LOWVOLTAGE PRODUCT CATALOGUE
CONTENTS
PowerDistribution
1-18P
EXW3SeriesAirCircuitBreaker
Dw45SeriesAirCircuitBreaker
HUW1Series Air Circuit Breaker
HYM1 Molded-CaseCircuitBreaker
HYM3LCKEarthLeakageCircuitBreaker
HYM1LEarth LeakageCircuit Breaker
HUM9Molded-CaseCircuitBreaker
HUM9LEarthLeakageCircuitBreaker
HUM9EElectronicMolded-CaseCircuitBreaker
HUM8SeriesMolded-CaseCircuitBreaker/MCCB
HUM8LSeriesEarth-Leakage CircuitBreaker/ELCB
HUM8D SeriesIntelligentMolded-CaseCircuitBreaker
EXM3Molded-CaseCircuitBreakers
EXM3LSeriesEarth-LeakageCircuitBreaker/ELCB
EXM3EElectronicMolded-CaseCircuitBreaker
EXT3-63CBClass AutomaticTransferSwitchingEquipment
EXT3AutomaticTransferSwitchingEquipment
EXT3PCBClass AutomaticTransferSwitchingEquipment
HR6FusetypeKnifeSwitch
HR17FusetypeKnife Switch
HYGLLoad switch
HH15(QsA)Disconnectorfusegroup(withfuse)
HH15A(QA)Disconnector(theswitchisinseriesinsideand
theinletandoutletterminalsarehorizontal)
HH15(QP)Disconnector(switchisinparallelinternally,and
incomingandoutgoinglineendsareinstaggeredorder)
RT16(NT)EnclosedTubeTypeKnifebladeFuse
RT18EnclosedTubeTypeFuse
RsO Enclosed TubeTypeFuse
Terminal distribution
19-29P
EXB3-40 Miniature CircuitBreaker
EXB3-63MiniatureCircuitBreaker
EXB3-125High breakingMiniature Circuit Breaker
EXB3LY-63ResidualCurrentCircuitBreakerwith
OvercurrentProtection
EXB3LE-63ResidualCurrentCircuitBreakerwith
OvercurrentProtection
EXB3LE-125ResidualCurrentCircuitBreakerwith
OvercurrentProtection
EXB3L1-100ResidualCurrentCircuitBreaker
EXH3-125SwitchDisconnectors(ModularIsolators)
HUM18-40Miniature Circuit Breaker
HUM18-63(Z) Miniature Circuit Breaker
HUM18-63NMiniatureCircuitBreaker
HUM18-80MiniatureCircuitBreaker
HUM18-125MiniatureCircuitBreaker
HUM18LY-63ResidualCurrentCircuitBreakerwith
OvercurrentProtection
HUM18LE-63SeriesMiniatureCircuitBreaker
HUH18-125SeriesIsolatorswitch
HUM18PV-63SeriesMiniature Circuit Breaker
HLS1Series Surge Protection Device
HYZF1-63 Series Self-compound Overvoltage and
UndervoltageProtector
JYC8SeriesACHouseholdContactor
HUX-30Seriesindoordistributionbox
IndustrialControland Protections
Powerappliancesandothers
30-36P
37-39P
CJX1SeriesACContactor
EXC3SeriesACContactor
CJX2SeriesACContactor
CJ19SeriesSwitchingCapacitorContactor
HUC1ACContactors
EXR3SeriesThermalOverloadRelay
JRS1SeriesThermalOverload Relay
JRS2SeriesThermalOverload Relay
F4SeriesAuxiliaryContactSet
LA2.LA3SeriesTimedelayauxiliarycontactblock
BHSeriesCurrentTransformer
HR17SeriesFuseTypelsolatingSwitch
HG2BSeriesFuseIsolatingSwitch
JBK5SeriesFuselsolatingSwitch
HH52PSeries Multi Purpose Relay
HH64PSeriesMultiPurposeRelay
BKSeriesControlTransformer
BSMJNSeriesSelf-healingLow-voltageParallelPowerCapacitor
HYIC3XSeriesHarmonicSuppressionIntelligentPowerCapacitor
CompensationDevice
HYIC3-KSeriesIntelligentReactivePowerCompensationController
JKWFSeriesReactivePowerAutomaticCompensationController
EXW3
Series Air Circuit Breaker
Application scope
EXW3seriesintelligentaircircuit breakersareapplicabletodistributionnetworkswithC50/60Hz,ratedworkingvoltage upto690Vandratedcurrentupto6300A.
The core components of the circuit breaker areintelligent controllerswith precise selective protection,which can avoid unnecessary power failure and improve the reliability,continuity and security of power supply.It can also be equipped with an open communicationinterface torealize the“fourremotes"function to meet therequirements of the control center and automationsystem.
Features
-Compactdesign,savingofspaceandlaborforinstallation.
-Eco-friendlyMaterials,ourproducts are compliant with the RoHS directive and the use of restricted substancesis within the linelimitsstipulatedbythesaiddirective.
-Completerangeofaccessories.
Conformingstandards:IEC60947-2
Main technical parameter
| Frame size | 1600、2000、2500、3200、4000、6300 | |||
| Rated current | EXW3-1600:200A、400A、630A、800A、1000A、1250A、1600A EXW3-2000:630A、8 800A、1000A、1250A、1600A、2000A EXW3-2500:630A、800A、1000A、1250A、1600A、2000A、2500A EXW3-3200:2000A、2500A、3200 EXW3-4000:4000A EXW3-6300:4000A、5000A、6300A | |||
| Ratedvoltage | 400V/690V | |||
| Ratedinsulationvoltage | 1000V | |||
| Poles | 3P、4P | |||
| Installation method | Fixed type,Draw-out type | |||
| Model | EXW3-1600 | EXW3-2000/2500 | EXW3-3200/4000 | EYW3-6300 |
| N | N | N | N | |
| Rated ultimate short-circuit breaking capacityIcu(kA) | 50 | 85 | 85 | 120 |
| Ratedservice short-circuitbreaking capacity Ics(kA) | 42 | 65 | 70 | 100 |
| Rated short-time withstand current Icw (1s) (kA) | 42 | 65 | 70 | 100 |
HUW9
Series Air Circuit Breaker
Application scope
HUW9 series intelligent molded case circuit breakers (hereinafter referred to as circuit breakers) are applicable to AC 0/60{\sf H z} rated workingvoltage upto690V,and ratedcurrentbelow6300A distribution networks,mainly used for,feederand power generation protection,to prevent the line and powerequipment with rated working voltage from being damaged by overloading,undervoltage,overvoltage current voltage imbalance, short circuit and grounding faults.The circuit breaker can also be used directly as overload,undervoltage and short-circuit protection motors and generators.The core components of the circuit breaker adopt intelligent controllers, which have precise selective protection, can avoid unnecessary power outage, and improve the reliability, and safety of power supply. It can also be equipped with open communication interfaces to realize the“four remotes"function to meet the requirements of control centers and automation.
Conforming standards:IEC60947-2.
Features -Completeprotectionfunctions. -Stableandreliable operation; -Modularization,communication,highbreaking
Power Distribution
Main technical parameter
| ModelandframesizeInm | HUW9-1600 | HUW9-2000 HUW9-2500 | HUW9-3200 | HUW9-4000HUW9-6300 | |||
| Ratedcurrent | 200、400、 630、800、 1000、1250、 1600 | 630、800、 1000、1250、 1600、2000 | 2500 AC400/690 | 2000、2500 3200 | 4000 | 4000、5000 | 6300 |
| Ratedvoltage | |||||||
| Poles | 3P/4P | ||||||
| Rated insulationvoltage | AC1000 | 120 | |||||
| Rated ultimate short-circuit breaking capacity Icu (kA) | 50 | 85 85 | |||||
| Rated service short-circuit breaking capacity Ics (kA) | 42 | 65 | 70 | 100 | |||
| Rated short-time withstand current Icw (1s)(kA) | 42 | 65 | 70 | 100 | |||
HUW1
Series Air Circuit Breaker
Application scope
HUW1 series intelligent air circuit breakers are used for distributing power and protecting circuits in the electrical distribution system is protected from overloading,voltage shortage,short circuit,ground,and other hazardousfaults.The circuit breaker has multiple intelligent protection functions available for selection.The protective actions have a high precisionforpreventingunnecessary powerfailure,closing powersupply much morereliable.
The reasonable operation of the power grid is realized throughload monitoring,regional interlocking and other functions. At thesametime,itcanalso beused tomeasurethecurrent,voltage,power,frequency,electricenergy,demand,harmonic and other grid parameters of grid nodes.The circuit breaker can also be directly used for overload, undervoltage and short circuit protection of motors and generators.The circuit breaker can be used for upperincoming line orlowerincoming line, which is applicable to various low-voltage power distribution fields such as power stations,factories, intelligent buildings, etc.It can also be used asthe core component ofthe circuit breakerforinfrequent starting of motors.With accurate selective protection, it can avoid unnecessary power outages and improve the reliability,continuity and security of power supply. It can also be equipped with an open communication interface to realize the"four remotes" function to meet the requirementsofthecontrolcenterandautomationsystem.
The derivative products HUw1PVA and HUW1F of this series of circuit breakers have passed the ultra-high and low temperature environmental tests and "three prevention"related tests, and are applicable to AC Photovoltaic and wind power generation systems with 50Hz,rated voltage up to 690V and rated current upto 3200A.
Conforming standards:IEC60947-2
Main technical parameter
| ModelandframesizeInm | HUW1-1000 | HUW1-2000 | HUW1-3200 | HUW1-4000 | HUW1-6300 |
| Ratedcurrent | 200、 400、 630、800、 1000 | 630、 800 1000、1250、 1600、2000 | 2000、2500 2900、3200 | 2500、2900 3200、4000 | 4000、5000 6300 |
| Ratedvoltage | AC400/690 | ||||
| Poles | 3P/4P | ||||
| Ratedinsulationvoltage | AC1000 | ||||
| Rated ultimate short-circuit breaking capacity Icu (kA) | 42 | 85 | 85 | 85 | 120 |
| Rated service short-circuit breaking capacity Ics (kA) | 30 | 65 | 70 | 70 | 100 |
| Rated short-time withstand current lcw (1s)(kA) | 30 | 65 | 70 | 70 | 100 |
| Installationmethod | Fixed type,Draw-outtype | ||||
HYM1
Molded-Case Circuit Breaker
Application scope
HYM1 is an ideal product for onshore and offshore application. The rated insulation voltage of 80ov (50ov for HYM1-63) is applicable tothe distribution network with the AC 50/60Hz,the rated working voltage of 690V(400V for HYM1-63).The circuit breaker is equipped with overload, short circuit and under-voltage protection devices,which can protect lines and power equipmentfromdamage.
reatuies
-Small volume,high breaking,short flashover and vibration resistance. -lt canbeinstalled vertically orhorizontally
-Ratedcurrentupto1250A
Main technical parameter
| FrameSize | 63、125、250、400、630、800、1250 |
| Ratedcurrent | 10A~1250A |
| Ratedvoltage | DC250,AC400V,AC690V |
| Ratedinsulationvoltage | AC800V(HYM1-63500V) |
| Poles | 2P、3P、4P |
Main technical parameter
| Ratedshort-circuit breakingcapacityclass | Rated ultimate short circuit breaking capacity Icu (kA) DC250V/AC400V/AC690V | Rated service short circuit breaking capacity lcs (kA) DC250V/AC400V/AC690V | |
| 63 | L | 25(AC400V) | 18(AC400V) |
| M | 50(AC400V) | 35(AC400V) | |
| 125 | L | 15/35/10 | 10/26/5 |
| M | 20/50/20 | 15/35/10 | |
| 250 | L | 20/35/10 | 15/25/5 |
| M | 25/50/20 | 18/35/10 | |
| 400 | L | 50(AC400V)/15(AC690V) | 35(AC400V)/8 |
| M | 65(AC400V)/20 | 42(AC400V)/10 | |
| 630 | L | 50(AC400V)/15 | 35(AC400V)/8 |
| M | 65(AC400V)/20 | 42(AC400V)/10 | |
| 800 | M | 75(AC400V)/30 | 50(AC400V)/15 |
| 1250 | M | 85(AC400V)/25 | 42(AC400V)/12.5 |
HYM1L
Earth Leakage Circuit Breaker
Application scope
It is applicable to circuits with AC 50Hz, rated insulation voltage of 80ov,rated working voltage of40oV, and rated current of 630A and below.It can provide indirect contact protection for people with fatal danger of electric shock,and also prevent fire hazard caused by ground fault current caused by equipment insulation damage.It can also be used to protect the overload, short circuit and undervoltage of lines,and also can be used forinfrequent switching of lines.
