MUSEN
POWER TEST EQUIPMENTMANUAL
ON-BOARD INTEGRATED AC WITHSTAND VOLTAGE TEST PLATFORM
SF6 OIL-IMMERSED, NO PARTIAL DISCHARGE VARIABLE FREQUENCY SERIES RESONANT DEVICE
SF6 OIL-IMMERSED, NO PARTIAL DISCHARGE TEST TRANSFORMER
MSXB(F) SERIES VARIABLE FREQUENCY SERIES RESONANT DEVICE
CONTENT
01 Ac Withstand Voltage Equipment 03
02 Transformer Test 17
03 High Voltage Test Series 19
04 Transformer Test 26
05 SF6 Gas Measurement And Detector 32
06 Insulating Oil Test Equipment 36
07 HV Switch Test 42
08 Secondary Injection Relay Tester 43
09 CT PT Analyzer 45
10 Battery Testing Series 46
FOCUS ON POWER TESTING EOUIPMENT 30 YEARS
Since its establishment in 1996, it has been committed to the research and development and production of substation power testing equipment and transmission line testing equipment, focusing on power testing products and services.
米+
米十X
Company Profile
Quality You See. Service You Feel. Integrity You Trust. Brand You Choose
Wuhan Musen ElectricCo., Ltd., established in 1996, is located in the Wuhan East Lake New Technology Development Zone (Wuhan OpticsValley), enjoying convenient transportation. As an OEM/ODM manufacturer with 30 years of experience, we specialize in the research, development, manufacturing, sales, andservice of high-voltage testing equipment and systems. Our products include AC/DC high-voltage testers, resonance test systems, frequency resonance test systems, transformer test equipment, transformer dielectric loss testers, and partialdischarge high-voltage testers. These products are widely used in power, energy, transportation, metallurgy, chemical industry, mining, and water conservancy projects. All products comply with international CE standards or Chinese national standards. Our products are exported worldwide, and our services are recognizedand highly praised by major global clients. Adhering to the 12-word principle of quality, excellent service, integrity, and brand, we specialize in power testing products and services and have successfully partnered with nearly 10,000 companies.
MS-GTU GIS Pressure Test Chamber
SCOPE OF APPLICATION
The 100-1200kV gas-filled, non-partial discharge combined electrical test device is suitable for conducting insulation withstand voltage tests, partial discharge tests, and GIS transformer accuracy tests on high-voltage, large-capacity GIS and GIL power equipment. It is an essential device for GIS substations, GIS and GIL power equipment manufacturers, and manufacturers of pot insulators and insulating structural components for preventive and factory testing.
Adding a high-voltage bushing port to the device allows high voltage to be extracted, enabling various high-voltage tests on conventional high-voltage equipment.
TECHNICAL PARAMETERS
Rated capacity
50-2000kVA
Impedance voltage
≤5%
100kV、200kV、250kV、300kV
Output voltage
500kV、750kV、1000kV、1200kV
Temperature rise
≤65K
Runtime
≤5min
MAIN FEATURES
1. High voltage is fully enclosed in a shielded space, ensuring safe and reliable testing.
2. Overall partial discharge can be controlled within 1-3 pcs.
3. Compact size minimizes space requirements and lightweight components.
4. Built-in high-voltage disconnect switch enables multi-purpose use.
5. Easy connection: Direct connection to the test object makes testing more convenient.
6. Rugged and durable structure capable of withstanding long-distance transportation.
7. Reduced system power capacity requirements
MS-GTU Variable Frequency NO PD Withstand Voltage Test System
SCOPE OF APPLICATION
145kV power system GIS non-partial discharge Ac withstand voltage test, applicable to test productmaximum capacitance s 0.0001jF/bay (based on 3 bays + 9m GIS internal busbar s 0.001uF) and testproduct total capacitance < 0.004uF, test frequency 100Hz, maximum test voltage 235kV.
TECHNICAL PARAMETERS
Output power
50kW
Input voltage
Frequency adjustment range
380V+10% three-phase; 50Hz
Frequency Resolution
Output waveform
Single-phase 0\~350V
Partial discharge
MAIN FEATURES
1. High voltage is fully enclosed in a shielded space, ensuring safe and reliable testing.
2. Overall partial discharge can be controlled within 5 pc.
3. Compact size minimizes space requirements and lightweight components.
4. Built-in high-voltage disconnect switch enables multi-purpose use.
5. Easy connection: Direct connection to the test object makes testing more convenient.
6. Rugged and durable structure capable of withstanding long-distance transportation.
7. Reduced system power capacity requirements.
MS-GTU GIS Pressure Test Chamber Project Case
600kV SF6 gas non-partial discharge test transformer (bushing)
MS-YDQW Integrated Sf6 Gas No Partial Discharge Test Transformer(bushing)
MUSEN
nall footprint, less on-site wiring fear of bumpy transportation
SCOPE OF APPLICATION
The device integrates a transformer, voltage divider, and protective resistor, and is equipped with safetyprotection measures such as overcurrent protection and overvoltage protection to ensure a safe and reliabletest process. It also features a user-friendly interface and data display function, making it easy for users toperform test operations and view results.
TECHNICAL PARAMETERS
| Rated capacity | 30-1000kVA Customizable |
| Rated voltage | AC 100-1200kV |
| Runtime | <5min |
| No-load loss | <4% |
| Load loss | <9% |
| Partial discharge | <5PC |
MS-YDOW Sf6 Gas No PD Test Transformer (bushing)
MUSEN
SCOPE OF APPLICATION
The non-partial discharge gas-filled test transformer is designed, developed andmanufactured by our company by introducing and absorbing advanced foreign technologieslt is widely used in manufacturers of electrical appliances, cables, motors, transformers, mutuainductors, insulation materials and related high-voltage components, as well as high-voltagetest laboratories in power, scientific research and colleges and universities. It can performpartial discharge and power frequency withstand volt-... tests on their products.
TECHNICAL PARAMETERS
Rated capacity
50-1200kVA
accuracy
≤1.5%
Input voltage
380V
Partial discharge
≤5Pc
Output voltage
50-1200kV
Protection function
Overcurrent and voltage protection alarms automatically return to zero
MAIN FEATURES
1. Filled with high-insulation SF6 gas as the insulating medium;
2. Compact size, light weight, high-grade craftsmanship, beautiful appearance, and easy transportation;
3. Due to the arc-extinguishing properties of SF6 gas and its unique process structure, partial dischargeis minimal, ≤5 PC at rated voltage;
4. The test process is simple and intuitive, and the operation is convenient and easy;
5. Effectively eliminates noise interference from the power supply;
6. Utilizes automatic control technology, with a high degree of automation and strong antiinterferencecapabilities:
7.Utilizes fast electronic protection devices for high reliability.
MS-YDJW No PD Test Transformer
SCOPE OF APPLICATION
Suitable for manufacturers of electrical appliances, cables, motors, transformers, instrument transformers, insulation materials, and related high-voltage components, this tester can perform partial discharge and power frequency withstand voltage tests on their products.
