49
EN
5. M313-A Keypad
Key Name Function
<<
In home display, press to switch the physical variables shown
for monitoring; In parameter number selection, press to
switch the digit place of the parameter number to be
modified; In parameter value modification, press to switch the
digit place of parameter value to be modified
STOP Press to control the product stop when product is in Local
Mode or reset the fault (if there is alarm)
DSP Press to enter the menu for parameter setup or exit the menu
ENTER/Potential
meter
1. Press to confirm the parameter number selection and enter
the parameter value displaying/modification, or press to
confirm the parameter value and back to the Parameter
number selection menu.
2. Turn the potential meter to change the reference in home
display of local mode, or to adjust the parameter number or
to adjust the parameter value in parameter setup
RUN Press to run the motor when product is in Local Mode.
The product can be set by P06.31 to two different running modes: Local Mode
and Remote Mode.
⚫ Local Mode: The product is controlled by keypad, including start/stop
and target frequency set etc.
⚫ Remote Mode: The product is controlled by I/O terminals or
communication Bus, keypad is only for monitoring and parameter
setup.
50
EN
Description of the lights on keypad
⚫ L/R Light: To indicate the mode of the product, Always On --- Remote
Mode, Flashing --- Local Mode.
⚫ FWD、REV Lights:
FWD REV Status
On Off Running in Forward Direction
Off On Running in Reverse Direction
Off Off Stopped
LED lights of “Hz”, “A”: Used to indicate the physical meaning of the values shown
on the key pad, please refer to the UM .The five digits LED display can show the
reference frequency, parameter number or value, alarm/warning code etc.
Keyboard External Lead Hole Dimensions
6. M313-A Basic Application Guide
6.1 Control with Keypad
1) Ensure the product is working in Local Mode (L/R light flashing), or set
P06.31=1 to switch to Local Mode.
2) Adjust the set frequency by turning the potential meter.
3) Press the “RUN” key to start the motor, and adjust the motor speed by
turning the potential meter.
4) Press the “STOP” key to stop the motor.
Note: In Local Mode, the product only receives commands from the keypad.
Normally Local Mode is for system debugging.
6.2 Control with Terminals
1) Ensure the product is working in Remote Mode (L/R light always ON). If not,
switch the product to the Remote Mode by set P06.31=0. The product is
default in Remote Mode.
51
EN
2) Control in default parameter setup: In default, the digital input terminal
named as “S1” is set to function of start/stop (P02.05=10), the digital input
terminal named as “S2” is set to function of reverse run (P02.06=12), and
the main set value source is set to AI1 terminal (P00.11 = 1), and the AI1
terminal is set as analogue voltage input (P03.00=0). In the default
parameter setup, you can start the motor forward direction by enabling the
signal to terminal “S1” (short circuit the “S1” terminal to “COM”) and stop
the motor by disconnecting the terminal “S1” from terminal “COM”. You can
start the motor reverse direction by connecting the terminal “S2” to “COM”
and stop the motor by disconnecting the terminal “S2” from terminal
“COM”. You can change the motor speed by adjusting the voltage on
terminal AI1.
3) Control with Preset multi-stage value: Based on the default parameter
setup, you need to change the main set value source to preset multi-stage
value (P00.11=11) and keep the function of terminals “S3”~“S5” as default
(P02.07~P02.10 = 22~24), and set the preset values in parameters
P00.30~P00.4 to the speeds you expect. Then you can change the motor
speed to preset value by changing the logic status of terminals “S3” ~ “S5”.
6.3 Reset the Faults (Alarms)
For non-locked faults, press “STOP” key to reset the fault.
For locked faults:
If parameter P05.30 = 0, press “STOP” to reset the fault;
If parameter P05.30 =1, you need to power down and power on first, then press
“STOP” key to reset the fault.
You can also set a digital input terminal function to reset fault (set one of the
parameters from P02.05 to P02.09 equals 1), and use digital input signal to reset
the fault.
6.4 Motor Parameters Auto Tuning
Correct motor parameters help to ensure the control performance. Motor
parameter auto tuning function can identify the motor parameters (parameters
from P01.14 to P01.27) automatically. If you did not run the motor parameter
auto tuning operation, the control will use default motor parameters or use the
parameters you set manually.
6.5 Motor Parameters Auto Tuning
Correct motor parameters help to ensure the control performance. Motor
parameter auto tuning function can identify the motor parameters (parameters
from P01.14 to P01.27) automatically. If you did not run the motor parameter
52
EN
auto tuning operation, the control will use default motor parameters or use the
parameters you set manually.
1) Ensure the motor is standstill
2) Set Parameters from P01.02 to P01.07 as the nameplate of the motor
3) Set parameter P01.13 to value 1 or 2 or 3 or 4 or 5 depending on your
demands (Refer to description of parameter P01.13 in 3.3.2). After you
confirm the parameter P01.13 value, the keypad will show “PUSH” “RUN”.
Then press the “RUN” key, the product starts the motor parameter auto
tuning function
4) Wait the until the keypad shows “PUSH” “Ent”, then press the “ENTER” key.
The motor parameter auto tuning function finished and the motor
parameters are updated.
7. Fault Handling
Warning Alarm Error Fault Name Reason
Description
Suggested Handling
A.01 Factory Reset
Parameters reset
to factory
defaults without
confirmation
Press \"STOP “key to
Confirm
A.02* Internal Fault
Contact our local
support
u.03 A.03*
Motor control /
IO
communicatio
n time out
Motor control
board Failed to
communicate
with IO board
1. Power off, then
confirm the
installation of IO
board
2. Contact our local
support
A.04*
Power Board
24V Error
Internal
Hardware fault
1. Confirm no
problem in external
load to 24v
2. Contact our local
support
A05*
Gate drive
voltage fault
Internal
Hardware fault
u.07 A.07* Fan Fault
Too much dust
on the fan or the
fan is aged
Clean or replace the
fan
A.16* Short Circuit
Short circuit
between phases
of motor
Check the motor
cable and motor
insulation status
u.17 A.17* Earth fault
Flashover or
short circuit
between output
phases and
1. Check cable or
motor phase to
ground insulation
status
53
EN
Warning Alarm Error Fault Name Reason
Description
Suggested Handling
ground
2.Replace cable or
motor
u.19 A.19*
Brake resistor
short circuit
Brake resistor is
short circuit
(22kW and
below)
Check the wire of
brake resistor or
Replace Brake
resistor
u.20 A.20*
Brake transistor
short circuit
Brake transistor
is damaged
(22kW and
below)
Contact our local
support to repair
u.21 A.21* Brake Detect
Brake resistor is
not connected or
working.