HYM3LCK
Earth Leakage Circuit Breaker
Main technical parameter
| Frame size | 125、250、400、630 | |||||
| Rated current | 16A~630A | |||||
| Ratedvoltage | AC230V/AC400V | |||||
| Ratedinsulationvoltage | AC800V | |||||
| Poles | 2P、3P、4P | |||||
| Ratedresidual currentI△n | 50mA、100mA、200mA、300mA、500mA、1000mA | |||||
| Ratedshort-circuitbreakingcapacityclass | 400 | 630 | ||||
| L | 125 M | 250 L | M | |||
| Rated ultimate short-circuit breaking capacity Icu (kA) AC230V/AC400V | 35/35 | 50/50 | 35/35 | 50/50 | 50(AC400) | 50(AC400) |
| Rated service short-circuit breaking capacity lcs (kA) AC230V/AC400V | 22/22 | 35/35 | 25/25 | 35/35 | 35(AC400) | 35(AC400) |
Application scope
HYM3LCK series residual current-acting circuit breaker is a new product developed by our company according to market demand,which isthefirst choice to match the operation of nationalintelligent power grid.
This series of products adopts LCD Chinese display, with many functions and intuitive. The circuit breaker part adopts the high breaking HuM8 circuit breaker,with high breaking capacity and accurate breaking time,integrated distribution comprehensive protection,and small size,easy to install and use, adjustable action value, easy to operate,can adapt to users around the It can be adapted to various users and environments, and set as required. In addition, the product has high-precision metering and measuring function,Beidou positioning function,temperature protection function andHPLC carrier,wireless Bluetooth,RS485 and other communication functions,but also has a station area topology identification function.
Products comply with the standards:GB/T32902,DL/T 20...
Communicationstatuteofresidualcurrentprotector.
Passed the test of China Electric Power Research Institute of Low-Voltage Electric Appliance Research Institute on communicationstandard.
Passed thecommunicationconformancetestbytheNational Grid CommunicationTestAuthorizationUnit.
Main technical parameter
| Framesize | 160、250、400、630、800 | ||||
| Rated current | 160、250、400、630、800 | ||||
| Settingcurrentrange | 64~800 | ||||
| Ratedvoltage | AC400 | ||||
| Ratedinsulationvoltage | AC1000 | ||||
| Poles | |||||
| Rated short-circuitbreakingcapacityclass | 3P+N、4P 400 | ||||
| Rated ultimate short-circuit breaking capacity Icu (kA) | 160 | 250 50/36(Ltype) | 630 | 800 | |
| Rated service short-circuit breaking capacity Ics (kA) | 50/36(Ltype) 36/20(Ltype) | 36/20(Ltype) | 70/50(L type) 70/36(Ltype) | 70/50(Ltype) 70/36(Ltype) | 70/50(L type) 70/36(Ltype) |
HUM9
Molded-Case Circuit Breaker
Application scope
HUM9 series molded case circuit breakers is the solution developed by EATON&HuYu for the all round integration of a company'sactivities,where each product isseenaspartof acompletesolution.
The circuit breakeris applicable to the power system with AC 50/60Hzrated voltage upto 690V and rated current up to 800A. It is used to distribute electric energy and protect the power system from overload,short circuit,undervoltage and other faults.Itcanalsobeused tocontrol infrequentmotoroperation.
The whole series canbe equipped with aunique"overload alarm withouttripping" functionto ensure overload continuity.
Features
-ZeroFlashoverdistance
-Compatible and differentiated design
-Standardized dimension(Depth,Cutout) when the panel is made
-Variousinstallable accessories
Conforming standards:IEC60947-2.
Main technical parameter
| Framesize | 63、100、125、250、400、630、800 |
| Rated current | 10A~800A |
| Ratedvoltage | AC400V/AC690V |
| Ratedinsulationvoltage | AC800(63AF)、AC1000 |
| Poles | 3P、4P |
| Ratedshort-circuit breakingcapacity class | Rated ultimate short circuit breaking capacity lcu (kA) AC400V/AC690V | Rated service short circuit breaking capacity Ics (kA) AC400V/AC690V | |
| 9 100 | S | 35(AC400) | 35(AC400) |
| S | 50/5 | 35/3 | |
| H | 50/10 | 65/5 | |
| 125 | R | 125/10 | 125/5 |
| S | 50/5 | 35/3 | |
| H | 50/10 | 65/5 | |
| 250 | R | 125/10 | 125/5 |
| S | 55/5 | 55/5 | |
| H | 85/10 | 85/5 | |
| 400 | R | 125/10 | 125/5 |
| S | 75/10 | 75/10 | |
| H | 100/15 | 100/10 | |
| 630 | R | 125/35 | 125/35 |
| S | 75/15 | 75/15 | |
| H | 100/20 | 100/15 | |
| 800 | R S | 125/35 | 125/35 |
| H | 75/15 100/20 | 75/15 100/15 | |
| R | 125/35 | 125/35 | |
HUM9L
Earth Leakage Circuit Breaker
Application scope
HUM9Lseries Earthleakage circuit breakeristo provideindirect contact protectionforpeople withfatal dangerofelectric shock,and also to prevent electrical fire caused bylong-term grounding fault current that cannot be detected by the overcurrentprotectiondevice.
Theresidual actioncurrentrating of the circuit breaker canbe adjusted,and the actiontime of the leakage protection can also be adjusted.Therefore, it can realize the selective protection of leakage inthe power distribution system.
Whentheratedresidualactioncurentissetto 30 \mathsf{m A} thecircuit breakercan alsobeusedasaprotectiondevicefordirect contact whentherelevant protection devicefails.
Features
-Breaking capacity upto 75kA Ics=Icu -Manual, Rotary or Motorised versions -Rated currentupto 630A -ROHScomplian
Conforming standards:IEC60947-2,IEC755
Main technical parameter
| Framesize | 100(125)、250、400、630 | |||
| Ratedcurrent | 10A~630A | |||
| Ratedvoltage | AC400V50Hz | |||
| Ratedinsulationvoltage | AC800V50Hz | |||
| Poles | 3P、4P | |||
| RatedresidualcurrentI△n | 100、300、500Adjustable,(500、800、100Adjustable) | |||
| Rated short-circuit breaking capacity class | 125 | 250 | 400 | 630 |
| Rated ultimate short-circuit breaking capacity Icu (kA) | 55 | 55 | 75 | 75 |
| Rated service short-circuit breaking capacity Ics(kA) | 55 | 55 | 75 | 75 |
HUM9E
ElectronicMolded-CaseCircuitBreaker
Application scope
HUM9E series electronic Molded Case Circuit Breakers is used to distribute electric energy and protect lines and power equipment from overload,shortcircuit,undervoltage and otherfaults,and alsotocontrol infrequent operation ofelectric motor.
The intelligent overcurrentrelease of the circuit breakeriscontrolled by amicroprocessor and hasthree section protection features,namely,overload inverse time delay protection, short circuit delay protection and short circuit instantaneous protection.Due to the adjustable artificial short circuit short time delay protection feature,the use category of the circuit breakeris Category B.Therefore,this series of circuit breakers can definitelyrealize selective protection with anothershortcircuit protection device connected in series on the load side.The three section overcurrent protection characteristics of the circuit breakercanbe easily set,whichcan meet therequirements of different loads onthe protection characteristics to achieve the best match.Therefore,the circuit breaker is an indispensable component in the intelligent power distribution systemwiththecomputerasthecore.
Conforming standards:IEC 60947-2.
Main technical parameter
| Frame size | 125、160、250、400、630、800、1250 | |||||||||
| Rated current | 50A ~1250A | |||||||||
| Ratedvoltage | AC400V/AC690V | |||||||||
| Ratedinsulationvoltage | AC1000 | |||||||||
| Poles | 3P、4P | |||||||||
| Rated short-circuitbreakingcapacity class | 125 | 160/250 | 400 | 630 | 800 | 1250 | ||||
| Rated ultimate short-circuit breaking capacity Icu (kA) | S | H | S | H | S | H S | H | S | H | |
| 55/5 | 1 85/20 | 55/5 | 85/2075/10100/3075/15100/3075/15100/3085/25 | |||||||
| AC400V/AC690V Rated service short-circuit breaking capacity Ics(kA) AC400V/AC690V | 55/555/10 | 55/5 55/1075/1075/20 75/1575/2075/1575/20 | 43/13 | |||||||
HUM8
Series Molded-Case Circuit Breaker/MCCB
Application scope
HUM8 series moulded case circuit breaker is applied in the network circuit of AC 50/60Hz, rated voltage to AC 690V power system,used to distribute electricenergyand power system protectionagainst overload,short circuit,undervoltage fault, also can be used to control the infrequent operation of electric machines.The characteristics of electronic release and intelligent release are accurate and convenient.Intelligentrelease has serial communicationinterface,which can meet the "fourremote"requirementsofcommunicationnetworking
The full series can be equipped with unique"overload alarm without tripping" function, to ensure continuity of power supply,tomeet therequirements of article6.3.6underGB50054.
Features
-Ratedcurrent upto1250A
-Breakingcapacityup to 200kA
-Eco-friendly Materials,compliant with the RoHS directive -CE,CBapproved.
