36kV-VoltagetransformerandauxiliarytypeCAVFuselinks
Specifications
Description
Voltage transfomer fuse links.suitable for the protection of auxiliary transformers.
Ratings
Voltage:36kV Current:2-4A Breaking capacity: 40 kA
Agency information
Comply with IEC 60282-1.
Time-current curves and cut-off curves See list page 104
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typical applications
·Protectionofauxiliary transformers.
Dimensions-mm
| Fuse link reference | A(mm) |
| CAV | 440 |
| Cold | ||||||||
| Part numbers | Current 1 (A) | Breaking capacity 1(kA) | resistance | Minimum | Maximum Length | Diameter | Weight kg | |
| 36CAV2 | 2 | 40 | m 3.12 | pre-arcing 6.2 x 100 | operating 1.8 x 101 | mm 440 | mm 41.3 | 1.2 |
| 36CAV4 | 4 | 40 | 1.12 | 4.8×101 | 1.4 x 102 | 440 | 41.3 | 1.2 |
38 kV- Voltage and auxiliary transformer type CAV Fuse links
Specifications
Description
Voltage transfomer fuse links.suitable for the protection of auxiliary transformers.
Ratings
ated Voltage:38 kV Current: 0.5-4A Breaking capacity: 40 kA
Agency information
Comply with IEC 60282-1.
Time-currentcurvesand cut-off curves
See list page 104
Featuresandbenefits
·Cool running,low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possible standards are maintained.
Partnumbersandtechnicaldata
Typical applications
·Protection of auxiliary transformers.
| Fuse link reference | A (mm) |
| CAV and CAVH | 440 |
| Part numbers | Current 1 (A) | Breaking capacity 1(kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight kg |
| 38CAV4E | 4 | 40 | 2.42 | 1.2 x 101 | 3.4x 101 | 440 | 41.3 | 1.2 |
| 38CAVH0.5E | 0.5 | 40 | 66.6 | 1.4 x 101 | 9x101 | 440 | 41.3 | 1.2 |
| 38CAVH1E | 1 | 40 | 66.6 | 1.4x 101 | 9x101 | 440 | 41.3 | 1.2 |
| 38CAVH2E | 2 | 40 | 2.2 | 1.8 x 101 | 1.1 x 102 | 440 | 41.3 | 1.2 |
Mediumvoltageoilfuselinks
Introductiontocurrentlimitingfuse linksforuse inoil switchgear. 34
British standard
3.6kV. .55
7.2kV.. .56
12 kV. .57
15.5kV ..58
17.5 kV .59
24kV .60
Introduction to current limiting fuse links for use in oil switchgear
·Fuse Links comply with IEC 60282-1,BS 2692-1 and ESl standard 12-8.
· 7.2 and 1 2 k V Fuse links tested at highest system voltageand approved by the UK Electricity Association approvalspanel.
·Voltage ranges from 3.6 to 24 kV.
·Fitted with powerful pyrotechnic striker pin.
Eaton'sBussmannseriesunderoil fuselinks
Eaton's Bussmann series oil tight fuse linksare designed for use in oil filled switchgear.This type was pioneered in the UK.Eaton has been in continuous manufacture for almost 40 years,being by far the mostwidely used device of itskind in the world.Over 1,0oo,oo0 Eaton's Bussmann series branded fuse links have been put into service without a single reported caseof oil ingress.Aunique triple seal system ensuresagainst long term seal deterioration.Low power dissipation ensures long running in oil filled switchgear.
Application
Oil medium voltage fuse linksare suitable for primary side transformerprotectionandoil filledswitchcombinationunit.
The range is not suitable foruse inside oil filled transformer tankswhere high oil temperatures may be expected.
Application procedure
Forany transformer the fuse current rating is determined by magnitude and duration of inrush current.
General Guide to the Selection of OilTightFuseLinks forUse in Primary Circuit of Three Phase Transformers.
Selectionofthese fuselinkshasbeenbased onacompromise betweenthe following:
1-Withstandagainstmagnetisinginrushcurrentis takenas12timesfull-loadcurrentfor0.1second.
2-Withstandagainst15o%permissibleoverload current.Recommendationsmarkedwiththe following:
\*Limitedtopermissibleoverloadof130%.
\*\* Permitsuse of a 12 kV OHFMA 80A fuse link witha1oo0kVAtransformerwherepermissible overloaddoesnotexceed \mathbb { E } ( \mathbb { P } _ { i } ^ { { n } }
3-For6.6kVsystems,12kVfuselinksare recommendedwherepossibleintheinterests ofstandardisation.
4-Wherever possible,254mm long fuse linksare offeredratherthanequivalent359mmtypes.
5-Theaboverecommendationsarenotgenerally applicabletotransformersfeedingmotor circuitswithstartingcurrentsinexcessofthe transformerfullloadcurrent.Inthiseventplease consult Eaton'sBussmannseriesapplication engineers:buletechnical@eaton.com.
| 3.3kV | 6.6kV | 11kV | 13.8kV | |||||||||
| Transformer kVA | Product code | Current (A) | Voltage kv | Product code | Current (A) | Voltage kv | ESI 12-8 Ref | Product code | Current (A) | Voltage kv | Product code (A) | Current Voltage kv |
| 200 | OEFMA | 63 | 3.6 | OEFMA | 31.5 | 12 | 01 | OEFMA | 25 | OEFMA 16 | 15.5 | |
| 250 | OEFMA | 80 | 3.6 | OEFMA | 40 | 12 | OEFMA 25 | 12 12 | OEFMA | 20 | 15.5 | |
| 300/315 | OEFMA | 100 | 3.6 | OEFMA | 50 | 12 | OEFMA 31.5 | 12 | OEFMA | 25 | 15.5 | |
| 400 | OEFMA | 125 | 3.6 | OEFMA | 63 | 12 | OEFMA 40 | 12 | OEFMA | 31.5 | 15.5 | |
| 500 | OEFMA | 160 | 3.6 | OEFMA | 71 | 12 | OEFMA 50 | 12 | OEFMA | 40 | 15.5 | |
| 630 | OEFMA | 200 | 3.6 | OEFMA | 100 | 7.2 | 03 | OHFMA 63 | 12 | OEFMA | 50 | 15.5 |
| 750/800 | OLGMA | 250 | 3.6 | OHGMA | 125 | 7.2 | 04 | OHFMA 80 | 12 | OEFMA | 63 | 15.5 |
| 1000 | OLGMA | 250* | 3.6 | OHGMA | 140 | 7.2 | 0GFMA 90** | 12 | OHGMA | 71 | 15.5 | |
| 1250 | 1 | OHGMA | 160* | 7.2 | OGFMA 100 | 12 | OHGMA | 90 | 15.5 | |||
| 1600 | : | OLGMA 125* | 12 | OLGMA | 100* | 15.5 | ||||||
3.6kV-Britishstandardoiltightfuse links
Specifications
Description
Oil tight fuse links suitable for the protection of primary side transformerand oil filled fuse switch combination unit.
Ratings
Voltage:3.6kV Current: 6.3 - 250 A Breaking capacity: 50 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-current curves and cut-off curves See list page 118
Featuresandbenefits
·Cool running,low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typicalapplications
·Primary side transformer protection. ·Oil filled fuse switch combination unit. The range is not suitable for use inside oil filled transformer tankswhere high oil temperatures may be expected.
| Current | Breaking capacity | Cold resistance | Dimensional | ||||||
| Minimum | Maximum | Reference | Length | Diameter | Weight | ||||
| Part numbers 3.60EFMA6.3 | 1(A) 6.3 | 1(kA) 50 | m 207 | pre-arcing 2x101 | operating 4.9 x 10 | BS 2692 F01 | mm 254 | mm | kg |
| 10 | 50 | 83.6 | 1.4 x 102 | 1.4 x 103 | F01 | 254 | 63.5 63.5 | 1.9 1.9 | |
| 3.60EFMA10 | |||||||||
| 3.60EFMA16 3.60EFMA20 | 16 20 | 50 50 | 42.5 33.9 | 1.7 × 102 2.7 x 102 | 2.4 x 103 3.6x 103 | F01 F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA25 | 25 | 50 | 26.5 | 4.5x 102 | 4.8 x 103 | F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA31.5 | 31.5 | 50 | 17.6 | 1x 103 | 8.8x103 | F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA40 | 40 | 50 | 15.4 | 8.9 x 103 | 1×104 | F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA50 | 50 | 50 | 11.5 | 1.6x 103 | 1.4 x 104 | F01 | 254 254 | 63.5 | 1.9 |
| 3.60EFMA63 | 63 | 50 | 7.60 | 3.3x103 | 2.4 x 104 | 63.5 | 1.9 | ||
| 3.60EFMA80 | 80 | 50 | 63 | 5.2x 103 | 3.4x 104 | F01 F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA100 | 100 | 50 | 42 | 1.2 x 104 | 6.2 × 104 | F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA125 | 125 | 50 | 32 | 2.1 × 104 | 9.6×104 | 254 | 63.5 | 1.9 | |
| 3.60EFMA160 | 160 | 50 | 2.21 | 1.5x 104 | 1.6 x 105 | F01 | 254 | 63.5 | 1.9 |
| 3.60EFMA200 | 200 | 50 | 1.74 | 2.4 × 104 | 2.3 x 105 | F01 F01 | 254 | 63.5 | 1.9 |
| 3.60EGMA63 | 6.3 | 50 | 11 | 3.2x 103 | 1.9 x 104 | F02 | 254 | 63.5 | 1.9 |
| 3.60EGMA80 | 80 | 50 | 8.70 | 5.2x 103 | 2.7 x 104 | F02 | 254 254 | 63.5 | 2.6 |
| 3.60EGMA100 | 100 | 50 | 5.5 | 5x103 | 4.9 x 104 | F02 | 254 | 63.5 | 2.6 |
| 3.60EGMA125 | 125 | 50 | 4.59 | 7.2 x 103 | 6.4× 104 | F02 | 254 | 63.5 | 2.6 |
| 3.60EGMA160 | 160 | 50 | 3.44 | 1.3x 104 | 1× 105 | F02 | 254 | 63.5 63.5 | 2.6 |
| 3.60EGMA200 | 200 | 50 | 2.29 | 2.9 x 104 | 1.8x 105 | F02 | 254 | 2.6 | |
| 3.60LGMA250 | 250 | 50 | 1.72 | 5.1 x 104 | 2.7 x 105 | F02 | 254 | 63.5 63.5 | 2.6 2.6 |
7.2kV-Britishstandard oiltightfuse links
Specifications
Description
Oil tight fuse linkssuitable for theprotectionof primaryside transformer and oil filled fuse switch combination unit.
Ratings
Voltage: 7.2 kV Current:80 - 160A Breaking capacity: 45 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-currentcurvesand cut-off curves
See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivityand low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typical applications
·Primary side transformerprotection. ·Oil filled fuse switch combination unit. The range is not suitable foruse inside oil filled transformer tankswhere highoil temperaturesmaybe expected.
| Breaking | Cold | Dimensional | |||||||
| Part numbers | Current I (A) | capacity 1(kA) | resistance mΩ | Minimum pre-arcing | Maximum | Reference BS 2692 | Length | Diameter | Weight |
| 7.20EFMA80 | 80 | 45 | 8.36 | 3.2 x 103 | operating 5.8x 104 | F01 | mm 254 | mm 63.5 | kg 1.9 |
| 7.20EFMA100 | 100 | 45 | 5.59 | 9x104 | F01 | 254 | 63.5 | 1.9 | |
| 7.20EFMA112 | 112 | 45 | 4.57 | 6.3x 103 9.1 × 103 | 1.3x 105 | F01 | 254 | 1.9 | |
| 7.20HGMA100 | 100 | 45 | 7.5x 104 | F02 | 63.5 | ||||
| 7.20HGMA125 | 125 | 45 | 69 58 | 5x103 7.2 x 102 | 9.6x 104 | F02 | 359 359 | 63.5 | 2.6 2.6 |
| 7.20HGMA140 | 140 | 45 | 4.35 | 9.8× 103 | 1.4 × 105 | F02 | 359 | 63.5 63.5 | 2.6 |
| 7.20HGMA160 | 160 | 45 | 3.81 | 1.3 x 104 | 1.8× 105 | F02 | 359 | 63.5 | 2.6 |
12kV-Britishstandardoil tightfuse links
Specifications
Description
Oil tight fuse links suitable for the protection of primary side transformerand oil filled fuse switch combination unit.
Ratings
Voltage: 12kV Current: 6.3 - 125A Breaking capacity: 40 -45 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-current curves and cut-off curves See list page 118
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typicalapplications
·Primary side transformer protection. ·Oil filled fuse switch combination unit. The range is not suitable for use inside oil filled transformer tanks where high oil temperatures may be expected.
| Breaking | Cold resistance | Dimensional | |||||||
| Current | capacity | Minimum | Maximum | Reference | Length | Diameter | Weight | ||
| Partnumbers | (A) 6.3 | 1(kA) 40 | m 520 | pre-arcing 2x101 | operating | BS2692 | mm | mm | kg |
| 120EFMA6.3 | 40 | 6.1x 102 | F01 | 254 | 63.5 | 1.9 1.9 | |||
| 120EFMA10 | 10 | 214 | 1.4× 102 | 1.8 x 103 | F01 | 254 | 63.5 | ||
| 120EFMA16 | 16 | 40 | 108 | 1.7 x 102 | 3×103 | F01 | 254 | 63.5 | 1.9 |
| 120EFMA20 120EFMA25 | 20 | 40 | 77 | 3.4x 102 | 5x103 | F01 | 254 | 63.5 | 1.9 |
| 25 | 40 | 57.8 | 4x102 | 6.5x103 | F01 | 254 | 63.5 | 1.9 | |
| 120EFMA31.5 120EFMA40 | 31.5 | 40 | 38.5 | 8.9 x 102 | 1.2 x 104 | F01 | 254 | 63.5 | 1.9 |
| 120EFMA50 | 40 | 40 | 28.2 | 1.5x 103 | 1.8x 104 | F01 | 254 | 63.5 | 1.9 |
| 120EFMA63 | 50 | 40 | 20.1 | 2.9 x 103 | 2.8x 104 | F01 | 254 | 63.5 | 1.9 |
| 120HFMA71 | 63 | 40 | 15.1 | 5.1 x 103 | 4.3x 104 | F01 | 254 | 63.5 | 1.9 |
| 120HFMA80 | 71 | 45 | 12.3 | 3.2x 103 | 5.4x 104 | F01 | 254 | 63.5 | 1.9 |
| 80 | 45 | 10.9 | 4.1 x 103 | 7x104 | F01 | 254 | 63.5 | 1.9 | |
| 120HGMA6.3 120HGMA10 | 6.3 | 40 | 520 | 2x101 | 6.1x 102 | F02 | 359 | 63.5 | 2.6 |
| 10 | 40 | 214 | 1.4× 102 | 1.8 x 103 | F02 | 359 | 63.5 | 2.6 | |
| 120HGMA16 120HGMA20 | 16 | 40 | 108 | 1.7x 102 | 3x103 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA25 | 20 25 | 40 | 77 | 3.4× 102 | 5x103 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA31.5 | 31.5 | 40 | 57.8 | 4x 102 | 6.5x 105 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA40 | 40 | 40 | 38.5 | 8.9 x102 | 1.2 x 104 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA50 | 50 | 40 | 28.2 | 1.5x 103 | 1.8x 104 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA63 | 63 | 40 | 22.6 | 2.3x 103 | 2.4× 104 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA71 | 71 | 40 | 17 | 4.1× 10 | 3.7× 104 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA80 | 80 | 40 | 16.6 | 2x 103 | 3.9x104 | F02 | 359 | 63.5 | 2.6 |
| 90 | 40 | 13.4 | 3.2x 103 | 5.5x 104 | F02 | 359 | 63.5 | 2.6 | |
| 120HGMA90 | 100 | 40 40 | 12.2 | 3.8x 103 | 6.2x104 8.9 x 104 | F02 | 359 | 63.5 | 2.6 |
| 120HGMA100 120LGMA125 | 125 | 40 | 8.75 79 | 6.3x 103 1x 104 | 1.7 x 105 | F02 F02 | 359 359 | 63.5 63.5 | 2.6 2.6 |
15.5kV-Britishstandardoiltightfuselinks
Specifications
Description
Oil tight fuse linkssuitable for theprotectionof primaryside transformerand oil filled fuse switch combinationunit.
Ratings
Voltage:15.5kV Current: 6.3- 100 A Breaking capacity: 40 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-currentcurvesand cut-off curves
See list page 118
Featuresandbenefits
·Cool running,low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possible standards are maintained.
Partnumbersandtechnicaldata
Typical applications
·Primary side transformer protection.
· Oil filled fuse switch combination unit.