Check the Brake
resistor or replace
suitable Brake
resistor
u.23 A.23
Over Current at
low voltage
Over current due
to that power
supply voltage
dips too much
Check the Power
supply
u.24 A.24 Under Voltage
Power supply
voltage dips too
much,
or high load to
too low power
supply voltage
Check the Power
supply
u.25 A.25
Overload at
low voltage
High load at
continuous low
power supply
voltage
Check the Power
supply
u.26 A.26*
Mains Phase
Loss
Missing phase on
supply side
Check the Power
supply
u.27 A.27 KEB fault
KEB function
triggered but
failed to hold the
DC voltage at
power supply
voltage drop,
due to too less
inertia or two
long time for
power supply
voltage drop.
1.Check the Power
supply
2.Set suitable KEB
Threshold voltage
54
EN
Warning Alarm Error Fault
Name
Reason Description Suggested Handling
A.28*
Motor
phase U
missing
1.motor phase
imbalance
2.motor cable
loose
Check the motor
phase cable and
motor.
A.29*
Motor
phase V
missing
A.30*
Motor
phase W
missing
u.36 A.36
Over
Voltage
1. The input
voltage is too high;
2. The motor works
in generator mode;
3. The deceleration
time is too short;
4. The braking unit
and braking
resistor are not
installed.
1. Check the power
supply
2. Use brake resistor
or energy feedback
unit to consume or
use up the generate
energy
3. Adjust relative
parameters to avoid
the motor working in
generator mode
u.37 A.37
IGBT Over
Temperatu
re
Too high load or
the cooling
condition beyond
the specification
1. Check the load
2. Check the cooling
condition, include to
clean the airduct or
replace the fan
u.43 A.43
Power
Board
Over
Temperatu
re
Too high load or
too high ambient
temperature
1. Check the load
2. Check the cooling
condition, include to
clean the airduct or
replace the fan
u.45 A.45
Over
Current
1.Motor
parameters and/or
motor control
parameters are not
set appropriately;
2.The power size of
inverter is too small
comparing to the
motor or the load;
3.The power supply
voltage is too low;
4.The inverter
1.Adjust relevant
parameters
2.Select inverter with
higher power rating
3.Check the power
supply voltage
4.Contact our local
support
55
EN
Warning Alarm Error Fault
Name
Reason Description Suggested Handling
failed to catch a
spinning motor at
fly
u.46 A.46
Drive
Overload
1. Too heavy load
or too low power
supply voltage
2. The power size
of inverter is too
small comparing to
the motor or the
load
3. Motor
parameters and/or
motor control
parameters are not
set appropriately;
1.Correctly set
relevant parameters
especially the motor
parameters;
2. Select inverter with
high power rating.
3. Contact the local
distributor
u.48 A.48
Motor
Over
Temperatu
re
1. Too heavy load
on the motor
2. Cooling
condition for the
motor is not good
enough
3. Thermistor for
motor temperature
sensing is not used
correctly
1.Check selection
/installation of the
thermistor for motor
temperature sensing
2.Check the cooling
conditions for motor
3. Check the load
versus rated power of
the motor
u.49 A.49
Motor
Overload
1. Motor
parameters and/or
motor control
parameters are not
set appropriately;
2. Too heavy load
on the motor
1. Correctly set
relevant parameters
especially the motor
parameters
2. Check the load
versus rated power of
the motor
u.50 A.50
Current
Limit
Current exceeds
the parameter set
max. current
(P05.07) due to:
1.Too heavy load
comparing to the
power size of the
inverter
Adjust P05.07 or try
A.45 solution
56
EN
Warning Alarm Error Fault
Name
Reason Description Suggested Handling
2.Too fast ramp
with inertia
3.Too low power
supply voltage
4.Motor
parameters and/or
motor control
parameters are not
set appropriately;
u.51 A.51
Torque
Limit
Torque exceeds the
parameter set max.
torque (P05.04/P05.05).
Adjust P05.04/P05.05
or try A.45 solution
u.57 A.57
Analogue
input
terminals
Error
1. Wire connection
problem
2. The parameters
for AI1/AI2 live
zero are not
correctly set
1. Check the wire
connection
2. Adjust the relevant
parameter setup
u.62 A.62
Communic
ation
Timeout
Drive
communication
timeout (with
external controller
PC/PLC/HMI etc.)
1. External
controller
abnormal
2. communication
line connection
problem
3. communication
Parameters(P00.8X)
incorrect.
4.EMC problem.
1.Check external
controller PC, PLC,
HMI etc.
2.Check
communication line
connection
3.Correctly set
communication
parameters(P00.8X)
4. Wiring the
communication cables
correctly, including
shielding and
grounding
5.Contact our local
support or Company
u.66
Motor
Loss
Motor cable
connection or
motor problems;
Check motor cable or
motor phase
A.69
Mechanic
Brake
Current
Low
Actual motor
current cannot
exceed release
brake current
Correctly set
mechanical brake
parameters(P01.97~P
01.98)
57
EN
Warning Alarm Error Fault
Name
Reason Description Suggested Handling
(P01.97~P01.98)
within start delay
time.
u.75
Drive
License
Timeout
Drive License
Timeout function
activated
Contact our local
support
u.76 A.76
External
alarm
Digital input
terminals select
external alarm
function
Check external alarm
source
Er.90
Communic
ation
failure
between
I0 and
Power
Hardware failure
Contact our local
support or Company
Er.93
Parameter
change
disabled
1. They keypad was
locked when
changing the
parameters
2. parameters over
the range
1. deblock the keypad
2. set the parameters
correctly
Err
Parameter
change
disabled
The parameter
cannot be changed
when Drive running
The parameter cannot
be changed when
Drive running
A.99 AMA Error
Failed to finish the
motor parameter
auto tuning
Correctly set motor
parameters according
to motor nameplate
8. Parameters List
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
Parameter Group 0:General Control Mode and Commands
P00.01 Control Mode 0: Speed Mode Speed Sensor less 0
*P00.02
Motor Control
Principle
0: V/F
1: Vector Control 1
0
P00.03 Macro-program
0:Invalid;1:Pump Control
2: Simple PLC
0
*P00.04
Torque
Characteristics
0:CT; 1:VT 0
*P00.05
Motor Speed
Direction
0:Clockwise; 1:Anticlockwise
2:Bidirectional
2
58
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P00.10
Speed Set Source
Selection
0: main set source
1: Multi preset value with priority
2: Calculation of main set source
and additional set source.
3: Switchover between main set
source and additional set source.
4: Switchover between main set
source and the calculation of
main set source and additional set
source
5: Switchover between additional
set source and the calculation of
main set source and additional set
source
Selecting 4 or 5 works similar as
selecting 3.