TECHNICAL PARAMETERS
Rated capacity
50-1200 kVA (customizable)
Partial Discharge
<5 PC
Output Voltage
AC 50-1200 kV, including 50, 100, 150, 200, 250, 300, 500, and 1000 kV
Transformation Ratio Accuracy
<1.5%
Protection
Overcurrent and voltage protection alarms with automatic reset
Transformer Losses
No-load loss: <4%; Load loss: <9%
MAIN FEATURES
1. Filled with high-insulation transformer oil as the insulating medium;
2. Low partial discharge (≤5 PCD) at rated voltage;
3. Simple and intuitive test process, easy to operate;
4. Effectively eliminates power supply interference;
5. Utilizes automatic control technology, offering a high degree of automation and strong anti-
interference capabilities;
6. Utilizes fast electronic protection devices for high reliability.
MSWJXZ No Partial Discharge Induction Voltage Withstand Resonance Test System
SCOPE OF APPLICATION
Non-PD Inductive Withstand Resonant Test SystemThis device utilizes a linearly amplified variable-frequency power supply with reactor-coupled compensation, making it suitable for inductive withstand voltage and partial discharge testing of power transformers of various capacities and voltage levels.
MAIN FEATURES
1. GIS, circuit breakers, transformers, cables, insulators, and other equipment at voltages up to 220kV can simultaneously perform partial discharge (PD) measurements during AC withstand voltage testing. The system's own partial discharge level is less than 10pc, enabling precise measurement of the system's insulation condition.
2. AC withstand voltage testing can be performed at a fully simulated power frequency. Test conditions more closely resemble those of the equipment in grid operation, providing a more realistic reflection of its operating conditions.
3. In variable-frequency mode, the frequency can vary from 50Hz to 300Hz, adapting to higher capacity requirements and providing greater flexibility in test environments and operating conditions.
4.The non-PD power supply can also be used as a test power source for long cables, suitable for AC withstand voltage and partial discharge testing of cables.
750kV AC Withstand Voltage Test Platform
Multiple specifications: 500kV, 750kV, and 1000kV integrated AC auxiliary voltage test platform.
TECHNICAL PARAMETERS
Rated Voltage
750kV
Resonant Reactor
Rated Inductance 435H
Rated Current
6A
Operating Frequency
30-300Hz
Rated Output Power
4500kVA
Rated Capacitance
8000pF
Duty
≥30min
Hydraulic System
1) System Operating Low Pressure 3MPa±1MPa
2) System Operating Medium Pressure 8MPa±1MPa
3) System Operating High Pressure 16MPa±1MPa
MAIN FEATURES
1. On-board Mobile Integrated Platform: The entire 750kV series resonance test system is highly integrated into a dedicated vehicle, enabling flexible deployment of testing capabilities.
2. Hydraulic Accumulation and Reduction System: Core components (such as reactors) are automatically raised and lowered via an on-board voltage platform, eliminating lifting and manual handling, significantly improving efficiency and safety.
3. Rapid On-site Deployment: Testing begins immediately after the hydraulic outriggers are leveled, eliminating complex lifting procedures and significantly reducing preparation time.
4. Fully Automated Test Process: Automatic tuning locks the resonance point, allowing one-click completion of the entire voltage step-up, timing, and voltage step-down process based on preset parameters.
5. Remote and Secure Operation: Supports fiber-optic remote control, ensuring operators can complete tests from a safe distance.
6. Intelligent Protection and Monitoring: Multiple real-time protections (overvoltage, overcurrent, flashover, etc.) combined with key parameter monitoring and data logging ensure safe and reliable testing.
7. Reliable Grounding: Integrated large-section grounding devices and ground detection ensure reliable equipment grounding during testing.
MS-CZ Vehicle-mounted High-pressure Inflatable No partial Discharge Combined Test Device
TECHNICAL PARAMETERS
| Voltage Levels | 100kV,200kV,250kV,300kV,500kV,800kV,1000kV |
| Capacity | 50-2000kVA |
| Input Voltage | 0.35-10kV (primary voltage) |
| Partial Discharge | 1-3pc at rated voltage (normal environment) |
| Temperature Rise | No more than 65kV (50Hz) after 60 minutes of operation at rated current |
| High VoltageGeneration Method | High-voltage transformer step-up and series resonance(power frequency,variable frequency). All step-up methods are single-stage, no cascade step-up required. |
MAIN FEATURES
1. A vehicle-mounted hydraulic lift mechanism allows for easy mobility and facilitates on-site testing.
2. High voltage is fully enclosed within a shielded enclosure, ensuring safe and reliable testing.
3. The overall PD level can be controlled to within 1-3 pcs.
4. Compact size minimizes space requirements and lightweight components.
5. A built-in high-voltage disconnector enables multi-purpose use.
6. Easy connection: Direct connection to the test product facilitates testing.
7. Rugged and durable construction withstands long-distance transportation.
MS-CZWJ Vehicle-mounted No PD Withstand Voltage Test System
TECHNICAL PARAMETERS
Voltage Levels
100kV, 200kV, 250kV, 300kV, 500kV, 800kV, 1000kV
Capacity
50-2000kVA
Input Voltage
0.35-10kV (primary voltage)
Partial Discharge
1-3pc at rated voltage (normal environment)
Temperature Rise
No more than 65kV (50Hz) after 60 minutes of operation at rated current
High Voltage Generation Method
High-voltage transformer step-up and series resonance (power frequency, variable frequency). All step-up methods are single-stage, no cascade step-up required
MAIN FEATURES
1. A large 27-inch LCD display provides clear and intuitive readings for voltage, current, time, status information, and prompts.
2. An all-Chinese interface provides simple and straightforward operation, adaptable to a variety of applications.
3. Touchscreen operation allows all functions to be preset, enhancing product safety and reliability.
4. Status reminder function with fully Chinese-guided operation.
5. Alarm function: A 5-second buzzer alerts when a combination alarm is triggered; a buzzer alert sounds when voltage signal acquisition is abnormal.
6. Emergency stop function: In automatic control, this function allows for an emergency stop at any point during voltage increase or decrease.
7. Automatic timing function: In automatic control, the device automatically starts timing when the voltage rises to the set value. When the timer expires, the device automatically decreases the voltage and returns to zero.
8. Manual control mode: Similar to traditional electric voltage increase/decrease, voltage increase/decrease is controlled by touch buttons, the device automatically determines upper and lower limits, and provides highvoltage overvoltage, low-voltage overcurrent, and high-voltage overcurrent protection.
MSXB-FSeriesVariable Frequency Series Resonant Device
Applicable to 10-220kV substation equipment and cable AC withstand voltage test Common specifications (kVA/kV): 135/108、270/108、270/270、540/270、1620/540、400/800、8100/500
MSXZ(f)-1620kVA/540kV Variable Frequency Series Resonance
SCOPE OF APPLICATION
1.AC withstand voltage test for 0.8km of 220kV/630mm² cable, 2km of 110kV/630mm² cable, and 3km of
35kV/240mm² cable
2.AC withstand voltage test for the neutral point of a 220kV main transformer and the line end of a 110kV main transformer
3.AC withstand voltage test for circuit breakers, PTs, CTs, insulators, and GIS components up to 220kV
Variable Frequency Series Resonant System
Suitable for acceptance and preventive testing of high-capacity, high-voltage electrical equipment.
The variable frequency series resonant test device utilizes brand-new, innovative technology to perform various tests, reducing the required power capacity and overcoming the limitation of traditional resonant testing, which can only satisfy the working time requirements of a single cable for 3 hours. The patented technology design ensures continuous withstand voltage testing for multiple cables at the engineering site.
To meet the requirements of different voltage levels for testing, the reactor is designed with multiple separate units that can be combined as needed for various test scenarios.
