DATA CENTER COOLING SOLUTIONS OVERVIEW 01
TICA WATER-COOLED CENTRIFUGAL CHILLER 02
TICA AIR-COOLED MAGNETIC BEARING CHILLER 07
TICA CHILLED WATER FAN WALL & CRAH 11
TICA DRY COOLER 16
TICA COOLANT DISTRIBUTION UNIT (CDU) 19
1 Data Center Product DATA CENTER COOLING SOLUTIONS
OVERVIEW
With the rapid growth of AI computing, high-performance computing (HPC), and high-density IT infrastructure,
traditional air cooling systems are facing increasing challenges in heat dissipation capacity and energy efficiency.
TICA introduces the Air-Liquid Unified Cooling Solution, an integrated cooling architecture that enables seamless collaboration
between air cooling and liquid cooling systems through a unified cooling source platform.
By integrating advanced chiller technology, intelligent cooling distribution, and flexible cooling terminals, TICA provides a scalable
solution that supports the entire evolution of data centers — from traditional air-cooled facilities to next-generation AI liquid-cooled
environments.
Air-Liquid Unified Cooling Architecture
One Cooling Platform for Both Air Cooling and Liquid Cooling Applications
Water-cooled Centrifugal Chiller
Air-Cooled Magnetic Bearing Chiller
Water Pump
Chilled Water Fan Wall & CRAH CDU Racks
Primary Cooling Source System Chilled Water Cooling System Direct‑to‑Chip Liquid Cooling System
TICA
2
WATER-COOLED DIRECT-DRIVE
CENTRIFUGAL CHILLER
TICA second-generation centrifugal chiller, TWCD series, employs a self-developed direct-drive, two-stage centrifugal
compressor and an ultra-efficient falling film evaporator. It offers stable and reliable performance, intelligent and user-friendly
control, and simple maintenance. It is suitable for a wide range of applications, including hotels, hospitals, sports venues, data
centers and industrial plants.
Innovative Highefficiency Technology
Multiple
Protection
Functions
Elegantly Simple
Design Intelligent
Control
Convenient
Installation and
Maintenance
TWC D 700 A E H C T
T = Standard;F = Customized
Application: C = Cooling-only;H = Heat Pump;R = Heat Recovery
U = Ultra Efficiency;P = Premium Efficiency;H = High Efficiency
Power Supply: A = 380V / 50Hz, B = 400V / 50Hz, C = 415V / 60Hz,
D = 380V / 60Hz, E = 460V / 60Hz,
Design Code
Cooling Capacity
Starting / Drive Mode: D = Direct-drive;
TICA Water-cooled Centrifugal Chiller
Nomenclature
3 Data Center Product Direct-Drive Two-Stage Compressor Falling Film Evaporator
Full CFD simulation and the upgraded 3-Dimensional flow
impeller make aerodynamic efficiency increased by 7% compared
to conventional 2-Dimensional impeller, reaching over 92%.
The compressor adopts a back-to-back impeller arrangement
with optimized force balancing. Compared to arranging on the
same side of the impellers, the axial force is reduced by 90% and
the aerodynamic efficiency loss is reduced by 5%.
■
■
The refrigerant distributor distributes liquid film uniformly and
enables 35% reduction of refrigerant charge.
Enhanced heat exchange tubes are utilized and tube
arrangement is upgraded optimized by CFD simulation,
improving heat exchange efficiency by 10% and achieving more
compact footprint.
Tube arrangement and structure optimization reduce water
pressure drop to as low as 40kPa, contributing to improvement
of efficiency of the entire HVAC system.
■
■
■
High-Efficiency High-Efficiency
TICA
4
High-precision Oil System Control
Real-time oil level monitoring guarantees
safe compressor operating across all load
conditions;
Refrigerant-cooled oil cooler with EXV+PID
algorithm maintains oil temperature stably;
Three-phase oil pump with adjustable
oil pressure ensures smooth and reliable
lubricant flow control
■
■
■
External Oil Sump Tank
Stable oil supply from external oil sump
tank; internal special filter maintains stable
oil level.
Internal high-efficiency oil separator – no
oil carryover risk.
Easy maintenance, inspection, and oil
replacement.
Leakage is easy to spot; risk is well
controlled.
■
■
■
■
Reliable Bearing Lubrication
Upon startup, the bearing quickly reaches
the minimum rotational speed to ensure
the establishment of a lubricating oil film.
The oil film in the sleeve bearing prevents
shaft current corrosion issues in variablefrequency drive applications.
The bidirectional oil-wedge hydrodynamic
bearing is resistant to reverse rotation
shutdown
■
■
■
Motor Cooling
The motor has 3 NTC thermistors for
real-time motor temperature monitoring,
ensuring protection against overheating;
An independent liquid receiver, located
at the bottom of the condenser, ensures
adequate refrigerant flow for motor
cooling.
Filter-drier ensures reliable motor cooling
protection.
■
■
■
Surge Protection
Dynamically adjustment of the minimum IGV
opening of each stage and compressor
speed keep maintaining operation within
the safe zone;
Under low-capacity conditions, the
discharge flow path is constricted by the
adjustable diffuser to increase discharge
velocity, thereby avoiding surge;
Real-time monitoring of temperature,
pressure and current pulsations enables
surge detection.
■
■
■
Self-developed VFD
Adaptive PWM technology with automatic
CPWM/DPWM switching achieves a
inverter efficiency of 97.5%;
The VFD features intelligent closedloop control and ultra-high frequency
operation with a carrier frequency up to
6000 Hz; Rapid restart time is less than
10s.
