H.Stars Sewage Source Heat Pump (For Spa only)
?H TARS宏 星
H.Stars (Guangzhou) Refrigerating Equipment Group Ltd.
CompanyProfile
H.Stars (Guangzhou) Refrigerating Equipment Group Ltd., established in 1992,in Economic & Technological Development Zoneof Guangzhou,China,composed of 8 subsidiaries to provide one-stop solution to HVAC customers,specializing in R&D,production,design and installation.As the company grows,H.Stars group expands its business globallyand has soldto53differentcountries.H.Stars Groupisawardedwith "New and High Technology Enterprise in Guangzhou"and has become the training base of manyuniversities both in China andabroadvia technologycooperation.
H.Stars Group supplies an extensive line of Commercial and Industrial Energy Saving HVAC products including: AirCooled Chiller,Water Cooled Chiller,Industrial Chiller, Centrifugal Chiller,Magnetic oil free centrifugal chiller,Multifunction Chiller,HotWater Unit,Heat Recovery Unit,Heat Pump Unit,Condensing Unit,Glycol Chiller,Shell and Tube Heat Exchanger,Air Handling Unit,Fan Coil Unit,Cooling Tower,etc.alltype of HVAC products.
H.Stars Group has beendedicated in qualityand innovation andis technically strong in commercial and industrial applicationasa HVAC manufacturer.Apart from obtaining plenty of energy-saving product patents,H.Stars Group has achieved CEcertificationsforPressureVesselandstandard chillers,BR1,ASME,ISO9001:2000,ISO14001:2004and other certifications.
A good reputation of H.Stars Group has been built and deliversa full HVAC service to customers worldwide.Our products are widely applied in industries for cooling of Lasergenerators,Welding electrodes,Cutting machines, Electric spark machines,Extrusion process,Hydraulic System,Electroplating,Ultrasonic Cleaning,lon Plating film,Electronic facility,Electrical appliance components, Compressed Gas Dehumidification,Dairy and Beverage Cooling processing,Pharmaceutical and Biological products, Medical equipment,Glass Coating,Tempered Glass and Cultivation Sea Food.
H.Stars Group will continue to develop energy saving and environmental friendly equipment to create "The Efficiency Planet"as ourobligation.By focusingoncustomers' needs andwants inorder to contributemore ourpotentials,from now on,H.Stars Group will hand in hand with you to be a shining star in the foreseeable future.
Product nomenclature
New trends of clean energy
In thearea of clean and renewable energy utilization,sewage source heat pump technology can be calleda model of energy saving and emission reduction.In line with world trend of "energy saving,emissionreduction,environmental protection,sustainable development",thistechnologysuccessfully heatsthedomestic water for users through the heat in urban sewage by adopting the heat pump technology.At present, the sewage source heat pump technology iswidely used in Spa,resort hot spring poolsand swimming pools.With the successful implementation of many projects,it has fully proved the advantages of the original sewage source heat pump technology.Comparedwith the conventional heatpump,the energysavingrateof this technologyreaches 3 0 % - 5 0 % ,andhasreallyachievedzeropollutionand zero emissions without any exhaust gas,waste and residue to the atmosphere.Inaddition,the investmentand operating costs of thistechnologyaresignificantly lower than traditional methods. Aftervigorous development,it can save hundreds of millions of tonsof coal each year,whichachievesreally energy conservation andenvironmental protection.
Sewagesource flowratecharacteristics--- largeand stable Sewage source temperature characteristics--- warm in winter and cool insummer.
Eveninseverecold regions,the temperatureof sewageisalso over 10-18 ^ { \circ } { \mathsf C } ,which isa rich heat source;the temperature of sewage in summer is 2 0 - 2 8 ^ { \circ } C ,which is the ideal heat source.
