FunctionsandFeatures
MiniatureCircuitBreakers
Normaloperationconditionsandinstallationfeatures
Anti-humidity(GB/T2423.4)
Benchmarkambienttemperature(℃)
Operatingambienttemperature(℃)
Applicablealtitudeheight(m)
Max.wiringcapacity(mm²)
Max.ultimatetorque(N▪m)
Incomingmethod
Mountingmethod
Pollutiondegree
Protectiondegree
28periodiccycles,RH:90-96%at55℃,RH:95-100%at25℃
30
-35°℃~+70℃
≤2000m
35
3.5
Top-in,Bottom-out
TH35-7.5standardrailmounting
2
IP20
Overcurrent protection characteristics
▪Trippingcharacteristics
Trip unit C type(li=8In) Dtype(li=12In) Initial State Tripping Time Expected Result
I1
I2
I4
I6
1.05In
1.3In
6.4In
9.6In
9.6In
14.4In
Coldchain
Instantly Following
above Experiment
Cold State
Cold State
t≤1h(In≤63A)
2h(In>63A)
t<1h(In≤63A)
t<2h(In>63A)
t≤0.2s
t<0.2s
No Tripping
Trip
No Tripping
Trip
Note:Thethermaltrippingcharacteristicsinthetablearetheexpectedresultsobtainedatatemperatureof30-35°C,if wired correctly and correspondently.Theproductisdebugged
accordinglywhenitleavesthefactory.Whentheconditionsaredifferent,theratedcurrentshouldbecompensatedaccordingly.
Thermaltrip
Magnetic trip
▪Instructions
Operating handle
Switch button
Manual and automatic switching dialing
Run status indicatorlight(Run)
Network communication light(Communicate)
Alarm/Lock Indicator(Lock)
50
FunctionsandFeatures
MiniatureCircuitBreakers
1.Operating handle:
push upward to close,push downward to open.
2.Switch button:
Click -open and close.If the switch is in locked state,you can press and hold 5 seconds to unlock.
3.Manual and automatic switching dialing:
4.Indicator status:
Run status indicator light (Run):If green light is always on then it means the circuit breaker is closed,if flashing,it means open.
Network communication light (Communicate):If bluelight is flashing then it means network pairing is in progress,if always on,it means
network communication is successful.Alarm/Lock Indicator (Lock):If redlight is flashingthen it is a product fault alarm,if always on when it’
s opening,it is a fault trip or it can be remotely controlled to lockout.
Outlinesanddimensions
1PN/2P
3PN/4P
51
FunctionsandFeatures
MiniatureCircuitBreakers
AC type circuit breaker wiring diagram
neutral wire
externally wired
L1
N
L1
N
L1
L2
L3
N
L1
L2
L3
N
1Pwiringdiagram 1PN/2Pwiringdiagram 3Pwiringdiagram 3PN/4wiringdiagram
1P/3P:neutral wire externally wired
RS 485 Communication Interface
neutral wire
externally wired
Port wiring diagram
DC type circuit breaker wiring diagram
Wiring diagram
LowerEntry
1PDC
LowerEntry
2PDC
UpperEntry
1PDC
UpperEntry
2PDC
load
load
1PExternalpositiveterminal
RS485Communicationinterface
52
FunctionsandFeatures
MiniatureCircuitBreakers
HUB9SL-80 IoT Earth Leakage Circuit Breaker
Standard:GB/T 16917.1CQC1149
Certifications:CCC
Product Overview
1.1Product overview
Application:office buildings,shopping malls,
home intelligent power management systems,
intelligent property management systems and etc.
1.2 Function:
Functionlistandaccuracy
Protection against
short circuit,overload,
overvoltage and undervoltage
Parameters like overload,short circuit,isolation,overvoltage,
undervoltage,phase loss,overtemperature,power limit,electricity
consumption limit,threshold,delay time,shutdown,alarm and trip are
adjustable to meet different requirements.
ElectromagnetictypeB(3-5In),C(5-10In),D(10-16In)
Thermalmagnetictype;ComplywithGB/T14048.2,CQC1148;Parameters
canbeadjustedtomaketheMCBelectronictype.)
