VL35-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual short circuit current I△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulsewithstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL36-63RCCB
General introduction
Function
VL36-63series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shockoccursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshorttimeto protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-rise buildingsand residential houses, etc.
Conformstostandard IEC/EN61008-1
VL36-63RCCB
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,6A |
| Ratedresidual operatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingand breaking capacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Rated residual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
General introduction
Function
VL37-63 series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshort timeto protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercialbuildings,high-rise buildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL37-63RCCB
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Rated limitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual short circuitcurrent I△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL38-63RCCB
General introduction
Function
VL38-63 series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent ingrid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshort timeto protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-rise buildingsand residential houses, etc.
Conformstostandard IEC/EN61008-1
VL38-63RCCB
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty typeas per DC component | AC,A |
| Rated limitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuitcurrentI△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
Generalintroduction
Function
VL39-63 series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent ingrid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshorttimeto protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL39-63RCCB
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Rated limitedshortcircuitcurrent Inc | 6000A |
| Rated limited residual shortcircuitcurrentI△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In=63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL40-63RCCB
General introduction
Function
VL40-63series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshort timeto protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL40-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,6A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual shortcircuit currentI△c | 6000A |
| Ratedmakingand breaking capacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residual makingand breakingcapacityl△m | 500A(In≤50A),630A(In= 63A) |
| Ratedresidual non-operatedcurrent I△no | 0.5l△n |
| Rated insulation voltage Ui | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Stored ambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL41-63RCCB
Generalintroduction
Function
VL41-63 series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshort time to protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercialbuildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL41-63RCCB
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual short circuit currentI△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulsewithstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
VL42-63RCCB
Generalintroduction
Function
VL42-63series RCCB(withoutovercurrent protection)appliesto AC 50Hz, ratedvoltage240V2poles,415V4poles,ratedcurrentupto63A.When electric shock occursto humanor leakagecurrent in grid exceedsstipulated values,RCCBcutsoff thefaultpowerinaveryshort time to protect the safetyof humanandelectrical equipments.Itcanalso functionasnon frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
VL42-63RCCB
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Duty type as per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual short circuit current I△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Ratedresidualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| RatedinsulationvoltageUi | 500V |
| Rated impulsewithstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000 Times |
| Mechanical life | 2000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
F7SERIES
VH11-125 Switch Disconnection
Generalintroduction
Function
VH11-125 series switch disconnection (hereinafter referred to as switch) applies to power distribution and control circuits with AC 5 0 H z ratedcurrent upto125A,ratedvoltageup to415V.It’smainlyusedasageneral switchof terminalcombinedapparatus,alsofunctionsascontrollerofunfrequently switched small powerapparatusand lighting.
Application
Industrialandminingenterprises,high-risebuildingsand residential houses, etc.
Conformtostandard IEC/EN60947-3
Mainparameters
| Types | Values |
| Rated current(le) | 32A,63A,80A,100A,125A |
| Poles | 1P、2P、3P、4P |
| Rated voltage(Ue) | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated insulationvoltage(Ui) | 400V |
| Rated working current (le) | 32A,63A,80A,100A,125A |
| Rated impulsewithstandvoltageUimp | 4Kv(2000m) |
| Ratedshort timewithstandcurrent(lcw) | 12le,1s |
| Rated short circuit making capacity(lcm) | 20le,0.1s |
| Ratedmakingand breaking capacity | 3le,1.05Ue,cosΦ=0.65 |
| Mechanical and electrical life | Mechanical life 8500 Timess |
| Electrical life1500 Timess | |
| Connection wire | See Form 1 |
| Operatedambient temperature℃ | -5~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Rated current In(A) | Nominal sectionarea of copper wire S(mm²) |
| 32 | 6 |
| 63 | 16 |
| 80 | 25 |
| 100 | 35 |
| 125 | 50 |
Overall and mounting sizes(mm)
VB11-63MCB
Generalintroduction
Function
VB11-63seriesMCB,usedasoverload and short circuit protection,appliesto acircuit of AC 50Hz,rated voltage230/400V,rated current up to 63A.Usually it functions as un frequently switching.In addition,it can be also used as an isolatortocutoffthecircuitformaintenanceofcircuitandequipment.
Application
Industryand commercial buildings,high-risebuildingsand residential houses, etc.
