TGM1NL系列剩余电流保护断路器
3.6断路器功率损耗参照表
| 产品型号 | 通电电流 (A) | 单极电阻 (mΩ) | 3/4极总功率损耗(W) | ||
| 板前接线 | 板后接线 | 插入式板后接线 | |||
| TGM1NL125 | 125 | 0.72 | 28 | 31 | 32 |
| TGM1NL-160 | 160 | 0.4 | 60 | 87 | 89 |
| TGM1NL-250 | 250 | 0.2 | 63 | 90 | 90 |
| TGM1NL-320 | 320 | 0.19 | 65 | 95 | 98 |
| TGM1NL400 | 400 | 0.15 | 68 | 72 | 100 |
| TGM1NL-630 | 630 | 0.14 | 180 | 190 | 200 |
| TGM1NL-800 | 800 | 0. 11 | 200 | 230 | 290 |
3.7产品连接铜导线截面积
| 额定电流(A) | 2 | 20 | 2 | 3 | ≤55 | 65 | 5250 | |||||||
| 导线截面积 (mm²) | 2.5 | 4 | 6 | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 150 | 185 | 240 |
| 额定电流(A) | 铜导线或绝缘铜线 | 铜母排 | ||
| 数量 | 截面积(mm²) | 数量 | 尺寸(mm×mm) | |
| >400 ≤500 | 2 | 150 | 2 | 30x5 |
| 530 | 2 | 185 | 2 | 40x5 |
| >630 ≤800 | 2 | 240 | 2 | 50x5 |
TGM1NL系列剩余电流保护断路器
3.8产品接线拧紧力矩
3.9环境温度变化的降容系数见表10
| 型号 | TGM1NL-125/160 | TGM1NL-250/320 | TGM1NL-400 | TGM1NL-630/800 |
| 螺纹公称直径(mm) | M8 | M8 | M10 | M12 |
| 拧紧力矩(N.m) | 10 | 12 | 22 | 28 |
| 产品型号 | -35℃ | -30°℃ | -25℃ | -20°℃|-15℃|-10°℃ | -5℃ | O℃ | 30℃ | 35℃ | 40℃ | 45℃ | 50℃ | 55℃ | 60℃ | ||
| TGM1NL-125 | 1. 4In | 1. 35In | 1. 3In | 1. 2In | 1. 18In | 1. 15In | 1. 15In | 1.1In | 1In | 0.95In | 0. 94In | 0.93In | 0.92In|0.91In|0.89In | ||
| TGM1NL-160 | 1. 4In | 1. 35In | 1. 3In | 1. 25In | 1. 22In | 1. 2In | 1. 15In | 1. 1In | 1In | 0. 95In | 0. 94In | 0. 93In | 0. 92In | 0. 91In | 0. 89In |
| TGM1NL-250 | 1. 4In | 1. 35In | 1. 3In | 1.25In | 1. 2In | 1. 18In | 1. 15In | 1. 1In | 1In | 0.95In | 0. 9In | 0. 89In | 0.85In | 0. 81In | 0.78In |
| TGM1NL320 | 1. 4In | 1. 35In | 1. 3In | 1. 25In | 1. 2In | 1. 18In | 1. 15In | 1. 1In | 1In | 0. 95In | 0.9In | 0. 89In | 0. 85In | 0. 81In | 0. 78In |
| TGMINL-400 | 1. 6In | 1.55In | 1. 44In | 1. 42In | 1. 4In | 1. 35In | 1. 3In | 1. 25In | 1In | 0.95In | 0. 9In | 0. 89In | 0. 85In | 0. 81In | 0. 78In |
| TGM1NL630 | 1. 34In | 1. 32In | 1. 3In | 1. 3In | 1. 25In | 1. 23In | 1. 18In | 1. 13In | 1In | 0.95In | 0. 93In | 0. 85In | 0. 82In | 0. 8In | 0. 78In |
| TGMINL-800 | 1.34In | 1. 32In | 1.3In | 1. 3In | 1. 25In | 1. 23In|1. 18In | 1. 13In | 1In | 0. 95In | 0. 93In | 0. 85In | 0. 82In | 0.8In | 0. 78In |
3.10海拔变化对断路器特性的影响见表11
海拔超过 2000m ,断路器电气特性可参照下表进行修正。
| 海拔(m) | 2000 | 3000 | 4000 | 5000 |
| 工作电流修正系数 | 1In | 0.94In | 0.88In | 0.85In |
| 绝缘电压(V) | 1000 | 800 | 700 | 600 |
| 工频耐压 (V) | 3000 | 2500 | 2000 | 1800 |
4正常工作条件及安装条件
4.1温度
4.1.1周围空气温度不超过 +40°C ,下限为 -59 ,24h内平均温度值不超过 +359 。
4.1.2特殊环境使用下:温度下限不低于 -259 ,上限不超过 +559 。
4.1.3如需在超过 +40°\mathsf{C} ,低于 -59 环境使用,请按温度补偿系数降容使用或联系我们。
4.2海拔
4.2.1正常工作的安装地点海拔不超过 2000\mathsf{m} 。
4.2.2如需在海拔超过2000m的情况下使用,请按海拔高度系数降容使用或联系我们。
4.3湿度
4.3.1大气的相对湿度在周围最高温度 +40°C 时不超过 50% ,在较低温度下可以有较高的相对湿度。
4.3.2最湿月的平均最大相对湿度不超过 90% ,同时该月的月平均最低温度不超过 +259 。
4.3.3请考虑因温度变化发生在产品表面上的凝露会对产品性能产生影响。
4.4污染等级:3级。
4.5安装类别:Ⅲ。
4.6安装条件:断路器安装的垂直倾斜度不超过5°。
4.7外磁场:断路器安装场所附近的磁场在任何方向不超过地磁场的5倍。
TGM1NL系列剩余电流保护断路器
5产品附件
塑壳断路器提供完整的内部附件和外部附件,以满足不同客户的需求。
5.1内部附件代号
| OF | 1N | 160 | L | D | A2 | |
| 附件代号 | 适配断路器代号 | 壳架电流代号 | 安装位置 | 接线引出方式 | 电压等级 | |
| OF:辅助触头 | 1N :TGM1NL | 160(125)、250、 320、400、630、 800 | L:左边 R:右边 | 缺省:直接导线 引出 D:接线端子盒 | 缺省:无 A1:AC220/230/240V A2:AC380/400/415V D1:DC24V D2:DC110V D3:DC220V | |
| SD:报警触头 | ||||||
| MN:欠压脱扣器 | ||||||
| MX:分励脱扣器 |
5.1.1辅助触头OF
●接在断路器的辅助回路中,用于远程指示断路器的合闸(ON)或分闸(OFF)/自由脱扣状态的附件。
\*注:TGM1NL-125壳架应选择160壳架附件。直接导线引出长度默认 50cm ,其他长度请订货说明。
例:TGM1NL系列250壳架右辅助(10N10FF)带端子盒代号为:OF1NL-250RD2。
●接线图
●电气特性
| 壳架等级额定电流 | Inm≤320A | Inm≥400A | ||
| 约定发热电流Ith | 3A | 6A | ||
| 使用类别 | AC-15 | DC-13 | AC-15 | DC-13 |
| 额定工作电流 | 0.3A | 0. 15A | 1A | 0. 15A |
TGM1NL系列剩余电流保护断路器
5.1.2欠压脱扣器MN
·实现断路器的欠电压保护功能,在电源电压过低时断开断路器,保护用电设备
a 额定工作电压的 35%-70% 时,欠压脱扣器应可靠使断路器脱扣;
b额定工作电压的 85%-110% 时,欠压脱扣器应保证断路器能合闸;
C额定工作电压低于 35% 时,欠压脱扣器应防止断路器合闸。
\*注:欠压脱扣器必须先通电,断路器才能再扣及合闸,否则将损坏断路器。
\*注:TGM1NL-125壳架应选择160壳架附件。直接导线引出长度默认 50cm ,其他长度请订货说明。例:TGM1NL系列250壳架左欠压AC220V(直接引线引出)代号为:MN1NL-250LA1。
●接线图
表14
| 产品型号 | 起动电流值(mA) | 功耗(W) | ||
| AC415V | AC230V | AC415V | AC230V | |
| TGM1NL-125/160 | 9.95 | 15.55 | 4.55 | 3.82 |
| TGM1NL-250/320 | 10.88 | 15.83 | 4. 85 | 3.92 |
| TGM1NL400 | 9.5 | 11. 2 | 3.8 | 2.83 |
| TGM1NL-630/800 | 5. 4 | 7. 75 | 2. 7 | 1. 85 |
TGM1NL系列剩余电流保护断路器
5.1.3报警触头SD
●接线图
●电气特性
| 壳架等级额定电流 | Inm≤320A | Inm≥400A | ||
| 约定发热电流Ith | 3A | 6A | ||
| 使用类别 | AC15 | DC-13 | AC15 | DC-13 |
| 额定工作电流 | 0.3A | 0. 15A | 1A | 0. 15A |
TGM1NL系列剩余电流保护断路器
5.1.4分励脱扣器MX
\*注:TGM1NL-125壳架应选择160壳架附件。直接导线引出长度默认 50cm ,其他长度请订货说明。例:TGM1NL系列250壳架左分励DC220V(直接引线引出)代号为:MX1NL-250LD3。
●接线图
\*注:K-分励脱扣器内部与线圈串联的微动开关为常闭触头,当断路器分闸后,该触头自行断开,合闸时闭合。
当控制电压为DC24V时,铜导线最大长度需满足以下要求:
| 导线面积 额定控制 电源电压Uc(DC24V) | 1. 5mm² | 2.5mm² |
| AC220/230/240V | 150m | 250m |
