CONTENT
OVERVIEW 01
SOLAR PV CABLES 04
EV CHARGER CABLES 06
HOUSEHOLD CABLES 09
Company Introduction
LESSO Group is a Hong Kong-listed (2128.HK) manufacturer of building materialswith an annual revenue of overUSD 4.38billion from its global operations.
LESSOCableisdedicated toprovidingsafe andreliablepower solutions.The company has strong scientific research,production and manufacturing capabilities.Cableproducts have the characteristics ofwearresistance,hightemperatureresistance, coldresistance,oilresistance,acid and alkaliresistance, ultravioletresistance,flameretardantandenvironmental protection,andlongservicelife.Stablepoweroutputisensured throughhigh-qualityproducts,whichmeettherequirementsof safeand efficientoperationof multi-scenepowergeneration systems.
Our Certificates
TUV 2PfG 1169/08-2007,
IEC62930:2017,EN50618:2014
ISO9001:2015
Quality Management System
ISO14001:2015
Environment ManagementSystem
ISO45001:2018
Occupational Health and Safety
Management System
Application
Suitable for PV power systems, Solar PV cable is designed for DC connections between PV modules, series cables between module strings, and parallel cables from strings to the DC distribution box, as well as from the DC distribution box to the inverter. They also serve as ACconnectionsbetween inverters and thepower grid.
Mechanical Performance
Temperature range
·Operating temperature: -40°C to +90°{C}
·Conductor temperature: +90°C
·Max. conductor temperature: +120°C for max.20,000 hours; ·Max. short-circuit temperature: +200°C for5sec;
·Expected service life:25 years.
Bendingradius
·WhentheouterdiameterDofthecableisnolargerthan 12\mathsf{mm} theallowable bendingradius should notbelessthan3D;
·When the outerdiameter Dof a cable islarger than 12\mathsf{mm} ,theallowablebending radiusshouldnotbelessthan4D.
Construction
Theinsulationonthisproductismadeof halogen-freelow-smoke cross-linked polyolefin,witha sheathmadeofhalogen-free low-smoke cross-linked polyolefin, offering oustandingflameretardantandlow-smoke properties.Theconductormeets the requirementsofGB/T3956forhighquality tinned copper conductors,providing good, stableelectrical conductivity.
| Model | Rated voltage(V) | Execution standards | |
| DC | AC(U。/U) | ||
| PV1-F | 1800 | 600/1000 | 2pfg 1169/08-2007 |
| 62930IEC131 | 1500 | 1000/1000 | IEC62930:2017 |
| H1Z2Z2-K | 1500 | 1000/1000 | EN50618:2014 |
| PV-YJYJ | 1500 | 600/1000 | NBT42073-2016 |
| Model | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 20°CMin. Insulation resistance (MQ·km) | 90°CMin. Insulation resistance (MQ·km) | Ampacity(A) | Reference weight (kg/km) | ||
| Single core in air | Single core | Two cores on the surface on the surface | ||||||||
| PV1-F | 2.5 | 5 | 5.1 | 8.21 | 100 | 0.1 | 41 | 39 | 33 | 43 |
| 4 | 5 | 5.6 | 5.09 | 100 | 0.1 | 55 | 52 | 44 | 61 | |
| 6 | 5 | 6.2 | 3.39 | 100 | 0.1 | 70 | 67 | 57 | 81 | |
| 62930IEC131 | 2.5 | 5 | 5.1 | 8.21 | 862 | 0.862 | 42 | 40 | 33 | 43 |
| 4 | 5 | 5.6 | 5.09 | 709 | 0.709 | 57 | 54 | 45 | 61 | |
| 6 | 5 | 6.2 | 3.39 | 610 | 0.61 | 72 | 69 | 58 | 81 | |
| H1Z2Z2-K | 2.5 | 5 | 5.1 | 8.21 | 690 | 0.69 | 41 | 39 | 33 | 43 |
| 4 | 5 | 5.6 | 5.09 | 580 | 0.58 | 55 | 52 | 44 | 61 | |
| 6 | 6.2 | 3.39 | 500 | 0.50 | 70 | 67 | 57 | 81 | ||
| PV-YJYJ | 2.5 | 5 | 5.1 | 8.21 | 690 | 0.69 | 41 | 39 | 33 | 43 |
| 5 | 5.6 | 5.09 | 580 | 0.58 | 55 | 52 | 44 | 61 | ||
| 6 | 5 | 6.2 | 3.39 | 500 | 0.50 | 70 | 67 | 57 | 81 | |
EV CHARGER CABLES
Application
EV charger cable series products are standard products designed according to general requirements,using the national standard GB/T 33594-2017.AC rated voltage is 450/750V, which is suitable for most electric vehicle charging scenarios and large-scale electric vehicle chargingstations.
Suitableformost charging scenarios
Low eccentricity
100%Sufficient length
Hightemperature resistance
Safetyand environmental protection
Mechanical Performance
Temperature range
·Operating temperature of type STPEthermoplasticelastomer conductor: -25°C to +70°C
·Operating temperature of type S90 TPE thermoplastic elastomer conductor: -40°C to +90°C
Bending radius
·When the outer diameterD is smaller than 25\mathsf{mm} ,thebendingradiusshouldnot belessthan4D;
·When the outer diameter D is larger than or equal to 25\mathsf{mm} ,thebendingradius shouldnotbelessthan6D.