The range is not suitable for use inside oil filled transformer tankswhere high oil temperatures may be expected.
| Breaking capacity | Cold resistance | Dimensional | |||||||
| Part numbers | Current | m | Minimum | Maximum | Reference | Length | Diameter | Weight kg | |
| 15.50EFMA6.3 | 1 (A) 6.3 | 1(kA) 40 | 392 | pre-arcing 4.8×101 | operating 1x103 | BS2692 F01 | mm 254 | mm 63.5 | 1.9 |
| 15.50EFMA10 | 10 | 40 | 188 | 4x 101 | 3.4x 103 | F01 | 254 | 63.5 | 1.9 |
| 15.50EFMA16 | 16 | 40 | 101 | 2.7× 101 | 3.4x 103 | F01 | 254 | 63.5 | 1.9 |
| 15.50EFMA20 | 20 | 40 | 78.7 | 4.5x 101 | 4.9 × 10 | F01 | 254 | 1.9 | |
| 15.50EFMA25 | 25 | 40 | 55.3 | 5.2 x 101 | 1.1 x 104 | F01 | 254 | 63.5 | 1.9 |
| 15.50EFMA31.5 | 31.5 | 40 | 36.9 | 1.2 x 103 | 1.5 x 104 | F01 | 254 | 63.5 | 1.9 |
| 15.50EFMA40 | 40 | 40 | 29.5 | 1.8 x 103 | 1.5x 104 | F01 | 254 | 63.5 | |
| 15.50EFMA50 | 50 | 40 | 22.1 | 3.3x 103 | 3x 104 | F01 | 254 | 63.5 | 1.9 |
| 15.50EFMA63 | 63 | 40 | 17.8 | 2x103 | 3.9 x 104 | F01 | 254 | 63.5 | 1.9 |
| 15.50HGMA71 | 71 | 40 | 17.7 | 2.5x 103 | 4.4× 104 | F02 | 63.5 | 1.9 | |
| 15.50HGMA80 | 80 | 40 | 15.5 | 3.2× 103 | 5.4 x 104 | F02 | 359 359 | 63.5 | 2.6 |
| 15.50HGMA90 | 90 | 40 | 11.6 | 5x 103 | 7.5 x 104 | F02 | 359 | 63.5 63.5 | 2.6 |
| 15.50LGMA100 | 100 | 40 | 10 | 7.2 x 103 | 9.6x 104 | F02 | 359 | 63.5 | 2.6 2.6 |
17.5kV-Britishstandardoiltightfuselinks
Specifications
Description
Oil tight fuse links suitable for the protection of primary side transformerand oil filled fuse switch combinationunit.
Ratings
Voltage:17.5kV Current: 6.3 - 80 A Breaking capacity: 35 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-current curves and cut-off curves See list page 118
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typical applications
·Primary side transformer protection.
· Oil filled fuse switch combination unit.
The range isnot suitable foruse inside oil filled transformer tankswhere highoil temperaturesmay be expected.
| Breaking | Cold | Dimensional | ||||||||
| Part numbers | Current 1 (A) | capacity 1(kA) | resistance mΩ | Minimum pre-arcing | Maximum operating | Reference BS 2692 | Length mm | Diameter mm | kg | Weight |
| 17.50HGMA6.3 | 6.3 | 35 | 665 | 2x101 | 6.1 x 102 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA10 | 10 | 35 | 282 | 1.4× 102 | 1.8x 103 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA16 | 16 | 35 | 139 | 1.7 x 102 | 3x103 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA20 | 20 | 35 | 100 | 3.4x 102 | 5x103 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA25 | 25 | 35 | 74.7 | 4x102 | 6.5x 103 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA31.5 | 31.5 | 35 | 49.8 | 9x102 | 1.2 x 104 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA40 | 40 | 35 | 36.5 | 1.5x103 | 1.9 x 104 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA50 | 50 | 35 | 26 | 2.9 x 103 | 2.9 x 104 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA63 | 63 | 35 | 19.5 | 5.2x 103 | 4.5 x 104 | F02 | 359 | 63.5 | 2.6 | |
| 17.50HGMA80 | 80 | 35 | 15.5 | 3.8x 103 | 5.7 x 104 | F02 | 359 | 63.5 | 2.6 | |
24kV-Britishstandardoiltightfuse links
Specifications
Description
Oil tight fuse linkssuitable for theprotectionof primaryside transformerand oil filled fuse switch combination unit.
Ratings
Voltage:24 kV Current: 6.3- 50A Breaking capacity: 25 kA
Agency information
Complywith IEC 60282-1,BS2692-1 and ESl standard 12-8.
Time-currentcurvesand cut-off curves
See list page 118
Featuresandbenefits
·Cool running,low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possible standards are maintained.
Partnumbersandtechnicaldata
Typical applications
·Primary side transformer protection.
·Oil filled fuse switch combination unit.
The range is not suitable for use inside oil filled transformer tankswhere high oil temperatures may be expected.
| Current | Breaking capacity | Cold resistance | Dimensional | ||||||
| Minimum | Maximum | Reference | Length | Diameter | Weight | ||||
| Part numbers 240EGMA6.3 | 1 (A) 6.3 | 1(kA) 25 | m 605 | pre-arcing 4.8x101 | operating 1x 103 | BS2692 F02 | mm 359 | mm 63.5 | kg 2.6 |
| 240EGMA10 | 10 | 25 | 290 | 2.5x 102 | 3.4x 103 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA16 | 16 | 25 | 153 | 2.7× 102 | 3.4x 103 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA20 | 20 | 25 | 119 | 4.4x 102 | 4.9 x 103 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA25 | 25 | 25 | 84.5 | 5.2 x 10 | 1.1 × 104 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA31.5 | 31.5 | 25 | 55.9 | 1.2 x 103 | 1.5 x 104 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA40 | 40 | 25 | 44.7 | 1.8x 103 | 2×104 | F02 | 359 | 63.5 | 2.6 |
| 240EGMA50 | 50 | 25 | 34 | 1.2 x 103 | 2.4x 104 | F02 | 359 | 63.5 | 2.6 |
MediumvoltageBritishstandardairfuse links
Introductiontocurrentlimitingfuselinksforuseinair 62
Britishstandard
3.6kV 63
7.2kV 65
12kV 67
15.5kV 69
24 kV. 70
36kV.. 71
72.5kV 72
Introductiontocurrentlimitingfuselinksforuseinair
·Medium voltage fuse links for use in air,comply with BS 2962-1 dimensions.
·Available involtage from3.6 kVto 72.5 kV.
·Full rangeperformance optionavailable at12kVand 24kV.
·Wide variety of fixing arrangements available.
·Powerful pyrotechnic striker fitted.
·E-rated North American dimension products also available.
·Suitable for indoor and outdoor use.
Eaton'sBussmannseriesfuse linksforuse inAir
Eaton's Bussmannseries fuse links foruse inairareavailable inBritishStandard form,BS2692,Part11975.A number of optionsare available,including Fullrange capability,and alternative fixing arrangements such as different types of tags,studsand collars etc.Detailsareavailable onapplication. Higher current ratings can be obtained by using fuse links in parallel and special fixingarrangementsare available for this purpose.
Eaton'sBussmannseriesfuse links-USADimensions
Acomprehensive range of 'E'rated North American dimension fuse linksfor industrialapplicationsisalsoavailable.These are the latest technology Fullrange fuse links in USA Industrial Standard2 inch and3 inch diameter ferrule style. Extended ratings in double barrel assemblies; striker,indicatorand tag versionsarealsoavailable,see Pages74 to 88.
Application
Airfuse linksaresuitableforprimarysidetransformer protection,fuse switch combination unit, fuse bases and fuse switches.
Selectionoffusetheselinkshasbeenbasedon acompromisebetweenthe following:
1-Thefuselinksshouldwithstandtransformer magnetisinginrushcurrents,takenas12timesfullload currentfor0.1seconds.
2- The fuse linksshould discriminate with the highest ratingof secondary fuse links.
3-The fuse links should withstand periodic overcurrents ofupto 15o% of transformer fuse load current.
4- The fuse linksshould operate reasonably quickly in the eventofatransformerinter-turnfaultorafaultinthe secondaryterminalzoneofthetransformer.
Notes
a)Theaboverecommendationsarenotgenerally applicable totransformersfeedingmotorcircuitswith startingcurrentsinexcessof the Current fuse. Inthis event,pleaseconsultEatonapplicationengineers.
b)For 6.6kV transformers,12 kVfuse linksare recommended,where therequired currentrating isavailable.
\*Where the transformer isnotsubjected to periodic overcurrents,a lowerfuseratingmaybesuitable,fuse ratingsmarked with "\*",are only suitable for use with the transformersizes quoted,where significantover loading doesnotoccur.
Fuse linksforuse intransformerswith primaryvoltages of3.3,22and33kVareavailable,please consultEaton applicationengineersforfurtherdetails buletechnical@eaton.com.
| TranstormerPriorityVoltage | |||||||||
| Transformer | 6.6kV | 13.8 kV | |||||||
| KVA | Product code | Current (A) | Voltage (kv) | Product code | Current (A) | Voltage (kv) | Product code | Current (A) | Voltage (kV) |
| 200 | BDG | 31.5 | 12 | BDG | 20 | 12 | BDG | 20 | 15.5 |
| 250 | BDG | 40 | 12 | BDG | 25 | 12 | BDG | 25 | 15.5 |
| 300/315 | BDG | 50 | 12 | BDG | 31.5 | 12 | BDG | 31.5 | 15.5 |
| 400 | BFG | 63 | 12 | BDG | 40 | 12 | BDG | 40 | 15.5 |
| 500 | BFG | 80 | 12 | BDG | 50 | 12 | BFG | 50 | 15.5 |
| 630 | BFG | 90 | 12 | BFG | 63 | 12 | BFG | 63 | 15.5 |
| 750/800 | BFG | 125 | 7.2 | BFG | 71 | 12 | BFG | 63 | 15.5 |
| 1000 | BFG | 140 | 7.2 | BFG | 90 | 12 | BFG | 85 | 15.5 |
| 1250 | BFG | 160 | 7.2 | AKG | 112 | 12 | BFG | 85* | 15.5 |
| 1500 | BFG | 160* | 7.2 | AKG | 125* | 12 | |||
3.6kV-Britishstandardairfuselinks
Specifications
Description
Air fuse links for the protection of primary side transformer. Theyare also used in fuse switch combination unit, fuse bases and fuse switches
Ratings
Voltage:3.6kV Current: 6.3 - 100 A Breaking capacity:25-40 kA
Agency information
Comply with BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves
See list page 118
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possible standardsare maintained.
Typicalapplications
·Primary side transformer protection.
·Used in fuse switch combination unit.
·Used in fuse bases.
·Used in fuse switches.
Dimensions-mm
| Tagstype | Code | A B | C | Dg |
| A | ADGHA | 359 N/A | N/A | 51 |
| C&D | ADFHC | 356 | 314 254 | 51 |
| ADGHC | 461 | 419 | 51 | |
| F | ADFHF | 356 | 314 | 359 254 51 |
| ADGHF | 461 | 419 359 | 51 |
ATags
3.6kV-Britishstandardairfuselinks
Partnumbersandtechnicaldata
| Partnumbers | Current (A) | Breaking capacityl, (kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight |
| 3.6ADFH*6.3 | 6.3 | 40 | 208 | 4.8 x 101 | 7.2 x 102 | 254 | 50.8 | kg 1.5 |
| 3.6ADFH*10 | 10 | 40 | 91.8 | 2.3x 102 | 2.3x 103 | 254 | 50.8 | 1.5 |
| 3.6ADFH*16 | 16 | 40 | 31.1 | 7.2 x 101 | 1x 103 | 254 | 50.8 | 1.5 |
| 3.6ADFH*20 | 20 | 40 | 24.9 | 1.1 x 102 | 1.5 x 103 | 254 | 50.8 | 1.5 |
| 3.6ADFH*25 | 25 | 40 | 18.6 | 2x102 | 2.1 x 103 | 254 | 50.8 | 1.5 |
| 3.6ADFH*31.5 | 31.5 | 40 | 14.9 | 3.1 x 102 | 2.8 x 103 | 254 | 50.8 | 1.5 |
| 3.6ADFH*40 | 40 | 40 | 10 | 7.1 x 102 | 7.7 x 103 | 254 | 50.8 | 1.5 |
| 3.6ADGH*6.3 | 6.3 | 25 | 185 | 4.8× 101 | 7.2 x 102 | 359 | 50.8 | 2.1 |
| 3.6ADGH*10 | 10 | 25 | 77.1 | 3.1x 102 | 4.7x 103 | 359 | 50.8 | 2.1 |
| 3.6ADGH*16 | 16 | 25 | 58.6 | 5.5x 102 | 8.3x 103 | 359 | 50.8 | 2.1 |
| 3.6ADGH*20 | 20 | 25 | 44 | 9.8× 102 | 1.5x 104 | 359 | 50.8 | 2.1 |
| 3.6ADGH*25 | 25 | 25 | 36.9 | 1.3x 102 | 1.5 x 103 | 359 | 50.8 | 2.1 |
| 3.6ADGH*31.5 | 31.5 | 25 | 24.6 | 2.9 x102 | 3.5x 103 | 359 | 50.8 | 2.1 |
| 3.6ADGH*40 | 40 | 25 | 13.9 | 8x102 | 9.6x 103 | 359 | 50.8 | 2.1 |
| 3.6ADGH*50 | 50 | 25 | 9.91 | 1.6 x 103 | 1.9 x 104 | 359 | 50.8 | 2.1 |
| 3.6ADGH*63 | 63 | 25 | 75 | 3.1 x 103 | 3.7x 104 | 359 | 50.8 | 2.1 |
| 3.6ADGH*80 | 80 | 25 | 4.94 | 6.3x 103 | 7.6 x 104 | 359 | 50.8 | 2.1 |
| 3.6ADGH*100 | 100 | 25 | 3.96 | 9.8x 103 | 1.2 × 105 | 359 | 50.8 | 2.1 |
Thereareawidevarietyof endterminationsavailable, the most popular types,some of which have dimensional references to BS2692:Part1,are:
·ADFHC and ADGHC: C Special offset tags,two hole fixings for Brush fuse switch equipment,BS Ref TA3 ·ADFHF and ADGHF:F Ofset tags two bolt fixing
·ADGHA:A No tags- Ferrule- BS Ref.FA3 ADIHA/ BS Ref FA4AFIHA/BSRef FA5- AFKHA
Seeprevious page for outline drawingsand dimensions.
Other tag variants available please consult Eaton'sapplication engineersbuletechnical@eaton.com.
7.2kV-Britishstandardairfuselinks
Specifications
Description
Air fuse links for the protection of primary side transformer. Theyarealsoused in fuseswitch combinationunit,fuse bases and fuse switches
Ratings
Voltage: 7.2 KV Current: 6.3- 160 A Breaking capacity: 20 - 40 kA
Agency information
Complywith BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves
See list page 118
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Typical applications
·Primary side transformer protection.
·Used in fuse switch combination unit.
· Used in fuse bases.
·Used in fuse switches.
Dimensions-mm
| Tagstype | Code | B | C | Dg |
| A | ADGHA | N/A | N/A | 51 |
| BFGHA | 359 359 N/A | N/A | 76 | |
| ADFHC | 356 314 | 254 | 51 | |
| BDGHC 461 | 419 | 359 | 51 | |
| BFGHD | 461 419 | 359 | 76 | |
| ADFHF | 356 314 | 254 | 51 | |
| F | BDGHF | 419 | 359 | 51 |
| AFFHF | 461 356 314 | 254 | 76 | |
| BFGHF | 461 419 | 359 | 76 |
ATags
7.2kV-Britishstandardairfuselinks
Partnumbersandtechnicaldata
| Partnumbers | Current | Breaking capacityl, (kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight |
| 7.2ADFH*6.3 | (A) 6.3 | 20 | 206 | 4.8x101 | 5.6x102 | 254 | 50.8 | kg 1.5 |
| 7.2ADFH*10 | 10 | 20 | 83 | 7.2x101 | 9.4x102 | 254 | 50.8 | 1.5 |
| 7.2ADFH*16 | 16 | 20 | 52.3 | 7.2x101 | 8.6x102 | 254 | 50.8 | 1.5 |
| 7.2ADFH*20 | 20 | 20 | 41.8 | 1.1x102 | 1.5x103 | 254 | 50.8 | 1.5 |
| 7.2ADFH*25 | 25 | 20 | 31.5 | 2x102 | 2.6x103 | 254 | 50.8 | 1.5 |
| 7.2ADFH*31.5 | 31.5 | 20 | 22.8 | 3.8x102 | 4.8x103 | 254 | 50.8 | 1.5 |
| 7.2ADFH*40 | 40 | 20 | 15.6 | 8×102 | 1.1x104 | 254 | 50.8 | 1.5 |
| 7.2ADFH*50 | 50 | 20 | 11.8 | 1.3x103 | 1.4x104 | 254 | 50.8 | 1.5 |
| 7.2ADFH*63 | 63 | 20 | 8.41 | 2.5x103 | 2.9x104 | 254 | 50.8 | 1.5 |
| 7.2AFFH*80 | 80 | 20 | 5.83 | 6.3x103 | 6.9x104 | 254 | 50.8 | 1.5 |
| 7.2AFFH*100 | 100 | 20 | 4.38 | 9.8x103 | 1.4x105 | 254 | 50.8 | 1.5 |
| 7.2BDGH*6.3 | 6.3 | 40 | 206 | 5.1x 101 | 6x102 | 359 | 50.8 | 2.1 |
| 7.2BDGH*10 | 10 | 40 | 83 | 1x102 | 1.3x103 | 359 | 50.8 | 2.1 |
| 7.2BDGH*16 | 16 | 40 | 52.3 | 8.4x101 | 1x103 | 359 | 50.8 | 2.1 |
| 7.2BDGH*20 | 20 | 40 | 41.8 | 1.1x102 | 1.5x103 | 359 | 50.8 | 2.1 |
| 7.2BDGH*25 | 25 | 40 | 31.4 | 2x102 | 2.6x103 | 359 | 50.8 | 2.1 |
| 7.2BDGH*31.5 | 31.5 | 40 | 22.8 | 4.6x102 | 5.8x103 | 359 | 50.8 | 2.1 |
| 7.2BDGH*40 | 40 | 40 | 15.7 | 8×102 | 1.1x104 | 359 | 50.8 | 2.1 |
| 7.2BDGH*50 | 50 | 40 | 11.8 | 1.6x103 | 1.8x104 | 359 | 50.8 | 2.1 |
| 7.2BDGH*63 | 63 | 40 | 7.48 | 3.6x103 | 4.3x104 | 359 | 50.8 | 2.1 |
| 7.2BDGH*80 | 80 | 40 | 5.82 | 6.4x103 | 7x104 | 359 | 50.8 | 2.1 |
| 7.2BFGH*90 | 90 | 40 | 4.72 | 1x104 | 1.4x105 | 359 | 76.2 | 4.2 |
| 7.2BFGH*100 | 100 | 40 | 45 | 1.3x104 | 1.9x105 | 359 | 76.2 | 4.2 |
| 7.2BFGH*125 | 125 | 40 | 3.15 | 1.6x104 | 1.9x105 | 359 | 76.2 | 4.2 |
| 7.2BFGH*140 | 140 | 40 | 2.57 | 2.4x104 | 3.3x105 | 359 | 76.2 | 4.2 |
| 7.2BFGH*160 | 160 | 40 | 2.35 | 2.9x104 | 4x105 | 359 | 76.2 | 4.2 |
Thereare a wide variety of end terminationsavailable, the most popular types,some of which have dimensional references to BS2692: Part1,are:
·ADFHC:C Special offset tags,two hole fixings for Brush fuse switch equipment,BSRefTA3 ·ADFHF: F Offset tags two bolt fixing ·AFFHD:D Special offset tags,two hole fixings for Brush fuse switch equipment,BS Ref TA3 ·AFFHF:F Offset tags two bolt fixing ·BDGHC:C Special offset tags,two hole fixings for Brush fuse switch equipment,BS Ref TA3
·BDGHA:A No tags- Ferrule-BSRef.FA3 ADIHA/BS Ref FA4AFIHA/BSRefFA5- AFKHABDGHF ·BFGHA:ANo tags-Ferrule- BSRef.FA3 ADIHA/BS Ref FA4 AFIHA/ BS Ref FA5- AFKHA ·BFGHF:F Offset tags two bolt fixing
See previous page for outline drawings and dimensions.
