TECHNICALSPECIFICATION
| Model Pecificatio | GN30-12M/400-12.5 GN30-12DM/400-12.5 | GN30-12M/630-20 | GN30-12M/1000-31.5 | GN30-12M/1250-31.5 | |
| GN30-12DM/630-20 | GN30-12DM/1000-31.5GN30-12DM/1250-31.5 | ||||
| Item Rated voltage(KV) | 12 | ||||
| Rated current(A) | 400 | 630 | 1000 | 1250 | |
| Ratedshort-timewithstand current(KA) | 12.5 | 20 | 31.5 | ||
| Rated short-circuit durations(S) | 4 | ||||
| Ratedpeakwithstand current(KA) | 31.5 50 80 | ||||
| Rated insulating level | Lighiningimpulse withstand voltage(KV) | Phasetophase/toearth:75/acrossopencontacts:85 | |||
| 1min.PF withstand voltage(KV) | Phasetophase/toearth:42/acrossopencontacts:48 | ||||
OVERALLDIMENSION
SPECIFICATION
TheGNF38-12KVseriesindoorisolatingswitch,inordertomeetfixed-pressurecabinet,RMUtorequireacompact, compactdesignandmanufactureof development,ithasthree-positionstructure,fullyinsulatedbottomplate,andisequipped withacoaxial lockandperfect mechanical interlocking structure,compactsize,isa compactbox-typeswitchgearbestequipped Switch.
AMBIENTCONDITION
MODELIMPLICATION
1.the altitude:Under2000M;
2.theambient temperature: -25~C-+40~C~
3.therelative humidityofair:monthly \lesssim90% daily \lesssim95%
4.Applicationoccasionsshouldfreefromfire,inflammables,
explosives,corrosivesandeseverevibration.
TECHNICALSPECIFICATION
| NO. | Item | Units | Parameters | |
| 1 | RatedVoltage | kV | 12 | |
| 2 | Ratedfrequency | Hz | 50 | |
| 3 | RatedCurrent | A | 630 | |
| 4 | Ratedshort-timewithstandcurrent(4S) | KA | 25,31.5 | |
| 5 | Ratedpeakwithstandcurrent(KA) | KA | 63,80 | |
| 6 | Rated insulation level | 1minfrequencywithstand | kV | Phasetophase/toearth:42、acrossopencontacts:48 |
| Lightningimpulsewithstand | Phasetophase/toearth:75、acrossopencontacts:85 | |||
OVERALLDIMENSION
SUMMARY
GN24-12D(IIl),GN24-12D(IIl)C series disconnect switch is an indoor electric apparatus of rated voltage 12KV,threephaseAC50Hz.
Structure
a,GN24-12D(I 1.2, Il1.21)Q disconnect switch is dynamic or static contact side earthing type. The main and earthing knife is combination inwhole frame;Type 1is forleft operation;type 2forright operation;Qis the safe working condition product,andcanbeattachedwithelectricindicatingdevice.
b,GN24-12SD1、Il(C.1.2.3.)is the dynamic and staticcontact onbothsidesearthing disconnect swith,meanwhile the contactcanbechangedtowallbushing,themainandearthingknifeiscombinationinthesameframe,onesetknifecan operateindependently,canalsobeoperatedbyamachineat thesametime.
AMBIENTCONDITION
PRODUCTFEATURE
1.the altitude: <=300000
2.the ambient temperature: -25°C-+40°C
3.therelativehumidityofair:monthly \lesssim90% daily \lesssim95%
4.ampitude:earthquakedegree8
5.Applicationoccasions should free frominflammables,explosives,
corrosivesandseverevibration.
1.Reasonableandscientificdesign,innovativestructure.
2.Contactingpointsdistributeontwoplanes,smalloperation
moment,strongpressurereleasecapability,easyadjustment.
3.Improveddriving and conductingparts.
4.Modelimplication
MODELIMPLICATION
OVERALLDIMENSION
| Size(mm) Current | 400A630A | 100A | 1250A | Mounting holespacing mm | |||||||||
| Model | A | B | C | D | A | B | C | D | A | B | C | D | |
| GN24-12DI | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | 700×300 |
| GN24-12DII | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | |
| GN24-12DI | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | |
| GN24-12DIIC | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | |
| GN24-12DI | 920 | 780 | 450 | 125 | 920 | 790 | 480 | 125 | 920 | 790 | 500 | 125 | |
| GN24-12DIC | 920 | 780 | 450 | 240 | 920 | 790 | 480 | 350 | 920 | 790 | 500 | 350 | |
GN27-40.5
SeriesIndoorHighVoltageDisconnectSwitcr
SPECIFICATION
GN27-40.5 indoor highvoltage disconnect switch is an indoor electric apparatus used inrated voltage 35kV, three-phase AC 50\mathsf{H}z system.Itusedforconnectandswitchthecircuitwithvoltagewithoutload.
This disconnect switch equipped withCS6-2 manual/handle operating mechanism,Dseries equipped withCS6-1 manual/handleoperatingmechanism.
AMBIENTCONDITION
PRODUCTFEATURE
1.Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Relative humidity:daily average \lesssim95% monthlyaverage \lesssim90%
4.Earthquake intensity: \lesssim8 degree;
5.Applicableoccasions should free from inflammables,explosives, corrosivesandseverevibration.
6.steampressure:daily average≤2.2\*10-3MPa,monthly average <=1.8^{*}10{-}3\mathsf{M}\mathsf{p}\mathsf{a}
1.Scientific design and innovative structure.
2.Multi contacts,rotary contacting,auto-cleaning capacity and effectivecooling.
3.Contacting points distribute on two planes, smalloperating moment andgoodpressurewithstandcapacityaswellas easyofadjustment.
4.Applicablewhen creepage distance,insulating capacity andwithstandvoltage are allon the highest level.
5.Axletree isfabricated on therotary axlesoas toprolong lifetime of apparatusand tosimplify operation.
森恒利
MODELIMPLICATION
TECHNICALSPECIFICATION
| Model | Rated voltage(KV)voltage(KV) | Max. | Rated current(A) | Ratedpeak withstandcurrent(kA) | 4sshort-time withstandcurrentKA |
| GN27-35(C)(D)/630 | 35 | 40.5 | 630 | 20 | 50 |
| GN27-35(C)(D)/1250 | 1250 | 31.5 | 80 | ||
| GN27-35(C)(D)/2000 | 2000 | 40 | 100 |
GN22-12
SeriesIndoorHighVoltageDisconnectSwitch
SPECIFICATION
GN22-12Disconnect switch is an indoorelectric apparatusof ratedvoltage 12kV three-phaseAC50/60Hz.it is used to break,makeandtransferlineswhenthe \mathsf{H V} apparatusisundersituationswithvoltageandno-load.
AMBIENTCONDITION
MODELIMPLICATION
1.Altitude: <=slant1000m
2.Ambienttemperature: -25° C\~+40°℃;
3.Relativehumidity:dailyaverage \lesssim95% monthlyaverage \lesssim90%
4.Earthquakeintensity: \L{<=slant}8 degree;
5.Applicableoccasionsshouldfreefrominflammables,explosives, corrosivesandseverevibration.
6.steam pressure:daily average ≤2.2×10-3MPa,monthly average <=1.8x10^{-3}Mpa
PRODUCTFEATURE
1.Scientific and reliable design.
2.Large current capacity.
3.Easy maintenance and operation.