MSXZ(f)-75kVA/75kV Variable frequency series resonance
AC withstand voltage test for 10kV/300mm²1.5km cables AC withstand voltage test for 35kV main transformers
Product Configuration
Excitation transformer: 6kVA/1.5/6kV/0.4kV, 1 unit
Frequency converter power supply: 6kW/220/380V, 1 unit
High-voltage reactor: 25kVA/25kV, 3 units
Capacitive voltage divider: 80kV/1000pF, 1 unit
Internal connecting cables: 1 set
AC withstand voltage test for 35kV/300mm², 0.6km long cables
AC withstand voltage test for 35kV switches and current
transformers
AC withstand voltage test for the neutral point of
110kV/40000kVA main transformer
Product Configuration Excitation transformer: 6kVA/1.5/6kV/0.4kV,1 unit Variable frequency power supply: 6kW/220/380V, 1 unit High-voltage reactor: 27kVA/27kV, 4 units Capacitive voltage divider: 110kV/1000pF, 1 unit Compensation capacitor: 70kV/10000pF, 1 unit
Scope of Application
AC withstand voltage test for 1km of 35kV/300mm² cable AC withstand voltage test for 35kV main transformer AC withstand voltage test for 35kV switches and instrument transformers
Product Configuration
Excitation Transformer: 7.5kVA/1.5/6kV/0.4kV(1unit) Variable Frequency Power Supply: 7.5kW/220/380V(1unit) High-Voltage Reactor: 33.75kVA/27kV(4unit) Capacitive Voltage Divider: 110kV/1000pF(1unit) Compensation Capacitor: 70kV/10000pF(1unit)
Scope of Application
AC withstand voltage test for 110kV GIS and switches
AC withstand voltage test for 0.7km of 110kV/400mm² cable
AC withstand voltage test for fully insulated
110kVA/80000kVA main transformer
Product Configuration
Excitation Transformer: 15kVA/4/8/16kV/0.4kV (2 units)
Variable Frequency Power Supply: 30kW/220/380V (1 unit)
High-Voltage Reactor: 54kVA/27kV (10 units)
Capacitive Voltage Divider: 270kV/500pF (2 units)
Compensation Capacitor: 160kV/5000pF (2 units)
MSXZ(f)-1000kVA/500kV Variable frequency series resonance
Scope of Application
220kV/300mm² 0.5km,110kV/630mm²1km
35kV/630mm² 2km AC withstand voltage test for cables
AC withstand voltage test for 220kV main transformer neutral point and 110kV main transformer line terminal
AC withstand voltage test for 220kV and below circuit breakers, PTs, CTs, insulators, GIS, etc.
Product Configuration
Frequency converter power supply: 45kW/0.4kV (1 unit)
Excitation transformer: 20VA/4/8/25kV/0.4kV (2 units)
High-voltage resonant reactor: 100kVA/50kV (10 units)
Capacitive voltage divider: 500kV/1000pF (1 unit)
Compensation capacitor: 160kV/5000pF (1 unit)
• SCOPE OF APPLICATION
1.AC withstand voltage test for 1.2km of 220kV/630mm² cable and 3.5km of 110kV/630mm² cable
2.AC withstand voltage test for the neutral point of a 220kV main transformer and the line end of a 110kV main transformer 3.AC withstand voltage test for circuit breakers, PTs, CTs, insulators, GIS, etc., 220kV and below
MSXZ(f)-8100kVA/500kV variable frequency series resonant transformer
SCOPE OF APPLICATION
1.AC withstand voltage test for 4km of 220kV/1000mm² cable, 10km of 110kV/1000mm² cable, and
13km of 35kV/240mm² cable
2.AC withstand voltage test for the neutral point of a 220kV main transformer and the line end of a
110kV main transformer
3.AC withstand voltage test for circuit breakers, PTs, CTs, insulators, GIS, etc., 220kV and below
MS-101G Series High Voltage Dielectric loss Tester
Upgrade 8 major functions to fully meet test reguirements
MUSEN
Simultaneous forward and reverse measurement
Four-channel simultaneous measurement
CVT ratio polarity
CVT self-excitation method
● LCR measurement
Bluetooth and data transmission
SCOPE OF APPLICATION
The dielectric loss insulation test can effectively detect the overall moisture deterioration and deterioration of the insulation of electrical equipment, as well as local defects. It is widely used in electrical manufacturing, electrical equipment installation, handover and preventive testing.
The variable frequency power supply adopts a high-power switching power supply, outputting single-frequency 45Hz\~65Hz anddual-frequency 47.5Hz\52.5Hz, 45.0Hz\55.0Hz,57.5Hz\62.5Hz, 55.0Hz\65.0Hz pure sine waves, automatically increasing voltage, and can provide a maximum voltage of 12kV; it automatically filters out 50Hz interference and is suitable for on-site testing with large electromagnetic interference such as substations.
TECHNICAL PARAMETERS
| Model | Function |
| MS-101G1 | Four channels / simultaneous forward and reverse measurement/ English program / CVT measurement |
| MS-101G2 | Four channels/forward and reverse measurementCVT measurement/CVT ratio polarity error/LCR function |
| MS-101G3 | Four channels/forward and reverse measurementCVT measurementCVT ratio polarity errorLCR function/insulation resistance functio |
| MS-101G4 | custom madel Output voltage 12kV, tgd-f curve, various data analysis, etc. |
MAIN FEATURES
1.Frequency conversion and anti-interference
Automatically identifies 50Hz/60Hz system voltage and can accurately measure under 200% interference
2.4-channel forward connection
Internal/external standard capacitanceinternal/external high voltage
3.Reverse wiring low voltage shielding function
220kV VCT busbar grounding, C11 performs 10kV reversewiring dielectric loss measurement without disconnectingthe line
4.C1/C2 simultaneous measurement
CVT self-excitation measurement,C1/C2 simultaneous measurement
5.Measures ratio, polarity and phase errors
CVT ratio measurement function, can measure ratio,polarity and phase error
6.Can be connected to an external 40Hz\~70Hz
high voltage power supply
7.Wireless Bluetooth interface and datareturn function
8. Built-in computer interface
APPLICABLE SCENARIOS
YDQ/YDJZ/GTB AC/DC Voltage Withstand Tester
SCOPE OF APPLICATION
The scope of application is mainly used for conducting insulation strength tests on various electrical products, electrical components, insulation materials, etc. under specified voltages, to assess the insulation level of the products, discover insulation defects of the tested products, and measure the ability to withstand overvoltage.