Other tag variants available please consult Eaton'sapplication engineers: buletechnical@eaton.com.
12kV-Britishstandardairfuselinks
Specifications
Description
Air fuse links for the protection of primary side transformer. Theyarealsoused in fuseswitch combinationunit,fuse bases and fuse switches
Ratings
Voltage: 12kV Current: 6.3 - 125A Breaking capacity: 12 - 40 kA
Agency information
Comply with BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves
See list page 118
Featuresandbenefits
·Cool running, low watts lossand power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Typical applications
·Primary side transformer protection.
·Used in fuse switch combination unit.
· Used in fuse bases.
·Used in fuse switches.
Dimensions-mm
| Tagstype | Code | A B | C | Dg |
| A | BDGHA 359 | N/A | N/A 51 | |
| AKGHA 359 | N/A | N/A 76 | ||
| BFGHA 359 | N/A | N/A 76 | ||
| C&D | ADFHC 356 | 314 | 254 51 | |
| BDGHC 461 | 419 | 359 51 | ||
| AFFHD 356 | 314 | 254 76 | ||
| AKGHD 461 | 419 | 359 76 | ||
| BFGHD 461 | 419 | 359 76 | ||
| F | ADFHF 356 | 314 | 254 51 | |
| BDGHF 461 | 419 | 359 51 | ||
| AFFHF 356 | 314 | 254 76 | ||
| AKGHF 461 | 419 | 359 76 | ||
| BFGHF 461 | 419 | 359 76 |
ATags
12kV-Britishstandardairfuselinks
Partnumbersandtechnicaldata
| Breaking capacityl, mΩ | Cold resistance | |||||||
| Partnumbers | Current (kA) | Minimum Maximum pre-arcing operating | Length mm | Diameter mm | Weight kg | |||
| 12ADFH*6.3 | (A) 6.3 | 12 | 356 | 4.8× 101 | 5x102 | 254 | 50.8 | 1.5 |
| 12ADFH*10 | 10 | 12 | 89.8 | 1.3x 102 | 2 x 103 | 254 | 50.8 | 1.5 |
| 12ADFH*16 | 16 | 12 | 56.5 | 1.3x 102 | 2x103 | 254 | 50.8 | 1.5 |
| 12ADFH*20 | 20 | 12 | 36.2 | 3.1x 10 | 3.5x103 | 254 | 50.8 | 1.5 |
| 12ADFH*25 | 25 | 12 | 28.3 | 5.1 x 102 | 6.1 x 103 | 254 | 50.8 | 1.5 |
| 12ADFH*31*5 | 31.5 | 12 | 22.6 | 8x102 | 9x103 | 254 | 50.8 | 1.5 |
| 12AFFH*40 | 40 | 12 | 21.8 | 1.2 x 103 | 1.5 x 104 | 254 | 76.2 | 2.8 |
| 12AFFH*50 | 50 | 12 | 15.7 | 2x103 | 2.5x 104 | 254 | 76.2 | 2.8 |
| 12AFFH*63 | 63 | 12 | 12.5 | 3.1x 103 | 3.9 x 104 | 254 | 76.2 | 2.8 |
| 12BDGH*6.3 | 6.3 | 40 | 356 | 5.2 x 101 | 5x102 | 359 | 50.8 | 2.1 |
| 12BDGH*10 | 10 | 40 | 138 | 6.4x 101 | 1 x 103 | 359 | 50.8 | 2.1 |
| 12BDGH*16 | 16 | 40 | 87 | 6.4x 101 | 1x103 | 359 | 50.8 | 2.1 |
| 12BDGH*20 | 20 | 40 | 63.3 | 1.6 x 102 | 1.8 x 103 | 359 | 50.8 | 2.1 |
| 12BDGH*25 | 25 | 40 | 43.5 | 3.2x 102 | 3.8x103 | 359 | 50.8 | 2.1 |
| 12BDGH*31.5 | 31.5 | 40 | 32.6 | 5.8 x 102 | 6.5x103 | 359 | 50.8 | 2.1 |
| 12BDGH*40 | 40 | 40 | 21.8 | 1.2 x 10 | 1.5x 104 | 359 | 50.8 | 2.1 |
| 12BDGH*45 | 45 | 40 | 17.5 | 1.8x 103 | 2.3x 104 | 359 | 5t0.8 | 2.1 |
| 12BDGH*50 | 50 | 40 | 14.5 | 2.5x 103 | 3.2 × 104 | 359 | 50.8 | 2.1 |
| 12BFGH*56 | 56 | 40 | 14.6 | 2.9 x 10 | 3.7x104 | 359 | 76.2 | 4.2 |
| 12BFGH*63 | 63 | 40 | 12.8 | 3.4x 103 | 4.5x 104 | 359 | 76.2 | 4.2 |
| 12BFGH*71 | 71 | 40 | 10.6 | 4.6x 103 | 6.3x104 | 359 | 76.2 | 4.2 |
| 12BFGH*80 | 80 | 40 | 9.73 | 6.1 x 103 | 7.8x 104 | 359 | 76.2 | 4.2 |
| 12BFGH*90 | 90 | 40 | 8.37 | 8.1 x 103 | 1 x 105 | 359 | 76.2 | 4.2 |
| 12BFGH*100 | 100 | 40 | 6.88 | 1.1 x 103 | 1.4x 105 | 359 | 76.2 | 4.2 |
| 12AKGH*112 | 112 | 20 | 5.25 | 1.5 x 104 | 1.9 x 105 | 359 | 76.2 | 4.3 |
| 12AKGH*125 | 125 | 20 | 4.92 | 2.1 x 104 | 2.4x 105 | 359 | 76.2 | 4.3 |
| Full range | ||||||||
| 12FFGN4910 | 10 | 40 | 90.6 | 2.7 x 102 | 4.7 x 103 | 359 | 76.2 | 4.1 |
| 12FFGN4916 | 16 | 40 | 69.1 | 4.2 x 102 | 6.1 x 103 | 359 | 76.2 | 4.1 |
| 12FFGN4920 | 20 | 40 | 45.8 | 9.5 x 102 | 1.1 x 104 | 359 | 76.2 | 4.1 |
| 12FFGN4925 | 25 | 40 | 36.5 | 1.6 x 103 | 1.5 x 104 | 359 | 76.2 | 4.1 |
| 12FFGN4931.5 | 31.5 | 40 | 25.4 | 3.1 x 103 | 2.5x 104 | 359 | 76.2 | 4.1 |
| 12FFGN4940 | 40 | 40 | 19.7 | 4.7 x 103 | 3.8 x 104 | 359 | 76.2 | 4.1 |
| 12FFGN4950 | 50 | 40 | 14.7 | 8.4× 103 | 5.6x 104 | 359 | 76.2 | 4.1 |
| 12FFGN4963 | 63 | 40 | 12.6 | 6.3x 103 | 5.4× 104 | 359 | 76.2 | 4.1 |
Thereareawidevarietyof endterminationsavailable, the most popular types,some of which have dimensional references to BS2692:Part1,are:
·ADFHC: C Special offset tags,two hole fixings for Brush fuse switch equipment,BS Ref TA3 ·ADFHF: F Offset tags two bolt fixing ·AFFHD:D Special offset tags, two hole fixings for Brush fuse switch equipment,BS Ref TA3 ·AFFHF:F Offset tags two bolt fixing ·AKGHD:D Special ofset tags, two hole fixings for Brush fuse switch equipment,BS Ref TA3 ·AKGHA:A No tags- Ferrule- BSRef.FA3 ADIHA/BS Ref FA4 AFIHA /BS Ref FA5 - AFKHA ·AKGHF: F Offset tags two bolt fixing
·BDGHC: C Special offset tags,two hole fixings for Brush fuse switch equipment,BS Ref TA3
·BDGHA: A No tags- Ferrule - BS Ref. FA3 ADIHA/ BS Ref FA4 AFIHA/BSRefFA5- AFKHA
·BDGHF:F Offset tags two bolt fixing
·BFGHA:A No tags-Ferrule- BSRef.FA3 ADIHA/BS Ref FA4 AFIHA/BS Ref FA5 - AFKHA
·BFGHF:F Ofset tags two bolt fixing
·FFGN49:49 Centre tags,single bolt fixing for use in Fused
See opposite page for outline drawingsand dimensions.
Other tag variants available please consult Eaton's application engineers: buletechnical@eaton.com
15.5kV-Britishstandardairfuselinks
Specifications
Description
Airfuse links for the protection of primary side transformer. Theyare also used in fuse switch combination unit, fuse bases and fuse switches
Ratings
Voltage:15.5kV Current: 6.3- 85A Breaking capacity:20-40 kA
Agency information
Complywith BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standards are maintained.
Typical applications
·Primary side transformerprotection. ·Used in fuse switch combination unit,fuse bases and fuse switches.
Dimensions-mm
| Tags type | Code A | B | C | D0 |
| A | BDGHA 359 | N/A | N/A | 51 |
| BFGHA | 359 N/A | N/A | 76 | |
| C&D | BDGHC | 461 419 | 359 | 51 |
| BFGHD | 461 419 | 349 | 76 | |
| F | BDGHF | 461 419 | 359 | 51 |
| BFGHF | 461 419 | 359 | 76 |
Partnumbersandtechnicaldata
A Tags
| Breaking capacityl, | Cold resistance mΩ | |||||||
| Current Part numbers (A) | (kA) | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight kg | ||
| 15.5BDGH*6.3 | 6.3 | 20 | 485 | 4.8x 101 | 8.5x 10 | 359 | 50.8 | 2.1 |
| 15.5BDGH*10 | 10 | 20 | 158 | 7.2 x 101 | 1.2 x 103 | 359 | 50.8 | 2.1 |
| 15.5BDGH*16 | 16 | 20 | 99.1 | 7.2 x 101 | 1.2 x 103 | 359 | 50.8 | 2.1 |
| 15.5BDGH*20 | 20 | 20 | 74.6 | 1.3x 102 | 2.8x 103 | 359 | 50.8 | 2.1 |
| 15.5BDGH*25 | 25 | 20 | 54.2 | 2.4× 102 | 4.3x 103 | 359 | 50.8 | 2.1 |
| 15.5BDGH*31.5 | 31.5 | 20 | 38.2 | 4.9x 102 | 7x 103 | 359 | 50.8 | 2.1 |
| 15.5BDGH*40 | 40 | 20 | 27.2 | 9.6x 102 | 1.2 x 104 | 359 | 50.8 | 2.1 |
| 15.5BFGH*50 | 50 | 20 | 22.2 | 1.6x 103 | 3.2x 104 | 359 | 76.2 | 4.2 |
| 15.5BFGH*63 | 63 | 20 | 15.5 | 3.2x 103 | 4.6 x 104 | 359 | 76.2 | 4.2 |
| 15.5BFGH*80 | 80 | 20 | 9.73 | 7.2 x 103 | 1x 105 | 359 | 76.2 | 4.2 |
| 15.5BFGH*85 | 85 | 20 | 9.45 | 7.2 x 103 | 1x 105 | 359 | 76.2 | 4.2 |
Thereareawidevariety of end terminationsavailable, the most popular types, some of which have dimensional references to BS2692:Part1,are:
BDGHC:C Special offset tags,two hole fixings for Brush fuseswitch equipment,BSRef TA3
BDGHA:ANotags-Ferrule-BSRef.FA3ADIHA/BSRef FA4 AFIHA/BS Ref FA5-AFKHA/BDGHF:F Oset tags two bolt fixing
BFGHA:ANo tags-Ferrule-BSRef.FA3ADIHA/BSRef FA4 AFIHA/BSRef FA5-AFKHA/BFGHF:F Offset tags two bolt fixing
24kV-Britishstandardairfuselinks
Specifications
Description
Airfuse linksforthe protectionof primaryside transformer They are also used in fuse switch combination unit, fuse bases and fuse switches
Ratings
Voltage:24kV
Current: 6.3 - 90 A
Breaking capacity:12-35.5kA
Agency information
Comply with BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standards are maintained.
Partnumbersandtechnicaldata
Typicalapplications
·Primary side transformer protection. ·Used in fuse switch combination unit, fuse bases and fuse switches.
| Tagstype | Code | A | Dg |
| A | ADIHA | 565 | 51 |
| FDIHA | 565 | 51 | |
| AFIHA | 565 | 76 |
| Part numbers | Current (A) | Breaking capacity , (kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight |
| 24ADIHA6.3 | 6.3 | 12 | 520 | 7.9 x 101 | 8.5 x 10 | 565 | 50.8 | kg 3 |
| 24ADIHA10 | 10 | 12 | 173 | 7.2 x 101 | 1.1 x 102 | 565 | 50.8 | 3 |
| 24ADIHA16 | 16 | 12 | 129 | 1.3x 102 | 1.7 x103 | 565 | 50.8 | 3 |
| 24ADIHA20 | 20 | 12 | 104 | 2x102 | 2.8x 103 | 565 | 50.8 | 3 |
| 24ADIHA25 | 25 | 12 | 82.7 | 3.1 x 102 | 4.1 x 103 | 565 | 50.8 | 3 |
| 24ADIHA31.5 | 31.5 | 12 | 66.2 | 4.9 x 102 | 6.8x 103 | 565 | 50.8 | 3 |
| 24AFIHA40 | 40 | 16 | 46.5 | 1.2 x 103 | 1.1 x 104 | 565 | 76.2 | 6.1 |
| 24AFIHA50 | 50 | 16 | 33.2 | 2.4 × 103 | 2.2 x 104 | 565 | 76.2 | 6.1 |
| 24AFIHA63 | 63 | 16 | 23.5 | 3.2x 103 | 5.2x104 | 565 | 76.2 | 6.1 |
| 24AFIHA80 | 80 | 16 | 17.9 | 5.5x 103 | 8.2x 104 | 565 | 76.2 | 6.1 |
| 24AFIHA90 | 90 | 16 | 14.7 | 7.2 x 103 | 1x 105 | 565 | 76.2 | 6.1 |
| Full range | ||||||||
| 24FDIHA3.15 | 3.15 | 35.5 | 893 | 3.1x 101 | 9.8x 101 | 565 | 50.8 | 3 |
| 24FDIHA5 | 5 | 35.5 | 412 | 5.9x 101 | 4.5 x 102 | 565 | 50.8 | 3 |
| 24FDIHA6.3 | 6.3 | 35.5 | 412 | 5.9x 101 | 4.5 × 102 | 565 | 50.8 | 3 |
| 24FDIHA10 | 10 | 35.5 | 205 | 2.7 x 102 | 2.1 x 103 | 565 | 50.8 | 3 |
| 24FDIHA16 | 16 | 35.5 | 103 | 1.1 x 10 | 8.3x 103 | 565 | 50.8 | 3 |
| 24FDIHA20 | 20 | 35.5 | 88.2 | 1.3x 103 | 4.8x 103 | 565 | 50.8 | 3 |
| 24FDIHA31.5 | 31.5 | 35.5 | 56 | 5.3 x 103 | 2x104 | 565 | 50.8 | 3 |
Therearea wide variety of end terminationsavailable, the most popular types,some of which have dimensional references to BS2692: Part1,are:
·ADIHA: A No tags- Ferrule- BS Ref.FA3 ADIHA/ BS RefFA4 AFIHA / BS Ref FA5 - AFKHA
Other tag variantsavailable please consult Eaton application engineersbuletechnical@eaton.com
36kV-Britishstandardairfuselinks
Specifications
Description
Airfuse linksforthe protectionof primaryside transformer They are also used in fuse switch combination unit, fuse bases and fuse switches
Ratings
Voltage:36kV Current:3.15-71A Breaking capacity:12-35.5kA
Agency information
Comply with BS 2962-1 dimensions.
Time-currentcurvesandcut-offcurves See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standards are maintained.
