目 录 1. 安全注意事项·······················································································12. 安装要求 ·····························································································12-1 安装位置·························································································22-2 安装方法·························································································32-3 电器配线························································································62-... [收起]
[展开]
BC-800T博图变频冷暖型机柜空调操作说明书
粉丝: {{bookData.followerCount}}
文本内容
第1页

苏州博图制冷设备有限公司

使

BC-800T 工业机柜空调说明书

第2页

目 录

1. 安全注意事项·······················································································1

2. 安装要求 ·····························································································1

2-1 安装位置·························································································2

2-2 安装方法·························································································3

2-3 电器配线························································································6

2-4 机器排水·························································································6

3. 启动与运转···························································································6

3-1 运行前后注意事项···········································································6

3-2 机器操作说明··················································································7

4. 维护与保养·························································································10

4-1 定期清洁·······················································································10

4-2 长时间停用时注意··········································································10

5. 故障排除·····························································································10

附录一······································································································11

附录二······································································································11

第3页

1,安全注意事项

⑴ 当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册

中所提到的注意事项,以避免出现意外情况;

⑵ 请勿用湿手操作,以免引起触电;

⑶ 当需要保养或维护时,请先切断所有电源以免引起触电事故;

⑷ 空调器上不易放置任何物品,以免滑落造成人员伤害;

⑸ 当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受

伤或机器损坏;

⑹ 本机器外部结构已做防水处理,请按照我公司给出的正确安装方式安装。此空调不适宜于安装

在振动较大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;

⑺ 本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;

⑻ 禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发生。

1. 安装要求

本空调器为侧挂式系列,侧挂式(图一),为使机组能在理想的状况下工作,在安装上请注意以

下要求:

图一 侧挂式

空调器

回风

(热)

出风

(冷)

第4页

2-1 安装位置

⑴ 空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘

类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装

空调器,则一定要每天做好空调器的清洁和保养工作。

⑵ 空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调

器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、

排风口离墙面的间距应大于 500mm;

⑶ 空调器周围请勿放置杂物,以保持空气畅通流通;

⑷ 本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。

⑸ 请安装本空调器于周围温度在 45℃以下的范围之内高温系列 55℃以下;

⑹ 本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜

角不大于 5°如图四所示;

⑺ 控制箱内正对出风口的电器元件与出风口的最小距离应大于 200mm,因距离太近电器元件表

面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;

并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。

⑻ 当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿

度能控制在较为理想的状态下。图三

冷气机

第5页

图 四

错 误 正 确 错 误 正 确

2-2 安装方法

⑴ 当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;

⑵ 为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进

行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;

⑶ 空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备

损坏,当安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的

重量不会使整个电气柜倾倒;

⑷ 电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;

⑸ 箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;

⑹ 当长期使用时请注意安装 螺栓是

否损坏或脱落,若有而未加处 理,将

有可能导致机器掉落而损坏;

⑺ 具体的安装方式如下

第6页

1,蒸发风机出风挡板安装示意图:(如不安装出风口有凝结水风险)

2-3 电器配线:

⑴ 机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若所

提供的电压在额定值±10%以内,本机组可正常使用;L,N,PE ,为电源输入引线

经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,

此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意

⑵ 空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,

当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;

⑶ 在机组的电器回路上请自行安装断路器或漏电保护装置;

⑷ 请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负载,

引发事故。

第7页

2-4 机器排水:(户外机型无以下排水管项目)

本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气

就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:

⑴ 请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;

⑵ 根据实际情况排水软管长度适当即可,过长部分请切除;

⑶ 排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水严

重时产生外溢,引起空调器或者电气柜故障。

启动与运行 3-1 运行前后注意事项

⑴ 启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开始

工作;(户外机型无排水管,直接在底部有漏水孔)

⑵ 当在运转中需重新启动空调器时,请间隔 3 分钟以上,倘若频繁启动且间隔时间过短会引起机

器损伤;

⑶ 当空调器倾斜时请勿开启,避免漏水、触电等情况发生;

⑷ 空调器在出厂时温度点已经设定好为 24℃,若需重新设定时请控制在允许范围之内设定,以

免引起机器运行不正常;如果空调器有加热功能,出厂时设置为 20℃

⑸ 当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进行检查

维修。

3-2 机器操作说明:系统参数设置界面进入:

1. 示意图

该显示面板包含 4 位LED 显示屏和 4 个按键,可用于实时数据和状态的显示,系统参数的

显示和设置。

接口型号

接口 规格 描述

SPI 2.5mm*6 与主控板通信接口

2. 安装说明

该显示面板外壳自带卡扣,安装简单,操作方便,机器钣金只需开一个孔即可安装,

第8页

具体开孔尺寸说明如下:

3. 指示灯含义

显示屏下方有一排 6 个指示灯,可以方便快捷的查看设备状态,具体含义定义如下:

指示灯 指示灯名称 亮 闪烁

温 度 参数设置状态 自检

制 冷 制冷状态 压缩机故障

制 热 制热状态 加热器故障

除 湿 除湿状态 ---

外 风 机 外风机开启 外风机故障

告 警 有告警 ---

第9页

4. 实时参数查询

4.1 冷凝盘管温度/外风机电流查询

在显示回风温度状态(主界面),按一次“”键,将显示冷凝盘管温度传感器检测到的

温度(C 闪烁)或者外风机运行电流,视具体系统配置而定,再按一次“”或者“M” 键,返回

到显示回风温度的主界面。

4.2 蒸发盘管温度/内风机电流查询

在显示回风温度状态(主界面),按一次“”键,将显示蒸发盘管温度传感器检测到

的温度(C 闪烁)或者内风机运行电流,视具体系统配置而定,再按一次“”或者“M” 键将返

回到显示回风温度的主界面。

4.3 柜内湿度查询

在主界面,同时按下“”和“Set”键,将显示柜内湿度(显示格式为‐XX‐),按 “M” 键

返回到显示回风温度的主界面。

4.4 柜外温度查询

在主界面,同时按下“”和“Set”键,将显示柜外温度,按 “M”键返回到显

示回风温度的主界面。

4.5 压缩机(或加热器)的当前运行电流查询

在显示回风温度状态(主界面),同时按下“”键,将显示压缩机(或加热器)

的当前运行电流,按“M”键返回到显示回风温度的主界面。

4.6 交流电输入电压查询

在显示回风温度状态(主界面),按“Set”键将显示当前交流供电电压值,显示格

式为:LXXX,单位 V。按一次“M”键,返回到显示回风温度的主界面。

5. 控制参数设定

控制参数项根据安全等级划分为用户参数和厂家参数,系统默认只显示用户参数,

厂家参数需要在 F111 参数项输入密码才能看到,密码默认 1111。用户参数无需密码,

可以直接设置。

在主显示界面,长按“M”键3 秒,进入参数设置状态,显示参数代码 F01,用“” 键选

择参数代码,选择一个代码后按“Set”键则显示该代码对应的参数值;这时通过

“”键即可对参数值进行设置(按住“或“”键不放可连发),设置完成后再

按“Set”键,系统保存新设置的参数并显示 End,然后回到显示参数代码状态;在设置参数

时,按“M”键表示放弃,退回显示参数代码但不改变参数值。在显示参数代码时长按

“M”键 3 秒可退出参数设置状态。在上述过程中,如果 30 秒钟之内没有任何按键按

下,控制器将退出系统设置菜单。

具体控制参数列表如下:

类别 代码 参数名称 范围 单位 备注

F01 制冷启动温度 18~50 ℃

F02 制冷停止回差值 2~15 ℃

F03 制热启动温度 -42~20 ℃

第13页

4.维护与保养

请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机

器上安装的是尼龙滤网的可直接从侧面拔出(户外机型底部有漏水孔)

4-1 定期清洁

本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,

一般每周需清洗一次; 有的机型为钣金的网孔,直接用气枪清洗即可。

⑵ 请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发

生触电事故;

4-2 长时间停用时注意

⑴ 请切断电源,以防意外;

⑵ 清理冷凝器、过滤网及内部油污;

⑶ 请对机器采取防尘措施,延长机器使用寿命。

2. 故障排除

故障状况 1 电源接通后,室内、室外风机不运转

可能原因

※保险丝熔断

※停电或无电源

状况排除

※更换保险丝

※检查电源状况

故障状况 2 在运行中突然停机,电控箱内温度高于设定点温度两度以上

可能原因

※环境温度过高,导致压缩机热保护

※过滤网堵塞或者冷凝器过脏,导致压缩机热保护

状况排除

※改善周边环境,使散热畅通

※对过滤器及冷凝器进行清洗

故障状况 3 机器正常运转,却不制冷

可能原因

※压缩机损坏

※制冷系统泄露

※机组蒸发器大面积结霜

状况排除

※更换压缩机,重新抽真空充注制冷剂

※查出泄露处,并重新抽真空加制冷剂

※立即停机,把设定温度调高到 35℃,十分钟后重新开机

◇若上述措施均不能排除故障,请致电本公司咨询!

第14页

附录 1:产品技术参数

型号:BC-800T

工作电源: 交流 220V ±10% 频率 50Hz ±4%

运行电流: <2.5A

功 率: 430W

制冷剂: R134a

制冷量: 800W 制热量: 800W

防护等级:内循环:IP54 外循环:IP34

允许机柜内温度设定范围:25--38℃(出厂设定 30℃)

允许使用环境温度范围:-25--45℃

噪音:60dB

附录 2:电气原理图

室内风机 室外风机 压缩机

M1 M2 M3

C2 C3

L

N

PE

t℃温控器

BC-800T主回路电路图控制温

第15页

苏 州 博 图 制 冷 设 备 有 限 公 司

地址:苏州市吴江区太湖新城镇同安东路 60 号

电话:0512-63172851 0512-63172852

传真:0512-63102853 邮编:215223

全国统一服务热线:400-920-7382

网址:www.botuzl.com Email:botu@botuzl.com

百万用户使用云展网进行电子画册在线制作,只要您有文档,即可一键上传,自动生成链接和二维码(独立电子书),支持分享到微信和网站!
收藏
转发
下载
免费制作
其他案例
更多案例
免费制作
x
{{item.desc}}
下载
{{item.title}}
{{toast}}