It is the preferred product for voltage withstand testing equipment required by departments related to power operation, electrical and appliance manufacturing enterprises, metallurgy, coal mines, electrified railways, scientific research institutions, and universities
It is an essential testing equipment for power equipment inspection and preventive testing
Fully automatic
MUSEN
TECHNICAL PARAMETERS
| Test transformer specificationsand parameters | capacity(kVA) | High voltageoutput voltage (kV) | High voltageoutput current (mA) | Low voltage input | transformationratio | |
| V | A | |||||
| 5kVA | 5 | 50 | 100 | 200 | 25 | 500 |
| 5 | 100 | 50 | 200 | 1000 | ||
| 10kVA | 10 | 50 | 200 | 220/380 | 50/26 | 500 |
| 10 | 100 | 100 | 200/380 | 1000 | ||
| 20kVA | 20 | 50 | 400 | 380 | 500 | |
| 20 | 100 | 200 | 380 | 53 | 1000 | |
| 20 | 150 | 133 | 380 | 1500 | ||
| 30kVA | 30 | 50 | 600 | 380 | 500 | |
| 30 | 100 | 300 | 380 | 1000 | ||
| 30 | 150 | 200 | 380 | 79 | 1500 | |
| 30 | 200 | 150 | 380 | 2000 | ||
| 30 | 250 | 120 | 380 | 2500 | ||
| 50kVA | 50 | 50 | 1000 | 380 | 500 | |
| 50 | 100 | 500 | 380 | 1000 | ||
| 50 | 150 | 333 | 380 | 132 | 1500 | |
| 50 | 200 | 250 | 380 | 2000 | ||
| 50 | 250 | 200 | 380 | 2500 | ||
| 1000kVA | 100 | 100 | 1000 | 3000 | 33 | 1000 |
| 100 | 150 | 666 | 3000 | 1500 | ||
| 100 | 200 | 500 | 3000 | 2000 | ||
MSVLF-80kV/1.1uF Ultra-Low-Frequency 0.1Hz Test Device
TECHNICAL PARAMETERS
| Rated Output Voltage | 80kV |
| Output Frequency | 0.1Hz, 0.05Hz, 0.02Hz |
| Load Capacity | 0.1Hz, maximum 1.1μF; 0.05Hz, maximum 2.2μF;0.02Hz, maximum 5.5μF |
| Measurement Accuracy | 1% |
| Positive and NegativeVoltage Peak Erro | ≤3% |
| Voltage Waveform Distortion | ≤5% |
MAIN FEATURES
1. Advanced technology: adopting digital frequency conversion technology, microcomputer control, fully automated testing processes such as boost, buck, measurement, and protection;
2. Equipment operation: simple wiring and convenient use;
3. Comprehensive protection: multiple protections (overvoltage protection, high and low voltage side overcurrent protection), quick action (action time ≤ 10ms), instrument safety and reliability;
4. Safe and reliable: The controller and high-voltage generator are connected at low voltage, with photoelectric control, ensuring safe and reliable use;
5. Adopting high and low voltage closed-loop negative feedback control circuit, the output has no capacitance rise effect.
MSVLF-101G UItra-Low Frequency Cable Dielectric Loss Tester
A single unit performs insulation resistance, dielectric loss, and AC/DC withstand voltage tests on 10kV/35kV cables.
TECHNICAL PARAMETERS
| Power Supply | 100-240V 50/60Hz, ±10% |
| Input Power | 400VA |
| Output Frequency | 0.01Hz - 0.1Hz in 0.01Hz increments |
| Frequency Optimization | Yes |
| Output Load Capacity | 0.5μF at rated voltage 0.1Hz; 12μF at lowfrequency or low voltage |
ZGS-80kV 300mA Water-cooled Generator DC Withstand Voltage Test Equipment
Designed for leakage current and DC withstand voltage tests of water-cooled generators
TECHNICAL PARAMETERS
MAIN FEATURES
Testing with Blowing Water
Advantages: A standard DC high-voltage generator can be used for testing. The equipment is lightweight, easy to operate, and provides accurate readings, unaffected by water quality.
MS-3126A Insulation Resistance Tester
It features five measurement ranges: 500V, 1000V, 2500V, 5000V, and 10000V, and can test resistances up to 10TΩ.It is powered by a lithium-ion battery that can be charged while in use.
MAIN FEATURES
1. Insulation resistance range: 10TΩ @ 10kV, with an adjustable short-circuit current up to 10mA.
2. Automatically displays polarization index (Pl) and dielectric absorption ratio (DAR) values, and can measure leakage current and capacitance.
3. Excellent anti-interference performance: the instrument maintains test accuracy even with interference currents up to 2mA.
4. Rapid discharge of capacitive test pieces. When testing cables, manual discharge is unnecessary; the instrument automatically discharges quickly
ZGF Series DC High Voltage Generator
SCOPE OF APPLICATION
The instrument is suitable for DC withstand voltage test and leakage test of zinc oxide lightning arrester, magnetic blowout lightning arrester, power cable, transformer, generator and other equipment in the power, railway, chemical, mining, metallurgy, steel and other departments. It can also be used as power source for electrostatic dust collection and spraying.
TECHNICAL PARAMETERS
| specifications | 60/2 | 60/3 | 60/5 | 120/2 | 120/3 | 120/5 | 200/2 | 200/3 | 200/5 | 300/2 | 300/3 | 300/5300/5 |
| structure | Integrated | Split body | ||||||||||
| Rated voltage(kV) | 60 | 120 | 200 | 300 | ||||||||
| Rated current(mA) | 2 3 5 | 2 3 5 | 2 3 5 | 2 3 5 | ||||||||
| Rated power (W) | 120 180 300 | 240 360 600 | 400 600 1000 | 600 900 1500 | ||||||||
| Voltage accuracy | ±(1.0% reading+2 words)± (1.0% reading+2 words) | |||||||||||
| current accuracy | ||||||||||||
MSDDG Series High Current Generator
MUSEN
SCOPE OF APPLICATION
It is an essential equipment for electrical tests where high current is required, and is used in power plants, distribution substations, electrical appliance manufacturing, scientific research, laboratories and other units.
TECHNICAL PARAMETERS
| Capacity (kVA) | Output Current (A) | Weight(kg) | Notes |
| 3 | 500 | 24 | Can be madeinto split orintegratedstructures |
| 5 | 1000 | 40 | |
| 10 | 2000 | 60 | |
| 12 | 2500 | 68 | |
| 15 | 3000 | 75 |
| Capacity (kVA) | Output Current (A) | Weight(kg) | Notes |
| 20 | 4000 | 110 | split type |
| 30 | 5000 | 160 | |
| 40 | 6000 | 180 | |
| 60 | 8000 | 240 | |
| 75 | 10000 | 280 |
YDQ[W)/YDJZ(W) Non-partial Discharge Power Frequency Withstand Voltage Test Device
This instrument is widely used for partial discharge measurement, product type testing, and
insulation operation monitoring of various high-voltage electrical products, including transformers,
mutual inductors, high-voltage switches, zinc oxide arresters, and power cables. It offers high
sensitivity, covers a wide range of sample capacitance, and is suitable for a wide range of test products.
It alen features a comnreheneive ranae of innut unite (detection impedance) and offers nine frequency ectly read the discharge capacity of a discharge
Common specifications
Inflatable non-partial discharge pressure-resistant device
system composition
1. Transformer without partial discharge test
2. Non partial discharge transformer control console
3. Non partial discharge isolation filter transformer
4. Non partial discharge coupling capacitor (with
built-in voltage divider function)
5. No partial discharge protection resistor
6. Partial discharge tester
MSJF-3001B Ultrasonic Partial Discharge Tester
MUSEN
SCOPE OF APPLICATION
Used to detect partial discharge in operating switchgear, transformers, cables, GIS, overhead lines, and more.A built-in two-in-one ultrasonic and geomagnetic wave sensor allows for PD detection in switchgear without the need for external sensors.
MAIN FEATURES
Non-invasive detection eliminates the need for power outages, making operation simple and versatile.Configurable with different sensors, it can detect partial discharge in virtually any highvoltage electrical equipment.Provides various discharge patterns, including time-domain waveforms, PRPD, and PRPS, enabling analysis of different discharge types.The test bandwidth ranges from 30kHz to 2.0GHz, enabling detection principles applicable to various frequency bands.
