安装、使用产品前,请阅读安装使用说明书。
请妥善保管好本手册,以便日后能随时查阅。
自动跟踪定位射流灭火装置
ZDMS0.6/5S-HA-Q3(自动炮)
ZDMS0.6/10S-HA-G3(自动炮)
[安装使用说明书]
(HA.2026.01.06 V1.0)
无锡皓安安全技术有限公司
Wuxi haoan safety technology co., ltd
江苏省无锡市滨湖区胡埭路 8 号
目录
一、概述··························································································································1
系统组成···················································································································1
设计与分布················································································································1
二、产品安装设计及参数···································································································2
外观及技术参数··········································································································2
安装方式·····················································································································3
安装部件·····················································································································4
安装使用·····················································································································4
三、接线及调试················································································································4
四、注意事项····················································································································5
第1页
一、产品概述
自动跟踪定位射流灭火装置是皓安公司自主研发生产的集报警、灭火于一体的新一代高科技消防产品。该系列产品将红外/紫
外传感器、计算机通信技术有机集合起来,具有主动探测火源、自动定位、对火源实施定点射流灭火,灭火后自动复位,如有复燃,
重新启动定位射流灭火,特别适用于大空间场所的灭火需求。产品方便安装,安装与维护费用低,节约水资源,最大程度的减小了
灭火后造成射水带来的危害,具有很高的实用性,经济性。
本系列产品广泛应用于:大型商场、会展中心、机场、火车站、汽车站、办公楼、医院、图书馆、电影院、体育馆、厂房、仓
库等空间大、楼间隔高的场所。
设计与分布
单排: 双排:
L=2×√(R×R-b×b) L=√2×R=1.414R
R 为装置保护半径 ,b 为实际需要保护半径 1/2 R 为装置保护半径 ,L 为装置距离
L 为装置距离
交叉:
L=(√3/2R)(2N-1)= (2N-1)0.866R
R 为装置保护半径,L 为装置距离,N 为装置每行用装置个数
第2页
二、安装设计及参数
1、外观及技术参数、
ZDMS0.6/10S-HA-G3 智能灭火装置(消防水炮)
型号 ZDMS0.6/5S-HA-Q3 ZDMS0.6/10S-HA-G3
执行标准号 GB25204-2010
射水流量 5L/S 10L/S
额定工作压力 0.6 Mpa
最大保护半径 25m 28m
接口 DN32 法兰(国标)
定位时间 ≤ 30s
俯仰角度/水平角度 -90°~+30°/0°~360°
安装高度 6-15m
通讯方式 485 总线 装置自重 约 3 Kg
配接线束 6 芯 TH3.81 弹簧插头线 喷水方式 直射往复摆动
配套控制产品
灭火装置控制器 HA-P2000Q/2001
区域控制箱 HA-QKX2011A
电源解码器 HA-JMQ2002A
火灾探测方式 水平垂直探测组件 HA-IR30
安装方式与边距
吊装;中心体距墙体≥ 300mm,
距吊顶≥300mm
注意:5L/S、10L/S 自动跟踪定位射流灭火装置均标配视频摄像头
灭火装置安装时应保证安装后,炮身水平垂直、左侧朝向墙面(标签),严禁震动炮体,扳动炮体枪管及法
兰;注意装修期间的探测器保护,防止污染后影响后期探测使用。
第3页
2、安装方式
2.1 楼板或架空安装,如下图所示:
2.2 吊顶安装,如下图所示:
第4页
3、安装部件
3.1 检修闸阀
检修闸阀安装在进水管末端。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入进水管内,
连接后应将连接处外部清理干净,检修闸阀的扳手部分应安装在管网上方。
3.2 电磁阀
电磁阀安装在检修闸阀后面管径为 DN50,中间用长 50~100mm 热镀锌管连接。电磁阀应安装在水平管段上,且保证水流方向
要与阀体的指示方向一致。螺纹连接的密封填料应均匀附着在配水管的螺纹部分,拧紧螺纹时,不得将填料挤入配水管内,连接后
应将连接处外部清理干净。电磁阀应安装在管网上方,应选用 AC220V 电源供电,电磁阀电源线应串入电源解码器接点使用,并作
防水处理。
4、安装使用
灭火装置的安装应按照国标喷水灭火系统设计、施工规范进行,各省、地方有自行规定的按自行规定安装。将灭火装置与管网
接口连接,固定灭火装置时注意按照规程操作。灭火装置连接线需用本公司原厂自带 6 芯 TH3.81 弹簧插头线与电源解码器相连接,
并固定插紧。灭火装置安装牢固后通电,通电后灭火装置会自动复位,待复位后观察灭火装置底部红色运行指示灯是否闪烁(如不
能复位请安装人员现场联系调试人员),如果状态正常及安装完毕。
三、接线及调试
灭火装置在通电之前应必须检查下联动柜、区域控制箱、手动控制盘、电源解码器之间的接线是否正确,区
域控制箱到电源解码器的接线:
电源解码器接线端子示意图
第5页
注意:当自购电磁阀无动作反馈信号线时,需增加辅助继电器解决动作反馈信号输入,无反馈
装置电输入: L、N、E(火线、零线、地线) 接线端
阀电输入:L、N (火线、零线)接线端
开阀:L1 火线接线端 公共:N 零线接线端
关阀:L2 火线接线端
水流指示:水流指示接口
信号蝶阀:信号蝶阀接口
阀反馈:电磁阀开启后,动作回答接线端(无源信号)
外部启动:第三方火警启动输入接线端(无源信号)
通讯总线:BUS通讯总线输入接线端(不区分极性)
轴芯、屏蔽:灭火装置视频输入线接线端
24V+/24V-输出:DC24V电源输出接线端
+24V/G/A/B/轴芯/屏蔽:灭火装置6P输入线对接端
信号输入,系统会默认判定水炮故障,导致无法开阀喷水。
水炮整机测试:
a)通电后炮管垂直 45°向下运动到限位点,5s 后灭火装置主程序复位,此时灭火装置处于待命状态。
b)短接电源解码器的端子排外部启动(模拟火灾信号)启动灭火装置,灭火装置水平顺时针旋转。
c)灭火装置水平旋转时可用模拟火源(如打火机)在灭火装置水平传感器前点火,灭火装置应水平定位。
d)灭火装置水平定位后可在垂直传感器前点火,灭火装置应垂直定位。
e)灭火装置垂直定位 3s 后发出报警声,炮管喷水并做上下左右往复射流运动。
通过以上测试,无异常发生后方可交付验收。
水炮精准度补偿调试:
可参见水炮红外遥控器说明书
本公司所有出厂产品均为已标定,如需调整请联系现场技术员或直接与本公司技术部沟通。
四、注意事项
1. 在开机前必须检查线路无问题,切勿短路、开路、错接等。
2. 本机需由经专业培训人员进行维护、维修,严禁他人随意操作。
3. 我公司负责本产品的维修,发现问题时请及时与我公司技术服务中心联系,用户不得擅自
开箱维修,否则后果自负。
4. 在安装前应进行功能检查,避免为运输过程中造成损坏的设备。
5. 严禁带电拆装各电路连接线和信号线,所有的操作均需在断电关机情况下进行。
6. 外壳、电源部分和外接导线的金属软管应作接地保护。
7. 本产品保修期为 12 个月,如在一年内出现非人为损坏的情况请即与本公司或者经销单位联
系。
从本公司购买设备者,自本公司发运日期起计算;从经销部门购买者,以经销单位发运日起计算,
整机保修为 12 个月