PI550A/PI550A系列基本频率变频器用户手册
收藏
手机阅读
阅读文字版 文字版

PI550A/PI550A系列基本频率变频器用户手册

目录
  • 1.PI550A1 Series
  • 1.Basic Frequency Inverter
  • 1.2. Instructions on nameplate
  • 1.3. Dimension
  • 2.4. Keyboard description
    • 2.4.2 Description of operation panel keys
  • 2.5. Standard specifications
  • 3.6.Wiring Diagram
  • 4.7. The load is a single-phase motor,Only available
  • 4.Figure 3
    • 4.d0 group Monitoring function group
      • 4.AI2 input voltage value
    • 5.F0 group Basic function group
      • 6.GF type
      • 6.1.G type (Constant torque load type)
      • 6.2.F type (Fans/pumps load type)
    • 7.F2 group Output terminal parameter set
      • 8.Set value
    • 8.F3 group Start/stop control parameters group
    • 9.F4 group V/F control parameters group
      • 9.Multipoint V/F voltage point 3
      • 9.Slip compensation coefficient
      • 9.Overexcitation gain
      • 9.Oscillation suppression gain
      • 9.V/F separation voltage source
      • 9.V/F separation voltage rise time
      • 9.F5.00
      • 9.Speed loop ratio G1
      • 9.1~100
      • 9.☆
      • 9.F5.01
      • 9.Speed loopintegral T1
      • 9.0.01s~10.00s
      • 9.F5.02
      • 9.Switching frequency 1
      • 9.0.00~F5.05
      • 9.F5.03
      • 9.Speed loop ratio G2
      • 9.0~100
      • 9.F5.04
      • 9.Speed loop integral T2
      • 9.0.01s~10.00s
      • 9.F5.05
      • 9.switching frequency 2
      • 9.F5.02~F0.19(Max. frequency)
      • 9.F5.06
      • 9.Speed loop integral
      • 9.0:Valid 1:Invalid
      • 9.F5.07
      • 9.Torque limit upper limit source
      • 9.0: Function code F5.08 setting;
      • 9.1: Analog AI1 setting;
      • 9.2: Analog AI2 setting;
      • 9.3: Panel potentiometer setting;
      • 9.4: High speed pulse setting;
      • 9.5:Communication settings;
      • 9.6: Min. (AI1, AI2 set)
      • 9.7: Max. (AI1, AI2 set)
      • 9.F5.08
      • 9.Upper limit digital setting for torque
      • 9.0.0%~200.0%
      • 9.F5.09
      • 9.Vector control differential gain
      • 9.50%~200%
      • 10.F5.10
      • 10.Speed loop filter time constant
      • 10.0.000s~0.100s
      • 10.F5.11
      • 10.Vector control overexcitation gain
      • 10.0~200
      • 10.F5.12
      • 10.Excitation regulator proportional gain
      • 10.0~60000
      • 10.F5.13
      • 10.Excitation regulator integral gain
      • 10.0~60000
      • 10.F5.14
      • 10.Torque regulator proportional gain
      • 10.0~60000
      • 10.F5.15
      • 10.Torque regulator integral gain
      • 10.0~60000
      • 10.F5.18
      • 10.Maximum output voltage coefficient
      • 10.100~110%
      • 10.F5.19
      • 10.Maximum torque coefficient in field weakening area
      • 10.Maximum moment of weak magnetic field at main infl
      • 10.F5.21
      • 10.Speed control (braking) torque upper limit source
      • 10.0~8
      • 10.F5.22
      • 10.Speed control (braking) torque upper limit digital
      • 10.0~200.0%
    • 10.F6 group Keyboard and display parameter group
      • 10.F6.00
      • 10.STOP/RESET key functions
      • 10.0: STOP/RES key is enabled only under keyboard ope
      • 10.1:STOP/RES key is enabled under any operation mode
      • 10.F6.01
      • 10.Running status display parameters 1
      • 10.0x0000~0xFFFF
      • 10.F6.02
      • 10.Running status display parameters 2
      • 10.0x0000~0xFFFF
      • 10.F6.03
      • 10.Stop status display parameters
      • 10.0x0001~0xFFFF
      • 10.F6.04
      • 10.Load speed display coefficient
      • 10.0.0001~6.5000
      • 10.F6.05
      • 10.Decimal places for load speed display
      • 10.0:0 decimal places 2:2 decimal places
      • 10.1:1 decimal places 3:3 decimal places
      • 10.F6.06
      • 10.Inverter module radiator temperature
      • 10.0.0℃~100.0℃
      • 10.F6.07
      • 10.Total run time
      • 10.0h~65535h
      • 10.F6.08
      • 10.Total power-on time
      • 10.0h~65535h
      • 10.F6.09
      • 10.Total power consumption
      • 10.0~65535kWh
      • 10.F6.10
      • 10.Product series number
      • 10.Frequency inverter series number
      • 10.F6.11
      • 10.Software version number
      • 10.Control board software version
      • 10.F6.17
      • 10.Power correction coefficient
      • 10.0.00~10.00
      • 10.F6.20
      • 10.Keypad lock selection
      • 10.0:RUN, STOP button valid
      • 10.2: RUN, STOP, UP, DOWN button valid
      • 10.3: STOP button valid
      • 10.Note: Keyboard potentiometers are not limited by t
      • 10.F6.21
      • 10.QUICK key function selection
      • 10.0: No function; 1: Jog running
      • 10.2: Shift switch display state;
      • 10.3: FWD/RVS switchover
      • 10.4: Clear-up UP/DOWN setting
      • 10.5: Free stop;
      • 10. 6: running command given in sequence
    • 10.F7 group Auxiliary functional parameters group
      • 10.F7.00
      • 10.Jog running frequency
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.01
      • 10.Jog acceleration time
      • 10.0.0s~6500.0s
      • 10.F7.02
      • 10.Jog deceleration time
      • 10.0.0s~6500.0s
      • 10.F7.03
      • 10.Jog priority
      • 10.0:Invalid;1:Valid
      • 10.F7.04
      • 10.Jump frequency 1
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.05
      • 10.Jump frequency 2
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.06
      • 10.Jump frequency range
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.07
      • 10.Jump frequency availability during ac/deceleration
      • 10.0:Invalid;
      • 10.1:Valid
      • 10.F7.08
      • 10.Acceleration time 2
      • 10.0.0s~6500.0s
      • 10.F7.09
      • 10.Deceleration time 2
      • 10.0.0s~6500.0s
      • 10.F7.10
      • 10.Acceleration time 3
      • 10.0.0s~6500.0s
      • 10.F7.11
      • 10.Deceleration time 3
      • 10.0.0s~6500.0s
      • 10.F7.12
      • 10.Acceleration time 4
      • 10.0.0s~6500.0s
      • 10.F7.13
