FAN COIL UNIT
www.yesncer.com
Contents
01
ABOU ENTERPRISE
About yesncer 01
Enterprise qualification 05
Development history 07
Cutomers' Visit 09
Services We Provide 11
02
ABOUT PRODUCT
Horizontal Concealed FCU 13
Horizontal Concealed FCU 190mm 28
Cassette fan coil unit 35
Slim Exposed FCU 47
Ultra-thin Exposed FCU 52
Exposed Fan coil Unit 57
Wall hanging Fan Coil Unit 61
4P Cabinet Fan Coil unit 67
High static pressure fcu 69
AHU catalog (combined) 73
I ABOUT YESNCER
Yuexin Company is an advanced professional heating and cooling equipment manufacturer in China that integrates R&D, production, sales and services. It was rated as a "National High-tech Enterprise" in 2022. After more than 30 years of continuous development, it has successively conquered super-national standard fan coils, combined air-conditioning units, constant temperature and humidity units, functional fan coils, industrial and agricultural heating and cooling fans.
The independently developed variable frequency series fan coils have outstanding use effects and are well received by users. High-performance open-mounted products are sold well in the international market and are now serving more than 60 countries around the world. Yuexin's full-scene application terminal products quickly lead the new market trend with its own unique style. Yuexin creates a learning-oriented corporate organization with the core values of "professionalism, innovation, and excellence".
With the business philosophy of "providing customers with high-quality products and services", it develops world-class central air-conditioning terminal products to meet the growing demand of the global market for comfortable, energy-saving and beautiful products. It is the driving force for Yuexin's development.
Yesncer always adhere to the implementation of "pre-sale, sale, after-sales" three-stage service, adhere to "your every little thing is our big thing" as a service concept. Management standard, unified standards, committed to the best service.
Set up remote intelligent service center, professional team real-time monitoring, in this era of consumer power, we recognize that your journey with our products or services does not end after the transaction. This is just the beginning of a lasting relationship that we are committed to nurturing and maintaining.
Our after-sales service is more than just a promise; It's a deal. We promise unparalleled support, assistance and satisfaction. Ensure that your journey is as exciting as the first contact, and provide users with a more effortless, worrying and money-saving central air conditioning service.
Establish user installation and maintenance database to provide users with quality service in time.
Research and development strength
Yesncer is a specialized central air conditioning end production company, has always adhered to independent research and development, adhering to the "no ceiling" in research and development funds to implement the "on-demand investment" principle, only in 2021 scientific research investment reached 5,726,800 yuan.
Yesncer has trained more than 20 professional and technical backbones to form different levels of technical research and development teams. Continue to receive the industry's cutting-edge information, learning, discussion, a strong guarantee of technological research and development of innovation.
The company has refrigeration technology research laboratory, mechanical and electrical technical engineer, professional HVAC design team, professional HVAC master, ISO9001 quality management system certification, ISO14001 environmental management system certification, and won the EU CEcertification in 2021.
39 + r
TECHNOLOGICAL SEDIMENTATION
26
SERVICE CITIES/ PROVINCES
60±起
EXPORT COUNTRIES
Warehousing strength
Yesncer is located in the ancient city of Baoding, Hebei Province, in the heart of the logistics center, and is very close to Beijing and Tianjin Port, covers an area of 5000 square meters, the daily reserve of 20,000 units, warehousing using ERP management system to ensure accuracy.
Existing cooperative logistics of SF Express, Deppon, Aneng, One meter Tick and other cooperative logistics, order direct destination! To serve customers accurately, efficiently and quickly
Quality control
Control system basis: The core is based on national GB/T19232-2019, and the safety performance has passed the IS09001 quality management system certification, IS014001 environmental management system certification, and IS045001 Occupational health and safety management system certification by Hefei General Machinery Research Institute. Key parameters of the production process.
Production technology
Advanced simulation, design tools SOLIDWORKS design modeling software, independent AHU selection software, independent research and development of linear design software. High-precision machining equipment Automatic welding equipment, air-tight helium leak detection technology, dynamic balance testing machine and other precision CNC machining equipment.
Scientific and rigorous quality control system Supply system → key parameter production process control system →QC system → Packaging system → storage system → pre-shipment inspection system →after-sales service system
100 %
NATIONAL SERVICE NETWORK
FULL SHIPMENT INSPECTION
I ENTERPRISE QUALIFICATIONS
Business License
ROHS Certificate
TUV Certification
Testing reports from 3rd Party
I DEVELEPMENT HISTORY
I Cutomers' Visit
I SERVICE WE SUPPLY
GOODS TRACKING
We will following the goods delivery untill yougot the goods
CUSTOMIZED
The CAD design drawing plan of the project are available
We will send you the test report before shipping
INSTALLATION GUIDE
Supply the installation and maintanence instruction online
QUALITY GUARANTEED
If any quality problem of product, we can refund you
SPARE PARTS
You can get us at any time, after order placed
WARRANTY
Three years' warranty
Brief of the Fan Coil Unit
Horizontal concealed fan coil, mainly composed of fan and coil, is the most durable series of all fan coil units. Large air volume, efficient heat exchange efficiency, ultra-thin height, very popular in the market.
Horizontal concealed fan coil unit is hidden inside the ceiling and does not occupy other indoor decoration space, installation is also very convenient.