TECHNICALSPECIFICATION
| Item | Units | Parameters | |||
| Ratedvoltage | KV | 12 | |||
| Ratedfrequency | Hz | 50 | |||
| Rated current | A | 1600-2000 | 2500 3150 | ||
| Ratedshort-circuitresistancecurrent | KA | 40 | 50 | ||
| Ratedpeakwithstandcurrent | KA | 100 | 125 | ||
| Ratedshort-circuitduration | S | 4 | |||
| Rated insulatinglevel | 1min.PFwithstandvoltage | KV | Phase tophase/to earth:42,across open contacts:49 | ||
| Lightningimpulsewithstandvoltage(peak) | KV | Phasetophase/toearth:75,across opencontacts:85 | |||
OVERALLDIMENSION
| Model | A | B | C | D | E |
| GN22-12/1600-2000 | 255 | 305 | 527 | 490 | 50 |
| GN22-12/2500-3150 | 262 | 325 | 538 | 494 | 60 |
| GN22-12C/1600-2000 | 537 | 255 | 305 | 807 | 580 |
| GN22-12C/2500-3150 | 539 | 267.5 | 330 | 880 | 630 |
SPECIFICATION
TheGW9outdoorhighvoltage disconnectswitchisa typeofHVelectricapparatusofratedvoltage10KV,15KV,24KV,is used tobreakandmakecircuitunderno-load.
ThisseriesdisconnectswitchmeetGB1985<ACHIGH-VOLTAGEDISCONNECTORANDEARTHINGSWITCH>、 IEC60129<ACHIGH-VOLTAGEDISCONNECTORANDEARTHINGSWITCH>andGB/T1022<COMMONSPECIFICATIONS FORHIGH-VOLTAGESWITCHGEARANDCONTROLGEARSTANDARDS>etcstandardrules.
AMBIENTCONDITION
MODELIMPLICATION
1.thealtitude:Under1000M 2.theambienttemperature: -30°C-+40°C alpineregion, -40°C 3.Application occasions should free fromfire,inflammables, explosives,corrosivesandeseverevibration.
TECHNICALSPECIFICATION
| Item | Units | Parameters | ||||||||||
| KV | 15 | 24 | ||||||||||
| RatedVoltage Ratedworkvoltage | KV | 10 12 | 17.5 | |||||||||
| Rated withstand insulation level | 1minfrequency | To earth | KV | 42 | 55 | 65 | ||||||
| Open contacts | KV | 48 | 65 | 79 | ||||||||
| Lightning impulse withstand | Toearth | KV | 75 | 105 | 125 | |||||||
| Open contacts | KV | 85 | 120 | 145 | ||||||||
| Ratedfrequency | HZ | 50 | ||||||||||
| Rated current | A | 200 | 400 | 630 | 1250 | 400 | 630 | |||||
| Rated short-time withstand current(4S) | KA | 6.3 | 12.5 | 20 | 31.5 | 16 | 20 | |||||
| Ratedpeakwithstandcurrent | KA | 16 | 31.5 | 50 | 80 | 40 | 50 | |||||
| Creepagedistance | mm | 300 | 380 | |||||||||
| Life | Times | 2000 | 2000 | 2000 | ||||||||
OVERALLDIMENSION
GW4-12(17.5-40.5) OutdoorHighVoltageDisconnectSwitch
SPECIFICATION
The GW4-12(1735/40.5) series outdoor H.V.disconnect switch is applicable device in outdoor AC 50 Hz. It is used to make,breakandtransferbetweenlinesundersituationwithvoltage17.5KV/40.5KVandno-load.It ismadeasperGB1985.
AMBIENTCONDITION
MODELIMPLICATION
1. The altitude: <=10000
2.Theambient temperature: -30°C-+40°C alpineregion,- 40 {cent}
3.Airpressure: \le700\mathsf{P a}
4.Earthquake intensity: <=8 degree;
5.Ice thickness: <=q10mm
6.Applicationoccasions should freefromfire,inflammables, explosives,corrosivesandeseverevibration.
TECHNICALSPECIFICATION
| Classification | Model | Rated voltage (KV) | Rated current (A) | Disconnectswitch | Earthingswitch | |||||
| Ratedpeak | Rated short circuit withstandcurrentKAwithstandcurrentKA | Rated peak withstand currentKA | Ratedshortcircuit withstand currentKA | |||||||
| General type (anti-pollution type) | GW4 | 12 | 600~630 | 80 | 31.5(4s) | 50 | 80 | 20 (4s) | 31.5 (4s) | Noearthing、 singleearthing、 doubleearthing |
| 17.5 | 400~1000 | 50 | 20(4s) | |||||||
| 40.5 | 400~1250 | 80 | 31.5(4s) | |||||||
OVERALLDIMENSION
SPECIFICATION
GW5seriesoutdoordisconnectswitchisthemostcommon equipmentsinelectricsystem.Itsmainfunctionisisolating high voltagewhen theequipmentsorcircuit dothemaintenance,toensuresafety.GW5cannotbreaktheloadcurrentandshortcircuitcurrent,needtousecooperativelywithcircuitbreaker.Whenpowercutfirstlyseparatebreakerthenseparatedisconnect switch:whenpoweronfirstlyclosedisconnectswitch,thenclosebreaker.
GW5seriesoutdoor disconnect switchbelong todouble columnV shape,horizontalopen-type.Eachsingle stage composedofsubstrate,supportinginsulator,outletpower,contact,etc.ltfixedbytwo 50° includedanglesubstrate,supporting insulatorandtwosupporting insulatormaketheangletoeachother,andinstallthebearingofsubstrate,verticalwithsubstrate. Leading electricpartseparate installonthe twosupporting insulator,make the 90° rotatetogetherwiththesupportinginsulator.
AMBIENTCONDITION
PRODUCTFEATURE
1.Thealtitude:under1000-3000M;
2.Theambient temperature: -30°C-+40°C coldareas-40°℃;
3.Windpressure \lesssim8
4.Ampitude:Earthquakedegree8;
5.Applicationoccasionsshouldfreefromfire,inflammables, explosives,corrosivesandseverevibration.
6.anti-pollutiontypesuitable forseriouspolluted area,but should nothasthematerial whichcancausefire/explode.
1.Completeinspecifications,high technicalparametersishigh, widerange.Additional,widescopeofapplication,itcanbe usedforhighlayout.Installationwayisflexible. 2.Perfect sealing Performance and Resistant ToRust 3.Simple,reliablemechanical rotating way. 4.Perfect dustproof,waterproof,and anti-corrosionability. 5.Fullset of steel galvanized foundation frame and thevertical andhorizontaldwangforoption.
森恒利
MODELIMPLICATION
TECHNICALSPECIFICATION
| Ratedvoltage(KV) | A | A1 | H | E | C | D |
| 40.5 | 1200 | 1075 | 1070 | 1400 | 240 | 300 |
| 72.5 | 1600 | 1285 | 1295 | 2200 | 240 | 300 |
| 123 | 2000 | 1660 | 1695 | 3000 | 240 | 300 |
OVERALLDIMENSION
SPECIFICATION
The GW7seriesoutdoorAChighvoltageisolationswitchisa three-phaseAC5011zhighvoltage electricalapplianceused inpowersystemswithratedvoltagesranging from126to50kV.It isusedforno-loadswitchingofhighvoltagelines,aswellas electrical isolation of electrical equipment such as highvoltagebusbars,circuit breakers,and livehighvoltage linesunder maintenance.
This product has the following varieties:
a.Dividedbythepresenceorabsenceofa grounding switch:ungrounded,singlegrounded,doublegrounded: b.Dividedbyusagereqion:ordinary type.pollutionresistant type,and plateau type.
This seriesof products complieswith the latestnational standards and1ECstandards,andmeets therequirementsof StateGridCorporationofChina for theimprovement of high-voltageisolatingswitches.