Conformstostandard IEC/EN60898-1
Form 1
| Types | Values |
| Ratedvoltage Un | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated current In | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Poles | 1P、2P、3P、4P |
| Instant tripping type | B.C,D |
| Ratedshortcircuit breakingcapacity(lcn) | 10000A |
| Overcurrent protection properties | SeeForm2,Diagram1,2and3 |
| Mechanicalandelectrical life | See Form3 |
| Connection wire | See Form4 |
| Tightening torque | 2.5N.m |
| Nominal temperature℃ | 30 |
| Operatedambient temperature℃ | -5~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Form 2
| Item | Type | Test curren | Initial status | Tripping or non tripping time limit | Expected result | Remarks |
| a | BCD | 1.13ln | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Test following the previous procedure; Processaftertest | t | Trip | Current increases to stipulated valuewithin 5s | |
| C | 2.55ln | Cold | 1s | Trip | ||
| d | B C D | 3ln 5ln 10ln | Cold | t≤0.1s | Non tripping | Connection of current by opening auxiliaryswitch |
| e | BC D | 5n 20In | Cold | t≤0.1s | Trip | Connectioofcrentbyopening |
VB11-63MCB
Mechanicalandelectrical life
| Type | Time |
| Electrical life | 10000 |
| Mechanical life | 20000 |
Connectionwire
| Ratedcurrent In(A) | Copperwire nominal cross-sectional area S(mm²) |
| 1~6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40,50 | 10 |
| 63 | 16 |
Overall and mounting sizes(mm)
VB11LE-32RCBO
Generalintroduction
Function
VB11LE-32 series RCBO mainly applies to the circuit of AC 5 0 H z rated voltage 240V,rated current up to 32A.When electric shock occurs to human, leakagecurrentorvoltagein grid exceedsstipulated values,RCBOcuts offthefaultpowerinaveryshort timetoprotectthesafetyof humanand electrical equipments,italsoowns the functionsof overload andshortcircuit protection.Inaddition,itcanswitchonandoffnonfrequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lighting and distribution system for industry and commerce system.
Conformsto IEC/EN61009-1
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A |
| Rated residualoperatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non trippingcurrent(l△no) | 0.51△n |
| DC component | AC type,A type |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Ratedshortcircuitbreakingcapacity(lcn) | 6000A |
| Rated residualmakingand breakingcapacity(l△m) | 500A |
| Breakingtimeofresidualoperatedcurrent | See Form2and 3 |
| Overcurrent protectionproperties | See Form4,Diagram1and2 |
| Mechanicaland electrical life | See Form5 |
| Connection wire | See Form6 |
| Tightening torque | 1.5N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protectionlevel | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | Breaking time(s)whenl△equalsto the belowvalues | |||
| I△n | 21△n | 51△n | 0.25A,5A~200A,500A | |||
| AC型 | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofA type
Form3
| Type | In(A) | 1△n(A) | Be | ||||
| 1.41△n | 350A | ||||||
| A型 | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form 4
| Item | Type | Test curren | Initial status | Tripping ornon tripping time limit | Expected resul | Remarks |
| a | B,C | 1.13ln | Cold Test following the | t≤1h | Non tripping | |
| b | 1.45ln | previousprocedure; Processaftertest | t | Trip | stipuren iacewithin5s | |
| C | 2.55ln | Cold | 132) | Trip | ||
| d | BC | 3n | Cold | t≤0.1s | Non tripping | Coniectionof aurentch |
| e | BC | 5n | Cold | t≤0.1s | Trip | Conection of aurenth |
Mechanicalandelectricallife
| Category | Time | Operation Time (time/hour) |
| Mechanical life | 10000 | 240 |
| Electricallife | 2000 | 120 |
Connectionwire
| Ratedcurrent In (A) | Section area of copper wire S (mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
Overall and mounting sizes(mm)
Generalintroduction
Function
VB12LE-40 series RCBO mainly applies to the circuit of AC 5 0 H z rated voltage 240V,rated current up to 40A.Whenelectric shock occurs to human, leakagecurrentorvoltagein gridexceedsstipulated values,RCBOcuts offthefaultpowerinaveryshort timetoprotect thesafetyof humanand electrical equipments,italsoowns the functionsof overload and short circuit protection.Inaddition,itcanswitchonandoff nonfrequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lighting and distribution system for industry and commerce system.