Water inlet 4 in and 4 out
Details parts of the fan coil unit
2-Pipe AC motorFCU Technical Data
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
| Cooling Ca.(Water in 7°℃) | kw | 1.9 | 2.8 | 3.75 | 4.6 | 5.5 | 7.3 | 9.2 | 11 | 12.8 |
| Heating Ca.(Water in 60°C) | kw | 3.4 | 5.18 | 6.67 | 7.5 | 9.35 | 12.4 | 14.7 | 17.6 | 20.5 |
| Power Input | W | 36 | 50 | 60 | 74 | 93 | 130 | 147 | 183 | 221 |
| Air flow | m³/h | 357 | 535 | 714 | 892 | 1071 | 1428 | 1785 | 2090 | 2390 |
| Motor Power | W | 25 | 20 | 25 | 25 | 40 | 40+25 | 40+40 | 40+40 | 50+50 |
| Noise | dB(A) | 37 | 39 | 41 | 43 | 45 | 47 | 48 | 50 | 52 |
| Motor No. | 1 | 2 | ||||||||
| Fan No. | 1 | 2 | 3 | 4 | ||||||
| Static pressure | 30Pa | |||||||||
| Water flow | m³/h | 0.32 | 0.478 | 0.64 | 0.797 | 0.956 | 1.275 | 1.59 | 1.9 | 2.23 |
| Condenser length | mm | 450 | 580 | 650 | 760 | 900 | 1100 | 1350 | 1550 | 1750 |
| Condenser height | mm | 20065 | ||||||||
| Condenser Width | mm | |||||||||
| Iron Wheel Weight | kg | 10.7 | 13.2 | 14.2 | 15.4 | 17 | 22.7 | 27 | 28.8 | 31.2 |
| ABS Weight | kg | 10.3 | 12.6 | 13.4 | 14.6 | 16.2 | 21.9 | 26.2 | 28 | 30.4 |
| Package length | mm | 790 | 880 | 980 | 1080 | 1180 | 1380 | 1680 | 1880 | 2080 |
| Package width | mm | 520250 | ||||||||
| Package height | mm | |||||||||
| 2-pipe AC motor FCU Size and Drawing Unit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B | 505 | 635 | 705 | 815 | 955 | 1155 | 1405 | 1605 | 1805 |
| C | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| Model | FCU-02EC F | CU-03EC F | CU-04EC | FCU-05EC | FCU-06EC | FCU-08EC | FCU-10EC | FCU-12EC | FCU-14EC | |
| Cooling Ca.(Water in 7°C) | kw | 1.8 | 3.26 | 3.97 | 4.6 | 5.75 | 7.45 | 9.19 | 10.8 | 12.7 |
| Heating Ca.(Water in 60°C) | kw | 3.49 | 5.27 | 6.77 | 8.65 | 11.17 | 13 | 15.97 | 17.7 | 21.2 |
| Power Input (12Pa) | W | 14 | 16.7 | 22.4 | 32.9 | 52.1 | 60 | 72.8 | 92.7 | 125.2 |
| Power Input (30Pa) | w | 19.8 | 24.3 | 32.5 | 43.5 | 67 | 78.5 | 92.2 | 116 | 156 |
| Power Input (50Pa) | w | 26.3 | 32.4 | 42.5 | 55.7 | 82.2 | 98 | 115.9 | 155.5 | 186 |
| Noise (12Pa) | dB(A) | 18~32 | 18~30 | 20~34 | 23~38 | 29~43 | 28~42 | 32~43 | 33~44 | 37~47 |
| Noise (30Pa) | dB(A) | 20~38 | 20~37 | 22~41 | 24~43 | 30~47 | 31~46 | 34~47 | 34~48 | 38~49 |
| Noise (50Pa) | dB(A) | 23~43 | 22~42 | 25~45 | 26~47 | 33~50 | 34~49 | 36~51 | 37~51 | 39~53 |
| Air Flow | m3/h | 360 | 545 | 724 | 900 | 1090 | 1440 | 1750 | 2140 | 2490 |
| Motor Power | w | 60 | ||||||||
| Motor No. | 1 | 2 | ||||||||
| Fan No. | 1 | 2 | 3 | 4 | ||||||
| Static pressure | 0~50Pa | |||||||||
| Water flow | m³/h | 0.4 | 0.59 | 0.73 | 0.81 | 1 | 1.2 | 1.57 | 1.86 | 2.19 |
| Condenser length | mm | 450 | 580 | 650 | 760 | 900 | 1100 | 1350 | 1550 | 1750 |
| Condenser height | mm | 210 | ||||||||
| Condenser Width | mm | 38.1 | ||||||||
| Weight | kg | 10.1 | 12.1 | 13 | 14.2 | 15.5 | 20.1 | 23.5 | 25.5 | 27.3 |
| Package length | mm | 790 | 880 | 980 | 1080 | 1180 | 1380 | 1680 | 1880 | 2080 |
| Package width | mm | 520250 | ||||||||
| Package height | mm | |||||||||
| Model | FCU-02EC | FCU-03EC | FCU-04EC | FCU-05EC | FCU-06EC | FCU-08EC | FCU-10EC | FCU-12EC | FCU-14EC |
| A | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B | 505 | 635 | 705 | 815 | 955 | 1155 | 1405 | 1605 | 1805 |
| C | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
| 3+1Cooling Ca.(Water in 7°℃ ) | kw | 1.85 | 2.78 | 3.7 | 4.63 | 5.56 | 7.41 | 9.27 | 11.1 | 12.9 |