VFD cooling is provided via refrigerantcooled ethelyne glycol solution, enabling
full-rated operation at 8 kHz switching
frequency and 45° C ambient temperature
without derating.
■
■
Pre-Lubrication
Speed
MinSpeed
Actual
Speed
IGV
Position
Actual
IGV
Position
Shut down
Post-Lubrication
IGV
Surge
Protection
Surge
Protection
Speed IGV
IGV
Stays Still
Speed
IGV
Stays Still
Motor RPM
t
t3 t4
v(rpm)
v3
v2
v1
t0 t1 t2
Regular Shutdown
Intelligent Shutdown
Stability & Reliability
Reliable
5 Data Center Product Advanced Touch Screen
Futuristic UX;
15-inch industrial touch screen, with
1920X1080 full HD;
Aluminum alloy enclosure with IP65-rated
protection;
2160 hours operational log storage;
Mounted on a swing arm, allowing for 360°
positional adjustment.
■
■
■
■
■
Communication Protocol
Modbus RTU is standard;
ModbusTCP/IP, BACnet is optional
Able to interface with the BAS (building
automation system)
■
■
■
Comprehensive Functions
Tri-mode control (Local, Remote, BAS);
Three-tier password security;
A multi-dimensional dynamic display for
real-time monitoring;
Detailed fault diagnostics and history
logging;
Power-off memory for auto-resume after
outages;
Programmable start/stop timers
■
■
■
■
■
■
Intelligent interconnection Control
TICA
6
Model TWCD0650AESCT TWCD0700AESCT TWCD0750AESCT TWCD0800AESCT TWCD0850AESCT
Cooling Capacity
Ton 650 700 750 800 850
kW 2286 2462 2638 2814 2989
Power Input kW 233.9 246.9 265.2 284.4 309.3
COP
kW / ton 0.3598 0.3527 0.3536 0.3554 0.3638
kW / kW 9.774 9.971 9.945 9.895 9.666
NPLV-IP
kW / ton 0.1518 0.1499 0.1533 0.1630 0.1957
kW / kW 23.16 23.47 22.94 21.57 17.97
RLA A 318.3 335.6 360.1 385.6 418.9
MCA A 397.9 419.5 450.1 482.0 523.6
MOCP A 557.1 587.4 630.1 674.8 733.1
Starter Type - VFD
Power Supply - 460V / 60Hz
Refrigerant - R513A
Regulation Range - 20%-100% (10%-100% with HGBP)
Evaporator
Flow Pass - 2
Water-side
Pressure
Psig 150.0
MPa 1.0
Flow Rate gpm 1564 1684 1805 1925 2045
m3
/h 355.2 382.4 410.0 437.3 464.6
Pressure Drop
ft H2O 30.9 25.2 28.4 31.7 27.7
kPa 92.4 75.3 84.9 94.8 82.8
Water Pipe
Diameter
inch 10 10 10 10 10
DN 250 250 250 250 250
Condenser
Flow Pass - 2
Water-side
Pressure
Psig 150.0
MPa 1.0
Flow Rate gpm 1853 1992 2134 2278 2425
m3
/h 421.0 452.4 484.7 517.4 550.9
Pressure Drop
ft H2O 28.1 26.5 25.2 23.4 21.4
kPa 84.0 79.2 75.3 69.9 64.0
Water Pipe
Diameter
inch 10 10 10 10 10
DN 250 250 250 250 250
Size
Length
inch 145.3 145.3 145.3 145.3 145.3
mm 3691 3691 3691 3691 3691
Width
inch 75.8 75.8 75.8 78.4 78.4
mm 1925 1925 1925 1990 1990
Height
inch 91.9 91.9 91.9 91.9 91.9
mm 2333 2333 2333 2333 2333
Shipping Weight
lb 14153.7 14484.4 14594.6 15256.0 15630.8
kg 6421 6571 6621 6921 7091
Operating Weight
lb 15696.9 16181.9 16358.3 17196.0 17747.2
kg 7121 7341 7421 7801 8051
Technical Parameters
1. Data are based on: Evaporator LWT at 70 ℉ /21.1℃ , EWT at 80 ℉ /26.67℃;
Condenser EWT at 90 ℉ /32.2℃ , LWT at 100 ℉ /37.78℃
2. The standard power supply is 460 V/60 Hz, and voltage fluctuation within ±10% is allowed. For other power supply options, please
consult TICA.
3. The standard water chamber pressure is 150 Psig.
4. Shipping weight refers to the net weight of the unit, excluding base channel steel and packaging materials.
Notes:
7 Data Center Product The TAMFV series free-cooling air-cooled magnetic bearing chiller is designed and manufactured in compliance with industry
standards, delivering high energy efficiency, exceptional reliability, and rapid response capabilities.
Depending on ambient temperature and detected water temperature, the unit operates in three different modes. When the ambient
temperature falls below a set threshold—such as during transitional seasons or winter—it utilizes natural cooling from outdoor cold air
to partially or fully meet the cooling load on the user side, significantly enhancing energy savings and reducing emissions.
The chiller can be installed directly on rooftops or open outdoor areas without the need for chiller plant rooms.
Ideal for a wide range of applications including pharmaceuticals, electronics, chemicals, metallurgy, and commercial use, this chiller
offers substantial annual cooling cost savings.
