额定电压0.6/1kV无卤低烟阻燃(耐火)电力电缆允许持续载流量(A)
| 型号 | WDZ-YJY、WDZN-YJY、WDZ-YJY23、WDZN-YJY23 0.6/1kV | ||||||||||||
| 芯数 | 单芯 | 2、3、3+1、3+2、4+1、5芯 | |||||||||||
| 敷设 | 空气中 | 土壤中 | 空气中 | 土壤中 | |||||||||
| 排列方式 | 8 | ○ ○)○ | 8 | ○ ○O | |||||||||
| 材质 | 铜Cu | 铝Al | 铜 | 铝 | 铜 | 铝 | 铜 | 铝 | 铜 | 铝 | 铜 | 铝Al | |
| Cu | Ai | Cu | AÍ | Cu | AI | Cu | Al | Cu | |||||
| 标称截面(mm²) | 1.5 | 26 | 32 | – | 33 | – | 35 | – | 20 | – | 31 | – | |
| 2.5 | 34 | 26 | 42 | 33 | 43 | 32 | 46 | 36 | 27 | 21 | 41 | 32 | |
| 4 | 44 | 35 | 56 | 44 | 56 | 42 | 59 | 47 | 35 | 28 | 53 | 42 | |
| 6 | 56 | 45 | 70 | 57 | 70 | 54 | 74 | 60 | 45 | 36 | 66 | 54 | |
| 10 | 77 | 59 | 97 | 75 | 94 | 69 | 99 | 76 | 63 | 49 | 90 | 69 | |
| 16 | 100 | 78 | 125 | 99 | 120 | 90 | 128 | 99 | 84 | 65 | 117 | 91 | |
| 25 | 130 | 100 | 165 | 125 | 155 | 115 | 164 | 128 | 113 | 88 | 151 | 117 | |
| 35 | 160 | 125 | 200 | 155 | 185 | 135 | 197 | 153 | 139 | 108 | 181 | 140 | |
| 50 | 195 | 150 | 245 | 190 | 220 | 165 | 232 | 180 | 161 | 125 | 210 | 163 | |
| 70 | 245 | 190 | 305 | 240 | 270 | 200 | 285 | 221 | 204 | 158 | 257 | 200 | |
| 95 | 300 | 230 | 375 | 290 | 320 | 240 | 342 | 265 | 252 | 195 | 310 | 240 | |
| 120 | 349 | 270 | 435 | 340 | 365 | 275 | 388 | 301 | 291 | 226 | 351 | 273 | |
| 150 | 400 | 310 | 500 | 390 | 410 | 310 | 436 | 338 | 333 | 258 | 393 | 305 | |
| 185 | 465 | 360 | 580 | 450 | 465 | 355 | 496 | 385 | 385 | 299 | 445 | 346 | |
| 240 | 550 | 430 | 685 | 535 | 540 | 410 | 577 | 449 | 457 | 356 | 516 | 402 | |
| 300 | 635 | 495 | 795 | 615 | 610 | 465 | 654 | 508 | 527 | 410 | 582 | 454 | |
| 400 | 745 | 590 | 930 | 730 | 695 | 535 | 749 | 585 | 600 | 475 | 645 | 510 | |
在空气中:
导体温度为90℃,周围环境温度为40℃。
单芯电缆平行敷设时的最小中心距离:185mm²及以下为电缆直径的2倍,240mm²及以上为90mm。
环境温度不同时的载流量修正系数:
| 环境温度 (°C) | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
| 校正系数 | 1.23 | 1.17 | 1.12 | 1.06 | 1.00 | 0.94 | 0.87 | 0.81 |
在土壤中:
导体温度为90℃,周围环境温度为25℃。
土壤热阻系数:1.0K·m/W。
直埋深度:0.7m。
单芯电缆不接触敷设时,最小中心距离为电缆直径的2倍。
环境温度不同时的载流量修正系数:
| 环境温度 (°C) | 10 | 15 | 20 | 25 | 30 | 35 |
| 校正系数 | 1.11 | 1.07 | 1.04 | 1.00 | 0.96 | 0.92 |
使用导则
交联聚乙烯绝缘无卤低烟阻燃电缆导体长期工作温度不超过90℃,短路时电缆导体的最高工作温度不超过250℃(最长持续5秒)。
电缆敷设时最小弯曲半径(D为电缆外径):单芯无铠装电缆为20D,多芯无铠装电缆为15D,单芯有铠装电缆为15D,多芯有铠装电缆为12D。
电缆敷设时环境温度不低于0℃。
额定电压0.6/1kV~26/35kV防鼠防白蚁电力电缆
执行标准及应用范围
本产品执行GB/T34016-2017《防鼠和防白蚁电线电缆通则》、GB/T12706.1-2008《额定电压1kV(Um=1.2kV)到35kV(Um=40.5kV)挤包绝缘电力电缆及附件》第1部分:额定电压1kV(Um=1.2kV)和3kV(UM=3.6kV)电缆、JB/T10696.9-2011《电线电缆机械和理化性能试验方法》第9部分:白蚁试验及JB/T10696.10-2011《电线电缆机械和理化性能试验方法》第10部分:大鼠啃咬试验。产品适应于鼠害或蚁害较严重的地区,在鼠害或蚁害条件下,电缆不会被破坏仍能保持良好的电力传输性能。本产品采用先进的化学防鼠防白蚁方法,具有易加工、易施工、易维护、重量轻等优点。具有低毒、无污染,不会对环境及人体造成二次灾害。防鼠防白蚁有效期长,可达二十年以上。可根据用户要求生产具有耐火、阻燃特性的防鼠防白蚁电线电缆。
型号及名称
| 型号 | 名称 |
| FS1-VV | 防大鼠(显著)1级铜芯聚氯乙烯绝缘聚氯乙烯护套电力电缆 |
| FS1-VV22 | 防大鼠(显著)1级铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FS1-YJV | 防大鼠(显著)1级铜芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| FS1-YJV22 | 防大鼠(显著)1级铜芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FS2-VV | 防大鼠(较好)2级铜芯聚氯乙烯绝缘聚氯乙烯护套电力电缆 |
| FS2-VV22 | 防大鼠(较好)2级铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FS2-YJV | 防大鼠(较好)2级铜芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| FS2-YJV22 | 防大鼠(较好)2级铜芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FY1-VV | 防白蚁1级铜芯聚氯乙烯绝缘聚氯乙烯护套电力电缆 |
| FY1-VV22 | 防白蚁1级铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FY1-YJV | 防白蚁1级铜芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| FY1-YJV22 | 防白蚁1级铜芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FSY11-VV | 防大鼠(显著)1级和防白蚁1级铜芯聚氯乙烯绝缘聚氯乙烯护套电力电缆 |