STRUCTURE
TheGW7seriesoutdoorAChighvoltageisolationswitchisasinglepolethreecolumnhorizontal rotatingstructure,mainly composed of abase,post insulators,and conductiveparts.Eachpoleis composed of three insulatedpillars,withfixed pillarson both sides and a rotating pilar in the middle;The dynamic switch is assembled on the upper part of the middle post insulator, and thestaticcontactsarerespectivelyinstalledontheupperpartsofthetwopostinsulators.Theoperatingmechanismdrives themiddleinsulatortorotateforopeningandclosingoperations.
Inorder toensurethecorrect operationsequencebetween theisolationswitchand thegroundingswitch,a mechanical interlocking device isinstalledbetweenthegrounding switch and themainswitch.
TheGW7seriesisolationswitchismadeinasinglepoleformandcanachievethreepolemechanical linkageoperation throughpole topolelinkages.Themainknife isequipped withCJ6or CJ6-1electricmechanism(when thecurrent isgreater than2000Aat252kVlevel),andthegroundknifeisequippedwithCS20- (\mathsf{X}) manualmechanismandDsw3electromagnetic lock.
1.Simplestructureandstableperformance; 2.The overall steel parts arehot-dip galvanized,with strong corrosionresistance 3.Thetransitionlinkof theconductiveswitchadoptsasoftconnectionstructureand thereisnophenomenonofexcessive temperatureriseduringlong-termuse. 4.Adoptingmaintenancefreebearing seatsandreliableinterlockingandlimitingdevices:5.Onsiteweldingfree,easy installationandmaintenance
TECHNICALSPECIFICATION
| ProductModel Parameter | GW7-126W | GW7-252W | GW7-363W | |
| RatedvoltagekV | 126 | 252 | 363 | |
| RatedcurrentA | 1250200025003150 | 1250200025003150 | 1600250031504000 | |
| Ratedshort-timewithstandcurrent | 4050 | 4050 | 405063 | |
| (effectivevalue)kV Ratedpeakwithstandcurrent(peak)kA | 100125 | 100125 | 100125160 | |
| Ratedshort-timepowerfrequency withstand(effectivevalue)kV | Ground fracture surface | 230 | 460 | 510 580 |
| 265 | 530 | |||
| Ground Ratedlightningimpulse fracture withstand(peak)kV surface | 550 630 | 1050 1200 | 1175 1175(205) | |
| Ratedhorizontaltensionofwiringterminal N | 1000 | 2000 | 2000 | |
| SingleboardweightKG | 600 | 1100 | 1500 | |
SPECIFICATION
TheGW8seriesneutralpointoutdoorAChighvoltageisolationswitchisasingle-phaseAC50Hzhighvoltageelectrical device used in power systems with rated voltages of 40.5-126kV, for connecting the neutral point of the transformer under noloadconditions.
Thisproduct isclassifiedbyusageregionasordinarytype,stainresistant type,andplateautype. Thisseriesofproductscomplieswiththelatestnationalstandardsand1ECstandards,andmeetstherequirementsof StateGridCorporationofChinafortheimprovementof high-voltageisolatingswitches.
STRUCTURE
TheGW8seriesoutdoorneutralpointACisolationswitchconsistsof anindependentsinglepole,includingabase,post insulator,conductive system,and transmissionsystem.There aremetalbrackets,connecting arms,andoperatingporcelain bottlesbetweenthesupportinginsulatorsand theoperating insulators.Theoperatingmechanismdrivesthedynamicswitch blade to perform opening and closing movements through the connecting rod and the insulator crank arm.
This product is equipped with CJ6 electricorCS17G manual mechanism,and can bepaired withDSW3 electromagnetic lock.
1.Simplestructureandstableperformance:
2.Small installationspacerequirementsandadaptabilitytoflexible anddiverse layoutmethods
3.Theoverallsteelpartsarehot-dipgalvanized,withstrongcorrosionresistance:
4.Adopting maintenancefreebearingseatsandreliableinterlocking andlimiting devices:
5.Onsiteweldingfree,easyinstallationandmaintenance.
TECHNICALSPECIFICATION
| ProductModel Parameter | GW8-126W | GW8-252W | GW8-363W | |
| RatedvoltagekV | 40.5 | 72.5 | 126 | |
| Rated currentA | 630 | 630 | 630 | |
| Ratedshort-timewithstandcurrent (effectivevalue)kV | 31.5 | 31.5 | 31.5 | |
| Ratedpeakwithstandcurrent(peak)kA | 80 | 80 | 80 | |
| Ratedshort-timepowerfrequency withstand(effectivevalue)kV | 85 | 140 | 230 | |
| Ratedlightningimpulse withstand(peak)kV | 185 | 325 | 550 | |
| RatedhorizontaltensionofwiringterminalN | 750 | 750 | 1000 | |
| SingleboardweightKG | 75 | 90 | 105 | |
OVERALLDIMENSION
SPECIFICATION
LW8-40.5outdoorhighvoltageSF6circuitbreakeris a three-phaseAC50Hzoutdoorhigh-voltage electricalequipment for control and protection of 35kV transmission and distribution systems,and can also be used to open and close contact breakerandcapacitorbanksoccasions.
LW8-40.5-breakerequipped withCT14 spring operating mechanism.
BreakerinlinewithnationalGB1984-89"AChighvoltagecircuitbreakers"andtheInternational.
AMBIENTCONDITION
MODELIMPLICATION
1.Thealtitude:1000M-3000M
2.Theambient temperature: -30°C-+40°C ,alpineregion,≥- 40 {>}
3.Windpressure:8degree;
4.Earthquakeintensity: \lesssim8 degree;
5.Flexiblemountingsiteshouldnotseriouslyaffect theisolation switchinsulationandconductivityofgases,vapors,chemical deposition,salt spray,dust and other explosive,corrosive substances;
6.Appliesto serious contamination andpollutionprevention areas,butshouldnothavecaused afireandexplosionand other substances;
TECHNICALSPECIFICATION
| Item | Units | Parameters | |
| Ratedvoltage | KV | 40.5 | |
| Rated insulationlevel | 1minpowerwithstandvoltage | KV | 95 |
| Lightning impulsewithstandvoltage | KV | 185 | |
| Ratedcurrent | A | 1600/2000 | |
| Machanicallife | Time | 3000 | |
| SF6gasratedpressure(when20℃ the gaugepressure) | Mpa | 0.45 | |
| Closurepressure(when20°Cthegaugepressure) | Mpa | 0.42 | |
| Thelowesttemperature | ℃ | -30 | |
| Ratedshort-circuitbreaking current | KA | 20/25/31.5 | |
| Rated short-circuitclosing current(peak) | KA | 50/63/80 | |
| Ratedshorttimewithstandcurrent(thermalcurrent) | KA | 20/25/31.5 | |
| Ratedpeakwithstandcurrent(dynamiccurrent) | KA | 63/80/100 | |
| Ratedoutofstepbreakingcurrent | KA | 63/80/100 | |
| Ratedshortduration | S | 4 | |
| Closingtime(ratedoperatingvoltage) | S S | ≤0.1 | |
| Operatingtime(ratedoperatingvoltage) | ≤0.07 | ||
| Ratedoperatingsequence | 0-0.3s-C0-180s-CO | ||
| Ratedcurrentopeningandclosingofasinglecapacitorcombination | A kg | 400 | |
| WeightofSF6 | 8/5 | ||
| Circuitbreakerweight(includingtheoperatingmechanism) | kg | 1400/1000 | |
OVERALLDIMENSION
SPECIFICATION
LW36-126/T3150-40outdoor self powered high-voltage SF6circuit breaker,alsoknown asthe third generationSF6 circuit breaker,adoptsa uniqueselfpowered arc extinguishingprinciple,whichhasa good arc extinguishing effect throughout the entirebreakingcurrentrange of thecircuit breaker,andfullyutilizesthe energyof the arcitself toextinguish the arc. Therefore,theoperatingpowerissmall,themechanical lifeishighanditcanreach60o0times,thusmproving thereliabilityf thecircuitbreakerasawhole
PURPOSEANDSCOPEOFAPPLICATION
LW36-72.5(G)T3150-31.5andLW36-126(G)/T3150-40 high-voltage sulfur hexafluoride AC circuit breakers are suitableforAC50Hz,66kV,and110kVpowersystems.They are control andprotectionequipment forpowersystems and can alsobeusedascontactcircuitbreakers.
