | 3.7 | 9 | |
| 380 | 5.5 | 13 | |
| 380 | 7.5 | 17 | |
| 380 | 11 | 25 | |
| 380 | 15 | 32 | |
| 380 | 18.5 | 37 | Depending on the number offrequency converters configuredin the user's cabinet |
| 380 | 22 | 45 | |
| 380 | 30 | 60 | |
| 380 | 37 | 75 | |
| 380 | 45 | 90 | |
| 380 | 55 | 110 | |
| 380 | 75 | 150 | |
| 380 | 90 | 176 | |
| 380 | 110 | 210 | |
| 380 | 132 | 250 | 1800*600*600 |
| 380 | 160 | 300 | |
| 380 | 185 | 340 | |
| 380 | 220 | 377 | |
| 380 | 220 | 420 | 1800*800*600 |
| 380 | 250 | 480 | |
| 380 | 280 | 540 | |
| 380 | 315 | 600 |
7 Introduction to Industry Application Fields
| Fan, water pump |
| Energy saving renovation of oil fields andcentral air conditioning |
| Energy saving renovationof air compressors |
| The entire production line of cement, ceramics,and glass |
| Municipal boilers, sewage treatment |
| Partial wire drawing machine traction |
| Mining equipment |
| Plastic and chemical fiber extrusion equipment |
| Metal processing machinery |
| Textile machinery |
| Petroleum extraction equipment |
| Wire and cable extrusion equipment |
| Passenger and freight elevators, liftingmachinery |
| Metallurgy |
Inverter booster integrated machine (American style/Chinese style)
1 Summary
Inverter booster integrated machine (American/Chinese) is a photovoltaic integrated machine developed by Jubang Group based on the characteristics of the photovoltaic power generation industry chain. In order to meet the needs of customers to reduce costs, reduce construction cycles, and adapt to various environments, in addition to inverter stations, European style box transformers, and American style box transformers, it has also derived a comprehensive and encompassing almost all photovoltaic industry chains. EBS integrates DC distribution, inverter, medium voltage transformer, ring main unit and system monitoring functions, with a standard power dispatch interface, providing a one-stop solution for the inverter unit scheme from the DC output link of photovoltaic cell modules to the grid connection link. It has significant advantages in system integration, environmental adaptation, overall investment cost and fast installation and commissioning
2 Product features
Basic configuration
• DC cabinet+ Inverter+ American style box transformer
Product features
• It can be lifted as a whole, and the installation on the construction site is convenient and fast, greatly reducing the
• construction period of the power station.
• Save construction costs, reduce construction difficulty and uncontrollable risks.
• Standardized unit overall plan, quick debugging and integration into the grid. Maximum system integration, reduce the cost of equipment.
Flexible plan
• Specifications:10kV\~35kV。
• The appearance can be customized according to user needs.
Quality experience
• Three-year warranty commitment, product reliability and safety.
• Simplify on-site installation engineering;
• Easy and convenient maintenance.
Inverter booster integrated machine (European Style)
1 Summary
Inverter booster integrated machine (European style) is a photovoltaic integrated machine developed by Jubang Group based on the photovoltaic power generation industry chain. In order to meet the needs of customers to reduce costs, reduce construction cycles, and adapt to various environments, in addition to inverter stations, European style box transformers, and American style box transformers, it has also evolved into a comprehensive and almost complete photovoltaic industry chain
EBS integrates DC distribution, inverter, medium voltage transformer, ring main unit and system monitoring functions, with a standard power dispatch interface, providing a one-stop solution for the inverterunit scheme from the DC output link of photovoltaic cell modules to the grid connection link. It has significant advantages in system integration environmental adaptation, overall investment cost, and fast installation and commissioning
2 Product features
Basic configuration
• DC cabinet+ inverter+ AC cabinet+ step-up transformer+ medium voltage load switchgear.
Product features
• It can be lifted as a whole, and the installation on the construction site is convenient and fast, greatly reducing the
• construction period of the power station;
• Save construction costs, reduce construction difficulty and uncontrollable risks;
• Standardized unit overall plan, fast debugging and integration into the grid;
Maximizing system integration and reducing equipment costs.
Flexible plan
• Specifications: 10kV\~35kV;
• The appearance can be customized according to user needs.
Quality experience
• Three year warranty commitment, product reliability and safety;
• Simplify on-site installation engineering;
• Easy and convenient maintenance.
Energy storage converter booster integrated cabin (European Style)
1 Features
Integrated design of "transformation" and "upgrading" to achieve integrated product delivery;
Highly integrated, rational and efficient layout, improving space utilization;
Secondary circuit integration, unified measurement, protection, and communication;
Flexible configuration, supporting multi machine parallel connection, PQ, VF and other functions;
1500V system has a wide DC voltage range and flexible DC terminal configuration;
Various applications such as peak shaving and valley filling, peak shaving and frequency regulation, and auxiliary new energy grid connection;
Maximizing system integration and reducing equipment costs.