| FSY11-VV22 | 防大鼠(显著)1级和防白蚁1级铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FSY11-YJV | 防大鼠(显著)1级和防白蚁1级铜芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| FSY11-YJV22 | 防大鼠(显著)1级和防白蚁1级铜芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FSY21-VV | 防大鼠(较好)2级和防白蚁1级铜芯聚氯乙烯绝缘聚氯乙烯护套电力电缆 |
| FSY21-VV22 | 防大鼠(较好)2级和防白蚁1级铜芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| FSY21-YJV | 防大鼠(较好)2级和防白蚁1级铜芯交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| FSY21-YJV22 | 防大鼠(较好)2级和防白蚁1级铜芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
电缆适应场所
| 代号 | 防护/蛀蚀等级 | 适应场所 |
| FS1FS2 | 防大鼠(显著)1级防大鼠(较好)2级 | 用于有鼠害或鼠害严重的地区和环境,电缆可敷设在电缆沟、电缆槽、电缆桥架、隧道和管廓、舰船等场所,也可直埋于有一定深度的地下。 |
| FY1 | 防白蚁1级 | 用于有白蚁危害的地区和环境,电缆可敷设在电缆沟、电缆槽、电缆桥架、隧道和管廓、舰船等场所,也可直埋于有一定深度的地下。 |
| FSY11FSY21 | 防大鼠(显著)1级和防白蚁1级防大鼠(较好)2级和防白蚁1级 | 用于有鼠害或鼠害严重及白蚁危害的地区和环境,电缆可敷设在电缆沟、电缆槽、电缆桥架、隧道和管廓、舰船等场所,也可直埋于有一定深度的地下。 |
公司生产范围
额定电压0.6/1kV防鼠防白蚁电力电缆生产范围、结构尺寸、载流量等参考0.6/1kV聚氯乙烯/交联聚乙烯绝缘电力电缆,额定电压3.6/6kV~26/35kV防鼠防白蚁电力电缆生产范围、结构尺寸、载流量等参考额定电压3.6/6kV〜26/35kV交联聚乙烯绝缘电力电缆。
产品主要性能
电缆导体正常运行时的最高温度:聚氯乙烯绝缘不超过70℃,交联聚乙烯绝缘不超过90℃。
短路时最高温度:聚氯乙烯绝缘不能超过160℃,交联聚乙烯绝缘不超过250℃(最长持续时间不超过5S)。
电缆防鼠防蚁性能:满足GB/T34016-2017《防鼠和防白蚁电线电缆通则》、JB/T10696.9-2011《电线电缆机械和理化性能试验方法》第9部分:白蚁试验及JB/T10696.10-2011《电线电缆机械和理化性能试验方法》第10部分:大鼠啃咬试验的要求。
电气性能:满足GB/T12706.1-2008《额定电压1kV(Um=1.2kV)到35kV(Um=40.5kV)挤包绝缘电力电缆及附件》第1部分:额定电压1kV(Um=1.2kV)和3kV(UM=3.6kV)电缆的要求。
机械性能:满足GB/T12706.1-2008《额定电压1kV(Um=1.2kV)到35kV(Um=40.5kV)挤包绝缘电力电缆及附件》第1部分:额定电压1kV(Um=1.2kV)和3kV(UM=3.6kV)电缆的要求。
额定电压0.6/1kV~26/35kV交联聚乙烯绝缘防水电力电缆
应用范围
防水电缆产品适用于沿海港口、内河港口、水电站、船闸、过江大桥、隧道、地铁、化工冶金和钢铁企业等额定电压35kV及以下供电防水可靠性要求高的重要工程设施及基地,特别是高降雨带、沿海和低洼潮湿地区的中低压电力传输及信号传输。
型号及名称
| 型号 | 名称 |
| FS-YJY | 铜芯交联聚乙烯绝缘聚乙烯护套防水电力电缆 |
| FS-N-YJY | 铜芯交联聚乙烯绝缘聚乙烯护套防水耐火电力电缆 |
| FS-YJY23 | 铜芯交联聚乙烯绝缘钢带铠装聚乙烯护套防水电力电缆 |
| FS-YJY63 | 铜芯交联聚乙烯绝缘不锈钢带铠装聚乙烯护套防水电力电缆 |
| FS-WDZ-YJY | 铜芯交联聚乙烯绝缘聚烯烃护套无卤低烟阻燃防水电力电缆 |
公司生产范围
额定电压0.6/1kV防水电力电缆生产范围、结构尺寸、载流量等参考0.6/1kV交联聚乙烯绝缘电力电缆,额定电压3.6/6kV~26/35kV防水电力电缆生产范围、结构尺寸、载流量等参考额定电压3.6/6kV~26/35kV交联聚乙烯绝缘电力电缆。
产品主要性能
导体直流电阻符合GB/T3956-2008。
电缆纵向阻水性能,可以通过GB/T12706.3-2020附录D(规范性附录)透水试验,阻水性能优良。
额定电压0.6/1kV预制分支电力电缆
应用范围
随着现代建筑日新月异的发展,建筑配电的复杂性成为人们日益关注和重视的一大课题。现代高层建筑施工现场对配电成本的降低、施工周期的缩短及供电系统的高可靠性成为投资商、建筑商和供电部门一致关注的焦点。
YFD系列分支电缆是能满足上述要求的一种崭新产品。该电缆可按照供电系统图纸在工厂内预制好分支电缆,而且其电气性能和物理性能均能在工厂内进行测试。因而该产品具备了电缆分接系统直接进工地而降低成本,又因能在工厂内预制,极大地缩短了施工周期,大幅度减少现场施工费用等优点,更保证了配电的高可靠性。
型号及名称
| 型号 | 名称 |
| YFD-VV | 铜芯聚氯乙烯绝缘聚氯乙烯护套预分支电力电缆 |
| YFD-ZC-VV | 铜芯聚氯乙烯绝缘聚氯乙烯护套阻燃C类预分支电力电缆 |
| YFD-N-VV | 铜芯聚氯乙烯绝缘聚氯乙烯护套耐火预分支电力电缆 |
| YFD-YJV | 铜芯交联聚乙烯绝缘聚氯乙烯护套预分支电力电缆 |
| YFD-ZC-YJV | 铜芯交联聚乙烯绝缘聚氯乙烯护套阻燃C类预分支电力电缆 |
| YFD-N-YJV | 铜芯交联聚乙烯绝缘聚氯乙烯护套耐火预分支电力电缆 |
| YFD-WDZA-YJY | 铜芯交联聚乙烯绝缘聚烯烃护套无卤低烟阻燃A类预分支电力电缆 |
| YFD-WDZAN-YJY | 铜芯交联聚乙烯绝缘聚烯烃护套无卤低烟阻燃A类耐火预分支电力电缆 |
型号规格表达方式说明:
预分支电缆
举例:
(1)YFD-ZC-YJV-4×(1×240)/4×(1×25),铜芯交联聚乙烯绝缘聚氯乙烯护套阻燃C类分支电缆,主干电缆为1×240mm²,分支电缆为1×25mm²。
(2)YFD-VV-4×(1×240)/4×(1×25),铜芯聚氯乙烯绝缘聚氯乙烯护套分支电缆,主干电缆为1×240mm²,分支电缆为1×25mm²。
(3)YFD-N-VV-4×240/4×25,铜芯聚氯乙烯绝缘聚氯乙烯护套耐火型多芯分支电缆,主干电缆为4×240mm²,分支电缆为4×25mm²。
规格
| 芯数 | 标称截面 (mm²) | |
| 主干电缆 | 分支电缆 | |
| 1芯 | 4~500 mm² | 4〜185 mm² |
| 2~5芯 | 4~300 mm² | 4~95 mm² |
依据本公司的设备生产能力,电缆芯数、主干电缆和分支电缆截面规格见下表。
结构尺寸
单芯电缆参数见下表,多分支电缆参数未列入。
额定电压0.6/1kV聚氯乙烯绝缘电力电缆结构尺寸(YFD-VV系列)
| 型号 | YFD-VV、YFD-ZC-VV、YFD-N-VV | ||||||
| 电压 | 0.6/1kV | ||||||
| 敷设 | 空气中 | ||||||
| 工作温度 | 70℃ | 载流量(A) | |||||
| 环境温度 | 35℃ | 排列 | |||||
| 标称截面(mm²) | 导体参考直径(mm) | 圣绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 20C导体最大电阻(Ω/km) | O〇O | |
| 1×10 | 3.8 | 1.0 | 1.4 | 9.0 | 1.83 | 72 | 59 |
| 1×16 | 4.8 | 1.0 | 1.4 | 10.0 | 1.15 | 95 | 77 |
| 1×25 | 5.9 | 1.2 | 1.4 | 12.0 | 0.727 | 120 | 99 |
| 1×35 | 7.0 | 1.2 | 1.4 | 13.0 | 0.524 | 150 | 120 |
