HUW9 ACB PRODUCT CATALOG
HUw9 Air Circuit Breaker
Functions andFeatures
Structuredescription
Circuitbreakerdescription
Thecircuitbreetructuremactndadulacharacteristihontatstemnledtweenwnulatinbalat withparistrtuhatatratenlttlinl mechanisalelrertinhanmararaneinfrfehterfhrtivnentt unit,the whole unit can be removed and replaced (see Fig.6,Fig.7).
HUw9 Air CircuitBreaker
FunctionsandFeatures
HUW9 AirCircuitBreaker
Functions andFeatures
Productdescription
Features
6FrameSize:1600,2000,2500,3200,4000,6300AF Rated current In (A):630-6300 Rated voltage AC Ue (V): Up to 690V Poles:3、4 3type of intelligent controllers With“fourremote"functions
Normal operating conditions
1、Applicable temperature:
1.1Ambienttemperature is-5°C\~+40°C(certification);
1.2the average value of24hisno more than 35°℃.
Note:
(1) when the temperature is more -10°\mathsf{C} or -25°C_{1} it should be noted;
(2) when the temperature is more than40°Corlessthan -25°C, itshould be noted;
2、Altitude: ≤2,000m athe mounting site;
3、Atmosphericconditions:
-Air relative humidity: <=slant50% at themaximumtemperatureof+40°C,andahigherrelative
humidity is allowed when at a lowertemperature;
-Forexample, at20°C,the humidityis 90% and special measures should be taken for
occasionalcondensationduetotemperaturechange;
4、Pollution level: Level3;
5、 Mountingcategory:
Circuitbreakermaincircuitandndervltagetripcoilpowertransformerprmarycoilarelevelauxiiaryiruit and controlcircuitislevelll
6.Utilization category:B
7、Installtioncondition:Installationpositionshallbevertical inclinationofeachdirectionshallnotmorethan
Classifications
1.By mounting method:Fixed type and withdrawable type
2.By operating mode: Motor operating and manual operating (for maintenance and repair)
3.By the number of poles:3P and 4P
4.By release type:Intelligent controller,under-voltage instantaneous(ortime delay)release, and shunt release
5.By intelligent over-current controller function: Mic5.0 (intelligent type),, Mic2.0 (multifunction type); Mic1.0 (standard type).
HUW9 AirCircuitBreaker
Functions andFeatures
Technical data
| Frame size(Ilnm) | HUW9-1600 | HUW9-2000 | HUW9-2500 | |||||
| Rated operating In(A) | 200、400、630、 800、1000、1250、1600 | 630、800、1000、1250、1600、2000 | 2500 | |||||
| Neutral pole rated rurrent In(A) | 100%ln | 100%ln | 100%ln | |||||
| Rated operated voltage Ue(V) | AC400、AC690 | |||||||
| Rated frequency (Hz) | 50/60Hz | |||||||
| Number of poles | 3P/4P | |||||||
| Rated impulse withstand voltage Uimp(kv) | AC12 | |||||||
| Rated insulation Voltage Ui(V) | AC1000 | |||||||
| Power frequency withstand voltage(V) | AC3500 | |||||||
| Rated short-circuit breaking capacity lcu (kA) | AC400V | 50 | 85 | 85 | ||||
| AC690V | 35 | 50 | 50 | |||||
| Operating short-circuit breaking capacity Ics(kA) | AC400V AC690V | 42 | 65 | 65 | ||||
| 35 | 50 | 50 | ||||||
| Rated short-time withstand current Icw/1s (kA) Rated short-circit making capacity Icm (kA) | AC400V AC690V | 42 | 65 | 65 | ||||
| AC400V | 35 | 187 50 | 187 | |||||
| AC690V | 110 73.5 | 110 | 50 | |||||
| Utilization category | B | 110 | ||||||
| Breaking time | ||||||||
| Marking time | ≤30ms ≤70ms | |||||||
| Service life (times) AC400VElectrical life | 5000 4500 4000 | |||||||
| ≤25001time/3min without maintenance >2500 1time/6min | 10000 | 10000 | 8000 | |||||
| with maintenance | 20000 | 20000 | 20000 | |||||