| 3+1Heating Ca.(Water in 60°℃ ) | kw | 1.2 | 1.9 | 2.5 | 3.1 | 3.7 | 4.85 | 6.1 | 7.3 | 8.6 |
| 2+2Cooling Ca.(Water in 7°℃ ) | kw | 1.2 | 1.8 | 2.5 | 3.2 | 3.8 | 5.1 | 6.2 | 7.7 | 8.8 |
| 2+2Heating Ca.(Water in 60°℃ ) | kw | 1.8 | 2.8 | 3.8 | 4.7 | 5.7 | 7.7 | 9.5 | 11.3 | 13.2 |
| Power Input | w | 36 | 50 | 60 | 74 | 93 | 130 | 147 | 183 | 221 |
| Air Flow | m³/h | 357 | 535 | 714 | 892 | 1071 | 1428 | 1785 | 2090 | 2390 |
| Motor Power | w | 25 | 20 | 25 | 25 | 40 | 40+25 | 40+40 | 40+40 | 50+50 |
| Noise | dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| Motor No. | 1 | 2 | ||||||||
| Fan No. | 1 | 2 | 3 | 4 | ||||||
| Static pressure | 30Pa | |||||||||
| Water flow | m³/h | 0.32 | 0.478 | 0.64 | 0.797 | 0.956 | 1.275 | 1.594 | 1.913 | 2.232 |
| Condenser length | mm | 450 | 580 | 650 | 760 | 900 | 1100 | 1350 | 1550 | 1750 |
| Condenser height | mm | 200 | ||||||||
| Condenser Width | mm | 108.3 | ||||||||
| Iron Wheel Weight | kg | 10.7 | 13.2 | 14.2 | 15.4 | 17 | 22.7 | 27 | 28.8 | 31.2 |
| ABS Weight | kg | 10.3 | 12.6 | 13.4 | 14.6 | 16.2 | 21.9 | 26.2 | 28 | 30.4 |
| Package length | mm | 790 | 880 | 980 | 1080 | 1180 | 1380 | 1680 | 1880 | 2080 |
| Package width | mm | 520260 | ||||||||
| Package height | mm | |||||||||
Total width 470
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B | 505 | 635 | 705 | 815 | 955 | 1155 | 1405 | 1605 | 1805 |
| C | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| Other option- with air return plenum Unit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A (Total length) | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B(Plenum length) | 507 | 637 | 707 | 817 | 957 | 1157 | 1407 | 1607 | 1807 |
| C (Distance betweenlifting holes) | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| The maximumnumber of air outlets(150mm) | 2 | 3 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
| The maximumnumber of air outlets(200mm) | 1 | 2 | 2 | 3 | 3 | 4 | 5 | 6 | 7 |
| Other option- with air return plenumUnit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A(Total length) | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B(Plenum length) | 507 | 637 | 707 | 817 | 957 | 1157 | 1407 | 1607 | 1807 |
| C(Distance betweenlifting holes) | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| The maximumnumber of jet ports | 3 | 4 | 5 | 6 | 7 | 9 | 10 | 12 | 14 |
Other option- with electrical damper air outlet
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A (Total length) | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B (Plenum length) | 507 | 637 | 707 | 817 | 957 | 1157 | 1457 | 1607 | 1807 |
| C (Distance betweenlifting holes) | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| The max NO ofdamper | 1 | 2 | 2 | 3 | 3 | 3 | 4 | 5 | 5 |
Brief :
Product name: Ultra-thin concealed fan coil unit with electric damper developed by ourselves.
The different damper could connect the air duct to different rooms to solve the problem of not enough space for install enough fan coil units.
What's more, the using room only a air inlet, no moise of the fan coil unit.
▶There the PCB we developed by ourselves, relizng seperate control in different rooms.
Control logic : One room open the thermostat, the fan coil open, all the thermsotat close, the fan coil unit close.
▶When the room temprature reach to the setting tempearature, the damper will be closed.
If you think the air flow is not enough, the RPM of the motor could be set by yourself on the PCB.