2
P00.11 Main Set Source
0: No function;
1: Terminal AI1
2: Terminal AI2
5: Pulse input, use pulse input as
set source
10: Multi preset value 0 +
Up/Down
11: Multi preset values
20: Communication
21: Process PID
30: Keypad
1
P00.12
Additional Set
Source
Same as P00.11 20
P00.14
Set Value
Calculation from
Main and
Additional Source
0:Main Set Source + Additional
Set Source
1:Main Set Source - Additional
Set Source
2:Maximal Value of Main and
Additional Set Source
3:Minimal Value of Main and
Additional Set Source
0
P00.15 Speed Set Range 0:0~P00.16; 1:-P00.16~P00.16 0
P00.16
Base Value for
Speed Set
0.0~590.0 50.0
P00.17 Control Site
0:Terminal or Bus
Communication
0
59
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
1:Terminal 2:Bus Communication
P00.18
Selection of
Communication
Control Source
0:Null 1:Local RS485 1
P00.30
Multi Preset
Value0
-100.00~100.00 % 0.00
P00.31
Multi Preset
Value1
-100.00~100.00 % 0.00
P00.32
Multi Preset
Value2
-100.00~100.00 % 0.00
P00.33
Multi Preset
Value3
-100.00~100.00 % 0.00
P00.34
Multi Preset
Value4
-100.00~100.00 % 0.00
P00.35
Multi Preset
Value5
-100.00~100.00 % 0.00
P00.36
Multi Preset
Value6
-100.00~100.00 % 0.00
P00.4
Multi Preset
Value7
-100.00~100.00 % 0.00
P00.46
UP/DOWN Step
Value
0.01~50.00 0.10
P00.47
Save Up/Down Set
Value
0:Not Save 1:Save when Stop 2:Save when Power Down
0
P00.48 Jog Speed 0.0~590.0Hz Hz 5.0
P00.49
Ramp Time
Resolution 0:0.1s; 1:0.01s 1
P00.50 Ramp 1 Type 0:Linear; 1:S ramp 0
P00.51
Ramp 1 Ramp Up
Time
0.05~655.35 s *
P00.52
Ramp 1 Ramp
Down Time
0.05~655.35 s *
P00.53 Ramp 2 Type 0:Linear; 1:S ramp 0
P00.54
Ramp 2 Ramp Up
Time
0.05~655.35 s *
P00.55
Ramp 2 Ramp
Down Time
0.05~655.35 s *
P00.56 Ramp 3 Type 0:Linear; 1:S ramp 0
P00.57
Ramp 3 Ramp Up
Time
0.05~655.35 s *
60
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P00.58
Ramp 3 Ramp Down
Time
0.05~655.35 s *
P00.59 Ramp 4 Type 0:Linear; 1:S ramp 0
P00.60
Ramp 4 Ramp Up
Time
0.05~655.35 s *
P00.61
Ramp 4 Ramp Down
Time
0.05~655.35 s *
P00.62 Jog Ramp Time 0.05~655.35 s *
P00.63
S Ramp Up Initiate
Period
0.05~655.35 s *
P00.64
S Ramp Up
Termination Period
0.05~655.35 s *
P00.65
S Ramp Down Initiate
Period
0.05~655.35 s *
P00.66
S Ramp Down
Termination Period
0.05~655.35 s *
P00.80 Local Address 1~127 1
P00.81 Baud Rate
0:2400 1:4800
2:9600 3:19200
4:38400 5~9:Reserved
3
P00.82
Communication Data
Format
(Parity/Stop Bits)
0:Even parity (1 stop bit)
1:Odd parity (1 stop bit)
2:No parity (1 stop bit)
3:No parity (2 stop bit)
2
P00.83
Min. Communication
Response Delay
0.000~0.500 s 0.002
P00.84
Max. Communication
Response Delay
0.010~10.000 s 5.000
P00.85 Message Response
0:Normal Reponses
1:Only Response Exceptional
Message
2:Not Response
0
P00.86
Parameter (Set by
Communication)
Saving at Power
Down
0:Not Save Parameter at Power
Down
1:Save Parameter at Power
Down
0
P00.88
Communication
Timeout Time
0.01~650.00 s 1.00
P00.89
Communication
Timeout Response
Function
0:No Function
2:Stop Motor
3:Jogging
4:Run with Max Frequency
0
61
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P05.03
5:Alarm Fault and Trip to stop
6:Warning
P00.90
Reset
Communication
Timeout
0:No Action;
1:Reset the Timeout
0
Parameter Group 1:Basics for Inverter and Motor Control
P01.00 Switching Frequency 2~10:2~16 kHz *
*P01.01 Grid Type 2~122 *
*P01.02 Motor Type
0:Induction Motor
1:SPM
2:IPM without Saturation
3:IPM with Saturation
0
*P01.03 Rated Motor Power 0.12~450 kW *
*P01.04 Rated Motor Voltage 50~1000 V *
*P01.05
Rated Motor
Frequency
20~1000 Hz *
*P01.06 Rated Motor Current 0.1~1200 A *
*P01.07 Rated Motor Speed 100~24000 rpm *
*P01.08 Rated Motor Torque 0.1~6553.5 N·m *
*P01.13
Autotuning for Motor
Parameters
0:No Function;
1:Simple Static Motor Auto
Tuning
2:Complete Static Motor Auto
Tuning
0
*P01.14 Stator Resistance (Rs) Depends on motor model Ω *
*P01.15 Rotor Resistance (Rr) Depends on motor model Ω *
*P01.16
Stator Leakage
Reactance (X1)
Depends on motor model Ω *
*P01.17 Main Reactance (Xh) Depends on motor model Ω *
*P01.18
Ld, PM D-axis
Inductance
0.01~655.35 mH *
*P01.19
Lq, PM Q-axis
Inductance
0.01~655.35 mH *
*P01.20
Ld-s, PM D-axis
Inductance Saturated
0.01~655.35 mH *
*P01.21
Lq-s, PM Q-axis
Inductance Saturated
0.01~655.35 mH *
*P01.22
Saturation Current at
D-axis for Ld-s
20~200 % 100
*P01.23
Saturation Current at
Q-axis for Lq-s
20~200 % 100
62
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
*P01.24
Number of Motor
Poles
2~100 P 4
*P01.25
BEMF at Rated Speed
for PM
0~9000 V *
*P01.26 Motor Cable Length 0~150 m 10
P01.32
Load Compensation
Gain for Low Speed
0~199 % 100
P01.33
Load Compensation
Gain for High Speed
0~199 % 100
P01.34
Motor Magnet
Current at 0 Speed
0~300 % 100
P01.35
Cut in Speed for
Normal Magnet
Current
0.0~10.0 Hz 0.0
P01.36
Min Motor Current at
Low Speed
0~120 % 80
P01.37
Slip Compensation
Gain
-400~399 % *
P01.38
Slip Compensation
Time Constant
0.05~5.00 s *
P01.39
Resonance Damping
Gain
0~3000 % *
P01.40
Time Constant for
Resonance Damping
Filter
0.005~0.050 s 0.005
P01.41
Damping Coefficient
for PM
0~2000 % 120
P01.42
Damping Time
Constant for