| AC380/400/415V | 100m | 160m |
若不满足上表要求,推荐采用下图进行分励控制器回路设计:
\*注:KA为DC24V中间继电器,触点电流容量为1A。
表17
| 产品型号 | 起动电流值(mA) | 功耗(W) | ||||||
| AC400V | AC230V | DC220V | DC24V | AC400V | AC230V | DC220V | DC24V | |
| TGM1NL-125/160 | 0.35 | 0. 45 | 0.37 | 4. 52 | 95.8 | 73 | 90. 7 | 91.2 |
| TGM1NL-250/320 | 0. 42 | 0.48 | 0.39 | 4. 51 | 112 | 68.8 | 90.7 | 85.3 |
| TGM1NL-400 | 0. 48 | 0. 51 | 0. 41 | 4. 51 | 132 | 78.3 | 94. 4 | 110 |
| TGM1NL-630/800 | 0. 54 | 0.85 | 1. 21 | 5. 51 | 163 | 153 | 158 | 120 |
TGM1NL系列剩余电流保护断路器
| CD2 | 1N | 160 | A2 | ||
| 附件代号 | 适配断路器代号 | 壳架电流代号 | 电压等级 | 极数代号 | |
| AH:圆形手操 | 1N:TGM1NL | 800 | 160(125)、250、 320、400、630、 | A1:AC220/230/240V A2:AC380/400/415V D1:DC24V D2:DC110V DC3:DC220V | 两极:2P 三极:3P 四极:4P |
| RH:方形手操 CD2:交直流通用电操机构 | |||||
| GP:板前接线过渡板 | |||||
| GB:相间隔板 | |||||
| BH:板后接线 | |||||
| LS:机械连锁 |
5.2外部附件
5.2.1手动操作机构RN/AH
●通过手柄的旋转方式来操作断路器,符合人体工程设计的旋转手柄使断路器操作更灵活TGM1NL系列断路器有2种形式的手动操作机构:直接旋转手柄(圆形手操,方形手操)延伸旋转手柄(圆形延伸手操,方形延伸手操)
\*注:TGM1NL-125壳架应选择160壳架附件。例:TGM1NL系列250壳架圆形手操代号为:AH1NL-250。
●手操外形尺寸
表19
| 型号规格 | TGM1NL-125/160 | TGM1NL-250/320 | TGM1NL-400 | TGM1NL-630/800 |
| 安装尺寸 (H) | 61 | 57 | 87 | 87 |
TGM1NL系列剩余电流保护断路器
5.2.2电动操作机构CD2
●用于断路器远距离电动闭合、断开及再扣以及自动化控制场合
\*注:TGM1NL-125壳架应选择160壳架附件。直接导线引出长度默认 50cm ,其他长度请订货说明。
例:TGM1NL系列250壳架电动操作机构AC380V代号为:CD21NL-250A2。
\bullet 电气特性及接线图
\*注:K-分励脱扣器内部与线圈串联的微动开关为常闭触头,当断路器分闸后,该触头自行断开,合闸时闭合。
P1、P2为外接、电源输入
SB1、SB2为操作按钮(用户自备)
●外形安装尺寸
| 型号 | A | B | H | H1 | a | b |
| TGM1NL-125/160 | 116 | 90 | 77 | 22 | 30 | 129 |
| TGM1NL-250/320 | 116 | 90 | 77 | 17 | 35 | 126 |
| TGM1NL400 | 176 | 130 | 115 | 24 | 44 | 194 |
| TGM1NL-630/800 | 176 | 130 | 115 | 17 | 70 | 243 |
TGM1NL系列剩余电流保护断路器
5.2.3板前接线过渡板GP
\bullet 使断路器的接线方式更灵活,通过加装该部件可以增加相间距,增加线路之间的安全性
\*注:TGM1NL-125壳架应选择160壳架附件。例:TGM1NL系列250壳架3P过渡板代号为:GP1NL-2503P。
5.2.4相间隔板GB
\bullet 可增强相间导体绝缘性能,即使在开关安装好后,也可以从正面插槽安装
\*注:TGM1NL-125壳架应选择160壳架附件。相间隔板为出厂标配,一台断路器(两极2片,三极4片,四极6片)。
例:TGM1NL系列250壳架3P相间隔板代号为:GB1NL-2503P。
5.2.5板后接线BH
●使断路器的接线方式更灵活,通过加装该附件可以实现板后接线
\*注:TGM1NL-125壳架应选择160壳架附件。例:TGM1NL系列250壳架3P板后代号为:BH1NL-2503P。
TGM1NL系列剩余电流保护断路器
5.2.6机械连锁LS
5.3漏电报警模块
漏电报警模块是通过发光二极管的发光起到指示报警作用,当发光二极管发出红光时,说明系统漏电超过整定值,此时常开触点转化为常闭状态,常闭触点转化为常开状态。
●主要应用在一些特殊场合,不因漏电而影响紧急情况下继续使用电源;用户得到漏电报警信号,可根据需要适时检修漏电故障的原因,排除故障。
输入电压:AC220/230V、AC380/400V、DC24V注:虚框内为漏电报警模块内部附件接线图。
说明:
P5-P6:输入电源;
P1、P2为公共端,P2为常闭触头,
P4为常开触头:触点容量 0.5\mathsf{A} AC250V
TGM1NL系列剩余电流保护断路器
6结构和工作原理
6.1结构
本系列断路器是电子式电流动作型漏电保护器。主要部件有:主开关(包括过电流脱扣器),零序电流互感器,电子放大部件,漏电脱扣器,试验装置,全部零部件均装于一个塑料外壳中。
6.2 工作原理
当被保护电路中有漏电或触电时,零序电流互感器有一个信号输出,当该信号输出达到一定值时,就触发可控硅导通,使漏电脱扣器动作,从而带动牵引杆使操作机构在很短的时间内断开,切断电源,从而实现漏电保护功能。(工作原理见图1)。
TGM1NL系列剩余电流保护断路器
7外形及安装尺寸
断路器的外形尺寸和面板开孔尺寸见图及表21,接线尺寸和安装尺寸见图及表22
TGM1NL系列剩余电流保护断路器
表21
| 产格 | 型号 | 极数 | 外形尺寸(m | 面板开孔礼尺寸(m3 | ||||||||||
| W | H1 | C | D | L6 | H4 | |||||||||
| TGM1NL-125/160 | L | 2P | 62 | 151 | 265 | 103 | 64 | 3 | 41 | 69 | 26 | 97 | 27.5 | 12 |
| 3P | 93 | 151 | 265 | 103 | 64 | 33 | 41 | 69 | 26 | 97 | 27.5 | 12 | ||
| 4P | 123 | 151 | 265 | 103 | 64 | 33 | 41 | 69 | 26 | 97 | 27.5 | 12 | ||
| TGMINL-125/160 | M | 2P | 62 | 151 | 265 | 118 | 82 | 3 | 41 | 69 | 26 | 97 | 27.5 | 12 |
| 3P | 93 | 151 | 265 | 118 | 82 | 33 | 41 | 69 | 26 | 97 | 27.5 | 12 | ||
| 4P | 123 | 151 | 265 | 118 | 82 | 33 | 41 | 69 | 26 | 97 | 27. 5 | 12 | ||
| TGM1NL250/320 | L | 2P | 78 | 165 | 302 | 103 | 69 | 9 | 49 | 66 | 29 | 97 | 35 | 10 |
| 3P | 107 | 165 | 302 | 103 | 69 | 39 | 49 | 66 | 29 | 97 | 35 | 10 | ||
| 4P | 142 | 165 | 302 | 103 | 69 | 39 | 49 | 66 | 29 | 97 | 35 | 10 | ||
| TGM1NL250/320 | M | 2P | 78 | 165 | 302 | 119 | 85 | 9 | 49 | 66 | 29 | 97 | 35 | 10 |
| 3P | 107 | 165 | 302 | 119 | 85 | 39 | 49 | 66 | 29 | 97 | 35 | 10 | ||
| 4P | 142 | 165 | 302 | 119 | 85 | 39 | 49 | 66 | 29 | 97 | 35 | 10 | ||
| TGM1NL400 | L、M | 3P | 150 | 257 | 469 | 154 | 98 | 46 | 71 | 110 | 59 | 155 | 51 | 15 |
| 4P | 198 | 257 | 469 | 154 | 98 | 46 | 71 | 110 | 59 | 155 | 51 | 15 | ||
| TGM1NL-630 | L、M | 3P | 181 | 270 | 482 | 160 | 102 | 61 | 80 | 110 | 59 | 155 | 57 | 14 |
| 4P | 239 | 270 | 482 | 160 | 102 | 61 | 80 | 110 | 59 | 155 | 57 | 14 | ||
| TGMINL-630大体 积/800 | L、M | 3P | 210 | 280 | 497 | 160 | 103 | 75 | 83 | 105 | 60 | 176 | 52 | 15 |
| 4P | 280 | 280 | 497 | 160 | 103 | 75 | 83 | 105 | 60 | 176 | 52 | 15 | ||
表22
| 产格 | 型号 | 极数 | 安装尺寸( | |||||||||||
| H2 | H3 | W1 | 接线尺寸(2) | L4 | L5 | M | A | H5 | ||||||
| TGMINL-125/160 | L | 2P | 25 | 25 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | / | 129 | 5 | 28 |
| 3P | 25 | 25 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | 30 | 129 | 5 | 28 | ||
| 4P | 25 | 25 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | 60 | 129 | 5 | 28 | ||