| 1×50 | 8.3 | 1.4 | 1.4 | 14.0 | 0.387 | 180 | 145 |
| 1×70 | 9.8 | 1.4 | 1.4 | 16.0 | 0.268 | 230 | 180 |
| 1×95 | 11.5 | 1.6 | 1.5 | 18.0 | 0.193 | 280 | 215 |
| 1×120 | 12.9 | 1.6 | 1.5 | 19.0 | 0.153 | 325 | 250 |
| 1×150 | 14.4 | 1.8 | 1.6 | 21.6 | 0.124 | 375 | 285 |
| 1×185 | 16.1 | 2.0 | 1.7 | 23.6 | 0.0911 | 430 | 330 |
| 1×240 | 18.5 | 2.2 | 1.8 | 27.0 | 0.0754 | 510 | 385 |
| 1×300 | 20.6 | 2.4 | 1.9 | 30.0 | 0.0601 | 585 | 445 |
| 1×400 | 23.3 | 2.6 | 2.0 | 32.3 | 0.0470 | 690 | 520 |
| 1×500 | 26.7 | 2.8 | 2.1 | 37.0 | 0.0366 | 800 | 595 |
分支连接部参数
| 型号 | YFD-YJV 、YFD-ZC-YJV 、YFD-N-YJV、YFD-WDZA-YJY 、YFD-WDZAN-YJY | ||||||
| 电压 | 0.6/1kV | ||||||
| 敷设 | 空气中 | ||||||
| 工作温度 | 90℃ | 载流量(A) | |||||
| 环境温度 | 40℃ | 排列 | |||||
| 标称截面(mm) | 参考导体直径(mm) | 绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 20C导体最大电阻(Ω/km) | O〇O | |
| 1×10 | 3.8 | 0.7 | 1.4 | 8.0 | 1.83 | 97 | 77 |
| 1×16 | 4.8 | 0.7 | 1.4 | 9.0 | 1.15 | 125 | 100 |
| 1×25 | 5.9 | 0.9 | 1.4 | 11.0 | 0.727 | 165 | 130 |
| 1×35 | 7.0 | 0.9 | 1.4 | 12.0 | 0.524 | 200 | 160 |
| 1×50 | 8.3 | 1.0 | 1.4 | 13.0 | 0.387 | 245 | 195 |
| 1×70 | 9.8 | 1.1 | 1.4 | 15.0 | 0.268 | 305 | 245 |
| 1×95 | 11.5 | 1.1 | 1.5 | 17.0 | 0.193 | 375 | 300 |
| 1×120 | 12.9 | 1.2 | 1.5 | 18.0 | 0.153 | 435 | 350 |
| 1×150 | 14.4 | 1.4 | 1.6 | 20.0 | 0.124 | 500 | 400 |
| 1×185 | 16.1 | 1.6 | 1.7 | 22.0 | 0.0911 | 580 | 465 |
| 1×240 | 18.5 | 1.7 | 1.8 | 25.0 | 0.0754 | 685 | 550 |
| 1×300 | 20.6 | 1.8 | 1.9 | 27.0 | 0.0601 | 795 | 635 |
| 1×400 | 23.3 | 2.0 | 2.0 | 31.0 | 0.0470 | 930 | 745 |
| 1×500 | 26.7 | 2.2 | 2.1 | 34.0 | 0.0366 | 1080 | 860 |
预分支电缆
| 序号 | 分支接头规格(主干/分支) | 分支接头长度(mm) | 分支接头直径(mm) |
| 1 | 10/10 | 125 | 35 |
| 2 | 16/10~16 | 125 | 35 |
| 3 | 25/10~25 | 125 | 35 |
| 4 | 35/10~35 | 125 | 35 |
| 5 | 50/10~50 | 125 | 35 |
| 6 | 70/10~50 | 145 | 45 |
| 7 | 70/70 | 145 | 50 |
| 8 | 95/10~50 | 145 | 55 |
| 9 | 95/70~95 | 145 | 60 |
| 10 | 120/10~50 | 145 | 55 |
| 11 | 120/70~120 | 145 | 60 |
| 12 | 150/10~50 | 145 | 55 |
| 13 | 150/70~150 | 145 | 60 |
| 14 | 185/10~70 | 150 | 65 |
| 15 | 185/95~185 | 150 | 65 |
| 16 | 240/10~185 | 150 | 65 |
| 17 | 300/10~185 | 150 | 65 |
| 18 | 400/10~185 | 165 | 75 |
| 19 | 500/10~185 | 165 | 75 |
| 20 | 630/10~185 | 165 | 75 |
| 21 | 800/10~185 | 165 | 80 |
| 序号 | 名称 | 型号 | 适用范围 |
| 1 | 吊头 | XFD-FJ-DT-1 | 10~50 mm² |
| 2 | 吊头 | XFD-FJ-DT-2 | 70~240 mm² |
| 3 | 吊头 | XFD-FJ-DT-3 | 300~500 mm² |
| 4 | 吊头 | XFD-FJ-DT-4 | 630~1000mm² |
| 序号 | 名称 | 型号 | 适用范围 |
| 1 | 横担 | XFD-FJ-HD-1 | 10~50mm² |
| 2 | 横担 | XFD-FJ-HD-2 | 70~240 mm² |
| 3 | 横担 | XFD-FJ-HD-3 | 300~500 mm² |
| 4 | 横担 | XFD-FJ-HD-4 | 630~1000mm² |
| 序号 | 名称 | 型号 | 适用范围 |
| 1 | 支架 | XFD-FJ-ZJ-1 | 10~35 mm² |
| 2 | 支架 | XFD-FJ-ZJ-2 | 50~120mm² |
| 3 | 支架 | XFD-FJ-ZJ-3 | 150~240mm² |
| 4 | 支架 | XFD-FJ-ZJ-4 | 300~500mm² |
| 5 | 支架 | XFD-FJ-ZJ-5 | 630~1000 mm² |
| 序号 | 主电缆规格(m) | 分支线规格(m) | 吊头选型 | 横担选型 | 支架选型 |
| 1 | 10 | 10 | XFD-FJ-DT-1 | XFD-FJ-HD-1 | XFD-FJ-ZJ-1 |
| 2 | 16 | 10~16 | XFD-FJ-DT-1 | XFD-FJ-HD-1 | XFD-FJ-ZJ-1 |
| 3 | 25 | 10~25 | XFD-FJ-DT-1 | XFD-FJ-HD-1 | XFD-FJ-ZJ-1 |
| 4 | 35 | 10~35 | XFD-FJ-DT-1 | XFD-FJ-HD-1 | XFD-FJ-ZJ-1 |
| 5 | 50 | 10~50 | XFD-FJ-DT-1 | XFD-FJ-HD-1 | XFD-FJ-ZJ-2 |
| 6 | 70 | 10~70 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-2 |
| 7 | 95 | 10~95 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-2 |
| 8 | 120 | 10~120 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-2 |
| 9 | 150 | 10~150 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-3 |
| 10 | 185 | 10~185 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-3 |