| Drawerseat mechanica life 1 time/2min | 1000 | 1000 | 1000 | |||||
| Incomming methed | Top or bottom enter | |||||||
| Flashover distance(mm) | 0 | |||||||
| Installation methed | Fixed type | Draw-out type | Fixed type | Draw-out type | Fixed type | Draw-out type | ||
| External dimensions(mm) a C | a | 339(4P)/269 (3P) | 372(4P)/302 (3P) | 457(4P)/362 (3P) | 500(4P)/405 (3P) | 457(4P)/362 (3P) | 500(4P)/405 (3P) | |
| b | 327 | 357 | 402 | 432 | 402 | 432 | ||
| C 235.5 | 337 | 338 | 457 | 338 | 457 | |||
HUW9Air Circuit Breaker
Functions andFeatures
| Frame size(Inm) | HUW9-3200 | HUW9-4000 | HUW9-6300 | |||||
| Rated operating In(A) | 2000、2500、3200 | 4000 | 4000、5000、6300 | |||||
| Neutral pole rated rurrent In(A) | 100%ln | 100%ln | 50%ln | |||||
| Rated operated voltage Ue(V) | AC400、AC690 | |||||||
| Rated frequency (Hz) | 50/60Hz | |||||||
| Number of poles | 3P/4P | |||||||
| Rated impulse withstand voltage Uimp(kv) | AC12 | |||||||
| Rated insulation Voltage Ui(v) | AC1000 | |||||||
| Power frequency withstand voltage(V) | AC3500 | |||||||
| Rated short-circuit breaking capacity lcu (kA) | AC400V | 85 | 85 | 120 | ||||
| AC690V | 65 | 65 | 85 | |||||
| AC400V | 70 | 70 | 100 | |||||
| Operating short-circuit breaking capacity lcs(kA) Rated short-timewithstand current lcw/1s (kA) | AC690V | 65 | 65 | 85 | ||||
| AC400V | 70 | 70 | 100 | |||||
| AC690V | 187 | 187 | 264 | |||||
| Rated short-ircit making | AC400V | 65 | 65 | 85 | ||||
| capacity Icm (kA) | 143 | 143 | 187 | |||||
| AC690V Utilization category | B | |||||||
| Breaking time | ≤30ms | |||||||
| Marking time | ≤70ms | |||||||
| Servicelife(times) ≤2500 1time/3min | AC400VElectrical life withoutmaintenance | 4000 8000 | 8000 | 2000 | ||||
| >2500 1time/6min | with maintenance | 15000 | 15000 | 5000 | ||||
| Drawerseat mechanicalife 1time/2min | 600 | 600 | 8000 | |||||
| Incomming methed | Top or bottom enter | 300 | ||||||
| Flashover distance(mm) | ||||||||
| 0 | ||||||||
| Installation methed External dimensions(mm) a C | Fixed type | Draw-out type | Fixed type | Draw-out type | Draw-out type | |||
| a | 537(4P)/422 (3P) | 579(4P)/464 (3P) | 537(4P)/422 (3P) | 579(4P)/464 (3P) | 927(4P)/927 (3P) | |||
| b | 402 | 432 | 402 | 432 | 432 | |||
| C | 338 | 493 | 338 | 493 | 497 | |||
Controllerpanelstructure
| Controlle function | 2M | 3M | Tabies 3H | ||
| Overload protection | |||||
| Short-circuitprotectionwithshortdelay | |||||
| Short-circuit protection instantaneous Ground protection | |||||
| chooseeither | Differentia type Ground currentype | 口 | 口 | 口 | |
| Earth leakage protection(choose eithergrounding protection or Earth leakage protection) | 二 | 口 | 口 | ||
| Overload warning | 二 | 口 | 口 | ||
| Current unbalance protection/Phase loss protection | 口 | 口 | 口 | ||
| Current demand value protection | 二 | 口 | 口 | ||
| Over-voltage protection | 二 | 口 | 口 | ||
| Under-voltage protection | 口 | 口 | |||
| Voltage unbalance protection | 二 | 口 | 口 | ||
| Over-frequency protection | 二 | 口 口 | |||
| Under-frequency protection | 二 | 口 | 口 | ||
| Phase sequence protection | 二 | 口 | 口 | ||
| Reverse power protection | 二 | 口 | 口 | ||
| Over-temperature protection and alarm | 二 | 口 | 口 | ||
| Standard Thermal memory protection functions | ■ | ||||
| Load monitoring | 二 | 口 | |||
| Zone interlock (ZSI) function | 二 | 口 | 口 | ||