| Other option- with air outlet elbowUnit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A (Total Length) | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B(Distance betweenlifting holes) | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| C(Elbow length(tuyere length)) | 512 | 642 | 712 | 822 | 962 | 1162 | 1412 | 1612 | 1812 |
| Other option- with air return plenumUnit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A | 755 | 855 | 955 | 1055 | 1155 | 1355 | 1655 | 1855 | 2055 |
| B | 505 | 635 | 705 | 815 | 955 | 1155 | 1405 | 1605 | 1805 |
| C | 477 | 607 | 677 | 787 | 927 | 1127 | 1377 | 1577 | 1777 |
| D | 510 | 640 | 710 | 820 | 960 | 1160 | 1410 | 1610 | 1810 |
| E | 460 | 590 | 660 | 770 | 910 | 1110 | 1360 | 1560 | 1760 |
| Vertical concealed FCU data sheet | ||||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
| Cooling Ca.(Water in 7°℃) | kw | 1.8 | 2.7 | 3.6 | 4.5 | 5.4 | 7.2 | 9.0 | 10.8 | 12.6 |
| Heating Ca.(Water in 60°℃) | kw | 2.7 | 4.05 | 5.4 | 6.75 | 8.1 | 10.8 | 13.5 | 16.2 | 18.9 |
| Power | w | 36 | 50 | 60 | 74 | 93 | 130 | 147 | 183 | 220 |
| Air flow | m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
| Noise | dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| Static pressure | 12Pa | |||||||||
| Water flow | m³/h | 0.32 | 0.478 | 0.64 | 0.797 | 0.956 | 1.275 | 1.594 | 1.913 | 2.232 |
| Condenser length | mm | 460 | 580 | 650 | 730 | 850 | 1050 | 1310 | 1510 | 1600 |
| Condenser height | mm | 190 | ||||||||
| Condenser Width | mm | 40 | ||||||||
| Iron Wheel Weight | kg | 11 | 14 | 15 | 17 | 18 | 25 | 28 | 34 | 38 |
| ABS Weight | kg | 10 | 13 | 14 | 16 | 17 | 24 | 27 | 33 | 37 |
| Vertical concealed FCU size & drawing Unit: mm | |||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A | 600 | 760 | 830 | 910 | 1030 | 1290 | 1500 | 1690 | 1790 |
| B | 410 | 570 | 640 | 730 | 850 | 1100 | 1310 | 1510 | 1600 |
| C | 460 | 610 | 690 | 780 | 870 | 1170 | 1360 | 1560 | 1650 |
| Vertical concealed FCU data sheet | ||||||||||
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 | |
| 2+2 Cooling Ca.(Water in 7°C) | kw | 1.8 | 2.7 | 3.6 | 4.5 | 5.4 | 7.2 | 9.0 | 10.8 | 12.6 |
| 2+2 Heating Ca.(Water in 60°℃ ) | kw | 1.2 | 1.8 | 2.4 | 3.1 | 3.6 | 4.8 | 6.1 | 7.3 | 8.5 |
| 2+2 Cooling Ca.(Water in 7°C) | kw | 1.2 | 1.8 | 2.5 | 3.2 | 3.8 | 5.1 | 6.2 | 7.7 | 8.8 |
| 2+2 Heating Ca.(Water in 60°℃ ) | kw | 1.8 | 2.8 | 3.8 | 4.7 | 5.7 | 7.7 | 9.5 | 11.3 | 13.2 |
| Power Input | W | 36 | 50 | 60 | 74 | 93 | 130 | 147 | 183 | 220 |
| Air flow | m3/h | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
| Noise | dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 |
| Static pressure | 12Pa | |||||||||
| Condenser length | mm | 460 | 580 | 650 | 730 | 850 | 1050 | 1310 | 1510 | 1600 |
| Condenser height | mm | 190 | ||||||||
| Condenser Width | mm | 52 | ||||||||
| Iron Wheel Weight | kg | 12 | 15 | 16 | 19 | 20 | 27 | 31 | 36 | 41 |
| ABS Weight | kg | 11 | 14 | 15 | 18 | 19 | 26 | 30 | 35 | 40 |
| Model | FP-34 | FP-51 | FP-68 | FP-85 | FP-102 | FP-136 | FP-170 | FP-204 | FP-238 |
| A | 600 | 760 | 830 | 910 | 1030 | 1290 | 1500 | 1690 | 1790 |
| B | 410 | 570 | 640 | 730 | 850 | 1100 | 1310 | 1510 | 1600 |
| C | 460 | 610 | 690 | 780 | 870 | 1170 | 1360 | 1560 | 1650 |
Coil
Details Parts of The Fan Coil Unit
Ultra-thin Fan Coil Unit Data Sheet
| Product Name | Ultra-thin concealed fan coil unit(AC motor) | ||
| Application | It is widely used for hotel,restaurant,hospital,shopping mall,factory and office building etc.And some other villa | ||
| Product Function | It can be used for cooling, heating, dehumidification | ||
