INNOVATION AND GLOBAL PARTNERSHIP
PROFESSIONAL LIGHTNINGPROTECTION, SAFE GUARDAGAINST DAMAGE
Lightning protection of buildings is a key issue of safe electric power & safety of electric appliances. Safe environment and reliable application of electric appliances directly relate to our personal safety and daily life, e.g. the overvoltage in our daily operation of household electrical appliances happens every day resulting in threat of power failure.
Lightning hazards to buildings and its electric appliances can cause various damages. The main causes can be thermal effect, mechanical force by lightning, lightning current invasion, electromagnetic induction etc. which bring about the damage on buildings and its electric equipment. Through years of our engineering experience against lightning, if there is no lightning protection measure, lightning strike may cause severe safety problems to people and property.
ZG provides most professional lightning protection solution to various buildings.
Our professional service guarantees you and your family to stay in a safe and comfortable living environment.
High quality living is guarded by our protection.
ZG LIGHTNING PROTECTION SOLUTION FOR BUILDINGS
ZG lightning protection solutions meet China standard GB 50057/ GB 50343-2012 (IEC 62305) which includes direct lightning protection, shielding, equipotential bonding, reasonable wiring, earthing, installation of surge protective devices etc. to build up a comprehensive lightning protection system. Installation of lightning protection system applies standard of NFPA 780. Ancient architecture applies China standard of GB 51017-2014 (IEC 62305).
Direct lightning protection: Choose ZG conventional lightning rod as direct protection against lightning and select type and post height based on calculation of rolling sphere method and set up protection ring belt of voltage sharing.
Earthing system: Choose ZG non-metal earthing module connected with natural earthing body of building to set up an integrated earthing grid.
Inductive lightning protection:
Install multi-stage surge protective devices in power distribution system and install multi-stage signal surge protective devices on signal lines to protect equipment concerned. Apply accordingly the shielding measures, reasonable wiring, equipotential bonding etc. to set up an integrated lightning protection system.
We provide the professional and safe measures to buildings against lightning through direct lightning protection, common earthing system and integrated measures against LEMP.
Our protection concept for buildings is based on common earthing, integrated measures and multistage discharge of over current & over voltage.
Class I SPD shall be installed at general distribution cabinet (LPZ0A or boundary between LPZ0B and LPZ1) or at connective interface between low voltage cable and overhead supply line. The SPD impulse discharge current Iimp generally shall be more than 12.5 kA for each protection mode and voltage protection level shall be less than 2.5 kV.
Decoupling device shall be installed between different class level SPDs when connective wire is <10 m between switch type SPD and voltage limiting type SPD as well as connective wire is <5 m between voltage limiting type SPDs.
The SPD has the tripping function and degradation display.
Signal SPD shall be installed at boundary of LPZ (LPZ0A or boundary between LPZ0B and LPZ1). Select single class SPD or coordinated SPDs based on amplitude of overvoltage, overcurrent and rated value of impulse voltage withstanding at equipment interface.
The selection of SPD shall match with the transmission rate, operational voltage and interface type. The SPD output port shall connect to equipment protected.
LIGHTNING PROTECTION FORDISTRIBUTED PHOTOVOLTAIC SYSTEM
Long-term, safe and efficient distribution of photovoltaic power generation system is ensured by the comprehensive lightning protection.
Enjoy your solar energy under safe protection.
SMART LIGHTNINGPROTECTION SYSTEM
The lightning monitoring system can monitor accurately on real-time the lightning current waveform, amplitude, polarity and time of the lightning current pass flow through the discharge passage.
PDUs and DCDUs are widely used based on the importance of equipment
distribution and power energy management in various data room systems.
DIRECT LIGHTNING PROTECTION PRODUCTS
Lightning Rod Receiving lightning and inducing lightningcurrent into the ground
Franklin Lightning Rod Optimized Lightning Rod
Low Resistance Earthing Module
Obtained invention patent High electrical conductivity Excellent anti-corrosionperformance
LEMP PROTECTION PRODUCTS
1stStage Three-phase/Single-phase AC Power SPD
Class I + Class Ⅱ The series has 3+1, 4+0, 3+0, 2+0, 1+1 etc. Used for TN,TT,IT low voltage AC power distribution system. Impulse discharge current (10/350 μs) \mathsf { I } _ { { i m p } } \colon 2 5 kA / 50 kA Nominal discharge current ( 8 / 2 0 \mu \ s ) \mid _ { { { \scriptsize { n } } } } : 25 kA / 50 kA
ZGD-I series
2 ^ { \mathsf { n d } } Stage Three-phase/Single-phase AC Power SPD
Class Ⅱ
The series has 3+1, 4+0, 3+0, 2+0, 1+1 etc. protection modes for TT, TN low voltage AC power distribution system. Impulse discharge current \mathsf { I } _ { \mathsf { i m p } } ( 8 / 2 0 \mu \mathsf { s } ) : 20 kA /30 kA /30 kA
ZGGF25-385 Series ZGGF50-385 Series ZGGFB25-385 Series ZGGFB50-385 Series
ZGG80-385e Series ZGG60-385e Series ZGG40-385/320/275e Series
ZG provides multiple sets of product configuration solutions for buildings lightning protection. If you have other requirements, please contact us directly. Our global service hotline is (+86) 400 682 1987.