Partnumbersandtechnicaldata
Typicalapplications
·Primaryside transformerprotection. ·Used in fuse switch combination unit, fuse bases and fuse switches.
| Tagstype | Code | A | Dg |
| A | ADIHA | 565 | 51 |
| AFIHA | 565 | 76 | |
| AFKHA | 914 | 76 |
| Partnumbers | Current | Breaking capacity 1, (kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum | Length | Diameter | Weight |
| 36ADIHA3.15 | (A) 3.15 | 16 | 1460 | 2x101 | operating 2.5 x 102 | mm 565 | mm 50.8 | kg 3 |
| 36ADIHA5 | 5 | 16 | 973 | 4.4x 101 | 5.5x 102 | 565 | 50.8 | 3 |
| 36ADIHA6-3 | 6.3 | 16 | 781 | 7.1 x 101 | 8.9x102 | 565 | 50.8 | 3 |
| 36ADIHA10 | 10 | 16 | 378 | 7.2 x 101 | 1.1× 103 | 565 | 50.8 | 3 |
| 36ADIHA16 | 16 | 16 | 190 | 1.1 x 102 | 1.7 x 103 | 565 | 50.8 | 3 |
| 36ADIHA20 | 20 | 16 | 142 | 2x102 | 2.8x 103 | 565 | 50.8 | 3 |
| 36ADIHA25 | 25 | 16 | 115 | 3.1 x 102 | 4.5x 103 | 565 | 50.8 | 3 |
| 36ADIHA31.5 | 31.5 | 16 | 81.5 | 6.1 x 102 | 8.1 x 103 | 565 | 50.8 | 3 |
| 36AFIHA40 | 40 | 25 | 61.5 | 1.2 x 10 | 1.9 x 104 | 565 | 76.2 | 6.1 |
| 36AFKHA50 | 50 | 25 | 54.5 | 1.9 x 103 | 2.8x 104 | 914 | 76.2 | 9.7 |
| 36AFKHA63 | 63 | 25 | 40.6 | 3.5x 103 | 5x104 | 914 | 76.2 | 9.7 |
| 36AFKHA71 | 71 | 25 | 32.5 | 5.5x 103 | 8.2× 104 | 914 | 76.2 | 9.7 |
Thereareawidevarietyofendterminationsavailable, the most popular types,some of which have dimensional references to BS2692: Part1,are:
ADIHA:ANo tags-Ferrule- BSRef.FA3ADIHA/BSRefFA4AFIHA/BSRefFA5-AFKHA
AFIHA:ANo tags-Ferrule- BSRef.FA3 ADIHA/BS Ref
FA4 AFIHA / BS Ref FA5 - AFKHA
AFKHA:ANo tags-Ferrule-BSRef.FA3ADIHA/BSRef FA4 AFIHA/BS Ref FA5- AFKHA
See previous page for outline drawings and dimensions.
Other tag variants available please consult Eaton's application engineers.
72.5kV-Britishstandardairfuselinks
Specifications
Description
Air fuse links for the protection of primary side transformer. Theyare also used in fuse switch combination unit, fuse bases and fuse switches
Ratings
Voltage: 72.5 kV Current:3.15-40 A Breaking capacity:12 kA
Agency information
Complywith BS 2962-1 dimensions.
Time-currentcurvesand cut-offcurves See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. ·Silver elements ensuring high conductivity and low power (revenue) loss. · 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possiblestandardsaremaintained.
Typical applications
·Primary side transformer protection. ·Used in fuse switch combinationunit, fuse basesand fuse switches.
ATags
| Tagstype | Code | A | Dg |
| A | AFKHA | 914 | 76 |
Partnumbersandtechnicaldata
| Part numbers | Current (A) | Breaking capacity 1 (kA) | Cold resistance mΩ | Minimum pre-arcing | Maximum operating | Length mm | Diameter mm | Weight |
| 72.5AFKHA3.15 | 3.15 | 12 | 4230 | 1.4 × 101 | 1.8 x 102 | 914 | 76.2 | kg 9.7 |
| 72.5AFKHA5 | 5 | 12 | 1600 | 1.1 × 102 | 1.4x 103 | 914 | 76.2 | 9.7 |
| 72.5AFKHA6.3 | 6.3 | 12 | 1200 | 1.9 x 10² | 2.5 x 103 | 914 | 76.2 | 9.7 |
| 72.5AFKHA10 | 10 | 12 | 519 | 7.2 x 101 | 9.3× 102 | 914 | 76.2 | 9.7 |
| 72.5AFKHA16 | 16 | 12 | 389 | 1.3 x 102 | 1.7 x 103 | 914 | 76.2 | 9.7 |
| 72.5AFKHA20 | 20 | 12 | 249 | 3.1 x 102 | 4x 103 | 914 | 76.2 | 9.7 |
| 72.5AFKHA25 | 25 | 12 | 195 | 5.1 x 102 | 6.6x 103 | 914 | 76.2 | 9.7 |
| 72.5AFKHA31.5 | 31.5 | 12 | 130 | 1x 103 | 1.3 x 104 | 914 | 76.2 | 9.7 |
| 72.5AFKHA40 | 40 | 12 | 92.7 | 2x 103 | 2.6 x 104 | 914 | 76.2 | 9.7 |
Thereare a wide variety of end terminationsavailable, the most popular types, some of which have dimensional references to BS2692: Part1,are:
·AFKHA: A No tags- Ferrule - BS Ref.FA3 ADIHA/BS Ref FA4 AFIHA/BS Ref FA5 - AFKHA
Other tagvariantsavailableplease consult Eaton'sapplication engineers buletechnical@eaton.com
USstyle E-Rated mediumvoltage fuse links
E-Rated DiNFuse links 5.5kVto38kV 74 -Ratedfuselinksfortransformersandfeederprotection 5.5 kV ... .76 8.25kV. .78 15.5kV 79
E-Rated fuse links for potential and small power transformers JCX,JCY,JCU,JCZan D .81 JCD,JCW,JCE,CQ,JCI and JCT .83 5-38kV. .84
CL-14andbolt-in 5.5kV .85 8.3kV. .86 15.5 kV. ..87
R-Rated fuse linksformotorcircuit protection .88
5.5kVto38kVE-RatedDiNfuselinks
Specifications
Description
DINdimensional E-Rated power fuse linkswithstriker fitted for indoor use.
Agency
Comply with BS 2962-1 dimensions.
Ratings
Voltage:5.5-38kV Current:10 -450 E IR:25-65kA
Time-currentcurvesand cut-offcurves See list page 118
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. : 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Partnumbersandtechnicaldata
Typicalapplications
·Medium voltage transformer primary protection.
·Medium voltage feeder circuit protection.
| Partnumbers | Current | Interrupting capacitysym kA | Number of barrels | Length inches (mm) | Diameter inches (mm) |
| 5.5 kV General purpose | |||||
| 55GDMSJ10E | 10E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ15E | 15E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ20E | 20E | 65 | 1 | 17.40 (442) | 2 (51) |
| 55GDMSJ25E | 25E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ30E | 30E | 65 | 1 | 17.40 (442) | 2 (51) |
| 55GDMSJ40E | 40E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ50E | 50E | 65 | 1 | 17.40 (442) | 2 (51) |
| 55GDMSJ65E | 65E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ80E | 80E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ100E | 100E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GDMSJ125E | 125E | 65 | 1 | 17.40 (442) | 2(51) |
| 55GFMSJ150E | 150E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ175E | 175E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ200E | 200E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ250E | 250E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ300E | 300E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ350E | 350E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ400E | 400E | 65 | 1 | 17.40 (442) | 3(76) |
| 55GFMSJ450E | 450E | 65 | 1 | 17.40 (442) | 3 (76) |
| 15.5 kV General purpose | |||||
| 155GXQSJ175E | 175E | 65 | 1 | 21.14 (537) | 3.5 (88) |
| 155GXQSJ200E | 200E | 65 | 1 | 21.14 (537) | 3.5 (88) |
5.5kVto38kVE-RatedDiNfuselinks
| Partnumbers | Current | Interrupting capacity symkA | Number of barrels | Length inches (mm) | Diameter inches (mm) |
| 17.5kV General purpose | |||||
| 175GDMSJ10E | 10E | 65 | 1 | 17.40 (442) | 2 (51) |
| 175GDMSJ15E | 15E | 65 | 1 | 17.40 (442) | 2(51) |
| 175GDMSJ20E | 20E | 65 | 1 | 17.40 (442) | 2(51) |
| 175GDMSJ25E | 25E | 65 | 1 | 17.40 (442) | 2(51) |
| 175GDMSJ30E | 30E | 65 | 1 | 17.40 (442) | 2 (51) |
| 175GFMSJ40E | 40E | 65 | 1 | 17.40 (442) | 3(76) |
| 175GFMSJ50E | 50E | 65 | 1 | 17.40 (442) | 3(76) |
| 175GFMSJ65E | 65E | 65 | 1 | 17.40 (442) | 3(76) |
| 175GXMSJ80E | 80E | 65 | 1 | 17.40 (442) | 3.5 (88) |
| 175GXMSJ100E | 100E | 65 | 1 | 17.40 (442) | |
| 175GXQSJ125E | 125E | 65 | 1 | 21.14 (537) | 3.5 (88) |
| 175GXQSJ150E | 150E | 65 | 1 | 3.5 (88) | |
| 25.8 kV Full range | 21.14 (537) | 3.5 (88) | |||
| 258GDQSJ10E | 10E | 25 | 1 | 21.14 (537) | |
| 258GDQSJ15E | 15E | 25 | 1 | 21.14 (537) | 2 (51) |
| 258GDQSJ20E | 20E | 25 | 1 | 21.14 (537) | 2 (51) |
| 258GDQSJ25E | 25E | 25 | 1 | 21.14 (537) | 2 (51) |
| 258GDQSJ30E | 30E | 25 | 1 | 21.14 (537) | 2 (51) |
| 258GXQSJ40E | 40E | 25 | 1 | 2(51) | |
| 258GXQSJ50E | 50E | 25 | 1 | 21.14 (537) | 3.46 (88) |
| 258GXQSJ65E | 65E | 1 | 21.14 (537) 21.14 (537) | 3.46 (88) | |
| 258GXZSJ80E | 80E | 25 | 1 | 3.46 (88) | |
| 258GXZSJ100E | 100E | 25 | 28.3(719) | 3.46 (88) | |
| 38 kVFullrange | 25 | 1 | 28.3(719) | 3.46 (88) | |
| 38GFZSJ10E | |||||
| 38GFZSJ15E | 10E 15E | 25 | 1 1 | 28.3 (719) | 3(76) |
| 38GFZSJ20E | 20E | 25 25 | 1 | 28.3 (719) 28.3 (719) | 3(76) |
| 38GFZSJ25E | 25E | 25 | 1 | 28.3 (719) | 3(76) |
| 38GFZSJ30E | 30E | 25 | 1 | 28.3 (719) | 3(76) |
| 38GXZSJ40E | 40E | 25 | 1 | 28.3 (719) | 3(76) |
| 1 | 28.3 (719) | 3.46 (88) | |||
| 38GXZSJ50E 38GXZSJ65E | 50E 65E | 25 25 | 1 | 28.3(719) | 3.46 (88) 3.46 (88) |
5.5kVE-Rated fuselinksfortransformersand feederprotection
Specifications
Description
E-Rated power fuse links having Full range clearing capability for medium voltage transformer circuit protection.
Ratings
Voltage:5.5kV Current:5-450E IR:50kA
Time-current curvesand cut-off curves See list page 118
Dimensions
See outline drawings below and part numbers details page 76
Featuresandbenefits
·Cool running, low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. : 1 0 0 % X-ray,all our medium voltage fuse links are X-rayed ensuring the highest possible standards are maintained.
Typical applications
·Medium voltage transformer primary protection.
·Medium voltage feeder circuit protection.
Double Barrel Dimensions
5.5kVE-Ratedfuselinksfortransformersandfeederprotection
| Part numbers | Current | Interrupting capacity sym kA | Numberof barrels | Length inches (mm) | Diameter inches (mm) | Clip center inches (mm) |
| 5.5FFNHA30E | 30E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHA40E | 40E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHA50E | 50E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHA65E | 60E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHA75E | 75E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHK100E | 100E | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5FFNHK150E | 150E | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BFNHA80* | 80A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BFNHA100* | 100A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BFNHA150* | 150A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BKNHA200* | 200A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BFNHK250* | 250A | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 5.5BFNHK300* | 300A | 50 | 2 | 15.87(403) | 3(76) | 12 (304) |
| 5.5BFNHK400* | 400A | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| MV055F1CAX5E | 5E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX7E | 7E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX10E | 10E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX15E | 15E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX20E | 20E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX25E | 25E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX30E | 30E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX40E | 40E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX50E | 50E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1CAX65E | 65E | 50 | 1 | 15.75 (400) | 2(50) | 12 (304) |
| MV055F1DAX10E | 10E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX15E | 15E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX20E | 20E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX25E | 25E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX80E | 80E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX125E | 125E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX175E | 175E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F1DAX200E | 200E | 50 | 1 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F2DAX250E | 250E | 50 | 2 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F2DAX300E | 300E | 50 | 2 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F2DAX350E | 350E | 50 | 2 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F2DAX400E | 400E | 50 | 2 | 15.75 (400) | 3(76) | 12 (304) |
| MV055F2DAX450E | 450E | 50 | 2 | 15.75 (400) | 3(76) | 12 (304) |
8.25kVE-Ratedfuselinksfortransformersandfeederprotection
Specifications
Description
E-Rated power fuse links having full range clearing capability for medium voltage transformer circuit protection.
Ratings
Voltage:8.25kV
Current:80-200A,20 - 150E
IR:50kA
Time-current curvesand cut-off curves See list page 118
Featuresandbenefits
·Cool running,low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. · 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standards are maintained.
Typical applications
·Medium voltage transformer primary protection.
·Medium voltage feeder circuit protection.
| Part numbers | Current | Interrupting capacity sym kA | Numberof barrels | Length inches (mm) | Diameter inches (mm) | Clip center inches (mm) |
| 8.25FFNHA20E | 20E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA25E | 25E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA30E | 30E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA40E | 40E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA50E | 50E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA65E | 65E | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHA75E | 75E | 50 | 1 | 15.87(4t03) | 3(76) | 12 (304) |
| 8.25FFNHK100E | 100E | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25FFNHK150E | 150E | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25BFNHA80* | 80A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25BFNHA100* | 100A | 50 | 1 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25BFNHA150* | 150A | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
| 8.25BFNHA200* | 200A | 50 | 2 | 15.87 (403) | 3(76) | 12 (304) |
15.5kVE-Rated fuse linksfortransformersand feederprotection
Specifications
Description
E-Rated power fuse links having fullrange clearing capability for medium voltage transformer circuit protection.
Ratings
Voltage:15.5kV Current:5-200E IR:50kA
Time-currentcurvesand cut-off curves See list page 118
Dimensions
See outline drawings below and part numbers table opposite page.
Featuresandbenefits
·Cool running,low watts loss and power dissipation thanks to the M-effect ensuring high levels of substation utilisation. · 1 0 0 % X-ray,all our medium voltage fuse linksare X-rayed ensuring the highest possible standardsare maintained.
Typical applications
·Medium voltage transformer primary protection.
·Medium voltage feeder circuit protection.
MV155F1DCX
15.5kVE-Rated fuse linksfortransformersand feederprotection
Partnumbersandtechnicaldata
| Part numbers | Current | Interrupting capacity sym kA | Numberof barrels | Length inches (mm) | Diameter inches (mm) | Clip center inches (mm) |
| 15.5FFVHA15E | 15E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA20E | 20E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA25E | 25E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA30E | 30E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA40E | 40E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA50E | 50E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA65E | 65E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHA75E | 75E | 50 | 1 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHK100E | 100E | 50 | 2 | 18.86 (479) | 3(76) | 15 |
| 15.5FFVHK150E | 150E | 50 | 2 | 18.86 (479) | 3(76) | 15 |
| MV155F1CBX5E | 5E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX7E | 7E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX10E | 10E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX15E | 15E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX20E | 20E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX25E | 25E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1CBX30E | 30E | 50 | 1 | 18.75 (476) | 2(50) | 15 |
| MV155F1DBX10E | 10E | 50 | 1 | 18.75 (476) | 3(76) | 15 |
| MV155F1DBX80E | 80E | 50 | 1 | 18.75 (476) | 3(76) | 15 |
| MV155F1DBX100E | 100E | 50 | 1 | 18.75 (476) | 3(76) | 15 |
| MV155F2DBX125E | 125E | 50 | 2 | 18.75 (476) | 3(76) | 15 |
| MV155F2DBX175E | 175E | 50 | 2 | 18.75 (476) | 3(76) | 15 |
| MV155F2DBX200E | 200E | 50 | 2 | 18.75 (476) | 3(76) | 15 |
| MV155F1DCX65E | 65E | 50 | 1 | 21.75 (552) | 3(76) | 18 |
| MV155F1DCX80E | 80E | 50 | 1 | 21.75 (552) | 3(76) | 18 |
| MV155F1DCX100E | 100E | 50 | 1 | 21.75 (552) | 3(76) | 18 |
| MV155F2DCX125E | 125E | 50 | 2 | 21.75 (552) | 3(76) | 18 |
| MV155F2DCX150E | 150E | 50 | 2 | 21.75 (552) | 3(76) | 18 |
| MV155F2DCX175E | 175E | 50 | 2 | 21.75 (552) | 3(76) | 18 |
| MV155F2DCX200E | 200E | 50 | 2 | 21.75 (552) | 3(76) | 18 |
JCX,JCY,jcU,JCZandJDZE-Ratedfuselinksorpotentialand smallpowertransformers
Specifications
Description
Indoor/enclosure E-rated medium voltage,current-limiting fuse links for potential & smallpower transformers with blown fuse link indication.
Ratings
Voltage:2.4-8.3kV
Current:1-750A
Breaking capacity: 40 - 63 kA Sym.