      • 10.Deceleration time 4
      • 10.0.0s~6500.0s
      • 10.F7.14
      • 10.Switching frequency point between acceleration tim
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.15
      • 10.Switching frequency point between deceleration tim
      • 10.0.00Hz~F0.19(Maximum frequency)
      • 10.F7.16
      • 10.Forward/reverse rotation deadband
      • 10.0.00s~3600.0s
      • 11.F7.17
      • 11.Reverse rotation control
      • 11.0:Allow ; 1:Prohibit
      • 11.F7.18
      • 11.Set frequency lower than lower limit frequency mod
      • 11.0:Running at lower limit frequency;
      • 11.1:Stop;
      • 11.2:Zero speed running
      • 11.F7.19
      • 11.Droop control
      • 11.0.00Hz~10.00Hz
      • 11.F7.20
      • 11.Setting cumulative power-on arrival time
      • 11.0h~36000h
      • 11.F7.21
      • 11.Setting cumulative running arrival time
      • 11.0h~36000h
      • 11.F7.22
      • 11.Start protection
      • 11.0:OFF; 1:ON
      • 11.F7.23
      • 11.Frequency detection value (FDT1)
      • 11.0.00Hz~F0.19(Maximum frequency)
      • 11.F7.24
      • 11.Frequency detection hysteresis value (FDT1)
      • 11.0.0%~100.0%(FDT1 level)
      • 11.F7.25
      • 11.Frequency reaches detection width
      • 11.0.00~100%(Maximum frequency)
      • 11.F7.26
      • 11.Frequency detection value (FDT2)
      • 11.0.00Hz~F0.19(Maximum frequency)
      • 11.F7.27
      • 11.Frequency detection hysteresis value (FDT2)
      • 11.0.0%~100.0%(FDT2 level)
      • 11.F7.28
      • 11.Random arrivals frequency detection value 1
      • 11.0.00Hz~F0.19(Maximum frequency)
      • 11.F7.29
      • 11.Random arrivals frequency detection width 1
      • 11.0.0%~100.0%(maximum frequency)
      • 11.F7.30
      • 11.Random arrivals frequency detection value 2
      • 11.0.00Hz~F0.19(Maximum frequency)
      • 11.F7.31
      • 11.Random arrivals frequency detection width 2
      • 11.0.0%~100.0%(Maximum frequency)
      • 11.F7.32
      • 11.Zero current detection level
      • 11.0.0%~300.0%(Rated motor current)
      • 11.F7.33
      • 11.Zero current detection delay time
      • 11.0.01s~360.00s
      • 11.F7.34
      • 11.Overrun value of output current
      • 11.0.0%(not detected);0.1%~300.0% (Rated motor curren
      • 11.F7.35
      • 11.Output Current overrun detection delay time
      • 11.0.00s~360.00s
      • 11.F7.36
      • 11.Random arrivals current 1
      • 11.0.0%~300.0%(Rated motor current)
      • 11.F7.37
      • 11.Random arrivals current 1 width
      • 11.0.0%~300.0%(Rated motor current)
      • 11.F7.38
      • 11.Random arrivals current 2
      • 11.0.0%~300.0%(Rated motor current)
      • 11.F7.39
      • 11.Random arrivals current 2 width
      • 11.0.0%~300.0%(Rated motor current)
      • 11.F7.40
      • 11.Module temperature arrival
      • 11.0℃~100℃
      • 11.F7.41
      • 11.Cooling fan control
      • 11.0:Fan running only when running
      • 11.1:Fan always running
      • 11.F7.42
      • 11.Timing function selection
      • 11.0:Invalid 1:Valid
      • 11.F7.43
      • 11.Timing run time selection
      • 11.0:F7.44setting; 1: Analog AI1; 2: Analog AI2;
      • 11.3: Panel potentiometer
      • 11.Note:Analog input range 100% corresponds~F7.44
      • 11.F7.44
      • 11.Timing run time
      • 11.0.0Min~6500.0Min
      • 11.F7.45
      • 11.Current running arrival time.
      • 11.0.0Min~6500.0Min
      • 11.F7.46
      • 11.Awakens frequency
      • 11.Dormancy frequency (F7.48) ~ maximum frequency(F0.
      • 11.F7.47
      • 11.Awakens delay time
      • 11.0.0s~6500.0s
      • 11.F7.48
      • 11.Dormancy frequency
      • 11.0.00Hz~awakens frequency(F7.46)
      • 11.F7.49
      • 11.Dormancy delay time
      • 11.0.0s~6500.0s
      • 11.F7.50
      • 11.AI1 input voltage protection lower limit
      • 11.0.00V~F7.51
      • 11.F7.51
      • 11.AI1 input voltage protection upper limit
      • 11.F7.50~10.00V
    • 11.F8 group Fault and protection parameter group
      • 11.F8.00
      • 11.Overcurrent stall gain
      • 11.0~100
      • 11.F8.01
      • 11.Overcurrent stall protection current
      • 11.100%~200%
      • 11.F8.02
      • 11.Motor overload protection
      • 11.0:Prohibit; 1:Allow
      • 11.F8.03
      • 11.Motor overload protection gain
      • 11.0.20~10.00
      • 11.F8.04
      • 11.Motor overload pre-alarm coefficient
      • 11.50%~100%
      • 11.F8.05
      • 11.Overvoltage stall gain
      • 11.0~100
      • 11.F8.06
      • 11.Overvoltage stall protection voltage / energy cons
      • 11.120%~150%
      • 11.F8.08
      • 11.Output phase loss protection selection
      • 11.0:Prohibit; 1:Allow
      • 11.F8.09
      • 11.Power-on short circuit to ground
      • 11.0:Invalid; 1:Valid
      • 11.F8.10
      • 11.Number of automatic fault reset
      • 11.0~32767
      • 11.F8.11
      • 11.Fault DO action selection during automatic fault r
      • 11.0:OFF;1:ON
      • 12.F8.12
      • 12.Automatic fault reset interval
      • 12.0.1s~100.0s
      • 12.F8.24
      • 12.Fault running frequency
      • 12.0: Current frequency running
      • 12.1: Setting frequency running
      • 12.2: Upper frequency running
      • 12.3: Down frequency running
      • 12.4: Abnormal reserve frequency running
      • 12.F8.25
      • 12.Abnormal reserve frequency
      • 12.60.0%~100.0%
      • 12.F8.26
      • 12.Momentary power cut action selection
      • 12.0:Invalid; 1:Deceleration;
      • 12.2:Deceleration and stop
      • 12.F8.27
      • 12.Instantaneous stop, pause judgment voltage
      • 12.80%~100%
      • 12.F8.28
      • 12.Recovery voltage judgment time of momentary power
      • 12.0.00s~100.00s
      • 12.F8.29
      • 12.Judgment voltage of momentary power cut
      • 12.50.0%~100.0%(Standard bus voltage)
      • 12.F8.30
      • 12.Load drop protection selection
      • 12.0:Invalid 1:Valid
      • 12.F8.31