Conformsto IEC/EN61009-1
Main parameters
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A,40A |
| Rated residual operatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(I△no) | 0.51△n |
| DC component | AC type,A type |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Rated short circuit breaking capacity(lcn) | 6000A |
| Rated residualmakingand breakingcapacity(l△m) | 500A |
| Breakingtimeof residualoperatedcurrent | See Form 2and 3 |
| Overcurrentprotectionproperties | See Form4,Diagram1and2 |
| Mechanicalandelectrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Breaking timeof AC type
| Type | In(A) | 1△n(A) | Bei | |||
| I△n | ||||||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofA type
Overcurrent protection properties(nominal temperature 3 0 { { ^ { \circ } C } } )
| Type | In(A) | 1△n(A) | Breaking time(s)whenl△equalstothebelowvalues | ||||
| 1.41△n | 2.81△n | 7I△n | 0.35A | 350A | |||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
| Item | Type | Test curren | Initial status | Tripping ornontripping time limitExpectedresul | Remarks | |
| a | B,C | 1.13ln | Cold | t≤1h | Nontripping | |
| b | 1.45ln | Test following the previousprocedure; Processafter test | t | Trip | Current increasesto stipulatedvaluewithin5s | |
| C | 2.55ln | Cold | 1 | Trip | ||
| d | BC | 3n | Cold | t≤0.1s | Non tripping | Coningionxf auyrentch |
| e | BC | 5n | Cold | t≤0.1s | Trip | Coenentionxof aurynthy |
Diagram1and 2
Mechanicalandelectrical life
| Category | Time | OperationTime (time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connectionwire
| Ratedcurrent In (A) | Sectionarea ofcopperwire S (mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
Overall and mounting sizes(mm)
VB11L-40RCBO
Generalintroduction
Function
VB11L-40 series RCBO mainlyapplies to the circuit of AC 5 0 H z rated voltage240V,rated currentupto 40A.Whenelectric shock occursto human, leakagecurrentorvoltage in grid exceedsstipulated values,RCBOcuts offthefaultpowerinaveryshorttimetoprotectthesafetyofhumanand electrical equipments,italsoowns the functionsof overloadandshortcircuit protection.Inaddition,itcanswitchonandoff nonfrequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lightingand distributionsystem for industryandcommercesystem.
Conforms to IEC/EN61009-1
Mainparameters
Form 2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A,40A |
| Rated residual operated current(l△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(I△no) | 0.51△n |
| DC component | AC type,Atype |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Ratedshort circuit breaking capacity(lcn) | 6000A |
| Rated residualmakingand breakingcapacity(l△m) | 500A |
| Breaking timeof residual operatedcurrent | See Form 2 and 3 |
| Overcurrentprotectionproperties | See Form4,Diagram1and2 |
| Mechanicalandelectrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominal temperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | e | |||
| I△n | ||||||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeof A type
Overcurrent protection properties(nominal temperature 3 0 ^ { \circ } { C } )
| Type | In(A) | 1△n(A) | Breaking time(s)whenl△equalstothebelowvalues | ||||
| 1.41△n | 2.8△n | 71△n | 0.35A | 350A | |||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form4
| Item | Type | Test curren | Initial status | Tripping ornontripping time limitExpected resul | Remarks | |
| a | B,C | 1.13ln | Cold | t≤1h | Nontripping | |
| b | 1.45ln | Processaftertest | t | Trip | stipurentiauewthinus | |
| C | 2.55ln | Cold | 1 | Trip | ||
| d | B C | 3ln 5ln | Cold | t≤0.1s | Non tripping | Connectionofcurrentby openingauxiliaryswitch |
| e | BC | 5n | Cold | t≤0.1s | Trip | Conention ofcaurenth |
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connectionwire
| Ratedcurrent In(A) | Sectionarea of copperwire S(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40 | 10 |
Overall and mounting sizes(mm)
WANXIANGSERIES
VH10-125 SwitchDisconnection
Generalintroduction
Function
VH10-125 series switch disconnection (hereinafter referred to as switch) appliesto powerdistributionandcontrol circuits withAC 5oHz,rated current upto125A,ratedvoltageup to415V.It’smainlyusedasa generalswitchof terminalcombinedapparatus,alsofunctionsascontrollerofunfrequently switched small powerapparatus and lighting.
Application
Industrial andminingenterprises,high-rise buildingsand residential houses, etc.