Low-Speed range
(PM)
0.01~20.00 s 0.8
P01.43
Damping Time
Constant for
High-Speed range
(PM)
0.01~20.00 s 0.8
P01.44
Time Constant for
Current Filter (PM)
0.001~1.000 s 0.5
P01.53/
P01.55 /
P01.57/
P01.59/
P01.61
Voltage for V/F curve
points
0.0~999.9 V *
63
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P01.54/
P01.56 /
P01.58/
P01.60/
P01.62
Frequency for V/F
curve Points
0.0~590.0 Hz *
P01.63 PM Start Method
0:Initial Position Detection
(IPD)
1:Parking
1
*P01.64 IM Start Method
0:Direct Start;
1:Fly start
0
P01.67 Min Valid Speed Set 0.00~50.00 Hz 0.00
P01.68
Bypass Range for IM
Low Speed
0.0~20.0 Hz 0.0
P01.70 Delay Time at Start 0.0~10.0 s 0.0
P01.71
Delay Function at
Start
0:Free Coast
1:DC Hold
0
P01.72 DC Hold Current 0~150 % 50
P01.80 Function at Stop
0:Free Coast
1:DC hold
0
P01.81
Cut in Speed for
Function at Stop
0.0~590.0 Hz 0.0
P01.82
DC Brake Current
(IM)
0~150 % 50
P01.83 DC Brake Time (IM) 0.0~60.0 s 2
P01.84
DC Brake Cut in
Speed (IM)
0.0~590.0 Hz 0.0
P01.85
Demagnetizing Rate
at DC Cut in
0~100 % 100
P01.86
Parking Current (PM
Start)
0~150 % 80
P01.87
Parking Time (PM
Start)
0.1~60.0 s 3.0
P01.91 Brake Function
0:No Function
1:Resistor Brake
2:AC Brake
0
P01.92
Max AC Brake
Current
0~150 % 100
P01.93 AC Brake Gain 1.0~2.0 1.4
P01.94
Threshold Voltage for
Brake Function
Grid Dependent V *
P01.95
Resistor Brake
Resistance
5~65535 Ω *
64
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
Parameter Group 2: Digital Terminal Functions
P02.00
Digital input
Positive-Negative
Logic Selection
0~65535 0
P02.01
DO/Relay
Positive-Negative
Logic Selection
0~65535 0
P02.04
digital input Filter
time
2~16 ms 4
P02.05
S1 Input Function
Selection
0:No Function
1:Reset
2:Coast to Stop (Negative
Logic)
3:Coast to Stop and Reset
(Negative Logic)
4:Stop (Negative Logic)
10:Run
11:Forward/Reverse Selection
12:Run in Reverse Direction
13:Latched run forward
14:Latched run reverse
15:Forward Jog
16:Reverse Jog
20:Forbid Forward
21:Forbid Reverse
22:Preset Value Command Bit
1
23:Preset Value Command Bit
2
24:Preset Value Command Bit
3
25:Preset Value Command Bit
4
26:Ramp Time Selection Bit 1
27:Ramp Time Selection Bit 2
30:Speed UP
31:Speed DOWN
32:Counter A
34:Reset Counter A
35:Counter B
37:Rest Counter B
40:Pulse Input
10
P02.06
S2 Input Function
Selection
12
P02.07
digital input Function
Selection - Terminal
D1
22
P02.08
digital input Function
Selection - Terminal
D2
23
65
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P02.09
digital input Function
Selection - Terminal
D3
41:Switch Set Source
42:Switch Speed Mode/Torque
Mode
50:External Fault Input
51:Freeze PID output
24
P02.21
Action for digital
input as External Fault
Input
0:No Action
2:Stop and Warning
3:Jog and Warning
4:un to Max Speed P05.03 and
Warning
5:Alarm Fault and Trip to stop
6:Warning
0
P02.22
DO Function
Selection - Terminal
DO1
0:No operation; 1:Drive ready,
2:Remote control ready
3:Drive ready/stop
4:Drive running, the drive is
running;
5:Drive running/No warning,
the drive is running and no
warning is present;
6:Run in current range
7:Run on reference
8:Reverse
10:Alarm
11:Alarm or warning
12:Thermal warning
13:Ready
14:Remote ready
15:Bus OK
20:Out of current range
21:Below current low
22:Above current high
23:Out of frequency range
24:Below frequency low,
25:Above frequency high
26:Out of feedback range
27:Below feedback low
28:Above feedback high
29:Out of reference range
30:Below reference low
31:Above reference high
40:Drive in Local mode
41:Drive in Remote mode
0
P02.28
Relay Output
Function Selection -
RL1
10
66
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
42:Mech. brake control,
43:External alarm
44:Unbalance warning
P02.29
Relay on Delay Time
- RL1
0.00~600.00 s 0.00
P02.30
Relay off Delay Time
- RL1
0.00~600.00 s 0.00
P02.46
Save digital input
Counter Value at
Power down
0:Save None
1:Save Counter A
2:Save Counter B
3:Save Both Counter A and B
0
Parameter Group 3: Analogue Terminal Functions
P03.00
Signal Type -
Terminal AI1
0:Analogue Voltage
1:Analogue Current
0
P03.01
Terminal AI1 Filter
Time
0.00~10.00 s 0.01
P03.02
Zero Voltage Dead
Band - Terminal AI1
0.00~20.00
V/
mA
0.00
P03.03
Min Input
Voltage-Terminal AI1
0.00~P03.04 V 0.00
P03.04
Max Input
Voltage-Terminal AI1
P03.03~10.00 V 10.00
P03.05
Min Input Current -
Terminal AI1
0.00~ P03.06 mA 0.00
P03.06
Max Input Current
-Terminal AI1
P03.05~20.00 mA 20.00
P03.07
Set Value/Feedback
Value Versus Min
Input -Terminal AI1
-200.00~200.00 % 0.00
P03.08
Set Value/Feedback
Value Versus Max
Input -Terminal AI1
-200.00~200.00 % 100.00
P03.09
Signal Type -
Terminal AI2
0:Analogue Voltage
1:Analogue Current
1
P03.10
Terminal AI2 Filter
Time
0.00~10.00 s 0.01
P03.11
Zero Voltage Dead
Band - Terminal AI2
0.00~20.00
V/
mA
0.00
P03.12
Min Input Voltage
-Terminal AI2
0.00~P03.13 V 0.00
P03.13
Max Input
Voltage-Terminal AI2
P03.12~10.00 V 10.00
67
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P03.14
Min Input Current -
Terminal AI2
P03.15~19.99 mA 0.00
P03.15
Max Input Current
-Terminal AI2
P03.14~20.00 mA 20.00
P03.16
Set Value/Feedback
Value Versus Min