      • 12.load drop detection level
      • 12.0.0%~100.0%(Motor rated current)
      • 12.F8.32
      • 12.Load drop detection time
      • 12.0.0s~60.0s
      • 12.F8.33
      • 12.Motor temperature sensor type
      • 12.0:Invalid ;
      • 12.1:PT100 detect
      • 12.F8.34
      • 12.Motor over heat protection value
      • 12.0~200
      • 12.F8.35
      • 12.Motor over heat alarm value
      • 12.0~200
      • 12.F8.36
      • 12.Start short circuit protection
      • 12.0:Enable; 1:Disable
      • 12.F8.37
      • 12.Holzer detection
      • 12.0:Two-way Hall;1:Three-way Hall
      • 12.F8.38
      • 12.Three way hall operation short circuit to ground t
      • 12.0~100%(Relative motor current)
      • 12.F8.39
      • 12.Energy consumption braking voltage
      • 12.200.0~2000.0V
    • 12.F9 group Communication parameter set
      • 12.F9.00
      • 12.Baud rate
      • 12.Units digit:Modbus
      • 12.0~1:Reserved; 2:1200bps; 3:2400bps; 4:4800b
      • 12.Tens digit:Reserved
      • 12.Hundreds digit: Reserved
      • 12.Thousands digit:Reserved
      • 12.F9.01
      • 12.Data format
      • 12.0:No parity(8-N-2); 1:Even parity(8-E-1)
      • 12.2:Odd parity(8-O-1) 3:No parity(8-N-1)
      • 12.F9.02
      • 12.This unit address
      • 12.1~250,0 for broadcast address
      • 12.F9.03
      • 12.Response delay
      • 12.0ms~20ms
      • 12.F9.04
      • 12.Communication timeout time
      • 12.0.0(Invalid); 0.1~60.0s
      • 12.F9.05
      • 12.Data transfer format selection
      • 12.Units digit:Modbus
      • 12.0:Non-standard MODBUS protocol;
      • 12.1:Standard MODBUS protocol
      • 12.Tens digit:Profibus-DP
      • 12.0:PPO1 format; 1:PPO2 format;
      • 12.2:PPO3 format; 3:PPO5 format
      • 12.F9.06
      • 12.Communication read current resolution
      • 12.0:0.01A ;1:0.1A
      • 12.F9.07
      • 12.Communication card type
      • 12.0:Modbus communication card
      • 12.F9.08
      • 12.Undefined
    • 12.Fb group Control optimization parameter group
      • 12.Fb.00
      • 12.Fast current limiting manner
      • 12.0:Disable; 1: Enable
      • 12.Fb.01
      • 12.Undervoltage point setting
      • 12.50.0%~140.0%
      • 12.Fb.02
      • 12.Overvoltage point setting
      • 12.200.0~2500.0V
      • 12.Fb.03
      • 12.Deadband compensation mode selection
      • 12.0:No compensation; 1:Compensation mode 1;
      • 12.Fb.04
      • 12.Current detection compensation
      • 12.0~100
      • 12.Fb.05
      • 12.Vector optimization without PG mode selection
      • 12.0:No optimization; 1:Optimization mode 1;
      • 12.Fb.06
      • 12.Upper limiting frequency for DPWM switching
      • 12.0.00~15.00Hz
      • 12.Fb.07
      • 12.PWM modulation method
      • 12.0:Asynchronous; 1:Synchronous
      • 12.Fb.08
      • 12.PWM modulation manner
      • 12.0:Invalid
      • 12.1~10:PWM carrier frequency random depth
    • 12.E0 group Pendulum frequency, fixed length and cou
      • 12.E0.00
      • 12.Swing setting mode
      • 12.0:Relative to center frequency;
      • 12.1:Relative to maximum requency
      • 12.E0.01
      • 12.Wobbulate range
      • 12.0.0%~100.0%
      • 12.E0.02
      • 12.Sudden jump frequency range
      • 12.0.0%~50.0%
      • 12.E0.03
      • 12.Wobbulate circle
      • 12.0.1s~3000.0s
      • 12.E0.04
      • 12.Triangle wave rise time coefficient
      • 12.0.1%~100.0%
      • 12.E0.05
      • 12.Set length
      • 12.0m~65535m
      • 12.E0.06
      • 12.Actual length
      • 12.0m~65535m
      • 13.E0.07
      • 13.Pulse per meter
      • 13.0.1~6553.5
      • 13.E0.08
      • 13.Set count value
      • 13.1~65535
      • 13.E0.09
      • 13.Specified count value
      • 13.1~65535
      • 13.E0.10
      • 13.Reduction frequency pulse number
      • 13.0:Invalid; 1~65535
      • 13.
      • 13.E0.11
      • 13.Reduction frequency
      • 13.0.00Hz~F0.19(Max frequency)
      • 13.5.00Hz
    • 13.E1 group Multi-section instruction and simple PLC
      • 13.E1.00~E1.15
      • 13.0-stage speed setting 0X ~
      • 13.15-stage speed setting 15X
      • 13.-100.0%~100.0%
      • 13.E1.16
      • 13.Simple PLC running mode
      • 13.0: Stop after single running
      • 13.1: Hold final value after single running 2:
      • 13.E1.17
      • 13.Simple PLC power-down memory selection
      • 13.Units digit: power-down memory selection
      • 13.0: Power-down without memory
      • 13.1: Power-down with memory
      • 13.Tens digit: Stop memory selection
      • 13.0: Stop without memory;
      • 13.1: Stop with memory
      • 13.E1.18
      • 13.0 stage running time T0
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.19
      • 13.0 stage ac/deceleration time selection
      • 13.0:F0.13, F0.14; 1:F7.08, F7.09;
      • 13.2:F7.10, F7.11; 3:F7.12, F7.13
      • 13.☆
      • 13.E1.20
      • 13.1 stage running time T1
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.21
      • 13.1 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.22
      • 13.2 stage running time T2
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.23
      • 13.2 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.24
      • 13.3 stage running time T3
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.25
      • 13.3 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.26
      • 13.4 stage running time T4
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.27
      • 13.4 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.28
      • 13.5 stage running time T5
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.29
      • 13.5 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.30
      • 13.6 stage running time T6
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.31
      • 13.6 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.☆
      • 13.E1.32
      • 13.7 stage running time T7
      • 13.0.0s(h)~6500.0s(h)
      • 13.☆