1.1Ue~1.4Ue(parameterforovervoltageisadjustable)
06Ue~0.9Ue(parameterforundervoltageisadjustable)
Metering
Parameterslikevoltage,temperature,power,powerfactor,electricity
consumption,andfrequencyaremeasurable.
Accuracy Measuring
voltage accuracy :Class 0.5,
current accuracy:Class 0.5
power accuracy :Class 2.0
electricity consumption accuracy :Class 1.
Temperature 85℃(adjustable),accuracy±2℃
Control
Multiple Control Ways:Manual and automatic integrated control,automatic
button control,manual push rod control ,mobile phone remote control
Communication
Multiple Communication Ways:It supports RS485/Bluetooth/WiFi in the downlink
and WiFi/4G/RJ45 in the uplink.Makingreal-time viewing of parameters possible,
including current,voltage,power,powerfactor,electricity consumption,leakage,
frequency and etc.It also provides realtime alarm push.
other
The circuit breaker has built-in coils,bi-metal and other physical protection devices.
Even when the digital chip fails, the circuit breaker can still achieve basic safety
protection functions such as short circuit protection and overload protection.
53
FunctionsandFeatures
MiniatureCircuitBreakers
Model description
HUB9SL 80 Z
No Description:AC MCB
Z:AC and DC
HUB9SL 80
□
No Description:6KA
H:10KA
Main technical data
Standard
Productmodel
Certificate
Electricalcharacteristics
Numberofpoles
Ratedcurrent(A)
Ratedvoltage(V)
Ratedfrequency(Hz)
Residualcurrenttype
RatedresidualoperatingcurrentlΔn(mA)
Ratedshort-circuitbreakingcapacitylcu(A)
Operatingshort-circuitbreakingcapacityIcs(A)
Remoteautomaticclosingtime(tc)
Automaticdisconnecttime(to)
Power-ondelaytime(td)
RatedimpulsewithstandvoltageUimp(1.2/50)(kV)
Electricallife(times)
Mechanicallife(times)
HUB9SL-80
GB/T16917.1、CQC1149
CCC
1P+N、2P、3P+N、4P
1A、2A、3A、4A、6A、10A、16A、20A、25A、32A、40A、50A、63A、80A
AC220V、AC230V、AC240V(1P+N、2P),
AC380、AC400V、AC415V(3P+N、4P)
50
TypeAC
30mA(10mA~1000mAadjusttable)
6kA(HUB9SL-80),10kA(HUB9SL-80H)
6kA(HUB9SL-80),7.5kA(HUB9SL-80H)
tc≤3s
to≤2s
td≤4soruserdefined
6kV
>10000
>20000
■
■
■
-
-
-
Thermalmagnetic
tripping
characteristics
Framesize Currenttype Breakingcapacity
B(3In-5In)
C(5ln~10ln)
D(10In~20In)
C(6.4In~9.6ln)
Regular(8In~12ln)
D(9.6In~14.4In)
Modelnumber
54
FunctionsandFeatures
MiniatureCircuitBreakers
Normaloperationconditionsandinstallationfeatures
Anti-humidity(GB/T2423.4)
Benchmarkambienttemperature(℃)
Operatingambienttemperature(℃)
Storageambienttemperature(℃)
Applicablealtitudeheight(m)
Max.wiringcapacity(mm²)
Max.ultimatetorque(N▪m)
Incomingmethod
Mountingmethod
Pollutiondegree
Protectiondegree
28periodiccycles,RH:90-96%at55℃,RH:95-100%at25℃
30
-35~+70℃
-35~+85℃
≤2000m
35
3.5
Top-in,Bottom-out
TH35-7.5standardrailmounting
2
IP20
Overcurrent protection characteristics
▪Trippingcharacteristics
Trip unit C type Dtype Initial State Tripping Time Expected Result
I1
I2
I4
I6
1.13In
1.45In
5In
10In
10In
16In
Coldchain
Instantly Following
above Experiment
Cold State
Cold State
t≤1h(In≤63A)
2h(In>63A)
t<1h(In≤63A)
t<2h(In>63A)
t≤0.2s
t<0.2s
No Tripping
Trip
No Tripping
Trip
Note:Thethermaltrippingcharacteristicsinthetablearetheexpectedresultsobtainedatatemperatureof30-35°C,if wired correctly and correspondently.Theproductisdebugged
accordinglywhenitleavesthefactory.Whentheconditionsaredifferent,theratedcurrentshouldbecompensatedaccordingly.