| MCR protection | 口 | 口 | 口 | ||
| HSISC protection | 口 | 口 | 口 | ||
| Remotereset | 二 | 口 | 口 | ||
| Current measurement | 口 | ||||
| Voltage measurement | 二 | 口 | |||
| Powermeasurement | 二 | 口 | |||
| Power factor measurement | 二 | 口 | 口 | ||
| Frequency measurement | 口 | 口 | |||
| Energy measurement | 二 | 二 | 口 | ||
| Harmonic measurement | 二 | 口 | |||
| Thermal capacity measurement | 二 | 口 | 口 | ||
| Phase sequence measurement | 二 | 口 | 口 | ||
| Demand measurement (current) | 二 | 口 | 口 口 | ||
| Demand measurement (power) | 二 | 口 | 口 | ||
| Contact wearequivalent measurement | 二 | ||||
| Measurement function | Temperaturemeasurement | 二 | 口 | 口 | |
| LED fault status display | ■ | ||||
| Fault recording and query | |||||
| Historical current peak record | 口 | 口 | |||
| Alarm history record query | 二 | 口 | 口 | ||
| Fault trip signal output | |||||
| Self-diagnosis function Simulated trip test function | |||||
| Numberof operationsquery | |||||
| Clock function | 二 | 口 | 口 | ||
| 1/O setting function | 二 二 | 口 | 口 | ||
| Othercptinal | 口 | 口 | |||
| 二口 | 口 | ||||
| Contact output | Programmable contact output | 口 | 口 | ||
| Auxiliary contact output | |||||
| Alarm signal output | ■ | ■ | |||
| Communicationfunction | Based on RS485, standard Modbus protocol other protocols can be customized | 二 | 二 | ||
HUW9AirCircuitBreaker
Functionsand Features
2M: Digital display
HUW9 Air CircuitBreaker
Functions andFeatures
3Mtype(LCD display) 3H type (communication)
Note:Due torapid upgrade of intelligent controllers,the actual controllertypeshall prevail,not limited to the above-mentioned controllertypes.Relevant functions can be tailor-made to your
HUW9AirCircuitBreaker
Functions andFeatures
2、Intelligentovercurrentcontrollerprotectioncharacteristics andfunctions 2.1 The protection characteristics of the intelligent controller are shown in Fig.1to Fig.4. Figure 1, Basic functions(long time delay short time delay and transient protection)
Table 4
| Long delay | Short delay | Instantaneous | Ground fault | ||||
| Ir | Tolerance | Isd | Tolerance | li | Tolerance | Ig | Tolerance |
| (0.4~1)In | ±10% | (0.4~15)In | ±10% | 1.0ln~75kA | ±15% | (0.2~1.0)In | ±10% |
HUW9 AirCircuitBreaker
Functions andFeatures
Function description
·Majorprtetionfuntionscntrolsfuctinresettrequrementsfctrydliveraecontactsfrreetin) Includeslngdelayve-ladprtectinhort-circuithort-tmefixedtmeandinveretimprtctionhor-t stantanottiuiidurfitnettetarottiurntl protection due to phase loss,and load inverse time monitoring.
·Measurementand operation monitoring
eltq fratitastasttistatrtsta
·Query function
peratioqttqrdqiatq powergrid measurement parameterquery
·Parametersetting function
Thefollownrttaraetlnthrlleaeenltturt circuitshrdlarottiertmcurrentandfixetmcurentandtetantaeusprotetiurend monitorinurrtnthaeprttiotinroinreiduurtprttiuretadanie coefficient,currentunbalance protection’sunbalancerateand time,and harmonicsInfluencefactor.
Thfolowngeratioaaefomonthecotrlleaneystemckadstntlalaafeltee linteratrthatargraratqriatadisqd
·Programminginterfacefunction
Anintefattralifuitft measuremtwinthdsytemckprttiohaactristiccuehmmrytimncati communicationbaudrate,andetc.
Commuicatwrftiolalafinelintrllnlrovidstadarinte ensuresdatatranisnthruMdurProfiusrDevceetprtocolstmethefourmterquiremetsindifere monitoring systems.