Conforming standards:IEC60947-2
Main technical parameter
| Framesize | 63、100(125)、250、400、630、800 |
| Ratedcurrent | 10A~800A |
| Ratedvoltage | AC230V、AC400V、AC690V |
| Ratedinsulationvoltage | AC800V(63AF)、AC1000V |
| Poles | 2P、3P、4P |
HUM8
Series Molded-Case CircuitBreaker/MCCB
Main technical parameter
| Rated short-circuit breakingcapacityclass | Rated ultimate short circuit breaking capacity Icu (kA)Rated service short circuit breaking capacity lcs (kA) 230V/AC400V/AC690V | 230V/AC400V/AC690V | |
| 63 100 (125) | S | 50/30(AC400V) | 38/22(AC400V) |
| C | 50/30(AC400V) | 25/15(AC400V) | |
| S | 100/50/5 | 50/35/3 | |
| H | 125/85/10 | 125/65/5 | |
| 250 | U | 200/125/10 | 200/125/5 |
| C | 50/30(AC400V) | 25/15(AC400V) | |
| S | 100/50/5 | 50/35/3 | |
| H | 125/85/10 | 125/65/5 | |
| 400 | U C | 200/125/10 85/45/10 | 200/125/5 85/45/10 |
| S | 100/70/10 | ||
| 100/70/10 | |||
| H | 150/100/15 | 100/100/10 | |
| 630 | U C | 200/125/35 85/45/10 | 200/125/35 |
| S | 85/45/10 | ||
| 100/70/15 | 100/70/15 | ||
| H | 150/100/20 | 100/100/15 | |
| 800 | U | 200/125/35 | 200/125/35 |
| C | 85/45/10 | 85/45/10 | |
| S | 100/70/15 | 100/70/15 | |
| H U | 150/100/20 200/125/35 | 100/100/15 200/125/35 | |
HUM8L
Series Earth-Leakage Circuit Breaker/ELCB
Application scope
HUM8L series earth leakage circuit breaker (hereinafter referred to as the circuit breaker) power system for AC 50/60Hz, ratedvoltageto 40ov,rated current upto 630A,fortheelectricity distributionandpowersystem protection against overload and short-circuit fault harm,alsocan be used to control theinfrequentoperation of motors.
The leakage current(residual current)protectionfunction ofthe circuit breakeristo provideindirect contact protectionfor fatalelectrocution,andto preventelectrical firescaused bylong-existinggroundingfaultcurrentwhichare not detected by over-currentprotectiondevices.
The rated value of the residual operation current is adjustable, and the leakage protection operation time can also be adjusted.Therefore,the selective protection of leakage can be realized in the distribution system.When the rated residual operation current is set to 30mA,in the case of the failure of the protective device,the circuit breaker can also be used as a devicefordirectcontactwiththeprotectiveeffect.
According to the classification of DC component:AC type,to ensure the CBR of the release for the residual sinusoidal current,whether suddenly or slowly rising without DC component.A type,with a specified residual pulsating DCresidual sinusoidalACcurrent,ensures theCBRoftherelease,whetherit is suddenlyexerted orslowly rising.
Conforming standards:IEC 60947-2、IEC755.
Main technical parameter
| Frame size | 100(125)、250、400、630 | ||||||||||
| 10A~630A | |||||||||||
| Rated current Ratedvoltage | AC400V50Hz | ||||||||||
| Ratedinsulationvoltage | AC800 | ||||||||||
| Poles | 3P、4P | ||||||||||
| Rated short-circuitbreakingcapacityclass | 100(125) 250 | ||||||||||
| Rated ultimate short-circuit breaking capacity lcu (kA) | S | H | U | S | H | U | S | 400 H | U | 630 S H | U |
| 50 85 | 125 | 50 | 85 125 | 70 100 | 125 | 70 | 100 | 125 | |||
| Rated service short-circuit breaking capacity lcs (kA) | 35 | 65 | 125 | 35 | 65 125 | 70 | 100 | 125 | 70 | 100 | 125 |
HUM8D
Series Intelligent Molded-Case Circuit Breaker
Application scope
HUM8D series intelligent molded case circuit breaker has advanced design,reliable performance,high technical index; beautiful appearance,compact size,the use of microelectronics technology,with intelligent over-current protection function.
The circuit breakeris suitable forAC50/60Hz,rated voltage upto 690V,rated currentup to1250Ain the power system,used to distribute electricalenergy and protect the line and power supplyequipment from overload,short circuit,undervoltage and otherfaults,alsocan beused to controltheinfrequent operation of themotor.
The circuit breaker's intelligent over-current release is microprocessor-controlled and has three protection features,'i.e., overload inverse time long delay protection,short circuit delay protection and short circuit instantaneous protection.Due to the adjustable artificial short-circuit short-delay protection feature,this circuit breakeris used in category B.Therefore, this series of circuit breakers is clearly able to achieve selective protection with another short-circuit protection device connected in series on the load side.The three over-current protection characteristics of the circuit breaker can be easily adjusted to suit the requirements of different loads for the best matching of protection characteristics.The circuit breaker has operating currentindication,overload pre-warning indication,and strikerpowerand self-diagnosticindication.
The circuit breaker with H-type intelligent release is equipped with RS485 serial interface, which can set the protection characteristicparametersby programmerandmeettherequirements of communication network.
Conforming standards:IEC60947-1"Low-voltage switchgear and controlgear Part 1: General Provisions".IEC60947-2"LowvoltageswitchgearandcontrolgearPart2:Circuitbreakers".
Main technical parameter
| Frame size | 100、160、250、400、630、800、1250 |
| Ratedcurrent | 100~1250 |
| Settingcurrentrange | 40 ~1250 |
| Ratedvoltage | AC230V、AC400V、AC690V |
| Ratedinsulationvoltage | AC800V(100AF),AC1000V |
| Poles | 3P、4P |
Main technical parameter
| Ratedshort-circuit breakingcapacity class | Rated ultimate short circuit breaking capacity lcu (kA) 230V/AC400V/AC690V | Rated service short circuit breaking capacity lcs (kA) 230V/AC400V/AC690V | |
| 100 | 100/55/5 | 100/55/5 | |
| H | 125/85/20 | 125/85/10 | |
| 160 | 100/50/5 | 50/35/3 | |
| H | 125/70/10 | 125/50/5 | |
| U | 200/125/10 | 200/125/5 | |
| 250 | 100/50/5 | 50/35/3 | |
| H | 125/70/10 | 125/50/5 | |
| U | 200/125/10 | 200/125/5 | |
| 400 | 100/70/10 | 100/70/10 | |
| H | 150/100/15 | 100/100/10 | |
| U | 200/125/35 | 200/125/35 | |
| 630 | 100/70/15 | 100/70/15 | |
| H | 150/100/20 | 100/100/15 | |
| U | 200/125/35 | 200/125/35 | |
| 800 | 100/70/15 | 100/70/15 | |
| H | 150/100/20 | 100/100/15 | |
| U | 200/125/35 | 200/125/35 | |
| 1250 | S | 125/85/25 | 63/43/13 |
EXM3
Molded-Case Circuit Breakers
Application scope
The EXM3moulded case circuit breakers(hereafteras the MCCBs) are suitable foruse in electric systems of AC 50Hz/60Hz, with the rated insulation voltage of up to100ov(800v for125A and below frames) and rated current up to 800A,to distribute electrical energy,protect circuits and power equipment from hazards dueto overload,shortcircuit,under-voltage,and otherfaults,andcontrolinfrequentmotoroperations.
The EXM3MCCBs offerTypeC(basic),Type S(standard),and Type H(high breaking)based onits rated ultimate short-circuit breaking capacity,and feature smallsize,high breaking capacity, and short arcing distance.
Conforming standards:IEC60947-2
Main technical parameter
| Frame size | 63、125、160、250、400、630、800 |
| Ratedcurrent | 10A~800A |
| Ratedvoltage | AC240V,AC400/415VAC500V,AC690V |
| Ratedinsulationvoltage | AC800 (63AF、125AF)、AC1000 |
| Poles | 1P、2P、3P、4P |
Main technical parameter
| Ratedshort-circuit breakingcapacityclass | Rated ultimate short circuit breaking capacity Icu (kA) 240V/(400V/415V)/500V/690V | Rated service short circuit breaking capacity lcs (kA) 240V/(400V/415V)/500V/690V | |
| 63 | C | 30/20/-/- | 20/10/-/- |
| S | 40/36/-/- | 30/25/-/- | |
| H | 75/50/-/- | 50/36/-/- | |
| 125 | C | 30/20/-/- | 20/10/-/- |
| S | 40/36/-/- | 30/25/-/- | |
| H | 75/50/-/- | 50/36/-/- | |
| 160 | C | 40/20/-/8 | 20/10/-/4 |
| S | 50/36/-/8 | 30/25/-/4 | |
| H | 75/50/30/10 | 50/36/30/5 | |
| 250 | C | 40/20/-/8 | 30/15/-/5 |
| S | 50/36/-/8 | 30/25/-/5 | |
| H | 75/50/30/10 | 50/36/30/5 | |
| 400 | C | 50/40/-/10 | 50/30/-/10 |
| S | 75/50/-/10 | 50/36/-/10 | |
| H | 100/70/36/15 | 75/50/36/10 | |
| 630 | C | 50/40/-/10 | 50/30/-/10 |
| S | 75/50/-/10 | 50/36/-/10 | |
| H | 100/70/36/15 | 75/50/36/10 | |
| 800 | C | -/50/-/- | -/35/-/- |
| S | -/70/-/- | -/50/-/- | |
EXM3L
Series Earth-Leakage Circuit Breaker/ELCB
Application scope
The EXM3L series earth leakage circuit breaker (hereafter as the ELCB) are developed with global leading technology, offering reliable performance, powerful technical features, easy maintenance, sleek design, and smallsize.
The RCCBs are suitable for use in electrical systems of AC 50Hz/60Hz, with the rated voltage of up to 415V and rated current of up to 800A,to distribute electrical energy,prevent the electrical systems from hazards due to overload, short-circuit and otherfaults,andcontrolinfrequentmotoroperations.
The ELCB offer leakage (residual current) protection to provide indirect contact protection against fatal electric shock, and preventelectrical fires caused bylongstanding ground fault currentsthat cannot be detected by over-current protectors. The RCcBs can also be used to provide direct contact protection when the concerned protector fails, with the rated residual operatingcurrentsetto 30 \mathsf{m A} (for non-delay type).Be noted that the ELCB does not offer protection against electric shock dueto simultaneous contact of two load conductors(two phase wires,orany phase wire and neutral wire).
Both theresidual operating currentratings and protection actuation time are adjustable,achieving selectivity protection in the event of residual currents.Two DC component types are available,including Type AC-CBR that ensures tripping caused byresidual sinusoidal current withno DC component,whether it is suddenlyapplied or slowly rising,and TypeA-CBRthat ensures tripping caused by residual sinusoidal current and residual pulsating DC (with/without specified superimposed DC component),whetheritissuddenlyapplied or slowly rising;
Conforming standards:IEC60947-2
Main technical parameter
| Frame size | 125、160、250、400、630、800 |
| Ratedcurrent | 16A~800A |
| Ratedvoltage | AC415V |
| Rated insulationvoltage | AC1000V |
| Poles | 3P、4P |
| RatedresidualcurrentI△n | Adjustable 30mA ( Non-delay type only) /50mA/100mA/200mA/300mA/400mA/500mA/600mA/800mA/1000mA |
Main technical parameter
| Ratedshort-circuit breakingcapacityclass | Rated ultimate short circuit breaking capacity Icu (kA) 415V | Rated service short circuit breaking capacity lcs (kA) 415V | |
| 125 | C | 20 | 10 |
| S | 36 | 25 | |
| H | 50 | 36 | |
| 160 | C | 20 | 10 |
| S | 36 | 25 | |
| H | 50 | 36 | |
| 250 | C | 20 | 15 |
| S | 36 | 25 | |
| H | 50 | 36 | |
| 400 | C | 40 | 30 |
| S | 50 | 36 | |
| H | 70 | 50 | |
| 630 | C | 40 | 30 |
| S | 50 | 36 | |
| H | 70 | 50 | |
| 800 | C | 40 | 30 |
| S | 50 | 36 | |
| H | 70 | 50 | |
EXM3E
ElectronicMolded-CaseCircuitBreaker
Application scope
The EXM3E electronic-type molded case circuit breakers (hereafter as the MCCBs) are developed with global leading technology,featuring advanced design,offering reliable performance,powerful technical features,easy maintenance, sleekdesign,andsmall size.