STANDARDSANDMAINFEATURES
Thecircuit breakercomplieswith therequirementsofGB1984-2003"HighVoltageACCircuitBreakers"andIEC62271- 100"HighVoltageACCircuit Breakers".The circuit breakerusesSF6gasas insulation and arcextinguishing medium,adopts self energy arc extinguishingprinciple,and is equipped with DCT-126P spring operating mechanism,which has the characteristicsof strong breaking ability,lowoperatingpower,and highreliability.
森恒利
THENORMALENVIRONMENTALCONDITIONSFORUSE COMPLYWITHTHEFOLLOWINGREGULATIONS:
a)Theambientairtemperaturerangesfrom-25 C (-40~°C) 0+40 ℃;
b)Altitude <=2500m\left(2000m\right)
c)Wind speed <=slant34m/s
d)Dailytemperaturedifference <=25
e)Sunshine intensity <=slant1000\mathsf{W}/\mathsf{m}
f)Seismichorizontal seismicintensity of 8degrees:horizontalaccelerationof0.2g,vertical accelerationof 0.1g; g)Icethickness <=slant10mm
h)Thedegreeofairpollutionshallnotexceedlevel IVinGB/T5582;
i) Installationlocationoutdoors.
Note:Thevaluesinparenthesesareparametersforacircuitbreakerpressureof0.33MPa.
If theuserhasspecialenvironmentalrequirementsforuse,theycannegotiatewiththemanufacturerseparately
STRUCTURALCHARACTERISTICS
Thecircuitbreakeradoptsa threepoleporcelainbushingpillarstructure,withthreepolesinstalledonacommonbase.The upperpart of thepoleis the arcextinguishing chamber,and the lowerpart is thepilarceramicsleeve.Thebase isequippedwith a three-phase linkagetransmissionsystem,a threepoleSF6gasconnectedpipelinesystem,and anSF6gasdensity controller.Thecontrol cabinetissuspended in thecenterunderthebase,and thereisaspringoperatedmechanismand control unit thatarejointlyusedbythreepolesinsidethecabinet.Theoutputrodof themechanismisconnectedtotheoutercrankarm of theB-pole,and thenoperated througha threepolemechanical linkage througha horizontal connectingrod.
The circuit breaker uses SF6 gas as the insulation and arc extinguishing medium.During operation,the SF6 gas inside the three poles of the circuit breakeris interconnected,and a pointer type densitycontroller isused tomonitor its pressure and density.Dueto theuseof self poweredarcextinguishing principleandoptimized designinthe circuit breakermotionsystem,the mechanical eficiencyhasbeen effectively improvedand the operatingpower hasbeenminimized to the greatestextent possible.
be careful:
1.Thevaluedisplayedbythedensitycontrolleristhepressurevalueat 20~°C
2.When thepole isnotconnected,thevalue displayed bythedensitycontrolleristhe pressure inside the trachea
SPECIFICATION
LW36-126high-voltage sulfurhexafluoride circuit breaker is a three-phaseAC,outdoor(indoor)high-voltagepower equipment.Mainlyusedfor controlandprotectionof 132kVpower systems,it canalsobe usedasacircuit breakerfor interconnection.
APPLICATIONSCOPE
Mainlyusedforcontrol andprotectionof126kVpowersystems,itcanalsobeused asa circuitbreakerforinterconnection.
TECHNICALSPECIFICATION
| project | parameter | ||||
| altitude | 1000m | 2000m | |||
| ambienttemperature | -30°C-40°℃ | -40°℃-40°℃ | -30℃-40℃ | -40℃-40℃ | |
| ratedvoltage | 145kV | ||||
| Rated current | 3150A | ||||
| Ratedshort-circuitbreaking currentIsc | 40KA | 31.5KA | 40KA | 31.5KA | |
| Rated short-circuit closing current(peak) | 100KA | 80KA | 100KA | 80KA | |
| Ratedshort-timewithstand current(effectivevalue)3s | 40KA | 31.5KA | 40KA | 31.5kA | |
| short linefaultbreakingcurrent | IscX90%、IscX75%(kA) | ||||
| Ratedout of stepbreakingcurrent | IscX25%(kA) | ||||
| 1minutepowerfrequency withstandvoltage (Effectivevalue) | fracture surface | 275+84kV | 275kV | 275+84kV | 275kV |
| Withstandvoltage | toground | 275kV | 275kV | 275kV | 275kV |
| againstlightning impulse (Peakvalue) | fracture surface | 650+119kV | 650kV | 650+119kV | 650kV |
| toground | 650kV | 650kV | 650kV | 650kV | |
| mechanicallife | 10000次 | ||||
| radiointerferencelevel | ≤500μV | ||||
| Electricallifespan | 20次 | ||||
FKN12-12RD
SeriesIndoor HighVoltageAir-BlastType LoadBreakSwitch-FuseCombinationApparatus
SPECIFICATION
FKN12A-12DSeriesair-blastloadbreakswitchandFKRN12A-12Dseriesair-blastloadbreakswitch-fusecombination apparatusarenewseriesswitchgearappliesto three-phaseelectricdistributionsystemofrated12kV,acting asprotecting and controlapparatusfortransformers,cableandoverheadwiring.Theseseriesareespeciallyapplicableinrural,urbanterminal substationand prefabricatedsubstations,aswellasring networkpowersupply.
FKN12A-12DSeriesair-blastloadbreakswitchcanbreakandmakeloadcurrentandover-current.
FKRN12A-12D Series air-blast load break switchcan break and make over-current,loadcurrent and short-circuit current(limitedcurrentfuse).
Thisproduct isfeatured withimpactstructure,aestheticappearancereliable interlockandhighinsulatinglevel.In thespring storage operating mechanism,ON/OFFspeed isfreefrom theinfluence of the manpower.For the arc-extinguishelectricarcextinguishinsidetheinsulatingcover,thefreegasoccursatsparkingdonotcausedescendof insulating level betweenphases andphase toearth.The insulatingcoverclapboardseparateselectrifiedpart thusboostprotectiongradeof ringmainunit.The copper-tungstencontactandmain contact brings alongreliableconductivity and long life.Thisproduct achievessound fame due toeasymaintenanceandoperationsaswellasreliableperformance.lIt isincompliancewithperIEC62271-105.
AMBIENTCONDITION
1.Ambienttemperature-25C-+40°℃
2.Elevation <=slant1000m
3.Humidity:daily averagehumidity \lesssim95% monthly \lesssim90%
4.The earthquake doesnotexceed degree8
5.No fire,explosion,chemical errosion.