Construction
The conductor of this product is made of high quality copper conductor, providing stable conductivity and soft performance.Theinsulation is made of thermoplasticelastomer,while the sheath is made of thermoplastic elastomer, offering excellent wear resistance.
| Nomial Voltage (V) | Conductor crosssection (ww) | Outerdiameter(mm) | 20°CMax. Insulation resistance (MQ·km) | Maximum temperatureinsulationresistance constant for normal operating conductor(MQ·km) | Ampacity (A) | ||
| Lowerlimit | Upper limit | S | S90 | ||||
| 450/750 | 3x1.0 | 10.9 | 14.0 | 19.5 | 0.037 | 3.67 | 16 |
| 3x1.5 | 11.6 | 14.9 | 13.3 | 0.037 | 3.67 | 21 | |
| 12.6 | 16.1 | 7.98 | 0.037 | 3.67 | 25 | ||
| 3x2.5 | 4.95 | 0.037 | 3.67 | 38 | |||
| 3x6 | 14.4 | 18.4 | 0.037 | 3.67 | 49 | ||
| 3x10 | 15.8 17.6 | 20.2 22.3 | 3.30 1.91 | 0.037 | 3.67 | 65 | |
| 3x16 | 20.1 | 25.4 | 1.21 | 0.037 | 3.67 | 84 | |
| 3x25 | 24.0 | 30.4 | 0.78 | 0.037 | 3.67 | 110 | |
| 3x35 | 27.7 | 35.0 | 0.554 | 0.037 | 3.67 | 135 | |
| 3x50 | 32.4 | 40.9 | 0.386 | 0.037 | 3.67 | 170 | |
| 3x70 | 37.1 | 46.8 | 0.272 | 0.037 | 3.67 | 215 | |
| 4x1.0 | 11.9 | 15.2 | 19.5 | 0.037 | 3.67 | 16 | |
| 4x1.5 | 12.6 | 16.1 | 13.3 | 0.037 | 3.67 | 22 | |
| 4x2.5 | 13.7 | 17.5 | 7.98 | 0.037 | 3.67 | 28 | |
| 4x4 | 16.0 | 20.4 | 4.95 | 0.037 | 3.67 | 37 | |
| 4x6 | 17.5 | 22.2 | 3.30 | 0.037 | 3.67 | 47 | |
| 4x10 | 19.7 | 25.0 | 1.91 | 0.037 | 3.67 | 65 | |
| 4x16 | 22.5 | 28.6 | 1.21 | 0.037 | 3.67 | 84 | |
| 4x25 | 27.2 | 34.3 | 0.78 | 0.037 | 3.67 | 110 | |
| 4x35 | 30.8 | 38.9 | 0.554 | 0.037 | 3.67 | 135 | |
| 4x50 | 36.2 | 45.6 | 0.386 | 0.037 | 3.67 | 170 | |
| 4x70 | 41.4 | 52.1 | 0.272 | 0.037 | 3.67 | 215 | |
| 5x1.0 | 12.9 | 16.4 | 19.5 | 0.037 | 3.67 | 16 | |
| 5x1.5 | 13.6 | 17.4 | 13.3 | 0.037 | 3.67 | 22 | |
| 5x2.5 | 14.9 | 19.0 | 7.98 | 0.037 | 3.67 | 28 | |
| 5x4 | 17.6 | 22.3 | 4.95 | 0.037 | 3.67 | 37 | |
| 5x6 | 19.3 | 24.5 | 3.30 | 0.037 | 3.67 | 47 | |
| 5x10 | 21.9 | 27.7 | 1.91 | 0.037 | 3.67 | 65 | |
| 5x16 | 25.0 | 31.7 | 1.21 | 0.037 | 3.67 | 84 | |
| 5x25 | 30.7 | 38.8 | 0.78 | 0.037 | 3.67 | 110 | |
| 5x35 | 34.2 | 43.1 | 0.554 | 0.037 | 3.67 | 135 | |
| 5x50 | 40.2 | 50.6 | 0.386 | 0.037 | 3.67 | 170 | |
| 5x70 | 45.9 | 57.7 | 0.272 | 0.037 | 3.67 | 215 | |
EV-RSS
| Nomial Voltage (V) | Conductor crosssection (mm²) | Outerdiameter(mm) | 20°C Max. Insulation resistance (MQ·km) | Maximum temperature insulationresistance constant fornormal operating conductor(MQ·km) | Ampacity (A) | ||
| Lower limit | Upper limit | S | S90 | ||||
| 450/750 | 3x1.0 | 12.3 | 15.7 | 19.5 | 0.037 | 3.67 | 16 |
| 3x1.5 | 12.9 | 16.6 | 13.3 | 0.037 | 3.67 | 21 | |
| 3x2.5 | 13.9 | 17.8 | 7.98 | 0.037 | 3.67 | 25 | |
| 16.1 | 20.5 | 4.95 | 0.037 | 3.67 | 38 | ||
| 3x6 | 17.4 | 22.1 | 3.30 | 0.037 | 3.67 | 49 | |