Theproducthasthreestates:closed,open,andlocked(In this case,theoperatinghandlecannotbeclosedanymore)
Thermaltrip
Magnetic trip
▪Circuit breaker switch button,indicator light status,manual and automatic mode instructions
B type
3In
5In
Operating handle
Switch button
Manual and automatic switching dialing
Run status indicatorlight(Run)
Leakageselftestbutton
Alarm Indicator(Alarm)
Locking indicator
55
FunctionsandFeatures
MiniatureCircuitBreakers
1.Operating handle:
push upward to close,push downward to open.
2.Switch button:
Click-open and close.If the switch is in locked state,you can press and hold 5 seconds to unlock.
3.Manual and automatic switching dialing:
By dialing up and down,the circuit breaker switches between local manual mode and remote automatic mode.
Local manual mode:You can open and close the circuit breaker locally through the operating handle or switch button; you cannot control
the closing of the circuit breaker remotely,but you can control the opening of the circuit breaker and open it to the locked state.In the
locked state,you cannot manually close the circuit breaker,at the same time,it enters the maintenance state.After the maintenance,
if you need to manually close the circuit breaker,press and hold the switch button for 5 seconds to unlock it.Then you can manually close
or remotely close the circuit breaker.
Remote automatic mode:You can open and close the circuit breaker directly through the operating handle or switch button locally:You
can remotely control the closing and opening of the circuit breaker,and open it to the locked state.In the locked state,you cannot manually
close the circuit breaker.When closing the circuit breaker,press and hold the switch button for 5 seconds to unlock it,and then you can
manually open and close the circuit breaker.
4.Indicator status:
Run status indicator light(Run):If green light is always on then it means the circuit breaker is closed,if flashing,it means open.
Network communication light(Communicate):If bluelight is flashing then it means network pairing is in progress,if always on,it means
network communication is successful.Alarm/Lock Indicator(Lock):If redlight is flashingthen it is a product fault alarm,if always on when it’
s opening,it is a fault trip or it can be remotely controlled to lockout.
5. Leakage test button
It is used for self-test of leakage protection.The circuit breaker trips instantly after pressing the button.The handle automatically closes 5
seconds after the test is completed.
Outlinesanddimensions
1PN/2P
3PN/4P
56
FunctionsandFeatures
MiniatureCircuitBreakers
▪Circuitbreakerwiringdiagram
Wiring diagram
L1
N
L1
L2
L3
N
1PN/2Pwiring diagram 3PN/2P wiring diagram Port wiring diagram
RS 485 Communication
Interface
57
FunctionsandFeatures
MiniatureCircuitBreakers
NT50 Series,
Residual Current Circuit Breaker with Overcurrent Protection
Standard:IEC 60898-1IEC 61008-1
Product Overview
1.1Application
Residential electrical systems or similar power distribution premises
1.2 Function:
-Overload protection-Short circuit protection
-Isolation function-Leakage protection
Model description
NT50
NT50
□ □ □ □