| 11 | 240 | 10~185 | XFD-FJ-DT-2 | XFD-FJ-HD-2 | XFD-FJ-ZJ-3 |
| 12 | 300 | 10~185 | XFD-FJ-DT-3 | XFD-FJ-HD-3 | XFD-FJ-ZJ-4 |
| 13 | 400 | 10~185 | XFD-FJ-DT-3 | XFD-FJ-HD-3 | XFD-FJ-ZJ-4 |
| 14 | 500 | 10~185 | XFD-FJ-DT-3 | XFD-FJ-HD-3 | XFD-FJ-ZJ-4 |
| 15 | 630 | 10~185 | XFD-FJ-DT-4 | XFD-FJ-HD-4 | XFD-FJ-ZJ-5 |
| 16 | 800 | 10~185 | XFD-FJ-DT-4 | XFD-FJ-HD-4 | XFD-FJ-ZJ-5 |
使用导则
防水性能:分支连接部浸入水中,做工频电压试验及绝缘电阻试验,均通过。
工频耐压:3.5kV/5min无击穿闪络。
绝缘电阻≥200MΩ。
接触电阻不大于与分支器等长分支线基准电阻的1.2倍。
热稳定性:分支器不受连接件热胀冷缩的影响。
最小弯曲半径:R=20D,D为电缆外径。
导体额定工作温度:交联聚乙烯绝缘型90℃,聚氯乙烯绝缘型70℃。
安装间距:排列安装平行电缆中心距为2倍电缆外径,拧绞型电缆安装可相互接触,拧绞节距不大于100倍电缆外径。
敷设时的环境温度不低于0℃。
预分支电缆
设计选型原则
一般场所或设备的照明及动力输电干线系统,环境温度平均35C以下,选用“VV”型或“ZC-VV”型。
对消防有要求的场所或设备的照明及动力输电干线系统,环境温度平均35C以上,选用“YJV”型或“ZC-YJV”型。
对消防有特别要求的场所或设备的照明及动力输电干线系统,选用“N-YJV”型。
电缆规格选定,首先将每一楼层用户的用电负荷算出,得出楼层总负荷,根据给出的载流量参数查出分支截面;然后根据各楼层负荷算出总负荷查出主干线截面。(注:如算出总负荷大于1605A,可采用分区供电或交叉供电方案,一般情况尽量采用分区供电供电方案,将电缆截面减小,可降低一次投资。)
分支电缆的安装
排列安装竖井内预留孔的尺寸。(见下图)
安装前的准备工作
将竖井道内的垃圾清理干净。
将卷扬机放在需要安装电缆的顶层并固定好。
将电缆可靠的放在放线架上。
将每层分支连接器两侧的安装支架固定牢靠。
将顶端的横担及横担支架安装在与安装电缆同一面的墙面上。
电缆的安装
吊装:首先将卷扬机安装好,然后用卷扬机的钢丝绳拴住主电缆顶端的吊头,开始吊装,吊装时每层必须站一人,以防分支护套受预留孔阻碍而损伤。吊到顶后将吊头穿到挂钩的槽中,用螺栓穿过挂钩及吊头上的安装孔即可,用挂钩的螺母调节分支点的高度到合适的位置。
放装:采用放装时,在订货时要向制造厂提出,电缆在出厂卷绕时逆向卷绕。先将整盘电缆吊到顶层,将电缆可靠的放在放线架上,放线架必须有制动装置,然后每层站一人缓慢地将电缆放出,放到位置后将吊头挂在挂钩上,调节分支点的位置。
无论采用吊装还是放装方式,在全部吊好后8小时必须将主电缆固定在安装支架上。然后方可解开分支电缆,分支电缆如需弯曲,在弯曲两边需有安装支架固定。电缆的最小弯曲半径为R=20D,D为电缆外径。
施工中的注意事项
事先确认运送方式(车辆大小、停车场等)。
确认预制分支部位是否能安全通过贯通孔洞。
采取预防措施,防止提升过程中分支部分被贯通孔洞损伤。
防止提升过程中不要对分支施加张力。
使用提升用绳索的强度应为电缆重量的四倍以上。
单芯电缆禁止使用铁质夹具。
安装完成通电之前,必须用兆欧表测出吊头与电缆芯之间的绝缘电阻,如绝缘电阻小于100MΩ,要通知生产厂家进行检查。
检查端头的相位标记与分支部相位标记是否对应,检查无误方可通电。
订货须知
为了能根据客户要求提供合格的YFD系列分支电缆及附件,请提供下列资料:
配电间平面图、配电干线系统图、楼层标高图。
主干线电缆型号规格、分支线电缆型号规格及长度。
楼层配电箱距楼地板高度及进线方式。
安装配件型号、规格及数量。
安装方式,放装或吊装。
其他需要说明的事项。
额定电压0.6/1kV交联聚乙烯绝缘变频电缆
执行标准及应用范围
本产品执行企业Q/EAAF193-2023标准,阻燃耐火电缆应符合GB/T19666-2019。该电缆适用于交流额定电压0.6/1kV及以下变频控制系统作供电电缆或电气连接,具有较强的耐电压冲击性,能经受变频时的脉冲电压。电缆具有良好的屏蔽性,并有效消除电磁干扰,降低变频电机噪音,保证系统稳定运行,广泛用于造纸、冶金、电力、矿山、铁路、石化等行业。
型号及名称
| 型号 | 名称 |
| BPYJVP | 铜芯交联聚乙烯绝缘铜丝编织屏蔽聚氯乙烯护套变频电缆 |
| BPYJVP2 | 铜芯交联聚乙烯绝缘铜带绕包屏蔽聚氯乙烯护套变频电缆 |
| BPYJVP22 | 铜芯交联聚乙烯绝缘铜丝编织屏蔽钢带铠装聚氯乙烯护套变频电缆 |
| BPYJVP2-22 | 铜芯交联聚乙烯绝缘铜带绕包屏蔽钢带铠装聚氯乙烯护套变频电缆 |
2.阻燃电缆应符合本手册中《阻燃/耐火/无卤低烟阻燃电缆说明》的相关规定,阻燃电缆技术参数参考相同型号规格普通电缆。
结构特点
对称性设计:变频器与变频电机之间的电缆均需采用对称电缆结构,对称电缆结构有3芯和3+3芯两种,3+3芯电缆结构是将三大一小四芯绝缘线芯中第四芯(中性线芯)分解为三个截面较小的绝缘线芯,把三大三小线芯对称成缆。对称电缆结构由于导线的互换性,有更好的电磁相容性,对抑制电磁干扰起到一定的作用,能抵消高次谐彼中的奇次频率,提高变频电机专用电缆的抗干扰性,减少了整个系统中的电磁辐射。
屏蔽结构:变频电缆一般采用铜丝编织屏蔽或铜带绕包屏蔽,屏蔽电缆可抗电磁感应、接地不良和电源线传导干扰,减小电感,防止感应电动势过大。屏蔽层既起到抑制电磁波对外发射的作用,又可作为短路电流的通道,能起到中性线芯的保护作用。屏蔽层在安装时应当良好接地。
变频电缆
技术参数
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 参考重量(kg/km) | 载流量(A) |
| 3×1.5 | 0.7 | 1.8 | 10.2 | 143.1 | 20 |
| 3×2.5 | 0.7 | 1.8 | 11.0 | 179.6 | 27 |
| 3×4 | 0.7 | 1.8 | 12.0 | 233.3 | 35 |
| 3×6 | 0.7 | 1.8 | 13.1 | 301.4 | 45 |
| 3×10 | 0.7 | 1.8 | 15.4 | 451.8 | 63 |
| 3×16 | 0.7 | 1.8 | 17.5 | 639.0 | 84 |
| 3×25 | 0.9 | 1.8 | 21.8 | 975.7 | 113 |
| 3×35 | 0.9 | 1.8 | 24.0 | 1277.1 | 139 |
| 3×50 | 1.0 | 1.8 | 26.2 | 1634.0 | 161 |
| 3×70 | 1.1 | 1.9 | 30.3 | 2284.6 | 204 |
| 3×95 | 1.1 | 2.0 | 34.4 | 3105.2 | 252 |
| 3×120 | 1.2 | 2.2 | 38.3 | 3898.7 | 291 |
| 3×150 | 1.4 | 2.3 | 42.4 | 4768.2 | 333 |
| 3×185 | 1.6 | 2.4 | 47.2 | 5928.5 | 385 |
| 3×240 | 1.7 | 2.6 | 53.0 | 7657.0 | 457 |
| 规格芯数×截面(mm) | 绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 参考重量(kg/km) | 载流量(A) |
| 3×6+3×1.5 | 0.7/0.7 | 1.8 | 14.5 | 372.2 | 45 |
| 3×10+3×2.5 | 0.7/0.7 | 1.8 | 16.7 | 545.9 | 63 |
| 3×16+3×4 | 0.7/0.7 | 1.8 | 18.9 | 774.3 | 84 |
| 3×25+3×6 | 0.9/0.7 | 1.8 | 22.9 | 1158.9 | 113 |
