QFW-2500G 工业机柜空调说明书
目 录
1. 安全注意事项·······················································································1
2. 安装要求 ·····························································································1
2-1 安装位置·························································································2
2-2 安装方法·························································································3
2-3 电器配线························································································6
2-4 机器排水·························································································6
3. 启动与运转···························································································6
3-1 运行前后注意事项···········································································6
3-2 机器操作说明··················································································7
4. 维护与保养·························································································10
4-1 定期清洁·······················································································10
4-2 长时间停用时注意··········································································10
5. 故障排除·····························································································10
附录一······································································································11
附录二······································································································11
1,安全注意事项
⑴ 当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册
中所提到的注意事项,以避免出现意外情况;
⑵ 请勿用湿手操作,以免引起触电;
⑶ 当需要保养或维护时,请先切断所有电源以免引起触电事故;
⑷ 空调器上不易放置任何物品,以免滑落造成人员伤害;
⑸ 当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受
伤或机器损坏;
⑹ 本机器露天放置外罩做好密封处理以免雨水进入机体内,并且也不适宜于安装在振动较大或
者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;
⑺ 本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;
⑻ 禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发
生。
1. 安装要求
本空调器为侧挂式系列,侧挂式(图一),为使机组能在理想的状况下工作,在安装上请注意以
下要求:
图一 侧挂式
空调器
电
控
箱
回风
(热)
出风
(冷)
2-1 安装位置
⑴ 空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘
类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装
空调器,则一定要每天做好空调器的清洁和保养工作。
⑵ 空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调
器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、
排风口离墙面的间距应大于 500mm;
⑶ 空调器周围请勿放置杂物,以保持空气畅通流通;
⑷ 本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。
⑸ 请安装本空调器于周围温度在 45℃以下的范围之内高温系列 55℃以下;
⑹ 本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜
角不大于 5°如图四所示;
⑺ 控制箱内正对出风口的电器元件与出风口的最小距离应大于 200mm,因距离太近电器元件表
面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;
并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。
⑻ 当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿
度能控制在较为理想的状态下。
图三
电
控
箱
冷气机
图 四
错 误 正 确 错 误 正 确
2-2 安装方法
⑴ 当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;
⑵ 为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进
行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;
⑶ 空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备
损坏,当安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的
重量不会使整个电气柜倾倒;
⑷ 电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;
⑸ 箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;
⑹ 当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而
损坏;
⑺ 具体的安装方式如下
安装示意图:
2-3 电器配线:
⑴ 机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若
所提供的电压在额定值±10%以内,本机组可正常使用;
经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,
此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意
⑵ 空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,
当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;
⑶ 在机组的电器回路上请自行安装断路器或漏电保护装置;
⑷ 请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负
载,引发事故。
2-4 机器排水:
本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气
就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:
⑴ 请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;
⑵ 根据实际情况排水软管长度适当即可,过长部分请切除;
⑶ 排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水
严重时产生外溢,引起空调器或者电气柜故障。
2. 启动与运行
3. 3-1 运行前后注意事项
⑴ 启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开
始工作;
⑵ 当在运转中需重新启动空调器时,请间隔 3 分钟以上,倘若频繁启动且间隔时间过短会引起
机器损伤;
⑶ 当空调器倾斜时请勿开启,避免漏水、触电等情况发生;
⑷ 空调器在出厂时温度点已经设定好为 32℃,若需重新设定时请控制在允许范围之内设定,以
免引起机器运行不正常;如果空调器有加热功能,出厂时设置为 5℃
⑸ 当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进行检
查维修。
3-2 机器操作说明·系统参数设置界面进入:
使用一组密码进入参数设置状态(出厂默认密码为 1111),按〖P〗键并保持 3 秒钟,数码管显示『---0』,
按〖▼〗键循环选择密码当前位,按〖▲〗键设置当前位密码值, 密码设置完成后按〖S〗键确认。如
果密码错误,显示『Err』蜂鸣器响三声后退出参数设置状态;如果密码输入正确,蜂鸣器响一声,进
入参数设置状态,这时数码管显示『U10』,用〖▲〗或〖▼〗键选择参数代码,选定一个参数后按
〖S〗键显示该参数的设定值,这时再按〖▲〗或〖▼〗键可对参数进行设置,设置完成后再按〖S〗
键,回到显示参数代码状态。
·系统参数设置界面退出:
当参数设置完成后必须长按〖P〗键 3 秒, 系统退出参数设置状态,此次参数设置被保存。在参数
设置状态如果连续 30 秒内无按键操作,系统退出参数设置状态,但此次参数设置无效,控制器仍按
原来的参数运行。
显示屏信号说明
面板数码管说明
4 位红色数码管显示测量温度值和告警代码;
图标 功能 亮 灭 闪烁
压缩机 启动 停止 准备制冷,压缩机正在延
时保护
AUX 电加热 运行 ---- ----
风机 运行 停止 ----
维修 有故障 无故障 ----
报警 有告警 无报警 ----
通讯 ---- ---- 正在通讯
HACCP
压缩机强
制
强制运行 ---- ----
序 号 显示代码 说 明
1 “E01” 温控传感器故障(短路或断路)
3 “E02” 蒸发器传感器故障(短路或断路)
3 “E03” 系统缺氟保护
4 “Hi” 高温告警
5 “Lo” 低温告警
6 “EE” 数据存取错误
7 “Err” 密码输入错误
8 “iA” 外部无源数字量输入告警(系统高压告警)
9 “UnL” 恢复默认出厂密码“1111”
10 “FrE 蒸发器冻结保护
序号
参数代
码
设置功能 设定范围 说明
出 厂 设 定
值
01 U00 制冷温度设定 25~ 40℃ 30
02 U02 温差 1.0~ 5.0℃ 5
03 U03 高温报警温度
-5.0~50℃ 高温/低温设定间隔 1℃
50
04 U04 低温报警温度 5
05 U05 蒸发风机温度设定 0~40℃ 26
06 U06 蒸发风机温差 1.0~ 5.0℃ 2
07 U10 温控探头校正
-3.0~+3.0
℃
0
08 U11 蒸发器探头校正
-3.0~+3.0
℃
0
09 U12 高温报警失效 0~1 0:禁用;1:启用 1
10 U13 低温报警失效 0~1 0:禁用;1:启用 1
11 U14 系统缺氟失效 0~1 0:禁用;1:启用 1
12 U21 蒸发器探头使能设定 0~1 0:禁用;1:启用 1
13 U22 压缩机工作模式 0~1
0:自动模式(启用压缩机)
1:禁用模式
0
14 U24 风机工作模式 0~1
0:温控模式
1:常开模式
0
15 U26 外部输入告警模式 0~1
0:常闭;
1:常开
0
16 U28 蜂鸣器报警 0~1 0:禁用;1:启用 1
17 U29 压缩机开机延时时间 1~5 分钟 3
18 U30
压缩机最短持续运行
时间
1~5 分钟 3
19 U34 RS485 波特率设定 0~3
0:2400bps
1:4800bps
2:9600bps
3:19200bps
3
20 U35 设备地址 1~99 1
21 U99 密码 0000 ~
9999
---- 1111
22 End 设定结束
控制功能说明:
压缩机控制
◇当测量温度 ≥【制冷设定温度】 + 【温差】,且压缩机停机时间大于【压缩机开机延时时间】,
压缩机开启;
◇当测量温度 ≤【设定温度】,且压缩机开机时间大于【压缩机最短持续运行时间】,压缩机关闭;
例如:【制冷设定温度】为 25 度, 【温差】为 2 度,则当温控传感器检测温度高于 27 度时启动压
缩机,温度
低于 25 度时关闭压缩机,将温度控制在 25~27 度之间;
◇压缩机强制启动:
1.在压缩机关闭情况下,按住〖▼〗键 5 秒不放,可以强制启动压缩机。在压缩机强制启动状态下,
按住〖▼〗键 5
秒不放,可以取消强制启动压缩机,压缩机恢复正常运行。
2.压缩机在强制启动状态下持续运行 60min 后,压缩机恢复正常运行。
压缩机延时保护
◇运行过程中压缩机停机,必须经过【压缩机开机延时时间】才能再次启动;
◇运行过程中压缩机开启,必须经过【压缩机最短持续运行时间】才能以实际情况停机(运行最短
时间为 3min);
风机控制: 控制器在运行过程中,风机按照如下规则运行:
如果风机设定为常开,则送风机始终开启;
如果风机设定为温控则风机根据温控传感器温度进行控制。控制条件如下:
◇当测量温度 ≥【蒸发风机设定温度】 + 【蒸发风机温差】,且风机已经停机时间大于 1 分钟,风机
开启;
◇当测量温度 ≤【蒸发风机设定温度】,且风机开机时间大于 1 分钟,风机关闭;
例如:【蒸发风机设定温度】为 23 度, 【蒸发风机温差】为 2 度,则当温控传感器检测温度高于
25 度时启动风机,温度低于 23 度时关闭风机,将温度控制在 23~25 度之间;
4.维护与保养
请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机
器上安装的是尼龙滤网的可直接从侧面拔出
4-1 定期清洁
本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,
一般每周需清洗一次;
⑵ 请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发
生触电事故;
4-2 长时间停用时注意
⑴ 请切断电源,以防意外;
⑵ 清理冷凝器、过滤网及内部油污;
⑶ 请对机器采取防尘措施,延长机器使用寿命。
4. 故障排除
故障状况 1 电源接通后,室内、室外风机不运转
可能原因
※保险丝熔断
※停电或无电源
状况排除
※更换保险丝
※检查电源状况
故障状况 2 在运行中突然停机,电控箱内温度高于设定点温度两度以上
可能原因
※环境温度过高,导致压缩机热保护
※过滤网堵塞或者冷凝器过脏,导致压缩机热保护
状况排除
※改善周边环境,使散热畅通
※对过滤器及冷凝器进行清洗
故障状况 3 机器正常运转,却不制冷
可能原因
※压缩机损坏
※制冷系统泄露
※机组蒸发器大面积结霜
状况排除
※更换压缩机,重新抽真空充注制冷剂
※查出泄露处,并重新抽真空加制冷剂
※立即停机,把设定温度调高到 35℃,十分钟后重新开机
◇若上述措施均不能排除故障,请致电本公司咨询!
附录 1:产品技术参数
型号: QFW-2500G
工作电源: 交流 220V ±10% 频率 60Hz ±4%
运行电流: <6.5A
功 率: 1250W
制冷剂: R134a
制冷量: 2500W
防护等级:内循环:IP45 外循环:IP55
循环风量: 内循环:910m ³/h 外循环:1250m ³/h
允许机柜内温度设定范围:25--38℃(出厂设定 30℃)
允许使用环境温度范围:-25--45℃
噪音:55dB
附录 2:电气原理图
室内风机 室外风机 压缩机
M1 M2 M3
C2 C3
L
N
PE
t℃温控器
QFW主回路
-2500G 电路图控制回路
温
控
器
上海勤封电气科技有限公司
地址:上海市嘉定区沪宜公路 1185 号 1 幢 1 层
电话:021-66020797