MSBR-II Transformer Winding Deformation Tester
internal structural fault detection of 63kV\~500kV power transformers
TECHNICAL PARAMETERS
| Amplitude measurement range | (-100dB) to (+20dB) |
| Amplitude measurement accuracy | +20dB ~-60dB ±1dB -60dB~-100dB ±2dB |
| Sweep frequency accuracy | 0.01% |
| Signal input impedance | 1MΩ |
| Signal output impedance | 50Ω |
| In-phase test repetition rate | 99.5% |
MS-560 Transformer Capacity Characteristics Tester
Used to measure no-load current, no-load loss, impedance voltage, load loss, and zerosequence impedance of various types of transformers.
MAIN FEATURES
1. Automatically performs waveform distortion and temperature correction.
2.Measures three-phase voltage/current, average voltage/current, and two-phase active power.
3. Measures harmonics and total distortion for each phase of voltage and current.
4. Displays real-time waveforms for each phase of voltage and current.
TECHNICAL PARAMETERS
0-750V (wide range)
| Measuring range | 0.9 to 10,000 |
| Phase angle measurement accuracy | 0.1° |
| Phase angle measurement range | 0 to 360° |
MS-103 Transformer Short Circuit Impedance Test System
Capable of measuring transformer short-circuit impedance, short-circuit reactance, short-circuit resistance, and three-phase impedance voltage.
TECHNICAL PARAMETERS
| Basic measurement accuracy | Voltage, current, and impedance 0.2% ± 3 digits |
| Power | 0.5% ± 3 digits (cosφ > 0.1),1.0% ± 3 digits (0.01 < cosφ ≤ 0.1) |
| Voltage measurement range | 0-800V AC |
| Current measurement range | 0-80AAC |
| Impedance measurement range | 1Ω-200Ω |
MS-100D Transformation Ratio Tester
This instrument overcomes the shortcomings of traditional ratio bridge testing, completing three-phase ratio testing in one go, with fast testing speed and high accuracy, greatly improving testing efficiency.
MAIN FEATURES
1. Wide testing range, up to 10000.
2. Displays hexagonal vector diagram and group number
3. Blind measurement of transformation ratio and group number
4. Phase angle measurement
5. High and low voltage reverse connection protection, transform short-circuit protection, and inter-turn short-circuit protection
6. AC and DC power supply options to meet diverse site requirem
TECHNICAL PARAMETERS
| Range | 0.9 to 10,000 |
| Accuracy | ±(reading × 0.2% + 2 digits) (≤ 500)(reading × 0.5% + 2 digits) (greater than 500) |
| Resolution | 0.9 to 9.9999 (0.0001) |
MS-100ES Handheld Three-Phase Transformer Turns Ratio Tester
Single-phase measurement, automatic testing of three-phase windings. No power supply is required on site to complete the test work. A full charge can perform more than 500 measurements continuously.
TECHNICAL PARAMETERS
| Turns ratio measurement range | 0.9 to 10,000 |
| Measurement speedt | Complete three-phase test in 35 seconds |
| Measurement accuracy | High-voltage side voltage measurementaccuracy:0.05% |
| Low-voltage side voltagemeasurement accuracy | 0.1% |
| Turns ratio resolution | 0.0001 |
| Turns ratio measurement accuracy | 0.1% (0.9-200), 0.2% (200-2000), 0.3% (2000-10,000)Full-range 0.1-level equipment available upon request |
MAIN FEATURES
1. Single-phase and three-phase measurements
2. Displays hexagonal vector diagram and group number
3. Blind measurement of transformation ratio and group number
4. Turns ratio and operating voltage ratio measurements
5. Demagnetization function eliminates residual magnetism in the transformer core
6. AC and DC power supply options to meet diverse field requirements
MS-100B(E) Transformer Turns Ratio Testing Equipment
TECHNICAL PARAMETERS
MAIN FEATURES
The instrument offers fast testing speeds, completing a three-phase ratio test in just 10 seconds with a single connection. It also features a blind test function, allowing you to perform ratio and group tests even when the high and low voltage connection configurations are unknown. It is suitable for testing distribution transformers up to 1000kV transformers, single-phase transformers, and current transformers.
MS-207T Transformer On-load Switch Tester
Used to measure the transient waveform, transient time, transient resistance, and three-phase synchronicity of transformer on-load tap-changers.
TECHNICAL PARAMETERS
| Output current | ≥ 1A, 3 channels |
| Data sampling | Sampling |
| channels | 6 channels |
| Sampling frequency | 10 kHz/s |
| Measurement range | Transition resistance: 0.5Ω to 20Ω |
MS-510S2Three-Channel Winding DC Resistance Tester
This device integrates magnetizing method testing, three-phase testing (Yn, Y, ∆), and demagnetization functions. It completes all DC resistance tests with a single connection, offering fast testing speed.
MAIN FEATURES
1. Three-phase measurement method, calculation of three-phase imbalance rate.
2.25kΩMaximum output current 20A, test range up to 25kΩ
3.Automatically calculates the resistance change rate over 5, 15, and 30 seconds.
TECHNICAL PARAMETERS
Output Current
MS-520S Three-channel DC Resistance Tester
Integrates three-phase testing, magnetizing, and demagnetizing functions.
TECHNICAL PARAMETERS
Three-phase test
20A+20A;10A+10A;5A+5A;1A+1A;
200mA+200mA;20mA+20mA;
Single-phase test
40A; 20A; 10A; 5A; 1A; 200mA; 20mA;
MAIN FEATURES
1.Mainly suitable for measuring inductive resistance in transformers, instrument transformers, and other devices.
2.Measures three-phase DC resistance on star-connected windings and automatically calculates three-phase imbalance.
MS-520 DC Resistance Tester
Offers six output current settings, with a maximum of 20A and a minimum of <5mA, making it suitable for measuring the DC resistance of a wide range of transformers and instrument transformers.
TECHNICAL PARAMETERS
Output current
20A, 10A, 5A, 2A, 100mA, <5mA
Measurement range
100μΩ to 1Ω (20A), 500μΩ to 2Ω (10A),
1mΩ to 4Ω (5A), 5mΩ to 10Ω (2A),
100mΩ to 200Ω (100mA), 200Ω to 100kΩ (<5mA)
Accuracy
0.2%±2μΩ
MAIN FEATURES
1.Wide measurement range (100μΩ to 100kΩ)
2.Discharge alarm function, clear discharge indication
3.On-load tap-changer can be directly switched during measurement
MS-401 SF6 Gas Density Relay Calibrator
Measures the alarm value, latch value, alarm return value, and latch return value of { \mathsf { S F } } _ { 6 } gas density relays. Both single latch and double latch measurements are available. The instrument also features normal temperature pressure gauge calibration and 2 0 ^ { \circ } { C } pressure gauge calibration.
TECHNICAL PARAMETERS
MUSEN
| Ambient temperature | -20°℃ to 70°℃ |
| Relative humidity | 90% RH |
| Power supply | AC220V, 50Hz |
| Power consumption | 50W |
| Accuracy | Class 0.2 |
| Pressure display resolution | 0.001MPa |
| Pressure calibration range | 0 to 1MPa |
| Ambient temperature display resolution | 0.1℃ |
| Calibration options | Single alarm, single latch,single alarm and single latch,single alarm and double latch |
MS-403 SF6 Gas Leak Detector
Performs qualitative and quantitative leak detection in { \mathsf { S F } } _ { 6 } electrical equipment.