| Product Models | FP-51/68/85/102/136/170CB | ||
| CoilCooper | Fin | 0.105mm thickness aluminum fins, distance between fins is 1.3mm | |
| tube | Three rows, 0.28mm thickness, 7mm diameter, 30 tubes or 24tubes in total | ||
| Drain | Drain pan | aterial with plastic coating | |
| Drain pump | Optional (internal) | ||
| Alertor | Optional | ||
| ProductComponents | Shell | Panel | 1mm Al-Zn-Si hot-dip galvanized steel sheet |
| Insulation | EVA insulation pasted outside and inside the panel, B1 rating. | ||
| Motor | EC motor with3-speed or 0-10v thermostat | ||
| Label | Labels: model label, wiring diagram, precautions, fan rotation, logo, etc. | ||
| Fan | ABS material Centrifugal, forward-curved blades | ||
| Control | Could connect both 3-speed thermostat and 0-10V thermostat. | ||
| ProductionTechnology | Tube | Mechanical expansion, automatic welding | |
| Body Panel | Fully automatic molding in one molding, with longitudinal reinforcement at the bend | ||
| Motor panel | Hydraulic abrasive ribs+longitudinal reinforcement at the bend | ||
| Inspection Standards | 1. No scratches or rust on the surface of the machine2. The internal cooler of the machine has no leakage under the pressure of 1.6Mpa(hold pressure for at least 5min)3. The unit starts under the condition of 90% of the rated voltage and runs stably for 10 minutes4. Under normal temperature and humidity conditions, use 500V insulation resistance meter tomeasure the insulation resistance between the live part and non-metal live part of the unit isnot less than 2MΩ | ||
| Model | A Total length | B Body length | C air outlet length | D lifting eye distance | F&G Air intake length | |
| FP-51CB | CBFCU-03EC | 926 | 848 | 650 | 890 | 740 |
| FP-68CB | CBFCU-04EC | 926 | 848 | 650 | 890 | 740 |
| FP-85CB | CBFCU-05EC | 1176 | 1098 | 900 | 1140 | 990 |
| FP-102CB | CBFCU-06EC | 1176 | 1098 | 900 | 1140 | 990 |
| FP-136CB | CBFCU-08EC | 1626 | 1548 | 1350 | 1590 | 1440 |
| FP-170CB | CBFCU-10EC | 1626 | 1548 | 1350 | 1590 | 1440 |
Parameter of both Ultra-thin FCU
| Ultra-thin concealed fan coil unit (AC motor) | |||||||||
| Model | FP-51CB | FP-68CB | FP-85CB | FP-102CB | FP-136CB | FP-170CB | |||
| Motor power | w | 12 | 20 | 20 | 25 | 25+25 | 40+40 | ||
| Power consumption | w | 48 | 55 | 72 | 90 | 129 | 148 | ||
| Motor NO. | 1 | 2 | |||||||
| Fan NO. | 2 | 4 | |||||||
| Static Pressure | Pa | 12Pa | |||||||
| Air flow | m3/h | 530 | 700 | 875 | 1030 | 1360 | 1750 | ||
| Cooling capacity,(7°C chilled water) | kw | 2.8 | 3.7 | 4.7 | 5.7 | 7.8 | 9.4 | ||
| Heating capacity(60°℃ hot water) | dB(A) | 5.0 | 6.5 | 7.2 | 9.1 | 11.8 | 14.8 | ||
| H | dB(A) | 39 | 41 | 43 | 45 | 46 | 48 | ||
| Noise | M | dB(A) | 36 | 38 | 41 | 42 | 43 | 45 | |
| L | kg | 33 | 35 | 36 | 38 | 39 | 40 | ||
| Weight | Net weight | kg | 18.3 | 18.5 | 21.2 | 21.5 | 30.6 | 31 | |
| Gross weight | mm | 21 | 21.3 | 24.4 | 24.7 | 34.6 | 35 | ||
| Coil length | mm | 650 | 650 | 900 | 900 | 1330 | 1330 | ||
| Coil width | mm | 21 | 0 | ||||||
| Coil | thickness | mm | 38.1 | ||||||
| Packagesize | L | mm | 1040 | 1040 | 1290 | 1290 | 1740 | ||
| HW | mm | 565250 | |||||||
| Model | CBFCU-03EC | CBFCU-04EC | CBFCU-05EC | CBFCU-06EC | CBFCU-08EC | CBFCU-10EC | ||
| Motor power | w | 60 | ||||||
| Power consumption | w | 33 | 45 | 52 | 83 | 63 | 116 | |
| Motor NO. | 1 | 2 | ||||||
| Fan NO. | 2 | 4 | ||||||
| Cooling capacity(7°℃C chilled water) | kw | 2850 | 3730 | 4700 | 5724 | 7810 | 9486 | |
| Heating capacity(60°℃ hot water) | kw | 5000 | 6520 | 7220 | 9108 | 11870 | 14810 | |