| 3x10 | 19.3 | 24.5 | 1.91 | 0.037 | 3.67 | 65 | |
| 3x16 | 21.6 | 27.4 | 1.21 | 0.037 | 3.67 | 84 | |
| 3x25 | 25.7 | 32.5 | 0.78 | 0.037 | 3.67 | 110 | |
| 3x35 | 29.7 | 37.6 | 0.554 | 0.037 | 3.67 | 135 | |
| 3x50 | 34.5 | 43.4 | 0.386 | 0.037 | 3.67 | 170 | |
| 3x70 | 39.2 | 49.3 | 0.272 | 0.037 | 3.67 | 215 | |
| 4x1.0 | 13.2 | 16.9 | 19.5 | 0.037 | 3.67 | 16 | |
| 4x1.5 | 13.9 | 17.8 | 13.3 | 0.037 | 3.67 | 22 | |
| 4x2.5 | 15.3 | 19.4 | 7.98 | 0.037 | 3.67 | 28 | |
| 4x4 | 17.6 | 22.3 | 4.95 | 0.037 | 3.67 | 37 | |
| 4x6 | 19.2 | 24.4 | 3.30 | 0.037 | 3.67 | 47 | |
| 4x10 | 21.4 | 27.1 | 1.91 | 0.037 | 3.67 | 65 | |
| 4x16 | 24.3 | 30.7 | 1.21 | 0.037 | 3.67 | 84 | |
| 4x25 | 29.2 | 36.8 | 0.78 | 0.037 | 3.67 | 110 | |
| 4x35 | 32.8 | 41.4 | 0.554 | 0.037 | 3.67 | 135 | |
| 4x50 | 38.2 | 48.1 | 0.386 | 0.037 | 3.67 | 170 | |
| 4x70 | 43.2 | 54.4 | 0.272 | 0.037 | 3.67 | 215 | |
| 5x1.0 | 14.2 | 1.81 | 19.5 | 0.037 | 3.67 | 16 | |
| 5x1.5 | 15.2 | 19.3 | 13.3 | 0.037 | 3.67 | 22 | |
| 5x2.5 | 16.4 | 20.9 | 7.98 | 0.037 | 3.67 | 28 | |
| 5x4 | 19.3 | 24.5 | 4.95 | 0.037 | 3.67 | 37 | |
| 5x6 | 20.8 | 26.4 | 3.30 | 0.037 | 3.67 | 47 | |
| 5x10 | 23.6 | 29.9 | 1.91 | 0.037 | 3.67 | 65 | |
| 5x16 | 26.8 | 33.8 | 1.21 | 0.037 | 3.67 | 8 | |
| 5x25 | 32.5 | 41.0 | 0.78 | 0.037 | 3.67 | 110 | |
| 5x35 | 36.2 | 45.6 | 0.554 | 0.037 | 3.67 | 135 | |
| 5x50 | 42.0 | 52.9 | 0.386 | 0.037 | 3.67 | 170 | |
| 5x70 | 48.1 | 60.5 | 0.272 | 0.037 | 3.67 | 215 | |
Application
Suitableforpower devices,household appliances,instruments and electronic equipment at a rated AC voltages of 450/750V and below, assuming maximum ambient temperature is not above 50°C and featuringfixed mounting inrooms,cabletrenches,directburied pipelines orotherfixedapplications.
Mechanical Performance
Temperature range
·Max.operatingtemperatureforPVCinsulatedcableconductor: +70°C
·Max. operating temperature for polyolefin insulated cable: +90°C
·Max. operating temperature for cross-linked polyolefin cable: +90°{C} +105°C +125°C · Max. duration of cable short circuit: 5 sec;
·Max.temperatureforpolyvinylchlorideinsulatedcableconductor: +160°C
·Max.temperatureforpolyolefin insulatedcable and cross-linkedpolyolefin insulated cableconductor: +250°C
Bending radius
·WhentheouterdiameterDissmallerthan 25mm ,thebendingradiusshouldnot belessthan4D;
·When the outer diameter D is larger than or equal to 25\mathsf{mm} ,thebendingradius shouldnotbelessthan6D.
Construction
The conductor is made of high quality copper conductor or aluminum conductor, which offers excellentelectricalconductivity,oxidationresistance andthermalconductivity.Theinsulationand sheath of the product are made of high quality polyvinyl chloride polymer or polyolefin polymer, which have excellent insulation properties, aging resistance and non-delayed burning properties.