·Testfunction
Thetestfunctionofferstwotypes:instantaneoustrippingsimulationtest andnon-trippingsimulationtest:
(stantaneustrippinmlatiotettantaneustrippingestcanerfdnthircuitbreakiththeactin (2)inherenttothecircuit breakertobedisplayed afterthe actiontime.
(3)Nn-trilatotltsilaiotetefothsttrgtsturtstlat (4)underthetestcurrent,andfaultcategoryofthesimulationtestwillediplayedinturafterthtestiscomleed
·Self-diagnosisfunction
Diagnose and alarm whenfaults occurinthe controlleritself.
·Fault clockfunction (optional)
Recordtthuithdtwhthfauwi records.
·Historical data recordingfunction(optional)
erdq Load monitoring protectionfunction
Ladmonitorinistontroldiffrentldsofthecircuitbreakertnurethewerupplytthemaladsmuhaspoid monitorincaeusdfrprelamngandbrachldconrolhecontrolraneprgramdtptwaiialtat for load monitoring.
·MCR ON-OFF and over-limit trip function (optional)
ON-OFFsthattweridisredfaltstatfrethirreduratthatl generatedulinandthecontrolestheircuitbreakeitataeusthhananlgcircuithistonlwrk the momentofclosing (within 100ms).
Over-itriiathatwtuierlatiothrtcuitrteenluuallt ultmaturefthiritattlwillinaaleatbearnanlrt not subject to instantaneous settings.
·Communicationprotocol IncludesaninternalModbus-RTU,andcanbetransferredtoProfibus-DPorDeviceNetthroughanexternalmodule.
HUW9 Air Circuit Breaker
Functions andFeatures
Installationandwiring
Outline and mounting dimensions of HuW9-1600 fixed type circuit breakers
| In (A) | a(mm) |
| ≤1000 | 10 |
| ≥1250 | 15 |
HUW9 AirCircuitBreaker
Functions andFeatures
Outline and mounting dimensions of Huw9-1600draw-outtype circuit breakers (choose either inner oroutermounting dimensionsfor fastening
| In (A) | a(mm) |
| ≤1000 | 10 |
| ≥1250 | 15 |
HUW9 Air Circuit Breaker
Functions andFeatures
Outline and mounting dimensions of HuW9-2000 and HUW9-2500 fixed type circuit breaker
1\mathsf{n m}=2000\mathsf{A} Extendedbusbar 11\mathsf{m}=2500\mathsf{A} Horizontalconnectiondimensions
Cabinet door cutout dimensions for HUW9-1600 fixed type
| In (A) | a(mm) |
| 630、800 | 10 |
| 1000、1250、1600 | 15 |
| 2000、2500 | 20 |
HUW9 AirCircuitBreaker
Functions andFeatures
Outline and mounting dimensions of HUW9-2000 and HUW9-2500 draw-out type circuit breakers (chooseeitherinneroroutermounting dimensionsforfastening)
K directionHorizontal wiring andmounting dimensions
Cabinet door cutout dimensions for HUW9-1600 draw-out type
| In (A) | a(mm) |
| 630、800 | 10 |
| 1000、1250、1600 | 15 |
| 2000、2500 | 20 |
HUW9 Air Circuit Breaker
Functions andFeatures
Cabinet door cutout dimensionsforHuW9-1600fixed type
HUW9 AirCircuitBreaker
Functions andFeatures
Outline and mounting dimensions of Uw9320 and UW9400 raw-outtype circuit breakers (choose either inner or outer mounting dimensions for fastening)
Inside the cabinet door
| In (A) | a(mm) |
| 2000、2500 | 20 |
| 3200、4000 | 30 |
HUW9AirCircuitBreaker
Functions andFeatures
Outline and mounting dimensions of HuW9-6300 withdrawabletypecircuit breakers (choose either inner or outer mounting dimensions for fastening)
| In(A) | a(mm) |
| 4000、5000 | 20 |
| 6300 | 30 |
HUW9AirCircuitBreaker
Functions andFeatures
Secondarycircuitwiringdiagram
hewitdhdhllriaretrerestzati cannot be madeforthedashed lines.
2)fthtrl operators,aredifferent,differentpowersourcesshould beconnectedtothem.
3)Theundervltagerelasisdirectlyconctedtothencmingteminalofthemaincircuit,withthemaxmumworkingvoltagt excedinitrtaWhthrinltanthmiruitshhethattrtatrafo needed to dropthe workingvoltagedownto its rated workingvoltage before putinto use;
)Thecassettethree-positionindicationfunctionisonlyavailableforwithdrawablecircuitbreakers.