| Weight | Net weight | kg | 18.3 | 18.5 | 21.2 | 21.5 | 30.6 | 31 |
| Gross weight | kg | 21 | 21.3 | 24.4 | 24.7 | 34.6 | 35 | |
| Coil length | mm | 650 | 650 | 900 | 900 | 1350 | 1350 | |
| Coil width | mm | 210 | ||||||
| Coil thickness | mm | 39 | ||||||
| long | mm | 1040 | 1040 | 1290 | 1290 | 1740 | 1740 | |
| Packagesize | wide | mm | 565250 | |||||
| thick | mm | |||||||
More Parameter of ultra-thin concealed FCU (EC motor)
| Model | S.P. | 12Pa | 30Pa | 50Pa | |||
| CBFCU-03EC | Votage adjust | 3.1V | 5.5V | 3.4V | 6.5V | 3.8V | 7.5V |
| Air Flow(m³/h) | 260 | 516 | 270 | 520 | 270 | 510 | |
| Noise(dBA) | 18 | 34 | 20 | 39 | 27 | 41 | |
| CBFCU-04EC | Votage adjust | 3.4V | 6.5V | 3.6V | 7.5V | 3.9V | 8.5V |
| Air Flow(m³/h) | 320 | 697 | 330 | 688 | 340 | 684 | |
| Noise(dBA) | 21 | 40 | 23 | 41 | 29 | 44 | |
| CBFCU-05EC | Votage adjust | 3.6V | 6.4V | 3.8V | 7.5V | 4.1V | 8.7V |
| Air Flow(m³/h) | 400 | 860 | 350 | 877 | 360 | 876 | |
| Noise(dBA) | 22 | 41 | 26 | 43 | 28 | 46 | |
| CBFCU-06EC | Votage adjust | 3.8V | 7.5V | 4.2V | 8.5V | 5V | 9.8V |
| Air Flow(m³/h) | 450 | 1100 | 460 | 1030 | 480 | 1040 | |
| Noise(dBA) | 24 | 43 | 27 | 45 | 29 | 48 | |
| CBFCU-08EC | Votage adjust | 4V | 6.8V | 4.3V | 7.8V | 5V | 8.5V |
| Air Flow(m³/h) | 700 | 1480 | 640 | 1380 | 730 | 1400 | |
| Noise(dBA) | 26 | 43 | 32 | 47 | 38 | 49 | |
| CBFCU-10EC | Votage adjust | 4.2V | 8.2V | 4.8V | 9.0V | 5V | 9.5V |
| Air Flow(m³/h) | 750 | 1720 | 840 | 1750 | 850 | 1730 | |
| Noise(dBA) | 28.2 | 45 | 34 | 48 | 38 | 51 | |
| Model | S.P. | 12Pa | 30Pa | 50Pa | ||||||
| CBFCU-03EC | DIP Switch adjust | 1100 | 1110 | 1101 | ||||||
| Air Flow(m3/h) | 350 | 580 | 380 | 545 | 390 | 550 | ||||
| Noise(dBA) | 23 | 35.8 | 25 | 40 | 30 | 42.5 | ||||
| CBFCU-04EC | DIP Switch adjust | 111 | 0 | 1101 | 0111 | |||||
| Air Flow(m3/h) | 400 | 695 | 420 | 710 | 340 | 685 | ||||
| Noise(dBA) | 24 | 41 | 25 | 42 | 30 | 44.5 | ||||
| CBFCU-05EC | DIP Switch adjust | 111 | 0 | 1101 | 011 | 1 | ||||
| Air Flow(m³/h) | 450 | 865 | 400 | 850 | 390 | 870 | ||||
| Noise(dBA) | 24 | 42 | 25 | 43 | 28.8 | 46.5 | ||||
| CBFCU-06EC | DIP Switch adjust | 110 | 1 | 1011 | 011 | 1 | ||||
| Air Flow(m³/h) | 510 | 1080 | 490 | 1025 | 470 | 1040 | ||||
| Noise(dBA) | 25 | 42.5 | 27.5 | 44.8 | 28 | 48 | ||||
| CBFCU-08EC | DIP Switch adjust | 000 | 1 | 101 | 1 | 011 | 1 | |||
| Air Flow(m3/h) | 750 | 1430 | 650 | 1490 | 650 | 1400 | ||||
| Noise(dBA) | 27 | 43.3 | 32.5 | 46 | 34 | 47 | ||||
| CBFCU-10EC | DIP Switch adjustAir Flow(m3/h) | 0011 | 1011 | 0111 | ||||||
| 810 | 1720 | 790 | 1750 | 780 | 1730 | |||||
| Noise(dBA) | 30 | 46 | 30 | 48 | 32 | 51 | ||||
| Digital Code | 0000 | 0010 | 0110 | |||||||
| Dip sample | m | Tm | T… | |||||||
\* Data sheet of air flow and noise in different DIP switch setting connected 3-speed thermostat
Slim Horizontal Concealed Fan Coil Unit With Electrical Damper
One fan coil used for a few of rooms
Product name: Ultra-thin concealed fan coil unit with electric damper developed by ourselves.
The different damper could connect the air duct to different rooms to solve the problem of not enough space for Install enough fan coil units.
What's more, the using room only a air inlet, no moise of the fan coil unit.
There the PCB we developed by ourselves, relizng seperate control in different rooms.
Control logic : One room open the thermostat, the fan coil open, all the thermsotat close, the fan coil unit close.
When the room temprature reach to the setting tempearature, the damper will be closed.
if you think the air flow is not enough, the RPM of the motor could be set by yourself on the PCB.