No Description:No Cover 2P
K:With Cover
□
1E:
One Way OverloadProtection
2E:
Two Way OverloadProtection
□ / 2P
Prouduct cover Number of Poles Typeofoverloadprotecion
Modelnumber
58
□
No Description:No Light
D:With LED Light
LEDindicator
NoDescription:
NoOverloadProtection
S:OverloadandInstantaneous
Trippingprotection
No Description:White
B:Black
Rated Current Typeofprotecion
6、10、16、20、
25、32、40
Leakageprotection Color
None: Noleakageprotection
L: Withleakageprotection
FunctionsandFeatures
MiniatureCircuitBreakers
Main technical data
Standard
Productmodel
Electricalcharacteristics
Numberofpoles
Ratedcurrent(A)
Ratedvoltage(V)
Ratedfrequency(Hz)
Residualcurrenttype
Ratedshort-circuitbreakingcapacitylc(A)
RatedresidualoperatingcurrentlΔn(mA)
RatedimpulsewithstandvoltageUimp(1.2/50)(kV)
Mechanicallife(times)
Electricallife(times)
NT50
IEC60898-1,IEC61008-1
2P1E、2P2E
5A、10A、15A、20A、25A、30A、40A
AC230V
50/60
TypeAC
1500
30
2.5
-
-
-
■
■
-
-
-
Thermalmagnetic
tripping
characteristics
B(3In-5In)
C(5ln~10ln)
D(10In~20In)
C(6.4In~9.6ln)
Regular(8In~12ln)
D(9.6In~14.4In)
Normaloperationconditionsandinstallationfeatures
Anti-humidity(GB/T2423.4)
Benchmarkambienttemperature(℃)
Operatingambienttemperature(℃)
Storageambienttemperature(℃)
Applicablealtitudeheight(m)
Max.wiringcapacity(mm²)
Max.ultimatetorque(N▪m)
Incomingmethod
Pollutiondegree
28periodiccycles,RH:90-96%at55℃,RH:95-100%at25℃
30
-35~+70
-35~+85
≤2000m
10
2
Top-in,Bottom-out
2
IP20
-
Protectiondegree
Directmounting
Mountedinthe distributionbox
59
FunctionsandFeatures
MiniatureCircuitBreakers
Outlinesanddimensions
Nt50(Without Leakage Protection)
NT50(With Leakage Protection)
60
FunctionsandFeatures
MiniatureCircuitBreakers
HYU3Series surge protection devices
Standard:IEC 61643-1/Ⅱ
Product Overview
1.1Application:
Home electrical systems,distribution systems in commercial buildings,
industrial control systems,communication base stations,and data centers,etc
1.2 Function:
Prevent transient surge voltage caused by lightning strikes or switch operations,
limit transient overvoltage and discharge surge current.
HYU3
HYU3 15〜160kA
□
Test type
□ □ □
ClassⅠ+Ⅱ
ClassⅡ
Model description
Maximumcontinuous
operatingvoltage
NumberofPoles
385/440V 1P、1N、2P
3P、3N、4P
/ /
Main technical data
385
2.0
385
20
40
15
Experimentalcategory
Model
Index
Voltageprotectionlevel Up(kV)
Ⅰ+Ⅱ Ⅱ
440
2.0
440
20
40
15
15kA 25kA
385
2.3
385
30
60
25
440
2.3
440
30
60
25
HYSCB3-I15 HYSCB3-I25
multistrandhardwire 4mm2〜25mm2
385V
1.5
385
10
20
-
440V
1.7
440
10
20
-
20kA 40kA
385V
1.8
385
20
40
-
440V
2.0
440
20
40
-
65kA 80kA 100kA 120kA 160kA
385V
2.0
385
30
65
-
385V
2.2
385
40
80
-
385V
2.4
385
50
100
-
385V
2.4
385
60
120
-
385V
3.0
385
80
160
-
440V
2.2
440
30
65
-
440V
2.4
440
40
80
-
440V
2.5
440
50
100
-
440V
2.7
440
60
120
-
440V
3.0
440
80
160
-
<25
HYSCB3-II20 HYSCB3-II40 HYSCB3-II65 HYSCB3-II80HYSCB3-II100HYSCB3-II120HYSCB3-II160
Maximumcontinuous
operatingvoltageUc(V〜)
NominaldischargecurrentIn
(8/20μs)kA
Maximumdischarge
currentImax(8/20μs)kA
Impulsedischarge
currentIimp(10/350μs)kA
Responsetime ta(ns)
Correspondingbackupprotection
periodspecifications
Terminalwiringcapability