| 3×35+3×6 | 0.9/0.7 | 1.8 | 24.5 | 1444.4 | 139 |
| 3×50+3×10 | 1.0/0.7 | 1.8 | 27.7 | 1939.1 | 161 |
| 3×70+3×16 | 1.1/0.7 | 2.0 | 32.5 | 2802.3 | 204 |
| 3×95+3×16 | 1.1/0.7 | 2.1 | 35.3 | 3555.1 | 252 |
| 3×120+3×25 | 1.2/0.9 | 2.2 | 40.4 | 4634.6 | 291 |
| 3×150+3×25 | 1.4/0.9 | 2.3 | 43.4 | 5460.2 | 333 |
| 3×185+3×35 | 1.6/0.9 | 2.5 | 48.5 | 6899.9 | 385 |
| 规格芯数×截面(mm) | 绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 参考重量(kg/km) | 载流量(A) |
| 3×1.5 | 0.7 | 1.8 | 10.3 | 149.2 | 20 |
| 3×2.5 | 0.7 | 1.8 | 11.0 | 186.4 | 27 |
| 3×4 | 0.7 | 1.8 | 12.0 | 241.2 | 35 |
| 3×6 | 0.7 | 1.8 | 13.1 | 310.2 | 45 |
| 3×10 | 0.7 | 1.8 | 15.5 | 464.2 | 63 |
| 3×16 | 0.7 | 1.8 | 17.6 | 653.6 | 84 |
| 3×25 | 0.9 | 1.8 | 21.8 | 994.8 | 113 |
| 3×35 | 0.9 | 1.8 | 24.1 | 1298.5 | 139 |
| 3×50 | 1.0 | 1.8 | 26.4 | 1664.2 | 161 |
| 3×70 | 1.1 | 1.9 | 30.5 | 2319.8 | 204 |
| 3×95 | 1.1 | 2.0 | 34.5 | 3105.8 | 252 |
| 3×120 | 1.2 | 2.2 | 38.3 | 3899.4 | 291 |
| 3×150 | 1.4 | 2.3 | 42.5 | 4769.0 | 33 |
| 3×185 | 1.6 | 2.4 | 47.2 | 5929.4 | 385 |
| 3×240 | 1.7 | 2.6 | 53.1 | 7657.9 | 457 |
| 规格芯数×截面i(mm) | 绝缘标称厚度(mm) | 护套标称厚度(mm) | 参考外径(mm) | 参考重量(kg/km) | 载流量(A) |
| 3×6+3×1.5 | 0.7/0.7 | 1.8 | 14.6 | 382.5 | 45 |
| 3×10+3×2.5 | 0.7/0.7 | 1.8 | 16.8 | 559.7 | 63 |
| 3×16+3×4 | 0.7/0.7 | 1.8 | 18.9 | 790.3 | 84 |
| 3×25+3×6 | 0.9/0.7 | 1.8 | 23.0 | 1179.1 | 113 |
| 3×35+3×6 | 0.9/0.7 | 1.8 | 24.5 | 1466.3 | 139 |
| 3×50+3×10 | 1.0/0.7 | 1.8 | 28.0 | 1971.2 | 161 |
| 3×70+3×16 | 1.1/0.7 | 2.0 | 32.6 | 2803.0 | 204 |
| 3×95+3×16 | 1.1/0.7 | 2.1 | 35.4 | 3555.7 | 252 |
| 3×120+3×25 | 1.2/0.9 | 2.2 | 40.5 | 4635.3 | 291 |
| 3×150+3×25 | 1.4/0.9 | 2.3 | 43.5 | 5461.0 | 333 |
| 3×185+3×35 | 1.6/0.9 | 2.5 | 48.6 | 6900.8 | 385 |
变频电缆
使用导则
额定电压U₀/U:0.6/1kV。
最高工作温度:交联聚乙烯90℃。
最低环境温度:聚氯乙烯护套电缆使用温度不低于-15℃,电缆敷设时最低温度不低于0℃。
电缆允许弯曲半径:电缆最小弯曲半径为电缆外径的15倍。
额定电压0.6/1kV\~26/35kV铝合金电力电缆
执行标准及应用范围
本产品执行GB/T31840-2015,是以AA8030系列铝合金材料为导体,采用特殊紧压工艺和退火处理等先进技术的一种新型节能环保电力电缆。具有使用寿命长、质量轻、性价比高等优点,可适用于钢铁、冶金、商业、工业、大型场馆、娱乐场所、光伏电站、风电发电站、地铁、房地产以及各类级别危险地区等场所。
型号及名称
| 型号 | 名称 |
| YJLHV | 铝合金导体交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| YJLHY | 铝合金导体交联聚乙烯绝缘聚乙烯护套电力电缆 |
| YYJLHVS | 铝合金导体交联聚乙烯绝缘铝合金带联锁铠装电力电缆 |
| YJLHVS2 | 铝合金导体交联聚乙烯绝缘铝合金带联锁铠装聚氯乙烯护套电力电缆 |
| YJLHVS3 | 铝合金导体交联聚乙烯绝缘铝合金带联锁铠装聚乙烯护套电力电缆 |
| YJLHV22 | 铝合金导体交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| YJLHY23 | 铝合金导体交联聚乙烯绝缘钢带铠装聚乙烯护套电力电缆 |
结构尺寸
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 1×16 | 0.7 | 9.0 | 98.4 | 13.2 | 156.2 | 16.2 | 248.9 |
| 1×25 | 0.9 | 10.2 | 134.5 | 14.4 | 197.8 | 17.4 | 298.2 |
| 1×35 | 0.9 | 11.2 | 166.4 | 15.4 | 234.1 | 18.4 | 340.7 |
| 1×50 | 1.0 | 12.3 | 208.0 | 16.5 | 281.0 | 19.7 | 403.4 |
| 1×70 | 1.1 | 14.2 | 286.8 | 18.4 | 368.0 | 21.8 | 511.9 |
| 1×95 | 1.1 | 16.0 | 374.3 | 20.0 | 456.1 | 23.4 | 612.0 |
| 1×120 | 1.2 | 17.5 | 458.0 | 21.5 | 545.9 | 25.1 | 723.0 |
| 1×150 | 1.4 | 19.5 | 564.7 | 23.3 | 651.6 | 26.9 | 842.4 |
| 1×185 | 1.6 | 21.6 | 696.3 | 25.4 | 822.4 | 29.2 | 1029.3 |
| 1×240 | 1.7 | 24.1 | 882.5 | 27.7 | 1009.6 | 31.7 | 1246.1 |
| 1×300 | 1.8 | 26.6 | 1093.7 | 30.0 | 1220.1 | 34.2 | 1488.9 |
| 1×400 | 2.0 | 29.7 | 1362.4 | 33.3 | 1526.3 | 37.7 | 1837.8 |
铝合金电缆
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 2×16 | 0.7 | 16.5 | 276.2 | 19.7 | 332.3 | 23.3 | 495.4 |
| 2×25 | 0.9 | 19.0 | 372.0 | 22.2 | 434.4 | 25.8 | 616.6 |
| 2×35 | 0.9 | 21.0 | 460.4 | 24.2 | 528.0 | 27.8 | 725.7 |
| 2×50 | 1.0 | 23.4 | 575.0 | 26.4 | 676.0 | 30.2 | 890.7 |
| 2×70 | 1.1 | 27.2 | 857.7 | 30.2 | 972.1 | 34.4 | 1242.5 |