Conformtostandard IEC/EN60947-3
VH10-125 Switch Disconnection
| Types | Values |
| Rated current(le) | 32A,63A,80A,100A,125A |
| Poles | 1P、2P、3P、4P |
| Ratedvoltage(Ue) | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated insulationvoltage(Ui) | 400V |
| Rated workingcurrent (le) | 32A,63A,80A,100A,125A |
| Rated impulsewithstandvoltage Uimp | 4Kv(2000m) |
| Rated short time withstand current(lcw) | 12le,1s |
| Rated short circuit making capacity(lcm) | 20le,0.1s |
| Rated makingand breaking capacity | 3le,1.05Ue,cosΦ=0.65 |
| Mechanicalandelectrical life | Mechanical life 850o Times |
| Electrical life1500Times | |
| Connection wire | See Form1 |
| Operatedambienttemperature℃ | -5~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Ratedcurrent In(A) | Nominal sectionarea of copper wire S(mm²) |
| 32 | 6 |
| 63 | 16 |
| 80 | 25 |
| 100 | 35 |
| 125 | 50 |
Overall and mounting sizes(mm)
VB10-63MCB
Generalintroduction
Function
VB10-63 series MCB,used as overload and short circuit protection,applies toacircuitofAC 50Hz,ratedvoltage230/40oV,ratedcurrentup to63A. Usually it functions as un frequently switching.Inaddition,it can be also usedasan isolatortocutoff thecircuitformaintenanceof circuitand equipment.
Application
Industryandcommercialbuildings,high-risebuildingsandresidential houses,etc.
Conformstostandard IEC/EN60898-1
VB10-63MCB
Form 1
| Types | Values |
| Ratedvoltage Un | 240V/415VAC(1P),415VAC(2P、3P、4P) |
| Rated current In | 1A,2A,3A,4A,6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Poles | 1P、2P、3P、4P |
| Instant tripping type | B.C,D |
| Ratedshortcircuit breakingcapacity(lcn) | 10000A |
| Overcurrent protection properties | SeeForm2,Diagram1,2and3 |
| Mechanicalandelectrical life | See Form3 |
| Connection wire | See Form4 |
| Tightening torque | 2.5N.m |
| Nominal temperature℃ | 30 |
| Operatedambient temperature℃ | -5~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Form2
| Item | Type | Test curren | Initial status | Tripping or non tripping time limit | Expected result | Remarks |
| a | BCD | 1.13ln | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Test following the previous procedure; Processaftertest | t | Trip | Current increases to stipulated valuewithin 5s | |
| C | 2.55ln | Cold | 1s | Trip | ||
| d | B C D | 3ln 5ln 10ln | Cold | t≤0.1s | Non tripping | Connection of current by opening auxiliaryswitch |
| e | BC D | 5n 20In | Cold | t≤0.1s | Trip | Connectioofcrentbyopening |
Mechanicalandelectricallife
| Type | Times |
| Electrical life | 10000 |
| Mechanical life | 20000 |
| RatedcurrentIn (A) | Copperwirenominalcross-sectional areaS(mm2) |
| 1~6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40.50 | 10 |
| 63 | 16 |
Overall and mounting sizes(mm)
VL18-63RCCB
General introduction
Function
VL18-63 series RCCB(without overcurrent protection)applies to AC 50Hz,ratedvoltage240V2poles,415V4poles,ratedcurrentup to63A. When electric shock occurs to human or leakage current in grid exceeds stipulatedvalues,RCCBcutsoff thefault powerinaveryshorttime to protect thesafetyof humanandelectrical equipments.Itcanalso functionas non frequently switching of circuits.
Application
Industryandcommercial buildings,high-risebuildingsandresidential houses, etc.
Conformstostandard IEC/EN61008-1
Mainparameters
| Types | Values |
| Rated voltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,20A,25A,32A,40A,50A,63A |
| RatedresidualoperatedcurrentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Dutytype as per DC component | AC,A |
| Rated limited short circuit current Inc | 6000A |
| Rated limited residual shortcircuit current1△c | 6000A |
| Ratedmakingand breakingcapacity Im | 500A(In≤50A),630A(In = 63A) |
| Rated residualmakingandbreakingcapacityl△m | 500A(In≤50A),630A(In = 63A) |
| Rated residual non-operated current I△no | 0.5l△n |
| Rated insulationvoltageUi | 500V |
| Rated impulsewithstand voltage Uimp | 4000V |
| Tightening torque | 3.0N.m |
| Electrical life | 1000Times |
| Mechanical life | 2000Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
Generalintroduction
Function
VB10LE-32 series RCBO mainly applies to the circuit of AC 5 0 H z rated voltage 240V,rated current up to 32A.When electric shock occurs to human, leakagecurrentorvoltagein gridexceedsstipulated values,RCBOcuts offthefaultpowerinaveryshort timetoprotectthesafetyof humanand electrical equipments,italso owns the functionsof overload and short circuit protection.Inaddition,itcanswitchonandoff nonfrequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lighting and distribution system for industry and commerce system.