TAMF V 220 2 A F C 5
Refrigerant: 5-R513A
Feature code: C-Cooling only; F-Free cooling
Power Supply: F-460V 3N ~60Hz
Design Code: A
Number of compressors: 2
Cooling Capacity: 180RT, 220RT, 250RT...
Operation mode: V-variable frequency
Name code: TICA Air-Cooled Magnetic Bearing Chiller
AIR-COOLED MAGNETIC BEARING CHILLER
Product Overview
Nomenclature
TICA
8
Widely used in the pharma-biotech industry, the microelectronics industry, metallurgy and commercial construction, it can greatly save
users' annual cooling costs.
The Operating Mode of Unit is as follows:
Compressor
Evaporator
FC Coil
Condenser
■ Summer: Machanical Mode
When the ambient temperature is high, the unit operates solely
in compressor-driven cooling mode with the free-cooling
function deactivated. This avoids unnecessary water pump power
consumption and prevents a loss of cooling capacity. As ambient
conditions change, the system primarily relies on compressor and
fan modulation to achieve an optimal energy-efficient operation
mode. This cooling mode is typically used during the summer.
Compressor
Evaporator
FC Coil
Condenser
■ Transition Seasons: Hybrid Mode
As the ambient temperature drops below a certain threshold relative
to the returning chilled water temperature, the system activates
hybrid cooling mode. In this mode, the returning chilled water is
first pre-cooled by passing through the free-cooling coil, which
handles a portion of the cooling load using the natural cold source.
The remaining load is then managed by the compressor. This hybrid
mode strikes an optimal balance between compressor and fan
power consumption, thereby minimizing the total power draw of the
unit.
Compressor
Evaporator
FC Coil
Condenser
■ Winter: Full Free-Cooling Mode
At sufficiently low ambient temperatures, the entire cooling load is
handled by the free-cooling coil. In this mode, the compressor is
completely shut down, and cooling capacity is regulated solely by
adjusting the fan speed. This operating mode is typically employed
during the winter.
Operating Mode
9 Data Center Product Technical specifications (without free‑cooling) TAMFV-AFC5 Model TAMFV180.2AFC5 TAMFV220.2AFC5 TAMFV250.2AFC5 TAMFV285.2AFC5 TAMFV370.3AFC5 TAMFV430.3AFC5 TAMFV510.4AFC5 TAMFV570.4AFC5
Cooling Mode
Data
Cooling
Capacity ton 180 220 250 285 370 430 510 570
Cooling
Capacity kW 630 772 879 1000 1300 1500 1800 2000
Power Input kW 143.1 172.4 197.1 207.7 295.3 319.5 408 430
EER
Btu/Wh 15.01 15.29 15.22 16.41 15.01 16.00 15.05 15.87
kW/kW 4.4 4.5 4.5 4.8 4.4 4.7 4.4 4.7
NPLV-IP
Btu/Wh 35.73 36.34 36.20 39.08 35.73 38.10 35.81 37.75
kW/kW 10 11 11 11 10 11 10 11
Electrical Data
RLA A 313 412 420 429 626 635 836 836
MCA A 347 457 465 474 671 680 881 881
MOCP A 400 600 600 600 800 800 1000 1000
Power Supply 460V / 60Hz
Refigerant
Type R513A
Refrigerant
Circuit Number 2 2 2 2 2 2 2 2 2
Compressor
Type Magnetic Bearing
Regulation
Range -
Starter Type VFD
Fan
Air Flow Rate
cfm 132430.1 158916.1 185402.1 211888.1 264860.1 291346.1 357561.2 357561.2
m3
/h 225000.1 270000.12 315000.16 360000.17 450000.21 495000.24 607500.3 607500.3
Quantity / 10 12 14 16 20 22 27 27
Power Input kW 19.5 23.4 27.3 31.2 39 42.9 48.6 48.6
Evaporator
Type Shell &Tube
Water Pipe
Diameter
inch 6 6 6 6 8 8 8 8
DN 150 150 150 150 200 200 200 200
Design
Pressure
Psig 150
MPa 1.0
Water Flow
Rate
gpm 328.0 401.5 457.5 520.4 676.7 780.6 936.5 1040.8
m3
/h 74.5 91.2 103.9 118.2 153.7 177.3 212.7 236.4
Water Pressure
Drop
ft H2O 29.7 30.7 33.4 32.4 22.5 21.6 23.2 22.4
kPa 88.8 91.8 99.8 96.9 67.4 64.6 69.3 66.9
Dimensions
Length
inch 252.4 299.2 346.1 392.9 469.9 516.7 443.9
mm 6410.0 7600.0 8790.0 9980.0 11935.0 13125.0 11275.0
Width
inch 89.4 136.6
mm 2270.00 3470.00
Height
inch 100.8
mm 2560.00
Weight
Shipping
Weight
lb 14753.3 16296.6 18060.3 20044.4 24233.2 25996.9 35362.2 35582.6
kg 6692 7392 8192 9092 10992 11792 16040 16140
Operating
Weight
lb 15458.8 17068.2 18898.0 20926.3 25225.3 27143.3 36618.8 36993.6
kg 7012 7742 8572 9492 11442 12312 16610 16780
Technical Parameters 1. Operating Conditions: Chilled water supply/return temperature 73.4°F (23℃) / 59°F (15℃), ambient dry-bulb temperature 95°F (35℃);
30% ethylene glycol used as fluid
2. The standard power supply is 460 V/60 Hz, and voltage fluctuation within ±10% is allowed. For other power supply options, please
consult TICA.