Description
05 | $3 ^ { \mathfrak { r d } }$ Stage Three-phase/Single-phase AC Power SPD Class Ⅱ The series has 3+1, 4+0, 3+0, 2+0, 1+1 etc. protection modes for TT, TN low voltage AC power distribution system. Impulse discharge current $\mathsf { I } _ { \mathsf { i m p } } ( 8 / 2 0 \mu \mathsf { s } )$ : 10 kA | ZGG20-385/320/275e Series |
$3 ^ { \mathfrak { r d } }$ 06 | stage DC power SPD Class Ⅱ Used for low voltage DC power distribution system. Impulse discharge current $\mathsf { I } _ { \mathsf { i m p } } ( 8 / 2 0 \mu \mathsf { s } )$ : 10 kA /20 kA | ZGG40-48e Series ZGG20-48e Series ZGG20-24e Series |
![]() | PCS & String Inverter - Power Supply Protection for 1000 V System | ZGGS**-670PV Series ZGGS**-500PV Series |
| Class Ⅱ lightning protection at the AC/DC ends, mounted on PCB Impulse discharge current $\mathsf { I } _ { \mathrm { i m p } } ( 8 / 2 0 \mu \mathsf { s } )$ : 10 kA /20 kA | ||
08 | PCS & String Inverter - Power Supply Protection for 1500 V System Class π lightning protection at the AC/DC ends, mounted on PCB Impulse discharge current $\mathsf { I } _ { \mathrm { i m p } } ( 8 / 2 0 \mu \mathsf { s } )$ : 10 kA /20 kA | ZGGS**-900PV Series ZGGS**-890PV Series |
Description
This series combines 2 in 1 of power protection & video signal protection The power protection part is in series connection suitable for AC or DC with load current less than 5A; the signal part is suitable for protection of HD camera.
RJ 45 Port
Combined SPD
ZGZH series
Ultra-transmission rate signal SPD
Efficiently suppress the over voltage & impulse occurred in Gb Ethernet High transmission rate, quick response, low protective dB
Signal SPD
ZGXT-4R-5
Used to protect internal high transmission rate interface of Ethernet High transmission rate, quick response, low protective dB RJ 45 Port
ZGXH-2R-5
24-port combined SPD
High transmission rate, quick response, low protective dB RJ 45 Port
ZGXH-2R24-5
Signal SPD
Used to protect camera, monitor Box type can be mounted on rack.
ZGM-1B16-5
Smart SPD monitoring system (used for online monitoring of SPD)
Detect surge current amplitude, polarity occurrence time & times occurred on SPD.
SPD remote function
SPD degradation display
Communication mode: RS485 bus line
ZGLJ-S2 series
Ethernet communication module
Transmit on real time the equipment status Communication mode: RS485 Ethernet
ZGLJ-C2
iDCDU
Suitable for the power distribution management of 5G base stations or equipment cabinets, providing intelligent power switching and monitoring.
Ensuring energy efficiency, emission reduction, and safe operation for equipment or data centers
ZGDCDU Series
PDU
ZG focuses on the research and development of intelligent PDUs. Providing the perfect front-end dynamic environment monitoring and complete background management solutions for customers
Common series Smart series
Socket with lightning protection
Max continuous operating voltage: 385 V AC Limited voltage: (8/20 μs 1.5 kA): L-PE, N-PE ≤1500 V
ZGJ8610
ONE-STOP SUPPLIER OFBUILDING CABLES AND CABINETS
Additionally, we offer a one-stop procurement service for commonly used electrical products in the building sector, including wires, cables, both high and low voltage distribution boxes and so on.
TPS FLAT COPPER CORE WIRE
Wire material: Oxygen-free copper / PVC Executive standard: AS/NS 5000.2 Product certification: SAA Product specification: 0.75/1/1.5/2.5/4/6/10 Number of cores: 2C/3C/2C+E
CONSUMER UNIT
A control unit used in residential electrical systems where the main power line enters and branches out into multiple circuits for indoor lighting, sockets, air conditioning, etc.
ELV BOX
A concentration box for low-voltage lines used to centrally manage and distribute various low-voltage signals within a household, including networking, telephone, television, and security systems, to prevent interference from high-voltage electrical systems.





05
06
08