Input -Terminal AI2
-200.00~200.00 % 0.00
P03.17
Set Value/Feedback
Value Versus Max
Input -Terminal AI2
-200.00~200.00 % 100.00
P03.48
Analogue Live Zero
Timeout Time
1~99 s 10
P03.49
Live Zero Timeout
Function
0:No Action
2:Stop and Warning
3:Jog and Warning
4:Un at Max Speed P05.03 and
Warning
5:Alarm Fault and Trip to stop
0
P03.50
Signal Type -
Terminal AO
0:0~20mA
1:4~20mA
3:0~10V
3
P03.51
Output Function
Selection- AO
0:No function
1:Output frequency
2:Output current
3:Output Power
4:Motor Speed
5:Output voltage
10:Set Value
11:Feedback
13:Set Value from Bus
14:Pulse input 1 input
frequency
15:Terminal AI1 input value
16:Terminal AI2 input value
20:DC link voltage
30:Output Torque
0
P03.52
Value Versus Min
Output - AO
0.00~200.00 % 0.00
P03.53
Value Versus Max
Output - AO
0.00~200.00 % 100.00
P03.54
Min Output
Voltage/Current - AO
0.00~P03.55
0.00
/4.00
68
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P03.55
Max Output
Voltage/Current - AO
P03.54~10.00/20.00 10.00
/20.00
P03.68
Min Set Value from
Keypad
-200.00~200.00 % 0.00
P03.69
Max Set Value from
Keypad
-200.00~200.00 % 100.00
Parameter Group 4: Process PID and Other Controllers
P04.00
Process PID Feedback
Source
0:No Function
1:Terminal AI1
2:Terminal AI2
5:Pulse Input 1
20:Bus Communication
0
P04.01
Process PID Set
Source
0:No Function
1:Terminal AI1
2:Terminal AI2
5:Pulse Input 11
10:Preset Value 0 + UP/DOWN
11:Multi Preset Value
20:Bus Communication
30:Keypad
0
P04.02
Fiducial Value for
Process PID
Set/Feedback
0.0~3000.0 50.0
P04.04
Process PID Control
Logic:
Positive/Negative
0:Positive
1:Negative
0
P04.05
Process PID Anti
Windup
0:Disable
1:Enable
1
P04.06
Cut-in Frequency for
Process PID Speed
Mode
0.0~200.0 Hz 0.0
P04.07
Proportional Gain -
Process PID 1
0.0~10.00 0.01
P04.08
Integral Time -
Process PID 1
0.01~655.35 s 655.35
P04.09
Differentiating Time -
Process PID 1
0.00~10.00 s 0.00
P04.13
Process PID
Differential Limit
1.0~50.0 5.0
P04.14
Error Tolerance Limit
to Enable Process PID 0.0~200.0 % 0.1
69
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P04.15
Process PID Out/In
Mode to Error
Tolerance
0~2 0
P04.18
Process PID Output
Low Limit
-100.00~100.00 % 0.00
P04.19
Process PID Output
High Limit
-100.00~100.00 % 100.00
P04.22
Process PID Integral
Output Low Limit
-100.00~100.00 % 0.00
P04.23
Process PID Integral
Output High Limit
-100.00~100.00 % 100.00
P04.51
PM Current Limit
Controller
Feedforward Gain
0~400 % 100
P04.52
Proportional Gain -
Current Limit
Controller
0~500 % 100
P04.53
Integration Time -
Current Limit
Controller
0.000~2.000 s 0.020
P04.54
Filter Time - Current
Limit Control
2.0~100.0 ms *
Parameter Group 5: Limitation, Protection and Failure Detection
*P05.02
Motor Low Speed
Limit
0.0~590.0 Hz 0.0
*P05.03
Motor High Speed
Limit
0.0~590.0 Hz 65.0
P05.07 Max Current Limit 0~300 % *
*P05.08
Max Output
Frequency Limit
0.0~590.0 Hz 65.0
P05.09
Threshold for Low
Current Warning
0.00~P09.16 A 0.0
P05.10
Threshold for High
Current Warning
0.00~P09.16 A *
P05.11
Threshold for Low
Speed Warning
0.0~590.0 Hz 0.0
P05.12
Threshold for High
Speed Warning
0.1~590.0 Hz 65.0
P05.13
Threshold for Low Set
Value Warning
-200.00~200.00 % 0.00
P05.14
Threshold for High
Set Value Warning
-200.00~200.00 % 100.00
70
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P05.15
Threshold for Low
Feedback Warning
-200.00~200.00 % 0.00
P05.16
Threshold for High
Feedback Warning
-200.00~200.00 % 100.00
*P05.17
Enable Motor Phase
Loss Protection
0:Disable
1:Enable
1
P05.18
Enable Current
Limit/Torque Limit
Warning
0:Disable
1:Enable
1
P05.26
Motor Thermal
Protection Function
0:No Function
1:ETR Warning
2:ETR Alarm Fault
3:ETR Warning for Self-cooled
Motor
4:ETR Alarm Fault for
Self-cooled Motor
0
P05.27
Motor Overload
Protection Time
0.1~60.0 min 2.0
P05.28
Threshold for Motor
Overload Protection
100~160 % 150
P05.29
Function at Mains
Phase Loss
0:No Action
1:Only Waring
2:Trip to stop and Alarm Fault
(Heavy Load)
3:Trip to stop and Alarm Fault
(Mid Load)
4:Trip to stop and Alarm Fault
(Light Load)
3
P05.30
Alarm/Fault Lock
Handling
0:Not Lock, Alarm/Fault
Resettable without Re-Power
On
1:Lock, Alarm/Fault Lock
Resettable only after Re-Power
On
1
P05.31
Delay Time to Alarm
Current Limit Fault
0~60 s 60
P05.33 Action at Warning
0:Trip to stop and Alarm Fault
directly
1:Warning and Re-catch Motor
after Failure Disappear
1
P05.34
Method to Re-catch
Motor at Warning
0:Speed Track(IM/PM) and
Angle Track (Fly start)
0
71
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
1:Direct Re-catch
Parameter Group 6: Keypad Operation and Display
P06.03
Customer Defined
Value for 0 Speed
0.0~6553.5 0.0
P06.04
Customer Defined
Value for Max Speed
0.0~6553.5 100.0
P06.05
Keypad Display
Option
0~8191 0
P06.31
Local/Remote Mode
Selection
0:Remote Mode
1:Local Mode
0
P06.34
Lock Keypad for
Parameter Edit
0:Disabled
1:Enabled and Lock
0
Parameter Group 7: Auxiliary and Special Functions
P07.00
Special Operation
Function
0:No Function
9:Reset Parameters to Factory
Defaults
0
P07.01
Function at Re-Power
(for Local Mode Only)
0:Resume with Set Value as Set