The EXM3E MCCBs are suitable for use in electric systems ofAC 50Hz/60Hz,with the rated insulation voltage of upto 1,000v and rated current of upto 1250A,to distribute electricalenergy,protect circuits and powerequipment from hazards dueto overload,short-circuit,under-voltage,and otherfaults,and controlinfrequentmotoroperations.
The EXM3E MCCBs offer Type C (basic), Type S (standard), and Type H (high breaking) based on the rated ultimate shortcircuitbreakingcapacity.
Conforming standards:IEC60947-2
Main technical parameter
| Framesize | 125、160、250、400、630、800、1000、1250 |
| Ratedcurrent | 125A~1250A |
| Ratedvoltage | AC220/230/240/380/400/415/660/690V |
| Ratedinsulationvoltage | AC1000V |
| Poles | 3P、4P |
Main technical parameter
| Rated short-circuit breakingcapacityclass | Rated ultimate short circuit breaking capacity lcu (kA) 240V/(400V/415V)/500V/690V | Rated service short circuit breaking capacity Ics (kA) 240V/(400V/415V)/500V/690V | |
| 125 | C | 40/20/-/8 | 20/10/-/4 |
| S | 50/36/-/8 | 30/25/-/4 | |
| H | 75/50/30/10 | 50/36/30/5 | |
| 160 | C | 40/20/-/8 | 20/10/-/4 |
| S | 50/36/-/8 | 30/25/-/4 | |
| H | 75/50/30/10 | 50/36/30/5 | |
| 250 | C | 40/20/-/8 | 30/15/-/5 |
| S | 50/36/-/8 | 30/25/-/5 | |
| H | 75/50/30/10 | 50/36/30/5 | |
| 400 | C | 50/40/-/10 | 50/30/-/10 |
| S | 75/50/-/10 | 50/36/-/10 | |
| H | 100/70/36/15 | 75/50/36/10 | |
| 630 | C | 50/40/-/10 | 50/30/-/10 |
| S | 75/50/-/10 | 50/36/-/10 | |
| H | 100/70/36/15 | 75/50/36/10 | |
| 800 | S | 75/50/-/20 | 50/36/-/10 |
| H | 100/70/-/30 | 75/50/-/20 | |
| 1000 | S | 75/50/-/20 | 50/36/-/10 |
| H | 100/70/-/30 | 75/50/-/20 | |
| 1250 | S | 75/50/-/20 | 50/36/-/10 |
| H | 100/70/-/30 | 75/50/-/20 | |
EXT3-63
CB Class Automatic Transfer Switching Equipment
Application scope
EXT3-63transferswitchis applicableto dual power supply system withAC 50Hz,rated working voltage of400V and below, andratedcurrentof10Ato63A
The two power supplies of the power supply system:the common power supply (N) and the standby power supply (R) are detected atthe same time.When the power supply has undervoltage and phase failure,it will automatically switch from the abnormal power supply to the normal power supply (or manual switching),improving the continuity,safety and reliability ofthepowersupplysystemintheuseplace.
Conforming standards:IEC 60947-6-1
Main technical parameter
| FrameSize | 63 |
| Ratedoperationalcurrent | 10A~63A |
| Ratedvoltage | AC400V(3P、4P) AC230V (2P) |
| Rated impulse withstand voltage Uimp | 4kV |
| Poles | 2P、3P、4P |
| Installationmode | Verticalfixed type |
| Electricalclass | CCC、CQC、CE |
| Utilizationcategory | AC-32B |
EXT3
Automatic Transfer Switching Equipment
Application scope
EXT3 dual power automatic conversion device is applicable to dual power supply systems with AC 50/60Hz, rated singlephase 400v (level3 and 4) and below, and rated current of10Ato 630A.It detects the two power supplies ofthe power supply system: common power supply (N) and standby power supply (R) at the same time, and automatically switches from abnormal power supply to normal power supply (or manual switching) in case of power failure such as undervoltage and phasefailure,Improve the continuity,safety and reliabilityofthe powersupply system at the place ofuse.
Conforming standards:IEC60947-6-1
Main technical parameter
| FrameSize | 125、160、250、400、630 |
| Ratedoperationalcurrent | 10A~630A |
| Ratedvoltage | AC400V |
| Rated impulse withstand voltage Uimp | 8kV、12kV |
| Poles | 3P、4P |
| Installationmode | Verticalfixed type |
| Electricalclass | CCC、CQC |
| Utilizationcategory | AC-33iB |
EXT3P
PC Class Automatic Transfer Switching Equipment
Application scope
EXT3P change-over switch is applicable to the dual power supply system with AC50/60Hz,rated working voltage of 230V (level 2),400v (level3,4) and below, and rated current of 16Ato 250A.It detects the two power supplies of the power supply system: common power supply (N) and standby power supply (R) at the same time, and automatically switches from the abnormal power supply to the normal power supply (it can also be set to manual switching) in case of power supply failure of undervoltage and phasefailure,Improve thecontinuity,safety andreliability of the power supplysystem atthe placeof Use.
Conforming standards:IEC 60947-6-1
HR6
Fuse type Knife Switch
Main technical parameter
| FrameSize | 125、250 |
| Ratedoperationalcurrent | 16A~250A |
| Ratedvoltage | AC400V |
| Rated impulse withstand voltage Uimp | 8kV |
| Poles | 2P、3P、4P |
| Installationmode | Integrated |
| Electricalclass | CCC、CQC、CE |
| Utilizationcategory | AC-33B |
Application scope
It is mainly used in power distribution circuits and motor circuits with high short circuit current with rated voltage of 400v and rated working current of 630A as power switch, disconnector,emergency switch and circuit protection,but generally notusedtodirectly switchasinglemotor.
Conforming standards: IEC 60947-3
Main technical parameter
| Model | HR6-160、HR6-250、HR6-400、HR6-630、HR6-800 |
| Ratedoperationalcurrent | HR6-160:160A HR6-250:250A HR6-400:400A HR6-630:200A、250A、315A、400A、500A、630A HR6-800:200A、250A、315A、400A、500A、630A、800A |
| Ratedvoltage | HR6-1000:800A、1000A AC400V/690V |
| Ratedinsulationvoltage | AC1140V |
| Poles | 3P |
HR17
Fuse type Knife Switch
Application scope
Hr17 series fuse Knife switch can be operated with load, and is applicable to rated current of 40A\~630A,including 1 group,2 groups and 3 groups.It can be mounted on the bus or fixed plate;The upper and lower input and output structures are provided, with knife edge lead-in and arc extinguishing devices; The switch cover is irregularly provided with closed detection holes, and built-in signal switches and detection switches.It can be equipped with fuse monitor orused as knife Switch.
Conforming standards:IEC60947-3
HYGL
Load switch
Main technical parameter
| Conventionalthermalcurrent | 40A:10A、16A、20A、25A、32A、40A; 63A:16A、20A、25A、32A、40A、50A、63A; 160A:16A、20A、25A、32A、40A、50A、63A、80A、100A、125A、160A; 250A:80A、100A、125A、160A、200A、250A; 400A:125A、160A、200A、250A、315A、400A; 630A:200A、250A、315A、400A、500A、630A; |
| Ratedvoltage | 800A:800A AC400V |
| Poles | 3P |
Application scope
HYGL series disconnectors are suitable for enterprise power distribution settings with AC 50Hz,rated voltage up to 69ov,DC voltage up to 440V, and agreed heating current up to 3200A.They are used for frequent connection and disconnection of circuits and electrical isolation (above 1oooAis only used forelectricalisolation). They are widely used in power distribution systems and automation systemsinbuildings,electricpower,petrochemical and otherindustries.
HYGL/C side operated disconnector adds a side operated mechanism on the basis of HYGL front central operated disconnector, whichis suitable for making and breaking circuit of side operation and electrical isolation.
HYGL/Z double throw transfer disconnectoris composed of two HYGL disconnectors stacked up and down orassembled side by side from left to right.It is applicable to the switching of two-way power supply orthe switching and safety isolation of two
Main technical parameter
| Conventionalthermalcurrent | 100A、160A、250A、400A、630A、1000A、1250A、1600A、2500A、3200A |
| Ratedinsulationvoltage | 1000V、1140V |
| Ratedimpulsewithstandvoltage | 12kv |
| Ratedoperationalcurrent | HYGL100:10A、16A、20A、25A、32A、40A、50A、63A、80A、100A HYGL-160:16A、20A、25A、32A、40A、50A、63A、80A、100A、125A、160A HYGL-250:80A、100A、125A、160A、200A、250A HYGL-400:125A、160A、200A、250A、315A、400A HYGL-630:200A、250A、315A、400A、500A、630A HYGL-1000:800A、1000A HYGL-1250:1000A、1250A HYGL-1600:1000A、 1250A、1600A HYGL-2500:2000A、2500A |
| Ratedoperationalvoltage | HYGL-3200:2500A、3200A |
| Poles | AC400V 3P、4P |
HH15(QSA)
Disconnector fuse group (with fuse)
Application scope
HH15 (QsA) series disconnectors fuse group disconnectors (hereinafter referred to as switches) are mainly used in distribution circuits and motor circuits with high short circuit current as main switches or master switches for infrequent manual operation.Itis especiallysuitable forinstallationin advanced drawertypelow-voltage completesets.
Conforming standards: IEC 60947-3
Main technical parameter
| ConventionalthermalcurrentIth | 63A | 125A | 160A | 250A | 400A | 630A | 800A | 1000A | 1250A | |
| Rated currentle | 63A | 125A | 160A | 250A | 400A | 630A | 800A | 1000A | 1250A | |
| Use catagory | AC-23B | AC-22B | ||||||||
| Rated limitingshort-circuitcurrentlq | 50kA | |||||||||
| Mechanical(cycle) | 3400 | 2800 | 2800 | 2800 | 1600 | 1600 | 1000 | 600 | 600 | |
| Electrical(cycle) | 600 | 400 | 400 | 400 | 400 | 400 | 200 | 200 | 200 | |
| Selectionoffuselink | RT16-00 | RT16-1 | RT16-2 | RT16-3 | RT16-3B | RT16-4 | ||||
| Torque (N·m) | 7.5 | 16 | 30 | 35 | ||||||
| Weight (kgwithouthandle) | 1.6 | 1.7 | 4.1 | 4.5 | 4.7 | 14.0 | 14.5 | 27.0 | 29.0 | |
HH15A(QA)
Disconnector (the'switch is in series inside and the inlet and outlet terminals are horizontal)
Application scope
HH15 (QA) series disconnectors (hereinafter referred to as switches) are mainly used in power distribution circuits and motor circuits with high short circuit current as main switches or master switches forinfrequent manual operation.It is especially suitableforinstallationin advanced drawertypelow-voltagecompletesets.