3. The standard water chamber pressure is 150 Psig.
4. Due to continuous product optimization, the above parameters are subject to change. Refer to the unit nameplate and physical
equipment for definitive data.
Notes: TICA
10
Technical specifications (with free‑cooling)
TAMFV-AFF5 Model TAMFV180.2AFF5 TAMFV220.2AFF5 TAMFV250.2AFF5 TAMFV285.2AFF5 TAMFV370.3AFF5 TAMFV430.3AFF5 TAMFV510.4AFF5 TAMFV570.4AFF5
Cooling Mode
Data
Cooling Capacity ton 180 220 250 285 370 430 510 570
Cooling Capacity kW 630 772 879 1000 1300 1500 1800 2000
Power Input kW 150.2 181 207 219.1 309.6 335.2 423.4 445.4
EER
Btu/Wh 14.30 14.57 14.50 15.56 14.33 15.25 14.50 15.32
kW/kW 4.2 4.3 4.3 4.6 4.2 4.5 4.3 4.5
NPLV-IP
Btu/Wh 34.04 34.62 34.47 37.04 34.08 36.32 34.50 36.45
kW/kW 10 10 10 11 10 11 10 11
Full Freecooling Ambient
Temperature
℉ 38.10 37.65 38.14 38.25 37.45 36.45 35.82 33.58
℃ 3.39 3.14 3.41 3.47 3.03 2.47 2.12 0.88
FC Coils Pressure Drop
ft H2O 14.7 15.1 14.4 14.4 15.4 16.7 7.7 9.4
kPa 44 45 43 43 46 50 23 28
Electrical Data
RLA A 313 412 420 429 626 635 836 836
MCA A 347 457 465 474 671 680 881 881
MOCP A 400 600 600 600 800 800 1000 1000
Power Supply 460V / 60Hz
Refigerant Type R513A
Refrigerant Circuit Number 2
Compressor
Type Magnetic Bearing
Regulation Range -
Starter Type VFD
Fan
Air Flow Rate
cfm 132430.1 158916.1 185402.1 211888.1 264860.1 291346.1 357561.2 357561.2
m3/h 224998.7 269998.4 314998.1 359997.9 449997.4 494997.1 607496.4 607496.4
Quantity / 10 12 14 16 20 22 27 27
Power Input kW 27 32.4 37.8 43.2 54 59.4 64.8 64.8
Evaporator
Type Shell &Tube
Water Pipe Diameter
inch 6 6 6 6 8 8 8 8
DN 150 150 150 150 200 200 200 200
Design Pressure Psig 150
MPa 1.0
Water Flow Rate gpm 328.0 401.5 457.5 520.4 676.7 780.6 936.5 1040.8
m3
/h 74.5 91.2 103.9 118.2 153.7 177.3 212.7 236.4
Water Pressure Drop
ft H2O 29.7 30.7 33.4 32.4 22.5 21.6 23.2 22.4
kPa 88.8 91.8 99.8 96.9 67.4 64.6 69.3 66.9
Dimensions
Length
inch 252.4 299.2 346.1 392.9 469.9 516.7 443.9
mm 6410 7600 8790 9980 11935 13125 11275
Width
inch 89.4 136.6
mm 2270 3470
Height
inch 100.8
mm 2560
Weight
Shipping Weight
lb 15727.8 17712.0 20137.0 23003.1 28735.1 31380.6 43960.2 44621.6
kg 7134 8034 9134 10434 13034 14234 19940 20240
Operating Weight
lb 17315.1 19585.9 22297.6 25428.1 31490.9 34511.2 47421.5 48237.2
kg 7854 8884 10114 11534 14284 15654 21510 21880
Technical Parameters
1. Operating Conditions: Chilled water supply/return temperature 73.4°F (23℃) / 59°F (15℃), ambient dry-bulb temperature 95°F (35℃);
30% ethylene glycol used as secondary coolant
2. The standard power supply is 460 V/60 Hz, and voltage fluctuation within ±10% is allowed. For other power supply options, please
consult TICA.
3. The standard water chamber pressure is 150 Psig.
4. The above NPLV values are provided based on operation in mechanical cooling mode
5. Due to continuous product optimization, the above parameters are subject to change. Refer to the unit nameplate and physical
equipment for definitive data.
Notes:
11 Data Center Product TICA CHILLED WATER FAN WALL & CRAH
Chilled water air conditioning is a type of end-point temperature control product. It is usually combined with chiller units,
water pumps, chilled water pipelines, etc. to form a refrigeration system, using a centralized cold source for cooling. It has the
characteristics of high cooling capacity and significant energy-saving effect.