Incomparison withthe initial investmentof traditional heating,coolingand groundsourceheatpumps,the initial investment of sewage source heat pumps is the lowest,and the economic benefits are significant. It recovers the heat energy in the urban sewage,which not only developsa clean energysource,butalso reduces the urbanwaste heat emissions and protects the environment.
System description
1.Heat-contaminated sewage after bathing ① iscollected in the sewage tank ② ,and the residual heatwatertemperature is 2 0 ^ { \circ } C 2.Thecleanwater is heatedto 5 5 ^ { \circ } C through the "H.Stars"heatrecovery unitand use it again ③ 3.H.Starsheatrecoveryunit forSpa ④ can supply freecoldwaterwhile heating,and provideairconditioningfortherestareas ⑤ .
\*Replace the boiler,safe and reliable,easy to
operate
\*Reduce operating costs and meet the
environmentalrequirements
\*Onemachine for two purposes,heatingand
cooling atthe same time
COPreaches8.0
Function Description
The heat pump unit for Spa is an energy-saving sewage source heat pump unit specially developed for the Spa. The system can save about 5 0 % energy compared with the conventional equipment,adopts the characteristics of the sewagesourcetomaintainthetemperatureabove 2 0 ^ { \circ } \mathsf { C } all the year,and uses the sewage source as the heat source, which can meet hot water supply byadoptingadvanced technology and equipment.
Application Scope
The unit hasa total of 12 standard specifications with the heating ranging 30kw-20okw, hot water temperature ranging 5 5 ^ { \circ } C - 8 5 ^ { \circ } C .The unit can be equipped with heat and cold recoveryunitsasrequired.Thewateroutlet temperature for heat recovery is 6 5 ^ { \circ } C ,and lowestwateroutlet temperature of chilled water is 5 ^ { \circ } \mathsf { C } .Inaddition to standard specifications, various non-standard products can be customized according to user requirements.
EconomicBenefit
Sewage Source Heat Pump Units have the lowest initial investmentin groundsource heat pumps.Itrecovers the heatenergyin theurbansewage,which notonlydevelops a clean energy source,but also reduces the urban waste heat emissions and protects the environment.The sewage source heat pump system has obvious advantages from the efficiency of heatingand cooling,or from the future energy source,its features significant economic benefits.
Technical Parameter Table of Sewage Source Medium-Temperature Heat Pump ( 5 5 ^ { \circ } \mathsf { C } )
Refrigerant:R22 Power:3Φ-380V-50Hz
| Model | Energy | Hotwater | Sewagewater | weight Running | |||||||||||
| MPa | in | ||||||||||||||
| 20STB-20WHDC4 | 72 | 16 | 6 | in 2" | 10 | 1 | 27 | 2 | 12 | 1 | 20 | 65 | 900 | 1000 | |
| 20STB-25WHDC4 | 88 | 18 | 7 | 2" | 12 | 1 | 40 | 2″ | 15 | 1 | 40 | 65 | 1000 | 1100 | |