| TGMINL-125/160 | M | 2P | 29 | 29 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | / | 129 | 5 | 28 |
| 3P | 29 | 29 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | 30 | 129 | 5 | 28 | ||
| 4P | 29 | 29 | 30 | 18 | 133 | 8.5 | 8.5 | M8 | 60 | 129 | 5 | 28 | ||
| TGM1NL-250/320 | L | 2P | 25.5 | 24. 5 | 35 | 26 | 147 | 13. 8 | 13.8 | M8 | / | 125. 4 | 5 | 44 |
| 3P | 25. 5 | 24.5 | 35 | 26 | 147 | 13. 8 | 13.8 | M8 | 35 | 125. 4 | 5 | 44 | ||
| 4P | 25.5 | 24.5 | 35 | 26 | 147 | 13. 8 | 13.8 | M8 | 70 | 125. 4 | 5 | 44 | ||
| TGMINL-250/320 | M | 2P | 21.5 | 21.5 | 35 | 26 | 147 | 13.8 | 13. 8 | M8 | 125. 4 | 5 | 60 | |
| 3P | 21.5 | 21.5 | 35 | 26 | 147 | 13. 8 | 13.8 | M8 | 35 | 125. 4 | 5 | 60 | ||
| 4P | 21.5 | 21.5 | 35 | 26 | 147 | 13. 8 | 13. 8 | M8 | 70 | 125. 4 | 5 | 60 | ||
| TGM1NL-400 | L | 3P | 38.5 | 38 | 48 | 33 | 224 | 14. 5 | 14. 5 | M10 | 44 | 194 | 8 | 67 |
| 4P | 38.5 | 38 | 48 | 33 | 224 | 14.5 | 14.5 | M10 | 94 | 194 | 8 | 67 | ||
| TGMINL400 | M | 3P | 39.5 | 38 | 48 | 33 | 224 | 14.5 | 14.5 | M10 | 44 | 194 | 8 | 67 |
| 4P | 39.5 | 38 | 48 | 33 | 224 | 14. 5 | 14.5 | M10 | 94 | 194 | 8 | 67 | ||
| TGMINL-630 | L、M | 3P | 43. 5 | 41. 5 | 58 | 41 | 235 | 15. 5 | 15.5 | M12 | 58 | 200 | 6 | 70 |
| 4P | 43.5 | 41. 5 | 58 | 41 | 235 | 15. 5 | 15. 5 | M12 | 116 | 200 | 6 | 70 | ||
| TGMINL-630大体 积/800 | L、M | 3P | 41 | 41 | 70 | 45 | 243 | 15. 5 | 14.7 | M12 | 70 | 243 | 7 | 70 |
| 4P | 41 | 41 | 70 | 45 | 243 | 15. 5 | 14. 7 | M12 | 140 | 243 | 7 | 70 | ||
TGM1NL系列剩余电流保护断路器
7.3插入式产品外形和安装尺寸见表23
| 型号 | 外形及安装尺寸 mm) | |||||||||||
| A | B1 | B2 | C1 | C2 | E | F | G | K | H | H1 | H2 | |
| TGM1NL-125/160 | 168 | 91 | 125 | 60 | 90 | 57 | 132 | 92 | 38 | 50 | 33 | 28 |
| TGM1NL-250/320 | 186 | 107 | 145 | 70 | 105 | 54 | 145 | 94 | 46 | 50 | 33 | 37 |
| TGM1NL-400 | 280 | 149 | 200 | 60 | 108 | 129 | 224 | 170 | 55 | 60 | 38 | 46 |
| TGM1NL-630/800 | 305 | 210 | 280 | 90 | 162 | 146 | 243 | 181 | 62 | 87 | 60 | 22 |
| 型号 | 外形及安装尺寸 mm) | ||||||||
| H3 | N | S | Q | B3 | B4 | AM | BM | 4-d | |
| TGM1NL-125/160 | 19 | 178 | 82 | 48 | 101 | 135 | M6 | M8 | Φ6.5 |
| TGM1NL-250/320 | 20 | 196 | 84 | 56 | 117 | 155 | M6 | M8 | Φ6.5 |
| TGM1NL400 | 24 | 290 | 160 | 65 | 159 | 210 | M8 | M12 | Φ8.5 |
| TGM1NL-630/800 | / | 315 | 171 | 72 | 220 | 290 | M10 | M12 (T) | Φ11 |
TGM1NL系列剩余电流保护断路器
8订货须知
用户订货时必须说明如下事项:
a)断路器的型号、名称、极数。b)断路器的额定电流。c)额定剩余动作电流及分断时间。d)断路器的附件名称、规格、组合代号:采用欠压脱扣器和分励脱扣器时,应注明工作电压(或控制电源电压)的电压值。d)用途:配电用(不注明按配电用交货)、电动机保护用(用2表示)。f)数量。例如:TGM1NL-125,三极四线、A型、L型分断能力的配电保护用断路器,复式脱扣器,额定电流100A,额定剩余动作电流100mA/300mA/500mA,非延时型,共200台。应写成:TGM1NL-125L/3N300A100A100mA/300mA/500mA200台。对断路器有特殊要求可与厂家协商决定。
TGM1NL系列剩余电流保护断路器
9产品选型表
9.1产品选型表
TGM1NL系列剩余电流保护断路器
9.2产品内部附件选型表
9.3产品外部附件选型表
TGM1L系列剩余电流保护断路器
1产品概述
TGM1L系列具有剩余电流保护的断路器(以下简称断路器)是本公司采用国际先进技术设计、开发的新型漏电断路器之一。适用于交流 50H z ,额定电压至400V,额定电流16A至800A的电路中。
其主要功能是对有致命危险的人身触电提供间接接触保护。额定剩余动作电流不超过 30\mathsf{m}\mathsf{A} 的漏电断路器在其他保护措施失效时,也可作为直接接触的补充保护,但不能作为唯一的直接接触保护。同时还可用来防止由于接触故障电流而引起的火灾危险。并可用来保护线路免受过载、短路等危害,亦可作为线路的不频繁转换和电动机不频繁启动之用。
该断路器具有体积小、分断高、飞弧短及剩余动作电流、剩余电流动作时间可调节等特点,同时可带报警触头、分励脱扣器、辅助触头、旋转手柄操作机构、电动操作机构等附件,并可采用板前、板后和插入式等多种接线方式,是用户使用的理想产品。
符合标准:GB/T14048.2和IEC60947-2。
2产品命名规则
| 代号 | 说明 |
| A型 | N极不安装过电流脱扣元件,N极始终接通,不与其它三极一起合分 |
| B型 | N极不安装过电流脱扣元件,N极与其它三极一起合分(N极先合后分) |
| C型 | N极安装过电流脱扣元件,N极与其它三极一起合分(N极先合后分) |
| D型 | N极安装过电流脱扣元件,N极始终接通,不与其它三极一起合分 |
TGM1L系列剩余电流保护断路器
| 脱扣器及附件代号 左面安装右面安装 口报警触头 ■辅助触头 ●分励脱扣器 手柄 表2 | ||||||
| 型号 脱扣 极数 方式 | TGM1L-125 TGM1L-250 | TGM1L-800 | ||||
| 及代号 200 | 附件名称 | 3极 | 4极 | 3极 | 4极 | |
| 300 | 无附件 | |||||
| 308 | 报警触头 | 回 | 口 | |||
| 318 | 分励脱扣器 | |||||
| 328 | 辅助触头 分励脱扣器 | |||||
| 340 | 辅助触头 | · | ||||
| 360 | 二组辅助触头 | |||||
| 318 | 分励脱扣器 报警触头 | 回 | · | |||
| 328 | 辅助触头 报警触头 | 司 | 司 | 日 | ||
| 348 | 分励脱扣器 报警触头 | 8 | ||||
| 368 | 二组辅助触头 报警触头 | 日口 | 日 | |||
TGM1L系列剩余电流保护断路器
3产品参数
3.1产品参数见表3
| 基本信息 | |||||||||
| 壳架等级额定电流 | 125 | 250 | 400 | 800 | |||||
| 极数 | 1P+N、2P 3P、 3P+N、4P | 1P+N、2P 3P、3P+N、 4P | 3P、3P+N、4P 3P、3P+N、4P | ||||||
| 频率(Hz) | 50 | 50 | 50 | 50 | |||||
| 额定工作电压Ue(V) | 230 | 400 | 230 | 400 | 400 | ||||
| 额定绝缘电压Ui(V) | 690 | 800 | 690 | 800 | 800 | ||||
| 额定冲击耐受电压Uimp(kV) | 8 | 800 8 | 8 | 8 | |||||
| 额定工作电流In(A) | 16A、20A、25A、 32A、40A、50A、 63A、80A、100A、 | 100A、125A、140A、 160A、180A、200A、 | 225A、250A、 315A、 | 400A、500A、 630A、700A、 800A | |||||
| 额定剩余动作电流I△n(mA) | 125A 30、50、75、100、 150、200、300、 | 225A、250A 30、50、75、100、 150、200、300、 | 350A、400A 50、75、 50、75、100、 100、、150、 200、300、 | ||||||
| 分断能力级别 | 400、500 L | 400、500 L | 200、300、 | 400、500、1000 L M | 500、1000 / | ||||