WithDCasthewrnerofthtlientntrolleistoecthpwedleptinaladthncnecthtie ontroller #1 and #2.
HUw9AirCircuitBreaker
Functions andFeatures
| Terminal No. | Function description | Note |
| 1、2 | Auxiliarypowerinput:AC230V,AC400V,DC220V,DC110V | |
| 3、 4、 5 | Fault tripping auxiliarycontact and contactcapacity:AC25ov,3A | |
| 6、7 | Circuit breakerstatusauxiliary contact(NC)and contactcapacity:AC250V,3A | |
| 8、9 | Circuit breakerstatus auxiliary contact(NO)and contact capacity:AC250V,3A | |
| 20 | Ground (PE) | |
| 21、22、23、24 | Voltage signal measurement:21toN,22toA,23toB,24toC | Optional function |
| 25、26 | Externaltransformerinputterminal (earth leakage transformer,neutral line transformer,ground current transformer) | Optional function and accessory |
| 27、28 | Undervoltagerelease | Optional accessory |
| 29、30 | Shunt release | |
| 31、32 | Closingelectromagnet | |
| 33、34、35 | Motoroperator | |
| 36~.. | DF1 auxiliary switch wiring terminal |
| Terminal No. | Function description | Note |
| 1、2 | Auxiliary powerinput:AC230V,AC400V,DC220V,DC110V | |
| 3、4、5 | Fault trip auxiliary contact and contact capacity:AC250V,3A | |
| 6、7 | Circuitbreakerstatus auxiliary contact(NC)and contactcapacity:AC250V,3A | |
| 8、9 | Circuit breakerstatus auxiliarycontact(NO)andcontactcapacity:AC250V,3A | |
| 10、11 | Communicationinterfaceoutput,10 connected toA,11connectedtoB | Modbusprotocolbydefault |
| 12~19 | Signalinput and output, 12 and 13 are D01; 14, 15 are D02; 16, 17 are D03; 18, 19 are D04 | Set tofunctional requirements |
| 20 | Ground (PE) | |
| 21、22、23、 24 | Voltage signal measurement:21toN,22toA,23toB,24to | |
| 25、26 | Extemaltransfomerinput(earthleakagetransfomer,neutralinetransformer,groundcurent transfommer) | |
| 27、28 | Undervoltage release | |
| 29、30 | Shunt release | Optional accessory |
| 31、32 | Closing electromagnet | |
| 33、34、35 | Motoroperator | |
| 36~.. | DF1auxiliary switchwiringtemminal |
HUW9 Air CircuitBreaker
Functions andFeatures
| Symbol | C | Note | Symbol | Description | Note |
| HUW9 | HUW9series universal circuit breaker | PE | Ground wire | ||
| S1~S7 | Signal light | User-supplied | L(+),N(-) | Control power supply | |
| TA | Currentransformer | A, B, C,N | (For DC,Lis positive and N is negative) Main circuit’ sphase line | ||
| SAL | Micro switch | Df1 | Auxiliary switch | Type can be selected | |
| SB1 | Opening button | User-supplied | DF2 | Cassettethree-position | Optional accessory |
| SB2 | Closing button | User-supplied | ST powermodule | electricalindicationswitch DC24V power supply is available | Optional accessory |
| X | Closing electromagnet | St201 | Relaymodule | Optional accessory | |
| F | Shunt release | Optional accessory Protocol converter | Exceptthe Modbus protocol, | Optional accessory | |
| Q | Undervoltagerelease | other protocols need to be configured | |||
| M | Motoroperator | ||||
| SA | Motoroperator’s limit switch |
HUw9 Air CircuitBreaker
Functions andFeatures
Accessoryfunctionsandfeatures
1600A frame closing electromagnet
2000A frame and above closing electromagnet
1600Aframe shuntrelease
Closing electromagnet
Whenthe circuit breakerisfully charged and in the normalopened state,theclosing electromagnetcanbeusedtoremotelycontrolthequickclosingofthecircuitbreaker
| Working voltage Us | AC230 | AC400 | DC220V | DC110V |
| Working voltage range | (85~110)%Us | |||
| Starting current | 1.3A | 0.7A | 1.3A | 2.5A |
| Circuit breaker response time | ≤60ms | |||
2000A frame and above undervoltagerelease
Shuntrelease
Whenthecircuit breakerisinthe closed state,the shuntrelease can be used toremotely controlthequickopeningofthecircuitbreaker
| Working voltage Us | AC230 | AC400 | DC220V | DC110V |
| Workingvoltage range | (70~110)%Us | |||
| Starting current | 1.3A | 0.7A | 1.3A | 2.5A |
| Circuit breakerresponse time | ≤30ms | |||
Undervoltagerelease