      • 13.E1.33
      • 13.7 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.34
      • 13.8 stage running time T8
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.35
      • 13.8 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.36
      • 13.9 stage running time T9
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.37
      • 13.9 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.38
      • 13.10 stage running time T10
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.39
      • 13.10 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.40
      • 13.11 stage running time T11
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.41
      • 13.11 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.42
      • 13.12 stage running time T12
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.43
      • 13.12 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.44
      • 13.13 stage running time T13
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.45
      • 13.13 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.46
      • 13.14 stage running time T14
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.47
      • 13.14 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.48
      • 13.15 stage running time T15
      • 13.0.0s(h)~6500.0s(h)
      • 13.E1.49
      • 13.15 stage ac/deceleration time selection
      • 13.Same as E1.19
      • 13.E1.50
      • 13.Simple PLC run-time unit
      • 13.0: S (seconds) 1: H (hours)
      • 13.E1.51
      • 13.Multi-stage command 0 reference manner
      • 13.0: Function code E1.00 reference
      • 13.1: Analog AI1 reference
      • 13.2: Analog AI2 reference
      • 13.3: Panel potentiometer setting
      • 13.4: High-speed pulse setting
      • 13.5: PID control setting
      • 13.6:Keyboard set frequency (F0.01) setting, UP/DOWN
    • 13.E2 group PID functional parameter group
      • 13.E2.00
      • 13.PID setting source
      • 13.0: E2.01 setting
      • 13.1: Analog AI1 reference
      • 13.2: Analog AI2 reference
      • 13.3: Panel potentiometer setting
      • 13.4: High-speed pulse setting
      • 13.5: Communications reference
      • 13.6: Multi-stage command reference
      • 13.
      • 13.☆
      • 13.E2.01
      • 13.PID keyboard reference
      • 13.0.0%~100.0%
      • 13.50.0%
      • 13.☆
      • 13.E2.02
      • 13.PID feedback source
      • 13.0.Analog AI1 reference
      • 13.1.Analog AI2 reference
      • 13.2. Panel potentiometer setting
      • 13.4: High-speed pulse setting
      • 13.5: Communications reference
      • 14.6: AI1+AI2 reference
      • 14.7: MAX(|AI1|, |AI2|) reference
      • 14.8: MIN (|AI1|, |AI2|) reference
      • 13.
      • 13.☆
      • 14.E2.03
      • 14.PID action direction
      • 14.0: Positive 1: Negative
      • 14.
      • 14.☆
      • 14.E2.04
      • 14.PID setting feedback range
      • 14.0~65535
      • 14.1000
      • 14.☆
      • 14.E2.05
      • 14.PID inversion cut off frequency
      • 14.0.00~F0.19(Maximum frequency)
      • 14.0.00Hz
      • 14.☆
      • 14.E2.06
      • 14.PID deviation limit
      • 14.0.0%~100.0%
      • 14.2.0%
      • 14.☆
      • 14.E2.07
      • 14.PID differential limiting
      • 14.0.00%~100.00%
      • 14.0.10%
      • 14.☆
      • 14.E2.08
      • 14.PID reference change time
      • 14.0.00s~650.00s
      • 14.0.00s
      • 14.☆
      • 14.E2.09
      • 14.PID feedback filter time
      • 14.0.00s~60.00s
      • 14.0.00s
      • 14.☆
      • 14.E2.10
      • 14.PID output filter time
      • 14.0.00s~60.00s
      • 14.0.00s
      • 14.☆
      • 14.E2.11
      • 14.PID feedback loss detection value
      • 14.0.0%: not judged feedback loss
      • 14.0.1%~100.0%
      • 14.0.0%
      • 14.☆
      • 14.E2.12
      • 14.PID feedback loss detection time
      • 14.0.0s~20.0s
      • 14.0.0s
      • 14.☆
      • 14.E2.13
      • 14.Proportional gain KP1
      • 14.0.0~200.0
      • 14.80.0
      • 14.☆
      • 14.E2.14
      • 14.Integration time Ti1
      • 14.0.01s~10.00s
      • 14.0.50s
      • 14.☆
      • 14.E2.15
      • 14.Differential time Td1
      • 14.0.00s~10.000s
      • 14.0.000s
      • 14.☆
      • 14.E2.16
      • 14.Proportional gain KP2
      • 14.0.0~200.0
      • 14.20.0
      • 14.☆
      • 14.E2.17
      • 14.Integration time Ti2
      • 14.0.01s~10.00s
      • 14.2.00s
      • 14.☆
      • 14.E2.18
      • 14.Differential time Td2
      • 14.0.00~10.000
      • 14.0.000s
      • 14.☆
      • 14.E2.19
      • 14.PID parameter switching conditions
      • 14.0:No switching;
      • 14.1:Switching via terminals
      • 14.2: Automatically switching according to deviation.
      • 14.
      • 14.☆
      • 14.E2.20
      • 14.PID parameter switching deviation 1
      • 14.0.0%~E2.21
      • 14.20.0%
      • 14.☆
      • 14.E2.21
      • 14.PID parameter switching deviation 2
      • 14.E2.20~100.0%
      • 14.80.0%
      • 14.☆
      • 14.E2.22
      • 14.PID integral properties
      • 14.Units digit: Integral separation
      • 14.0: Invalid; 1: Valid
      • 14.Tens digit: Whether stop integration when output r
      • 14.0: Continue; 1:Stop
      • 14.00
      • 14.☆
      • 14.E2.23
      • 14.PID initial value
      • 14.0.0%~100.0%
      • 14.0.0%
      • 14.☆
      • 14.E2.24
      • 14.PID initial value hold time
      • 14.0.00s~360.00s
      • 14.0.00s
      • 14.☆
      • 14.E2.25
      • 14.Maximum deviation of twice outputs(Forward)
      • 14.0.00%~100.00%
      • 14.1.00%
      • 14.☆
      • 14.E2.26
      • 14.Maximum deviation of twice outputs(Backward)
      • 14.0.00%~100.00%
      • 14.1.00%
      • 14.☆
      • 14.E2.27
      • 14.Computing status after PID stop
      • 14.0: Stop without computing;
      • 14.1: Stop with computing
      • 14.1
      • 14.☆
      • 14.E2.29
      • 14.PID automatic decrease frequency selection
      • 14.0:Invalid; 1:Valid