Conforming standards:IEC60947-3
Main technical parameter
| ConventionalthermalcurrentIth | 125A | 200A | 400A | 630A | 1000A |
| Rated current le | 125A | 200A | 400A | 630A | 1000A |
| Use catagory | AC-23B | ||||
| Rated limitingshort-circuitcurrentlq | 8kA | 30kA | 50kA | ||
| Mechanical (cycle) | 4kA | 20kA | 30kA | ||
| Electrical(cycle) | 2800 | 1600 | 1000 | ||
| Selectionoffuselink | 400 | 400 | 200 | ||
| Torque (N·m) | 7.5 | 16 | 30 | ||
| Weight (kgwithouthandle) | 1.5 | 1.6 | 4.1 | 4.3 | 11.7 |
HH15(QP)
Disconnector(switch isinparalle internally,and incoming and outgoing line ends are instaggered order)
Application scope
HH15 (QP) series disconnectors (hereinafter referred to as switches) are mainly used in power distribution circuits and motor circuits with high short-circuit current as main switches or master switches for infrequent manual operation. It is especially suitableforinstallationin advanced drawertypelow-voltagecompletesets.
Conforming standards:IEC 60947-3
Main technical parameter
RT16(NT)
| ConventionalthermalcurrentIth | 250A | 630A | 1000A | 1250A | 1600A | 2500A | 3150A |
| Ratedcurrentle | 250A | 630A | 1000A | 1250A | 1600A | 2500A | 3150A |
| Usecatagory | AC-23B | AC-20B | |||||
| Rated limiting short-circuit currentlq | 10kA | 30kA | 32kA | 50kA | |||
| Mechanical (cycle) | 2800 | 1600 | 1000 | 1000 | 1000 | 600 | 600 |
| Electrical (cycle) | 400 | 400 | 200 | 200 | 200 | ||
| Torque (N·m) | 7.5 | 16 | 30 | 70 | |||
| Weight (kgwithouthandle) | 1.9 | 5.0 | 5.4 | 14.0 | 14.5 | 49.0 | 52.5 |
Enclosed Tube Type Knife blade Fuse
Application scope
RT16 series low voltage fuses has the advantages of small size,light weight, low power consumption and high breaking capacity,and is used in AC power distribution device with rated frequency 50Hz,rated voltage upto AC69oV and below,and with rated current up to 1250A for overload and short-circuit protection.Also,the product with an “impactor” function is selected and used in the electrical devicessuch as power distribution devicefor signaloutput in case of product fusing.
Conforming standards:IEC 60947-2.
Main technical parameter
| Fuse size | 0、00C、00、1、2、3、4 |
| Rated currentIn | FuSeSiZe0:2A、4A、6A、8A、10A、12A、16A、20A、25A、32A、40A、50A、63A、80A、100A FuSeSize00:2A、4A、6A、8A、10A、12A、16A、20A、25A、32A、40A、50A、63A、80A、100A FuSeSize00C:2A、4A、6A、8A、10A、12A、16A、20A、25A、32A、40A、50A、63A、80A、100A FuSeSize1:80A、100A、125A、160A、200A; FuSeSize2:125A、160A、200A、250A、300A、315A、400A; FuSeSize3:315A、400A、500A、630A |
| Ratedvoltage | FuSeSize4:800A、1000A |
| Frequency | 660V 50Hz |
RT18
Enclosed Tube TypeFuse
Application scope
It is suitable for overload and short circuit protection in power distribution devices with rated voltage of 220v/380V and ratedcurrentof63A.Neonlampand resistance
Fuse link fusing signal device (code"x") constituting isolator.
Conforming standards:IEC 60947-2
Main technical parameter
| Model | RT18-32、RT18-32X、RT18-63、RT18-63X |
| Rated current | RT18-32:2A、4A、6A、8A、10A、16A、20A、25A、32A; RT18-32X:2A、4A、6A、8A、10A、16A、20A、25A、32A; RT18-63:2A、4A、6A、8A、10A、16A、20A、25A、32A、40A、50A、63A; |
| RT18-63X:2A、4A、6A、8A、10A、16A、20A、25A、32A、40A、50A、63A | |
| Ratedvoltage | 380V/660V |
| Frequency | 50Hz |
RSO
Enclosed Tube Type Fuse
Application scope
It is applicable to the short circuit or overload protection of silicon rectifier components and their complete sets in AC circuitswithratedvoltagenotexceeding750V and frequency50Hz.
Conforming standards :IEC 60947-1/IEC 60947-4.
Main technical parameter
| Model | RS0-100、RS0-200、RS0-350、RS0-480 |
| Ratedcurrent | RS0-100:80A、100A RS0-200:150A、200A RS0-350:200A、250A、320A、350A |
| Frequency | RS0-480:480A 50Hz |
EXB3-40
Miniature Circuit Breaker
Feature
- Compactin structure and has two polesin the width of 18mm
-Thermal-electromagnetictripping mechanism
-DIN railmouting
-CBapproved
Conforming standards:EN/IEC60898-1
Main technical parameter
| Productmodel | EXB3-40 |
| No. of poles | 1P+N |
| Rated current | 6A、10A、16A、20A、25A、32A、40A |
| Ratedvoltage | AC230V |
| Ratedfrequency | 50Hz/60Hz |
| Ratedimpulsewithstandvoltage | 4kV |
| Ratedshort-circuitbreakingcapacity | 4500A |
| Ratedserviceshort-circuit breaking capacity | 4500A |
| Instantaneoustrippingtype | C、D |
| Mechanical life(cycles) | 20000 |
| Electricallife(cycles) | 8000 |
EXB3-63
Miniature Circuit Breaker
Feature
-Costeffective -For all applications upto 63A -Thermal magnetic protection -Highquality, subtle,and precise -CB、RoHS、KEMA、CE approved
Conforming standards:EN/IEC60898-1
Main technical parameter
| Productmodel | EXB3-63 |
| No. of poles | 1P、1P+N、2P、3P、3P+N、4P |
| Rated current | 1A、2A、3A、4A、6A、10A、 16A、20A、25A、32A、40A、50A、63A |
| Rated voltage | AC230V/400V(1P),AC230V(1P+N) AC400V(2P、3P、3P+N、4P) |
| Rated frequency | 50Hz/60Hz |
| Rated impulse withstand voltage | 6kV |
| Ratedshort-circuitbreakingcapacity | 6000A |
| Rated service short-circuit breakingcapacity | 6000A |
| Instantaneous tripping type | B、C、D |
| Mechanical life(cycles) | 20000 |
| Electrical life(cycles) | 8000 |
EXB3-125
High breaking Miniature Circuit Breaker
Features
-RatedCurrentupto125A
-Switchgearforindustrialand advanced commercialapplications
-CB、CE、TUVapprove
Conforming standards:EN/IEC60947-2
Main technical parameter
| Product model | EXB3-125 |
| No. of poles | 1P、1P+N、2P、3P、3P+N、4P |
| Rated current | 63A、80A、100A、125A |
| Ratedvoltage | AC230V(1P、1P+N) AC400V(2P、3P、3P+N、4P) |
| Rated frequency | 50Hz/60Hz |
| Ratedimpulsewithstandvoltage | 4kV |
| Ratedshort-circuitbreakingcapacity | 6000A |
| Rated service short-circuit breakingcapacity | 6000A |
| Instantaneoustrippingtype | C、D |
| Mechanical life(cycles) | 10000 |
| Electrical life(cycles) | 6000(In≤100A),4000(In>100A) |
EXB3LY-63
Residual Current Circuit Breaker with Overcurrent Protection
Feature
-Costeffective -Forall applications upto 63A -Thermal magnetic protection -Highquality, subtle,nd preis
Conforming standards:EN/IEC61009-1
Main technical parameter
| Product model | EXB3LY-63 |
| No. of poles | See Table 1 |
| Rated current | 6A、10A、16A、20A、25A、32A、40A、50A、63A |
| Rated voltage | AC230V |
| Ratedoperatingfrequency | 50Hz/60Hz |
| Rated impulsewithstandvoltage | 4kV |
| Breaking capacity | See Table1 |
| Ratedresidualoperatedcurrent | 30mA、50mA(only50mAfordelaytype) |
| Instantaneoustrippingtype | SeeTable1 |
| Mechanical life(cycles) | 20000 |
| Electrical life(cycles) | 10000 |
| Residual current type | See Table 1 |
| Productmodel | No.ofPoles | Breaking capacityIcn | Breaking capacityIcs | Instantaneous tripping type | Residual current type | Remark |
| EXB3LY-63 | 1P+N、N-pole with break point | 6000A | 6000A | B、C、D | Type AC/A | Withisolation function |
EXB3LE-63
Residual CurrentCircuitBreakerwithOvercurrentProtection
Feature
-Costeffective
-For allapplications up to 63 A -Thermal magnetic protection -High quality,subtle,and precise -CBapproved
Conforming standards:EN/IEC61009-1
Main technical parameter
| Product model | EXB3LE-63 | ||||||
| No.of poles | See Table 1 | ||||||
| Rated current | 6A、10A、16A、20A、25A、32A、40A、50A、63A | ||||||
| Rated voltage | AC220V/230V/240V(1P+N、2P),AC380V/400V/415V(3P、3P+N、4P) | ||||||
| Rated operatingfrequency | 50Hz/60Hz | ||||||
| Rated impulsewithstandvoltage | 4kV | ||||||
| Breakingcapacity | See Table 1 | ||||||
| Ratedresidual operated current | 30mA、50mA、75mA、100mA、300mA | ||||||
| Instantaneous trippingtype | See Table 1 | ||||||
| Over-voltageprotectionrange | See Table1 | ||||||
| Mechanical life(cycles) | 20000 | ||||||
| Electrical life(cycles) | 8000 | ||||||
| Residual current type | See Table1 | ||||||
| Table 1 | |||||||
| Product model | No.of poles | Breaking capacityIcn | Service breaking capacityIcs | Over-voltage protectionrange | Instantaneous trippingtype | Residual current type | |
| EXB3LE-63 | 1P+N、2P、3P、3P+N、4P | 6000A | 6000A | B、C、D | Type AC/A | ||
EXB3LE-125
Residual Current Circuit Breaker with OvercurrentProtection
Features
-RatedCurrentupto125A -Switchgearforindustrialand advanced commercialapplications
Conforming standards:IEC 60947-2
Main technical parameter
| Product model | EXB3LE-125 |
| No. of poles | 1P+N、2P、3P、3P+N、4P |
| Rated current | 63A、80A、100A、125A |
| Ratedvoltage | AC230V(1P+N、2P),AC400V(3P、3P+N、4P) |
| Ratedoperatingfrequency | 50Hz/60Hz |
| Rated impulsewithstandvoltage | 4kV |
| Ratedshort-circuitbreakingcapacity | 4500A |
| Ratedserviceshort-circuitbreakingcapacity | 4500A |
| Ratedresidual current | 30mA、50mA、75mA、100mA、150mA、200mA、300mA |
| Instantaneous tripping type | C、D |
| Mechanical life(cycles) | 10000 |
| Electrical life(cycles) | 6000(In≤100A).4000(In>100A) |
EXB3L1-100
Residual Current Circuit Breaker
Features
-High quality execution and attention to details -Leakagecurrentprotection,thermalmagnetictripping -Rated Currents from 16A upto100A -Rated Sensitivity10mA,30mA,50mA,100mA,300mA -CB、CE、RoHS approved
Conforming standards:IEC61008-1
Main technical parameter
| Items | Parameter |
| Ratedvoltage | 240V(2P)、415V(4P) |
| Insulationvoltage | 500V |
| Rated impulse withstand voltage(Uimp) | 4kV |
| No. of poles | 2P、4P |
| Ratedcurrent | 16A、25A、32A、40A、50A、63A、80A、100A |
| Ratedresidualcurrent(In) | 10mA(16A,25A,32A,40A),30mA,50mA,100mA,300mA |
| Type | AC/A |
| Ratedcurrentmaking&breakingcapacity(lm) | 1000A |
| Ratedresidual currentmaking&breakingcapacity(Im) | 1000A |
| Ratedconditional short-circuitcurrent(Icn) | 10kA |
| Rated residual conditional short-circuit current(Ic) | 10kA |
Breaking time of residual current under I△n
| Type(wave form of the earth leakage sensed) | 1n(mA) | In(A) | Maximum breaking time | |||
| I△n | 21n | 51△n | 250mA | |||
| Rated sensitivity of A/AC type | >30 | 16A,25A,32A,40A 50A,63A,80A,100A | 0.1 | 0.1 | 0.04 | |
| 00 | 0.1 | 0.1 | 0.04 | |||
| Rated sensitivityofA type | In(mA) | In(A) | Maximum breaking time | |||
| 1.41n | 2.81n | 71△n | 0.35A | |||
| >30 | 16A,25A,32A,40A 50A,63A,80A,100A | 0.1 | 0.1 | 0.04 | ||
| ≤30 | 0.1 | 0.1 | 0.04 | |||
The circuit breaker is connected with cable (the cable selection is shown in Table 3), Tightening torque:2.0 N· m\~2.5 N· m
| Rated currentIn(A) | 16、20 | 25 | 32 | 40、50 | 63 | 80 | 100 |
| Terminalsizeforcable(mm2) | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 |
EXH3-125
Switch Disconnectors (Modular Isolators)
The EXH3-125 disconnector switches offer below functions: -Isolationfunction
Main technical parameter
| Product model | EXH3-125 |
| No. of poles | 1P、2P、3P、4P |
| Rated current | 20A、25A、32A、40A、50A、63A、80A、100A、125A |
| Rated insulation voltage | 500V |
| Ratedvoltage | AC220V/230V/240V(1P),AC230V(2P),AC380V/400V/415V(2P、3P、4P) |
| Ratedoperatingfrequency | 50Hz/60Hz |
| Ratedimpulsewithstandvoltage | 6kV |
| Ratedshort-timewithstandcurrent | 1.5kA(RMS), t=1s |
| Ratedshort-circuitmakingcapacity | 2.5kA(peak) |
| Mechanical life(cycles) | 8500 |
| Electrical life(cycles) | 3000 |
| Utilizationcategory | AC-22A、AC-21B |
HUM18-63(Z)
Miniature Circuit Breaker
Application scope
HUM18-63 series miniature circuit breakers (hereinafter referred to as circuit breakers) are mainly used for over-current protection of powerline facilitiesand electricalequipmentin buildings and similar places withAC50/60Hz,ratedvoltage of 230v/40oV andrated working current of no more than 63A,and also forinfrequent on-offoperations.