The circuit breakercannot be closed whentheundervoltage release is not powered;for 2500A frame and above,two types are available forthe undervoltage release:Assisteddrawn(without delayfunction) and self-drawn;
| Working voltage Ue | AC230 | AC400 |
| Opening voltage range | (35~70)%Ue | |
| Reliable closingvoltage range | (85~110)%Ue | |
| No-closing voltage range | ≤35%Ue | |
| Power loss | 20VA | |
| Delay tripping time | Instantaneous、0.5s、1s、3s、5s | |
Note1:Within1/2ofthe delaytripping time,the circuit breakercannotbe opened when the workingvoltagerecoverstomorethan 85% ofUe;
Note 2: In areas prone to lightning and power grids with unstable power supply voltage,it is recommendedtousetheundervoltagerelease withtimedelay,topreventthecircuit breaker from opening due to short time voltage drop;
Note 3: Maximum delay time forthe undervoltage delay tripping time is 10s,and maximum delaytimeforthe zero-voltage delaytrippingtimeis 5s(consult withthemanufacturer upon ordering).
HUW9 Air Circuit Breaker
Functions andFeatures
Inter-phase partition
Inter-phase partition
The inter-phasepartitionisvertically mounted betweenthe wiring busbarsofeach phase of the circuit breaker,to enhance theinsulation capacity ofthe circuit breakerbetween phases
1600A frame charging motor
2000A frame and above charging motor
Charging motor
The charging motorenables the circuit breakerto be charged electrically.Automatic charging operation willbe conducted afterthe circuit breakeris closed, allowingthe circuit breakertobe closed again right afterit is opened.
2000A frame and above auxiliary switch
| Working voltage Us | AC230 | AC400 | DC220V | DC110V |
| Working voltage range | (85~110)%Us | |||
| Charging time 1600 frame power loss | ≤7s (Cyclical period: ≤1 time/min) | |||
| 2000/2500 frame power loss | 75VA 85VA | 75W 85W | ||
| 3200/4000 frame power loss 6300 frame power loss | 110VA 150VA | 110W 150W | ||
Note:Manual chargingoperationcan also be performed during the maintenance ofthecircuit breaker.
Auxiliary switch
| Rated working voltage | AC230 | AC400 | DC220V | DC110V |
| Conventional thermal current | 6A | |||
| Rated control capacity | 300VA | 60W | ||
Method 1: One power supply and one load Circuit diagramPossible operation mode
Key lock
To unlockthe circuit breaker:The key can be inserted to the lock when the gap on the key matches the red-dot position on the lock.Turn the key clockwise to the rightmost position, which is now in the unlocked state.At thistime,thekeycannot be pulled out directly,and thecircuitbreakercanbe closed;
To lockthecircuit breaker:First presstheopening button ofthecircuit breaker,and then turn thekey counterclockwise totheleftmost positionto remove thekey.Atthistime,the circuit breakercannot be closed.
Note 1:The power supply modes listed below are only forreference.The interlock can be installed accordingto the actual powersupply system needs on site.Orconsult with the manufacturer.Onelock and one key:A circuit breakerisequipped with onelock and one key,and the circuit breakeris not allowed to close wheninthelocked state Note 1:
QF:HuW9 circuit breaker;0:Circuit breakeris opened;1:Circuit breakeris closed
HUw9 AirCircuitBreaker
Functions andFeatures
Circuit diagramPossible operationmode
Method 3:Two power supplies and two load interlocks
Method 4:Three power supplies and one load interlock
Circuit diagramPossible operation mode
Twolocks and onekey:Two circuit breakers are equipped with twoidentical locks andonekey,andonlyonecircuitbreakerisallowedtoclose
Threelocks and twokeys:Three circuit breakers are equippedwiththreeidentical locks and twokeys,and onlya maximum oftwo circuit breakers are allowed to close
Threelocks and one key:Three circuit breakers are equipped with threeidentical locksand onekey,andonly one circuit breakeris allowed to close
Escutcheon ^+ sealing ring
Theescutcheon andsealingringaremounted onthe doorofthepower distribution cabinet wherethecircuit breakerisinstalled,to offerthesealing function and beautiful outlook,and featureIP 40 protectionlevel.