      • 14.1
      • 14.☆
      • 14.E2.30
      • 14.PID stop frequency
      • 14.0.00Hz~maximum frequency(F0.19)
      • 14.25
      • 14.☆
      • 14.E2.31
      • 14.PID checking time
      • 14.0s~3600s
      • 14.10
      • 14.☆
      • 14.E2.32
      • 14.PID checking times
      • 14.10~500
      • 14.20
      • 14.☆
      • 14.E2.33
      • 14.Constant pressure water supply mode selection
      • 14.0: Standard machine mode
      • 14.1: Constant pressure water supply mode
      • 14.
      • 14.☆
      • 14.E2.34
      • 14.Pressure setting
      • 14.0Mpa~655.35Mpa
      • 14.0.45Mpa
      • 14.☆
      • 14.E2.35
      • 14.Pressure gauge range
      • 14.0Mpa~655.35Mpa
      • 14.1.60Mpa
      • 14.☆
      • 14.E2.36
      • 14.Pressure feedback channel selection
      • 14.0:AI1 1:AI2
      • 14.
      • 14.☆
      • 14.E2.37
      • 14.Low pressure alarm pressure setting
      • 14.0Mpa~655.35Mpa
      • 14.0.05Mpa
      • 14.☆
      • 14.E2.38
      • 14.Low-voltage alarm delay
      • 14.0s~6553.5s
      • 14.500.0s
      • 14.☆
      • 14.E2.39
      • 14.Ultra-high pressure alarm pressure setting
      • 14.0Mpa~655.35Mpa
      • 14.0.65Mpa
      • 14.☆
      • 14.E2.40
      • 14.Ultra-high pressure alarm delay
      • 14.0s~6553.5s
      • 14.500.0s
      • 14.☆
      • 14.E2.41
      • 14.Pressure sleep mode
      • 14.0: Invalid 1: Valid
      • 14.
      • 14.☆
      • 14.E2.42
      • 14.Sleep pressure
      • 14.0Mpa~655.35Mpa
      • 14.0.55Mpa
      • 14.☆
      • 14.E2.43
      • 14.Sleep delay
      • 14.0s~6500.0s
      • 14.600.0s
      • 14.☆
      • 14.E2.44
      • 14.Wake up pressure
      • 14.0Mpa~655.35Mpa
      • 14.0.40Mpa
      • 14.☆
      • 14.E2.45
      • 14.Wakeup delay
      • 14.0s~6500.0s
      • 14.10.0
      • 14.☆
      • 14.E8.29
      • 14.Motor type selection:
      • 14.0: Ordinary three-phase asynchronous motor,
      • 14.1: Single-phase motor forward rotation (capacitor
      • 14.2: Single-phase motor reverse rotation (capacitor
      • 14.3: Single-phase motor (Without removing capacitor)
      • 14.Notice:Only available for PI550A1 G1S.
      • 14.
      • 14.★
      • 14.b0.00
      • 14.Motor type selection
      • 14.0: General asynchronous motor
      • 14.1: Asynchronous inverter motor
      • 14.b0.01
      • 14.Rated power
      • 14.0.1kW~1000.0kW
      • 14.b0.02
      • 14.Rated voltage
      • 14.1V~2000V
      • 14.b0.03
      • 14.Rated current
      • 14.0.01A~655.35A (Inverter power ≦ 55kW)
      • 14.0.1A~6553.5A (Inverter rate> 55kW)
      • 15.b0.04
      • 15.Rated frequency
      • 15.0.01Hz~F0.19 (Maximum frequency)
      • 15.b0.05
      • 15.Rated speed
      • 15.1rpm~36000rpm
      • 15.b0.06
      • 15.Asynchronous motor stator resistance
      • 15.0.001Ω~65.535Ω (Inverter power <= 55kW)
      • 15.0.0001Ω~6.5535Ω (Inverter power> 55kW)
      • 15.b0.07
      • 15.Asynchronous motor rotor resistance
      • 15.0.001Ω~65.535Ω (Inverter power <= 55kW)
      • 15.0.0001Ω~6.5535Ω (Inverter power> 55kW)
      • 15.b0.08
      • 15.Asynchronous motor leakage inductance
      • 15.0.01mH~655.35mH (Inverter power <= 55kW)
      • 15.0.001mH~65.535mH (Inverter power> 55kW)
      • 15.b0.09
      • 15.Asynchronous motor mutUal inductance
      • 15.0.1mH~6553.5mH (Inverter power <= 55kW)
      • 15.0.01mH~655.35mH (Inverter power> 55kW)
      • 15.b0.10
      • 15.Asynchronous motor no-load current
      • 15.0.01A~b0.03 (Inverter power <= 55kW)
      • 15.0.1A~b0.03 (Inverter power> 55kW)
      • 15.b0.27
      • 15.Motor parameter auto tunning
      • 15.0: No operation
      • 15.1: Asynchronous motor parameters still auto tunnin
      • 15.2: Asynchronous motor parameters comprehensive aut
    • 15.y0 group Function code management
      • 15.y0.00
      • 15.Parameter initialization
      • 15.0:Nno operation 1: Restore default parameter valu
      • 15.3: Restore default parameter values, including mot
      • 15.501: Restore from backup user parameters
      • 15.y0.01
      • 15.User password
      • 15.0~65535
      • 15.y0.02
      • 15.Function parameter group display selection
      • 15.Units digit: d group display selection
      • 15.0: Not displays 1: Displays
      • 15.Tens digit: E group display selection(The same abo
      • 15.Hundreds digit:b group display selection(The same
      • 15.Thousands digit:y group display selection(The same
      • 15.Tens thousands digit:L group display selection(The
      • 15.y0.03
      • 15.Personality parameter group display selection
      • 15.Units digit:User’s customization parameter display
      • 15.0:Not display 1:Display
      • 15.Tens digit :User’s change parameter display select
      • 15.0:Not display 1:Display
      • 15.y0.04
      • 15.Function code modification properties
      • 15.0: Modifiable
      • 15.1: Not modifiable
      • 15.y0.05
      • 15.Undefined
    • 15.y1 group Fault query parameter group
      • 15.y1.00
      • 15.Type of the first fault
      • 15.0: No fault
      • 15.1: Inverter unit protection
      • 15.2: Acceleration overcurrent
      • 15.3: Deceleration overcurrent
      • 15.4: Constant speed overcurrent
      • 15.5: Acceleration overvoltage
      • 15.6: Deceleration overvoltage
      • 15.7: Constant speed overvoltage
      • 15.8: Control power failure
      • 15.9: Undervoltage
      • 15.10: Inverter overload
      • 15.11: Motor overload
      • 15.13: Output phase loss
      • 15.14: Module overheating
      • 15.15: External fault
      • 15.16: Communication abnormal
      • 15.17: Contactor abnormal
      • 15.18: Current detection abnormal
      • 15.19: Motor self-learning abnormal
      • 15.21: Parameter read and write abnormal
      • 15.22: Inverter hardware abnormal
      • 15.23: Motor short to ground
      • 15.26: Running time arrival
      • 15.27: Custom fault 1