| Model | Executionstandards |
| 60227IEC01(BV) | GB/T5023.3-2008/IEC60227-3:1997 |
| 60227IEC05(BV) | |
| ZC-60227IEC01(BV) | GB/T19666-2019/GB/T5023.3-2008/IEC |
| ZC-60227IEC05(BV) | 60227-3:1997 |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20℃ Max.DCresistance | 70°C Min. Insulation | Ampacity (A) | Reference weight(kg/km) | NH | |||
| (Q/km) Copper Aluminium | resistance (MQ·km) | Aluminium Copper | Common/ZR Aluminium | ||||||||
| 300/500 | 0.75 | 1 | 2.2 | 24.5 | " | Copper 0.012 | 14 | 11 | Copper 15 | ||
| 0.75 | 2 | 2.3 | 24.5 | 0.014 | 14 | 11 | 15 | ||||
| 1.0 | 1 | 2.3 | 18.1 | 0.011 | 16 | - | 14 | 18 | |||
| 1.0 | 2 | 2.5 | 18.1 | 0.013 | 16 | 14 | 18 | ||||
| 450/750 | 1.5 | 1 | 2.8 | 12.1 | 0.011 | 21 | - | 20 | - | 25 | |
| 1.5 | 2 | 3.0 | 12.1 | 0.010 | 21 | - | 20 | - | 25 | ||
| 2.5 | 1 | 3.4 | 7.41 | 12.1 | 0.010 | 25 | 24 | 32 | 16 | 37 | |
| 2.5 | 2 | 3.6 | 7.41 | 0.009 | 25 | 32 | 37 | ||||
| 4.0 | 1 | 3.9 | 4.61 | 7.41 | 0.0085 | 38 | 32 | 46 | 22 | 53 | |
| 4.0 | 2 | 4.1 | 4.61 | 0.0077 | 38 | 46 | 53 | ||||
| 6.0 | 1 | 4.4 | 3.08 | 4.61 | 0.0070 | 49 | 43 | 66 | 31 | 74 | |
| 6.0 | 2 | 4.7 | 3.08 | 0.0065 | 49 | 66 | 74 | ||||
| 10 | 2 | 6.0 | 1.83 | 3.08 | 0.0065 | 68 | 55 | 115 | 53 | 117 | |
| 16 | 2 | 7.1 | 1.15 | 1.91 | 0.0050 | 91 | 75 | 173 | 75 | 174 | |
| 25 | 2 | 8.8 | 0.727 | 1.20 | 0.0050 | 120 | 96 | 269 | 117 | 269 | |
| 35 | 2 | 9.9 | 0.524 | 0.868 | 0.0040 | 150 | 115 | 370 | 152 | 368 | |
| 50 | 2 | 11.7 | 0.387 | 0.641 | 0.0045 | 180 | 140 | 493 | 202 | 489 | |
| 70 | 2 | 13.4 | 0.268 | 0.443 | 0.0035 | 230 | 180 | 694 | 272 | 687 | |
| 95 | 2 | 15.7 | 0.193 | 0.320 | 0.0035 | 290 | 215 | 696 | 372 | 948 | |
| 120 | 2 | 17.3 | 0.153 | 0.253 | 0.0032 | 335 | 255 | 1182 | 448 | 1174 | |
| 150 | 2 | 19.2 | 0.124 | 0.206 | 0.0032 | 390 | 290 | 1453 | 552 | 1432 | |
| 185 | 2 | 21.4 | 0.0991 | 0.164 | 0.0032 | 450 | 335 | 1820 | 694 | 1795 | |
| 240 | 2 | 24.5 | 0.0754 | 0.125 | 0.0032 | 545 | 400 | 2373 | 886 | 2351 | |
| 300 | 2 | 27.2 | 0.0601 | 0.100 | 0.0030 | 630 | 465 | 2966 | 1101 | 2926 | |
| 400 | 2 | 30.7 | 0.0470 | 0.0778 | 0.0028 | 735 | 550 | 3785 | 1396 | 3736 | |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Outer diameter (mm) | 20℃ Max.DCresistance (Q/km) | 70°C Min. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 450/750 | 0.75 | 2.5 | 24.5 | 0.013 | 14 | 15.2 |
| 1.0 | 2.7 | 18.1 | 0.012 | 16 | 15.8 | |
| 1.5 | 3.0 | 12.1 | 0.011 | 21 | 21.1 | |
| 2.5 | 3.7 | 7.41 | 0.011 | 25 | 33.6 | |
| 4.0 | 4.2 | 4.61 | 0.009 | 38 | 49.6 | |
| 6.0 | 4.8 | 3.08 | 0.0084 | 49 | 70.6 | |
| 10 | 6.7 | 1.83 | 0.0072 | 68 | 121.9 | |
| 16 | 7.8 | 1.15 | 0.0062 | 91 | 175.7 | |
| 25 | 10.1 | 0.727 | 0.0058 | 120 | 287.3 | |
| 35 | 11.1 | 0.524 | 0.0052 | 150 | 377.4 | |
| 50 | 13.0 | 0.387 | 0.0051 | 180 | 518.4 | |
| 70 | 15.4 | 0.268 | 0.0045 | 230 | 719.7 | |
| 95 | 17.5 | 0.193 | 0.0044 | 290 | 961.9 | |
| 120 | 19.2 | 0.153 | 0.0040 | 335 | 1187.4 | |
| 150 | 21.7 | 0.124 | 0.0040 | 390 | 1463.6 | |
| 185 | 24.0 | 0.0991 | 0.0040 | 450 | 1830.7 |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 70°C Min. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/500 | 0.75 | 1 | 2.2 | 24.5 | 0.012 | 14 | 11 |
| 0.75 | 2 | 2.3 | 24.5 | 0.014 | 14 | 11 | |
| 1.0 | 1 | 2.3 | 18.1 | 0.011 | 16 | 14 | |
| 1.0 | 2 | 2.5 | 18.1 | 0.013 | 16 | 14 | |
| 1.5 | 1 | 2.8 | 12.1 | 0.011 | 21 | 20 | |