TECHNICAL PARAMETERS
MAIN FEATURES
1. Accurately locates leak points in { \mathsf { S F } } _ { 6 } gas-filled electrical equipment.
2.Displays multiple parameters simultaneously, including { \mathsf { S F } } _ { 6 } concentration, temperature and humidity, battery indicator, time, and diaphragm pump status.
3.Utilizes non-dispersive infrared (NDIR) technology and a German-made sensor.
MS-405 SF6 Trace Moisture Tester
Integrates three-phase testing, magnetizing, and demagnetizing functions.
TECHNICAL PARAMETERS
| Measurement Method | RC measurement principle |
| Ambient Temperature | $- 2 0 ^ { \circ } \mathsf { C } \mathsf { t o } + 6 0 ^ { \circ } \mathsf { C }$ |
| Measurement Range | -80°C to +20°C(When the dew point is below 0°C,the sensor output is frost point)Response Time: 63% [90%] $+ 2 0 ^ { \circ } \mathsf { C } \mathsf { t o } - 2 0 ^ { \circ } \mathsf { C } :$ Td: 5s [45s] $- 2 0 ^ { \circ } \mathsf { C } \mathsf { t o } - 6 0 ^ { \circ } \mathsf { C } :$ Td: 10s [240s] |
| Measurement Error | $\mathsf { B e t t e r \ t h a n \pm 2 ^ { \circ } C }$ |
| Repeatability | $\pm 0 . 5 ^ { \circ } \mathsf { C } ,$ Resolution: $0 . 0 1 ^ { \circ } \mathrm { C }$ |
SCOPE OF APPLICATION
Applications:
1. Trace moisture monitoring in SF₆ gas-fired electrical equipment
2. SF₆ gas cylinder quality testing
3. High-purity gas manufacturing
4. Dry gas supply for the semiconductor industry
5. R&D applications
6. Cleanroom/dryroom monitoring
7. Humidity testing of industrial gases in metal heat treatment sites and laboratories.Examples include air, \mathsf { C O } _ { 2 } , \mathsf { N } _ { 2 } , \mathsf { H } _ { 2 } , \mathsf { O } _ { 2 } , \mathsf { S F } _ { 6 } , He, Ar, and other inert gases.
MS-405B SF6 Dew Point Analyzer
MUSEN
TECHNICAL PARAMETERS
Dew point measurement range
Dew point accuracy
-60°C to +20°C (at 20°C atmospheric pressure)
Dew point repeatability
±0.1°C to ±0.2°℃
±0.05℃
MAIN FEATURES
1. Chilled mirror balance principle eliminates measurement errors caused by
hysteresis, resulting in high measurement accuracy.
2. Excellent repeatability, fast response, high sensitivity, and excellent stability.
3. Conversion between dew point and moisture concentration is possible.
MS-406 SF6 Purity Tester
TECHNICAL PARAMETERS
MAIN FEATURES
1.The sensor probe can automatically calibrate the zero point, automatica eliminate the system error introduced by zero point and drift, and ensure the accuracy of each measurement.
2.Quick and gas-saving: After the instrument is turned on and enters the measurement state, each purity measurement takes about 2 minutes.
3.Self-locking connector: Uses original imported self-locking connector, which is safe, reliable and leak-free.
MS-407 SF6 Gas Decomposition Analyzer
By simultaneously monitoring { \mathsf { S O } } _ { 2 } , { \mathsf { H } } _ { 2 } { \mathsf { S } } , and CO decomposition products, it can quickly detect and diagnose early-stage faults within SF₆ electrical equipment (circuit breakers, instrument transformers, transformers, GIS, bushings, etc.) on-site.
TECHNICAL PARAMETERS
| H2S | Measuring range | 0-100ppm |
| Minimum detectable level | ≤ 0.1ppm | |
| Accuracy | ± 0.5% | |
| Repeatability | ≤ 1% | |
| SO2 | Measuring range | 0-100ppm |
| Minimum detectable level | ≤ 0.1ppm | |
| Accuracy | ± 0.5% | |
| Repeatability | ≤ 1% | |
| CO | Measuring range | 0-1000ppm |
| Minimum detectable level | ≤ 1ppm | |
| Measuring range | ± 0.5% | |
| Measuring range | ≤ 1% |
MS-408 SF6 Gas Analyzer
Combining an SF₆ moisture meter, SF₆ purity meter, and SF₆ decomposition product analyzer, this single instrument combines the functions previously required three instruments. A single on-site measurement allows you to test all three indicators.
TECHNICAL PARAMETERS
SF₆ Gas Trace Moisture
SF₆ Gas Purity
Decomposition
Product Parameters
① -80 to +20°C (supports ppmv, etc.)
② Response Time 63% [90%]
③ +20 to -20°C Td 5s [45s]
④ -20 to -60°C Td 10s [240s]
1. Purity Accuracy: ±0.5% FS
2. Repeatability: ±0.5%
H2S:1\~200PPmv SO2:1\~100PPmv CO:1\~500PPmv MS-408 SF₆Gas Analyzer
MS-409 Insulating Oil Gas Content Tester
For transformers with voltage levels of 330-750 kV, samples are taken after a specified rest period to measure the gas content (volume fraction) in the oil.
TECHNICAL PARAMETERS
| Range | 0.05-10.00% (gas content) |
| Accuracy | 0.5% |
| Repeatability | Better than the permissible repeatability of the DI423 |
| Reproducibility | Better than the permissible reproducibility of the DL/T-703 |
| Oil usage | < 40 mL/time (including flushing oil) |
MAIN FEATURES
1. Wide detection range and accurate testing.
2. On-site measurement, complementing the limitations of chromatographic instruments.
3. Simple operation, convenient maintenance, and calibration.
4. Minimizes insulating oil usage.
MSKS-403 Fully Automatic Open-Cut Flash Point Tester
Utilizes a high-performance ion ring to detect sudden changes in flame conductivity resistance.
TECHNICAL PARAMETERS
| Temperature measurement | 40-400°℃ |
| Measurement accuracy | ±1℃ |
| Repeatability | 0.5% |
| Resolution | 0.1°℃ |
MAIN FEATURES
1. Automatic measurement process including detection, ignition, alarm, cooling, and printing.
2. Platinum heating wire with selectable electric and gas ignition modes.
3. Automatic atmospheric pressure detection and correction of test results.
4. Power-off memory function automatically saves test results.
MSQN-601 Transformer Oil Pour Point Automatic Tester
TECHNICAL PARAMETERS
| Temperature Measurement | Platinum Resistance Temperaturet |
| Accuracy | ±1℃ |
| Resolution | 0.1℃ |
| Measuring Range | +10°C to -70°℃ |
| Test Oil Quantity | 20ml per test |
| Cooling Water Requirement: Pressure | 4.9×101 to 4.9×105 Pa |
| Flow Rate | 1.5 L/min |
MAIN FEATURES
Featuring self-diagnostic capabilities, it analyzes samples quickly, accurately, with excellent repeatability, stability, and reliability. This instrument is a specialized instrument for the power, petroleum, and chemical industries, replacing imported products. When testing the pour point of petroleum products, the display shows the pour point temperature when the sample cools to the lowest temperature at which it can flow (the pour point), an audible prompt sounds, and the test results are printed.