| 20STB-30WHDC4 | 134 | 24 | 0 50 100 | 8 | 2 | 19 | 1 | 50 | 2” | 24 | 1 | 50 | 70 | 1200 | 1300 |
| 20STB-40WHDC4 | 152 | 32 | 10 | 2-1/2" | 21 | 1 | 45 | 2-1/2° | 26 | 1 | 45 | 65 | 1350 | 1480 | |
| 20STB-50WHDC4 | 176 | 36 | 12 | 2-1/2" | 24 | 1 | 55 | 2-1/2" | 30 | 1 | 55 | 70 | 1450 | 1580 | |
TechnicalParameterTableofSewageSourceHighTemperatureHeatPump ( 9 0 ^ { \circ } \mathsf { C } )
Refrigerant: R22 Power:3φ-380V-50Hz
| Model | Povuer | Eonrgy | Hotwater | Sewagewater | ||||||||||
| 三 | ||||||||||||||
| 80HW-25WH4 | 28 | 9 | 3 | 1-1/2" | 6 | 1 | 23 | 1-1/2" | 5 | 1 | 23 | 810 | 900 | |
| 80HW-30WH4 | 31 | 11 | 3 | 1-1/2" | 7 | 1 | 26 | 1-1/2" | 5 | 1 | 26 | 860 | 960 | |
| 80HW-35WH4 | 36 | 13 | 3.5 | 1-1/2" | 8 | 1 | 29 | 1-1/2" | 6 | 1 | 29 | 900 | 1020 | |
| 80HW-40WH4 | 40 | 14 | 0 100 | 4 | 1-1/2" | 9 | 1 | 31 | 1-1/2" | 7 | 1 | 31 | 1040 | 1170 |
| 80HW-45WH4 | 48 | 17 | 4 | 2" | 11 | 1 | 41 | 2" | 8 | 1 | 41 | 1130 | 1260 | |
| 80HW-60WH4 | 63 | 22 | 6 | 2 | 15 | 1 | 45 | 2″ | 11 | 1 | 45 | 1260 | 1440 | |
| 80HW-70WH4 | 77 | 28 | 7 | 2" | 18 | 1 | 50 | 2" | 13 | 1 | 50 | 1350 | 1530 | |
Technical Parameter Table of Sewage Source Medium-Temperature Heat Pump ( 5 5 ^ { \circ } \mathsf { C } )
| Model | Energy | Hotwater | Sewagewater | Roning | Sweigne | weight Running | |||||||||
| MPa | in | MPa | |||||||||||||
| 20STB-20WHDC4 | 86 | 19 | 6 | in 2" | 12 | 1 | 27 | 2 | 14 | 1 | 20 | 65 | 990 | 1100 | |
| 20STB-25WHDC4 | 106 | 21 | 7 | 2 | 15 | 1 | 40 | 2" | 18 | 1 | 40 | 65 | 1100 | 1210 | |
| 20STB-30WHDC4 | 161 | 28 | 0 50 100 | 8 | 2" | 23 | 1 | 50 | 2 | 28 | 1 | 50 | 70 | 1320 | 1430 |
| 20STB-40WHDC4 | 182 | 38 | 10 | 2-1/2" | 25 | 1 | 45 | 2-1/2" | 31 | 1 | 45 | 65 | 1485 | 1628 | |
| 20STB-50WHDC4 | 211 | 43 | 12 | 2-1/2" | 29 | 1 | 55 | 2-1/2" | 36 | 1 | 55 | 70 | 1595 | 1738 | |
Notes:
TechnicalParameterTableofSewageSourceHighTemperatureHeatPump ( 9 0 ^ { \circ } \mathsf { C } )
Refrigerant:R22 Power:3φ-460V-60Hz
| Model | Power | Eonrol | Hotwater | Sewagewater | Running | |||||||||
| 三 | P | 三 | ||||||||||||
| 80HW-25WH4 | 34 | 11 | 3 | 1-1/2" | 8 | 1 | 23 | 1-1/2" | 6 | 1 | 23 | 891 | 990 | |
| 80HW-30WH4 | 37 | 13 | 3 | 1-1/2" | 9 | 1 | 26 | 1-1/2" | 6 | 1 | 26 | 946 | 1056 | |
| 80HW-35WH4 | 43 | 15 | 3.5 | 1-1/2" | 10 | 1 | 29 | 1-1/2" | 7 | 1 | 29 | 990 | 1122 | |
| 80HW-40WH4 | 48 | 17 | 0 100 | 4 | 1-1/2" | 11 | 1 | 31 | 1-1/2" | 8 | 1 | 31 | 1144 | 1287 |
| 80HW-45WH4 | 57 | 20 | 4 | 2 | 13 | 1 | 41 | 2 | 10 | 1 | 41 | 1243 | 1386 | |
| 80HW-60WH4 | 75 | 27 | 6 | 2" | 18 | 1 | 45 | 2″ | 13 | 1 | 45 | 1386 | 1584 | |
| 80HW-70WH4 | 92 | 33 | 7 | 2" | 22 | 1 | 50 | 2" | 16 | 1 | 50 | 1485 | 1683 | |
Technical Outline Drawing of Sewage Medium Temperature Heat Pump (55C)
| Model | A | B | C | D | E |