Conforming standards:EN/IEC60898-1.
Main technical parameter
| Frame size | 63 | |
| RatedVoltage | 50HZ AC230V/400V,DC220V(1P、2P) | |
| Rated Current | 1、2、4、6、10、16、20、25、32、40、50、63 | |
| Ratedbreakingcapacity | AC10000A,DC:6000A | |
| Ratedservice short-circuitbreakingcapacity | AC7500A,DC:6000A | |
| Poles | 1P、2P、3P、4P、1P+N、3P+N | |
| Lifespan(cycle) | Mechanical | 20000 |
| Electrical | 10000 | |
| Characteristicsand Trip current range | Bcurve | AC:3~5ln |
| Ccurve | AC:5~10ln DC:7~14ln | |
| Dcurve | AC:10~20ln | |
HUM18-63N
Miniature Circuit Breaker
Application scope
HUM18-63N series Miniature circuit breakers offer a compact solution forall areas of protection requirements.They put you in control of all electric circuits -in industry,in non-residential buildings and in residential buildings.
The circuit breakers arein accordance with GB/T 14048.2 and IEC 60947-2 standards.
Conforming standards:EN/IEC60898-1.
Features
-RoHS compliant -KEMA,CB approved -Suitable forreverse feed -Fingersafe terminals -Widerange of accessories
HUM18-80
Miniature Circuit Breaker
Main technical parameter
| Frame size | 63 | |
| RatedVoltage | 50Hz,230/400V((1P),400V(2P,3P,3P+N,4P) | |
| RatedCurrent | 1、2、4、6、10、16、20、25、32、40、50、63 | |
| Ratedbreakingcapacity | 6000 | |
| Poles | 1P、1P+N、2P、3P、3P+N、4P | |
| Trip Curve | B、C、D | |
| Lifespan(cycle) | Mechanical | 20000 |
| Electrical | 10000 | |
Application scope
HUM18-80 seriesminiature circuit breakers are mainly used forover-current protection of powerline facilities and electrical equipment in buildings and similar places with AC 50/60Hz, rated voltage up to 380/400V and rated working current not exceeding80A,andalsoforinfrequenton-offoperations.
Conforming standards:EN/IEC60898-1.
Main technical parameter
| Frame size | HUM18-80/HUM18-80E | |
| RatedVoltage | 230/400V(1P),400V(2P,3P,3P+N,4P) | |
| RatedCurrent | 80A | |
| Trip Curve | 6000 | |
| Ratedbreakingcapacity | 1P、2P、3P、3P+N、4P | |
| Poles | C、D | |
| Lifespan(cycle) | Mechanical | 20000 |
| Electrical | 10000 | |
HUM18-125
Miniature Circuit Breaker
Application scope
HUM18-125 seriesminiaturecircuit breakers aremainly used for over-current protection of power facilities and electrical equipment in power lines with AC 50/60Hz, rated voltage of 230v/400V and rated working current of 125A, and also for infrequenton-offoperations.
This productasreliableerformance,accurateprotectioncharacteristic,highreakingcapacity,mallsize,andgat appearance,and is anidealreplacementproduct.
Conforming standards:EN/IEC60898-1.
Features
-Energylimiting -Breaking capacityupto 15kA -Suitable forreverse feed
Main technical parameter
| Frame size | 125 | |
| Ratedvoltage | 50HZ 230V/400V | |
| Rated current | B、Ccurve | 63、80、100、125 |
| D curve | 63、80、100 | |
| Ratebreakingcapacity | lcs=7500A 1cn=15000A | |
| Poles | 1P、2P、3P、4P | |
| Characteristics and Trip current range | B curve | 3ln~5ln |
| Ccurve | 5ln~10ln | |
| Dcurve | 10ln~20ln | |
| Lifespan (cycle) | Mechanical | 20000 |
| Electrical | 10000 | |
HUM18LY-63
Residual CurrentCircuitBreakerwithOvercurrentProtection
Application scope
HUM18LY-63 RCBO combine residual current circuit breakers and miniature circuit breakers in one device.It protects people fromfaultcurrents and systemsfrom shortcircuitsand overload.
Features
-TypeAC,Type A
-Completerangeofaccessories
-Less spacerequired dueto compact design and less wiring
Main technical parameter
| Model | HUM18LY-63 | |
| Poles | 1P+N,N-pole is switched on and off togetherwith otherpoles,without protection | |
| Ratedcurrent | 6、10、16、20、25、32、40、50、63 | |
| RatedresidualoperatingcurrentIn(mA) | 30mA,50mA | |
| Leakage type | AC、A | |
| Rated breaking capacity | Voltage (V) | 230 |
| Breaking capacity (A) | 10000 | |
| Ratedresidualmakingandbreakingcapacity(A) | 2000 | |
| Trip curve | B、C、D | |
| Remark | Withisolationfunction | |
HUM18LE-63
SeriesMiniature CircuitBreaker
HUH18-125
Series Isolator switch
Application scope
HUM18LE series miniature leakage circuit breaker is a new product developed by our company. It is suitable for AC 50\ensuremath{\H{z}} rated voltage 40ov,rated current does not exceed 63A,neutral grounding power circuit,mainly for personal electric shock protection and line equipment on buildings and similar use of overcurrent protection, it can also be used to protect the electricalequipment frominsulation damageofground fault currentcausedbythefireriskprotection.
Conforming standards:EN/IEC61009-1.
Main technical parameter
| Model | HUM18LE-63 |
| Poles | 1P+N、2P、3P、3P+N、4P |
| Ratedcurrent (A) | 6、10、16、20、25、32、40、50、63 |
| Rated residualoperating current In (mA) | 30、50、75、100、150、200、300 |
| Ratedresidual operatingVoltage(V) | 230/400V |
| Rated breaking capacity (A) | 10000 |
| Rated residual making and breaking capacity (A) | 2000 |
| Trip Curve | B、C、D |
Application scope
HUH18-125 series isolation switch is a newly devloped product.This product is smallin size,easyto install and beautiful in appearance.It is mainly used forisolation in electrical lines with AC50Hz,rated voltage 230v/400V adn rated current up to 125A.It can also be used forinfrequent switch on and offthe circuit.
Conforming standards:IEC60947-3.
Main technical parameter
| Frame size | 125 |
| Ratedvoltage | 50Hz、230V/400V |
| Rated operational current(A) | 32、40、50、63、80、100、125 |
| Poles | 1P、2P、3P、4P |
| Ratedshort-timewithstandcurrent | 20le/1S |
| Rated short-time makingcapacity | 28.1le |
| Ratedimpulsewithstandvoltage(kv) | 6 |
| Lifespan(cycles) | Mechanical10,000 Electrical3,000 |
| Use catagory | AC-22A |
| Protectiondegree | IP20 |
HUM18PV-63
Series Miniature Circuit Breaker
Application scope
HUM18DC-63 plastic case circuit breaker (hereinafter referred to as circuit breaker) is mainly suitable for overcurrent protectionforpower facilities and electricalequipmentinthe DC line with rated voltage upto1ooov and rated current upto 63A.
CB、CE、TUVapproved
HLS1
Series Surge Protection Device
Main technical parameter
| Frame size | 63 |
| Ratedvoltage | (1P)DC250V、(2P)DC500V、(3P)DC750V、(4P)DC1000V |
| Ratedoperationalcurrent(A) | 1、2、3、4、5、6、10、16、20、25、32、40、50、63 |
| Rated short-timewithstandcurrent | 1000A |
| Ratedshort-time makingcapacity | 7500A |
| Poles | 1P、2P、3P、4P |
| Rated impulse withstandvoltage(kV) | 4、6 |
| Usecatagory | A |
| Lifespan | Mechanical20000Electrical8000 |
| Trip type | powerdistributionprotection |
Application scope
The HLS1 Series Surge Protection Device (SPD) is suitable for low-voltage power grids with AC 50/60 Hz and rated voltage of 400\ \forall, which can protect the system from theimpact of transient surge voltage caused by lightning strike or switching operation,limit instantaneous overvoltage and dischargesurge current.
Conforming standards: IEC 61643-11.