MSWS-2 KarIFischer Titrator
Constant pressure detection, high accuracy, fast measurement speed, stable and reliable
TECHNICAL PARAMETERS
| Measuring range | 1μg-200mg |
| Measuring accuracy | 3μg-1000μg ≤±3μg, ≥ 1000μg ≤± 0.3% |
| Electrolysis current | 0-400mA |
| Resolution | 0.1μg |
MAIN FEATURES
1. Real-time electrolysis curve graph, monitor reagent status at any time;
2. Power-off memory function automatically saves results, with a capacity of 100 data sets;
3. Touchscreen LCD display, simple operation, and user-friendly interface;
4. High measurement accuracy, fast measurement speed, and stable data
MSYN-1301 Kinematic Viscometer
Imported sensor and digital PID temperature control technology provide a wide temperature control range and high accuracy.
TECHNICAL PARAMETERS
| Number of bath wells | 4 |
| Temperature control range | Room temperature to $1 3 0 ^ { \circ } \mathsf { C }$ |
| Constant temperature accuracy | $\pm \ : 0 . 1 ^ { \circ } \mathrm { C }$ |
| Measurement accuracy | $\pm \ 0 . 0 1 ^ { \circ } \mathrm { C }$ |
| Power supplyt | AC 220 V, 10% |
MAIN FEATURES
1. Power-off memory function automatically saves results and can store up to 100 sets of data.
2. Touchscreen LCD display for simple operation and a user-friendly interface.
3. High measurement accuracy, fast speed, and stable data.
MSZL-203 Transformer Oil Interfacial Tension Meter
Unique fast-response electromagnetic force balance sensor improves measurement accuracy and linearity.
TECHNICAL PARAMETERS
MAIN FEATURES
1. Calibration requires only one point, eliminating the need for multiple calibration points.
2. Real-time display of equivalent tension and current weight.
3. Integrated temperature detection circuitry for automatic temperature compensation of measurement results.
MUSEN
MSSZ-2006 Insulating Oil Acid Value Tester
Three-cup and six-cup integrated design, suitable for testing the acid value of transformer oil and turbine oil.
TECHNICAL PARAMETERS
| Acid value range | 0.001 to 1 mg KOH/g |
| Minimum resolution | 0.001 mg KOH/g |
| Repeatability | 0.002 mg KOH/g |
MAIN FEATURES
1. Automatically completes extractant addition, neutralization titration, endpoint determination, and acid value calculation.
2. No need to prepare extractant, neutralization solution, or other working solutions.
3. Average oil sample testing time is approximately 2 minutes.
4. Automatic standard acid calibration minimizes system errors.
5. Large-capacity, high-efficiency carbon dioxide and water purification system.
6. Guaranteed neutralization solution concentration stability.
YJJ-II Insulating Oil Dielectric Strength (BDV) Tester
0-80 kV (0-100 kV customizable) Single-cup
TECHNICAL PARAMETERS
| Output voltage | 0-80 kV (0-100 kV customizable) |
| Voltage distortion rate | <2% |
| Boosting rate | 2.0-3.5 kV/s (∆ = 0.5 kV/s) |
| Booster capacity | 1.5 kVA |
| Measurement accuracy | ±(2% + 2 digits) |
MAIN FEATURES
1.Automatically performs voltage boosting, holding, stirring, settling, and calculations
Features data storage and printout functions
2.Power-off memory function automatically saves test results
3.Overvoltage, overcurrent, limit, and ground fault alarms
Waveform conditioning function eliminates harmonic interference that can interfere with accurate measurements
YJJ-3S Insulating Oil Dielectric Strength [BDV) Tester
0-80 kV (0-100 kV customizable) Three-Cup Integrated
TECHNICAL PARAMETERS
| Output voltage | 0-80 kV (0-100 kV customizable) |
| Voltage distortion rate | <2% |
| Boosting rate | 2.0-3.5 kV/s (∆ = 0.5 kV/s) |
| Booster capacity | 1.5 kVA |
| Measurement accuracy | ±(2% + 2 digits) |
MAIN FEATURES
1.Automatically performs voltage boosting, holding, stirring, settling, and calculations
2.Features data storage and printout functions
3.Power-off memory function automatically saves test results
4.Overvoltage, overcurrent, limit, and ground fault alarms
5.Waveform conditioning function eliminates harmonic interference that can interfere with accurate measurements
MSPH-3003 Insulating Oil Acidity Tester
Three-in-one design offers fast measurement cycles and high efficiency.
TECHNICAL PARAMETERS
MAIN FEATURES
1. Automatically completes heating, constant temperature, oscillation, sampling, testing, cleaning, and printing.
2. Power-off memory function automatically saves test results.
3. Flexible selection between direct and standard tests for convenient testing.
4. Programmable cleaning function allows for convenient line cleaning.
MSBS-303A Closed Cup Flash Point Tester
Automatically completes the test process: testing, opening the lid, ignition, alarm, cooling, and printing.
TECHNICAL PARAMETERS
| Temperature measurement | Room temperature to $3 0 0 ^ { \circ } \mathsf { C }$ |
| Measurement accuracy | $\geq 1 1 0 ^ { \circ } \mathsf { C } \pm 2 ^ { \circ } \mathsf { C } , \mathsf { \leq } 1 1 0 ^ { \circ } \mathsf { C } \pm 1 ^ { \circ } \mathsf { C }$ |
| Repeatability | 0.5% |
| Resolution | 0.1°℃ |
MAIN FEATURES
1. Platinum heating wire, selectable ignition modes: electric and gas.
2. Power-off memory function automatically saves test results.
3. Automatic atmospheric pressure detection and correction of test results.
4. High-power, high-frequency switching power supply heating technology for high heating efficiency. 5. PID control algorithm automatically adjusts the heating curve. Detection stops and alarms automatically when the temperature exceeds the specified value.
MSGK-E Circuit Breaker Analyzer
Equipped with an industrial computer architecture, it is suitable for all models of SF6 switches with metal contacts, GlS combination switches, vacuum switches, and oil switches manufactured domestically and internationally.
TECHNICAL PARAMETERS
Vacuum circuit breaker
range: 50.0mm; resolution: 0.1mm; error: ≤1% rdg ±0.1
SF6 circuit breaker
range: 300.0mm; resolution: 0.1mm; error: ≤1% rdg ±0.1
Oil circuit breaker
range: 1000.0mm; resolution: 0.1mm;error: ≤1% rdg ±0.1
MAIN FEATURES
1. Accelerometers, rotational speed sensors, and linear travel sensors are extremely easy and simple to install.
2. Triggering modes: internal, external, sensor, and manual.
3. Energy storage power supply output: An adjustable energy storage power supply with a maximum starting current of 20A.
The MSHL-100A Micro-Ohmmeter
The MSHL-100A Micro-Ohmmeter is suitable for high-precision measurement of contact (loop) resistance of high and low voltage switches and DC resistance of cable lines. It is also suitable for other applications requiring high current and micro-resistance measurements.
TECHNICAL PARAMETERS
Measuring range
50A- 0-10mΩ, 100A- 0-5mΩ
Resolution
0-99.99μΩ-0.01μΩ, 100.0-10000.0μΩ- 0.1μΩ
MAIN FEATURES
1. Latest switching power supply technology enables long-term continuous high current output.
2. Stable readings within ±1 digit even under severe interference conditions.
3. Highest resolution up to 0.01μΩ.
4. Imported high-performance CPU with automatic range switching ensures test accuracy.
5. Powerful functions: Optional current selection between 50A and 100A.
MS-208V Vacuum Tester
Widely applicable to industries using vacuum switches, such as power, steel, petrochemicals, textiles, coal, and railways.