| Model | CBFCU-03EC | CBFCU-04EC | CBFCU-05EC | CBFCU-06EC | CBFCU-08EC | CBFCU-10EC |
| A | 859 | 859 | 1109 | 1109 | 1579 | 1579 |
| B | 265 | 265 | 312.5 | 312.5 | 400 | 400 |
| C | 263.5 | 163.5 | 241 | 241 | 188 | 188 |
| D | 890 | 890 | 1140 | 1140 | 1609 | 1609 |
| E | 759 | 759 | 1009 | 1009 | 1478 | 1478 |
| Damper Dia | 150 | 150 | 150 | 150 | 150 | 150 |
Structure of 4-way cassette
Wired control or remote control to adjust the temperature
| Model | FP-34KM-S F | P-51KM-S F | P-68KM-SF | P-85KM-SF | P-102KM-SF | P-136KM-S F | P-170KM-S | FP-204KM-SF | P-238KM-S | |
| Cooling Ca. (kw)(Water in 7°C)(Airinlet temperature:DB 27℃, WB19.5℃) | H | 1.98 | 2.98 | 3.68 | 4.98 | 5.4 | 7.2 | 9.9 | 10.8 | 12.6 |
| M | 1.63 | 2.27 | 2.81 | 3.75 | 4.32 | 5.53 | 7.51 | 8.08 | 9.68 | |
| L | 1.04 | 1.51 | 1.89 | 2.51 | 2.85 | 5.53 | 5.00 | 5.55 | 6.45 | |
| Heating Ca. (kw)(Water in 60°℃)( Air inlet temperature:DB 20C) | H | 2.97 | 4.80 | 5.48 | 7.20 | 8.1 | 10.80 | 14.50 | 16.20 | 18.90 |
| M | 2.45 | 3.67 | 4.19 | 5.42 | 6.33 | 8.17 | 11.00 | 12.35 | 14.52 | |
| L | 1.57 | 2.44 | 2.82 | 3.60 | 4.52 | 5.47 | 7.33 | 8.48 | 9.68 | |
| Air flow (m3/h) | H | 345 | 510 | 690 | 875 | 1035 | 1375 | 1705) | 2045 | 2380 |
| M | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
| L | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
| Power Input (W) | 50 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 | |
| Current (A) | 0.151 | 0.225 | 0.258 | 0.32 | 0.385 | 0.561 | 0.547 | 0.677 | 0.882 | |
| Noise (dB (A)) | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 49 | 52 | |
| Static Pressure (Pa) | 12 | |||||||||
| Power Supply | 220-240v/1ph/50Hz | |||||||||
| Control Way | Wired or remote controller | |||||||||
| Water Flow (m³/h) | 0.42 | 0.52 | 0.62 | 0.86 | 0.98 | 1.08 | 1.58 | 1.78 | 1.92 | |
| Water Pressure Drop(kPa) | 14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 46 | |
| Water Pipe For in/out | ZG3/4” | |||||||||
Size Drawing of Self-drainage 4 way Cassette:
390 Normal Type Mounting Dimensions
a: Hook to ceiling base distance
b: Indoor mainframe size
C: Distance from hook to top of indoor unit
d: Distance from top of indoor unit to bottom of ceiling
A: Panel size
B: Ceiling opening dimensions
C: Indoor unit mainframe size
D: Lifting eye size
| Model | FP-34KM | FP-51KM | FP-68KM | FP-85KM | FP-102KM | FP-136KM | FP-170KM | FP-204KM | FP-238KM | |
| Cooling Ca. (kw)(Water in 7°C)(Air inlet temperature:DB 27℃, WB19.5℃) | H | 1.98 | 2.98 | 3.68 | 4.98 | 5.4 | 7.2 | 9.9 | 10.8 | 12.6 |
| M | 1.63 | 2.27 | 2.81 | 3.75 | 4.32 | 5.53 | 7.51 | 8.08 | 9.68 | |
| L | 1.04 | 1.51 | 1.89 | 2.51 | 2.85 | 5.53 | 5.00 | 5.55 | 6.45 | |
| Heating Ca. (kw)(Water in 60°C)(Air inlet temperature:DB 20C) | H | 2.97 | 4.80 | 5.48 | 7.20 | 8.1 | 10.80 | 14.50 | 16.20 | 18.90 |
| M | 2.45 | 3.67 | 4.19 | 5.42 | 6.33 | 8.17 | 11.00 | 12.35 | 14.52 | |
| L | 1.57 | 2.44 | 2.82 | 3.60 | 4.52 | 5.47 | 7.33 | 8.48 | 9.68 | |
| Air flow (m³/h) | H | 345 | 510 | 690 | 875 | 1035 | 1375 | 1705) | 2045 | 2380 |
| M | 280 | 390 | 520 | 640 | 790 | 1030 | 1290 | 1500 | 1800 | |
| L | 180 | 260 | 350 | 430 | 520 | 690 | 860 | 1030 | 1200 | |
| Power Input (W) | 50 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 | |
| Current (A) | 0.151 | 0.225 | 0.258 | 0.32 | 0.385 | 0.561 | 0.547 | 0.677 | 0.882 | |
| Noise (dB (A)) | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 49 | 52 | |
| Static Pressure (Pa) | 12 | |||||||||
| Power Supply | 220-240v/1ph/50Hz | |||||||||
| Control Way | Wired or remote controller | |||||||||
| Water Flow (m³/h) | 0.42 | 0.52 | 0.62 | 0.86 | 0.98 | 1.08 | 1.58 | 1.78 | 1.92 | |
| Water Pressure Drop(kPa) | 14 | 14 | 16 | 18 | 22 | 25 | 39 | 44 | 46 | |
| Water Pipe For in/out | ZG3/4” | |||||||||
Size drawing of 2-pipe 4 way Cassette :
290 High End Model Mounting Dimensions
a:: Hook to ceiling base distance
b: Indoor mainframe size
C: Distance from hook to top of indoor unit
d: Distance from top of indoor unit to bottom of ceiling
A: Panel size
B: Ceiling Opening Dimensions
C: Indoor unit mainframe size
D: lifting eye Size
Remote control reception and function display
4-pipe 4 way Cassette