2 Technical parameters
| Technical parameters | ||
| Rated grid connected voltage | 10kV/35kV | |
| Rated grid frequency | 50/60Hz | |
| Rated output power | 2.0/2.5MW | |
| Maximum output current | 127A(@10kV/36.3A(@35kV) 160A(@10kV or 45.7A(@35kV) | |
| Overload capacity | 1.1 times rated current long-term | |
| Battery capacity | Configure according to actual situation | |
| Topology structure multi-level inverters topology | Multi-level inverters topology | |
| Maximum output power | 2.2/2.772MVA | |
| Maximum direct current | 926*4/1166*4A | |
| Dc side voltage | 600-900VDC | |
| Power factor range | -1~1 | |
| Current harmonics (THDi) | <3%(Rated output power) | |
| Stable voltage accuracy | 2% | |
| Maximum efficiency | 99% | |
| DC side buffer | Support | |
| Multi machine parallel connection | Support | |
| Communication interface | RS232/485、Ethernet、GPRS(Optional) | |
| Altitude | Derating required for 2000m or above | |
| Protection level | IP54 | |
| Working temperature | -30~65C℃ | |
| Cooling method | Intelligent air cooling | |
| Installation method | Outdoor installation | |
| External dimensions(width x height x depth) | 6058x2896x2438 | |
Energy storage converter booster integrated machine (American Style)
1 Summary
Our company's independently developed three point flat medium voltage high-power energy storage converter, switchgear, and step-up transformer have been optimized and integrated. They have the characteristics of higher power per set of equipment, simple application, flexible installation site selection, and convenient operation and maintenance. The system can directly connect 10/35kV high voltage to the power grid, reducing complex high voltage system design work, shortening the system design cycle, and reducing system design costs.
2 Product features
Intelligent and efficient
• Advanced multi-level inverters circuit topology, high conversion efficiency, and better power quality
• Wide DC voltage range, up to 1500V
• Advanced control algorithms with multiple operating modes available, including constant current, constant voltage, and constant power
• Supports long-term overload operation at 110% rated power and short-term overload capacity at 120% rated power
• Intelligent temperature control air cooling, stable operation over a wide temperature range
• Ultra high power density, smaller volume at the same power level
Safe and reliable
• Comprehensive battery protection and maintenance strategies to improve battery life
• Protection against overcurrent, overheating, overload, overvoltage, short circuit, lightning protection and grounding, etc
• Equipped with zero voltage and high voltage ride through functions, with strong adaptability to the power grid
• Equipped with anti islanding protection to ensure safe operation of the power grid
• Adapt to harsh environments of low temperature, high humidity, and high altitude
• The protection level of the inverter is IP55, and the outdoor installation of the entire machine is convenient
Efficient layout
• Integrated design of inverter, switchgear, and transformer, with simple application
• Complete power level, easy for user system configuration
• Local touch screen monitoring, real-time display, and convenient operation
• Standard Ethernet, RS485, CAN communication interface
3 Technical parameter
GTE2000/2500/3150/3450
| DC parameters | ||||
| Maximum DC inputpower | 2200kW | 2750kW | 3465kW | 3795kW |
| DC input voltagerange | 5800-1000V | 730-1200V | 910-1500V | 1000-1500V |
| Maximum DC inputcurrent | 1935A*2 | 1935A*2 | 1935A*2 | 1935A*2 |
| Stable voltageaccuracy | ±1% | ±1% | ±1% | ±1% |
| Steady currentaccuracy | ±1% | ±1% | ±1% | ±1% |
| DC current ripple | ≤ 2% | ≤ 2% | ≤ 2% | ≤ 2% |
| Topology structureof inverter | Multi-level inverters | Multi-level inverters | Multi-level inverters | Multi-level inverters |
| Number of DC inputchannels | 2 | 2 | 2 | 2 |
Communication side parameters (grid connected operation mode)
| Rated AC output power | 2000kW | 2500kW | 3125kW | 3450kW |
| Rated AC output current | 2886A | 2886A | 2886A | 2886A |
| Rated AC output voltage | 400V | 500V | 630V | 690V |
| AC output voltage range | 340-400V(Adjustable) | 425-550V(Adjustable) | 536-639V(Adjustable) | 586-759V(Adjustable) |
| Rated grid frequency | 50Hz | 50Hz | 50Hz | 50Hz |
| Allow frequencyfluctuation range of thepower grid | 47-50Hz(Adjustable) | 47-50Hz(Adjustable) | 47-50Hz(Adjustable) | 47-50Hz(Adjustable) |
| Total harmonic distortion rate of current | < 3%(Rated power) | |||
| Power factor | ≥0.99 | |||
| Adjustable range of power factor | 0.9(leading)~0.9(lagging) | |||
Communication side parameters (island operation mode)
| Rated voltage | 400V | 500V | 630V | 690V |
| Voltage accuracy | Within ± 3% | Within ± 3% | Within ± 3% | Within ± 3% |
| Rated output power | 50Hz | 50Hz | 50Hz | 50Hz |
| Output voltage distortion(THD) | < 3% (Linearload) | < 3% (Linearload) | < 3% (Linearload) | < 3% (Linearload) |
| Frequency accuracy | ±1Hz | ±1Hz | ±1Hz | ±1Hz |
| Voltage transition range | Within 10%, 0 to 100% load variation | |||