Application scenarios:Mainly used in large data centers, medium data centers, cloud computing centers, switch rooms,
communication rooms, etc.
xxxx: Cooling Capacity in kW
FW: Far-End Fan Wall
TICA
T FW XXXX A C 2 L N T 1 L T A
A B C D···
C:Chilled Water
1:Single System;2:Dual Systems
L:Cooling Only;S: Cooling and Humidity Control
E: EPIV Valve; T: Electric Two-way Valve; S: Electric Threeway Valve
N: No Compressor
Name Composition Sequence Number Code Code Meaning
Brand 1 1 Alphabet TICA
Product 2-3 2 Alphabets FW: Far-End Fan Wall
Cooling Capacity 4-7 4 Numbers xxxx: Cooling Capacity in kW
Design Code 8 1 Alphabet A B C D···
System Type 9 1 Alphabet C:Chilled Water
Qty. of System 10 1 Number 1:Single System;2:Dual Systems
Function 11 1 Alphabet L:Cooling Only;S: Cooling and Humidity Control
System Form 12 1 Alphabet N: No Compressor
Valve Type 13 1 Alphabet E: EPIV Valve; T: Electric Two-way Valve; S: Electric Three-way Valve
Qty.of modules 14 1 Number 1 2 3···
Electrical Cabinet Access Side 15 1 Alphabet L: Left type; R: Right type; H: Return Air side; S: Supply Air side
Pipe Connection Side 16 1 Alphabet L: Left Side; R: Right Side; T: Top Connection; F: Bottom Connection (Reference:
Facing the supply air side)
Power Supply 17 1 Alphabet A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V 3N~60HZ;I:415V 3N~50HZ;L:
400V 3N~50HZ;P:480V 3N~60HZ
1 2 3···
L: Left type; R: Right type; H: Return Air side; S: Supply Air side
A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V
3N~60HZ;I:415V 3N~50HZ;L:400V 3N~50HZ;P:
480V 3N~60HZ
L: Left Side; R: Right Side; T: Top Connection; F: Bottom
Connection (Reference:Facing the supply air side)
TICA
12
xxxx: Cooling Capacity in kW
RAC:Room-Air-Conditioner
TICA
T RAC XXX A C 2 L U N T N L A
A B C D···
C:Chilled Water
1:Single System;2:Dual Systems
L:Cooling Only;S: Cooling and Humidity Control
N: No Compressor
U: Upflow; D: Downflow; N: Downflow with Lower Fan
Section; P: Downflow with front air discharge base module
Name Composition Sequence Number Code Code Meaning
Brand 1 1 Alphabet TICA
Product 2-4 3 Alphabets RAC:Room-Air-Conditioner
Cooling Capacity 5-7 3 Numbers xxxx: Cooling Capacity in kW
Design Code 8 1 Alphabet A B C D···
System Type 9 1 Alphabet C:Chilled Water
Qty. of System 10 1 Number 1:Single System;2:Dual Systems
Function 11 1 Alphabet L:Cooling Only;S: Cooling and Humidity Control
Air Supply Direction 12 1 Alphabet U: Upflow; D: Downflow; N: Downflow with Lower Fan Section; P: Downflow with
front air discharge base module
System Form 13 1 Alphabet N: No Compressor
Valve Type 14 1 Alphabet E: EPIV Valve; T: Electric Two-way Valve; S: Electric Three-way Valve
Outdoor Unit Type 15 1 Alphabet N: None
Pipe Connection Side 16 1 Alphabet L: Left Side; R: Right Side; S: Lower Left Side; E: Lower Right Side(Reference:
Facing the front door control panel)
Power Supply 17 1 Alphabet A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V 3N~60HZ;I:415V 3N~50HZ;L:
400V 3N~50HZ;P:480V 3N~60HZ
E: EPIV Valve; T: Electric Two-way Valve; S: Electric
Three-way Valve
N: None
A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V
3N~60HZ;I:415V 3N~50HZ;L:400V 3N~50HZ;P:
480V 3N~60HZ
L: Left Side; R: Right Side; S: Lower Left Side; E: Lower
Right Side(Reference:Facing the front door control panel)
Features and values
Energy efficient
The fan adopts EC backward-tilting centrifugal fan, which has a wide range of adaptations. It can automatically adjust the
rotational speed according to the load of the unit.
The unit uses copper tube hydrophilic aluminum fin heat exchanger, which has high heat density and higher heat exchange
efficiency.
Intelligent control
The intelligent controller is used for PID adjustment, the temperature control accuracy can reach ±1 ℃ , creating a more stable
operating environment for the equipment in the computer room.
RS485 communication interface is configured as standard.
Electric valves precisely regulate water flow to ensure a stable water supply, and optional EPIV or EV valves can be used to
directly and accurately regulate and monitor water flow.
Convenient maintenance
The control system and safety protection devices are installed in a separate space isolated from the airflow,allowing for front
maintenance.
Using a centralized cooling source for refrigeration, no additional outdoor units need to be installed. The cooling towers are
centrally placed, effectively saving installation space.
Chilled Water Precision Air-Conditioner
Environmental and reliable
The use of chilled water as a refrigerant is the most natural way of air conditioning, green, healthy and environmentally friendly.
Perfect automatic alarm and diagnosis function, all-round protection of the air conditioning unit, but also more effective
prevention of failure, prolong the service life of the air conditioning unit.
13 Data Center Product Water-cooled magnetic levitation chiller
Air-cooled magnetic levitation chiller
Air-cooled screw chiller
Cooling tower Dry cooler
Water-cooled chiller solution Air-cooled chiller solution
Data center chilled water system solution
The data center chilled water air conditioning system solution mainly consists of chilled water units, chilled water circulation pumps,
expansion water tanks, pipelines, and indoor terminal equipment(chilled water precision air-conditioner,chilled water fan wall).
The chilled water unit, under the action of the compressor, enables the refrigerant to circulate within the unit, where it exchanges heat with
water to produce low-temperature chilled water. The low-temperature chilled water then enters the indoor terminal equipment devices to
remove the indoor heat.
Chilled Water Fan Wall
Computer room layout
Features and values
The fan matrix layout enables a larger air supply volume, shortens the airflow path, ensures uniform air distribution, and reduces the
power consumption of the fans.