| 450/750 | 1.5 | 2 | 3.0 | 12.1 | 0.010 | 21 | 20 |
| 2.5 | 1 | 3.4 | 7.41 | 0.010 | 25 | 32 | |
| 2.5 | 2 | 3.6 | 7.41 | 0.009 | 25 | 32 | |
| 4.0 | 1 | 3.9 | 4.61 | 0.0085 | 38 | 46 | |
| 4.0 | 2 | 4.1 | 4.61 | 0.0077 | 38 | 46 | |
| 6.0 | 1 | 4.4 | 3.08 | 0.0070 | 49 | 66 | |
| 6.0 | 2 | 4.7 | 3.08 | 0.0065 | 49 | 66 | |
| 10 | 2 | 6.0 | 1.83 | 0.0065 | 68 | 115 | |
| 16 | 2 | 7.1 | 1.15 | 0.0050 | 91 | 173 | |
| 25 | 2 | 8.8 | 0.727 | 0.0050 | 120 | 269 | |
| 35 | 2 | 9.9 | 0.524 | 0.0040 | 150 | 370 |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 70°C Min. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/500 | 0.75 | 5 | 2.3 | 26.0 | 0.011 | 14 | 12 |
| 1.0 | 5 | 2.5 | 19.5 | 0.010 | 16 | 15 | |
| 450/750 | 1.5 | 5 | 3.0 | 13.3 | 0.010 | 21 | 21 |
| 2.5 | 5 | 3.9 | 7.89 | 0.009 | 25 | 34 | |
| 4.0 | 5 | 4.6 | 4.95 | 0.007 | 38 | 50 | |
| 6.0 | 5 | 5.3 | 3.30 | 0.006 | 49 | 71 | |
| 10 | 5 | 6.8 | 1.91 | 0.0056 | 68 | 118 | |
| 16 | 5 | 7.9 | 1.21 | 0.0046 | 91 | 176 | |
| 25 | 5 | 9.8 | 0.780 | 0.0044 | 120 | 275 | |
| 35 | 5 | 11 | 0.554 | 0.0038 | 150 | 366 |
| Nomial Voltage (V) | Nominal cross cection (mm) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 70°C Min. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/500 | 1.0 | 2 | 3.1 | 18.1 | 0.010 | 14 | 17 |
| 450/750 | 1.5 | 2 | 3.4 | 12.1 | 0.010 | 21 | 23 |
| 2.5 | 2 | 4.1 | 7.41 | 0.010 | 33 | 35 | |
| 4.0 | 2 | 4.8 | 4.61 | 0.0079 | 48 | 52 | |
| 6.0 | 2 | 5.3 | 3.08 | 0.0068 | 68 | 72 | |
| 10 | 2 | 7.3 | 1.83 | 0.0066 | 114 | 124 | |
| 16 | 2 | 8.6 | 1.15 | 0.0054 | 171 | 182 | |
| 25 | 2 | 10.2 | 0.727 | 0.0051 | 266 | 292 | |
| 35 | 2 | 11.7 | 0.524 | 0.0043 | 365 | 381 |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20°℃ Max.DCresistance (Q/km) | Ampacity (A) | Reference weight (kg/km) | ||||
| Copper | Aluminium | Copper | Aluminium | WDZ-BYJ Copper | Aluminium | WDZN-BYJ Copper | ||||
| 300/500 | 0.75 | 1 | 2.2 | 24.5 | 18 | 11 | 15 | |||
| 0.75 | 2 | 2.3 | 24.5 | 18 | - | 11 | 15 | |||
| 1.0 | 1 | 2.3 | 18.1 | - | 22 | 14 | ||||
| 1.0 | 2 | 2.5 | 18.1 | 22 | 14 | 19 19 | ||||
| 1 | 2.8 | 12.1 | " | 28 | 21 | 26 | ||||
| 450/750 | 1.5 1.5 | 2 | 3.0 | 12.1 | - | 28 | 21 | 26 | ||
| 2.5 | 3.4 | " | 41 | 33 | ||||||
| 2.5 | 1 | 7.41 | 41 | - | 39 | |||||
| 2 | 3.6 | 7.41 | - | 54 | 33 | 39 | ||||
| 4.0 | 1 | 3.9 | 4.61 | - | 48 | 55 | ||||
| 4.0 | 2 | 4.1 | 4.61 | 54 | 48 | 55 | ||||
| 6.0 | 1 | 4.4 | 3.08 | - | 68 | 68 | 76 | |||
| 6.0 | 2 | 4.7 | 3.08 | " | 68 | 68 | 76 | |||
| 10 | 2 | 6.0 | 1.83 | 93 | 114 | 125 | ||||
| 16 | 2 | 7.1 | 1.15 | - | 120 | - | 171 | - | 184 | |
| 25 | 2 | 8.8 | 0.727 | 155 | 266 | 282 | ||||
| 35 | 2 | 9.9 | 0.524 | - | 195 | 365 | 383 | |||
| 50 | 2 | 11.7 | 0.387 | - | 235 | 492 | 513 | |||
| 70 | 2 | 13.4 | 0.268 | 295 | 690 | 715 | ||||
| 96 | 2 | 15.7 | 0.193 | " | 370 | 953 | 981 | |||
| 120 | 2 | 17.3 | 0.153 | - | 430 | 1179 | 1211 | |||
| 150 185 | 2 | 19.2 | 0.124 | 495 | 1449 | 1484 | ||||
| 2 | 21.4 | 0.0991 | 570 | 1815 | 1855 | |||||
| 240 | 2 | 24.5 | 0.0754 | 680 | - | 2376 | 2421 | |||
| 300 | 2 | 27.2 | 0.0601 | 790 | - | 2969 | 3018 | |||
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20℃C Max.DC resistance (Q/km) | 70°CMin. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) | |||
| Copper | Aluminium | Copper | Aluminium | Copper | Aluminium | |||||
| 300/500 | 0.75 | 1 | 3.8 | 24.5 | 0.012 | 14 | 22 | |||