Maximum discharge current
/Impulse current
Modelnumber
61
FunctionsandFeatures
MiniatureCircuitBreakers
Outlinesanddimensions
62
FunctionsandFeatures
MiniatureCircuitBreakers
HYSCB3series surge protection devices
Standard:NB/T 42150
Product Overview
1.1Application:
Power systems in industrial plants,data centers,
low-voltage power systems in buildings
1.2 Function:
-Overload protection
-Selective disconnection:distinguish power frequency current and lightning current and respond accordingly
-Lightning current withstand and short-circuit current breaking
-SPD fire protection
HYSCB3
HYSCB3 20〜160kA
□
Test type
□ □ □
Class I
ClassⅡ
Model description
Maximum discharge current
/Impulse current
NumberofPoles Rated short-circuit
breaking capability
1P、2P、3P、4P 65KA、100KA
/ /
Main technical data
15
20
/
15
Ratedultimatebreakingcapacity(kA)
Testtype
NominaldischargecurrentIn(kA)
MaximumdischargecurrentImax(kA)
Impulsedischargecurrent Iimp(kA)
Rated working voltageUe
Minimum delay action currentId
Minimum instantaneous action currentIi
Mechanical lifespan
Shell protection level
Wiringscrews
Wiringability
InstallationDINrail
Ratedoperatingfrequencyf/Hz
HYSCB3-II
25
30
/
25
HYSCB3-I
65kA、100kA
T1(10/350μs)
20
10kA
20kA
/
40
20kA
40kA
/
65
30kA
65kA
/
80
40kA
80kA
/
100
50kA
100kA
/
120
60kA
120kA
/
160
80kA
150kA
/
65kA、100kA
T2(8/20μs)
AC230V(1P);AC230V/400V(2P、3P、4P)
3±1A
6A
4000
IP20
M5torque 2.5N.m
2.5mm2〜25mm2
EN60715(35mm)
50Hz
Model
Modelnumber
63
FunctionsandFeatures
MiniatureCircuitBreakers
Outlinesanddimensions
64
RemoteSignalingAuxiliaryPiece
OutlineDimensionsofBackupProtectorwithRemoteSignaling
FunctionsandFeatures
MiniatureCircuitBreakers
DZ47series Miniaturecircuitbreaker
Standard:GB10963.1
Product Overview
Application:
DZ47
B
C
D
DZ47
□ □ □
Model description
Trippingcurvetype Ratedcurrent(A)
1、2、3、4、6
10、16、20、25
32、40、50、63
/
Main technical data
Modelnumber
TheDZ47-63seriesminiaturecircuitbreaker(hereinafterreferredtoasthe\"breaker\")
ismainlysuitableforpowerlineinstallationsandelectricalequipmentinbuildings
andsimilarplaces,operatingatAC50Hzwitharatedvoltageupto400Vandarated
workingcurrentupto63A,providingovercurrentprotection.Itisalsoapplicablefor
infrequentswitchingoperations.
Thisbreaker complies withthe standardGB10963.1:Electrical accessories—Circuit
breakersforovercurrentprotectionforhouseholdandsimilarinstallations—Part1:
CircuitbreakersforACoperation.
NumberofPoles
1P、2P、3P、4P
FrameclassratedcurrentInm:63A
RatedvoltageUe:50HzAC230V/400V(1P),AC400V(2P,3P,4P),RatedcurrentIn:B,C,Dtypes:1~63A
RatedbreakingcapacityIcn:6000A(≤40A)、4500A(50Aand63A)
Poles:1P,2P,3P,4P
Lifespan:
Mechanical:20,000cycles
Electrical:4,000cycles
ProductFeatures
TrippingUnits:
Thermaltrip
Magnetictrip
min sec
35±0.5 80 45±0.31
65
FunctionsandFeatures
MiniatureCircuitBreakers
Outlinesanddimensions
TestCurrent(A)
1.13In
1.45In
3In
5In
10In
20In
TypeB
√
√
√
√
×
×
TypeC
√
√
√
√
√
×
TypeD
√
√
√
√
√
√
TrippingTime
≤1h
<1h
≤0.1s
<0.1s
<0.1s
<0.1s
ExpectedResult
Notrip
Trip
Notrip
Trip
Trip
Trip
Notes
Coldstate
Thermal
Hotstate
Note:Thermaltrippingcharacteristicsarebasedonambienttemperature30‒35℃andwireconnectionsasperTable4.