Featuresandbenefits
·Physically dimensioned for retrofitting in existing hardware.
·Open fuse indicator for ease in troubleshooting.
·Full range ANSl classification.
Typical applications
·Medium voltage transformer primary protection.
·Medium voltage feeder circuit protection.
·Medium voltage switches.
·Medium voltage metal-enclosed switchgear.
Partnumbersandtechnicaldata
| Partnumbers | Voltage | Current | Interrupting capacity sym kA | Numberof barrels | Length inches (mm) | Diameter inches mm) |
| JCX-1/2E | 2.4 kV | 0.5E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-1E | 2.4 kV | 1E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-2E | 2.4 kV | 2E | 40 | 1 | 9.19 (233) | 2(51) |
| JCX-3E | 2.4 kV | 3E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-5E | 2.4 kV | 5E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-7E | 2.4 kV | 7E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-10E | 2.4 kV | 10E | 40 | 1 | 9.19 (233) | 2 (51) |
| JCX-15E | 2.4 kV | 15E | 50 | 1 | 9.50 (241) | 2.1(53) |
| JCX-20E | 2.4 kV | 20E | 50 | 1 | 9.50 (241) | 2.1 (53) |
| JCX-25E | 2.4 kV | 25E | 50 | 1 | 9.50 (241) | 2.1(53) |
| JCX-30E | 2.4 kV | 30E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-40E | 2.4 kV | 40E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-50E | 2.4 kV | 50E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-65E | 2.4 kV | 65E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-80E | 2.4 kV | 80E | 50 | 1 | 10.88(276) | 3(76) |
| JCX-100E | 2.4 kV | 100E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-125E | 2.4 kV | 125E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-150E | 2.4 kv | 150E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-200E | 2.4 kV | 200E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-225E | 2.4 kV | 225E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-250E/280X | 2.4 kV | 250E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-300E/325X | 2.4 kV | 300E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-350E | 2.4 kV | 350E | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-400X | 2.4 kV | 400X | 50 | 1 | 10.88 (276) | 3(76) |
| JCX-450X | 2.4 kV | 450X | 50 | 1 | 10.88 (276) | 3(76) |
JCX,JCY,JCU,JCZandjZE-Rateduselinksorpotentialand smallpowertransformers
Partnumbersandtechnicaldata
| Partnumbers | Voltage | Current | Interrupting capacity sym kA | Number of barrels | Length inches (mm) | Diameter inches (mm) |
| JCY-1/2E | 5.5kV | 0.5E | 40 | 11.19 (284) | 2(51) | |
| JCY-1E | 5.5 kV | 1E | 40 | 11.19 (284) | 2 (51) | |
| JCY-2E | 5.5kV | 2E | 40 | 11.19(284) | 2(51) | |
| JCY-3E | 5.5 kV | 3E | 40 | 11.19 (284) | 2(51) | |
| JCY-5E | 5.5kV | 5E | 40 | 11.19 (284) | 2(51) | |
| JCY-7E | 5.5kV | 7E | 40 | 11.19 (284) | 2(51) | |
| JCY-10E | 5.5 kV | 10E | 40 | 11.19 (284) | 2(51) | |
| JCY-15E | 5.5 kV | 15E | 40 | 11.19 (284) | 2(51) | |
| JCY-20E | 5.5 kV | 20E | 40 | 11.19 (284) | 2(51) | |
| JCY-25E | 5.5kV | 25E | 40 | 11.19 (284) | 2(51) | |
| JCU-10E | 5.5 kV | 10E | 50 | 17.81(452) | 3(76) | |
| JCU-15E | 5.5kV | 15E | 50 | 12.87 (326) | 2.1(53) | |
| JCU-20E | 5.5 kV | 20E | 50 | 12.87 (326) | 2.1(53) | |
| JCU-25E | 5.5kV | 25E | 50 | 12.87 (326) | 2.1(53) | |
| JCU-30E | 5.5kV | 30E | 63 | 17.88 (454) | 3(76) | |
| JCU-40E | 5.5kV | 40E | 63 | 17.88 (454) | 3(76) | |
| JCU-50E | 5.5kV | 50E | 63 | 17.88 (454) | 3(76) | |
| JCU-65E | 5.5 kV | 65E | 63 | 17.88 (454) | 3(76) | |
| JCU-80E | 5.5kV | 80E | 63 | 17.88(454) | 3(76) | |
| JCU-100E | 5.5kV | 100E | 63 | 17.88 (454) | 3(76) | |
| JCU-125E | 5.5 kV | 125E | 63 | 17.88 (454) | 3(76) | |
| JCU-150E | 5.5 kV | 150E | 63 | 17.88 (454) | 3(76) | |
| JCU-175E | 5.5kV | 175E | 63 | 17.88 (454) | 3(76) | |
| JCU-200E | 5.5kV | 200E | 63 | 17.88 (454) | 3(76) | |
| JCU-250E | 5.5 kV | 250E | 63 | 17.88 (454) | 3(76) | |
| JCU-300E | 5.5kV | 300E | 63 | 17.88 (454) | 3(76) | |
| JCU-350E | 5.5 kV | 350E | 63 | 17.88 (454) | 3(76) | |
| JCU-400E | 5.5kV | 400E | 63 | 17.88 (454) | 3(76) | |
| JCU-450E | 5.5kV | 450E | 63 | 17.88 (454) | 3(76) | |
| JCU-600E | 5.5kV | 600E | 50 | 28.81 (731) | 4(101) | |
| JCU-750E | 5.5 kV | 750E | 50 | 28.81(731) | 4(101) | |
| JCZ-15E | 8.3kV | 15E | 50 | 15.51 (393) | 2.1 (53) | |
| JCZ-20E | 8.3kV | 20E | 50 | 15.51(393) | 2.1 (53) | |
| JCZ-25E | 8.3kV | 25E | 50 | 15.51 (393) | 2.1(53) | |
| JCZ-30E | 8.3 kV | 30E | 50 | 17.88 (454) | 3(76) | |
| JCZ-40E | 8.3kV | 40E | 50 | 17.88 (454) | 3(76) | |
| JCZ-50E | 8.3kV | 50E | 50 | 17.88 (454) | 3(76) | |
| JCZ-65E | 8.3kv | 65E | 50 | 17.88 (454) | 3(76) | |
| JCZ-80E | 8.3kV | 80E | 50 | 17.88 (454) | 3(76) | |
| JCZ-100E | 8.3kV | 100E | 50 | 17.88 (454) | 3(76) | |
| JCZ-125E | 8.3kV | 125E | 50 | 17.88 (454) | 3(76) | |
| JCZ-150E | 8.3kV | 150E | 50 | 17.88 (454) | 3(76) | |
| JCZ-200E | 8.3kV | 200E | 50 | 17.88 (454) | 3(76) | |
| JDZ-20E | 8.3kV | 20E | 50 | 15.87 (403) | 3(76) | |
| JDZ-25E | 8.3kV | 25E | 50 | 15.87 (403) | 3(76) | |
| JDZ-30E | 8.3kV | 30E | 50 | 15.87 (403) | 3(76) | |
| JDZ-40E | 8.3kV | 40E | 50 | 15.87 (403) | 3(76) | |
| JDZ-50E | 8.3kv | 50E | 50 | 15.87 (403) | 3(76) | |
| JDZ-65E | 8.3kV | 65E | 50 | 15.87 (403) | 3(76) | |
| JDZ-80E | 8.3kV | 80E | 50 | 15.87 (403) | 3(76) | |
| JDZ-100E | 8.3kV | 100E | 50 | 15.87 (403) | 3(76) | |
| JDZ-125E | 8.3kV | 125E | 50 | 15.87 (403) | 3(76) |
JCD,JCW,JCE,CQjCI,JCTE-Ratedfuselinksforpotentialand smallpowertransformers
Specifications
Description
Indicating and non-indicating E-Rated medium voltage,current limiting fuse links for potential and smallpower transformers.
Ratings
Voltage:2.4- 15.5kV
Current:- 10A
Breaking capacity: 25- 80 kA Sym.
Typical applications
·Primary protection of medium voltage potential transformers.
Partnumbersandtechnicaldata
| Partnumbers | Voltage | Current | Interrupting capacity sym kA | Number of barrels | Length inches (mm) | Diameter inches (mm) |
| JCD-1/2E | 2.4 kV | 0.5E | 63 | 1 | 4.49 (114) | 0.8 (20) |
| JCD-1E | 2.4 kV | 1E | 40 | 1 | 4.49 (114) | 0.8(20) |
| JCD-2E | 2.4 kV | 2E | 40 | 1 | 4.49 (114) | 0.8 (20) |
| JCD-5E | 2.4 kV | 5E | 25 | 1 | 4.49 (114) | 0.8 (20) |
| JCW-1/2E | 2.4 kV/5.5 kV | 0.5E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCW-1E | 2.4 kV/5.5 kV | 1E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCW-2E | 2.4 kV/5.5 kV | 2E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCW-3E | 2.4 kV/5.5 kV | 3E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCW-4E | 2.4 kV/5.5 kV | 4E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCW-5E | 2.4 kV/5.5 kV | 5E | 40 | 1 | 7.31(185) | 1.56 (39) |
| JCE-1/2E | 5.5kV | 0.5E | 50 | 1 | 5.63(143) | 0.8 (20) |
| JCE-1E | 5.5 kV | 1E | 50 | 1 | 5.63 (143) | 0.8 (20) |
| JCE-2E | 5.5 kV | 2E | 50 | 1 | 5.63 (143) | 0.8 (20) |
| JCE-3E | 5.5 kV | 3E | 50 | 1 | 5.63 (143) | 0.8 (20) |
| JCE-4E | 5.5 kV | 4E | 50 | 1 | 5.63(143) | 0.8(20) |
| JCE-5E | 5.5 kV | 5E | 50 | 1 | 5.63 (143) | 0.8 (20) |
| JCQ-1/2E | 5.5 kV | 0.5E | 80 | 1 | 9.50 (241) | 1.6 (40) |
| JCQ-1E | 5.5kV | 1E | 80 | 1 | 9.50 (241) | 1.6 (40) |
| JCQ-1-1/2E | 5.5 kV | 1.5E | 80 | 1 | 9.50 (241) | 1.6 (40) |
| JCQ-3E | 5.5 kV | 3E | 80 | 1 | 9.44 (239) | 1.6 (40) |
| JCQ-5E | 5.5kV | 5E | 80 | 1 | 9.44 (239) | 1.6 (40) |
| JCQ-10E | 5.5kV | 10E | 80 | 1 | 9.44 (239) | 1.6 (40) |
| JCI-1/2E | 8.3kV | 0.5E | 80 | 1 | 9.50 (241) | 1.6 (40) |
| JCI-3E | 8.3kV | 3E | 80 | 1 | 12.88 (327) | 1.6 (40) |
| JCI-5E | 8.3kV | 5E | 80 | 1 | 12.88 (327) | 1.6 (40) |
| JCI-10E | 8.3 kV | 10E | 80 | 1 | 12.88 (327) | 1.6 (40) |
| JCT-1/2E | 15.5 kV | 0.5E | 80 | 1 | 12.93 (328) | 1.6 (40) |
| JCT-1E | 15.5 kV | 1E | 80 | 1 | 12.93 (328) | 1.6 (40) |
| JCT-1-1/2E | 15.5 kV | 1.5E | 80 | 1 | 12.93 (328) | 1.6 (40) |
| JCT-3E | 15.5 kV | 3E | 80 | 1 | 17.50 (444) | 1.6 (40) |
| JCT-5E | 15.5 kV | 5E | 80 | 1 | 17.50 (444) | 1.6 (40) |
| JCT-10E | 15.5kV | 10E | 80 | 1 | 17.50 (444) | 1.6 (40) |
E-Rated fuse linksforpotential andsmall powertransformers
Specifications
Description
Indicating and non-indicating E-Rated medium voltage, currentlimiting fuses forpotential and small power transformers.
Ratings
Voltage: 5-38 kV(See Part numbers table for details) Current: 0.5- 7E
Breaking capacity: 40 -80 kA.
Time-currentcurvesand cut-offcurves See list page 118
Typical applications
·Primary protection of medium voltage potential transformers.
Partnumbersandtechnicaldata
| Interrupting capacity sym kA | Number of barrels | Length inches (mm) | Diameter inches (mm) | Clipping Centres inches (mm) | |||
| Part numbers | Voltage | Current | |||||
| 5.5AMWNA0.5E | 5.5kV | 0.5E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 5.5AMWNA1E | 5.5kV | 1E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 5.5AMWNA2E | 5.5kV | 2E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 5.5AMWNA3E | 5.5 kV | 3E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 5.5AMWNA4E | 5.5kV | 4E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 5.5AMWNA5E | 5.5kV | 5E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 5.5ABWNA0.5E | 5.5 kV | 0.5E | 50 | 1 | 5.59 (141) | 1(25) | |
| 5.5ABWNA1E | 5.5kV | 1E | 50 | 1 | 5.59 (141) | 1(25) | : |
| 5.5ABWNA2E | 5.5kV | 2E | 50 | 1 | 5.59 (141) | 1(25) | : |
| 5.5ABWNA3E | 5.5 kV | 3E | 50 | 1 | 5.59 (141) | 1(25) | |
| 5.5ABWNA5E | 5.5kV | 5E | 50 | 1 | 5.59 (141) | 1(25) | : |
| 5.5CAV15E | 5.5kV | 15E | 50 | 1 | 7.36 (186) | 1.63 (41) | 6 (152) |
| 5.5CAVH0.5E | 5.5kV | 0.5E | 50 | 1 | 7.36 (186) | 1.63 (41) | 6 (152) |
| 5.5CAVH1E | 5.5 kV | 1E | 50 | 1 | 7.36 (186) | 1.63 (41) | 6(152) |
| 5.5CAVH2E | 5.5kV | 2E | 50 | 1 | 7.36 (186) | 1.63 (41) | 6(152) |
| 7.2AMWNA0.5E | 7.2 kV | 0.5E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 7.2AMWNA1E | 7.2 kV | 1E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 7.2AMWNA2E | 7.2 kV | 2E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 7.2AMWNA3E | 7.2 kV | 3E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 7.2AMWNA4E | 7.2 kV | 4E | 50 | 1 | 5.59 (141) | 0.81(20) | |
| 7.2AMWNA5E | 7.2 kV | 5E | 50 | 1 | 5.59 (141) | 0.81(20) | : |
| 15.5CAV0.5E | 15.5 kV | 0.5E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5CAV1E | 15.5 kV | 1E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5CAV2E 15.5CAV3E | 15.5 kV | 2E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5 kV | 3E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) | |
| 15.5CAV5E 15.5CAV7E | 15.5kV | 5E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5CAVH0.5E | 15.5 kV | 7E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5CAVH1E | 15.5 kV | 0.5E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5CAVH2E | 15.5kV | 1E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) |
| 15.5 kV | 2E | 80 | 1 | 12.87 (326) | 1.63 (41) | 11.5 (292) | |
| 38CAVH0.5E | 38kV | 0.5E | 40 | 1 | 17.32 (439) | 1.63 (41) | 15 (381) |
| 38CAVH1E | 38kV | 1E | 40 | 1 | 17.32 (439) | 1.63 (41) | 15 (381) |
| 38CAVH2E 38CAV4E | 38kV 38kV | 2E 4E | 40 40 | 1 1 | 17.32 (439) 17.32 (439) | 1.63 (41) 1.63 (41) | 15 (381) 15 (381) |
E-Ratedfuselinks:5.5kVCL-14andbolt-in
ECL055Specifications
Description
E-Rated medium voltage,current-limiting fuses for transformer and feeder protection.
Ratings
Voltage:5.5kVE-Rated Current:10 -900 A Breaking capacity: 63 kA Sym. Max.
Agency information
Meets E requirements per ANSl C37.46, meets general purpose requirements per ANSl C37.40.
Typicalapplications
·5kVTransformer primary protection.
·5kV Feeder circuit protection.
·5 kV Voltage switches.
·5 kV Metal-enclosed switchgear.
| Part numbers | Voltage (kV) | Current (E) | Breaking capacity(Sym) kA | Numberofbarrels |
| ECL055-10E | 5.5 | 10 | 63 | 1 |
| ECL055-15E | 5.5 | 15 | 63 | 1 |
| ECL055-20E | 5.5 | 20 | 63 | 1 |
| ECL055-25E | 5.5 | 25 | 63 | 1 |
| ECL055-30E | 5.5 | 30 | 63 | 1 |
| ECL055-40E | 5.5 | 40 | 63 | 1 |
| ECL055-50E | 5.5 | 50 | 63 | 1 |
| ECL055-65E | 5.5 | 65 | 63 | 1 |
| ECL055-80E | 5.5 | 80 | 63 | 1 |
| ECL055-100E | 5.5 | 100 | 63 | 1 |
| ECL055-125E | 5.5 | 125 | 63 | 1 |
| ECL055-150E | 5.5 | 150 | 63 | 1 |
| ECL055-200E | 5.5 | 200 | 63 | 1 |
| ECL055-250E | 5.5 | 250 | 63 | 1 |
| ECL055-300E | 5.5 | 300 | 63 | 2 |
| ECL055-400E | 5.5 | 400 | 63 | 2 |
| ECL055-450E | 5.5 | 450 | 63 | 2 |
| ECL055-500E | 5.5 | 500 | 63 | 2 |
| ECL055-600E | 5.5 | 600 | 63 | 2 |
| ECL055-750E | 5.5 | 750 | 63 | 3 |
| ECL055-900E | 5.5 | 900 | 63 | 3 |
Partnumbersconstruction (example)
| Partnumbers | Voltagerating | Ampere rating |
| ECL | 055(055=5.5 kV) | 300E |
E-Ratedfuselinks:8.3kVCL-14
ECL083Specifications
Description
E-Rated medium voltage, current-limiting fuses for transformer and feeder protection.