6.Pollution:level 2
TECHNICALSPECIFICATION
OVERALLDIMENSION
| Size(MM) Model | A | H | C | D | E | F | K | J | L | M | N | P | R | S | D | V | W | Z | Weight |
| FKN12A-12D | 390 | 940600210 | 648270 | 67 | 50 | 155 | 287 | 171368 | 11 | 337 | 170 | 94 | 105 | 868 | 180 | 70kg |
SPECIFICATION
FZN25,FZRN25typevacuumloadswitchandcompositeapparatus,suitableforthree-phaseAC50Hzringnetworkor terminalpowersupplyandindustrialelectricalequipment,forloadcontrol andshortcircuitprotectionuse,loadswitchopenand closetheclosedloopcurrent,no-load transformerand cablechargingcurrent,compositeapparatuscanbreakanycurrent tll ratedshortcircuitcurrent.Adoptthestraightmoveorisolatingfractureandvacuuminterrupterlinkage.Withfunctionofmanual andelectricoperation.
FZN25,FZRN25special transmissionstructure design,arcextinguishchamberonly withstandvoltage in themomentof closingand breaking,small size,Lightweight.
FZN25,FZRN25hasa grounding switchmutual linkagegrounding valvebetween thestaticcontact andmova conductive cylinder,ensuressafety andconvenientmaintenance.
AMBIENTCONDITION
1.Theambienttemperature: -25°C-+40°C ,alpineregion, >=-40°C
2. The altitude: <=1000\mathsf{M}
3.Relativehumidity:dailyaveragevalueisnotgreaterthan 95% monthlyaverageisnotgreaterthan 90%
4.Earthquakeintensity: \L{<=slant}8 degree;
5.Thesurroundingairisnotcorrosiveandflammablegas,steamandothersignificantpollution;
6.Contaminationgrade:llclass;
MODELIMPLICATION
TECHNICALSPECIFICATION
| NO. | Item | Units | Parameters FZRN25-12D/T125-31.5 | ||
| FZN25-12D/T630-20 | |||||
| 1 Ratedvoltage | KA | 12 | |||
| 2 | Rated frequency | HZ | 50 | ||
| 3 | Rated Current | A | 630 125 | ||
| 4 | Rated insulationlevel | 1minfrequencyvoltage | KV | Interrupterractur30.onthegroundwhit42solationFracture48 | |
| Lightningimpulsewithstandvoltage | KV | Ontheground,white75solationFracture85 | |||
| 5 | Rated dynamicstability current(peak) | KA | 50 | ||
| 6 | 4Sthermalcurrent | KA | 20 | 一 | |
| 7 | Ratedactiveloadbreakingcurrent | A | 630 | 125 | |
| 8 | Ratedclosed-Loopbreakingcurrent | A | 630 | 125 | |
| 9 | Ratedcablechargingbreakingcurrent | A | 10 | 10 | |
| 10 | Breakingloadtransformer | KV | 1250 | 1250 | |
| 11 | Ratedshort-circuitbreakingcurrent | KA | 31.5 | ||
| 12 | Rated transfercurrent,ratedcurrenttransfer | A | 2000 | ||
| 13 | FuseModel | SDLAJ-12SFLAJ-12 | |||
| 14 | Impactenergyoutput | J | 2-5 | ||
| 15 | Ratedshortcircuit making current | KA | 50 | ||
| 16 | GroundswitchratedDynamiccurrent | KA | 50 | ||
| 17 | Groundingswitch2Sthermalcurrent | KA | 20 | ||
| 18 19 | SecondarycircuitRatedvoltage | V | AC/CD220:110 | ||
| Mechanicallife | Times | 1000 | |||
OVERALLDIMENSION
SPECIFICATION
FN7-12DRModel IndoorAC HVLoadSwitch is suitable in50Hz,rated voltage of 12Kvthe three-phaseACpower system as the breaking load short-circuit current of thepowerand used the Closing,until the combinationof electrical short-circuit current canbe breaking any current canbeused asprotectionpurposes.
RATINGS
| Ratedvoltage(KV) | 12 | ||
| Insulationlevel | 1minfrequencyvoltage(KV) | Phasetophase、toearth42 | lsolationfracture48 |
| Lightningimpulse withstandvoltage(OKV | Phasetophase、toearth75 | lsolationfracture85 | |
| Ratedcurrent(A) | 400 | 630 | |
| 4SRated thermalcurrent(KA) | 12.5 | 20 | |
| RatedactiveloadbreakingcurrentKA(Peak) | 31.5 | 50 | |
| Ratedshortcircuitmakingcurrent(KApeak) | 31.5 | 50 | |
TECHNICALSPECIFICATION
| Name Models | DS | DX | L | R | RA | F | Use | |
| Grounding switch incomingfedderside | Grounding switch outgoingfedderside | Interlockdevice | Fuse | Impactfuse Electric sub- | ||||
| Switches Load | FN7-12 | gatedevices | switch | |||||
| FN7-12DSL | peo | |||||||
| -impactfuse FN7-12DXL | △ | △ | Line | |||||
| FN7-12R | △ | Protection | ||||||
| -UON FN7-12DSLR | △ | △ | △ | |||||
| FN7-12DXLR | △ | △ | △ | TransformerR | ||||
| FN7-12RAF | △ | △ | ||||||
| impactfuse FN7-12DSLRAF | △ | Transformer Protection | ||||||
| FN7-12DXLRAF | △ | △ | △ △ | △ △ | ||||
OVERALLDIMENSION
FN5-12
SeriesIndoorACHighVoltageLoad BreakSwitch-FuseCombinationApparatus
SPECIFICATION
FN5-12R(L) model indoorACHV loadbreak switch-fusecombinationapparatusisdeveloped and designedbasedon international technologyandnationalpowersupplyrequirement,itpassedalltypetestsandtrial-operationinspections.The apparatuSconformstoIEC420:ACLOADBREAKSWITCHANDFUSECOMBINATIONAPPARATUS(1990EDITION)and GB3804:3-63KVAC HVLOADBREAKSWITCHVOLUMEANDLIGHTWEIGHT.Compared to international product itkeeps upwithtechnical levelwithsmallvolumeand light weight.It isapplicableinringmainunit andprefabricatedsubstationsaswell as12kvlineandpowerdistributionsystem.Theproductrealizesthreeworkingpositions:powermaking,powerbreakingand earth.lIt appliestopowersystemof ratedvoltage6-12kv,50/60HZbreaking loadcurrentoberloadcurrentandshort-circuit current.
AMBIENTCONDITION
1.The altitude:under 1000M;
2.The ambient temperature: -25 C-+40 ^\circC
3.Therelativehumidityofair:monthly \lesssim90% ,daily \lesssim95%
4.Ampitude:Earthquakedegree8;
5.Application occasions should free from fire,inflammables,
explosives,corrosivesandseverevibration.
TECHNICALSPECIFICATION
| Rated voltageKV | 1min frequency voltage KV | Rated CurrentA | 4Sthermal currentA | Dynamic current (peak)KA | Rated breaking currentA | Shortcircuit closecurrent KA |
| 12 | 42 | 400 | 12.5 | 31.5 | 400 | 31.5 |
| 48 | 630 | 20 | 50 | 630 | 50 |
OVERALLDIMENSION
Left side:Load switch and
CS6-10 operating mechanism drawing
1.Loadswitch
2.Bend connection
3.3/4""Welded steel pipe”
4.Operating mechanism
IndoorAChighvoltageloadswitch
1.Bottombase2.lnsulator
3.Fuse 4.Tripper gear
5.Movablecontact
6.Arc-extinguishing tube
7.Guidance piece 8.Static contact
9.Switching mechanism
10.lnterlocking apparatus
11.Load switchoperating mechanism
12.Earthing switch
| Model | Ratedvoltage(KV) | Rated current(A) | Fondantrated current(A) |
| SDLA*J | 12 | 50 | 6.3,1016,20,25,31,540 |
| SFLA*J | 12 | 100 | 50,63,71,80,100 |
| SKLA*J | 12 | 125 | 125 |
SPECIFICATION
JN15-12seriesindoorhighvoltage (H V) earthingswitchabsorbsadvancednewtechnicalfromdomesticandabroad.lt confirmstoGB1985-89<ACHVDISCONNECTSWITCHANDEARTHSWITCH>,relativestandardsIEC129andpassKEMA test.The apparatus appliestopowersystemofratingbelow 12kv,andAC50/60HZ.It issuitableforvarious typesHV switchgearforearthingprotection.Theholisticearthingswitchconsistsofbasis,supportinginsulatormainaxismainbladefast spring,fixedandmovingcontact.Additional electronicdisplayis alsoavailableaccording to theusers’srequirement.