Main technical parameter
| SPD(surgeprotection device) | B、C |
| Maximumcontinuousoperatingvoltage | L-N:385V(C type);385V、440V(B type);M N-PE: 260V |
| Nominal dischargecurrent | 10kA( (Ctype)、2 20kA(C type)、25kA、40kA、60kA、80kA(B type) |
| Maximum discharge current | 20kA(C type)、4 40kA(C type)、50kA、80kA、100kA、150kA(B type) |
| Short-circuitcurrenttolerance | 300A |
HYZF1-63
Series Self-compound Overvoltage and Undervoltage Protector
Application scope
HYZF1-63 series self-compound overvoltage and undervoltage protector(hereinafterreferred to as protector) is applicable to single-phase line with AC230v,50Hz and rated working current upto 63A,protect overvoltage and undervoltagecaused bylinefaulttoavoid abnormalvoltageinput
Electricalequipment.Itismainlyusedinthe incoming lineof residentialhousehold boxand the distribution linethat needs toprotectelectricalequipment.
Main technical parameter
| RatedVoltage | 50Hz,230V |
| Frame sizerated current | 63A |
| Ratedoperationalcurrent | 20A、25A、32A、40A、50A、63A |
| Load power | 4.4kVA、5.5kVA、6.6kVA、8.8kVA、11kVA、13.2kVA |
| Overvoltageoperatingvoltage | 275 (1±5%)V |
| Overvoltagerecoveryvoltage | 250 (1±5%)V |
| Undervoltageoperatingvoltage | 175 (1±5%)V |
| Undervoltagerecoveryvoltage | 190 (1±5%)V |
| Delaypowertransmissionafterpowerfailure | S09> |
| Delayofpowertransmission duringfaultrecovery | 20s~60s |
| Operationtime | ≤1s |
| Selfpowerconsumption | ≤1W |
| Ratedimpulsewithstand voltage | 4kV |
| Ratedlimitingshortcircuitcurrent | 3000A |
JYC8
SeriesAC Household Contactor
Application scope
JYC8 series household AC contactoris mainly used for lines with AC 50Hz(or60Hz),rated operating voltage up to 400V,rated operating current up to 63A,to control household appliances and similar uses of low sensing micro load;It can also be used to control theloadof householdmotors,and thecontrolpower willbelowered accordingly.
The products are applied in the home, villa,apartment,hotel and other places to achieve automation function,applied in themassproductionof householdappliances.
Main technical parameter
| Framesize | 25,63 |
| Numberofpoles | 1P、2P、3P、4P |
| Ratedoperationalcurrent | 16A、20A、25A、32A、40A、63A |
| Coil working current | AC24V、48V、110v、230V,other specifications can be negotiated with the manufacturer |
| Ratedinsulationcurrent | 500V |
Application scope
It is suitable for power supply in power plants and industrial and mining enterprises with 50Hz,less than 5oov, three-phase three wire,three-phase four wireinfrequently operated power distribution systems orfor lighting power distribution.
Conforming standards:IEC61439-3
Main technical parameter
| Numberof ways | 4、6、8、10、12、15、18、20、24、30、36、40、45 |
| Ratedoperationalcurrent | 6A~80A |
| Ratedvoltage | AC380V |
| Rated insulation voltage | AC500V |
CJX1
Series AC Contactor
Application scope
Suitable for 50Hz or 60Hz AC,voltage to 660V, current to 475A power lines,for long-distance frequent start and control of motors, and closing and breaking circuit.The CJX1 series reversible contactor is composed of mechanical interlocking mechanism,whichcancontrolthe start, stop and reverseofthemotor.
Conforming standards:IEC60947-4-1
Features
Double break point direct moving structure,flexible action mechanism,manual inspection is convenient, compact structure;Contact system,magnetic system are closed structure,powderDustis noteasyto enterimprove the service life; Theterminaliscovered byprotectivecover,safeand reliableuse.
Main technical parameter
| Ratedoperationalcurrent | 9A、 12A、 16A、 22A、 32A、 45A、 63A、 75A、 85A、 110A、 140A 170A 205A、 250A 300A 400A 475A |
| Coilworkingvoltage | AC36V、 110V、 127V、 220V、380V, DC24V、 DC110V、 DC220V Only9-22Aspecifications are available |
| Ratedinsulationvoltage | Other specifications can be negotiated with the manufacturer; A069 |
EXC3
Series AC Contactor
Application scope
It is mainly used for circuit ofAC 50Hz/60Hz,rated voltage up to 690V,and rated operating current upto 95A under the AC-3 usage category.It is mainly used for frequent start and control of AC motor, closing and breaking the circuit remotely, and can be assembled as an electromagnetic starter with an appropriate thermal overload relay to protect the circuit from possibleoverload.
Conforming standards:IEC60947-4-1
Productcharacteristics
Small size,light weight, long life,low power consumption; Configurable and chaplain auxiliary contact group,air delay head,mechanical interlocking mechanism and other accessories,Composed of delay contactor,mechanical interlocking contactor,startriangle starter;And canbe directly connected with thethermal overloadrelaytoformelectromagneticstart device.
Main technical parameter
| Ratedcurrent | 6A、9A、 12A、 18A、 25A、 32A、 38A、 40A 50A、 65A、 80A 95A、 115、 150、 225、 265、3 330、 400、5 500、6 630、800 |
| Coilworkingvoltage | AC24V、 36V、 110V、 127V、 220V、3 380V,other specifications canbe negotiated with manufacturer |
| Ratedinsulationvoltage | 690V |
CJX2
Series AC Contactor
Application scope
Suitable for AC 50Hz or 60Hz, voltage up to 660V, current up to 95A circuit, for remote closing and breaking circuit and frequent start and control ofthe AC motor.The contactor can also be equipped with a blocktype auxiliary contact group,air delay head,mechanical interlocking mechanism and other accessories to form a delay connection contact,reversible contactor and startriangle starter.It can be directly inserted and installed with thermal relay to form an electromagnetic Sstarter.
Conforming standards:IEC60947-4-1
Features
Smallsize, light weight,long life,low power consumption;Auxiliary contact group of blocktype,air delay head,mechanical interlocking mechanism and other accessories can be configured into delay contactor,mechanical interlocking contactor and star triangle starter; And the electromagnetic starter can be directly inserted and installed with the thermal overload relay.
Main technical parameter
| Ratedcurrent | 9A、12A、18A、25A、32A、40A、50A、65A、80A、95A |
| Coilworkingvoltage | AC36V、110V、127V、220V、380V,other specifications can benegotiated with manufacturer |
| Ratedinsulationvoltage | 690V |
CJ19
Series Switching Capacitor Contactor
Application scope
Mainly suitable forAC 50Hz,rated operating voltage up to 400V,control capacitor capacityupto50kvar electricity system underAC-6B usage category,to switch three-phase single pole ormultipole capacitorbanks toimprove powerfactor.
Conforming standards:IEC60947-4-1
Features
The limited current resistor can restrain the closing inrush current within the allowable range.Direct action double breakpoint structure,flexible operation structure,manualinspectionis convenient,and the structureis compact.
Main technical parameter
| Conventionalthermalcurrent | 25A、 32A、 43A、 63A、 80A、 95A |
| Ratedoperationalcurrent | 17A、 26A、 29A、 44A、 54A、 72A |
| Coil workingvoltage | AC36V、 110V、1 127V、 220V、 380V,otherspecificationscanbe negotiated withmanufacturer |
| Ratedinsulationvoltage | 500V |
Industrial Control and Protections
HUC1
ACContactors
Application scope
HUC1 Series contactors are mainly used for controlling non-inductive or slightly inductive loads and generally for controlling power circuits up to 690 V AC.These contactors are of the block type design with 3 or 4 main poles.It can be widely used in wind power,photovoltaic and otherrenewable energy projects.
Conforming standards:IEC60947-4-1
Features
-Compactsize.
-Ratecurrent up to1200A.
-Reducedcoilconsumption.
-Add-on auxiliary contact blocks forside mounting and a widerange of accessories -Wide control voltage range (24V,120v,220v,277V,480V,690v).
-Easy,fast and secure starters assembly.
Main technical parameter
| Rated operational current | 6A、9 9A、 12A、 16A、 25A、 30A、 40A、5 50A、6 63A、 75A、 80A、 90A、 100A、 145A、 175A、 210A、 260A、 300A、 370A、 550A、 700A、 800A |
| Ratedvoltage | AC24V、 36V、 110V、 220V、 380V, other specifications can be negotiated with the manufacturer |
| Rated insulation voltage | 690V |
EXR3
Series Thermal Overload Relay
Application scope
EXR3 series thermal overload relay is mainly used in circuits with AC 50Hz,rated working voltage up to 660V and rated working current of 0.1\~630A, and to start and accelerate motorto the normal speed,as wellasforcircuit and three phase AC motor overload and phase breaking protections.lt can also form a starter with the adaptive AC contactoras.Similar model :LR2/JR28.This productcanreplaceJRS1perfectly.
Conforming standards:IEC60947-4-1
Features
With phasefaultand temperature compensation structure;
Combined installationcanprevent fingercontact;
The settingcurrentis continuouslyadjustable;
Automaticandmanualreset arbitraryselection,actionindicatingfunction;
Normally closed and normally open auxiliary contact insulation separate;
It has a test button and a stopbutton.
Main technical parameter
| Frame size | 25A、36A、93A、180A、400A、630A |
| Settingcurrent | 0.1~630A |
| Protectionfunction | motoroverloadandlackofphaseprotection |
| Installationmode | plug-intype |
| Tripping class | 10A |
| Resetmode | manualresetandautomaticreset |
| Compatiblewithcontactor | EXC3 |
JRS1
Series Thermal Overload Relay
Application scope
It issuitableforcircuitwithAC 50 Hz rated working voltage up to 660V and rated working current of 0.1-93A,and for AC motor overload and phase breaking protections.It canform a starter with the adaptiveAC contactoras,and inserted and installed withCJX2and H8CseriesACcontactors.
Conforming standards:IEC60947-4-1
Features
With phasefault and temperaturecompensation structure;
Combinedinstallationcanpreventfingercontact;
Thesettingcurrentiscontinuouslyadjustable;
Automaticand manual reset arbitrary selection,action indicatingfunction;
Normally closed and normally open auxiliary contactinsulation separate;
Ithas a test button and a stop button.
Main technical parameter
| Frame size | 25A、36A、93A |
| Settingcurrent | 0.1~93A |
| Protectionfunction | motoroverloadandlackofphaseprotection |
| Installationmode | plug-in type |
| Trip grade | 10A |
| Resetmode | manualresetandautomaticreset |
| Compatiblewithcontactor | CJX2 |
JRS2
Series Thermal Overload Relay
Application scope
Suitable forelectricity system with AC 50Hz,main circuit rated voltage up to 660V and rated current of0.1-630A.Itis used for three-phaseACasynchronousmotoroverload andphase-out protection.
Conforming standards:IEC60947-4-1
Features
With differentialphase breakprotectionand temperaturecompensation device;
Combined installation canpreventfingerelectric shock;
Thesettingcurrentiscontinuouslyadjustable;
Withautomaticormanualresetbutton;
Normally closed normally open auxiliary contact insulation separate;
There is a detectionbutton and a trip indication.
Main technical parameter
| Currentsettingrange | 12.5~630A |
| Setting current | 0.1~630A |
| Function | motoroverloadandlackofphaseprotection |
| Installationmode | combined andindependentinstallation |
| Tripping class | 10A |
| Compatiblewithcontactor | CJX1 |
F4
Series Auxiliary Contact Block
Application scope
F4 auxiliarycontactsetisasupporting accessoryforJZC4 andCJX2seriesproducts.The numberofauxiliarycontactscanbe increasedtoformstartrianglestarter.