before Re-power
1:Not Run, but Keep Set Value
as Set before Re-power
2:Not Run and Clear Set Value
1
*P07.10 Min Switch Frequency 2~16:2~16 kHz kHz 2
*P07.11
Over Modulation
Coefficient
90.0~105.5 % 100.0
*P07.12
DC-Link Voltage
PWM Compensation
Function
0:Compensate Average DC
voltage
2:Compensate DC Ripple
Voltage
0
P07.13
DC-link Voltage
PWM Compensation
Disable at VF control
0:Disable
1:Enable
1
P07.14
Dead Time
Compensation
Adjustment
Coefficient
0~200 % 100
P07.17
Max Speed for Dead
Time Compensation
20~590 Hz *
P07.26
Function at Mains
Voltage Sag
0:No Function
1:Passive Ramp Down
2:Passive Ramp Down, Trip
3:Coast and Fly start
4:KEB Control
0
72
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
5:KEB Control, Trip
6:Trip to stop and Alarm
P07.27
Threshold Triggering
Mains Voltage Sag
Function
100~220/380 V *
P07.28 KEB Control Gain 0 ~ 500 % 100
P07.36
Method to Reset
Alarm Fault
0:Reset by Command
1~10:Auto Reset for 1~10
Times
11:Auto Reset for Unlimited
Times
0
P07.37
Alarm Auto Reset
Waiting Time
0~600 s 10
*P07.38 VT Function Level 40~90 % 90
P07.46
Threshold Voltage for
OVC Function
Grid Voltage Dependent V *
P07.47 OVC Function
0:Disable
1:Enable with Mode 1
2:Enable with Mode 2
*
P07.48 OVC Integral Time 0.01~0.10 s *
P07.49
OVC Proportional
Gain
0~200 % *
P07.50 Bypass Speed Start 1 0.0~590.0 Hz 0.0
P07.51 Bypass Speed End 1 0.0~590.0 Hz 0.0
P07.52 Bypass Speed Start 2 0.0~590.0 Hz 0.0
P07.53 Bypass Speed End 2 0.0~590.0 Hz 0.0
P07.54 Bypass Speed Start 3 0.0~590.0 Hz 0.0
P07.55 Bypass Speed End 3 0.0~590.0 Hz 0.0
Parameter Group 8: Basic and Running Information
P08.00 PU SW Version
P08.30
Total Days with
Power On
0~9999 d
P08.31 Total Running Hours 0~60000 h
P08.32
Total Energy
Consumed (kWh)
0~65535
kW
h
P08.33
Number of Power
Ups
0~65535
P08.34
Number of
Over-Temperatures
0~65535
P08.35
Number of
Over-Voltages 0~65535
73
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P08.36
Reset Consumed
Energy Counter
0:Not Reset
1:Reset
0
P08.37
Reset Running Hours
Counter
0:Not Reset
1:Reset
0
P08.40~
P08.49
Alarm Log
P08.50~
P08.59
Warnings Log
Parameter Group 9: Real Time Running Status Monitoring
P09.00 Control Word 0~65535
P09.01 Status Word 0~65535
P09.02 Set Value -4999.0~4999.0
P09.04 Motor Speed 0~24000 rpm
P09.05 Output Power 0.000~655.35 kW
P09.06 Output Voltage 0.0~6553.5 V
P09.07 Output Frequency 0.0~590.0 Hz
P09.08 Output Current 0.00~655.35 A
P09.09 Output Torque -200.0~200.0 %
P09.10
Motor Thermal Load
Status
0~100 %
P09.11 DC Link Voltage 0~65535 V
P09.13
Heatsink or IGBT
Temperature
-128~127 ℃
P09.14
Inverter Thermal
Load Status
0~255 %
P09.15
Nominal Inverter
Current
0.0~6553.5 A
P09.16 Max Inverter Current 0.0~6553.5 A
P09.17
Power Board
Temperature
-128~127 ℃
P09.18 Rectifier Temperature -128~127 ℃
P09.19 PID Set Value -200.0~200.0 %
P09.20 PID Feedback Value -200.0~200.0
P09.21 PID Output -200.0~200.0 %
P09.22 Digital Input 0~65535
P09.23
AI1 Analogue Input
Type
0:0~10V
1:0~20mA
P09.24 AI1 Input Value 0.00-20.00 V/mA
P09.25
AI2 Analogue Input
Type
0:0~10V
1:0~20mA
P09.26 AI2 Input Value 0.00-20.00 V/mA
74
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P09.39 Relay Output Status 0~65535
P09.40 AO Output 0.00-20.00 V/m
A
P09.45 Counter A Value 0~65535
P09.46 Counter B Value 0~65535
P09.47
Set Value from Bus
Communication
-32768~32767
P09.48
Variable Defined by
Customer
0~6553.5
Parameter Group 19:Simple PLC function
P19.00 SPLC control mode
0:Once running then keep
running
1:Once running then stop
2:Cycle running
0
P19.01 SPLC store selection
0:No function
1:Save at Stop
2:Save at Power down
0
P19.02
SPLC reset times
reset
0: Invalid
1: Reset times are reset
0
P19.10 SPLC multi-speed0 -100.00%~100.00% % 0
P19.11 SPLC multi-speed1 -100.00%~100.00% % 0
P19.12 SPLC multi-speed2 -100.00%~100.00% % 0
P19.13 SPLC multi-speed3 -100.00%~100.00% % 0
P19.14 SPLC multi-speed4 -100.00%~100.00% % 0
P19.15 SPLC multi-speed5 -100.00%~100.00% % 0
P19.16 SPLC multi-speed6 -100.00%~100.00% % 0
P19.17 SPLC multi-speed7 -100.00%~100.00% % 0
P19.18 SPLC multi-speed8 -100.00%~100.00% % 0
P19.19 SPLC multi-speed9 -100.00%~100.00% % 0
P19.20 SPLC multi-speed10 -100.00%~100.00% % 0
P19.21 SPLC multi-speed11 -100.00%~100.00% % 0
P19.22 SPLC multi-speed12 -100.00%~100.00% % 0
P19.23 SPLC multi-speed13 -100.00%~100.00% % 0
P19.24 SPLC multi-speed14 -100.00%~100.00% % 0
P19.25 SPLC multi-speed15 -100.00%~100.00% % 0
P19.26
SPLC step0 ramp
time
0.0~6000.0 S 0
P19.27
SPLC step1 ramp
time
0.0~6000.0 S 0
P19.28
SPLC step2 ramp
time 0.0~6000.0 S 0
75
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P19.29
SPLC step3 ramp
time
0.0~6000.0 S 0
P19.30
SPLC step4 ramp
time
0.0~6000.0 S 0
P19.31
SPLC step5 ramp
time
0.0~6000.0 S 0
P19.32
SPLC step6 ramp
time
0.0~6000.0 S 0
P19.33
SPLC step7 ramp
time
0.0~6000.0 S 0
P19.34
SPLC step8 ramp
time
0.0~6000.0 S 0
P19.35
SPLC step9 ramp
time
0.0~6000.0 S 0
P19.36
SPLC step10 ramp
time
0.0~6000.0 S 0
P19.37
SPLC step11 ramp
time
0.0~6000.0 S 0
P19.38
SPLC step12 ramp
time
0.0~6000.0 S 0
P19.39
SPLC step13 ramp
time
0.0~6000.0 S 0
P19.40