High inlet/outlet water temperature, high return air design, low power consumption of the cooling source, and extended utilization
time of natural cooling source
Installation does not require the use of raised floors, freeing up space in the server room. Combined with enclosed cold and hot
aisles, it is suitable for medium to high heat density scenarios.
Configure an EC rearward-tilting centrifugal fan. The fan speed will automatically adjust according to the load. It features low power
consumption, low noise and low vibration.
The operation is simple. It can set the fan speed based on temperature or pressure difference. It is also available with the option to
read real-time values for cooling capacity and air volume.
Easy maintenance. The windscreen is equipped with a maintenance passage, which is conveniently located on the side and allows
for the repair of all components.
System redundancy design ensures the ability to maintain cooling even when some components fail, thereby ensuring more reliable
operation of the unit and reducing operational risks.
TICA
14
Technical Parameters
Mode TRAC035AC TRAC050AC TRAC090AC TRAC135AC TRAC190AC TRAC230AC
Cooling capacity kW 35 50 90 135 190 230
Return/Supply AT ℃ 34/22 34/22 34/22 34/22 34/22 34/22
℉ 93.2/71.6 93.2/71.6 93.2/71.6 93.2/71.6 93.2/71.6 93.2/71.6
Inlet/Outlet WT ℃ 15/22 15/22 15/22 15/22 15/22 15/22
℉ 59/71.6 59/71.6 59/71.6 59/71.6 59/71.6 59/71.6
Media / Water Water Water Water Water Water
Power Supply / 460V/3Ph/60Hz
Input Power kW 1.7 2.3 4.8 7.2 10.5 13.2
Air flow m³/h 10000 12000 24000 36000 37500 50000
CFM 5886 7063 14126 21189 22072 29429
Qty. of Fans / 1 1 2 3 3 4
ESP Pa 150 150 150 150 150 150
Water pressure drop kPa ≤ 80 ≤ 80 ≤ 80 ≤ 80 ≤ 80 ≤ 80
psi ≤ 11.6 ≤ 11.6 ≤ 11.6 ≤ 11.6 ≤ 11.6 ≤ 11.6
Connection type / Flange Flange Flange Flange Flange Flange
Pipe diameters / DN32 DN50 DN50 DN65 DN50 DN65
Operating weight kg 300 350 680 1060 1300 1400
lb 661 772 1499 2337 2866 3086
Width(W) mm 1180 1250 1830 2730 3000 3300
in 46.5 49.2 72 107.5 118.1 129.9
Depth(D) mm 900 1000 1000 1000 1000 1000
in 35.4 39.4 39.4 39.4 39.4 39.4
Height(H) mm 2000 2100 2100 2100 2400 2400
in 78.7 82.7 82.7 82.7 94.5 94.5
Chilled Water Precision Air-Conditioner
1. The above unit dimensions do not include the dimensions of optional accessories such as air valves;
2. Different power supply systems can be adjusted according to customer requirements. For details, please consult the Tica technicians;
3. The unit capacity is strongly related to the operating conditions. The above data is only for reference. For other media (ethylene
glycol), other operating conditions or altitudes exceeding 1000m, please contact the Tica technicians.
Notes:
15 Data Center Product Technical Parameters
Mode TFW0155AC TFW0210AC TFW0350AC TFW0500AC
Cooling capacity kW 155 210 350 500
Return/Supply AT ℃ 34/22 34/22 34/22 34/22
℉ 93.2/71.6 93.2/71.6 93.2/71.6 93.2/71.6
Inlet/Outlet WT ℃ 15/22 15/22 15/22 15/22
℉ 59/71.6 59/71.6 59/71.6 59/71.6
Media / Water Water Water Water
Power Supply / 460V/3Ph/60Hz
Input Power kW 9.5 12.8 22.4 28.8
Air flow m³/h 44000 50000 75000 125000
CFM 25898 29429 44144 73572
Qty. of Fans / 4 4 8 12
ESP Pa 150 150 150 150
Water pressure drop kPa ≤ 80 ≤ 80 ≤ 80 ≤ 100
psi ≤ 11.6 ≤ 11.6 ≤ 11.6 ≤ 14.5
Connection type / Flange Flange Flange Flange
Pipe diameters / DN80 DN80 DN80 DN100
Operating weight kg 1500 1400 2100 4780
lb 3307 3086 4630 10538
Width(W) mm 2100 2200 4000 4000
in 82.7 86.6 157.5 157.5
Depth(D) mm 1600 1400 1900 4650
in 63 55.1 74.8 183.1
Height(H) mm 3400 2500 2540 4150
in 133.9 98.4 100 163.4
Chilled Water Fan Wall
1. The above unit dimensions do not include the dimensions of optional accessories such as air valves;
2. Different power supply systems can be adjusted according to customer requirements. For details, please consult the Tica technicians;
3. The unit capacity is strongly related to the operating conditions. The above data is only for reference. For other media (ethylene
glycol), other operating conditions or altitudes exceeding 1000m, please contact the Tica technicians.
Notes:
TICA
16
TICA DRY COOLER
The Dry Cooler fully utilizes outdoor ambient cooling to reduce heat within the data center or server room.
The Dry Cooler is installed outdoors, where ambient air enters the unit and exchanges heat with the cooling medium (water or
ethylene/ propylene glycol fluid). The cooled medium is then circulated back to the indoor terminal cooling equipment, where it
completes the heat exchange process on the indoor side.
