KG316TG Time Switch
1.Scope Of Application
2.Type Definition
1
3.Operational Condition
Suitable for AC 50Hz, rated control power supply voltage AC 220V and
below the control circuit, as a delay timing element.
The power supply of various control circuits can be switched on or off at a
predetermined time, which is suitable for lamps, neon lights, advertising
signs, radio and television equipment and various household appliances.
3.1 Use environment: the altitude does not exceed 2000 meters;
3.2 The ambient temperature is not higher than +40℃ and not lower than
-5℃;
3.3 The rated control power supply voltage changes to 85%-110% of the
rated voltage;
3.4 In a medium without serious vibration and explosion risk, and there is no
gas and dust in the medium sufficient to corrode metal and destroy insulation;
3.5 Where rain and snow can't erode.
KG 316 T G -
Switch
Design sequence number
Time control
improved
Rated voltage Us
4.Structure Characteristics
5.Technical Characteristics
6.Installation Use Operation
This series of time-control switch adopts eight-bit microprocessor chip, can
be directly packaged on PCB board, peripheral use patch components,
surface mounting, LCD LCD display, high-power relay output; Compact
structure can be mounted on guide rails.
5.1 Rated insulation voltage Ui: AC 220V
5.2 Rated impulse withstand voltage Uimp: AC 1.5kV
5.3 Rated control power supply voltage Us: AC 220V
5.4 Pollution Level: 3
5.5 Enclosure Protection class: IP20
5.6 Load power: (resistive load: 6KW; Inductive load: 1.8KW; Motor load:
1.2KW; Lamp load: 0.9KW)
5.7 Daily travel time error: less than or equal to ±2 seconds;
5.8 You can set 16 on and 16 off actions per day;
5.9 The switching time can be cycled daily or weekly;
5.10 The maximum time control is 168 hours, the minimum time control is 1
minute;
5.11 Mechanical life: greater than or equal to 1 million times;
5.12 Electrical life: more than or equal to 100,000 times;
5.13 Coordination with the short circuit protector (SCPD) is enough. The
relay should not cause harm to people and equipment under short circuit
conditions, and should not be allowed to continue to use before repair or
replacement of parts.
6.1 Press and hold the “Cancel/Restore ”key to power on the device
6.2 If you do not operate the keyboard for 30 seconds, it will automatically
lock, and the sign “ ” is displayed in the lower left corner.
2
UNIT:(mm)
Installation using 35.3mm standard guide rail
N IN L
N OUT L
36.0 42.7 80.6 35.3 45.6
65.3
7.Product outline and installation dimensions
1
2
3
4
5
6
7
8
9
Press the“TMG”key Enter the timed start setting display“on1”
Entering the timed shutdown setting display“1off”
Set the time to open on a certain day or day or every day of the week
Enter the scheduled start setting and display settings. Set the time for
this shutdown to be on a certain day or day of the week
Set the time for automatic opening
Set an automatic shutdown time
Set the switch time for the remaining 2-16 times. If timing is not
required, make it display:“--:--”
End timing setting and return to clock running state
End the timing setting, return to the clock running state, point the switch
flag to the \"off\" position, and then adjust to the \"automatic\" position
Press the“D+”key
Press the“D+”key
Repeat the process from 1 to 6
Press the“TMG”key
Press the“CLK”key
Press the“A/M”key
Press the \"H+\" and \"M+\"
buttons respectively
Press the \"H+\" and \"M+\"
buttons respectively
STEP KEY SET CONTENT
6.3 Unlocking: Press the “Cancel/Resume” button 4 times to automatically
unlock, and the symbol “ ” disappears..
6.4 After unlocking, press “Calibration Week”, “Calibration Time”, and
“Calibration Score” to calibrate the time.
6.5 Set the switch time according to the steps in the table below.
3
N IN L
N OUT L
INPUT TERMINAL
N L
Upper incoming and lower outgoing lines
N OUT L
N IN L
INPUT TERMINAL
N L
LOWER INCOMING AND UPPER OUTGOING LINES
LOAD:220V
8.Precautions For Operation
8.1 To prevent contact heating under strong current, it is necessary to tighten
the screws on the wire post during wiring.
8.2 It is strictly prohibited to install or disassemble products with electricity.
8.3 If you do not use it for a long time and press the “time calibration” and
“minute calibration” buttons for 3 seconds, you will enter a sleep state;
Release the sleep state, press and hold the “Cancel/Resume” button for 5
seconds, and re-enter use (note: In the sleep state, all the original set data is
cleared, and after restarting, it enters the factory state).
8.4 For equipment that may cause significant economic losses or personal
safety, it is important to design with sufficient margin for technical characteristics and performance values, and safety facilities such as double circuit
protection should be used.
4
9.Common fault
9.1 The time control switch after power on operation is not working properly. Check whether the time control switch period setting meets the required
requirements, and whether the week setting is set in the \"automatic\"
position.
9.2 When the time control switch reaches the set time, the output indicator
light is on, but the relay does not switch. Check if the power supply voltage
is too low.
9.3 Burnt products
Check if the power supply exceeds the rated power supply voltage of the
product and if the power cord is connected incorrectly.
9.4 Troubleshooting
When a product malfunctions, the first step is to quickly disconnect the
power supply, connect the wires correctly according to the wiring diagram,
check the wiring is correct, and then follow the operating precautions. If the
product itself has quality issues, please contact your local distribution
company or our company.
5