Conformsto IEC/EN61009-1
Mainparameters
Form2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,2A |
| Rated residualoperatedcurrent(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non tripping current(l△no) | 0.51△n |
| DC component | AC type,A type |
| Poles | 1P+N |
| Instant tipping type | B type,C type |
| Rated short circuit breaking capacity(lcn) | 6000A |
| Rated residual making and breaking capacity(l△m) | 500A |
| Breaking timeofresidual operatedcurrent | SeeForm2and3 |
| Overcurrentprotectionproperties | See Form4,Diagram1and2 |
| Mechanicaland electrical life | See Form5 |
| Connection wire | See Form 6 |
| Tightening torque | 1.5N.m |
| Nominal temperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | Breaking time(s)whenl△equalsto the belowvalues | |||
| I△n | 21△n | 51△n | 0.25A,5A~200A,500A | |||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeof A type
Form3
| Type | In(A) | 1△n(A) | Be | ||||
| 1.41△n | 350A | ||||||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form 4
| Item | Type | Test curren | Initial status | Tripping ornontripping time limit | Expected resul | Remarks |
| a | B,C | 1.13ln | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Testfuloaingthe Processaftertest | t | Trip | stipuren iacewithin 5s | |
| C | 2.55ln | Cold | 132) | Trip | ||
| d | BC | 3n | Cold | t≤0.1s | Non tripping | Coniectionof aurenth |
| e | BC | 5n | Cold | t≤0.1s | Trip | Conection ofcaurenth |
VB10LE-32RCBO
Diagram1and 2
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connectionwire
| Rated current In(A) | Sectionarea ofcopperwire S(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
Overall and mounting sizes(mm)
VB10L-40RCBO
Generalintroduction
Function
VB10L-40 series RCBO mainly applies to thecircuit of AC 5 0 H z rated voltage 240V,rated current up to 40A.When electric shock occurs to human, leakagecurrentorvoltagein gridexceedsstipulated values,RCBOcuts offthefaultpowerinaveryshort timetoprotectthesafetyof humanand electrical equipments,italsoowns the functionsof overloadandshortcircuit protection.Inaddition,itcanswitchonandoff nonfrequentlytheelectrical facilitiesand lightingcircuitwhile thecircuitworkswell.
Application
Lighting and distribution system for industry and commerce system.
Conformsto IEC/EN61009-1
Form 2
| Types | Values |
| Rated voltage(Un) | 240VAC |
| Rated current(In) | 6A,10A,16A,20A,25A,32A,40A |
| Rated residual operated current(I△n) | 0.03A,0.1A,0.3A |
| Rated residual non trippingcurrent(l△no) | 0.51△n |
| DC component | AC type,A type |
| Poles | 1P+N |
| Instanttipping type | B type,C type |
| Ratedshortcircuitbreakingcapacity(lcn) | 6000A |
| Rated residualmakingandbreakingcapacity(l△m) | 500A |
| Breakingtimeofresidualoperatedcurrent | SeeForm2and3 |
| Overcurrent protection properties | SeeForm4,Diagram1and2 |
| Mechanical and electrical life | See Form5 |
| Connection wire | See Form6 |
| Tightening torque | 1.5N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperatureC | -25~+70 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
| Type | In(A) | 1△n(A) | Breaking time(s)whenl△equalsto the below values | |||
| I△n | 21△n | 51△n | 0.25A,5A~200A,500A | |||
| AC | 6~40 | 0.03,0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 |
Breaking timeofAtype
Overcurrent protection properties(nominal temperature 3 0 ^ { \circ } { C } )
| Type | In(A) | 1△n(A) | ret | ||||
| 1.41△n | 350A | ||||||
| A | 6~40 | 0.03 | 0.3 | 0.15 | 0.04 | 0.04 | |
| 0.1,0.3 | 0.3 | 0.15 | 0.04 | 0.04 | |||
Form4
| Item | Type | Test curren | Initial status | Tripping ornontripping time limit | Expected resul | Remarks |
| a | B,C | 1.13ln | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Test following the previous procedure; Processafter test | t | Trip | Current increasesto stipulatedvaluewithin5s | |