Ratings
Voltage:8.3kVE-Rated Current: 65-350 A Breaking capacity: 50 kA
Agency information
Meets E requirements per ANSl C37.46,meets general purpose requirements per ANSl C37.40.
Typical applications
·8.3 kV Transformer primary protection.
·8.3kV Feeder circuit protection.
·8.3kVVoltageswitches.
· 8 . 3 \mathsf { k V } Metal-enclosed s witchgear.
Partnumbersandtechnicaldata
| Part numbers | Voltage (kV) | Current (E) | Breaking capacity (Sym) kA | Numberof barrels |
| ECL083-65E | 8.3 | 65 | 50 | 1 |
| ECL083-80E | 8.3 | 80 | 50 | 1 |
| ECL083-100E | 8.3 | 100 | 50 | 1 |
| ECL083-125E | 8.3 | 125 | 50 | 1 |
| ECL083-150E | 8.3 | 150 | 50 | 1 |
| ECL083-175E | 8.3 | 175 | 50 | 1 |
| ECL083-200E | 8.3 | 200 | 50 | 2 |
| ECL083-250E | 8.3 | 250 | 50 | 2 |
| ECL083-300E | 8.3 | 300 | 50 | 2 |
| ECL083-350E | 8.3 | 350 | 50 | 2 |
Partnumbersconstruction(example)
| Partnumbers | Voltagerating | Ampererating |
| ECL | 083(0.83=8.3kV) | 300E |
E-Ratedfuselinks:15.5kVCL-14
ECL155Specifications
Description
E-Rated medium voltage, current-limiting fuses for transformer and feeder protection.
Ratings
Voltage:15.5kVE-Rated Current:10-300A Breaking capacity: 63 kA Sym.(10-200 A) 50 kA Sym.(250-300 A)
Agencyinformation
Meets E requirements perANSl C37.46,meets general purpose requirements per ANSl C37.40.
Partnumbersandtechnicaldata
Typicalapplications
·15 kVTransformer primary protection.
·15kV Feeder circuit protection.
·15kV Voltage switches.
·15 kV Metal-enclosed switchgear..
| Part numbers | Voltage (kV) | Current (E) | Breaking capacity(Sym) kA | Number of barrels |
| ECL155-10E | 15.5 | 10 | 63 | 1 |
| ECL155-15E | 15.5 | 15 | 63 | 1 |
| ECL155-20E | 15.5 | 20 | 63 | 1 |
| ECL155-25E | 15.5 | 25 | 63 | 1 |
| ECL155-30E | 15.5 | 30 | 63 | 1 |
| ECL155-40E | 15.5 | 40 | 63 | 1 |
| ECL155-50E | 15.5 | 50 | 63 | 1 |
| ECL155-65E | 15.5 | 65 | 63 | 1 |
| ECL155-80E | 15.5 | 80 | 63 | 1 |
| ECL155-100E | 15.5 | 100 | 63 | 1 |
| ECL155-125E | 15.5 | 125 | 63 | 1 |
| ECL155-150E | 15.5 | 150 | 63 | 2 |
| ECL155-200E | 15.5 | 200 | 63 | 2 |
| ECL155-250E | 15.5 | 250 | 50 | 2 |
| ECL155-300E | 15.5 | 300 | 50 | 2 |
Partnumbersconstruction(example)
| Partnumbers | Voltage rating | Ampererating |
| ECL | 155 (155= 15.5 kV) | 300E |
R-Rated fuse linksformotorcircuit protection
Specifications
Description
Indoor/enclosure R-Rated medium voltage, current-limiting fuse links for motor circuit protection.
Ratings
Voltage:2.4-7.2 kV Current:25-450A Breaking capacity:50 kA Sym
Agency information
UL recognized: 2540Vac-JCK,JCK-A, 5080Vac- JCL, JCL-A, UL recognized (Guide #MSSS2, File #E96676).
Typicalapplications
·Mediumvoltage motor controllers.
R-Rated fuse links formotorcircuit protection
Partnumbersandtechnicaldata
| Partnumbers | Current | Interrupting capacity symkA | Number of barrels | Length in (mm) | Diameter in (mm) |
| (A) 2400V (se figure page 89) | |||||
| JCK-2R | 70A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-3R | 100A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-4R | 130A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-5R | 150A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-6R | 170A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-9R | 200A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-12R | 230A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-18R | 390A | 50 | 2 | 11.24 (285) | 3(76) |
| JCK-24R | 450A | 50 | 2 | 11.24 (285) | 3(76) |
| 2400V-WithWestinghouseampguard hookeye (sefigure 1 page 89) | |||||
| JCK-A-2R | 70A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-3R | 100A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-4R | 130A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-5R | 150A | 50 | 1 | 11.24 (285) | 3((76) |
| JCK-A-6R | 170A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-9R | 200A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-12R | 230A | 50 | 1 | 11.24 (285) | 3(76) |
| JCK-A-18R | 390A | 50 | 2 | 11.24(285) | 3(76) |
| JCK-A-24R | 450A | 50 | 2 | 11.24 (285) | 3(76) |
| 2400V- Bolt-on (seefigures 2 and 3 page 89) | |||||
| JCK-B-30 | 25A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-2R | 70A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-3R | 100A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-4R | 130A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-5R | 150A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-6R | 170A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-9R | 200A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-12R | 230A | 50 | 1 | 14.18 (360) | 3(76) |
| JCK-B-18R | 390A | 50 | 2 | 14.18 (360) | 3(76) |
| JCK-B-24R | 450A | 50 | 2 | 14.18 (360) | 3(76) |
| 2400V-Hermeticallysealedfousewithmpguardmotorstarters(seefigurepge89) | |||||
| JCH-30 | 25A | 50 | 10.81(275) | ||
| JCH-2R | 70A | 50 | 1 1 | 10.81(275) | 3(76) |
| JCH-3R | 100A | 50 | 1 | 10.81 (275) | 3(76) 3(76) |
| JCH-4R | 130A | 50 | 1 | 10.81 (275) | 3(76) |
| JCH-5R | 150A | 50 | 1 | 10.81(275) | 3(76) |
| JCH-6R | 170A | 50 | 1 | 10.81 (275) | 3(76) |
| JCH-9R | 200A | 50 | 1 | 10.81 (275) | 3(76) |
| JCH-12R | 230A | 50 | 1 | 10.81(275) | 3(76) |
| JCH-18R | 390A | 50 | 2 | 10.81 (275) | 3(76) |
| JCH-24R | 450A | 50 | 2 | 10.81(275) | 3(76) |
| 4800V (se figure 1 page 89) | |||||
| JCL-2R | 70 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-3R | 100 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-4R | 130 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-5R | 150 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-6R | 170 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-9R | 200 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-12R | 230 | 50 | 1 | 15.76 (400) | 3(76) |
| JCL-18R | 390 | 50 | 2 | 15.76 (400) | 3(76) |
| JCL-24R | 450 | 50 | 2 | 15.76 (400) | 3(76) |
R-Rated fuse linksformotorcircuit protection
Partnumbersandtechnicaldata
| Partnumbers | Current (A) | Interrupting capacity symkA | Number of barrels | Length in (mm) | Diameterin (mm) |
| 4800V-With Westinghouse ampguard hookeye (seefigure1page 89) | |||||
| JCL-A-2R | 70 | 50 | 1 | 15.76 (400.3) | 3(76.2) |
| JCL-A-3R | 100 | 50 | 15.76 (400.3) | 3(76.2) | |
| JCL-A-4R | 130 | 50 | 15.76 (400.3) | 3(76.2) | |
| JCL-A-5R | 150 | 50 | 15.76 (400.3) | 3(76.2) | |
| JCL-A-6R | 170 | 50 | 15.76 (400.3) | 3(76.2) | |
| JCL-A-9R | 200 | 50 | 15.76 (400.3) | 3(76.2) | |
| JCL-A-12R | 230 | 50 | 1 | 15.76 (400.3) | 3(76.2) |
| JCL-A-18R | 390 | 50 | 2 | 15.76 (400.3) | 3(76.2) |
| JCL-A-24R | 450 | 50 | 2 | 15.76 (400.3) | 3(76.2) |
| 4800V-Bolton (seefigureandpage89) | |||||
| JCL-B-30 | 30 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-2R | 70 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-3R | 100 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-4R | 130 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-5R | 150 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-6R | 170 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-9R | 200 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-12R | 230 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-18R | 390 | 50 | 19.25 (488.9) | 3(76.2) | |
| JCL-B-24R | 450 | 50 | 19.25 (488.9) | 3(76.2) | |
| 4800V-Hermeticallyaledfrsewithmpguardmotorsrters (seefiurege89) | |||||
| JCG-30 | 30 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-2R | 70 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-3R | 100 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-4R | 130 | 50 | 15.91(404.1) | 3 (76.2) | |
| JCG-5R | 150 | 50 | 15.91(404.1) | 3(76.2) | |
| JCG-6R | 170 | 50 | 15.91(404.1) | 3(76.2) | |
| JCG-9R | 200 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-12R | 230 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-A-18R | 390 | 50 | 15.91 (404.1) | 3(76.2) | |
| JCG-A-24R | 450 | 50 | 15.91(404.1) | 3(76.2) | |
| 7200V-With ampguard hookeye (seefigure 1 page 89) | |||||
| JCR-A-2R | 70 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-3R | 100 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-4R | 130 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-5R | 150 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-6R | 170 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-9R | 200 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-12R | 230 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-18R | 390 | 50 | 15.85 (402.6) | 3(76.2) | |
| JCR-A-24R | 450 | 50 | 15.85 (402.6) | 3(76.2) | |
| 7200V- Bolt-on (seefigures 2 and 3 page 87) | |||||
| JCR-B-2R | 70 | 50 | 19.25 (488.9) | 3.31(84.1) | |
| JCR-B-3R | 100 | 50 | 19.25 (488.9) | 3.31(84.1) | |
| JCR-B-4R | 130 | 50 | 19.25 (488.9) | 3.31(84.1) | |
| JCR-B-5R | 150 | 50 | 19.25 (488.9) | 3.31 (84.1) | |
| JCR-B-6R | 170 | 50 | 19.25 (488.9) | 3.31(84.1) | |
| JCR-B-9R | 200 | 50 | 19.25 (488.9) | 3.31 (84.1) | |
| JCR-B-12R | 230 | 50 | 19.25 (488.9) | 3.31 (84.1) | |
| JCR-B-18R | 390 | 50 | 19.25 (488.9) | 3.31(84.1) | |
| JCR-B-24R | 450 | 50 | 2 2 | 19.25 (488.9) | 3.31(84.1) |
Fuse clips
·VTFuse Clips for 2 5 . 4 \mathsf {mm } diameter.
·DIN standard Clips for'F'and T'range fuse links.
·BSMounting Clips suitable for 50.8mm and 76.2mm Oil,Air, and Motor Fuse Links up to 200A.
Eaton'sBussmannseriesfuseclips
Tocomplementtherangeof tagfixingsofferedby Eaton,a range of fuse clipsare available.These are suitable for use with British Standard, DIN Dimensioned and VT ferrulestyle fuse links.The BS and DIN Clips are rated up to 200 Amps. They are designed to be fitted onto insulated studs or directly onto a busbar.
| Fuse clips | Clip reference |
| DIN fuse links to 43625 | 270303 or A3354745 |
| Voltage transformer and auxiliary type fuse links | A3354705 |
| British standard fuse links | |
| 50.8mm (2") diameter | A3354710 |
| 63.5mm (2") diameter | A3354720 |
| 76.2mm (2") diameter | A3354730 |
Clipsfor25.4mmVTFuselinks
Material Nickel silver alloy.
Orderas partnumber:A3354705#
ClipsforDINFuse links
Material Nickel-plated copper
Orderas part number:270303
Suitable forusewith Eaton's Bussmann series DIN fuse links.Also suitable for use with other Eaton's Bussmann series fuse links having type J'end tags,to DIN 43625,with maximum current rating of 200 Amps
ClipsforBritishstandardandDiNStylefuselinks
Material Nickel-plated copper
Orderaspart number:
A3354745for 4 5mm diameter A3354710 for 5 0 . 8 \mathsf {mm } diameter A3354720 for 6 3 . 5 \mathsf {mm } diameter A3354730 for 7 6 . 2 \mathsf {mm } diameter
Expulsionfuse linksforusein high voltage distributioncut-outs
·Wide range of optionsavailable from15kV to 72 kV in ANSIT&Kcharacteristics.
·Extra rapid option also available.
Eaton'sBussmannseriesexpulsionfuselinks
Eaton's Bussmannseries expulsion fuse links have been widely used throughout the world for over 40 years.They have in that time built upa formidable reputation and consistency of performance.
Eaton's Bussmann series expulsion fuse linksare designed to be interchangeable with other types of manufacturers cut-out unitsand are available in several patterns.
Application
Expulsion fuse links current ratings should be selected on the basis of maximum expected transient no damage currents ratherthanon full load current. Inaddition, theselection of highercurrent ratings will reduce the possibility of supply interruption due to transient surges suchas those due to lightning strikes (for information on our Surge Protection Device SPD,please contact buletechnical@eaton.com.
Links should be handled with a reasonable degree of care when installing. Excessively rough handling may damage the element.
It is normal,under certain fault conditions,for arc extinguishing material and/ormetal particles to be expelled from the fuse assembly.Itistherefore recommended thatreasonable precautions be taken to prevent the installation being approached by unauthorised persons.
| Voltage(kV) | 1st Letter Type of current characteristics | 2nd letter Type of termination | Current (A) |
| 15 | T= complies with ANSl C37-42 requirements for slow acting T characteristics. | B = a fixed NEMA button head link. | 1t06,7.5,8, 10,12,15,20, |
| 25 46 | K= complies with ANSI C37-42 requirements for fast acting K | U= a universal link, with double tail and slip off NEMA button head. | 25,30,40,50, |
| 72 | characteristics. XA=this type of expulsion fuse link has an extra rapid characteristic.It | D= double tailed link without NEMA button head. | 60,65,75,80, 100. |
| is suitable for applications where a high degree of system protection is required at the expense of discrimination. | BR= as pattern B but the button head is attached via a 1/4 UNF thread to allow use of an extension rod. | ||
| S=Solidlinksratedat10oAonlyarealsoavailableinbothbuttonhead and universal versions for fiting into expulsion fuse carriers where required.These canbeorderedinasimilar wayusing theabbreviation S, e.g.15SB100,etc. | See outline drawings opposite page for reference. |
Expulsionfuse links
Specifications
Description
Expulsion fuse linksavailable ina wide range of options from 15kV to 72 kVin ANSlT&Kcharacteristics.
Ratings
Voltage:15to72kV
Amps:1 to100 A
Breaking capacity: depends on voltage but isapproximately 8 kA
Agency information
Type T: complies with ANSl C37-42
Type K: complies with ANSl C37-42
Time-current curves and cut-off curves See list page 118
Packaging
Up to and including 50A: 25 in a carton.
From 60A to 100A:10 in a carton.
Toavoid incorrect replacement the fuse links have colour coded labels:
Pink label: Type XA.
Yellow label: Type K.
Green label: Type T.
Typical applications
·Primary side transformer protection.
·Feeder protection.
·Capacitor bank protection.
| Type kV | A |
| 15kV | 533 (21") |
| 25 kV | 660 (26") |
| 46 kV | 787 (31") |
| 72 kV | 1016 (40") |
Note
Type BR is similar to buttn head shown, except that the button head is attached via a /4 UNF thread.
Tails can be cut to any length.