AMBIENTCONDITION
MODELIMPLICATION
1.Altitude: <=slant1000m
2.Ambient temperature: -10°C^{ -+40°C}
3.Humidity:daily average humidity \lesssim95% monthly \lesssim90%
4.Earthquake does not exceed degree8;
5.No fire,explosion,chemical erosion.
PRODUCTFEATURE
1.Advanceddesignandsteadyperformance.
2.Simple structures,simple mounting and adjustment.
3.Quickbreaking andmaking capability.
4.Handsome appearance and delicate manufacture technical.
5.Usableandscientific,availableoperationonbothtwosides
(rightandleft).
森恒利
TECHNICALSPECIFICATION
| Item | Units | Parameters | ||
| Ratedvoltage | kV | 12 | ||
| Ratedshort-timewithstandcurrent | kV | 31.5 | ||
| Ratedshort-circuitduration | S | 4 | ||
| Ratedcircuit-timemakingcurrent | KA | 80 | ||
| Ratedpeakwithstandcurrent | KA | 80 | ||
| Centraldistancebetweenpoles | mm | 150,210,275 | ||
| Rated insultinglevel | 1min.PFwithstandvoltage | kV | Toearth,phasetophase/fracture | 42/48 42/48 |
| Lightingimpulsewithstandvoltage | ||||
OVERALLDIMENSION
| Model | L | E | C |
| JN15-12/31.5-210 | 655 | 210 | 516 |
| JN15-12/31.5-230 | 710 | 230 | 556 |
| JN15-12/31.5-250 | 760 | 250 | 596 |
| JN15-12/31.5-275 | 810 | 275 | 646 |
SPECIFICATION
JN15-24/31.5indoorAVHVearthing switch is thenewearthing switchourBoxd companyresearchand developed.It has theadvanced design,simpleandcompactstructure,reliabletechnicalperformance,etc.ItaccordingwithGB1985-2004AC HV disconnect switch and earthing switch,relative standards IEC62271-102: 2002.The apparatus applies to power system of rating below24kV,and AC50/60 Hz.lt has short-circuit making capacity toprotect other electricalequipment in the switching equipment,and alsobeused forearthingprotectionwhenoverhauling high-voltageelectrical apparatus.
AMBIENTCONDITION
1. Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:dailyaveragehumidity \lesssim95% ,monthly \lesssim90%
4.Earthquake does not exceed degree 8;
5.No fire,explosion,chemical erosion;
6.Pollution: level 2.
森恒利
PRODUCTFEATURE
1.Altitude less than 1000m.
2.Ambient air temperature:up to +\;40 °C ,the lowerlimit of -25 C
3.The daily averagerelative humidity of 95% is not dry,on average less than 90%
4. Filthy rating: ll.
TECHNICALSPECIFICATION
| NO. | Item | Units | Parameters | ||
| 1 | Rated current | KA | 24 | ||
| 2 | Ratedshort-timewithstandcurrent | KA | 31.5 | ||
| 3 | Ratedcircuit-timemakingcurrent | KA | 80 | ||
| 4 | Ratedpeakwithstandcurrent | KA | 80 | ||
| 5 | Ratedshort-circuitduration | S | 4 | ||
| 6 | 1min.PFwithstandvoltage Rated insultinglevel | kV | Toearth, 65 Phasetophase | ||
| 7 | Lightingimpulsewithstandvoltage Mechanical life | 次 | 125 2000 | ||
OVERALLDIMENSION
JN22B-40.5/31.5
SeriesIndoorAC HighVoltageEarthingSwitch
SPECIFICATION
JN22B-40.5/31.5seriesindoor highvoltage(HV) earthing switch absorbsadvanced new technicalfrom domestic and abroad.ItconfirmstoGB1985-2004<ACHVDISCONNECTSWITCHANDEARTHSWITCH>standard.Andappliestothreephaseratedvoltage 405kV,AC50/60Hzpowersystem.Itcansupport theuseofKYN61-405HVswitchpanelandother models,thefoundationisprotecttheHVelectricequipmentswhenrepairormaintenance.JYN22-40.5/31.5seriesHVearthing switchisrevisedandupdateonthebaseof theabovemodel,itsstructureismoresimpleandcompact,bestperformanceand easy operatewith smallangle.It is samewith JN15-12,theconnect and driving medium are incommon use.
AMBIENTCONDITION
MODELIMPLICATION
1.Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:dailyaveragehumidity \lesssim95% monthly \lesssim90%
4.Earthquake doesnot exceed degree8;
5.No fire,explosion,chemical erosion.
MOUNTINGCUTOUTFIGURE
| Model | E | G | L | D |
| JN22B-40.5/31.5-280 | 280 | 290 | 1010 | 656 |
| JN22B-40.5/31.5-300 | 300 | 340 | 1100 | 696 |
| JN22B-40.5/31.5-350 | 350 | 340 | 1200 | 796 |
| JN22B-40.5/31.5-360 | 360 | 320 | 1200 | 816 |
| JN22B-40.5/31.5-400 | 400 | 340 | 1300 | 896 |
JN22-40.5/31.5
Series IndoorAC HighVoltage Earthing Switch
SPECIFICATION
JN22B-40.5/31.5 seriesindoorhighvoltage(HV) earthing switch absorbs advancednew technicalfrom domestic and abroad.ItconfirmstoGB1985-2004<ACHVDISCONNECTSWITCHANDEARTHSWITCH>standard.Andappliestothreephaseratedvoltage405kV,AC50/60Hzpowersystem.It cansupporttheuseofKYN61-405HVswitchpanelandother models,thefoundation isprotect theHVelectricequipmentswhenrepairor maintenance.
AMBIENTCONDITION
1.Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:dailyaveragehumidity \lesssim95% monthly \lesssim90%
4.Earthquake does not exceed degree8;
5.No fire,explosion,chemical erosion.
TECHNICALSPECIFICATION
| NO. | Item | Units | Parameters | ||
| 1 | Ratedvoltage | kV | 40.5 | ||
| 2 | Ratedshort-timewithstandcurrent | KA | 31.5 | ||
| 3 | Ratedcircuit-timemakingcurrent | KA | 80 | ||
| 4 | Ratedpeakwithstandcurrent | KA | 80 | ||
| 5 | Ratedshort-circuitduration | S | 300、350、400 | ||
| 6 | Rated insultinglevel | 1min.PFwithstandvoltage | kV | Toearth, 95 phasetophase | |
| Lightingimpulsewithstandvoltage | 185 | ||||
OVERALLDIMENSION
MOUNTINGCUTOUTFIGURE
| Model | E | G | L | D |
| JN22-40.5/31.5-280 | 280 | 290 | 1010 | 656 |
| JN22-40.5/31.5-300 | 300 | 340 | 1100 | 696 |
| JN22-40.5/31.5-350 | 350 | 340 | 1200 | 796 |
| JN22-40.5/31.5-360 | 360 | 320 | 1200 | 816 |
| JN22-40.5/31.5-400 | 400 | 340 | 1300 | 896 |
SPECIFICATION
Thisproductscanbeusedinindoorsystemof50Hzandratedvoltageof12KV,24kV,36KV.itcanbeusedtogetherwith otherswitchfacilitiessuchasloadingswitches,vacuumcontactors.Itcanprotectelectrictransformersandotherelectric facilitiesagainstoverloadorcircuitbreaker.lt isalsoanecessaryqeuipmentforhighvoltageswitchbox,circularcircuitcabinet high/lowvoltagetop-loadingtransformersubstation.