| 额定极限短路分断能力 Icu (kA) | AC400V | 35 | M 50 | 35 | M 50 | 50 | 65 | 65 | |
| 额定运行短路分断能力 | AC400V | 22 | 35 | 22 | 35 | 35 | 42 | ||
| Ics (kA) | 42 | ||||||||
| 隔离功能 | 2P、3P、4P有 | 2P、3P、4P有 | 3P、4P有 | 3P、4P有 | |||||
| 使用类别 | A类 | A类 | A类 | A类 | |||||
| 机械 | 40000 | 40000 | 20000 | 20000 | |||||
| 使用寿命 | 电气 | 8000 | 8000 | 7500 | 7500 | ||||
| 飞弧距离(mm) ≤50 | ≤50 | ≤100 | ≤100 | ||||||
| 手柄直接操作 | ■(标配) | 附件信息 ■(标配) | ■(标配) | ||||||
| 加长旋转手柄 | 口(可选配) | (可选配) | 口(可选配) | ■(标配) (可选配) | |||||
| 电动操作机构 | (可选配) | (可选配) | (可选配) | (可选配) | |||||
| 分励脱扣器 | 口(可选配) | 口(可选配) | (可选配) | (可选配) | |||||
| 辅助触头 报警触头 | (可选配) | 口 (可选配) | (可选配) | (可选配) | |||||
| 固定式板前 | 口(可选配) | 口(可选配) | (可选配) ■(标配) | (可选配) ■(标配) | |||||
| 固定式板后 | ■(标配) | ■(标配) 口(可选配) | 口(可选配) | (可选配) | |||||
| 插入式板前(4P产品不能选配) | 口(可选配) 口(可选配) | (可选配) | (可选配) | (可选配) | |||||
| 插入式板后 | (可选配) | (可选配) | (可选配) | (可选配) | |||||
| 过渡排 | |||||||||
TGM1L系列剩余电流保护断路器
| 序号 | 试验电流名称 | I/In | 约定时间 | 起始状态 |
| 1 | 约定不脱扣电流 | 1. 05 | ≥2h(In>63A),≥1h(In≤63A) | 冷态 |
| 2 | 约定脱扣电流 | 1. 3 | 63A), | 紧接着序号1试验后开始 |
| 序号 | 试验电流名称 | I/In | 约定时间 | 起始状态 |
| 1 | 约定不脱扣电流 | 1. 0 | ≥2h | 冷态 |
| 2 | 约定脱扣电流 | 1. 2 | 紧接着序号1试验后开始 |
3.4配电用断路器的瞬时动作特性整定为 101n±20% 0电动机保护用断路器的瞬时动作特性整定为12ln ±20% 。注:40A以下瞬时动作特性按40A整定。
4正常工作条件和安装条件
4.1周围空气温度:周围空气温度上限为 +40°C ,周围空气温度下限为 -59 ,周围空气温度24h 的平均值不超过 +359 0
4.2海拔:安装地点的海拔不超过 2000\mathsf{m} 。
4.3污染等级:3级。
4.4安装类别:Il。
4.5大气条件:大气相对湿度在周围空气温度为 +40°\mathsf{C} 时不超过 50% ;在较低温度下可以有较高的相对湿度;最湿月的月平均最大相对湿度为 90% ,同时该月的月平均最低湿度为 +259 ,并考虑到因温度变化发生在产品表面上的凝露。
4.6外磁场:断路器安装场所附近的磁场在任何方向不超过地磁场的5倍。
4.7安装在无冲击振动及无雨雪侵袭的地方,上接线端子接电源侧,下接线端子接负载侧,与各方向倾斜度不超过 5° 。
5断路器的剩余电流分断时间
5.1一般型断路器的动作特性
一般型断路器的动作特性见表6( \Delta n<=slant30m\Delta 的断路器应是非延时型)。
表6
| 剩余电流 | I△n | 21△n | 51△na) | 101△n(b) |
| 最大断开时间(s) | 0.2 | 0.15 | 0.04 | 0. 04 |
5.2延时型断路器的动作特性
延时型断路器的极限不驱动时间按2l△n规定,其动作时间见表7。
表7
| 极限不驱动 时间(s) | I△n时的最大 分断时间(s) | 2I△n时的极限 不驱动时间(s) | 最大分断时间 (s) | 5I△n时的最大 分断时间(s) | 101△n时的最大 分断时间(s) |
| 0. 1 | 0.3 | 0. 1 | 0.3 | 0.25 | 0.25 |
| 0. 2 | 0. 4 | 0. 2 | 0. 4 | 0.35 | 0.35 |
| 0.3 | 0.5 | 0.3 | 0.5 | 0. 45 | 0. 45 |
| 0. 4 | 0.6 | 0. 4 | 0.6 | 0.55 | 0.55 |
| 0.5 | 0.7 | 0.5 | 0.7 | 0.65 | 0.65 |
| 0.6 | 0.8 | 0.6 | 0.8 | 0. 75 | 0. 75 |
| 0.7 | 0. 9 | 0.7 | 0. 9 | 0.85 | 0.85 |
| 0.8 | 1 | 0.8 | 1 | 0.95 | 0.95 |
TGM1L系列剩余电流保护断路器
6 6断路器反时限保护特性曲线
TGM1L系列剩余电流保护断路器
TGM1L系列剩余电流保护断路器
8结构与工作原理
本系列断路器是电子式剩余电流动作断路器。主要部件有:主开关(包括过电流脱扣器),零序电流互感器,电子放大部件,漏电脱扣器,试验装置,全部零部件均装于一个塑料外壳内。
工作原理
当被保护电路中有漏电或人身触电时,当电流达到整定动作电流值,零序电流互感器二次绕组的输出信号就触发可控硅导通,并通过漏电脱扣器使断路器动作,切断电源,从而起到漏电和触电保护功能。工作原理图(见下图)
当被保护电路出现过载或短路时,热磁式脱扣器完成延时或瞬时脱扣动作使断路器动作,从而切断电源起到过载或短路保护功能。
TGM1L系列剩余电流保护断路器
9断路器的内部附件和外部附件
9.1断路器的内部附件
a、分励脱扣器及其接线图
| 额定控制电源电压Us | AC400V/380V、AC230/220V、DC220V、DC110V、DC24V | |
| 动作电压 | (0. 7-1. 1) Us | |
| 接线图 | 电源输入 A1O A2O | 注:K-分励脱扣器内部与线圈串联 的微动开关为常闭触头,当断路器 分闸后,该触头自行断开,合闸时 闭合。 |
| 壳架等级额定电流 | Inm≤250A | Inm≥400A | ||
| 约定发热电流Ith | 3A | 6A | ||
| 使用类别 | AC-15 | DC-13 | AC-15 | DC-13 |
| 工作电压 | AC380V/400V | DC220V/230V | AC380V/400V | DC220V/230V |
| 额定工作电流 | 0. 26A | 0. 14A | 3A | 0. 2A |
| 接线图 | F12 F12 F11 F11 F14 F14 断路器在"分"位置时的状态 断路器在”合”位置时的状态 | |||
c、报警触头及其接线图
| 约定发热电流Ith | 3A | |
| 额定工作电流Ie | 同辅助触头 | |
| 接线图 | B12 B11 B14 断路器在自由脱扣(报警)时的状态 | B12 B11 B14 断路器在"分”、”合"位置时的状态 |
TGM1L系列剩余电流保护断路器
| 输入电压 | AC230V、AC400V、DC24V | |
| P6O P5O | 说明:P5-P6:输入电源; P1-P2、P3-P4:触头容量 AC230V,0.5A。 | |
9.2断路器的外部附件
a、电动操作机构
| 型号 | A | B | H | H1 | a | b |
| TGM1L-125 | 116 | 90 | 77 | 12. 5 | 30 | 129 |
| TGM1L-250 | 116 | 90 | 77 | 15 | 35 | 126 |
| TGM1L-400 | 176 | 130 | 115 | 27 | 44 | 194 |
| TGM1L-800 | 176 | 130 | 115 | 31 | 70 | 243 |
TGM1L系列剩余电流保护断路器
b、手动操作机构安装尺寸
转动手柄安装尺寸
| 型号 | TGM1L-125 | TGM1L-250 | TGM1L-400 | TGM1L-800 |
| 安装尺寸(H) | 61mm | 57mm | 86. 5mm | 87mm |
10外形及安装尺寸
10.1断路器板前接线的外形及安装尺寸
TGM1L系列剩余电流保护断路器
| 型号 | 板前接线 | |||||||||||||||||||||
| H | 外 形 尺 寸 (mm) | 安装尺寸 | ||||||||||||||||||||
| 极 数 | W | L | W1 | L1 | L2 | L3 | H1 | H2 | H3 | H4 | H5 | H6 E | F | D | G | M | A A1 | B | ||||
| TGM1L- 125L | 2P | 62 | 151 | 73.5 | 30 | 256 | 106 | 96 | 95 | 25 8 | 10 | 3 | 30 | 50 | 23 | 50 | 18 | M8 | 129 | 4. 5 | ||
| 3P | 92 | 151 | 75 | 30 | 256 | 106 | 96 | 95 | 27 | 7 | 10 | 3 | 33 | 50 23 | 50 | 18 | M8 | 30 | - | 129 | 4. 5 | |
| 4P | 122 | 151 | 73.5 | 31 | 256 | 106 | 96 | 95 | 25 | 7 | 10 | 3 | 30 | 50 | 23 | 50 | 18 | M8 30 | 30 | 129 | 4.5 | |
| TGMIL- 125M | 151 | 92 | 30 | 256 | 106 | 96 | 111 | 29 8 | 10 | 3 | 25 | 50 | 23 | 50 | 18 | M8 | 一 | 129 | 4.5 | |||
| 2P 3P | 62 92 | 151 | 92 | 30 | 256 | 106 | 96 | 111 | 29 | 7 | 10 | 3 | 25 | 50 23 | 50 | 18 M8 | 30 | - | 129 | 4.5 | ||
| 4P | 122 | 151 | 92 | 30 | 256106 | 96 | 111 | 29 | 7 | 10 3 | 25 | 50 23 | 50 | 18 | M8 | 30 | 30 | 129 | 4. 5 | |||