SPLC step14 ramp
time
0.0~6000.0 S 0
P19.41
SPLC step15 ramp
time
0.0~6000.0 S 0
P19.42
SPLC step0 running
time
0.0~6000.0 S 0
P19.43
SPLC step1 running
time
0.0~6000.0 S 0
P19.44
SPLC step2 running
time
0.0~6000.0 S 0
P19.45
SPLC step3 running
time
0.0~6000.0 S 0
P19.46
SPLC step4 running
time
0.0~6000.0 S 0
P19.47
SPLC step5 running
time
0.0~6000.0 S 0
P19.48
SPLC step6 running
time
0.0~6000.0 S 0
P19.49
SPLC step7 running
time
0.0~6000.0 S 0
76
EN
Parameter
Number
Parameter Name Value Range Unit
Factory
Default
P19.50
SPLC step8 running
time
0.0~6000.0 S 0
P19.51
SPLC step9 running
time
0.0~6000.0 S 0
P19.52
SPLC step10 running
time
0.0~6000.0 S 0
P19.53
SPLC step11 running
time
0.0~6000.0 S 0
P19.54
SPLC step12 running
time
0.0~6000.0 S 0
P19.55
SPLC step13 running
time
0.0~6000.0 S 0
P19.56
SPLC step14 running
time
0.0~6000.0 S 0
P19.57
SPLC step15 running
time
0.0~6000.0 S 0
P19.80 Average Speed 0~65535
RP
M
P19.81 Current Running step 0~15
P19.82
Current Running step
time
0.0~6553.5
S
P19.83 SPLC reset times 0~65535
Parameter Group 20:Pump control function
P20.00 pump control mode 0:pressure mode 0
P20.01
minimum output
frequency
0.00~P20.02
%
40
P20.02
maximum output
frequency
P20.01~100.00
%
100
P20.60
Sleep enable
selection
0:disable
1:enable
0
P20.61
Sleep frequency
threshold
0.00~100.00
%
2
P20.62
Sleep pressure
threshold
0.00~100.00
%
2
P20.63 Sleep detection time 0.0~300.0 S 10
P20.64 minimum sleep time 0.0~1800.0 S 300
P20.65
wake up pressure
threshold
0.00~100.00
%
10
P20.66
wake up detection
time 0.0~60.0 S 1
77
EN
9. Din-rail Install
M313-A also offers a variety of accessories including Din-rail mounting attachments and
EMC decoupling metal plates, among others. It is important to note that the Din-Rail
mounting accessories are only provided for products below 4kW. Should you have any
requirements, please contact our sales department.
10. Modbus Communication Guidance
The M313-A drive provide RS485 communication interface. It adopts
international standard Modbus communication protocol to perform master-slave
communication. The user can realize centralized control through PC/PLC to adapt
specific application requirements.
10.1 Application Mode
10.1.1 Interface Mode
The communication interface is RS485. RS485 works on semi duplex and its data
signal applies differential transmission which is called balance transmission too.
10.1.2 Networking Mode
The drive has two networking modes: single master/multiple slaves networking
and single master/single slave networking.
Single master/single slave networking diagram
Single master/multiple slaves networking diagram
78
EN
Specification:
1) No matter which mode, the drive is used as a slave in communication.
When master sends commands using broadcast address, the slave
does not respond;
2) It is recommended to use shield cables in multiple connection. The
basic parameter of the devices, such as baud rate and digital check bit
in RS485 should be the same as slave device’s and there should be no
repeated addresses in slave devices.
10.2 Protocol Format
Modbus protocol only support RTU mode.
RTU data frame format is shown as the figure below:
Specification:
Start At least 3.5 idle characters
Slave address Address:0-127(0 is broadcast address)
Function code Modbus function code
Data (N-1)
Data (N-2) 2 * N data
…
Data 0
CRC CHK high-8-bit CRC check
CRC CHK low-8-bit
End At least 3.5 idle characters
10.3 Function Code
Function code supported by M313 drive Modbus protocol are as shown in the
table below:
Function code Description Meaning
0x03 Read Holding
Registers
Read drive functional parameters and
running status parameters
0x06 Preset Single
Register
Over-write individual drive functional
parameters
0x10 Preset Multiple
Regs
Over-write multiple Registers
10.4 Register Address Definition
All the following register addresses are started from 0.
79
EN
10.4.1 The Rules of Register Address of the Parameter Number
The parameters can be mapping to register address. The rules of register address
of the parameter number are shown below:
Register address = PNU – 1
For example: The register address of P00.30 is 30 - 1 = 29 (0x001D)
The register address of P09.11 is 911 - 1 = 910(0x038E)
Attention: Parameters Group 8 and 9 are Read-only.
The Drive don’t support write or read multiple parameters at a time.
10.4.2 Other Register Addresses Specification
In addition to parameter is mapped to Modbus registers, there are some
additional registers within the drive which can be used to control the drive,
monitor the drive's status. These registers can support write or read maximum 10
registers at a time.
Register address Specification R/W
9999*
Control command W
10000*
Frequency command W
10099*
State R
10100* Warning/Alarm code R
10101 Output frequency (0~Fmax, unit: 0.1Hz) R
10102 Output current (unit: 0.01A) R
10103 Output voltage (unit: 1V) R
10104 Output power (unit: 0.01kW) R
10105 Motor speed (unit: 1rpm) R
10106 DC bus voltage (unit: 1V) R
10107 Reference R
10108 Process PID Feedback R
* Reg. 9999 specification
Bit Specification
Bit 7~0(run/stop control
etc.)