MODELIMPLICATION
TECHNICALSPECIFICATION
| Type | Counterpart | Rated voltage | Ratedcurrent ofthefuse(A) | Rated current ofthefuselink(A) |
| XRNT-12 | SDLAJ | 12 | 40 | 3.15、6.3、10、16、20、25、31.5、40 |
| XRNT-12 | SDLAJ | 12 | 100 | 50、63、71、80、100、(125) |
| XRNT-12 | SDLAJ | 12 | 125 | 125、160、200、250 |
| XRNT-24 | 24 | 200 | 3.15、6.3、10、16、20、25、31.5、40、50、 63、80、100、125、160、200 | |
| XRNT-40.5 | 40.5 | 125 | 80、100、125、160、2003.15、6.3、10、16、 20、25、31.5、40、50、63、 |
OVERALLDIMENSION
12KV-15KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) (BIL) | Impulse voltage withstand | Power frequency | Creepage distance | Weight (KG) (MM) | Dimension (CM) |
| RH-33 | 15 | 100 | 10000 | 100 | voltage 40 | 250 | 7.5 | 40×34.5 |
| RH-33 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 | ×11 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand (MM) | Creepage distance | Weight (KG) | Dimension (CM) |
| Rw10 | 15 | 100 | 10000 | 100 | voltage 40 | 250 | 7.5 | 48×34.5× |
| Rw10 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 | 11 |
| Item | Rated Rated voltage | current (A) | current (A) | Breaking Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RD-24 | (KV) 24 | 100 | 8000 | 150 | voltage 65 | 530 | 12 | 48×34.5× |
| RD-24 | 24 | 200 | 10000 | 150 | 65 | 530 | 12 | 14 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RH-C | 11 | 100 | 10000 | 110 | voltage 40 | 250 | 7.5 | 40×34.5 X11 |
| RH-C | 11 | 200 | 12000 | 110 | 40 | 250 | 7.5 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) (BIL) | Impulse voltage withstand | Power frequency | Creepage distance (MM) | Weight | Dimension (KG) (CM) |
| PD | 11 | 100 | 6000 | 110 | voltage 42 | 340 | 7.5 | 49×27 |
| PD | 11 | 200 | 8000 | 110 | 42 | 340 | 7.5 | X11.5 |
12KV-15KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| FSC-23 | 33 | 100 | 8000 | 170 | voltage 70 | 820 | 27.5 | 68×17 |
| FSC-23 | 33 | 200 | 10000 | 170 | 70 | 820 | 27.5 | X15 |
10KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW11 | 12 | 100 | 6300 | 100 | voltage 42 | 230 | 7.8 | 48×12× 31 |
| RW11 | 12 | 200 | 8000 | 110 | 42 | 230 | 7.8 |
10KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage withstand (BIL) | frequency | Power Creepage distance (MM) | Weight | Dimension (KG) (CM) |
| Rw10 | 15 | 100 | 10000 | 100 | voltage 40 | 250 | 7.5 | 48×34.5× |
| Rw10 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 | 11 |
10KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| Rw10-10F | 12 | 100 | 6300 | 110 | voltage 42 | 260 | 7.5 | 53×32× 12 |
| Rw10-10F | 12 | 200 | 8000 | 110 | 42 | 260 | 7.5 |
10KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW3 | 10 | 100 | 6300 | 100 | 42 | 230 | 6.2 | 48×27× 12 |
| RW3 | 10 | 200 | 8000 | 110 | 42 | 230 | 6.2 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| HRW3 | 12 | 100 | 6300 | 100 | voltage 42 | 380 | 8.8 | 61×13X |
| HRW3 | 12 | 200 | 8000 | 110 | 42 | 380 | 8.8 | 42 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| HPRWG2 | 12 | 100 | 6300 | 170 | 70 | 870 | 16 | 61×13× |
| HPRWG2 | 12 | 200 | 8000 | 170 | 70 | 870 | 16 | 42 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| HRW11 | 12 | 100 | 6300 | 100 | voltage 42 | 350 | 3.8 | 42×35× 11 |
| HRW11 | 12 | 200 | 8000 | 110 | 42 | 350 | 3.8 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| SHY5WS | 3 | 100 | 6300 | 100 | voltage 42 | 350 | 3.8 | 42×35× 11 |
| SHY5WS | 6 | 100 | 8000 | 110 | 42 | 350 | 3.8 | |
| SHY5WS | 10 | 150 | 6300 | 100 | 42 | 350 | 3.8 | |
| SHY5WS | 10 | 150 | 8000 | 110 | 42 | 350 | 3.8 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW7 | 10 | 100 | 6300 | 110 | voltage 42 | 230 | 6.2 | 48×27× |
| RW7 | 10 | 200 | 8000 | 110 | 42 | 230 | 6.2 | 12 |
COMPOSITECOAT METALOXIDESURGEARRESTERS
HYW-0.22\~0.66KV
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Lightning impulse current peak value(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value (kA) | Max.leaking current under 0.75DCref. voltage (uA) | |
| Low voltage | HY1.5W-0.28/1.3 | 0.25 | 0.22 | 0.24 | 0.6 | 1.30 | 50 | 25 | 50 | |
| HY1.5W-0.5/2.6 | 0.50 | 0.38 | 0.42 | 1.20 | 2.60 | |||||
| HY1.5W-0.8/3.9 | 0.8 | 0.66 | 0.72 | 1.80 | 3.90 |
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Capacitance | HY0.1W-14R | 1.4 | 1.14 | 1.20 | 2.6 | 9.45 | 6.85 | 3.85 | 250 | 40 | 50 |
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | impulse current | Lighting Operating impulse current | |||||||||
| Power distribution (S) | HY5WS-3.8/15 | 3.8 | 3 | 2.0 | 7.5 | 17.3 | 15.0 | 12.8 | 75 | 40 | 50 |
| HY5WS-5/15 | 5 | 3 | 4.0 | 7.5 | 17.3 | 15.0 | 12.8 | ||||
| HY5WS-7.6/30 | 7.6 | 6 | 4.0 | 15.0 | 34.6 | 30.0 | 25.6 | ||||
| HY5WS-10/30 | 10 | 6 | 8.0 | 15.0 | 34.6 | 30.0 | 25.6 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | |||
| Teep wave impulse current | impulse current | LightingOperating impulse current | ||||||||||
| Power station (Z) | HY5WZ-3.8/13.5 | 3.8 | 3 | 2.0 | 7.2 | 15.5 | 13.5 | 11.5 | 150 | 40 | 50 | |
| HY5WZ-5/13.5 | 5 | 3 | 4.0 | 7.2 | 15.5 | 13.5 | 11.5 | |||||
| HY5WZ-7.6/27 | 7.6 | 6 | 4.0 | 14.4 | 31.0 | 27.0 | 23.0 | |||||
| HY5WZ-10/327 | 10 | 6 | 8.0 | 14.4 | 31.0 | 27.0 | 23.0 | |||||
COMPOSITECOAT METALOXIDESURGEARRESTERS
HY5WS-10KV