Adjustmentsshouldbemadefordifferentoperatingconditions.
TrippingCharacteristiccurvediagram
I1 I2
I3
B C D
I4
I5
I4
I5
I4
I5
300
60
10
1
10
1
0.1
0.01
min
X In
sec t
1 2 3 4 5 7 10 20
35±0.5
5.5
36max
80
18max 54max 72max
1P 2P 3P 4P
78max
45±0.31
37
60
2
66
Remoteindicationaccessories
Trippingaccessories
OFauxiliarycontact
-Externalcircuit,indicatingthecircuitbreaker'sON/OFFstatus
-Basictypeofauxiliarycontact:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
SDalarmcontact
-Sendsignalsoffaulttrippingofthecircuitbreaker
-Withmechanicalindicationavailableonthefrontpanel,toindicatefaulttripping
-Basictypeofauxiliarycontact:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
MX+OFshuntrelease
-Externalcircuit,indicatingthecircuitbreaker'sON/OFFstatus
-Thecircuitbreakerforusewiththereleasewillbetriggeredtotripuponreceivingasignal
-Basictypeofauxiliarycontact:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
MVover-voltagerelease
-Providelineprotectionduetoover-voltagefault
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesatbothendsof
thereleaseerisetotheratedvoltagerange
- Withfaulttrippingindicationavailableonthefrontpanel,toindicateanover-voltage trippingwith
theindicatorpoppedup
-Ratedoperatingtrippingover-voltage:(280±14)VAC
-Wiringcapacity:1-2.5mm²wire
MNunder-voltagerelease
-Providelineprotectionduetounder-voltagefault
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesatbothendsof
thereleaseedroptotheratedvoltagerange
-Withfaulttrippingindicationavailableonthefrontpanel,toindicateunder-voltagetrippingwiththe
indicatorpoppedup
-Ratedoperatingtrippingunder-voltage:(161±8.05)VAC
-Under-voltageprotectionrange:(35%〜70%)ofUe
-Wiringcapacity:1-2.5mm²wire
MVMNover/under-voltagerelease
-Providelineprotectionduetoover-voltageandunder-voltagefault
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesat bothendsof
thereleaseeriseordroptotheratedrange
- Withfaulttrippingindicationavailableonthefrontpanel,toindicateover-voltageorunder-voltage
trippingwiththeindicatorpoppedup
-Ratedoperatingtrippingover-voltage:(280±14)VAC
-Ratedoperatingtrippingunder-voltage:(161±8.05)VAC
-Under-voltageprotectionrange:(35%〜70%)ofUe
-Wiringcapacity:1-2.5mm²wire
MNsloss-voltagerelease
Accessories
EXB3accessories(63framesize)
67
Accessories
EXB3accessories(63framesize)
5 4 3 2 1
6
1、Accessoriescanbeassembledtobreakerleftsidebytool-free.
2、Thetotalmountingwidthiswithin54mm,includingOF,SD(3max.)+MO,MNs,MV,MN,MVMN(2max.)+MCBfromlefttoright.