| C | 2.55ln | Cold | 1 | Trip | ||
| d | BC | 3n | Cold | t0.1s | Non tripping | Coninginxf ayrentch |
| e | B C | 5ln 10ln | Cold | t≤0.1s | Trip | Connection of current by openingauxiliaryswitch |
Mechanicalandelectrical life
| Category | Time | OperationTime(time/hour) |
| Mechanical life | 10000 | 240 |
| Electrical life | 2000 | 120 |
Connectionwire
| RatedcurrentIn(A) | Sectionarea of copperwire S(mm²) |
| 6 | 1.0 |
| 10 | 1.5 |
| 16,20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40 | 10 |
Overall and mounting sizes(mm)
General introduction
Function
VDF-63isakindofcircuitbreakerwithcompleteupdateofresidualcurrent detection,based on current typeA RCCB.It can not only effectively protect ACand pulsing DC(A type),the possible compound residual current (Ftype),butalsosmoothingDCandhigh frequencyresidualcurrent(1K Hz).Inacircuitconsistingofrectifier,inverter,frequency inverter,etc,the leakage currentcaused in DC loopcircuitcanbe effectivelydetectedand protected.
Application
Industry,medical,EVcharger,elevator,tc
Conformstostandard IEC/EN61008-1,IEC/EN62423;certifiedbyCCC,SEMKO,CE
Detectionresidual currenttype A C + A + smoothing DC + F + high frequency signal (1K Hz)
Mainparameters
| Types | Values |
| Ratedvoltage Un | 240V~1P+N,415V~3P+N |
| Ratedcurrent In | 16A,25A,32A,40A,63A |
| Rated residual operated currentI△n | 0.03A,0.1A,0.3A |
| Poles | 1P+N,3P+N |
| Type of residual current | Type B (AC+A+smoothing DC+F+ high frequency signal 1K Hz) |
| Ratedlimitedshortcircuitcurrent Inc | 10000A |
| Rated limited residual shortcircuit current I△c | 10000A |
| RatedmakingandbreakingcapacityIm | 1000A |
| Rated residual making and breaking capacityl△m | 1000A |
| Rated insulationvoltageUi | 500V |
| Rated impulse withstand voltage Uimp | 4000V |
| Electrical life | 2000Times |
| Mechanical life | 10000 Times |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambient temperature℃ | -25~+70 |
| Tightening torque | 3N.m |
| Connectioncapacity | 16mm2 |
| Pollution level | 2 |
| Protection level | IP20 |
| Mounting type | Ⅱ |
Overall and mounting sizes(mm)
| Circuitdiagram | Normal loopcurrent Loopcurrentof earthing fault | AC | Detection type of residual current | |||
| IL | IF | A | B | |||
| N PE Singlephase | ||||||
| N PE- Phase control | ||||||
| PE- Impulsecontrol N | ||||||
| N PE | ||||||
| Singlephasehalf-waverectification | ||||||
| Singlephase full-wave rectification N PE | ||||||
| halfphasecontrol PE | ||||||
| N PE Single phase half-wave rectification, with filtering | IF | |||||
| Three phase half-wave rectification 本本本F | ||||||
General info
Brief introduction
AFDD(arc fault detection device) isa new electrical anti-fire equipment. It could avoid variousof fires caused by short circuit,circuit aging,heavy load,poorcontact,fault electrical devices,etc.Automaticcontrol isrealized bybuilt-incomputerchip.Itsoperatingprinciple:thedetectedarc impulse isprocessed,compared and identified by electronic circuit and MCU.Once faultarc impulsewhicheasilycreatesfiredetected,theoutputwilldrive trippingunit tocut off the load powersupply,so that thefire isprevented.
Function
AFDDaimstodetect hazardousarc impulsewhich easilycreatesfire(such asinsulationdecreasingbetween lines,load shortcircuit,poor contact ofconnector,arccausedbyhouseelectricalapparatus fault).Thenit triggers trippingunit tocutoff thepowersupplytoprevent electrical fire. AFDD isused togetherwith leakagecircuitbreaker,lowvoltage circuit breaker(overcurrent protection)to buildamulti functionelectrical protective device.Asatrueintelligentlowvoltageelectricalapparatus,tcannotonly prevent electricalfire,electric shockto human,overloaddanger,etc,but alsobecustomizedwithdifferentfunctions.