| TGMIL- 250L | 2P | 78 | 165 | 75 | 35 | 300110 | 96 | 95 | 24.5 7 | 6 | 3 | 44 50 | 23 | 52 | 23 | M8 | 126 | 4.5 | ||||
| 3P | 107 | 165 | 75 | 35 | 300 | 110 | 96 | 95 | 26 | 7 | 6 | 3 | 44 | 50 23 | 52 | 23 | M8 | 35 | 126 | 4. 5 | ||
| 4P | 142 | 165 | 75 | 35 | 300 | 110 | 96 | 95 | 24.5 7 | 6 | 3 | 44 | 50 23 | 52 | 23 | M8 | 35 | 35 | 126 | 4.5 | ||
| TGM1L- 250M | 2P | 78 | 165 | 90 | 35 | 300 | 110 | 96 | 110|21.5 | 7 | 6 3 | 60 | 50 | 23 | 52 | 23 | M8 | 126 | 4.5 | |||
| 3P | 107 | 165 | 90 | 35 | 300 | 110 | 96 | 110 | 23 | 7 | 6 | 3 | 60 | 50 23 | 52 | 23 | M8 | 35 | 126 | 4. 5 | ||
| 4P | 142 | 165 | 90 | 35 | 300 | 110 | 96 | 110 21.5 | 7 | 6 | 3 | 60 | 50 | 23 | 52 | 23 | M8 | 35 | 35 | 126 | 4.5 | |
| TGMIL- 400L、M | 3P | 150257 | 107 | 48 | 470 | 193 | 175 | 152 | 38 | 8 10 | 3 | 47 | 91 | 56 | 82 | 32 | M10 | 44 | 194 | 7 | ||
| 4P | 198 | 257 | 107 | 48 | 470 | 193 | 175 | 152 | 38 | 8 | 10 3 | 47 91 | 56 | 82 | 32 | M10 | 44 | 50 | 194 | 7 | ||
| TGM1L -800 | 3P | 212 | 280 | 116 | 71 | 490 | 242 | 203 | 159 | 4 8 | 2 | 3 | 70 | 91 | 64 | 93 | 45 | M12 | 70 | 243 | 7 | |
| 4P | 283 | 280 | 116 | 71 | 490 |242 | 203 | 159 | 41 8 | 12 | 3 | 70 | 91 | 64 | 93 | 45 | M12 | 70 | 70 | 243 | 7 | ||
10.2插入式板后接线的外形及安装尺寸
| 型号 | 外形安装尺寸(mm) | |||||||||||
| A B1 | B2 | C1 | C2 | E | F | G | K | H | AM BM | 4-Φd | ||
| TGM1L-125 | 168 | 91 | 125 | 60 | 90 | 56 | 132 | 92 | 48 | 50 | M6 M8 | Φ6.5 |
| TGM1L-250 | 186 | 107 | 145 | 70 | 105 | 54 | 145 | 94 | 56 | 50 M6 | M8 | Φ6.5 |
| TGM1L-400 | 280 | 149 | 200 | 60 | 108 | 129 | 224 | 170 | 65 60 | M8 | M12 | Φ8.5 |
| TGM1L-800 | 305 | 210 | 280 | 90 | 162 | 143 | 242 | 181 | 72 | 87 M10 | M14 | Φ11 |
TGM1L系列剩余电流保护断路器
11选用原则
a)选择断路器的额定剩余动作电流值时,应充分考虑到被保护线路和设备可能发生的正常泄漏电流值,必要时可通过实际测量取得被保护线路或设备的泄漏电流值。
b)选择断路器的额定剩余不动作电流,应不小于电气线路和设备的正常泄漏电流的最大值的2倍。
c)手持式的电动工具、移动电器、家用电器、插座、建筑工地用电器(额定电流不小于100A)等设备接地有困难的应优先选用额定剩余动作电流为30mA或以下的断路器。
d)单台设备可选用额定剩余动作电流为30mA或以下的断路器。多台设备(多支点)的总保护应选用额定剩余动作电流为30mA或以上的断路器。
e)安装在潮湿场所的电气设备应选用额定剩余动作电流为30mA或以下的断路器。
12订货须知
客户在订货时必须说明:
a)断路器的型号及名称。
b)断路器过电流脱扣器的额定电流。
c)断路器的额定剩余动作电流。
d)断路器的分断时间。
e)保护种类、极数、及数量。
f)断路器内部附件和外部附件的额定工作电压值。
注:订货时请注明N极保护类型,在未注明保护类型的情况下,提供的产品L型均为A型,M型均为B型。
例:订购TGM1L-125,额定电流125A,额定剩余动作电流100/300/500mA(三档可调),非延时0.2S,分断能力为标准型,四极,配电保护用,带分励脱扣器(AC220V),N极保护类型为A型,100台。
应写成:TGM1L-125L/3N310A125A100/300/500mA0.2sAC220V100台。
13快速选型
例:TGM1L-125MP/43002Bll80A100/300/500mA0.2sAC220V。
表示TGM1L-125型电动机保护用具有剩余电流保护的断路器,壳架等级额定电流为125A,额定电流80A,分断能力为较高型,四极,B型,额定剩余动作电流为100/300/500mA三档可调,分断时间 {<=slant}0.2{\mathsf{s}} ,热磁式脱扣器,带报警不跳闸模块,电动机操作机构(AC220V)。
TGM1L系列具有剩余电流保护的断路器
DZ20L系列剩余电流保护断路器
1产品概述
DZ20L系列剩余电流保护断路器(以下简称断路器),主要适用于交流 50H z 额定电压为380V,额定电流至600A的电路中,作为人身触电或者设备漏电保护之用;也可用来防止因设备绝缘损坏,产生接地故障电流而引起的火灾危险;同时还可以用来分配电能和线路及电源设备的过载和短路保护,亦可以用作线路的不频繁转换之用。
本系列派生的透明外壳剩余电流保护断路器,盖子采用新型、耐高温、高强度聚碳酸酯材料制造而成,可直观判断触头的通断。
符合GB/T14048.2标准。
2产品命名规则
| 电流脱扣器型式 | 不带附件 | 报警触头 | 分励脱扣器 | 辅助触头 | 欠电压脱扣器 |
| 瞬时脱扣器 | 200 | 208 | 210 | 220 | 230 |
| 热磁式脱扣器 | 300 | 308 | 310 | 320 | 330 |
3产品参数
| 基本参数 | |||||
| 壳架等级额定电流 | 160 | 250 | 400 | 600 | |
| 极数 | 3P+N、4P | 3P+N、4P | 3P+N、4P | 3P+N、4P | |
| 频率(Hz) | 50 | 50 | 50 | 50 | |
| 额定工作电压Ue(V) | 380 | 380 | 380 | 380 | |
| 额定绝缘电压Ui(V) | 690 | 690 | 690 | 690 | |
| 额定冲击耐受电压Uimp(kV) | 6 | 6 | 6 | 6 | |
| 额定工作电流In(A) | 50A、63A、 80A、100A、 125A、140A、 160A | 125A、140A、 160A、180A、 200A、225A、 250A | 200A、250A、 315A、350A、 400A | 400A、500A、600A 50、75、100、 | |
| 额定剩余动作电流I△n(mA) 额定极限短路分断能力 | 30、50、75、90、100、150、200、250、270、300、 400、500 | 150、200、250、 300、400、500 | |||
| Icu (kA) 额定运行短路分断能力 | AC380V | 12 | 15 | 20 | 20 |
| Ics (kA) | AC380V | 8 A类 | 10 | 14 | 14 |
| 使用类别 | A类 | A类 | A类 | ||
| 飞弧距离(mm) | ≤60 | ≤60 | 八8 | ≤100 | |
| 使用寿命 | 机械 | 7000 | 7000 | 4000 | 4000 |
| 电气 | 1000 | 1000 | 1000 | 1000 | |
DZ20L系列剩余电流保护断路器
| 附件信息 | ||||
| 手柄直接操作 | ■(标配) | ■(标配) | ■(标配) | ■(标配) |
| 加长旋转手柄 | 口(可选配) | 口(可选配) | 口(可选配) | 口(可选配) |
| 电动操作机构 | 口(可选配) | 口(可选配) | 口(可选配) | 口(可选配) |
| 分励脱扣器 | 口(可选配) | 口(可选配) | (可选配) | 口(可选配) |
| 辅助触头 | 口(可选配) | 口(可选配) | 口(可选配) | 口(可选配) |
| 欠压脱扣器 | 口(可选配) | 口(可选配) | 口(可选配) | 口(可选配) |
| 报警触头 | 口(可选配) | 口(可选配) | 口(可选配) | 口(可选配) |
| 固定式板前 | ■(标配) | ■(标配) | ■(标配) | ■(标配) |
| 过渡排 | ■(标配) | ■(标配) | ■(标配) | ■(标配) |
| 相间隔板 | ■(标配) | ■ (标配) | ■(标配) | ■ (标配) |
3.2剩余电流保护断路器的最大分断时间
| 剩余电流 | I△ n | 2I △ n | 5I △ n | 10I △ n |
| 分断时间(s) | 0. 1 | 0. 1 | 0. 04 | 0. 04 |
| 壳架等级额定 电流Inm(A) | 每小时操作循环次数 | 操作循环次数 | ||
| 通电 | 不通电 | 总次数 | ||
| 160、250 | 120 | 1000 | 7000 | 8000 |
| 400、600 | 60 | 1000 | 4000 | 5000 |
| 延时时间(s) | I△n时的最大 分断时间(s) | 21△n时 | 51△n时的最大 分断时间(s) | 101△n时的最大 分断时间(s) | |
| 极限不驱动时间(s) | 最大分断时间(s) | ||||