| Model | FP-34KM-4P | FP-51KM- 4P | FP-68KM- 4P | FP-85KM- 4P | FP-102KM-4P | FP-136KM- 4P | FP-170KM- 4P | FP-204KM-4P | FP-238KM-4P | |
| Cooling Ca. (kw)(Water in 7°C) | H | 1.215 | 1.935 | 2.52 | 3.105 | 3.735 | 4.635 | 6.3 | 7.29 | 8.01 |
| Heating Ca. (kw)(Water in 60°C) | H | 1.53 | 2.295 | 2.88 | 3.69 | 4.365 | 5.31 | 7.38 | 8.325 | 9.045 |
| Air flow (m3/h) | H | 340 | 510 | 680 | 850 | 1020 | 1360 | 1700 | 2040 | 2380 |
| Power Input (W) | 34 | 50 | 58 | 72 | 92 | 126 | 128 | 152 | 198 | |
| Running current (A) | 0.151 | 0.225 | 0.258 | 0.32 | 0.385 | 0.561 | 0.547 | 0.547 | 0.882 | |
| Noise dB (A) | 37 | 39 | 41 | 43 | 45 | 46 | 47 | 49 | 52 | |
| Static pressure (Pa) | 12220-240v/1ph/50HzWired or remote controller | |||||||||
| Power Supply | ||||||||||
| Control way | ||||||||||
| Water pipe for in/out | ZG3/4”Male thread 26mm | |||||||||
| Drain pipe | ||||||||||
| Weight (kg) | 21 | 22 | 23 | 30.5 | 31 | 31.5 | 38.5 | 39.5 | 40.5 | |
| Panel size (mm) | 650*650*30 | 800*800*30 | 950*950*30 | |||||||
Size drawing of 4 pipe :
290 High End Model Mounting Dimensions
a: Hook to ceiling base distance
b: Indoor mainframe size
C: Distance from hook to top of indoor unit
d: Distance from top of indoor unit to bottom of ceiling
A: Panel size
B: Ceiling Opening Dimensions
C: Indoor unit mainframe size
D: lifting eye Size
18 way Cassette Fan Coil Unit
The machine adopts an eight-sided air outlet design, which reduces the indoor air supply resistance, quickly delivers the airflow to every corner, makes the space environment temperature more uniform, and achieves low noise in overall operation.
Standard:
Optional: Wired controller WIFI connection
| Model | FP-170KM-8W | FP-204KM-8W | FP-238KM-8W | |
| Cooling Ca. (kw)(Water in 7°C) | H | 9.9 | 10.4 | 12.6 |
| Heating Ca. (kw)(Water in 60°C) | H | 14.5 | 15.2 | 18.9 |
| Air flow (m³/h) | H | 1700 | 2040 | 2380 |
| M | 1275 | 1575 | 1850 | |
| 」 | 850 | 1050 | 1250 | |
| Power Input (W) | 128 | 152 | 198 | |
| Running current (A) | 0.547 | 0.547 | 0.882 | |
| Noise dB (A) | 48 | 49 | 52 | |
| Static pressure (Pa) | 12 | |||
| Power Supply | 220-240v/1ph/50Hz | |||
| Control way | Wired or remote controller | |||
| Water pipe for in/out | ZG3/4” Femal thread | |||
| Drain pipe | Male thread 20mm | |||
| Packing Size(mm) | 1000*1000*380 | |||
| Install whole open size(mm) | 840-900 | |||
| Hanging anchor size(mm) | 867*420 | |||
Size drawing :
Mounting Dimensions
a: Hook to ceiling base distance
b: Indoor mainframe size
C: Distance from hook to top of indoor unit
d: Distance from top of indoor unit to bottom of ceiling
A: Panel size
B: Ceiling Opening Dimensions
C: Indoor unit mainframe size
D: lifting eye Size
2 way Cassette Fan Coil Unit
It is composed of copper tubes and hydrophilic aluminum foil, with exhaust valve.
| Model | FP-51KM-2W | FP-68KM-2W | FP-85KM-8W | FP-102KM-2W | FP-136KM-8W | |
| Cooling Ca. (kw)(Water in 7°C) | H | 2.7 | 3.8 | 4.5 | 5.4 | 7.2 |
| Heating Ca. (kw)(Water in 60°C) | H | 4.5 | 5.5 | 6.7 | 8 | 10.8 |
| Air flow (m³/h) | H/M/L | 510/390/260 | 680/520/400 | 850/640/490 | 1020/765/600 | 1360/1050/800 |
| Power Input (W) | 50 | 64 | 70 | 85 | 110 | |
| Running current (A) | 0.23 | 0.29 | 0.31 | 0.38 | 0.49 | |
| Noise dB (A) | 39 | 42 | 43 | 45 | 46 | |
| Static pressure (Pa) | 12Pa | |||||
| Power Supply | 220V-50Hz-1Ph | |||||
| Control way | Remote controller (Wired as optional) | |||||
| Water flow(L/H) | 520 | 620 | 776 | 930 | 1245 | |
| Water pressure drop (KPa) | 10 | 11 | 13 | 16 | 20 | |
| Water pipe for in/out | DN20 | |||||
| Unit Size mm | 1259*680*340 | |||||
| Panel Size(mm) | 1240*680*30 | |||||
| Install whole open size(mm) | 1172*475mm | |||||
I Size drawing :
Mounting Dimensions
a:: Hook to ceiling base distance
b: Indoor mainframe size
C: Distance from hook to top of indoor unit
d: Distance from top of indoor unit to bottom of ceiling
A: Panel size
B:Ceiling Opening Dimensions
C: Indoor unit mainframe size
D: lifting eye Size
130mm Slim Exposed FCU
Enhancing comfort and air quality—making it the ideal choice for home use in fan coil units.
Efficient energy saving
Flexible speed adjustment
Strong environmental adaptability
Easy maintenance
Convenient installation
Intelligent control