      • 15.28: Custom fault 2
      • 15.29; Power-on time arrival
      • 15.31: PID feedback loss when running
      • 15.40: Fast current limiting timeout
      • 15.51:Initial position error
      • 15.COF: communication failure
      • 15.y1.01
      • 15.Type of the second fault
      • 15.y1.02
      • 15.Type of the third(at last) fault
      • 15.y1.03
      • 15.Frequency of the third(at last) fault
      • 15.-
      • 15.y1.04
      • 15.Current of the third(at last) fault
      • 15.-
      • 15.y1.05
      • 15.Bus voltage of the third(at last) fault
      • 15.-
      • 15.y1.06
      • 15.Input terminal status of the third(at last) fault
      • 15.-
      • 15.y1.07
      • 15.Output terminal status of the third(at last) fault
      • 15.-
      • 15.y1.09
      • 15.Power-on time of the third(at last) fault
      • 15.-
      • 15.y1.10
      • 15.Running time of the third(at last) fault
      • 15.-
      • 15.y1.13
      • 15.Frequency of the second fault
      • 15.-
      • 15.y1.14
      • 15.Current of the second fault
      • 15.-
      • 15.y1.15
      • 15.Bus voltage of the second fault
      • 15.-
      • 15.y1.16
      • 15.Input terminal status of the second fault
      • 15.-
      • 15.y1.17
      • 15.Output terminal status of the second fault
      • 15.-
      • 15.y1.19
      • 15.Power-on time of the second fault
      • 15.-
      • 15.y1.20
      • 15.Running time of the second fault
      • 15.-
      • 16.y1.23
      • 16.Frequency of the first fault
      • 16.-
      • 16.y1.24
      • 16.Current of the first fault
      • 16.-
      • 16.y1.25
      • 16.Bus voltage of the first fault
      • 16.-
      • 16.y1.26
      • 16.Input terminal status of the first fault
      • 16.-
      • 16.y1.27
      • 16.Output terminal status of the first fault
      • 16.-
      • 16.y1.29
      • 16.Power-on time of the first fault
      • 16.-
      • 16.y1.30
      • 16.Running time of the first fault
      • 16.-
  • 16.9. Fault alarm and countermeasures
    • 16.Err.01
    • 16.Inverter unit protection
    • 16.1.The short circuit of inverter output happens
    • 16.2.The wiring for the motor and the inverter is to
    • 16.3.Module overheating
    • 16.4.The internal wiring of inverter is loose
    • 16.5.The main control panel is abnormal
    • 16.6.The drive panel is abnormal.
    • 16.7.The inverter module is abnormal
    • 16.1.Eliminate peripheral faults
    • 16.2.Additionally install the reactor or the output f
    • 16.3.Check the air duct is blocked or not and the fan
    • 16.4.Correctly plug all cables
    • 16.5.Seek for technical support
    • 16.Err.02
    • 16.Acceleration overcurrent
    • 16.1.The acceleration time is too short
    • 16.2.Manual torque boost or V/F curve is not suitable
    • 16.3.The voltage is low
    • 16.4.The short-circuit or earthing of inverter output
    • 16.5.The control mode is vector and without identific
    • 16.6.The motor that is rotating is started unexpected
    • 16.7.Suddenly increase the load in the process of acc
    • 16.8.The type selection of inverter is small
    • 16.1.Increase acceleration time
    • 16.2.Adjust manual torque boost or V/F curve
    • 16.3.Set the voltage to the normal range
    • 16.4.Eliminate peripheral faults
    • 16.5.Perform identification for the motor parameters
    • 16.6.Select Speed Tracking Start or restart after sto
    • 16.7.Cancel the sudden load
    • 16.8.Choose the inverter with large power level
    • 16.Err.03
    • 16.Deceleration overcurrent
    • 16.1.The short-circuit or earthing of inverter output
    • 16.2.The control mode is vector and without identific
    • 16.3.The deceleration time is too short
    • 16.4.The voltage is low
    • 16.5.Suddenly increase the load in the process of dec
    • 16.6.Didn't install braking unit and braking resistor
    • 16.1.Eliminate peripheral faults
    • 16.2.Perform identification for the motor parameters
    • 16.3.Increase the deceleration time
    • 16.4.Set the voltage to the normal range
    • 16.5.Cancel the sudden load
    • 16.6.Install braking unit and brake resistor
    • 16.Err.04
    • 16.Constant speed overcurrent
    • 16.1.The short-circuit or earthing of inverter output
    • 16.2.The control mode is vector and without identific
    • 16.3.The voltage is low
    • 16.4.Whether suddenly increase the load when running
    • 16.5.The type selection of inverter is small
    • 16.1.Eliminate peripheral faults
    • 16.2.Perform identification for the motor parameters
    • 16.3.Set the voltage to the normal range
    • 16.4.Cancel the sudden load
    • 16.5.Choose the inverter with large power level
    • 16.Err.05
    • 16.Acceleration overvoltage
    • 16.1.Didn't install braking unit and braking resistor
    • 16.2.The input voltage is high
    • 16.3.There is external force to drag the motor to run
    • 16.4.The acceleration time is too short
    • 16.1.Install braking unit and brake resistor
    • 16.2.Set the voltage to the normal range
    • 16.3.Cancel the external force or install braking res
    • 16.4.Increase acceleration time
    • 16.Err.06
    • 16.Deceleration overvoltage
    • 16.1.The input voltage is high
    • 16.2.There is external force to drag the motor to run
    • 16.3.The deceleration time is too short
    • 16.4.Didn't install braking unit and braking resistor
    • 16.1.Set the voltage to the normal range
    • 16.2.Cancel the external force or install braking res
    • 16.3.Increase the deceleration time
    • 16.4.Install braking unit and brake resistor
    • 16.Err.07
    • 16.Constant speed overvoltage
    • 16.1.There is external force to drag the motor to run
    • 16.2.The input voltage is high
    • 16.1.Cancel the external force or install braking res
    • 16.2.Set the voltage to the normal range
    • 16.Err.08
    • 16.Control power failure