TECHNICAL PARAMETERS
| Test Objects | Various types of vacuum switch tubes |
| Test Method | Non-disassembly measurement using a new excitation coil |
| Scope of Application | Multi-purpose unit capable of measuring various types ofvacuum switches |
| Measuring Ranget | 10-5 to 10-1 Pa |
MAIN FEATURES
1. Quantitatively measures the vacuum level within the arc extinguishing chamber of various vacuum switch models.
2. No need to disassemble the vacuum switch for on-site measurement.
3. Accurate and reliable test results.
4. Simple and convenient operation.
MS-702C/802C Relay Protection Tester
It can calibrate various relays (such as current, voltage, inverse time, power direction, impedance, differential, low-frequency, synchronous, frequency, DC, intermediate, and time) and microcomputer protection devices. It can also simulate a variety of complex transient, permanent, and switching faults to conduct complete tests.Accuracy
MAIN FEATURES
1. Features 4-phase voltage and 3-phase current outputs, enabling convenient output combinations for various types of protection tests.
2. Each phase can output 120V voltage, and all three phases can output 120A current.
3. The fourth phase voltage, Ux, is a multi-function voltage setting.
4. Outputs can be set to four different values: 3U0, sync check voltage, or any other voltage value.
MS-1200C Six-phase Relay Protection Tester
(Six-phase, Class 0.2 Accuracy)
It can calibrate various relays (current, voltage, inverse time, power direction, impedance, differential, low-frequency, synchronous, frequency, DC, intermediate, and time) and microcomputer protection systems. It can also simulate a variety of complex transient, permanent, and switching faults for complete testing.
TECHNICAL PARAMETERS
| AC current output | 6 channels, 30A/450VA each, 180Ain six-phase parallel connectiont |
| AC voltage output | 6 channels, 120V/80VA each, 240V line voltage |
| Output accuracy | 0.2% (within the main range) |
| DC current output | 3 channels, ±10A/200VA each |
| DC voltage output | 3 channels, ±160V/70VA each |
| Output accuracy | 0.5% (within the main range) |
MAIN FEATURES
1. Outputs up to 6 voltage and 6 current phases, which can be combined to achieve conventional 4-phase voltage and 3-phase current modes.
2.6-phase voltage, 6-phase current, and 12-phase output modes are compatible with various traditional test methods.
MS-601G CT/PT Transformer Comprehensive Tester
Test Applications: Protection CTs and Pts
TECHNICAL PARAMETERS
Output
0-180Vrms, 12Arms, 36A(peak)
CT ratio measurement range
1-40000, accuracy: ±0.2%
PT ratio measurement range
1-40000, accuracy: ±0.2%
Phase measurement: accuracy
±5min, resolution: 0.5min
MAIN FEATURES
1. Meets the requirements for testing the excitation characteristics (i.e., volt-ampere characteristics), turns ratio, polarity, secondary winding resistance, secondary load, ratio difference, and angular difference of various CTs (e.g., protection, metering, and TP).
2. Tests the excitation characteristics, turns ratio, polarity, secondary winding resistance, ratio difference, and angular difference of the electromagnetic units of various Pts.
3. Automatically generates knee point voltage/current and 10% (5%) error curves.
4. Low-frequency testing principle, capable of testing CTs with knee points up to
5. One-click CT DC resistance, excitation, ratio, and polarity testing.
MS-601D CT/PT Analyzer
TECHNICAL PARAMETERS
| CT (Protection, Metering) | PT |
| Volt-ampere characteristic (excitation characteristic) curve | Volt-ampere characteristic (excitation characteristic) curve |
| Automatic inflection point value | Automatic inflection point value |
| Automatic 5% and 10% error curves | Turns ratio measurement |
| Transformation ratio measurement | Polarity determination |
| Ratio difference measurement | Ratio difference measurement |
| Phase (angle difference) measurement | Phase (angle difference) measurement |
| Polarity determination | AC withstand voltage test |
| Primary current test | Secondary load test |
| AC withstand voltage test | Secondary winding test |
| Secondary load test | Core demagnetization |
| Secondary winding test | |
| Core demagnetization |
MS-3982 Battery Discharge Tester
DC110V,220V,88-264V,100A
TECHNICAL PARAMETERS
| Discharge voltage | DC88V-264V |
| Discharge current | 0-100A |
| Operating mode | Standalone mode, parallel master mode,parallel slave mode, remote control mode |
| Cell voltage acquisition | Multi-band RF wireless module, communication distancecan reach more than 100 meters, compatible with2V/4V/6V/12V single battery voltage monitoring, 1 to 25groups of RF wireless monitoring modules, can monitor upto 300 batteries, a single wireless monitoring module canmonitor 12 single batteries |
MAIN FEATURES
When the battery is offline, it acts as a discharge load, continuously regulating the discharge current to achieve a set constant current discharge. During discharge, the instrument automatically stops discharging when the battery pack terminal voltage or cell voltage drops to the set lower limit, when the set discharge time or discharge capacity is reached, and records all valuable, continuous, real-time process data.
MS-3985 Battery Charge And Discharge Tester Load Group
TECHNICAL PARAMETERS
| Charge voltage | DC190V-300V |
| Charge current | 0-40A |
| Discharge voltage | DC176V-270V |
| Discharge current | 0-100A |
| Current accuracy | 1% |
| Voltage accuracy | 0.5% |
MAIN FEATURES
This product integrates constant current discharge, intelligent charging, cell monitoring, and activation.
1. DC 220V charge and discharge function
2. Constant current discharge function for battery packs
3. Intelligent charging function for battery packs
4. Activation function
MS-3986 Load Capacity Battery Tester
DC 48V/110V/220V Charge 40A Discharge 50A
TECHNICAL PARAMETERS
| Charging voltage | DC10-300V |
| Discharging voltage | DC10-300V |
| Charging current | 0-40A |
| Discharging current | 0-50A |
| Operating modes | Standalone mode, parallel master mode,parallel slavemode, remote control mode |
MAIN FEATURES
When the battery is offline, the instrument acts as a discharge load, continuously controlling the discharge current to achieve a set constant current discharge. During discharge, the instrument automatically stops discharging when the battery pack terminal voltage or cell voltage drops to the set lower limit, when the set discharge time or capacity is reached, and records all valuable, continuous, real-time process data.
1. DC 220V charge and discharge function:
2. High-precision resistors are used to avoid red-heating.
3. The cell monitoring module uses long-distance RF wireless communication to transmit voltage data.
4. The wireless data acquisition box monitors each battery cell.
5. Data is transmitted between the cell monitoring module and the main unit of the charge and discharge instrument.
MS-3006 Battery Internal Resistance Meter
Measures internal resistance and performance evaluation of single-cell batteries, battery packs, and batteries with connection resistors (optional).
TECHNICAL PARAMETERS
MUSEN
Internal resistance
0.0mΩ to 120mΩ
Voltage
0.000V to 25V
Connection resistance measurement range
0.0mΩ to 65.0mΩ
Minimum measurement
Internal resistance 0.001mΩ
MAIN FEATURES
1. Intelligent, digital design for accurate measurement and simple op
2. Weighs less than 0.45 kg and is handheld.
3. Meets various battery internal resistance testing standards.
4. Four-terminal multi-purpose test clip combines the functions of a test clip and a probe.