0x00: No function
0x01: Run forward
0x02: Reverse
0x03: Jog
0x04: Jog reverse
0x05: Stop
0x06: Coast
0x07: Reset
Bit 11~8(Preset value
select)
0000B:P00.30(Preset Value 0)
0001B: P00.31(Preset Value1)
80
EN
Bit Specification
…
1111B: P00.45(Preset Value 15)
Bit 13~12(Ramp time
select)
00B: Ramp 1
01B: Ramp 2
10B: Ramp 3
11B: Ramp 4
Bit 14 Reserved
Bit 15 1B: Enable Bit8~13 function; 0B: Disable Bit8~13
function
* Reg. 10000 specification
When using communication to control the drive, you can set the frequency
directly by writing register 10000 . The register value is in the range of 0.00 ~
P05.08, unit 0.01Hz.
* Reg. 10099 specification
Bit Specification
Bit 0 0B: None;1B: Warning
Bit 1 0B: None;1B: Alarm
Bit 3~2 00B: Stop
01B: Run forward
10B: Reverse
11B: Reserved
Bit 7~4 Reserved
Bit 11~8 0000B: Using Preset Value 0
0001B: Using Preset Value 1
…
1111B: Using Preset Value 15
Bit 15~12 Reserved
* Reg. 10100specification
Register 10100 is used to read the drive warning/alarm code. For example: When
the drive occurs A.48 alarm, the value of register 10100 is 48. When the drive
occurs u.24 warning, the value of register 10100 is 24.
10.5 Communication ratio values
The Communication data is expressed by hexadecimal in actual application and
there is no radix point in hexadecimal. For example, if you want to set P05.08 =
61.5, 61.5 can be magnified by 10 times into 615. So hex 0x0267 (615) can be
used to express 61.5.
A non-integer can be timed by a multiple to get an integer and the integer can
be called communication ratio values.
81
EN
The communication ratio values are referred to the radix point of the setting
range of default value in the functional parameter list. If there are radix point n,
then the communication ratio value m is 10^n.
10.6 Error message
There may be errors in the communication process, for example, some
parameters are read-only, but the PC/PLC sends a written directive, the drive will
return an error message.
Error message data frame format is shown as the figure below:
Error message function code = requirements function code + 0x80
Error code Specification
0x01 Function code error, the drive does not support this kind of
function code.
0x02 The register address is invalid.
0x03 The value exceeds the upper limit of the parameter
0x04 Operation error.
10.7 Examples
10.7.1 Read Holding Registers (0x03)
10.7.1.1 Read Motor speed
Read parameter P09.04(Reg 903) to get the Motor speed.
Transmit: 01 03 03 87 00 01 34 67 (Hexadecimal)
Receive: 01 03 02 05 DC BA 8D (Hexadecimal)
Transmit data specification:
Field Description
01 Address
03 Function
03 87 Register address: 903(0x0387)
00 01 The number of read registers is 1
Receive data specification:
Field Description
01 Address
03 Function
02 The byte number of received data
05 DC 0x05DC converts to decimal number is 1500. So, the value of
P09.04 is 1500RPM
82
EN
10.7.1.2 Read Drive Status, warning/alarm code and output frequency
Read multiple Registers 10099、10100、10101 to get all information.
Transmit: 01 03 27 73 00 03 FE A4 (Hexadecimal)
Receive: 01 03 06 00 04 00 00 01 F4 D0 A2 (Hexadecimal)
Transmit data specification:
Field Description
01 Address
03 Function
2773 Register address: 10099(0x2773)
00 03 The number of read registers is 3
FE A4 CRC check
Receive data specification:
Field Description
01 Address
03 Function
Field Description
06 The byte number of received data
00 04 00 00 01
F4
The value of Reg. 10099 is 0x0004.
Note:
Bit 0 is 0B, that is No warning;
Bit 1 is 0B, that is No Alarm;
Bit 3~2 is 01B, that is Run forward;
Bit 11~8 is 0000B, that is Using Preset Value 0;
The value of Reg. 10100 is 0x0000(0). The drive doesn’t have
warning/ alarm, so it is 0.
The value of Reg. 10101 is 0x01F4(500). So, the drive output
frequency is 500/10=50.0Hz.
10.7.2 Write Single Register (0x06)
Set motor rated speed to 1430RPM.
Write P01.07(Reg 106) =1430.
Transmit: 01 06 00 6A 05 96 2A E8 (Hexadecimal)
Receive: 01 06 00 6A 05 96 2A E8 (Hexadecimal)
Transmit data specification:
Field Description
01 Address
06 Function
00 6A Register address of P01.07 is :107-1= 106(0x006A)
05 96 The value wants to set to P01.07 is 0x0596(1430)
Receive data specification:
83
EN
Field Description
01 Address
06 Function
00 6A Register address of P01.07 is :107-1= 106(0x006A)
05 96 The value of P01.07 is 0x0596(1430)
10.7.3 Write Multiple Registers (0x10)
Start the drive and set Drive output frequency.
Write register 9999 to control the drive running and write register 10000 to set
the drive output frequency.
Transmit: 01 10 27 0F 00 02 04 00 01 09 C4 5A 1D (Hexadecimal)
Receive: 01 10 27 0F 00 02 7B 7F (Hexadecimal)
Transmit data specification:
Field Description
01 Address
10 Function
27 0F Register address: 9999(0x270F)
00 02 The number of write registers is 2
04 The byte number of write data is 4
00 01 09 C4 Reg. 9999= 0x0001
Note:
Bit 7~0 is 0x01, that is Run forward;
Bit 11~8 is 0000B, that is Using Preset Value 0;
Bit 13~12 is 00B, that is Using ramp 1;
Bit 15 is 0B, that is Disable bit 13~8;
Reg. 10000= 0x09C4(2500, So the Reference frequency is
2500 / 100 = 25.00Hz)
Receive data specification:
Field Description
01 Address
10 Function
27 0F Register address: 9999(0x270F)
00 02 The number of write registers is 2
01 Address
10.8 Debugging
Most customers use specialized or packed communication app or function
afforded by the supplier of PLC or touch screen. when there is communication
failure, it’s difficult to judge whether it’s the host’s issue or the frequency
converter’s issue. In this case, you can use the PC software tool like “serial
84
EN
debugging assistant” (which is free to download from internet) to help the
diagnosis.
First please connect the system as blow figure. Normally a PC does not have
RS485 port, you can use a transfer module to connect the PC. With the PC SW
tool like “serial debugging assistant”, you can monitor the details of the message
sent from the host and the message replied from the frequency converter.
r
▲ Wiring for Modbus Debugging
VER:V1.1 2025.05
P0101060