| 2×95 | 1.1 | 31.0 | 1062.5 | 34.0 | 1203.4 | 38.4 | 1520.9 |
| 2×120 | 1.2 | 34.2 | 1319.3 | 37.0 | 1459.0 | 41.6 | 1819.7 |
| 2×150 | 1.4 | 38.0 | 1685.3 | 40.7 | 1823.2 | 45.5 | 2235.7 |
| 2×185 | 1.6 | 42.5 | 1977.8 | 47.3 | 2214.4 | 52.5 | 2733.0 |
| 2×240 | 1.7 | 47.5 | 2544.7 | 51.9 | 2766.2 | 57.5 | 3378.3 |
| 2×300 | 1.8 | 52.7 | 3216.5 | 57.1 | 3460.1 | 63.1 | 4180.6 |
| 2×400 | 2.0 | 59.0 | 3937.4 | 63.0 | 4158.6 | 69.4 | 5005.3 |
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 3×16 | 0.7 | 17.4 | 338.3 | 20.6 | 396.8 | 24.2 | 567.3 |
| 3×25 | 0.9 | 20.2 | 446.9 | 23.4 | 512.3 | 27.0 | 703.5 |
| 3×35 | 0.9 | 22.3 | 592.1 | 25.5 | 694.8 | 29.3 | 902.6 |
| 3×50 | 1.0 | 24.9 | 720.0 | 27.9 | 826.4 | 31.9 | 1065.2 |
| 3×70 | 1.1 | 29.2 | 957.2 | 32.0 | 1078.1 | 36.2 | 1363.5 |
| 3×95 | 1.1 | 33.0 | 1213.4 | 36.0 | 1362.5 | 40.6 | 1714.2 |
| 3×120 | 1.2 | 36.5 | 1511.7 | 39.3 | 1659.6 | 44.1 | 2058.9 |
| 3×150 | 1.4 | 40.8 | 2000.4 | 45.6 | 2172.2 | 50.8 | 2672.7 |
| 3×185 | 1.6 | 45.6 | 2416.9 | 50.2 | 2649.6 | 55.6 | 3220.5 |
| 3×240 | 1.7 | 51.0 | 3076.1 | 55.2 | 3290.7 | 61.0 | 3963.4 |
| 3×300 | 1.8 | 56.5 | 3812.8 | 60.7 | 4048.9 | 66.9 | 4839.5 |
| 3×400 | 2.0 | 63.3 | 4680.7 | 67.1 | 4890.2 | 73.9 | 5847.7 |
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 4×16 | 0.7 | 19.1 | 403.6 | 22.3 | 466.3 | 25.9 | 649.4 |
| 4×25 | 0.9 | 22.1 | 555.9 | 25.3 | 657.8 | 29.1 | 864.0 |
| 4×35 | 0.9 | 24.6 | 705.8 | 27.8 | 817.1 | 31.8 | 1054.4 |
| 4×50 | 1.0 | 27.7 | 907.5 | 30.5 | 1023.0 | 34.7 | 1295.9 |
| 4×70 | 1.1 | 32.4 | 1282.0 | 35.4 | 1428.6 | 39.8 | 1758.5 |
| 4×95 | 1.1 | 36.7 | 1616.1 | 39.5 | 1764.6 | 44.3 | 2165.7 |
| 4×120 | 1.2 | 40.7 | 1979.2 | 45.5 | 2150.7 | 50.7 | 2650.4 |
| 4×150 | 1.4 | 45.3 | 2401.4 | 49.9 | 2632.8 | 55.3 | 3200.5 |
| 4×185 | 1.6 | 50.9 | 3048.5 | 55.1 | 3262.9 | 60.9 | 3934.9 |
| 4×240 | 1.7 | 56.8 | 3800.5 | 61.1 | 4037.8 | 67.3 | 4832.4 |
| 4×300 | 1.8 | 63.0 | 4937.6 | 66.8 | 5146.4 | 73.4 | 6071.3 |
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm)) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 5×16 | 0.7 | 20.9 | 463.6 | 24.1 | 531.0 | 27.7 | 727.9 |
| 5×25 | 0.9 | 24.3 | 655.4 | 27.5 | 765.7 | 31.3 | 988.5 |
| 5×35 | 0.9 | 27.0 | 825.7 | 30.2 | 946.3 | 34.4 | 1217.1 |
| 5×50 | 1.0 | 30.6 | 1052.1 | 33.7 | 1191.7 | 38.1 | 1506.4 |
| 5×70 | 1.1 | 35.9 | 1565.2 | 38.7 | 1711.0 | 43.5 | 2104.6 |
| 5×95 | 1.1 | 40.9 | 2051.2 | 45.7 | 2223.2 | 50.9 | 2724.3 |
| 5×120 | 1.2 | 45.2 | 2481.7 | 49.8 | 2712.3 | 55.2 | 3278.1 |
| 5×150 | 1.4 | 50.5 | 3080.9 | 54.7 | 3293.8 | 60.5 | 3960.9 |
| 5×185 | 1.6 | 56.7 | 3832.4 | 60.9 | 4069.0 | 67.1 | 4861.3 |
| 5×240 | 1.7 | 63.3 | 4797.6 | 67.1 | 5007.1 | 73.7 | 5935.1 |
| 5×300 | 1.8 | 70.1 | 6118.8 | 73.9 | 6349.5 | 81.1 | 7465.1 |
铝合金电缆
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 3×16+1×10 | 0.7/0.7 | 18.5 | 383.1 | 21.7 | 444.4 | 25.3 | 623.3 |
| 3×25+1×16 | 0.9/0.7 | 21.4 | 521.2 | 24.6 | 589.8 | 28.2 | 790.6 |
| 3×35+1×16 | 0.9/0.7 | 23.2 | 645.0 | 26.4 | 751.2 | 30.2 | 966.0 |
| 3×50+1×25 | 1.0/0.9 | 26.2 | 836.1 | 29.2 | 947.1 | 33.2 | 1195.9 |
| 3×70+1×35 | 1.1/0.9 | 30.4 | 1163.1 | 33.6 | 1314.5 | 38.0 | 1628.6 |
| 3×95+1×50 | 1.1/1.0 | 34.6 | 1458.1 | 37.4 | 1599.1 | 42.0 | 1963.4 |
| 3×120+1×70 | 1.2/1.1 | 38.7 | 1851.2 | 41.3 | 1991.0 | 46.1 | 2409.5 |
| 3×185+1×95 | 1.6/1.1 | 47.5 | 2714.6 | 51.9 | 2936.0 | 57.5 | 3547.8 |
| 3×240+1×120 | 1.7/1.2 | 53.0 | 3369.4 | 57.4 | 3614.1 | 63.4 | 4337.8 |
| 3×300+1×150 | 1.8/1.4 | 58.8 | 4329.0 | 62.8 | 4549.6 | 69.2 | 5394.0 |