| 0.75 2 | 3.9 24.5 | 0.014 | 14 | - | 22 | |||||
| 1.0 | 1 | 3.9 | 18.1 | 0.011 | 16 | 25 | ||||
| 1.0 | 2 | 4.1 | 18.1 | - | 0.013 | 16 | 25 | |||
| 1.5 | 1 | 4.4 | 12.1 | 0.011 | 21 | 33 | ||||
| 1.5 | 2 | 4.6 | 12.1 | 0.010 | 21 | 33 | ||||
| 2.5 | 1 | 5.0 | 7.41 | 12.1 | 0.010 | 25 | 24 | 47 | 32 | |
| 2.5 | 2 | 5.2 | 7.41 | 0.009 | 25 | - | 47 | |||
| 4.0 | 1 | 5.7 | 4.61 | 7.41 | 0.0085 | 88 | 32 | 66 | 42 | |
| 4.0 | 2 | 5.9 | 4.61 | 0.0077 | 38 | 66 | ||||
| 6.0 | 1 | 6.2 | 3.08 | 4.61 | 0.0070 | 49 | 43 | 88 | 53 | |
| 6.0 | 2 | 6.5 | 3.08 | 0.0065 | 49 | - | 88 | |||
| 10 | 2 | 7.8 | 1.83 | 3.08 | 0.0065 | 68 | 55 | 114 | 82 | |
| 16 | 2 | 8.9 | 1.15 | 1.91 | 0.0050 | 91 | 75 | 206 | 108 | |
| 25 | 2 | 10.8 | 0.727 | 1.20 | 0.0050 | 120 | 96 | 314 | 162 | |
| 35 | 2 | 12.1 | 0.524 | 0.868 | 0.0040 | 150 | 115 | 426 | 207 | |
| 50 | 2 | 14.3 | 0.387 | 0.641 | 0.0045 | 180 | 140 | 571 | 280 | |
| 70 | 2 | 16.2 | 0.268 | 0.443 | 0.0035 | 230 | 180 | 789 | 367 | |
| 95 | 2 | 18.7 | 0.193 | 0.320 | 0.0035 | 290 | 215 | 1078 | 491 | |
| 120 | 2 | 20.5 | 0.153 | 0.253 | 0.0032 | 335 | 255 | 1321 | 587 | |
| 150 | 2 | 22.8 | 0.124 | 0.206 | 0.0032 | 390 | 290 | 1626 | 726 | |
| 185 | 2 | 25.2 | 0.0991 | 0.164 | 0.0032 | 450 | 335 | 2023 | 868 | |
| 240* | 2 | 27.7 | 0.0754 | 0.125 | 0.0032 | 545 | 400 | 2565 | 1087 | |
| 300* | 2 | 30.6 | 0.0601 | 0.100 | 0.0030 | 630 | 465 | 3191 | 1327 | |
| 400* | 2 | 34.3 | 0.0470 | 0.0778 | 0.0028 | 735 | 550 | 4053 | 1662 | |
| Nomial Voltage (V) | Nominal cross cection (mm) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 70°CMin. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/500 | 0.75 | 5 | 2.3 | 26.0 | 0.014 | 14 | 12 |
| 1.0 | 5 | 2.5 | 19.5 | 0.011 | 16 | 15 | |
| 450/750 | 1.5 | 5 | 3.0 | 13.3 | 0.010 | 21 | 21 |
| 2.5 | 5 | 3.9 | 7.89 | 0.009 | 25 | 34 | |
| 4.0 | 5 | 4.6 | 4.95 | 0.007 | 38 | 50 | |
| 6.0 | 5 | 5.3 | 3.30 | 0.006 | 49 | 71 | |
| 10 | 5 | 6.8 | 1.91 | 0.0056 | 68 | 118 | |
| 16 | 5 | 7.9 | 1.21 | 0.0046 | 91 | 176 | |
| 25 | 5 | 9.8 | 0.780 | 0.0044 | 120 | 275 | |
| 35 | 5 | 11.0 | 0.554 | 0.0038 | 150 | 366 | |
| 50 | 5 | 13.7 | 0.386 | 0.0037 | 180 | 538 | |
| 70 | 5 | 15.7 | 0.272 | 0.0032 | 230 | 735 | |
| S6 | 5 | 18.3 | 0.206 | 0.0032 | 290 | 921 | |
| 120 | 5 | 20.3 | 0.161 | 0.0029 | 335 | 1158 | |
| 150 | 5 | 23.2 | 0.129 | 0.0029 | 390 | 1447 | |
| 185 | 5 | 25.1 | 0.106 | 0.0029 | 450 | 1766 | |
| 240 | 5 | 34.7 | 0.0801 | 0.0028 | 545 | 2360 |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20℃ Max.DC resistance (Q/km) | 70°C Min. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/300 | 2x0.75 | 6 | 5.72 | 26.0 | 0.013 | 12 | 22 |
| 2×1.0 | 6 | 6.20 | 19.5 | 0.012 | 14 | 30 | |
| 2×1.5 | 6 | 6.86 | 13.3 | 0.009 | 18 | 37 | |
| 2×2.5 | 6 | 8.26 | 7.89 | 0.009 | 25 | 48 | |
| 2×4.0 | 6 | 9.30 | 4.95 | 0.007 | 33 | 71 | |
| 2x6.0 | 6 | 11.9 | 3.30 | 0.006 | 42 | 105 |
Application
RVV type cables are suitable for medium and light mobile electrical appliances, instruments, household appliances, power equipment, lighting equipment and other soft ormobileapplicationswithratedvoltagesof300/50oVandbelow.
YJV typelow-voltage power cables are suitable for fixed laying on the transmission and distributionlines of electricpower,construction,metallurgy and otherindustries with ratedvoltagesof600/1000Vandbelow,inindoor,cabletrench,directburiedpipeline andotherfixedapplications.