| 20STB-20WHDC4 | 1700 | 900 | 1600 | 1300 | 860 |
| 20STB-25WHDC4 | 1700 | 900 | 1600 | 1300 | 860 |
| 20STB-30WHDC4 | 1800 | 1150 | 1750 | 1300 | 1110 |
| 20STB-40WHDC4 | 1800 | 1150 | 1750 | 1300 | 1110 |
| 20STB-50WHDC4 | 1800 | 1150 | 1750 | 1300 | 1110 |
Technical Outline Drawingof Sewage HighTemperature HeatPump (90 ^ { \circ } \mathsf { C } )
| Model | A | B | C | D | E |
| 80HW-25WH4 | 2000 | 1700 | 1400 | 1500 | 1660 |
| 80HW-30WH4 | 2000 | 1700 | 1400 | 1500 | 1660 |
| 80HW-35WH4 | 2000 | 1700 | 1400 | 1500 | 1660 |
| 80HW-40WH4 | 2200 | 1800 | 1400 | 1600 | 1760 |
| 80HW-45WH4 | 2200 | 1800 | 1400 | 1600 | 1760 |
| 80HW-60WH4 | 2200 | 1800 | 1500 | 1600 | 1760 |
| 80HW-70WH4 | 2300 | 1800 | 1500 | 1600 | 1760 |
Economic BenefitsAnalysisCurve
| Typeof HotWater Unit | GasBoiler | SewageSource HeatPump Unit |
| Energy consumed | Fuel gas | Electricity |
| Unit heat | 14700kJ/m³ | 3612kJ/KW·h |
| Average heat efficiency | 0.75 | 4.9 |
| Unit price of energy | RMB2.6 yuan/m³ | RMB1.07yuan/KW·h |
| Initial investment | Low | High |
| Operating cost | RMB81.7yuan | RMB17.5yuan |
| Safety | With risk of poisoning and explosion | Without risk of electric shock |
| Service life | 6-8 years | 13-16years |
| Pollution to environment | Yes | No |
Cold Recovery Technology
The principle of cold recovery is based on the principle ofheating,recoveringthecoldthatisreleasedtothe environment and converting it into the air conditioning systemtogeneratecoldwaterfortheairconditioner,it canreplacepartof theoriginalairconditioningsystem load to achieve energy saving effects.
Variable Frequency Drive (VFD) Technology
VFDis to change the power supply frequency, thereby adjusting the load,reducing power consumption, reducing losses,and extending the service life of the equipment.The core of the VFD is the frequency converter,which realizes theautomatic adjustment of the running speed of the motor through the conversion of the power supply frequency,and changes the fixed grid frequency of 5 0 H z to a changing frequency of 30- 1 3 0 mathsf { H z } .Inaddition,it canwiden theadaptable range of the power supply voltage to 142-270V,which solves the problem of the grid voltage instability which can affect the operation of the equipment.The technology thatrealizes AC control by changing the AC frequency is called VFD technology.
H.Stars (Guangzhou) Refrigerating Equipment Group Ltd
Address:No.1 Guoyuan 4th Road,Guangzhou Economic&
Technological Development Zone,HuangPu District,Guangzhou,
China Zip Code510530
Email:sales@hstars.com.cn
Tel:+862062266755 ext. 886
Fax:+862082266081
Website:www.hstarschiller.com
Twitter:twitter.com/HStarsGroup
Facebook:www.facebook.com/Hstarsgroup
Linkedln:www.linkedin.com/company/hstarsgroup
Instagram:www.instagram.com/hstars_chiller_maker