| 0.1 | 0.3 | 0.1 | 0.3 | 0. 25 | 0.25 |
| 0.2 | 0. 4 | 0.2 | 0. 4 | 0.35 | 0.35 |
| 0.3 | 0.5 | 0.3 | 0.5 | 0. 45 | 0. 45 |
3.3剩余动作电流保护特性
3.3.1在正常的工作条件下,剩余电流保护断路器的剩余动作电流小于或等于额定剩余动作电流,并大于额定剩余不动作电流。
3.3.2剩余电流保护断路器用主电源作为辅助电源,其要求为剩余电流保护断路器在0.85\~1.1Ue之间正常运行。
3.5剩余电流保护断路器的过电流脱扣器保护特性
| 周围空气温度 | 试验电流/ 额定电流 | 约定时间h | 起始状态 | |
| In≤63 | In>63A | |||
| +40℃ | 1. 05 | ≥1 | ≥2 | 冷态 |
| 1. 30 | 热态 | |||
| 任何合适温度 | 10. 00 | ≤0.2s | 冷态 | |
DZ20L系列剩余电流保护断路器
| 类别 | 额定工作电压(V) | |||
| AC | DC | |||
| 脱扣器 | 分励脱扣器 | Us | 220、380 | 24 |
| 欠电压脱扣器 | Ue | 220、380 | 二 | |
装有欠压脱扣器的断路器,只有对欠电压脱扣器通以其额定电压的情况下,断路器才能合闸操作,否则将有可能损坏断路器。
3.7辅助触头和报警触头的主要参数
| 约定发热电流 Ith(A) | 额定绝缘电压 Ui (v) | 额定工作电流Ie(A) | 适用壳架等级 额定电流 | |
| AC380V | DC220V | |||
| 1 | 380 | 0.3 | 0. 15 | 作报警器触头用 |
| 3 | 380 | 0. 26 | 0. 14 | 250A及以下 |
| 6 | 380 | 3 | 0.2 | 400A及以上 |
断路器正常合分时,报警触头不动作,只有在脱扣(或故障跳闸)后报警,触头才改变原始位置,即常开变闭合、常闭变打开。待断路器再扣后,报警触头恢复原始状态。
4正常工作条件及安装条件
4.1周围空气温度
4.1.1周围空气温度上限为 +40°C 0
4.1.2周围空气温度下限为 -59 。
4.1.3周围空气温度24h的平均值不超过 \mathtt{+359} 0
4.2海拔:安装地点的海拔不超过 2000\mathsf{m} 。
4.3污染等级:3级。
4.4安装类别:川类。
4.5大气条件:大气相对湿度在周围空气温度为 +40°\mathsf{C} 时不超过 50% ;在较低温度下可以有较高的相对湿度;最湿月的月平均最大相对湿度为 90% ,同时该月的月平均最低温度为 +259 ,并考虑到因温度变化发生在产品表面上的凝露。
4.6外磁场:漏电断路器安装场所附近的磁场在任何方向不超过地磁场的5倍。
4.7安装位置应垂直,各方向倾斜度不超过 5° 。
结构及工作原理
本系列断路器系电子式剩余电流保护断路器,主要由零序电流互感器、集成电路放大器、漏电脱扣器、试验装置及带有过载和短路保护的断路器组成,全部零部件均装在一个塑料外壳中。
当被保护电路或电源设备出现过载或短路时,主开关中的热磁式脱扣器完成延时或瞬时脱扣动作,从而切断电源起到过载或短路保护作用;当被保护电路中有漏电或人身触电时,只要漏电电流达到动作电流值,零序电流互感器的二次绕组就输出一个信号,并通过漏电线路板处理指令漏电脱扣器动作,从而切断电源起到漏电和触电保护作用。
DZ20L系列剩余电流保护断路器
6外形及安装尺寸
| 产品型号 | 极数 | 外形尺寸 | 安装尺寸 | |||||
| A | B | C | D | a | b | 安装孔中d | ||
| DZ20L-160 | 4或3N | 143 | 225 | 103.5 | 88.5 | 70 | 201 | Φ 4. 3 |
| DZ20L-160/G | 3N | 143 | 225 | 89.5 | 73 | 70 | 204 | Φ4.3 |
| DZ20L-250 | 4或3N | 144 | 276 | 139 | 109 | 70 | 240 | Φ5.3 |
| DZ20L-250/G | 3N | 144 | 276 | 97 | 80 | 70 | 240 | Φ5.3 |
| DZ20L-400 | 4或3N | 206 | 360 | 143 | 117 | 102 | 324 | Φ7 |
| DZ20L-600 | 4或3N | 206 | 360 | 143 | 117 | 102 | 324 | Φ7 |
7连接使用铜导线标准截面积
| 额定电流(A) | 50 | 63 | 80 | 100 | 125 | 140 | 160 | 1802200 | 250 | 3.5 | 400 |
| 导线截面积(mm²) | 10 | 16 | 25 | 35 | 50 | 70 | 95 | 120 | 185 | 240 |
| 额定电流 (A) | 电缆线 | 铜排 | ||
| 数量 | 截面积(mm²) | 数量 | 截面积(mm²) | |
| 500 | 2 | 150 | 2 | 30×5 |
8订货须知
a)用户订货时必须说明:产品名称、型号、规格、极数、脱扣方式及附件名称、额定电流、额定剩余动作电流、数量。
b)例如:订购DZ20L-160剩余电流保护断路器,四极,热磁式脱扣器,额定电流160A,额定剩余动作电流100mA,共20台。
c)应写为:DZ20L-160/4300、160A、100mA、20台。
DZ20L系列剩余电流保护断路器
DZ15LE系列剩余电流保护断路器
1产品概述
DZ15LE系列剩余电流保护断路器(以下简称断路器),适用于交流50Hz,额定电压为220V或380V,额定电流至100A的电路中,作剩余电流保护之用,也可用来防止因设备绝缘损坏,产生接地故障电流而引起的火灾危险。并可用来保护线路免受过载和短路等危害,以及用作线路不频繁转换之用。本系列派生的透明外壳剩余电流保护断路器,盖子采用新型、耐高温、高强度聚碳酸酯材料制作而成,可直观判断触头的通断状态,广泛用于建筑工地等临时用电场所。
符合标准:GB/T14048.2。
2产品命名规则
注:N极不安装过电流脱扣元件,且N极始终接通,不与其它三极一起合分。
3产品参数
3.1产品参数见表1
| 基本参数 | ||||
| 壳架等级额定电流 | 40 | 100 | ||
| 极数 | 2P、3P、3P+N | 2P、3P、3P+N | ||
| 频率(Hz) | 50 | |||
| 额定工作电压Ue(V) | 220/380 | |||
| 额定绝缘电压Ui(V) | 400 | |||
| 额定工作电流In(A) | 10/16/20/25/32/40 | 50/63/80/100 | ||
| 额定极限短路分断能力Icu(kA) | AC220V | 3 | 5 | |
| AC380V | 3 | 5 | ||
| AC220V | 1. 5 | 2.5 | ||
| 额定运行短路分断能力Ics(kA) | AC380V | 1. 5 | 2. 5 | |
| 隔离功能 | 无 | 无 | ||
| 使用类别 飞弧距离(mm) | A类 | A类 | ||
| ≤50 | ≤70 | |||
| 使用寿命 | 机械 | 8500 | 8500 | |
| 电气 | 1500 | 1500 | ||
DZ15LE系列剩余电流保护断路器
表2
| 剩余电流 | I△n | 21△n | 5I△na | 101△nb |
| 最大分断 时间(s) | 0.1 | 0.1 | 0. 04 | 0. 04 |
| a.对于I△n≤0.03A的剩余电流保护断路器,5I△n可用0.25A取代。 b.按注a采用0.25A时,则10I△n为0.5A。 | ||||
3.3断路器操作循环次数见表3
| Inm (A) | 操作循环次数 | 每小时操作 循环次数 | ||
| 有载 | 无载 | 总次数 | ||
| 40 | 1500 | 8500 | 10000 | 120次 |
| 100 | 1500 | 8500 | 10000 | 120次 |
3.4过电流脱扣器的保护特性
3.4.1配电保护用断路器过电流脱扣器的保护特性见表4
3.4.2电动机保护用断路器过电流脱扣器的保护特性见表5
| 周围空气温度 | 试验电流/额定电流 | 试验时间 | 起始状态 | |
| In>63A | In≤63A | |||
| +30±2℃ | 1. 05 | 2h内不脱扣 | 1h内不脱扣 | 冷态开始 |
| 1. 30 | 2h内脱扣 | 1h内脱扣 | 热态开始 | |
| 周围空气温度 | 试验电流/额定电流 | 试验时间 | 起始状态 |
| +20±2℃ | 1. 05 | 2h内不脱扣 | 冷态开始 |
| 1. 20 | 2h内脱扣 | 热态开始 | |
| -5±2℃ | 1. 05 | 2h内不脱扣 | 冷态开始 |
| 1. 30 | 2h内脱扣 | 热态开始 | |
| +40±2°℃ | 1. 00 | 2h内不脱扣 | 冷态开始 |
| 1. 20 | 2h内脱扣 | 热态开始 |
3.4.3 瞬时过电流脱扣器电流整定值
配电用断路器瞬时过电流脱扣器电流整定值为 101n±20% 电动机保护用断路器瞬时过电流脱扣器电流整定值为12ln ±20% 8
DZ15LE系列剩余电流保护断路器
4正常工作条件及安装条件
4.1安装地点的海拔不超过 2000\mathsf{m} 。
4.2周围空气温度a.周围空气温度上限不超过 +40°C ,下限不低于- -59 。b.周围空气温度24h的平均值不超过 +359 0
4.3大气条件大气的相对湿度,在周围最高温度为 +40°\mathsf{C} 时不超过 50% ,在较低温度下可以有较高的相对湿度,月平均最大相对湿度为 90% ,同时,该月的平均最低温度为 +259 ,并考虑到因温度变化发生在产品表面上的凝露。
4.4安装类别为IⅢI。
4.5安装条件安装在无冲击振动及无雨雪侵袭的地方,上接线端子接电源侧,下接线端子接负载侧,与垂直面的倾斜度不超过5°。
4.6污染等级为3级。
4.7断路器安装场所附近的外磁场在任何方向不超过地磁场的5倍。
结构与工作原理
本系列断路器系电子式剩余电流保护断路器,主要由零序电流互感器、电子控制漏电脱扣器、电子放大部件、试验装置及带有过载和短路保护的断路器组成。
工作原理:当被保护电路中有漏电或人身触电时,当漏电流达到整定动作电流值,零序电流互感器的二次绕组就输出一个信号,触发可控硅导通,并通过漏电脱扣器使断路器动作,从而切断电源起到漏电和触电保护功能。工作原理图见图1。