Wet film and spray systems are available, which can reduce the effective inlet air temperature during high-temperature seasons,
thereby enhancing heat transfer capacity and improving overall energy efficiency to achieve energy savings.
Dry Coolers are widely used in regions with abundant natural cooling resources and offer significant economic advantages.
xxxx: Heat Exchange Capacity in kW
DR: Dry Cooler
TICA
T DR XXXX A E W S C A
A B C D···
E: EC Fan; A: AC Fan
W: With Wet Film; N: Without Wet Film
S: With Spray System; N: Without Spray System
A:380V 3N~50HZ;B:380V 3N~60HZ;F:
460V 3N~60HZ;I:415V 3N~50HZ;L:400V
3N~50HZ;P:480V 3N~60HZ
C: With Pump; N:Without Pump
Name Composition Sequence Number Code Code Meaning
Brand 1 1 Alphabet TICA
Product 2-3 2 Alphabets DR: Dry Cooler
Heat Exchange Capacity 4-7 4 Numbers xxxx: Heat Exchange Capacity in kW
Design Code 8 1 Alphabet A B C D···
Fan Type 9 1 Alphabet E: EC Fan; A: AC Fan
Wet Film 10 1 Number W: With Wet Film; N: Without Wet Film
Spray System 11 1 Alphabet S: With Spray System; N: Without Spray System
Pump 12 1 Alphabet C: With Pump; N:Without Pump
Power Supply 13 1 Alphabet A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V 3N~60HZ;I:
415V 3N~50HZ;L:400V 3N~50HZ;P:480V 3N~60HZ
17 Data Center Product High Efficiency
Utilizes natural cooling sources, combined with a multi-fan
forced convection design, delivering high heat exchange efficiency
and low unit energy consumption.
Integrates wet film and spray technologies; fan speed can be
reduced during high-temperature seasons to achieve energy savings. Easy Maintenance
Front-access maintenance design; pumps, valves, and the
electrical control panel are all serviceable from the front,
ensuring convenient access to all maintenance points.
Low Noise
High-efficiency EC fans with stepless speed regulation,
ensuring stable operation, high efficiency, and low noise.
Environmentally Friendly·
Optional wet film circulating water pre-cooling system significantly
reduces water onsumption compared to cooling towers, enabling
ultra-low WUE operation.
Compact Structure
Large “V”-shaped heat exchanger design provides sufficient
heat transfer surface area while optimizing installation
footprint.
Data Center Corrosive
Environment Power Plant
Data Center, Corrosive Environment, Power Plant, Bank, Museum.
Product Advantages
The Dry Cooler can be integrated with wet film and spray system. During operation, the unit prioritizes the use of outdoor ambient
cooling. When outdoor temperatures rise, the wet film and spray systems are activated to provide pre-cooling, ensuring cooling
capacity while reducing fan speed for energy-efficient operation.
Operating Mode
Free-cooling Mode
During winter or transitional seasons, when
outdoor temperatures are
low, the EC fans are activated to operate in
forced air-circulation mode, utilizes natural
cooling to exchange heat with the coils,
meeting the cooling requirements.
Wet Film Pre-cooling Mode
When outdoor temperatures are high, the
wet film evaporative pre-cooling is activated
and, together with forced air circulation for
convective heat transfer, fulfills the cooling
requirements.
Spray System Mode
When outdoor temperatures rise further, the
water pump is
activated to pre-cool the air using sprayed
water, combined with forced air circulation
for convective heat transfer, meeting the
cooling demand.
Applications
TICA
18
Model - TDR0350AENNNF TDR0450AENNNF TDR0550AENNNF TDR0650AENNNF TDR0800AENNNF TDR0950AENNNF TDR1050AENNNF TDR1200AENNNF
Power Supply - 460V/3Ph/60Hz
Ambient DB
˚F 95
℃ 35
Performance Parameters
Heat dissipation kW 340 472 586 680 812 946 1080 1214
EWT
˚F 116.6
℃ 47
LWT
˚F 105.8
℃ 41
Num of Fans - 6 8 10 12 14 16 18 20
Air flow
CFM 77647 103529 129412 155294 181176 207059 232941 258824
m³/h 132000 176000 220000 264000 308000 352000 396000 440000
Input Power kW 13.8 18.4 22.9 27.5 32.1 36.7 41.3 45.9
Media - 50%EG
Dimensions & Weight
Width(W)
in 89.76
mm 2280
Height(H)
in 99.61
mm 2530
Depth(D)
in 173.23 220.47 267.72 314.96 362.2 409.45 456.69 503.94
mm 4400 5600 6800 8000 9200 10400 11600 12800
Net weight
lb 6393.41 8377.57 10141.26 11904.96 13889.12 15873.28 17857.44 19841.6
kg 2900 3800 4600 5400 6300 7200 8100 9000
Marine transport without spray or wet-film
Technical Parameters
1.The power supply specifications can be adjusted accordingly. For details, please consult TICA technical support.
2. The unit capacity is highly dependent on operating conditions, the above data is for reference only. For other media (such as water
or glycol), different operating conditions, or altitudes above 1000 m, please contact TICA technical support for verification and proper
selection.