Application
Asper IEC62606,thesedifferentratingsavailable:10A,16A,20A,32A,40A, 63A,usuallyused inresidential housesasa terminal protectivedevice. TheapplicationsofAFDDarewide,in theory,itcanbeusedtoavoid fire wherever there iselectricity,suchas in residential house,office building, hospital,shoppingmall,supermarket,factory,vehicle(auto,train,vessel,ir plane),especially foranti-fire use inresidential house.
Conformto IEC61009-1 IEC62606
Mainparameters
Ratedvoltage(Un):230V/50Hz;
Rated operating frequency:50/60Hz;
Maxload current:10A、16A、20A、32A、40A、63A;
Min load current:3A;
Maxload power:4KVA(dependson loadcurrent);
Mainparameters
| Mainparameters | Values |
| Ratedvoltageoptions(Un) | AC:110V~,230V~,240V |
| Ratedcurrent(In) | 6A,10A,16A,20A,25A,32A,40A,50A,63A |
| Rated residual operatedcurrent(l△n) | 0.03A |
| Ratedresidual nontrippingcurrent(l△no) | 0.51△n |
| DC component | ACtype,Atype |
| Poles | 2P |
| Instanttrippingtype | TypeC |
| Ratedshortcircuitbreakingcapacity(lcn) | 6000A |
| Ratedresidualmakingandbreakingcapacity(l△m) | 500A(In≤50A),630A(In=63A) |
| Overcurrent protectionproperties | SeeForm5,Diagram1 |
| Mechanicalandelectricallife | SeeForm6 |
| Connectionwire | See Form7 |
| Tighteningtorque | 2.0N.m |
| Nominaltemperature℃ | 30 |
| Operatedambienttemperature℃ | -25~+40 |
| Storedambienttemperature℃ | -25~+70 |
| Pollutionlevel | 2 |
| Protection level | IP20 |
Normaluseconditions
Ambienttemperature - 5 { { C } } or + 4 0 ^ { \circ } { C } ,averagedailytemperature + 3 5 { { C } } Max.Altitudenot exceeding 2 0 0 0 \mathsf { m } ,relative humidity: 50 % Maxat 4 0 ^ { \circ } { C } ” 9 0 % at 2 0 { { ^ { c } } } :
Characteristics
AFDD-63hastefoloingrotetiosidaloratdrrtfuldndocierppingaactesticsf esidual operated current shownasForm1.
Form 2
| Type | In(A) | 1△n(A) | eakinie | |||
| I△n | ||||||
| AFDD-63 | Any value | >0.03 | 0.3 | 0.15 | Maxbreaking time | |
| 0.03 | 0.3 | 0.15 | ||||
| 0.3 | 0.15 | 0.04 | ||||
TheprotectionuitsofAFDD63consistsofthfollowingsarcfaultprotectionndetectionunitmodificationfunitdetectioadsd atripingsignalwendistingshingtefaularcthtripperpushesthemechanicalstructuretotripthenthemaincontactofADil beswitchedfomoeingpositiontosconnectiogpositionwichakesthfaultircuitdiscoectedndvodefitlyfie createdbyarcfault. Form2andform3showtheultimatelimitoftrippingjudgementofarcfaultandbreakingtimeforratedvoltageof230V.
Limitvalue of tripping judgement of 63Aandbelow
| Testedarc current(effective value) | 3A | 6A | 13A | 20A | 40A | 63A |
| Maxbreaking time | 1s | 0.5s | 0.25s | 0.15s | 0.12s | 0.12s |
Form4
| Testedarccurrent(effectivevalue) | 75A | 100A | 150A | 200A | 300A | 500A |
| N | 12 | 10 | 8 | 8 | 8 | 8 |
| Item | Type | Testcurrent | Initial status | Time limit of tripping or non tripping | Expected result | Remarks |
| a | C | 1.13In | Cold | t≤1h | Non tripping | |
| b | 1.45ln | Testfollowingtse preinusprocedure; | t | Trip | sticurent inare wthin 5s | |
| C | 2.55ln | Cold | 132AA) | Trip | ||
| d | C | 3ln、5ln、10ln | Cold | t≤0.1s | Non tripping | Connection of current by openingauxiliaryswitch |
| e | C | 3ln、5ln、10ln | Cold | t≤0.1s | Trip | Coninctionxificuyrentbh |