Conforming standards:IEC60947-5-1
LA2、LA3
Series Time delay auxiliary contact block
Main technical parameter
| Model | F4-11、F4-20、F4-02、F4-40、F4-31、F4-22、F4-13、F4-04 |
| ConventionalthermalcurrentIth | 10A |
| RatedoperationalvoltageUe/Ratedoperationalcurrentle | AC-15:AC380V/0.95A,AC220V/1.63A; DC-13:DC220V/0.15A,DC110V/0.3A |
| Rated insulation voltage Ui | 660V |
| Numberofcontacts | 2、4 |
Application scope
The air delay head is an accessory of the AC contactor and contactor relay,which is connected to the AC contactor and contactorrelay on electrical appliances,to switch on and off instantaneouslyorwith delayin the control circuit.
Main technical parameter
| Model | LA2-D20、LA2-D22、LA2-D24 (LA2ispowerondelay) LA3-D20、LA3-D22、LA3-D24 (LA3ispoweroffdelay) |
| Conventionalthermalcurrent | 10A |
| Ratedvoltage/Ratedcurrent | AC-15:AC380V/0.95A,AC220V/1.63ADC-13:DC220V/0.15A,DC110V/0.3A |
| Ratedinsulationvoltage | 660V |
| No.ofContacts | 1NO+1NC |
| Delayrange | 0.1~3s、0.1~30s、10~180s |
BH
Series Current Transformer
Application
Tobe used incombination wihmeasurement instrument;ammeterswat-hourmeters,measurement units,contolrelays,ete.
Technical data
1.Secondary curentIlsm:5A
2.Max,voltage rating Ue:660V
3.Frequency:50/60Hz
4.Safety factor(f):10
5.Degree of protection:IP20
6.Operating temperature;-5°Cto+40°℃,humidity<80%
7.Standards:IEC/EN60044-1
8.lnstallation type: Mounting on plates or bars
HH52P
Series Multi purpose relay
| Model | Transformation ratio(lpn/Isn) | Rated output(VA) | Circlesofthe cable | |||
| Aocuracy class | ||||||
| BH-0.66 solid type | 5/5 10/5 | 5 5 5 5 | 0.5 2.3 2.5 2.3 | 0.55 | 0.2 | |
| 15/5 20/5 25/5 30/5 40/5 50/5 | 5 5 5 | 2.5 2.5 2.5 2.5 | ||||
| 5 | 2.5 | |||||
| BH-0.66 201 | 75/5 | 5 | 2.5 | |||
| 75/5 | 2.5 2.5 | 1 | ||||
| 100/5 | 1 | |||||
Application scope
HH52P series Multi-purpose electromagnetic relay is applicable to electronic control equipment,household appliances, office automation,test, security, commercial machinery, communication equipment, automobiles,machine tools, construction,transportation equipment,instruments and meters, and can be used as remote control intermediate conversion or amplification elements.Complete AC/DC specifications and variousinstallation methods;Avariety of sockets are available,and there arespecificationswith lights.
Main technical parameter
| contact | form | 2Z、3Z、4Z |
| Load (resistive) | 5A/250VAC 30VDC | |
| Contact resistance(initial) | 500mΩ | |
| Material | silver alloy | |
| Electrical life(cycles) | 1X105 | |
| Mechanical life(cycles) | 1X107 | |
| Insulation Resistance | ≥100mΩ (500VDC) | |
| AmbientTemperature | -25°℃~+55°℃ | |
| Ambient Humidity | 45%~75%RH | |
| AtmosphericPressure | 86kPa~106kPa | |
| Impact(stability) | celeration100m/s²,pulse duration11ms | |
| Vibration | Doubleamplitude1.0mm,10~55Hz | |
| Installation Method | din-rail socket type,bolt mounted type,PCB printingboard welding type | |
HH64P
Series Multi purpose relay
Application scope
HH64P series electromagnetic relay is applicable to electronic control equipment,household appliances,office automation,test,security,commercial machinery,communicationequipment,automobiles,machinetools,construction, transportation equipment, instruments and meters, and can be used as remote control intermediate conversion or amplification elements.Complete AC/DC specifications and variousinstallation methods;A variety of sockets are available, andtherearespecificationswithlights.
Main technical parameter
| contact | form | 1Z、2Z、3Z、4Z |
| Load(resistive) | 16A/240VAC30VDC10A/240VAC30VDC | |
| Contactresistance(initial) | 500mΩ | |
| Material | silver alloy | |
| ElectricalLife(cycles) | 1X105 | |
| Mechanical Life(cycles) | 1X107 | |
| Insulation Resistance | ≥100mΩ(500VDC) | |
| Ambient Temperature | -25°℃~+55°℃ | |
| Ambient Humidity | 45%~75%RH | |
| AtmosphericPressure | 86kPa~106kPa | |
| Impact (stability) | celeration100m/s²,pulse duration 11ms | |
| Vibration | Doubleamplitude1.0mm,10~55Hz | |
| Installation Method | din-rail socket type,boltmounted type,PCBprintingboard welding type | |
BSMJN
Series Self-healing Low-voltage Parallel Power Capacitor
Application scope
Itis mainlyusedtoimprove powerfactor,reducereactive powerloss and improve voltagequalityinlow-voltage powergrid. Conformingstandards:EN/IEC60831-1
Main technical parameter
| Ratedvoltage | 0.12~1.2kV |
| Rated capacity | 1~100kVar |
| Capacitytolerance | 5%~10% |
| Tangent value of loss angle | tg&≤0.1% |
| Withstandvoltage | 2.15 times5sbetween poles,nopermanent breakdown orflashover |
| Dischargedevice | Built-in discharge resistance, and the voltage of capacitor drops tobelow75Vwithin three minutesaftercuttingoffthepowersupply |
| Maximumallowableovervoltage | 110%ofratedvoltage |
| Maximumallowableovercurrent | 130%ofratedcurrent |
Instructions
Capacitors of one grade higherthan the actual voltage shall be selected toprolong the servicelife; Ifthe voltagechangerate ishigherthan 5%,the frontend ofthe capacitorincoming line must be treated; When used in systems with higher harmonics,reactance must be added to block higher harmonics; Capacitors shall bemaintained and operated underthe condition of notexceeding therated voltage and current
HYIC3
Series Harmonic Suppression Intelligent Power Capacitor Compensation Device
Application scope
HYIC3 seriesintelligent integrated powercapacitorcompensationdeviceisbased ontwo or more groups(deltatype)orone or more(Y type) of low-voltage power capacitors,integrating advanced technologies such as modernmeasurement and control, power electronics,network communication,and automated control. It the traditional system where separate components including controllers,fuses, composite switches or mechanical contactors,thermal relays,low-voltage capacitors,and indicatorlights arebywireswithin acabinet.
The low-voltage reactive power compensation device composed of it has the characteristics of flexible compensation methods,good compensation effects, small device, low power consumption, convenient installation and maintenance, long service life, strong protection functions,and high reliability.It also truly achieves zero-crossing switching,meets actual needs of users for equipment, and adapts to the higher requirements of modern power grids for reactive power compensationdevices.
Executive standard:GB/T 15576"Low-voltage integrated reactive powercompensation device".
HYIC3X
Series Harmonic Suppression Intelligent Power Capacitor Compensation Device
Application scope
HYIC3Xseries harmonicsuppression intelligent power capacitorcompensation device,intelligent zero crossing switching relay, intelligent protection unit, low-voltage self-healing type power capacitors and dry-type series reactors form an independentandcompleteintelligentcompensationunit.
Replace the automatic reactive power compensation device assembled by intelligent reactive power controller,fuse (or micro break),thyristor composite switch (or connector),thermal relay,indicator light,low-voltage power capacitor, dry seriesreactorandotherscatteredcomponents.
The product integrates advanced technologies such as electronic technology,sensor technology,network technology and electrical manufacturing,and integrates,networking and intelligentize traditional reactive powercompensation products. It changes the structure mode of the existing low-voltage reactive power automatic compensation equipment,greatly improves the reliability and service life of the equipment, and has the comprehensive advantages of simple structure, simpleproduction,lowcost,improvedperformance,and simple
The product is mainly used for reactive power compensation in very serious harmonic situations.It can operate reliably without resonance,has no amplification effect on harmonics, and has the function of absorbing and eliminating harmonics toacertainextent.Amongthem,theproductsconnectedwith 7% reactorsinseriesareused intheelectricalenvironment where the main harmonicis5times,and the products connectedwith 14% reactorsinseries areusedintheelectrical environmentwherethemainharmonicis3times.
HYIC3-K
Series Intelligent Reactive Power Compensation Controller
Application scope
Low voltage reactive powerintegrated measurement and control instrument(hereinafterreferred to as measurement and control instrument) is a newgeneration product developed and produced by the company on thebasis of absorbing lowvoltagereactive power automatic compensation technology athome and abroad to meet the development needs of lowvoltagereactivepowerautomaticcompensation.
The measurement and control instrument has RS-485 communication interface,which can be used together with the intelligent capacitor produced by our company.It has the functions of collecting and displaying electrical measurement data,monitoring and displayingthe operating condition and switching statusoftheintelligentcapacitor,and automatically controlling the switching container according toreactive power and target power factor.The connection is simple and the operation is reliable. This product can replace 3voltmeters,3 ammeters,3 power factor meters,1 low-voltage reactive compensation controller and all capacitor status indicators on the existing low-voltage reactive compensation cabinet, makingitextremely simpleandsavingalotof wiring.
Main technical parameter
Capacity control (1) Three phase compensation type: 48 sets (2) Split phase compensation type: 48 sets (3) Mixed compensation type: 48 sets
Operation powersupply
(1) Operation voltage:AC 50HZ, 380V±20%
(2) Power consumption: less than 2VA
(3) Current sampling:AC 0\~5A
measurement accuracy
(1) Voltage: ≤ 0.5%
(2) Current: ≤0.5%
(3) Reactive power: ≤ 1.0%
(4) Active power:≤ 1.0%
(5) Power factor: ± 0.01
JKWF
Series Reactive Power Automatic Compensation Controller
Application scope
JKWF seriesreactive power automatic compensation controllertakes high-speed high-performance microprocessor as the core device to sample 3-phase voltage and 3-phase current signals at the same time,and provides 6 sub compensation+co compensation schemes and 12 switching coding schemes. Users can choose at will by modifying control parameters. Once the control parameters are modified and permanently saved, power loss will not be lost.Fundamental wave power factor and fundamental wave reactive power are used to control the switching of capacitor bank.The switching is stable without switching oscillation, and is insensitive to voltage harmonic and current harmonic interference. It is applicable to the automaticcontrol ofreactive powercompensationof powersystems underAC45Hz-65Hz and 0.4KV.
In accordance with standard:JB/T 9663.
Main technical parameter
| Rated workingcurrent | AC0~5A |
| Rated working voltage | AC220V±20% |
| Staticoutputcontactcapacity | AC2207A |
| Dynamicoutput capacity | -12V 10mA |
| Display powerfactor | lag 0.001-lead 0.01 |
| Undervoltageprotectionvalue | 170V |
| Sensitivity | 50mA |
| Protectiongrade | enclosureIP40 |