当被保护电路中出现过载或短路时,液压式脱扣器完成延时或瞬时脱扣动作而使剩余电流保护断路器动作,从而切断电源起到过载或短路保护作用。
DZ15LE系列剩余电流保护断路器
外形及安装尺寸
| 壳架等级 额定电流(A) | 极 数 | 外形尺寸(mm) | |||
| A | B | C | D | ||
| 40 | 2 | 53 | 213 | 85 | 73.5 |
| 3 | 78 | 221 | 88 | 73.5 | |
| 3N | 103 | 221 | 88 | 73.5 | |
| 100 | 2 | 66 | 230 | 95 | 80 |
| 3 | 96 | 251 | 95 | 80 | |
| 3N | 126 | 251 | 95 | 80 | |
| 壳架等级 额定电流(A) | 极 数 | 安装尺寸(mm) | ||
| a | b | 安装孔中d | ||
| 40 | 2 | / | 180 | Φ5 |
| 3 | 25 | 180 | Φ5 | |
| 3N | 50 | 180 | Φ5 | |
| 100 | 2 | / | 188 | Φ5 |
| 3 | 30 | 210 | Φ5 | |
| 3N | 60 | 210 | Φ5 | |
连接使用铜导线标准截面积
| 额定电流(A) | 6 | 10 | 16 | 20 | 25 | 32 | 40 | 50 | 63 | 80 | 100 |
| 铜导线截面积(mm²) | 1. 0 | 1. 5 | 2.5 | 2.5 | 4 | 6 | 10 | 10 | 16 | 25 | 35 |
| 型号(接线螺钉规格) | DZ15LE-40(M5) | DZ15LE-100 (M6) |
| 扭矩 (N.m) | 3 | 4 |
8订货须知
8.1用户订货时必须说明:
8.1.1断路器的名称及型号。
8.1.2断路器额定电流。
8.1.3断路器额定剩余动作电流。
8.1.4保护种类、极数及数量。
8.2例:订购DZ15LE-40,40A,三极四线,电动机保护用,额定剩余动作电流50mA,数量80台。
订购代号为:DZ15LE-40/3N902,40A,50mA,80台。
TGM1EL系列剩余电流保护断路器
1产品概述
TGM1EL系列剩余电流保护断路器(以下简称“断路器”)适用于交流50Hz,额定电压400V,额定电流至630A的电路中作为线路不频繁转换和电动机的不频繁启动使用。
断路器具有长延时、短路短延时、短路瞬时、过压、欠压、断相、剩余电流保护及热模拟等保护功能。控制器采用高精度电子式脱扣器,电压、电流、剩余电流及故障信息实时显示,各参数可调、可查、可设置。
产品标配1路RS485标准接口,符合《低压塑壳断路器通讯规约一带漏电保护》(DL/T645)。
产品标配1路外控分闸无源接口,短接该端口可使断路器立即分闸。
断路器符合标准:
GB/T14048.1(IEC60947-1)《低压开关设备和控制设备第1部分:总则》GB/T14048.2(IEC60947-2)《低压开关设备和控制设备第2部分:断路器》
| 附件种类 | 代号 |
| 无 | 00 |
| 报警触头 | 08 |
| 辅助触头 | 20 |
| 组辅助触头+报警触头 | 28 |
| 两组辅助触头 | 60 |
| 代号 | 说明 |
| A | N极不安装过电流脱扣元件,且N极常通。 |
| B | N极不安装过电流脱扣元件,且N极与其他三极一起合分(N极先合后分)。 |
| C | N极安装过电流脱扣元件,且N极与其他三极一起合分(N极先合后分)。 |
| D | N极安装过电流脱扣元件,且N极常通。 |
TGM1EL系列剩余电流保护断路器
3正常工作及安装条件
3.1周围空气温度为 -590-4090
3.2 安装地点的海拨不超过 2000m
3.3安装地点的空气相对湿度在 +40°C 时不超过 50% ,在较低的温度下可以允许有较高的相对湿度,例如在 +2090 时可以达到 90% ,对由于温度变化偶尔产生的凝露应采取防护措施;
3.4污染等级为3级;
3.5主电路的安装类别为Ⅲ,不接至主电路的辅助电路和控制电路的安装类别为;
3.6断路器应安装在无爆炸危险和无导电尘埃、无足以腐蚀金属和破坏绝缘的地方;
3.7断路器应安装在没有雨雪侵袭的地方;
3.8安装场所的外磁场在任何方向不超过地磁场的5倍。
4产品参数
| 壳架等级额定电流(A) | 250 | 400 | 630 | |||
| 额定电流规格Ir(A) | 100~250可调 | 160~400可调 | 250~630可调 | |||
| 级差1A | ||||||
| 额定工作电压Ue(V) | AC400 | |||||
| 频率(Hz) | 50 | |||||
| 额定绝缘电压Ui(V) | 1000 | |||||
| 额定冲击耐受电压Uimp(kV) | 8 | |||||
| 分断能力级别 | M | H | M | H | M | H |
| Icu (kA) | 50 | 85 | 50 | 85 | 50 | 85 |
| Ics (kA) | 50 | 50 | 50 | 50 | 50 | 50 |
| 极数 | 3P+N、4P | |||||
| 隔离功能 | 3P+N无,仅4P有 | |||||
| 使用类别 | B B | |||||
| 额定短时耐受电流Icw(kA)/1s | 10 | 5 | 8 | |||
| 飞弧距离(mm) | ≤50 | ≤100 | ≤100 | |||
| 短路短延时保护特性(Isd) | 短延时保护整定值:2Ir~12Ir可调,级差1,特性见表5 | |||||
| 短路瞬时保护特性(Ii) | 瞬时保护整定值:4Ir~14Ir可调,级差1,特性见表6 | |||||
| 过压保护特性 | 电压动作值:相电压为253V~286V(线电压时为437V~494V) 可调,级差1V,可关闭 动作延时时间:1s-30s可调,级差1s | |||||
| 欠压保护特性 | 电压动作值:相电压为154V~187V(线电压时为266V~323V)可调, 级差1V,可关闭 动作延时时间:1s-30s可调,级差1s | |||||
| 断相保护特性 | 断路器进线端除N极之外任意一相电压断线,断路器立即跳闸,动作时间 ≤0.5s 50/100/200/300/500/ | |||||
| 剩余电流保护特性I△n(mA) | 30/50/100/200/300/500/ 50/100/200/300/500/ 800/1000mA可调 800/1000mA可调 | |||||
| 极限不驱动时间△t(s) | 0.06/0.1/0.2/0.3/0.4/0.5/0.6/0.7/0.8/0.9/1s 可选 | |||||
| 1I△n时最大分断时间(s) | 非延时型:0.3s,延时型:0.5/0.8/1/1.2/1.4/1.6/1.7/1.8/1.9/2/2s可 调 | |||||
| 额定剩余不动作电流值I△no | 50%I △ n | |||||
| 额定剩余短路分断能力I△m | 25%Icu | |||||
| 通讯功能(可选配) | 1路RS485接口 通信协议:《低压塑壳断路器通信规约一带漏电保护》(DL/T645) | |||||
| 远程分闸端口 | 通信波特率:2400、4800、9600、19200、38400五档可调 标配远程分闸控制端口(无源端口,短接即分闸) | |||||
TGM1EL系列剩余电流保护断路器
5保护特性说明
5.1 长延时动作特性
5.1.1配电长延时动作特性
| 动作特性 | 动作时间 | ||||||||
| 1. 05 Ir | 2小时内不动作 | ||||||||
| 1.3 Ir | 1小时内动作 | ||||||||
| 2 Ir | 壳架等级 | 400/630 | |||||||
| 整定时间tr(s) | 12 | 250 60 | 80 | 100 | 12 | 60 | 100 | 150 | |
5.1.2电动机保护型长延时动作特性
| 动作特性 | 动作时间 | ||||||||
| 1. 05 Ir | 2小时内不动作 | ||||||||
| 1. 2 Ir | 1小时内动作 | ||||||||
| 1. 5 Ir | 壳架等级 | 250 | 400/630 | ||||||
| 动作时间 (s) | 21.3 | 107 | 142 | 178 | 21.3 | 107 | 178 | 267 | |
| 2 Ir | 动作时间 (s) | 12 | 60 | 80 | 100 | 12 | 60 | 100 | 150 |
| 7.2 Ir | 动作时间 (s) | 0.93 | 4.63 | 6.17 | 7.72 | 0.93 | 4.63 | 7.72 | 11.6 |
| 脱扣级别 | 10A | 10 | 20 | / | 10 | 20 | 30 | ||
5.2短路短延时动作特性
| 电流设定值 | 动作特性 | 脱扣时间(tsd) | |||||
| Isd:2~2Tr可调 | Isd≤I | 定时限 | 时间(s) | 0.06 | 0.1 | 0.2 | 0.3 | |
| 允差(s) | ±0. 02 | ±0. 03 | ±0. 04 | ±0. 06 | |||
| 可返回时间 | 0. 14 | 0.21 | |||||
5.3短路瞬时动作特性
| 电流设定值 | 动作特性 | 脱扣时间(ti) |
| Ii:4~14Ir可调(可关闭) | I≤0.85Ii | 不动作 |
| I > 1. 15Ii |
TGM1EL系列剩余电流保护断路器
5.4配电保护型电流动作特性曲线
5.5剩余电流保护特性
5.5.1档位设置范围
| 参数 | 设定值 | 出厂整定值 |
| 剩余动作电流I△n(mA) | (30)、50、100、200、300、400、500、800、1000 | 500 |
5.5.2动作特性
| 参数 | 特性 | |||
| I △n (mA) | 30、50、100、200、300、500、800、1000。 | |||
| 额定不动作电流 | 0.5I △n | |||
| 额定动作电流 | 启动值>0.8I△n,返回值 | |||
| t (s) | 最大分断时间 (s) | |||
| I △ n | 2I △ n | 5I △ n | 10I △ n | |
| 0 | 0.3 | 0.15 | 0.04 | 0. 04 |
| 0.06 | 0.5 | 0.2 | 0.15 | 0.15 |
| 0.1 | 0.8 | 0.3 | 0.3 | 0.3 |
| 0.2 | 1 | 0. 4 | 0. 4 | 0. 4 |