1、Basicdeviceofthecircuitbreaker
2、MVMNover/under-voltagerelease,MNsloss-
voltagerelease,MNunder-voltagereleaseand
3、MX+OFshuntrelease
4、OFauxiliarycontact
5、SDalarmcontact
6、Combbusbar
Accessorymountingdiagram
Mountinginstruction
MVover-voltagerelease
68
OFauxiliarycontact
-Externalcircuit,indicatingthecircuitbreaker'sON/OFFstatus
-Basictypeofauxiliarycontacts:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
SDalarmcontact
-Sendsignalsoffaulttrippingofthecircuitbreaker
-Withmechanicalindicationavailableonthefrontpanel,toindicatefaulttripping
-Basictypeofauxiliarycontacts:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
MX+OFshuntrelease
-Externalcircuit,indicatingthecircuitbreaker'sON/OFFstatus
-Thecircuitbreakerforusewiththereleasewillbetriggeredtotripuponreceivingasignal
-Basictypeofauxiliarycontacts:1NO/1NC
-Wiringcapacity:1-2.5mm²wire
MVover-voltagerelease
-Offerlineprotectionincaseofover-voltagefaults
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesatbothendsof
thereleaseerisetotheratedvoltagerange
- Withfaulttrippingindicationavailableonthefrontpanel,toindicateanover-voltagetrippingwith
theindicatorpoppedup
-Ratedoperatingtrippingover-voltage:(280±14)VAC
-Wiringcapacity:1-2.5mm²wire
MNunder-voltagerelease
-Offerlineprotectionincaseofunder-voltagefaults
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesatbothendsof
thereleaseedroptotheratedvoltagerange
- Withfaulttrippingindicationavailableonthefrontpanel,toindicateanunder-voltagetrippingwith
theindicatorpoppedup
-Ratedoperatingtrippingunder-voltage:(161±8.05)VAC
-Under-voltageprotectionrange:(35%〜70%)ofUe
-Wiringcapacity:1-2.5mm²wire
MVMNover/under-voltagerelease
-Offerlineprotectionincaseofover-voltageandunder-voltagefaults
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthevoltagesatbothendsof
thereleaseeriseordroptotheratedvoltagerange
- Withfaulttrippingindicationavailableonthefrontpanel,toindicateover-voltageorundervoltage
trippingwiththeindicatorpoppedup
-Ratedoperatingtrippingover-voltage:(280±14)VAC
-Ratedoperatingtrippingunder-voltage:(161±8.05)VAC
-Under-voltageprotectionrange:(35%〜70%)ofUe
-Wiringcapacity:1-2.5mm²wire
MNsloss-voltagerelease
- Thecircuitbreakerforusewiththereleasewillbetriggeredtotripwhenthepowersupplyvoltage
dropstotheratedvoltagerange,toachieveloss-voltag protection
-Ensurethecircuitbreakertoclosenormallywhenthepowersupplyvoltagereturnstonormal
- Preventthecircuitbreakerfromre-closingwhenthepower supplyvoltageis zeroordropstothe
ratedvoltagerange
- With fault tripping indication available on the front panel, to indicate loss-voltag tripping when
poppedup
- Rated operating tripping loss-voltag: (161±8.05) V AC, with loss-voltag protection range of
(35%〜70%)ofUe
-Normalrecoveryvoltage:≥85%Ue,withloss-voltageprotectionrange<35%Ue
-Wiringcapacity:1-2.5mm²wire
Remoteindicationaccessories
Trippingaccessories
Accessories
EXB3accessories(125framesize)
69
Accessories
EXB3accessories(125framesize)
1、Circuitbreaker
2、MVMNover/under-voltagerelease,MNsloss-voltagerelease,MNunder-voltagereleaseandMVover-voltagerelease
3、MX+OFshuntrelease
4、OFauxiliarycontact
5、SDalarmcontact
1、OFandSDaremountedontheleftsideofthecircuitbreaker,andonlyoneaccessorycanbemountedontheleftsideofeach