Cassette operatingpadlock
Whenthebasicdeviceofthewithdrawablecircuitbreakerisinthe “Disconnected” position, pull out the clamping board and lock it with a padlock. After locking,the basic device cannot be racked into the “Test” or “Connected” position.(Padlock is supplied by users)
Relaymodule
Input voltage:DC24V
Contactcapacity:10A/AC250V,10A/DC28V.
Arelay moduleis neededforconversionandcontroliftheload capacityislarge when controllingtheopeningand closingofthe circuitbreaker.A 35mm standard rail is used for mounting.
HUW9AirCircuitBreaker
Functions andFeatures
Position-door interlock
Position-doorinterlock
The cabinet doorisforbiddento open whenthewithdrawable circuit breaker’s basic device isin the"Test"or"Connected" position.The cabinet door is allowed to open when the basic device in the"Disconnected"position.
RCD zero-sequence currentTransformer
RCDzero-sequencecurrenttransformer
Anexternalzero-sequencecurrenttransformerisrequiredwhenresidualcurrent typeis used forthe ground protection.The vectorsum ofeach phase currentis used asthe signal sampling method,whichis suitableforprotecting smaller currents.
HUW9 Air CircuitBreaker
Functions andFeatures
Mechanicalinterlock
Steel cableinterlockingis used fortwo circuit breakers placed sideby side,or connectingrodinterlockingis used fortwo circuit breakers placed in stack.
Steel cable interlocking or connecting rod interlocking of two circuit breakers
Note1:The transition arc at the steel cable interlock bending point is not less than {\mathsf{R120mm}} Note2:Onecircuitbreaercaeremvedfrmthelevr-threnterlockinschm,whichswthever-twonterlockingch;
HUw9 Air Circuit Breaker
Functions andFeatures
Mechanical interlocking cutout positions and dimensions(applicable forcircuit breakers mountingupto down)
Circuitbreakermaintenance
Thepurposesofcircuitbreakermaintenanceareasfollows: ·Monitortheoperatingstatusofthecircuitbreaker,todetermine whetheritisinthenormaloperatingstate; ·Predict and diagnosethe potential faults and mal-functions ofthecircuit breakerand clearthem; ·Beneficialforensuring trouble-free operationofthe circuit breaker during its life cycle.
The circuit breakerneedstobemaintained underthefollowing conditions
·Electricalfaults duetoinsulationfailure causedbyremainingforeignmatterorexcessive dust;
·Operationalfaultsandshortediecausedbyjammedpartsduetolackofmaintenanceonthecircuitbreakersinternalmechanism forlongtime,orlack of regularlubricationtothe rotating and sliding parts;
·Controlcircuitfailure,ncorrectelectricalsignalfedbackorfailedelectricalinterlockingduetopoorcontact;
·Duringlngtmperatinfthecircuitbreakerrelvantmeasurehoulbetakenifthecircuitbreakerisaffctedbyhih tmperatidittatstntifdintfailreei circuit breakerorcause it to malfunction;
·When the circuit breakertripsoran alarm accident occurs.
Whatismaintainedonthecircuitbreaker?
MakesuretenthircuitbreakfreconutinintenaneFrwithdrawalrcuitreaerthbasievicehu racked intotheDisconnected position.Verifythatthe incomingandoutgoingendsandthecontrolcircuitarenotenergized. Checkwhthrthedust,dirt,dwaterletnthircitbreefaneeleitwithdhafst it is necessaryto drythe device;
·Checkwhetherthesecondarywiringterminalsconductorsareingoodcontact,andthecrewsareloosenedoroxidized; ·Checkwhetherthefixingscrewsarelsenedoroxidizedinthemaincircuitofthecircuitbreakerandthesufaceoftheconuctiv copperbarisseverelydiscolored.There should beno discoloration onthe contactsurface;
Checkwitha50Vmeggerandmaesurethatthenulationesistancebetweenthemaincircuitfeachphaseofthecircuitbreke and betweenthedisconnected incomingandoutgoingwiringsofthecircuit breakershould notbelessthan50MQ;
·Manualharineninndlinfthiuitbreakrecaidourmalyanladtofaendtheithrawalty circuit breakerscan beracked in and out normally.