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 3×16+2×10 | 0.7/0.7 | 19.9 | 419.1 | 23.1 | 483.7 | 26.7 | 672.6 |
| 3×25+2×16 | 0.9/0.7 | 22.9 | 586.5 | 26.1 | 691.6 | 29.9 | 904.0 |
| 3×35+2×16 | 0.9/0.7 | 24.6 | 695.7 | 27.8 | 807.0 | 31.6 | 1031.8 |
| 3×50+2×25 | 1.0/0.9 | 28.1 | 898.7 | 30.9 | 1015.7 | 35.1 | 1291.9 |
| 3×70+2×35 | 1.1/0.9 | 32.4 | 1277.0 | 35.4 | 1423.6 | 39.8 | 1753.5 |
| 3×95+2×50 | 1.1/1.0 | 36.8 | 1720.4 | 39.4 | 1854.2 | 44.2 | 2254.8 |
| 3×120+2×70 | 1.2/1.1 | 41.5 | 2138.6 | 46.3 | 2312.9 | 51.5 | 2820.5 |
| 3×185+2×95 | 1.6/1.1 | 50.3 | 3162.9 | 54.6 | 3375.2 | 60.4 | 4040.8 |
| 3×240+2×120 | 1.7/1.2 | 56.1 | 3899.9 | 60.3 | 4134.4 | 66.5 | 4919.8 |
| 3×300+2×150 | 1.8/1.4 | 62.4 | 4778.9 | 66.2 | 4985.7 | 72.8 | 5901.7 |
| 规格芯数×截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY | YJLHS | YJLHS2、YJLHS3 | |||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 4×16+1×10 | 0.7/0.7 | 20.4 | 441.3 | 23.6 | 507.3 | 27.2 | 700.1 |
| 4×25+1×16 | 0.9/0.7 | 23.6 | 620.9 | 26.8 | 728.6 | 30.6 | 946.3 |
| 4×35+1×16 | 0.9/0.7 | 25.8 | 760.7 | 29.0 | 876.7 | 33.0 | 1124.0 |
| 4×50+1×25 | 1.0/0.9 | 29.3 | 969.3 | 32.5 | 1115.8 | 36.9 | 1420.0 |
| 4×70+1×35 | 1.1/0.9 | 34.2 | 1419.0 | 37.0 | 1558.8 | 41.6 | 1919.9 |
| 4×95+1×50 | 1.1/1.0 | 38.7 | 1877.7 | 41.3 | 2017.7 | 46.1 | 2436.8 |
| 4×120+1×70 | 1.2/1.1 | 43.4 | 2318.5 | 48.0 | 2541.3 | 53.4 | 3088.3 |
| 4×185+1×95 | 1.6/1.1 | 53.5 | 3496.4 | 57.9 | 3743.3 | 63.9 | 4473.4 |
| 4×240+1×120 | 1.7/1.2 | 59.7 | 4330.2 | 63.7 | 4553.7 | 70.1 | 5408.9 |
| 4×300+1×150 | 1.8/1.4 | 66.2 | 5314.8 | 69.9 | 5506.1 | 76.7 | 6501.4 |
| 标称截面(mm²) | YJLHV、YJLHY 0.6/1kV 1芯 | YJLHV、YJLHY 0.6/1kV 2-5芯,YJLHS、YJLHS2、YJLHS3 0.6/1kV 1-5芯 | ||
| 敷设方式 | 空气中 | 土壤中 | 空气中 | 土壤中 |
| 导体工作温度 | 90℃ | |||
| 环境温度 | 40℃ | 25℃ | 40℃ | 25℃ |
| 16 | 78 | 90 | 70 | 100 |
| 25 | 100 | 111 | 95 | 125 |
| 35 | 125 | 135 | 115 | 145 |
| 50 | 150 | 165 | 140 | 180 |
| 70 | 190 | 200 | 200 | 230 |
| 95 | 230 | 245 | 220 | 270 |
| 120 | 270 | 286 | 250 | 300 |
| 150 | 310 | 325 | 290 | 340 |
| 185 | 360 | 375 | 330 | 375 |
| 240 | 400 | 435 | 400 | 435 |
| 300 | 455 | 505 | 455 | 505 |
| 400 | 525 | 580 | 525 | 565 |
铝合金电缆
| 规格芯数x截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY-8.7/15kV | |
| 参考外径(mm) | 参考重量(kg/km) | ||
| 1×25 | 4.5 | 21.1 | 461 |
| 1×35 | 4.5 | 22.3 | 510 |
| 1×50 | 4.5 | 23.0 | 566 |
| 1×70 | 4.5 | 24.8 | 674 |
| 1×95 | 4.5 | 26.4 | 789 |
| 1×120 | 4.5 | 28.0 | 902 |
| 1×150 | 4.5 | 29.4 | 1012 |
| 1×185 | 4.5 | 31.1 | 1170 |
| 1×240 | 4.5 | 33.5 | 1389 |
| 1×300 | 4.5 | 35.6 | 1617 |
| 1×400 | 4.5 | 38.3 | 1929 |
| 1×500 | 4.5 | 41.6 | 2315 |
| 1×630 | 4.5 | 45.0 | 2929 |
| 规格芯数x截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY-26/35kV | |
| 参考外径(mm) | 参考重量(kg/km) | ||
| 1×50 | 10.5 | 23.0 | 566 |
| 1×70 | 10.5 | 24.8 | 674 |
| 1×95 | 10.5 | 26.4 | 789 |
| 1×120 | 10.5 | 28.0 | 902 |
| 1×150 | 10.5 | 29.4 | 1012 |
| 1×185 | 10.5 | 31.1 | 1170 |
| 1×240 | 10.5 | 33.5 | 1389 |
| 1×300 | 10.5 | 35.6 | 1617 |
| 1×400 | 10.5 | 38.3 | 1929 |
| 规格芯数x截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY-8.7/15kV | YJLHV22、YJLHY23-8.7/15kV | ||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 3×25 | 4.5 | 43.4 | 1635 | 48.3 | 2629 |
| 3×35 | 4.5 | 45.7 | 1815 | 50.6 | 2841 |
| 3×50 | 4.5 | 47.4 | 2048 | 52.5 | 3147 |
| 3×70 | 4.5 | 51.0 | 2405 | 56.1 | 3581 |
| 3×95 | 4.5 | 54.7 | 2818 | 59.9 | 4107 |
| 3×120 | 4.5 | 57.9 | 3194 | 63.3 | 4578 |
| 3×150 | 4.5 | 61.1 | 3593 | 66.5 | 5051 |
| 3×185 | 4.5 | 64.7 | 4104 | 70.5 | 5706 |
| 3×240 | 4.5 | 69.8 | 4868 | 77.0 | 7294 |