| 0.3 | 1. 2 | 0.5 | 0.5 | 0.5 |
| 0.4 | 1. 4 | 0.8 | 0.8 | 0.8 |
| 0.5 | 1.6 | 1 | 1 | 1 |
| 0.6 | 1. 7 | 1. 2 | 1.1 | 1. 1 |
| 0.7 | 1. 8 | 1. 4 | 1. 2 | 1. 2 |
| 0.8 | 1. 9 | 1.6 | 1.3 | 1.3 |
| 0.9 | 2 | 1. 8 | 1. 4 | 1. 4 |
| 1 | 2 | 1. 8 | 1. 5 | 1. 5 |
TGM1EL系列剩余电流保护断路器
5.5.3过压保护功能
当线路相电压高于过压保护设定值时,断路器保护跳闸。当线路电压恢复到正常电压后,断路器可进行合闸投运。过压保护的设置值范围为253V\~286V,出厂设置为280V,用户可自行设定或关团保护。
5.5.4欠压保护功能
当线路相电压低于欠压保护设定值时,断路器保护跳闸。当线路电压恢复到正常电压后,断路器可进行合闸投运。欠压保护的设置值范围为154V\~187V,出厂设置为160V,用户可自行设定或关团保护。
5.5.5缺相保护功能
当线路电源端出现缺相时,断路器保护跳闸。当线路恢复到正常电压后,可进行合闸投运。
5.5.6联动保护功能
通过联动接口可与其他消防设备进行联动保护具体如下:
通过上盖上面的远程分闸控制端口,远控COM与远控OFF短接即可分闸(需在型号后备注:带分励线)。
6常规产品出厂参数默认整定值
| 序号 | 参数整定值 | |
| 1 | 过载长延时整定 | 电流(Ir):1In;保护功能状态:跳闸 |
| 2 | 短路短延时整定 | 延时时间(tr):60s |
| 电流(Isd):6Ir;保护功能状态:跳闸 | ||
| 短路瞬时整定 | 延时时间(tsd):0.3s | |
| 3 4 | 过压保护整定 | 电流(Ii):10Ir; 保护功能状态:跳闸 |
| 动作值: 280V 保护功能状态: 跳闸; 延时时间:3s | ||
| 5 | 欠压保护整定 | 动作值: 160V |
| 保护功能状态:告警; 延时时间:3s | ||
| 6 | 断相保护整定 | 保护功能状态:告警 |
| 7 | 剩余电流整定 | I △ n:500mA 保护功能状态:跳闸 |
| 8 | t: 0.06s | |
| 9 | 通信波特率(可选配) | 9600 |
| 10 | 通信地址(可选配) | 1 |
7产品技术资料
7.1不同温度下的降容系数
| 通电电流(A) | 环境温度 | |||||
| 40℃ | 50℃ | 55℃ | 60℃ | 65℃ | 70℃ | |
| 250 | 1In | 0. 9 In | 0.89 In | 0. 85 In | 0.81 In | 0.78 In |
| 400 | 1In | 0. 9 In | 0.89 In | 0.85 In | 0. 81 In | 0. 78 In |
| 630 | 1In | 0.9 In | 0.89 In | 0.85 In | 0.81 In | 0. 78 In |
TGM1EL系列剩余电流保护断路器
| 海拔(m) | 2000 | 2500 | 3000 | 4000 | 5000 |
| 工频耐压(V) | 3000 | 3000 | 2500 | 2000 | 1800 |
| 绝缘电压(V) | 1000 | 800 | 700 | 600 | 500 |
| 工作电流修正系数 | 1In | 1In | 0. 94In | 0.88In | 0. 85In |
7.3导线规格选用推荐值
| 额定电流In(A) | 125 | 160 | 250 | 320 | 400 | 500 | 630 |
| 导线截面积(mm²) | 50 | 70 | 120 | 185 | 240 | 2*150 | 2*185 |
7.4进出电缆/铜排扭紧力矩推荐值
| 额定电流 | 板前/板后接线力矩(N·m) |
| 250 | 8.8 ~ 12 |
| 400 | 18~ 22 |
| 630 | 28~32 |
8产品附件介绍
8.1辅助触头(左侧安装)
| 报警触头 | 约定发热电流Ith | 250:3A | 400/630:6A | ||
| 使用类别 | AC-15 | DC-13 | AC-15 | DC-13 | |
| 工作电压 | AC380V/415V | DC110V/250V | AC380V/415V | DC110V/250V | |
| 额定工作电流 | 0. 3A | 0. 15A | 1A | 0. 15A | |
| 接线图 F12 F12 F11 F11 F14 F14 断路器在“分”、“自由脱扣” | |||||
8.2报警触头
表16
| 辅助开关 | 约定发热电流Ith | 250:3A | 400/630:6A |
| 额定工作电流Ie | 同辅助触头 | 同辅助触头 | |
| 接线图 B12 B14 断路器在自由脱扣(报警) | B12 B11 B14 | B11 |
TGM1EL系列剩余电流保护断路器
8.3旋转手动操作机构
旋转手柄外形及安装尺寸图表如下:
| 型号规格 | TGM1EL-250 | TGM1EL-400 | TGM1EL-630 |
| 安装尺寸(H) | 57 | 87 | 89 |
| 手柄长度(L) | 95 | 125 | 125 |
8.4电动操作机构
8.4.1电动操作机构接线原理图
表18
TGM1EL系列剩余电流保护断路器
8.4.2电动操作机构外形及安装尺寸
| 型号 | A | B | H | H1 | a | b |
| TGM1EL-250 | 116 | 90 | 77 | 16. 5 | 35 | 126 |
| TGM1EL-400 | 174 | 130 | 117 | 35.5 | 44 | 193 |
| TGM1EL-630 | 174 | 130 | 115 | 31.5 | 114 | 233 |
9外形及安装尺寸
9.1断路器外形及安装尺寸
注:虚线部分为隔弧皮
表20
| 产品型号 | 外形尺寸 | 安装尺寸 | ||||||||||||||||
| L1 | L4 | W | W1 | W2 | H | H1 | H2 | H3 | H4 | H5 L2 | L3 | L5 | L6 | W3 | H6 | Φd | ||
| TGM1EL-250 | 165 | 300 | 142 | 35 | 26 | 118 | 85 | 21.521.5 | 17. 5 | 17.5 | 146 126 | 14 | 14 | 70 | 60 | 4. 5 | ||
| TGM1EL-400 | 257 | 469 | 198 | 48 | 33 | 153 | 98 | 39 | 38.5 | 34 | 35.5 | 224 | 194 | 14. 5 14. 5 | 94 | 67 | 8 | |
| TGM1EL-630 | 280 | 484 | 239 | 58 | 44 | 159 | 103 | 38 | 37 | 32 | 32 | 250 | 233 | 16 | 16 | 116 | 72 | 7 |
TGM1EL系列剩余电流保护断路器
9.2产品手柄位置及面板尺寸
| 型号 | A | B | C | D | E | F | H |
| TGM1EL-250 | 22 | 63 | 107 | 50.6 | 102 | 42 | 8 |
| TGM1EL-400 | 59 | 101.5 | 198 | 76 | 144 | 56 | 8 |
| TGM1EL-630 | 65 | 102 | 239 | 76.5 | 162. 5 | 82 | 8 |
9.3插入式板后外形及安装尺寸
| 型 号 | A | B1 | B2 | C1 | C2 | E | F | G | K | H | H1 | H2 | H3 | N | S | Q | B3 | B4 | AM | BM | Od |
| 250 | 186 | 107 | 145 | 70 | 105 | 54 | 145 | 94 | 46 | 50 | 33 | 37 | 20 | 196 | 84 | 56 | 117 | 155 | M6 | M8 | 6.5 |
| 400 | 280 | 149 | 200 | 60 | 108 | 129 | 224 | 170 | 55 | 60 | 38 | 46 | 24 | 290 | 160 | 65 | 159 | 210 | M8 | M12 | 8.5 |
TGM1EL系列剩余电流保护断路器
10.1面板指示灯说明
* “运行”指示灯(绿色):产品正常运行时闪烁;
* “预警”指示灯(黄色):1、当电流 > 过载电流整定值 \vert r^{\star} 过载预报警整定系数(固定0.9)时预警灯闪烁, <=slant0.95^{\star} 过载电流整定值 \vert r^{\star} 过载预报警整定系数(固定0.9)时预警灯不亮。2、剩余电流预警开启时,当剩余电流值 > 剩余电流档位值 (\mathsf{m}\mathsf{A})^{\star} 剩余电流预警整定系数(默认60% )并持续超过剩余电流预警延时时间(默认60s)时预警灯闪烁,当剩余电流值<[剩余电流档位值 (\mathsf{m A})^{\star} 剩余电流预警整定系数(默认 60% )-5mA]时预警灯不亮。
* “故障”指示灯(红色):告警功能打开且有电压或电流故障发生时该灯闪烁;跳闸功能打开时因电压或电流故障导致产品跳闸后该灯常亮;正常运行时该灯熄灭。
注:界面可整定剩余电流预警的“开启”或“关闭”,默认关闭
10.2外控端口说明
* 远控分闸端口:无源接口,当接通“远控COM”和“远控OFF”时断路器分闸;当接通“远控COM”和“远控ON"时自动合闸(需定制控制器、外控引线与电操配合使用);* 调试:该端口供出厂校准使用,用户切勿接入其它设备。
TGM1EL系列剩余电流保护断路器
11订货须知
用户订货时必须说明如下事项:
a)断路器的型号、名称、极数。
b)断路器的额定电流。
c)断路器的附件名称、规格、组合代号(分励脱扣器和欠电压脱扣器应注明工作电压值)。
d)用途:配电用(不注明按配电用交货)、电动机保护用(用2表示)。
e)数量。
例如:TGM1EL-250, 3P+N ,50kA分断能力,额定电流250A,带辅助触头,共20台。应写成:TGM1EL-250M/3N320250A20台。
断路器有分励线、通讯线、分励通讯线三种线型,断路器本身带有功能接口,配对应线表示对应功能需求。对断路器有特殊要求可与厂家协商决定。