Wide applicability
Low eccentricity
High temperature resistance
Safety and environmental protection
Flameretardant insulation
Mechanical Performance
Temperature range
·Max.operating temperatureforPVCinsulatedcable conductor: +70°C ·Max.operating temperature for cross-linked polyolefin cable: +90°{C} · Max. duration of cable short circuit: 5 sec; · Max. temperature for polyvinyl chloride insulated cable conductor: +160°C · Max. temperature for cross-linked polyolefin insulated cable conductor: +250°C
Bending radius
·TheRvVcablebendingradiusshouldnotexceed7D;
· Low-voltage cable and single-core unarmored cable bending radius should not exceed20D;
·Thebendingradiusofasingle-corearmoredcableshouldnotexceed15D;
·Thebendingradiusofamulti-coreunarmoredcableshouldnotexceed15D;
·The bending radius of a multi-core armored cable should not exceed 12D.
Construction
The conductor is made of high quality copper, aluminum or aluminum alloy conductor, offeringoutstandingelectrical conductivity,oxidationresistance and thermalconductivity.The insulationof theproduct ismadeofhighqualitypolyvinyl chlorideor crosslinked polyethylene, providing good insulation properties, mechanical properties, aging resistance and other characteristics.The sheath of theproduct is made of high quality polyvinyl chloride or low smoke halogen-free polyolefin, offering excellent agingresistance,oil resistance,wear resistance,andnon-delayfireresistance.
| Nomial Voltage (V) | Nominal cross cection (mm²) | Conductor type | Outer diameter (mm) | 20°℃ Max.DC resistance (Q/km) | 70°CMin. Insulation resistance (MQ·km) | Ampacity (A) | Reference weight (kg/km) |
| 300/500 | 2x0.75 | 5 | 6.8 | 26.0 | 0.011 | 14 | 47 |
| 2x1.0 | 5 | 7.1 | 19.5 | 0.010 | 16 | 54 | |
| 2x1.5 | 5 | 8.0 | 13.3 | 0.010 | 21 | 70 | |
| 2x2.5 | 5 | 10.1 | 7.98 | 0.009 | 25 | 111 | |
| 2x4.0 | 5 | 11,7 | 4.95 | 0.007 | 38 | 157 | |
| 2x6.0 | 5 | 13.2 | 3.30 | 0.006 | 49 | 207 | |
| 2x10 | 5 | 16.3 | 1.91 | 0.0056 | 68 | 326 | |
| 3x0.75 | 5 | 7.2 | 26.0 | 0.011 | 14 | 60 | |
| 3x1.0 | 5 | 7.5 | 19.5 | 0.010 | 16 | 70 | |
| 3x1.5 | 5 | 8.7 | 13.3 | 0.010 | 21 | 97 | |
| 3x2.5 | 5 | 10.9 | 7.98 | 0.009 | 25 | 153 | |
| 3x4.0 | 5 | 12.7 | 4.95 | 0.007 | 38 | 217 | |
| 3x6.0 | 5 | 14.3 | 3.30 | 0.006 | 49 | 289 | |
| 4x0.75 | 5 | 7.8 | 26.0 | 0.011 | 14 | 75 | |
| 4x1.0 | 5 | 8.4 | 19.5 | 0.010 | 16 | 91 | |
| 4x1.5 | 5 | 9.6 | 13.3 | 0.010 | 21 | 126 | |
| 4x2.5 | 5 | 11.9 | 7.98 | 0.009 | 25 | 192 | |
| 4x4.0 | 5 | 13.9 | 4.95 | 0.007 | 38 | 275 | |
| 4x6.0 | 5 | 15.7 | 3.30 | 0.006 | 49 | 369 | |
| 5x0.75 | 5 | 8.7 | 26.0 | 0.011 | 14 | 93 | |
| 5x1.0 | 5 | 9.1 | 19.5 | 0.010 | 16 | 109 | |
| 5x1.5 | 5 | 10.7 | 13.3 | 0.010 | 21 | 156 | |
| 5x2.5 | 5 | 13.2 | 7.98 | 0.009 | 25 | 237 | |
| 5x4.0 | 5 | 15.5 | 4.95 | 0.007 | 38 | 347 | |
| 5x6.0 | 5 | 18.6 | 3.30 | 0.006 | 49 | 499 |
| Nomial Voltage (M) | Nominal cross cection (mm²) | Outer diameter (mm) | Ampacity(A) | |||
| Laid in air | Buried laying | |||||
| 600/1000 | 3×16+1×10 | 18.6 | Copper 84 | Aluminum 99 | Copper 110 | Aluminum 98 |
| 3×25+1×16 | 110 | 87 | 140 | 110 | ||
| 3x35+1×16 | 22.1 23.9 | 135 | 105 | 170 | 130 | |
| 3x50+1×25 | 27.4 | 170 | 130 | 205 | 160 | |
| 3×70+1x35 | 31.9 | 215 | 165 | 250 | 195 | |