    • 16.The range of input voltage is not within the speci
    • 16.Adjust the voltage to the range of the requirement
    • 16.Err.09
    • 16.Under voltage fault
    • 16.1.The momentary power cut
    • 16.2.The inverter's input voltage is not within the s
    • 16.3.The bus voltage is not normal
    • 16.4.The rectifier bridge and buffer resistance are a
    • 16.5.The drive panel is abnormal.
    • 16.6.The control panel is abnormal
    • 16.1.Reset fault
    • 16.2.Adjust the voltage to the normal range
    • 16.3.Seek for technical support
    • 16.Err.10
    • 16.Inverter overload
    • 16.1.The type selection of inverter is small
    • 16.2.whether the load is too large or the motor stall
    • 16.1.Choose the inverter with large power level
    • 16.2.Reduce the load and check the motor and its mech
    • 16.Err.11
    • 16.Motor Overload
    • 16.1. power grid voltage is too low
    • 16.2.whether the setting motor protection parameters
    • 16.3.whether the load is too large or the motor stall
    • 16.1.Check the power grid voltage
    • 16.2.Correctly set this parameter.
    • 16.3.Reduce the load and check the motor and its mech
    • 16.Err.13
    • 16.Input phase loss
    • 16.1.The drive panel is abnormal.
    • 16.2.The lightning protection plate is abnormal
    • 16.3.The main control panel is abnormal
    • 16.4.The three-phase input power is not normal
    • 16.1.Replace the drive, the power board or contactor
    • 16.2.Seek for technical support
    • 16.3.Check and eliminate the existing problems in the
    • 16.Err.14
    • 16.Output phase loss
    • 16.1.The lead wires from the inverter to the motor is
    • 17.2.The inverter's three phase output is unbalanced
    • 17.3.The drive panel is abnormal.
    • 17.4.The module is abnormal
    • 16.1.Eliminate peripheral faults
    • 17.2.Check the motor's three-phase winding is normal
    • 17.3.Seek for technical support
    • 17.Err.15
    • 17.Module overheating
    • 17.1.The air duct is blocked
    • 17.2.The fan is damaged
    • 17.3.The ambient temperature is too high
    • 17.4.The module thermistor is damaged
    • 17.5.The inverter module is damaged
    • 17.1.Clean up the air duct
    • 17.2.Replace the fan
    • 17.3.Decrease the ambient temperature
    • 17.4.Replace the thermistor
    • 17.5.Replace the inverter module
    • 17.Err.16
    • 17.External equipment fault
    • 17.Input external fault signal through the multi-func
    • 17.Reset run
    • 17.Err.17
    • 17.Communication fault
    • 17.1.The communication cable is not normal
    • 17.2.The settings for communication expansion card F9
    • 17.3.The settings for communication parameters F9 gro
    • 17.4.The host computer is not working properly
    • 17.1.Check the communication cable
    • 17.2.Correctly set the communications expansion card
    • 17.3.Correctly set the communication parameters
    • 17.4.Check the wiring of host computer
    • 17.Err.18
    • 17.Contactor fault
    • 17.1.Input phase loss
    • 17.2.The drive plate and the contact are not normal
    • 17.1.Check and eliminate the existing problems in the
    • 17.2.Replace the drive, the power board or contactor
    • 17.Err.19
    • 17.Current detection fault
    • 17.1.Check Hall device
    • 17.2.The drive panel is abnormal.
    • 17.1.Replace the drive panel
    • 17.2.Replace hall device
    • 17.Err.21
    • 17.Motor parameter auto tuning fault
    • 17.1.The motor parameters was not set according to th
    • 17.2.The identification process of parameter is timeo
    • 17.1.correctly set motor parameter according to the n
    • 17.2.check the lead wire from the inverter to the mot
    • 17.Err.22
    • 17.Disk code fault
    • 17.1.The encoder is damaged
    • 17.2.PG card is abnormal
    • 17.3.The encoder model does not match
    • 17.4.The encoder connection has error
    • 17.1.Replace the encoder
    • 17.2.Replace the PG card
    • 17.3.Correctly set the encoder model according to the
    • 17.4.Eliminate the line fault
    • 17.Err.23
    • 17.EEPROM read and write fault
    • 17.EEPROM chip is damaged
    • 17.Replace the main control panel
    • 17.Err.26
    • 17.Inverter hardware fault
    • 17.1.Overvoltage
    • 17.2.Overcurrent
    • 17.1.Eliminate overvoltage fault
    • 17.2.Eliminate overcurrent fault
    • 17.Err.27
    • 17.Short-circuit to ground fault
    • 17.Motor short to ground
    • 17.Replace the cable or motor
    • 17.Err.28
    • 17.Cumulative running time arrival fault
    • 17.Cumulative running time arrival fault
    • 17.Clear history information by using initialization
    • 17.Err.29
    • 17.Custom fault 1
    • 17.Input custom fault 1 signal through the multi-func
    • 17.Reset run
    • 17.Err.31
    • 17.Custom fault 2
    • 17.Input custom fault 2 signal through the multi-func
    • 17.Reset run
    • 17.Err.40
    • 17.Total power-on time arrival fault
    • 17.Total power-on time reaches the set value
    • 17.Clear history information by using initialization
    • 17.Err.41
    • 17.Load drop fault
    • 17.The inverter running current is less than F8.31
    • 17.Confirm whether the load is removed or not or the
    • 17.Err.42
    • 17.PID feedback loss when running fault
    • 17.PID feedback is less than the set value of E2.11
    • 17.Check PID feedback signal or set E2.11 to an appro
    • 17.Err.51
    • 17.Quick current limiting fault
    • 17.1.Whether the load is too large or the motor stall
    • 17.2.The type selection of inverter is small
    • 17.1.Reduce the load and check the motor and its mech
    • 17.2.Choose the inverter with large power level
    • 17.COF
    • 17.Switch motor when running fault
    • 17.Change current motor through the terminal when the
    • 17.Switch motor after the inverter stops
  • 17.Appendix:Dimension drawing of PI550A1 keyboard ins
icon
复制
共17页
3D翻页模式
免费制作
更多 内容