2、MX+OF,MV,MN,andMVMNaremountedontherightsideofthecircuitbreaker,andonlyoneaccessorycanbemountedonthe
3、AccessoriescannotbemountedontherightsideofEXB3LE-125residualcurrentproducts
4、AccessoriescanbemountedtoEXB3-125andEXB3LE-125seriescircuitbreakers
5、Theaboveaccessoriescannotbeorderedseparately;theyneedtobemountedontothecircuitbreakerbeforedeliveryfromthefactory
1
1
4 5 3 2
4 5
circuitbreaker
rightsideofeachcircuitbreaker
Accessorymountingdiagram
Mountinginstruction
70
▪ TemperaturecorrectiontableofEXB3-63
▪ TemperaturecorrectiontableofEXB3-125H
Accessories
Temperature correction table
▪ TemperaturecorrectiontableofEXB3-63H
1-6
10-25
32-40
50-63
RatedcurrentcorrectionvalueA
RatedcurrentA
-35℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1.28
1.27
1.27
1.28
1.25
1.24
1.24
1.25
1.18
1.19
1.19
1.18
1.13
1.13
1.13
1.13
1.08
1.07
1.08
1.08
1.03
1.02
1.04
1.03
1
1
1
1
0.96
0.96
0.97
0.96
0.91
0.91
0.92
0.91
0.87
0.87
0.88
0.87
0.82
0.82
0.83
0.82
▪ TemperaturecorrectiontableofEXB3LY-63
1-6
10-25
32-40
50-63
RatedcurrentcorrectionvalueA
RatedcurrentA
-35℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1.28
1.27
1.27
1.28
1.25
1.24
1.24
1.25
1.18
1.19
1.19
1.18
1.13
1.13
1.13
1.13
1.08
1.07
1.08
1.08
1.03
1.02
1.04
1.03
1
1
1
1
0.96
0.96
0.97
0.96
0.91
0.91
0.92
0.91
0.87
0.87
0.88
0.87
0.82
0.82
0.83
0.82
63
80
100
125
RatedcurrentcorrectionvalueA
RatedcurrentA
-40℃
1.31
1.31
1.31
1.31
-20℃
1.25
1.25
1.25
1.25
-10℃
1.2
1.2
1.2
1.2
0℃
1.15
1.15
1.15
1.15
10℃
1.11
1.11
1.11
1.11
20℃
1.05
1.05
1.05
1.05
30℃
1
1
1
1
40℃
0.94
0.94
0.94
0.94
50℃
0.88
0.88
0.88
0.88
60℃
0.82
0.82
0.82
0.82
70℃
0.75
0.75
0.75
0.75
-30℃
1.29
1.29
1.29
1.29
6
10-25
32-40
50-63
RatedcurrentcorrectionvalueA
RatedcurrentA
-35℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1.45
1.27
1.27
1.26
1.4
1.24
1.24
1.25
1.3
1.19
1.19
1.18
1.23
1.13
1.13
1.13
1.15
1.08
1.08
1.08
1.08
1.04
1.04
1.03
1
1
1
1
0.98
0.98
0.97
0.95
0.96
0.95
0.92
0.9
0.93
0.92
0.89
0.86
0.91
0.89
0.87
0.84
Temperaturecorrectiontable
71
Accessories
▪ TemperaturecorrectiontableofEXB3LE-63
▪ TemperaturecorrectiontableofEXB3LE-125
Temperature correction table
▪ TemperaturecorrectiontableofEXB3LE-63H
6
10-25
32-40
50-63
RatedcurrentcorrectionvalueA
RatedcurrentA
-35℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1.45
1.27
1.27
1.26
1.4
1.24
1.24
1.25
1.3
1.19
1.19
1.18
1.23
1.13
1.13
1.13
1.15
1.08
1.08
1.08
1.08
1.04
1.04
1.03
1
1
1
1
0.98
0.98
0.97
0.95
0.96
0.95
0.92
0.9
0.93
0.92
0.89
0.86
0.91
0.89
0.87
0.84
63
80
100
125
RatedcurrentcorrectionvalueA
RatedcurrentA
-40℃
1.31
1.31
1.31
1.31
-20℃
1.25
1.25
1.25
1.25
-10℃
1.2
1.2
1.2
1.2
0℃
1.15
1.15
1.15
1.15
10℃
1.11
1.11
1.11
1.11
20℃
1.05
1.05
1.05
1.05
30℃
1
1
1
1
40℃
0.94
0.94
0.94
0.94
50℃
0.88
0.88
0.88
0.88
60℃
0.82
0.82
0.82
0.82
70℃
0.75
0.75
0.75
0.75
-30℃
1.29
1.29
1.29
1.29
6
10-25
32-40
50-63
RatedcurrentcorrectionvalueA
RatedcurrentA
-35℃ -20℃ -10℃ 0℃ 10℃ 20℃ 30℃ 40℃ 50℃ 60℃ 70℃
1.45
1.27
1.27
1.26
1.4
1.24
1.24
1.25
1.3
1.19
1.19
1.18
1.23
1.13
1.13
1.13
1.15
1.08
1.08
1.08
1.08
1.04
1.04
1.03
1
1
1
1
0.98
0.98
0.97
0.95
0.96
0.95
0.92
0.9
0.93
0.92
0.89
0.86
0.91
0.89
0.87
0.84
72