·Conductgularmaintenanceonthecircuitbreakergnceeverymnths),fortimelytroleshotingincasefanyfaults;e andopentheciruibreefivetiforeputtingintperatinafemantnance,tnurethattheircitbrentt system is in good contact
HUW9AirCircuitBreaker
Functions andFeatures
Orderinginstructions
| Product mode | HUW9-1600 | HUW9-2000 | HUW9-2500 | HUW9-3200 | HUW9-4000 | HUW9-6300 | ||||
| Rated current | 200400630800 10001250 | 630 □800 1000 125016002000 | 2500 | 20002500 3200 | 4000 | 40005000 6300 | ||||
| No. of poles Mounting method | 3 P 4 P | |||||||||
| Fixed type Withdrawable type | ||||||||||
| Intelligent centroler | Type | 2M (Economy type))口3M (Ordinary type) 2H (smart type, digital display) | 3H (smart type, LCD display ) | |||||||
| Rated voltage | AC230V AC400V DC220V DC110V DC24V | |||||||||
| Protection | Factory default settings:Ir=1ln, Tr=15s;fixed time Isd=8lr, Tsd=0.4s; inverse time Is= 4lr; li=12ln; Ig is OFF{default value Ig=In,inverse time shear coefficient k =OFF,Tg=0.4s} | |||||||||
| Long delay. Ir= In (select a value from 0.4 to1.0, or OFF) protectionlr Tr(1.5lr)=s(select a value from 15,30,60,..,960) | ||||||||||
| peramer | short-circueley | Isd= Ir (select a value from 1.5 to 15, or OFF) Fixed time Tsd = s(select a value from 0.1 to 0.4); | ||||||||
| protectionIsd | li= In(select a value from 1.0 to 20,or OFF),with the maximum of 100kA | |||||||||
| Ground protectionlg | Ig= In (select a value from 0.2to 1.0, or OFF) Tg= s (select a value from 0.1 to 1.0) Inverse time shear coefficient k= (select a value from 1.5 to 6,or OFF) | |||||||||
| Optional function | Voltage me surementFrequencymeasurementVoltage unbalance rate measurementPhase sequence detection Power measurementPowerfactormeasurementTemperature control monitoring Electricenergy measurement Zone interlock(ZSI)functionHarmonics measurementOvervoltage protectionUndervoltage protection Voltageunbalance protectionOverfrequencyprotectionUnderfrequencyprotectionPhasesequence protection ReversepowerprotectionDemand protectionDemandmeasurement(current,powerResidualoperatincurrent protectir Load monitoring function Neutral line protection Dl input function DO output function | |||||||||
| Accessories equippedas Charging motor standard | electrosiagnet | Communicationfunction:Modbusprotocol(Mic5.0standardconfiguration)Internetof thingsfunction(wifGPRS) | ||||||||
| Shunt release | AC230V AC400V AC230V AC400V | DC220V DC220V | DC110V DC110V | |||||||
| AC230V Auxiliary switch | AC400V DC220V DC110V Changeover 4NO/4NCIndependent 4NO/4NCChangeover 6NO/6NCIndependent 6NO/6NC Special type | |||||||||
| Eseutcheon,+ | )Note:HUW9-1600 device can be equipped with Changeover4NO/4NC or Changeover6NO/6NC) | |||||||||
| Uundervotage | Fixed typeWithdrawable type | |||||||||
| Self-drawn AC230V AC400V | Assisted drawn (by default) | |||||||||
| Optional | Self-drawn 0.5s 1s 3s 5s | Assisted drawn (by default) | ||||||||
| accessories Key lock | One circuit breaker with one lock and one key Three circuit breakers with three locks and twokeys | Two circuit breakers with two locks and one key Special form (customized according to user requirements) | ||||||||
| imtecharkiag | Two circuit breakers Lever interlocking (up-down interlocking) Steel cable interlocking | |||||||||
| Dualtpower | Leakage current transformerN-phase current transformerGround current transformerPoweradapter Door interlocking Relay module Protocol conversion module (Profibus-DP, Device Net) | |||||||||