快速跳转到指定页

PI550A/PI550A系列基本频率变频器用户手册

时间:

2024-8-27
云展网企业宣传册制作 用户案例 机械设备 PI550A/PI550A系列基本频率变频器用户手册

普传科技的产品介绍、应用案例、企业文化 【收起】

【展开】
内容简介
推荐案例
书籍缩略图

名称:

PI550A/PI550A系列基本频率变频器用户手册

时间:

2024-8-27

上传者:

普传科技图书库

其他信息:

《 PI550A/PI550A系列基本频率变频器用户手册(2024-8-27)》电子宣传画册作品由普传科技图书库于2024-8-27制作并发布于云展网电子画册制作平台。云展网是电子画册,企业宣传册,期刊杂志在线制作平台,一键上传PDF即转为逼真的3D翻页画册,或直接套用模板,生成永久有效的链接/二维码,微信扫码即可分享。
电力机电设备 电子零件 说明手册 POWTRAN Technical Specifications Wiring Diagram dimension standard specifications KEYBOARDS Frequency Inverter PI550A

选择下载版本

PDF
下载
PDF下载
.zip
下载
ZIP(HTML)下载
.exe
下载
防杀毒软件误报EXE包
.exe
下载
独立EXE文件
.MAC
下载
MAC下载
取消
分享到