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | impulse current | Lighting Operating impulse current | |||||||||
| Power distribution (S) | HY5WS-12.7/50 | 12.7 | 10 | 6.6 | 25 | 57.5 | 50 | 42.5 | 75 | 40 | 50 |
| HY5WS-16.5/50 | 16.5 | 10 | 12.7 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17/50 | 17 | 10 | 13.6 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17.5/50 | 17.5 | 10 | 13.6 | 25 | 57.5 | 50 42.5 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | HY5WZ-12.7/45 | 12.7 | 10 | 6.6 | 24 | 51.8 | 45 | 38.3 | 150 | 40 | 50 |
| HY5WZ-16.5/45 | 16.5 | 10 | 12.7 | 24 | 51.8 | 45 | 38.3 | ||||
| HY5WZ-17/45 | 17 | 10 | 13.6 | 24 | 51.8 | 45 | 38.3 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Electric rotating | HY2.5W-3.8(5)/9.5 | 3.8(5) | (kV) | 2.0(3.0) | than(kv) 5.7 | 10.7 | 9.5 | 7.6 | 40 | (μA) | |
| HY2.5W-7.6(8)19.0 | 7.6(8) | 4.0(6.3) | 11.2 | 21.0 | 19.0 | 15.0 | 200 | ||||
| The motor neutral point | HY1.5W-2.4/6 | 2.4 | 1.9 | 3.4 | 6.0 | 5.0 | 40 | 50 | |||
| HY1.5W-4.8/12 | 4.8 | 3.8 | 6.8 | 12.0 | 10.0 | ||||||
| Capacior (R) | HY5WR-3.8(5)/13.5 | 3.8(5) | 3 | 2.0(4.0) | 7.2 | 13.5 | 10.5 | 400 | 65 | ||
| HY5WR-7.6(10)/27.0 | 7.6(10) | 6 | 4.0(8.0) | 14.4 | 27.0 | 20.8 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref voltage (μA) | ||
| Teep wave impulse current | Lighting Operating impulse current | ||||||||||
| Capacitor (R) | HY5WR-12.7/45 | 12.7 | (kV) 10 | 6.6 | than(kv) 23.0 | impulse current | 400 | 65 | 50 | ||
| HY5WR-16.5/45 | 16.5 | 10 | 12.7 | 23.0 | 45.0 45.0 | 35.0 35.0 | |||||
| HY5WR-17/45 | 17 | 10 | 13.6 | 24 | 45.0 | 35.0 | |||||
| Electric rotating machinery | HY2.5W-12.7/31.0 | 12.7 | 10.5 | 18.9 | 34.7 | 31.0 | 25.0 | 200 | 40 | ||
| HY2.5W-17.5/40.0 | 14.5 | 13.8 | 24.4 | 44.8 | 40.0 | 32.0 | |||||
| HY2.5W-20.0/45.0 | 20.0 | 15.8 | 28.0 | 50.4 | 45.0 | 36.0 | |||||
COMPOSITECOAT METALOXIDESURGEARRESTERS
HY5W-3\~6KV
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power distribution (S) | HY5WS-3.8/15L | 3.8 | 3 | 2.0 | 7.5 | 17.3 | 15.0 | 12.8 | 75 | 40 | 50 |
| HY5WS-5/15L | 5 | 3 | 4.0 | 7.5 | 17.3 | 15.0 | 12.8 | ||||
| HY5WS-7.6/30L | 7.6 | 6 | 4.0 | 15.0 | 34.6 | 30.0 | 25.6 | ||||
| HY5WS-10/30L | 10 | 6 | 8.0 | 15.0 | 34.6 | 30.0 25.6 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | |||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | ||||||||||
| Povwer distribution (S) | HY5WS-12.7/50L | 12.7 | 10 | 6.6 | 25 | 57.5 | 50 | 42.5 | 75 | 40 | 50 | |
| HY5WS-16.5/50L | 16.5 | 10 | 12.7 | 25 | 57.5 | 50 | 42.5 | |||||
| HY5WS-17/50L | 17 | 10 | 13.6 | 25 | 57.5 | 50 | 42.5 | |||||
| HY5WS-17.5/50L | 17.5 | 10 | 13.6 | 25 | 57.5 | 50 | 42.5 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | |||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | ||||||||||
| Power station (Z) | HY5WZ-42/134 | 42 | (kV) 35 | 23 | than(kv) 73 | 154 | 134 | 114 | 150 | 65 | 50 | |
| HY5WZ-51/134 | 51 | 35 | 40.8 | 73 | 154 | 134 | 114 | |||||
| HY5WZ-52.7/134 | 52.7 | 35 | 40.8 | 73 | 154 | 134 | 114 | |||||
| HY5WZ-54/134 | 54 | 35 | 41 | 73 | 154 | 134 | 114 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | HY5W-75/215 | 75 | (kV) 66 | 60 | than(kv) 123 | 248 | 215 | 183 | 400 | 65 | 50 |
| HY5W-90/224 | 90 | 66 | 72.5 | 130 | 258 | 224 | 190 | ||||
| HY10W-75/250 | 75 | 66 | 60 | 127 | 288 | 250 | 213 190 | 600 | 100 | 50 | |
| HY10W-75/223 HY10W-75/230 | 75 75 | 66 66 | 60 | 127 | 256 265 | 223 | |||||
| 60 | 127 | 230 | 196 | ||||||||
| HY10W-90/224 HY10W-90/232 | 90 | 66 | 72.5 | 130 | 258 | 224 190 | |||||
| HY10W-90/235 | 90 90 | 66 66 | 72.5 72.5 | 130 130 | 266 232 270 235 | 198 201 | |||||
COMPOSITECOAT METALOXIDESURGEARRESTERS
YHW-110KV
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value (kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5W-100/260 | 100 | 110 | 78 | 145 | 299 | 260 | 221 | 400 | 65 | 50 |
| YH5W-102/266 | 102 | 110 | 79.6 | 148 | 305 | 266 | 226 | ||||
| YH5W-108/281 | 108 | 110 | 84 | 157 | 323 | 281 | 239 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (μA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH10W-100/260 | 100 | (kV) 110 | 78 | 145 | 291 | 260 | 221 | 600 | 100 | 50 |
| YH10W-102/266 | 102 | 110 | 79.6 | 148 | 297 | 266 | 226 | ||||
| YH10W-108/281 | 108 | 110 | 84 | 157 | 315 | 281 | 239 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (μA) | |||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | ||||||||||
| Power station (Z) | YH10W-200/520 | 200 | 220 | 156 | 290 | 582 | 520 | 442 | 600 | 100 | 50 | |
| YH10W-204/532 | 204 | 220 | 159 | 296 | 594 | 532 | 452 | |||||
| YH10W-216/562 | 216 | 220 | 168.5 | 314 | 630 | 562 | 478 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5WX1-51/134L | 51 | 35 | 40.8 | 73 | 154 | 134 | 114 | 400 | 100 | 50 |
| YH5WX1-54/142L | 54 | 35 | 43.2 | 77 | 163 | 142 | 121 | ||||
| YH5WX1-57/170L | 57 | 35 | 45.6 | 80 | 195 | 170 | 145 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref voltage (μA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5WX2-51/134L | 51 | 35 | 40.8 | than(kv) 73 | 154 | 134 | 114 | 400 | 100 | 50 |
| YH5WX2-54/142L | 54 | 35 | 43.2 | 77 | 163 | 142 | 121 | ||||
| YH5WX2-57/170L | 57 | 35 | 45.6 | 80 | 195 | 170 | 145 | ||||