| 3x95+1x50 | 36.0 | 265 | 205 | 300 | 235 | |
| 3×120+1×70 | 40.3 | 310 | 240 | 345 | 265 | |
| 3×150+1×70 | 44.2 | 350 | 270 | 385 | 300 | |
| 3x185+1x95 | 49.2 | 405 | 315 | 435 | 340 | |
| 3×240+1×120 | 54.7 | 480 | 375 | 500 | 395 | |
| 3×300+1×150 | 60.7 | 555 | 435 | 565 | 445 | |
| 3×400+1×185 | 68.4 | 640 | 510 | 640 | 510 | |
| 3x16+2×10 | 19.9 | 84 | 65 | 110 | 85 | |
| 3×25+2×16 | 23.5 | 110 | 87 | 140 | 110 | |
| 3x35+2×16 | 25.2 | 135 | 105 | 170 | 130 | |
| 3x50+2×25 | 29.3 | 170 | 130 | 205 | 160 | |
| 3×70+2×35 | 33.9 | 215 | 165 | 250 | 195 | |
| 3×95+2×50 | 38.4 | 265 | 205 | 300 | 235 | |
| 3×120+2×70 | 43.3 | 310 | ||||
| 3x150+2×70 | 46.8 | 350 | 240 | 345 | 265 | |
| 3x185+2x95 | 52.1 | 270 | 385 | 300 | ||
| 405 | 315 | 435 | 340 | |||
| 3×240+2×120 | 58.0 | 480 | 375 | 500 | ||
| 3×300+2×150 | 64.4 | 555 | 435 | 565 | 445 | |
| 4×10+1×6 | 17.7 | 65 | 50 | 86 | 66 | |
| 4×16+1×10 | 20.4 | 84 | 65 | 110 | 85 | |
| 4×25+1×16 | 24.4 | 110 | 87 | 140 | 110 | |
| 4×35+1×16 | 26.6 | 135 | 105 | 170 | 130 | |
| 4x50+1×25 | 30.6 | 170 | 130 | 205 | 160 | |
| 4×70+1x35 4×95+1×50 | 35.9 | 215 | 165 | 250 | 195 | |
| 4×120+1×70 | 40.3 45.3 | 265 | 205 | 300 | 235 | |
| 4×150+1×70 | 310 | 240 | 345 | 265 | ||
| 49.8 | 350 | 270 | 385 | 300 | ||
| 4×185+1×95 | 55.4 | 405 | 315 | 435 | 340 | |
| 4×240+1×120 | 61.6 | 480 | 375 | 500 | 96 | |
| 4×300+1×150 | 68.3 | 555 | 435 | 565 | 445 | |
| Nomial Voltage (V) | Nominal cross cection (mm²) | Outer diameter (mm) | Ampacity(A) | |||
| Laid in air | Buried laying | |||||
| 600/1000 | 3×16+1×10 | 20.6 | Copper 83 | Aluminum 64 | Copper | Aluminum |
| 110 | 85 | |||||
| 3×25+1×16 | 24.1 | 110 | 86 | 140 | 110 130 | |
| 3x35+1×16 | 25.9 | 135 | 105 | 170 | 155 | |
| 3×50+1×25 | 29.4 | 165 | 125 | 200 | ||
| 3×70+1×35 3x95+1×50 | 34.1 39.8 | 210 260 | 165 | 245 | 190 | |
| 3×120+1×70 | 44.3 | 305 | 200 235 | 300 | 230 260 | |
| 3×150+1×70 | 48.2 | 345 | 270 | 335 | 295 | |
| 3x185+1x95 | 53.6 | 395 | 380 | |||
| 59.1 | 465 | 310 | 430 | 335 | ||
| 3×240+1×120 3x300+1×150 | 64.9 | 535 | 365 | 500 | 390 | |
| 3x400+1×185 | 72.8 | 620 | 420 495 | 565 | 440 | |
| 21.9 | 83 | 64 | 650 | 505 | ||
| 3×16+2×10 | 25.5 | 110 | 110 | 85 | ||
| 3×25+2×16 | 27.2 | 135 | 86 | 140 | 110 | |
| 3×35+2×16 | 31.3 | 165 | 105 | 170 | 130 | |
| 3x50+2×25 3×70+2x35 | 35.9 | 210 | 125 165 | 200 | 155 | |
| 3x95+2×50 | 42.2 | 260 | 245 | 190 | ||
| 3×120+2×70 | 47.3 | 200 | 300 | 230 | ||
| 3×150+2×70 | 50.8 | 305 | 235 | 335 | 260 | |
| 345 | 270 | 380 | 295 | |||
| 3x185+2x95 | 56.5 | 310 | 430 | 335 | ||
| 3×240+2×120 | 62.4 | 465 | 365 | 500 | 390 | |
| 3x300+2×150 | 68.8 | 535 | 420 | 565 | 440 | |
| 4×16+1×10 4×25+1×16 | 22.4 | 83 | 64 | 110 | 85 | |
| 4x35+1×16 | 26.4 | 110 | 86 | 140 | 110 | |
| 28.6 | 135 | 105 | 170 | 130 | ||
| 4×50+1×25 | 32.8 | 165 | 125 | 200 | 155 | |
| 4×70+1×35 | 39.1 | 210 | 165 | 245 | 190 | |
| 4x95+1x50 4×120+1×70 | 44.3 | 260 | 200 | 300 | 230 | |
| 4×150+1×70 | 49.1 | 305 | 235 | 335 | 260 | |
| 4×185+1x95 | 54.2 | 345 | 270 | 380 | 295 | |
| 59.8 | 395 | 310 | 430 | 335 | ||
| 4×240+1×120 | 66.0 | 465 | 365 | 500 | 390 | |
| 4x300+1×150 | 72.7 | 535 | 420 | 565 | 440 | |
| 4x400+1×185 | 82.9 | 620 | 495 | 650 | 505 | |