1-50A
Crossreference
DINFuselinks
| Eaton's Bussmann EFEN | ETI (50N | ||||||||
| series | SIBA | MESA | (80N Striker) | Striker) | Merlin Gerin | Elimsan | Inael | ABB | |
| 3.6kV | |||||||||
| 3.6AD0SJ6.3 | 67110060 | 3000213 | CF-7.2/6.3 | 4226005 | 4225005 | 51006500M0 | N/A | 3.61B-D26.3 | 1YMB531001M0001 |
| 3.6ADOSJ10 | 67110100 | 3000213 | CF-7.2/10 | 4226006 | 4225006 | 51007.501.M0 | N/A | 3.6IB-D210 | 1YMB531001M0002 |
| 3.6ADOSJ16 | 67110160 | 3000213 | CF-7.2/16 | 4226007 | 4225007 | 51008502.M0 | N/A | 3.6IB-D216 | 1YMB531001M0003 |
| 3.6ADOSJ20 | 67110200 | 3000213 | CF-7.2/20 | 4226008 | 4225008 | 51009503M0 | N/A | 3.6IB-D220 | N/A |
| 3.6AD0SJ25 | 67110250 | 3000213 | CF-7.2/25 | 4226009 | 4225009 | 51010504M0 | N/A | 3.6IB-D225 | 1YMB531001M000 |
| 3.6ADOSJ31.5 | 67110320 | 3000213 | CF-7.2/31.5 | 4226010 | 4225010 | 51011505M0 | N/A | 3.6IB-D231.5 | N/A |
| 3.6ADOSJ40 | 67110400 | 3000213 | CF-7.2/40 | 4226011 | 4225011 | 51012506M0 | N/A | 3.61B-D240 | 1YMB53100M0005 |
| 3.6WD0SJ50 | 67110500 | 3000213 | CF-7.2/50 | 4226012 | 4225012 | 51013507M0 | N/A | 3.61B-D250 | 1YMB531001M0006 |
| 3.6WD0SJ63 | 67110630 | 3001013 | CF-7.2/63 | 4226013 | 4225013 | 51014508M0 | N/A | 3.6IB-D263 | 1YMB531001M0007 |
| 3.6WDOSJ80 | 67110800 | 3001013 | CF-7.2/80 | 4226014 | 4225014 | 51015509M0 | N/A | 3.61B-D280 | 1YMB531001M0008 |
| 3.6WDOSJ100 | 67110.1000 | 3001013 | CF-7.2/100 | 4226015 | 4225015 | 51016510M0 | N/A | 3.6IB-D2100 | 1YMB531001M0009 |
| 3.6WDOSJ125 | 67110.1250 | 3001013 | N/A | 4226016 | 4225016 | N/A | N/A | N/A | N/A |
| 3.6WFOSJ160 | 67110.1600 | 3001813 | N/A | 4226017 | 4225017 | N/A | N/A | N/A | N/A |
| 3.6WFOSJ200 | 67210.2000 | 3001814 | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 7.2kV | |||||||||
| 7.2TDLSJ6.3 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0001 |
| 7.2TDLSJ10 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0002 |
| 7.2TDLSJ16 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0003 |
| 7.2TDLSJ20 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 7.2TDLSJ25 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0004 |
| 7.2TDLSJ31.5 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 7.2TDLSJ40 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0005 |
| 7.2TDLSJ50 | N/A | 3009813 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0006 |
| 7.2TDLSJ63 | N/A | 3009913 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0007 |
| 7.2TFLSJ80 | N/A | 3009913 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0008 |
| 7.2TFLSJ100 | N/A | 3009913 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531034M0009 |
| 7.2TFLSJ125 | N/A | 3009913 | CF-7.2/125 | N/A | N/A | 757352BN | N/A | N/A | 1YMB531034M0010 |
| 7.2TFLSJ160 | N/A | 3010013 | CF-7.2/160 | N/A | N/A | 757352BP | N/A | N/A | 1YMB531034M0011 |
| 12kV | |||||||||
| 12TDLEJ6.3 | 67120060 | 3000413 | CF-12/6.3 | 4236005 | 4235005 | 51006511M0 | ES6509006 | 12IB-D16.3 | 1YMB531042M0001 |
| 12TDLEJ10 | 67120100 | 3000413 | CF-12/10 | 4236006 | 4235006 | 51006512M0 | ES6509010 | 12IB-D110 | 1YMB531042M0002 |
| 12TDLEJ16 | 67120160 | 3000413 | CF-12/16 | 4236007 | 4235007 | 51006513M0 | ES6509016 | 12IB-D116 | 1YMB531042M0003 |
| 12TDLEJ20 | 67120200 | 3000413 | CF-12/20 | 4236008 | 4235008 | 51006514M0 | ES6509020 | 12IB-D120 | 1YMB531042M0004 |
| 12TDLEJ25 | 67120250 | 3000413 | CF-12/25 | 4236009 | 4235009 | 51006515M0 | ES6509025 | 12IB-D1/D225 | 1YMB531002M0004 |
| 12TDLEJ31.5 | 67120320 | 3000413 | CF-12/31.5 | 4236010 | 4235010 | 51006516M0 | ES6509030 | 12 IB-D1/D231.5 | 1YMB531002M0014 |
| 12TDLEJ40 | 67120400 | 3000413 | CF-12/40 | 4236011 | 4235011 | 51006517M0 | ES6509040 | 12IB-D1/D240 | 1YMB531002M0005 |
| 12TDLEJ50 | 67120500 | 3000413 | CF-12/50 | 4236012 | 4235012 | 51006518M0 | ES6509050 | 12IB-D250 | 1YMB531002M0006 |
| 12TDLEJ63 | 67120630 | 3001213 | CF-12/63 | 4236013 | 4235013 | 51006519M0 | ES6509063 ES6509080 | 12IB-D263 12IB-D380 | 1YMB531002M0007 1YMB531002M0021 |
| 12THLEJ80 12THLEJ100 | 67120800 67120.1000 | 3001213 3001213 | CF-12/80 CF-12/100 | 4236014 4236015 | 4235014 4235015 | 51006520M0 51006521M0 | |||
Crossreference
DINFuselinks
| Eaton's Bussmann | ETI (50N | ||||||||
| series | EFEN | SIBA | MESA | (80N Striker) | Striker) | Merlin Gerin | Elimsan Inael | ABB | |
| 17.5 kV | |||||||||
| 17.5TDLSJ6.3 | N/A | 3025513 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D16.3 | 1YMB531003M0001 |
| 17.5TDLSJ10 | N/A | 3025513 | CFR-17.5/10 | N/A | N/A | 51006522M0 | N/A | 17.5IB-D110 | 1YMB531003M0002 |
| 17.5TDLSJ16 | N/A | 3025513 | CFR-17.5/16 | N/A | N/A | 51006523M0 | N/A | 17.5IB-D116 | 1YMB531003M0003 |
| 17.5TDLSJ20 | N/A | 3022113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D120 | 1YMB531003M0013 |
| 17.5TDLSJ25 | N/A | 3022113 | CFR-17.5/25 | N/A | N/A | 51006524M0 | N/A | 17.51B-D1/D225 | 1YMB531003M0004 |
| 17.5TDLSJ31.5 | N/A | 3022113 | CFR-17.5/31.5 | N/A | N/A | 51006525M0 | N/A | 17.5IB-D1/D231.5 | 1YMB531003M0014 |
| 17.5TDLSJ40 | N/A | 3022113 | CFR-17.5/40 | N/A | N/A | 51006525M0 | N/A | 17.5IB-D1/D240 | 1YMB531003M0021 |
| 17.5TFLSJ50 | N/A | 3022113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D250 | 1YMB531003M0022 |
| 17.5TDMEJ6.3 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D16.3 | 1YMB531037M0001 |
| 17.5TDMEJ10 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D110 | 1YMB531037M0002 |
| 17.5TDMEJ16 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D116 | 1YMB531037M0003 |
| 17.5TDMEJ20 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D120 | 1YMB531037M0013 |
| 17.5TDMEJ25 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D125 | 1YMB531037M0004 |
| 17.5TDMEJ31.5 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5 IB-D131.5 | 1YMB531037M0014 |
| 17.5TDMEJ40 | N/A | 3023113 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D140 | 1YMB531037M0021 |
| 17.5TDMEJ50 | N/A | 3023213 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531037M0006 |
| 17.5TDMEJ63 | N/A | 3023213 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D263 | 1YMB531037M0007 |
| 17.5THMEJ80 | N/A | 3023213 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531037M0008 |
| 17.5THMEJ100 | N/A | 3023313 | N/A | N/A | N/A | N/A | N/A | 17.5IB-D2100 | 1YMB531003M0009 |
| 17.5TKMEJ125 | N/A | 3023414 | N/A | N/A | N/A | N/A | N/A | N/A | 1YMB531003M0010 |
| 24kV | |||||||||
| 24TDMEJ6.3 | 67140060 | 3000613 | CF-24/6.3 | 4256005 | 4255005 | 51006538M0 | ES6513-006 | 24IB-D16.3 | 1YMB531044M0001 |
| 24TDMEJ10 | 67140100 | 3000613 | CF-24/10 | 4256006 | 4255006 | 51006539M0 | ES6513-010 | 24IB-D110 | 1YMB531044M0002 |
| 24TDMEJ16 | 67140160 | 3000613 | CF-24/16 | 4256007 | 4255007 | 51006540M0 | ES6513-016 | 24IB-D116 | 1YMB531044M0003 |
| 24TDMEJ20 | 67140200 | 3000613 | CF-24/20 | 4256008 | 4255008 | 51006541M0 | ES6513-020 | 24IB-D120 | 1YMB531044M0004 |
| 24TDMEJ25 | 67140250 | 3000613 | CF-24/25 | 4256009 | 4255009 | 51006542M0 | ES6513-025 | 24IBD1/D225 | 1YMB531004M0004 |
| 24TDMEJ31.5 | 67140320 | 3000613 | CF-24/31.5 | 4256010 | 4255010 | 51006543M0 | ES6513-030 | 24IBD1/D231.5 | 1YMB531004M0012 |
| 24TDMEJ40 | 67140400 | 3000613 | CF-24/40 | 4256011 | 4255011 | 51006544M0 | ES6513-040 | 24IBD1/D240 | 1YMB531004M0005 |
| 24TDMEJ50 | 67140500 | 3001413 | CF-24/50 | 4253012 | 4255012 | 51006545M0 | ES6513-050 | 24IB-D250 | 1YMB531004M0021 |
| 24THMEJ63 | 67140630 | 3001413 | CF-24/63 | 4253013 | 4255013 | 51006546M0 | ES6513-063 | 24IB-D263 | 1YMB531004M0022 |
| 24TFMEJ80 | 67140800 | 3001413 | CF-24/80 | 4253014 | 4255014 | 51006547M0 | ES6513-080 | 24IB-D380 | 1YMB531022M0001 |
| 24TFMEJ100 | 67240.1000 | 3002213 | CF-24/100 | 4253015 | 4255015 | 51006548M0 | ES6513-100 | 24IB-D3100 | 1YMB531022M0002 |
| 24TXMEJ125 | 67240.1250 | 3002213 | N/A | 4253016 | 4255016 | N/A | N/A | N/A | 1YMB531022M0003 |
| 24TXMEJ160 | 67240.1600 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 36kV | |||||||||
| 36TDQSJ3.15 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
| 36TDQSJ6.3 | 67150060 | 3000813 | CF-36/6.3 | 4266005 | 4265005 | 51006549M0 | ES6515-006 | 24IB-D16.3 | 1YMB531006M0001 |
| 36TDQSJ10 | 67150100 | 3000813 | CF-36/10 | 4266006 | 4265006 | 51006550M0 | ES6515-010 ES6515-016 | 24IB-D110 24IB-D116 | 1YMB531006M0002 1YMB531006M0003 |
| 36TDQSJ16 36TDQSJ20 | 67150160 67150200 | 3000813 3000813 | CF-36/16 CF-36/20 | 4266007 4266008 | 4265007 4265008 | 51006551M0 51006552M0 | |||
Crossreference
Motorfuselinks
| Eaton's Bussmann series | SIBA | GE | ABB |
| 3.6kV | |||
| 3.6WDFH050 | 3026956-50 | ||
| 3.6WDFH063 | 3026956-63 | ||
| 3.6WDFH080 | 3026956-80 | ||
| 3.6WDFH0100 | 3026956-100 | K81PEX100 | |
| 3.6WDFH0125 | 3026956-125 | K81PEX125 | |
| 3.6WFFH0160 | 3026956-160 | K81PEX160 | |
| 3.6WFFH0200 | 3026956-200 | K81PEX200 | |
| 3.6WFFH0250 | 3026956-250 | K81PEX250 | |
| 3.6WKFH0315 | 3026956-315 | K81PEX315 | |
| 3.6WKFH0355 | K81PEX350(1) | ||
| 3.6WKFH0400 | K81PEX450(2) | ||
| 3.6WFGH0100 | 3025513-100 | 1YMB531031M0001 | |
| 3.6WFGH0150 | 1YMB531031M0002 | ||
| 3.6WFGH0200 | 1YMB531031M0003 | ||
| 3.6WFGH0250 | 1YMB531031M0004 | ||
| 3.6WKGH0315 | 1YMB531031M0005 | ||
| 3.6WDLSJ50 | 3020153-50 | ||
| 3.6WDLSJ63 | 3020153-63 | ||
| 3.6WDLSJ80 | 3020153-80 | ||
| 3.6WDLSJ100 | 3020153-100 | 1YMB531028M0001 | |
| 3.6WDLSJ125 | 3020253-125 | ||
| 3.6WFLSJ160 | 3020253-160 | 1YMB531028M0002 | |
| 3.6WFLSJ200 | 3020253-200 | 1YMB531028M0003 | |
| 3.6WKLSJ250 | 3020054-250 | 1YMB531028M0004 | |
| 3.6WKLSJ315 | 3020054-315 | 1YMB531028M0005 | |
| 7.2kV | |||
| 7.2WFNHO50 | 3027156-50 | K81SDX50 | |
| 7.2WFNH063 | 3027156-63 | K81SDX63 | 1YMB531032M0001 |
| 7.2WFNH080 | 3027156-80 | K81SDX80 | |
| 7.2WFNH0100 | 3027156-100 | K81SDX100 | 1YMB531032M0002 |
| 7.2WFNH0125 | 3027156-125 | K81SDX125 | |
| 7.2WFNH0160 | 3027156-160 | K81SDX160 | 1YMB531032M0003 |
| 7.2WFNH0200 | 3027156-200 | K81SDX200 | 1YMB531032M0004 |
| 7.2WKNH0224 | 3027156-224 | K81SDX225 | |
| 7.2WKNH0250 | 3027156-250 | K81SDX250 | 1YMB531032M0005 |
| 7.2WKNH0315 | 3027156-315 | K81SDX315 | 1YMB531032M0006 |
| 7.2WFMSJ50 | 3010853-50 | ||
| 7.2WFMSJ63 | 3010853-63 | 1YMB531029M0001 | |
| 7.2WFMSJ80 | 3010853-80 | ||
| 7.2WFMSJ100 | 3010853-100 | 1YMB531029M0002 | |
| 7.2WFMSJ125 | 3010953-125 | ||
| 7.2WFMSJ160 | 3010953-160 | 1YMB531029M0003 | |
| 7.2WKMSJ200 | 3011054-200 | 1YMB531029M0004 | |
| 7.2WKMSJ224 | 3011054-224 | ||
| 7.2WKMSJ250 | 3011054-250 | 1YMB531029M0005 | |
| 7.2WKMSJ315 | 3011054-315 | 1YMB531029M0006 |
Voltageandauxiliaryfuse links
| Bussmann series | SIBA | GE |
| 3.6kV | ||
| 3.6ABWNA3.15 | AIR3.3/3 | |
| 7.2kV | ||
| 7.2ABWNA3.15 | 3038311-3 | VTF6.6/3 |
| 7.2ABCNA3.15 | 3037711-3 | |
| 7.20BCNA3.15 | VTF6.6/3 | |
| 12kV | ||
| 12ABCNA3.15 | 3037811-3 | VTF11/3 |
| 12ABCN223.15 | 5XVTF11/3 | |
| 120BCNA3.15 | VTF11/3 | |
| 120BCN223.15 | 5XVTF11/3 | |
| 15.5kV | ||
| 15.5ABFNA3.15 | VTF15/3 | |
| 15.50BFNA3.15 | VTF15/3 | |
| 15.5ABFNA223.15 | 6XVTF15/3 | |
| 15.50BFN223.15 | 6XVTF15/3 | |
| 17.5kV | ||
| 17.5ABGNA3.15 | 3037911-3 | |
| 24kV | ||
| 24ABGNA3.15 | 3038011-3 |
Crossreference
Oil fuse links
| Eaton'sBussmannseries | Siba | GE | Notes |
| 3.6kV | |||
| 3.60EFMA6.3 | 3013236-6.3* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA10 | 3013236-10* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA16 | 3013236-16* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA20 | 3013236-20* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA25 | 3013236-25* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA31.5 | 3013236-31.5* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA40 | 3013236-40* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA50 | 3013236-50* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA63 | 3013236-63* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA80 | 3013236-80* | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV | |
| 3.60EFMA100 | 3013236-100* | KSBXO100 | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximumof3.6kV |
| 7-2 kV | |||
| 7.20EFMA80 | 3013236-80 | ||
| 7.20EFMA100 | 3013236-100 | KSBX0100 | |
| 7.20EFMA112 | 3013236-112 | ||
| 7.20HGMA100 | KSMX0100 | ||
| 7.20HGMA125 | 3023436-125 | KSMX0120 | GEfuselinkisratedat12OA,Eaton'sBussmannseriesat125A |
| 7.20HGMA140 | 3023436-160 | KSMX0140 | |
| 7.20HGMA160 12kV | |||
| 120EFMA6.3 | 3014436-6.3 | KEBXO5 | GEfuselinkisratedat5A,Eaton'sBussmannseriesat6.3A |
| 120EFMA10 | 3014436-10 | KEBX010 | |
| 120EFMA16 | 3014436-16 | KEBX016 | |
| 120EMFA20 | 3014436-20 | KEBXO20 | |
| 120EFMA25 120EFMA31.5 | 3014436-25 | KEBX025 | |
| 120EFMA40 | 3014436-31.5 | KEBXO36 | GEfuselinkisratedat36A,Eaton'sBussmannseriesat31.5A |
| 120EFMA50 | 3014436-40 | KEBX040 | |
| 120EFMA63 | 3014436-50 | KEBXO50 | |
| 120HFMA80 | 3014436-63 | KEBX063 | |
| 15.5kV | 3014436-80 | KEBXO80 | |
| 15.50EFMA25 | |||
| KFBX025 | |||
| 15.50EFMA31.5 | KFBXO36 | GEfuselinkisratedat36A,Eaton'sBussmannseriesat31.5A | |
| 15.50EFMA40 | KFBX040 | ||
| 15.50EFMA50 | KFBX050 | ||
| 15.50EFMA63 | KFBXO63 | ||
| 15.50HGMA80 | KFMX085 | GEfuselinkisratedat85A,Eaton'sBussmannserieat80A | |
| 15.50LGMA100 | KFMXO100 | ||
| 17.5kV | |||
| 17.50HGMA20 | KFMX020 | ||
| 17.50HGMA25 | KFMX025 | ||
| 17.50HGMA31.5 | KFMXO32 | ||
| 17.50HGMA40 | KFMX040 | ||
| 17.50HGMA50 | KFMX050 | ||
| 17.50HGMA63 | KFMXO63 | ||
| 17.50HGMA80 | KFMXO80 | ||
| 24kV | |||
| 240EGMA6.3 | 3023736-6.3** | ||
| 240EGMA10 | 3023736-10** | KTMX010*** | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximum24kV |
| 240EGMA16 | 3023736-16** | ||
| 240EGMA20 | 3023736-20** | KTMXO20*** | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximum24kV |
| 240EGMA25 | 3023736-25** | KTMXO25*** | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximum24kV |
| 240EGMA31.5 | 3023736-31.5** | KTMXO32*** | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximum24kV |
| 240EGMA40 | 3023736-40** | KTMXO40*** | Eaton'sBussmannseriesfuselinkcanonlybeusedatamaximum24kV |
| 240EGMA50 | 3023736-50** | KTMXO50*** | |
Crossreference
Britishstandardairfuselinks
| series | SIBA |
| 24kV | |
| 24ADIHA6.3 | 3024436-6.3 |
| 24ADIHA10 | 3024436-10 |
| 24ADIHA16 | 3024436-16 |
| 24ADIHA20 | 3024436-20 |
| 24ADIHA25 | 3024436-25 |
| 24ADIHA31.5 | 3024436-31.5 |
| 24FIHA40 | 3016136-40 |
| 24AFIHA50 | 3016136-40 |
| 24AFIHA63 | 3016136-63 |
| 24AFIHA80 | 3016136-80 |
| Eaton's Bussmann | Eaton's Bussmann | |||
| series | SIBA | series | SIBA | GE |
| 3.6kV | 12kV | |||
| 3.6ADFHA6.3* | 3024136-6.3 | 12ADFHA6.3 | 3014136-6.3 | |
| 3.6ADFHA10* | 3024136-10 | 12ADFHA10 | 3014136-10 | |
| 3.6ADFHA16* | 3024136-16 | 12ADFHA16 | 3014136-16 | |
| 3.6ADFHA20* | 3024136-20 | 12ADFHA20 | 3014136-20 | |
| 3.6ADFHA25* | 3024136-25 | 12ADFHA25 | 3014136-25 | |
| 3.6ADFHA31.5* | 3024136-31.5 | 12ADFHA31.5 | 3014136-31.5 | |
| 3.6ADFHA40* | 3024136-40 | 12AFFHA40 | 3013536-40 | |
| 7.2kV | 12AFFHA50 | 30133536-50 | ||
| 7.2ADFHA6.3 | 3024136-6.3 | 12AFFHA63 | 30133536-63 | |
| 7.2ADFHA10 | 3024136-10 | 12ADFN6B31.5 | K6EB32 | |
| 7.2ADFHA16 | 3024136-16 | 12AFFN6B40 | K6EB40 | |
| 7.2ADFHA20 | 3024136-20 | 12AFFN6B50 | K6EB50 | |
| 7.2ADFHA25 | 3024136-25 | 12AFFN6B63 | K6EB63 | |
| 7.2ADFHA31.5 | 3024136-31.5 | 12BDGHA6.3 | 3024336-6.3 | |
| 7.2ADFHA40 | 3024136-40 | 12BDGHA10 | 3024336-10 | |
| 7.2ADFHA50 | 3024136-50 | 12BDGHA16 | 3024336-16 | |
| 7.2ADFHA63 | 3024136-63 | 12BDGHA20 | 3024336-20 | |
| 7.2AFFHA80 | 3013536-80 | 12BDGHA25 | 3024336-25 | |
| 7.2AFFHA100 | 3013536-100 | 12BDGHA31.5 | 3024336-31.5 | |
| 7.2BDGHA6.3 | 3024236-6.3 | 12BDGHA40 | 3024336-40 | |
| 7.2BDGHA10 | 3024236-10 | 12BDGHA50 | 3024336-50 | |
| 7.2BDGHA16 | 3024236-16 | 12BFGHA50 | 3014736-50 | |
| 7.2BDGHA20 | 3024236-20 | 12BFGHA63 | 3014736-63 | |
| 7.2BDGHA25 | 3024236-25 | 12BFGHA80 | 3014736-80 | |
| 7.2BDGHA31.5 | 3024236-31.5 | 12BFGHA100 | 3014736-100 | |
| 7.2BDGHA40 | 3024236-40 | 12AKGHA125 | 3014736-125 | |
| 7.2BDGHA50 | 3024236-50 | 12BDGHC6.3 | 3024736-6.3 | |
| 7.2BDGHA63 | 3024236-63 | 12BDGHC10 | 3024736-10 | |
| 7.2BDGHA80 | 3024236-80 | 12BDGHC16 | 3024736-16 | |
| 7.2BFGHA100 | 3013736-100 | 12BDGHC20 | 3024736-20 | |
| 7.2BFGHA125 | 3013736-125 | 12BDGHC25 | 3024736-25 | |
| 7.2BFGHA140 | 3013736-140 | 12BDGHC31.5 | 3024736-31.5 | |
| 7.2BFHA160 | 3013736-16 | 12BDGHC40 | 3024736-40 | |
| 7.2BDGHC6.3 | 3024636-6.3 | 12BDGHC50 | 3024736-50 | |
| 7.2BDGHC10 | 3024636-10 | 12BFGHC63 | 3025036-63 | |
| 7.2BDGHC16 | 3024636-16 | 12BFGHC80 | 3025036-80 | |
| 7.2BDGHC20 | 3024636-20 | 12BFGHC90 | 3025036-90 | |
| 7.2BDGHC25 | 3024636-25 | 12BFGHC100 | 3025036-100 | |
| 7.2BDGHC31.5 | 3024636-31.5 | 12AKGHC125 | 3025036-125 | |
| 7.2BDGHC40 7.2BDGHC50 | 3024636-40 | 15.5kV | ||
| 7.2BDGHC63 | 3024636-50 | 15.5BDGHC6.3 | 3025836-6.3 | |
| 7.2BDGHC80 | 3024636-63 | 15.5BDGHC10 | 3024836-10 | |
| 7.2BFGHC90 | 3024636-80 | 15.5BDGHC16 | 3024836-16 | |
| 7.2BFGHC100 | 3024936-90 | 15.5BDGHC20 | 3024836-20 | |
| 3024936-100 | 15.5BDGHC25 | 3024836-25 | ||
| 7.2BFGHC125 | 3024936-125 | 15.5BDGHC31.5 | 3024836-31.5 | |
| 7.2BFGHC140 | 3024936-140 | 15.5BDGHC40 | 3024836-40 | |
| 7.2BFGHC160 | 3024936-160 | 15.5BFGHC50 | 3024836-50 | |
| 15.5BFGHC63 | 3024836-63 |
Crossreference
| Eaton's Bussmannseries | Mersen (Ferrazshawmut) | Cutlerhammer | GE | Littelfuse |
| 5.5kVE-Ratedfuselinksfortransformersandfeederprotection | ||||
| MV055F1DAX10E | A055F1DOR0-10E | 5HLE-10E | 10E-1C-5.5 | |
| MV055F1DAX15E | A055F1DOR0-15E | 5HLE-15E | 15E-1C-5.5 | |
| MV055F1DAX20E | A055F1DORO-20E | 5HLE-20E | 20E-1C-5.5 | |
| MV055F1DAX25E | A055F1DOR0-25E | 5HLE-25E | 25E-1C-5.5 | |
| MV055F1DAX80E | A055F1DOR0-80E | 5HLE-80E | 9F62DCB080 | 80E-1C-5.5 |
| MV055F1DAX125E | A055F1DOR0-125E | 5HLE-125E | 9F62DCB125 | 125E-1C-5.5 |
| MV055F1DAX175E | A055F1D0R0-175E | 5HLE-175E | 9F62DCB175 | 175E-1C-5.5 |
| MV05F1DAX200E | A055F1D0R0-200E | 5HLE-200E | 9F62DCB200 | 200E-1C-5.5 |
| MV055F2DAX300E | A055F2D0R0-300E | 5HLE-300E | 9F62FCB300 | 300E-1C-5.5 |
| MV055F2DAX350E | A055F2D0ORO-350E | 5HLE-350E | 9F62FCB350 | 350E-2C-5.5 |
| MV055F2DAX400E | A055F2DORO-400E | 5HLE-400E | 9F62FCB400 | 400E-2C-5.5 |
| MV055F2DAX450E | A055F2D0RO-450E | 5HLE-450E | 9F62FCB450 | 450E-2C-5.5 |
| 5.5FFNHA30E | A055F1DOR0-30E | 5HLE-30E | 9F60FJD030 | 30E-1C-5.5 |
| 5.5FFNHA40E | A055F1DOR0-40E | 5HLE-40E | 9F60FJD040 | 40E-1C-5.5 |
| 5.5FFNHA50E | A055F1D0R0-50E | 5HLE-50E | 9F60FJD050 | 50E-1C-5.5 |
| 5.5FFNHA65E | A055F1D0R0-65E | 5HLE-65E | 9F60FJD065 | 65E-1C-5.5 |
| 8.3kVE-Ratedfuselinksfortransformersandfeederprotection | ||||
| 8.25FFNHA20E 8.25FFNHA25E | A825X20E-1 | 8HLE-20E | 9F60FJE020 | 20E-1C-8.25 |
| 8.25FFNHA30E | A825X25E-1 | 8HLE-25E | 9F60FJE025 | 25E-1C-8.25 |
| 8.25FFNHA40E | A825X30E-1 | 8HLE-30E | 9F60FJE030 | 30E-1C-8.25 |
| 8.25FFNHA50E | A825X40E-1 | 8HLE-40E | 9F60FJE040 | 40E-1C-8.25 |
| 8.25FFNHA65E | A825X50E-1 | 8HLE-50E | 9F60FJE050 | 50E-1C-8.25 |
| 15.5kVE-Rated fuse links for transformersand feeder protection | A825X65E-1 | 8HLE-65E | 9F60FJE065 | 65E-1C-8.25 |
| MV155F1DBX10E | A155F1D0R0-10E | 15HLE-10E | 10E-1C-15.5 | |
| MV155F1DBX80E | A155F2DOR0-80E | 15HLE-80E | 9F60HMH080 | 80E-1C-15.5 |
| MV155F1DBX10OE | A155F2D0RO-100E | 15HLE-100E | 9F60HMH100 | 100E-1C-15.5 |
| MV155F2DBX175E | A155F2DOR0-175E | 15HLE-175E | 175E-2C-15.5 | |
| MV155F2DBX200E | A155F2DOR0-200E | 15HLE-200E | 200E-2C-15.5 | |
| 15.5FFVHA15E | A155F1D0R0-15E | 15HLE-15E | 9F60FMH015 | 15E-1C-15.5 |
| 15.5FFVHA20E | A155F1DORO-20E | 15HLE-20E | 9F60FMH020 | 20E-1C-15.5 |
| 15.5FFVHA25E | A155F1D0R0-25E | 15HLE-25E | 9F60FMH025 | 25E-1C-15.5 |
| 15.5FFVHA30E | A155F1D0R0-30E | 15HLE-30E | 9F60FMH030 | 30E-1C-15.5 |
| 15.5FFVHA40E | A155F1D0R0-40E | 15HLE-40E | 9F60FMH040 | 40E-1C-15.5 |
| 15.5FFVHA50E | A155F1D0R0-50E | 15HLE-50E | 9F60FMH050 | 50E-1C-15.5 |
| 15.5FFVHA65E | A155F2D0R0-65E | 15HLE-65E | 9F60FMH065 | 65E-1C-15.5 |
| 15.5FFVHK150E | A155F2D0R0-150E | 15HLE-150E | 150E-2C-15.5 | |
| E-Ratedfuselinks: CL-14andbolt-in 5.5 kV | ||||
| ECL055-10E | A055C1DORO-10E | 5HCL-10E | 10E-1CL-5.5 | |
| ECL055-15E | A055C1D0R0-15E | 5HCL-15E | 15E-1CL-5.5 | |
| ECL055-20E | A055C1D0R0-20E | 5HCL-20E | 20E-1CL-5.5 | |
| ECL055-25E | A055C1D0R0-25E | 5HCL-25E | 25E-1CL-5.5 | |
| ECL055-30E | A055C1D0R0-30E | 5HCL-30E | 30E-1CL-5.5 | |
| ECL055-40E | A055C1D0R0-40E | 5HCL-40E | 40E-1CL-5.5 | |
| ECL055-50E | A055C1D0R0-50E | 5HCL-50E | 50E-1CL-5.5 | |
| ECL055-65E ECL055-80E | A055C1D0R0-65E | 5HCL-65E | 65E-1CL-5.5 | |
| ECL055-100E | A055C1D0R0-80E | 5HCL-80E | 80E-1CL-5.5 | |
| ECL055-125E | A055C1D0RO-100E | 5HCL-100E | 100E-1CL-5.5 | |
| ECL055-150E | A055C1D0R0-125E | 5HCL-125E | 125E-1CL-5.5 | |
| A055C1D0R0-150E | 5HCL-150E | 150E-1CL-5.5 | ||
| ECL055-200E | A055C1DORO-200E | 5HCL-200E | ||
| ECL055-250E | A055C1DORO-250E | 5HCL-250E | ||
| ECL055-300E | A055C1D0R0-300E | 5HCL-300E | 300E-2CL-5.5 | |
| ECL055-400E | A055C1D0R0-400E | 5HCL-400E | 350E-2CL-5.5 | |
| ECL055-450E | A055C2D0R0-450E | 5HCL-450E | 400E-2CL-5.5 | |
| ECL055-500E | A055C2D0R0-500E | 5HCL-500E | ||
| ECL055-600E | A055C2D0R0-600E | 5HCL-600E | ||
| EBI055-750E EB1055-900E | A055B3D0R0-750E A055B3D0R0-900E | 5HCL-750E 5HCL-900E | ||
Crossreference
USStyle E-Rated fuse links
| Eaton'sBussmann series | Mersen (Ferrazshawmut) | Cutler hammer | GE | Littelfuse |
| E-Rated fuse links: CL-14 and bolt-in- 15.5 kV | ||||
| ECL155-10E | A155C1DOR0-10E | 15HCL-10E | 10E-1CL-15.5 | |
| ECL155-15E | A155C1D0R0-15E | 15HCL-15E | 15E-1CL-15.5 | |
| ECL155-20E | A155C1D0R0-20E | 15HCL-20E | 20E-1CL-15.5 | |
| ECL155-25E | A155C1DOR0-25E | 15HCL-25E | 25E-1CL-15.5 | |
| ECL155-30E | A155C1DOR0-30E | 15HCL-30E | 30E-1CL-15.5 | |
| ECL155-40E | A155C1DOR0-40E | 15HCL-40E | 40E-1CL-15.5 | |
| ECL155-50E | A155C1D0R0-50E | 15HCL-50E | 50E-1CL-15.5 | |
| ECL155-65E | A155C1D0R0-65E | 15HCL-65E | 65E-1CL-15.5 | |
| ECL155-80E | A155C1DORO-80E | 15HCL-80E | 80E-1CL-15.5 | |
| ECL155-100E | A155C1DOR0-100E | 15HCL-100E | 100E-1CL-15.5 | |
| ECL155-125E | A155C2D0R0-125E | 15HCL-125E | ||
| ECL155-150E | A155C3D0R0-150E | 15HCL-150E | ||
| ECL155-200E | A155C3D0R0-200E | 15HCL-200E | ||
| ECL155-250E | A155C3D0R0-250E | 15HCL-250E | ||
| ECL155-300E | A155C3D0R0-300E | 15HCL-300E | ||
| E-Rated fuses for transformersand feeder protection-2.4kVE-Rated indoor/enclosure | ||||
| JCX-15E | ||||
| JCX-20E | 2CLE-15E 2CLE-20E | |||
| JCX-25E | 2CLE-25E | |||
| JCX-30E | 2CLE-30E | 9F60ECB030 | 30E-1C-2.75 | |
| JCX-40E | 2CLE-40E | 9F60ECB040 | 40E-1C-2.75 | |
| JCX-50E | 2CLE-50E | 9F60ECB050 | 50E-1C-2.75 | |
| JCX-65E | 2CLE-65E | 9F60ECB065 | 65E-1C-2.75 | |
| JCX-80E | 2CLE-80E | 9F60ECB080 | 80E-1C-2.75 | |
| JCX-100E | 2CLE-100E | 9F60ECB100 | 100E-1C-2.75 | |
| JCX-125E | 2CLE-125E | 9F60GCB125 | 125E-1C-2.75 | |
| JCX-150E | 2CLE-150E | 9F60GCB150 | 150E-1C-2.75 | |
| JCX-200E | 2CLE-200E | 9F60GCB200 | 200E-1C-2.75 | |
| JCX-250E/280X | 2CLE-250E | |||
| JCX-300E/325X | 2CLE-300E | |||
| JCX-350X | 2CLE-350X | |||
| JCX-400X | 2CLE-400X | |||
| JCX-450X | 2CLE-450X | |||
| E-Ratedfuselinksfortransformersandfeederprotection-5.5kVERatedindoor/enclosure | ||||
| JCU-10E | 5CLE-10E-D | |||
| JCU-15E | 5CLE-15E | |||
| JCU-20E | 5CLE-20E | |||
| JCU-25E | 5CLE-25E | |||
| JCU-30E | 5CLE-30E-D | |||
| JCU-40E | 5CLE1-40E | |||
| JCU-50E | 5CLE1-50E | |||
| JCU-65E JCU-80E | 5CLE1-65E | |||
| JCU-100E | 5CLE1-80E | |||
| 5CLE1-100E | ||||
| JCU-125E JCU-150E | 5CLE1-125E | |||
| 5CLE-150E | ||||
| JCU-175E | 5CLE-175E | |||
| JCU-200E | 5CLE-200E | |||
| JCU-250E | 5CLE-250E | |||
| JCU-300E | 5CLE-300E | |||
| JCU-350E | 5CLE-350E | |||
| JCU-400E | 5CLE-400E | |||
| JCU-450E | 5CLE-450E | |||
| JCU-600E | 5CLE-600E | |||
| JCU-750E | 5CLE-750E | |||