Notes:
19 Data Center Product TICA COOLANT DISTRIBUTION UNIT (CDU)
CDU leverages the high thermal conductivity and high heat capacity of liquids to replace air as the heat dissipation medium,
boasting the advantages of low energy consumption, high heat dissipation efficiency, and low noise.
xxxx: Cooling Capacity in kW
CDU:Coolant Distribution Unit
TICA
T CDU XXXX A C E XXX T A
A B C D···
C:Cold Plate Type
E: Standard Cabinet; R: Rack Mount; T: Box Type; N:
Custom Frame
xxx:Inlet and Outlet Pipe Diameter (DN)
A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V
3N~60HZ;I:415V 3N~50HZ;L:400V 3N~50HZ;P:
480V 3N~60HZ
S: Single Pump; D: Dual Pumps; T: Triple Pumps
Name Composition Sequence Number Code Code Meaning
Brand 1 1 Alphabet TICA
Product 2-4 3 Alphabets CDU:Coolant Distribution Unit
Cooling Capacity 5-8 4 Numbers xxxx: Cooling Capacity in kW
Design Code 9 1 Alphabet A B C D···
System Type 10 1 Alphabet C:Cold Plate Type
Configuration Type 11 1 Alphabet E: Standard Cabinet; R: Rack Mount; T: Box Type; N: Custom Frame
Pipe Diameter 12-14 3 Number xxx:Inlet and Outlet Pipe Diameter (DN)
Qty.of Pump 15 1 Alphabet S: Single Pump; D: Dual Pumps; T: Triple Pumps
Power Supply 16 1 Alphabet A:380V 3N~50HZ;B:380V 3N~60HZ;F:460V 3N~60HZ;I:415V 3N~50HZ;L:
400V 3N~50HZ;P:480V 3N~60HZ
TICA
20
Adaptive Stepless Regulation for LowFlow and High-Flow Scenarios
Online Non-stop Maintenance of
Circulation Pumps
Maintenance of a Single Expansion Tank
Does Not Affect System Stable Operation
Online Non-stop Maintenance of
Expansion Tanks
High Effective Filtration Capacity
No Filtration Dead Zone in SecondarySide System
Online Non-stop Maintenance of Filters
Triple Redundancy of
Expansion Tank
Triple Redundancy of
Circulation Pumps
Triple Redundancy of
Circulation Pumps
It features the following control modes
Secondary-Side Liquid Temperature
Control Accuracy ±0.5℃
Differential Pressure Control Accuracy
±0.1bar
Real-time Display of Operation Curves
for Intuitive Status Monitoring
Target Differential Pressure / Target Flow
Rate Mode
Target Temperature / Anti-Condensation
/ Dew Point Tracking Mode
Intelligent Identification of High and Low
Load Scenarios
Noise ≤ 65dB (A), Delivering a Quiet
Computer Room Environment
The controller is equipped with a UPS,
enabling online monitoring even when the
entire system is powered off.
Redundancy Design of Core
Components, Ensuring Stable Unit
Operation Upon Single Component Failure
Auto-Intelligent Control
Quiet Operation
High-Precision Control
Convenient Management
Controller Power Failure Memory
Fault-Free Operation
TCDU1350 Product Advantages
The cold source adopts medium-temperature water-cooled sources — dry coolers or cooling towers, which are compatible with
liquid-cooled cold sources. The air-liquid ratio can be flexibly adjusted, supporting rapid and flexible business deployment.
TCDU Product Advantages
Compatibility - Air-Liquid Homologous Source
sever sever sever sever sever sever ... ... sever sever sever sever sever sever
Fan Fan wall
Heaf
exchanger
Comnpressor
Dry
cooler
Cooling
pump
EXV Water
coiL
DX
coil
21 Data Center Product TCDU TCDU0300 TCDU0450 TCDU0800 TCDU1350 TCDU2500
Heat Exchange Capacity kW 300 450 800 1350 2500
Primary-Side
Supply Temp
℃ 35 35 35 35 35
℉ 95 95 95 95 95
Coolant / water water water water water
Pipe Diameter
DN 80 80 100 100 150
Inch(ISO) 2.5 2.5 4 4 6
Secondary-Side
Supply Temp
℃ 39 39 39 39 39
℉ 102.2 102.2 102.2 102.2 102.2
Coolant / water water water water water
Pipe Diameter
DN 80 80 100 100 150
Inch(ISO) 2.5 2.5 4 4 6
Rated Flow
m³/h 20.4 30 78 120 196.5
L/min 340 500 1300 2000 3275
Rated Head bar 1.5 1.5 2 2 2.5
Rated Power kW 4.5 5.5 14 21 44
Supply Power / 460V/60Hz
Size(W×D×H) mm 600×1200×2000 900×1200×2200 1000×1500×2300
in 23.6×47.2×78.7 35.4×47.2×86.6 39.4×59×90.6
Net Weight kg 470 750 900 1100 2500
lb 1036 1654 1984 2425 5512
TManifold
Size 30x30mm/40x40mm/50x50mm
Branch 20-50pcs
Branch flow 1-3L/min
Distribution non-uniformity rate ≤ 10%
Material SUS304/SUS316
Simulation of Fluid Distribution Imbalance Rate
Fluid Distribution Imbalance Rate Test
Sanitary Grade Stainless Steel Square Pipe
Installation and Cleaning in Dust-Free Workshop
Arc Angle Transition Design for Reducing Hygienic Dead Corners
TCDU Technical Parameter List
TManifold
Technical Parameters
TICA
22
Date Topic
23 Data Center Product Date Topic TICA
24
Date Topic
Fostering a better life
Limiting the temperature increase to 1.5°C
Note:Due to constant improvement and innovation of TICA product,the specifications and parameters contained in
this document are subject to change without prior notice.