| 3×300 | 4.5 | 74.7 | 5706 | 81.9 | 8302 |
| 3×400 | 4.5 | 80.4 | 6763 | 88.0 | 9630 |
| 3×500 | 4.5 | 87.5 | 8037 | 95.2 | 11170 |
| 3×630 | 4.5 | 94.7 | 9905 | 102.8 | 13713 |
额定电压26/35kV交联聚乙烯绝缘铝合金电力电缆1芯结构尺寸(YJLHV、YJLHY、YJLHV22、YJLHY23)
| 规格芯数x截面(mm²) | 绝缘标称厚度(mm) | YJLHV、YJLHY-26/35kV | YJLHV22、YJLHY23-26/35kV | ||
| 参考外径(mm) | 参考重量(kg/km) | 参考外径(mm) | 参考重量(kg/km) | ||
| 3×50 | 10.5 | 74.9 | 4316 | 82.3 | 6967 |
| 3×70 | 10.5 | 78.5 | 4815 | 86.1 | 7622 |
| 3×95 | 10.5 | 82.2 | 5340 | 89.7 | 8280 |
| 3×120 | 10.5 | 85.4 | 5804 | 93.1 | 8887 |
| 3×150 | 10.5 | 88.6 | 6288 | 96.5 | 9525 |
| 3×185 | 10.5 | 92.4 | 6952 | 100.1 | 10280 |
| 3×240 | 10.5 | 97.3 | 7807 | 105.4 | 11385 |
| 3×300 | 10.5 | 102.2 | 8756 | 110.4 | 12559 |
| 3×400 | 10.5 | 107.9 | 9986 | 116.4 | 14052 |
产品特性
导电率铝合金的导电率是常用基准材料铜IACS的61.8%,载流量是铜的79%。但在同样体积下,铝合金的实际重量大约是铜的三分之一。因此,相同载流量时铝合金电缆的重量大约是铜芯电缆的一半。采用铝合金电缆取代铜芯电缆,可以减轻电缆重量,降低安装成本,减少设备和电缆的磨损,使安装工作更轻松。
电缆重量在满足同等电气性能的前提下,使用铝合金电缆的重量是铜芯电缆的一半,其截面是传统铜芯电缆的1.1~1.25倍,价格比传统铜芯电缆低20~30%。
国家扶持政策及发展趋势铝合金电缆已获国家政策层面大力支持,据有关报道,国家工信部已明确表态将支持铝合金电缆产业的发展,将其纳入新材料范畴,列入国家《产业调整指导目录》。国家层面开始大力支持铝合金电缆行业的发展,国家住建部2012年4月1日正式实施的国家行业标准JGJ242-2011《住宅建筑电气设计规划》明确了铝合金电缆与铜电缆相同的使用地位。各省建设管理部门也相继颁布了铝合金应用相关地方标准。国内行业管理部门已开始制定铝合金单线和铝合金电力电缆的相关国家标准和行业标准,很快将颁布实施。
产品性能介绍
安全性、可靠性高
历史证明美国自1968年研发出铝合金电缆到使用至今50多年,从未发生任何故障,通过这50多年的使用与验证,该种产品是安全的,正因为它的安全性,让北美区域的国家使用该种产品已正当普遍,市场占有率达到80%。
权威性部门检测报告证明经过中国最权威的国家电线电缆检测中心、国网武汉高压研究所、国家防火建筑材料质量监督检验中心的检测。
合金成份的添加导体的合金成分大大改进了其连接性能。尤其是当导体退火时添加的铁产生了高强度抗蠕变性能,在电流过载时,铁发挥作用,持续的连接,而不会使铝合金导体发生蠕变。
电气性能优
载流量的实现当合金导体的截面积是铜的1.5倍时,其电气性能相同,即实现了和铜相同的载流量、电阻和电压损失。
线路损耗低非磁性材料,不会产生涡流,能减少线路的损耗。铝合金带连锁铠装材料是非磁性材料,即使存在三相不平衡电流,也不会产生涡流,能够减少线路的损耗。
成品轮廓截面的减小最先进的分层紧压技术,其导体的填充系数能达到89%以上。
机械性能优
高延伸伸长率是导体机械性能重要指标,是关系产品优劣和能承受外力大小的重要标志。也是电缆导体检验的一个重要指标。铝合金导体退火处理后的延伸率能达到30%以上,而铜芯电缆的伸长率规定为25%(普通铝杆的伸长率为1.5%),是能取代铝芯电缆与铜芯电缆的重要指标。
强柔韧扭转试验:主要检验金属线材的韧性。韧性越好,能承受的扭转的次数越多。普通铝丝的一个重要缺点是脆度高,在安装时只要几次一定角度的扭转,导体就会产生裂纹,裂纹会增加接触电阻,是出现火灾的重要原因。使用铝合金电缆,由于它的韧性好,不会产生裂纹,在安装中出现安全的隐患减少。铝合金电缆比铜芯电缆反弹性能减少40%。经过特殊处理的铝合金电缆柔韧性得以大幅度提高,比铜芯电缆提高25%。
易弯曲弯曲试验:主要检验金属的抗弯曲性能。材质不均或性脆的材料,抗弯曲性能差。根据GB/T12706中对铜芯电缆安装时弯曲半径的规定,铜芯电缆的弯曲半径是12~20倍电缆直径,铝合金电缆的弯曲半径最小为7倍电缆直径,使用铝合金电缆减少了安装布局的空间,减小了安装成本,更易于敷设。
稳定连接合金中的铁产生高强度抗蠕变性能可保证其连接稳定性。
低反弹在室温条件下将铜芯电缆与铝合金电缆弯曲90度,应力释放后,铝合金电缆反弹角度是铜芯电缆的60%。因铝合金电缆具有记忆力,所以反弹性能优于铜芯电缆,在安装过程中,更有利于端子连接接头处的紧密程度,易于压紧提高连接的稳定性。
经济性能优
性价比高综合以上性能描述与铜芯电缆的对比,要想取代铜芯电缆,铝合金电缆的价格成本与铜芯电缆的比较就显得犹为重要,而铝合金电缆的价格只有铜电缆的40%左右。
安装成本的节约由于铝合金电缆的弯曲半径更小和重量更轻,特别是采用铝合金带连锁铠装电缆安装不用桥架,不用穿管,节约大量的钢材,安装成本可以减少20%~50%。
产品性能对比
| 电缆类型 | 铝合金电缆 | 铜芯电缆 | 铝芯电缆 | 备注 |
| 导体材质 | AA8030 铝合金 | 电工铜 | 电工铝 | |
| 导体抗折断性 | 优 | 优 | 差 | 铝合金导体中由于Fe、Cu、Mg、Si等元素的添加,增强了铝的韧性 |
| 设计寿命 | 40年 | 30年 | 30年 | |
| 载流量 | 相当 | 相当 | 相当 | 通过适当选型 |
| 电缆重量 | 轻 | 重 | 轻 | 同等载流量时,铝合金电缆重量是铜芯电缆的一半 |
| 电缆直径 | 中 | 小 | 大 | 同等载流量时 |
| 弯曲半径 | 7D | 12D~15D | 12D~15D | D为电缆直径 |
| 安装方便性 | 优 | 一般 | 一般 | 铝合金电缆重量轻、易弯曲、反弹小 |
| 经济性 | 优 | 差 | 中 | 合金电缆比铜芯电缆的价格大约低30%50%,安装高效,节省人力和时间 |
| 电压降 | 相当 | 相当 | 相当 | 通过适当选型 |
| 防腐蚀性 | 优 | 差 | 优 | 铝合金中加入的稀土等化学元素可以增加铝合金的耐腐蚀性能,增加耐电化学腐蚀性能 |
| 抗蠕变性能 | 优 | 优 | 差 | 铝合金中Fe加强了其抗蠕变性能 |
| 接头连接稳定性 | 优 | 优 | 差 | 铝合金中Fe、Cu和Mg起了主要作用 |
| 铠装 | 联锁铠装 | 钢装铠装 | 钢带铠装 | 減少施工难度,降低人工成本 |
| 回弹性 | 低 | 高 | 低 | 回弹量越低施工越方便,合金电缆比铜芯电缆约低40% |
A、加入适量Cu,提高了热稳定性;B、加入适量Fe,消除了蠕变,并增加了强度;C、加入适量Mg,增加了导体连接的接触点,减少电阻发热;D、加入适量稀土元素,能起到净化、提高纯度、填补表层缺陷、细化晶粒、减少偏析,消除显微不均而导致的局部腐蚀,从而大大提高了铝的耐腐蚀性能。
通过数据对比,我们可以得出:铝合金电缆综合的电气性能、机械性能、安装性能和经济性能是铜芯电缆无法比拟的,可根据截流量大小选择合适的铝合金电缆代替铜芯电缆。
使用特性
电缆导体的长期允许工作温度为90℃。
短路时(最长时间5S)电缆导体的最高温度不超过250℃。
铠装电缆最小弯曲半径为电缆直径的7倍。
额定电压1kV及以下架空绝缘电缆
生产标准及应用范围
本产品执行GB/T12527-2008及企业标准,适用于额定电压0.6/1kV及以下架空电力线路中,可作为固定敷设或引户线。该产品是在紧压铜、铝、铝合金、钢芯铝绞线芯导体外挤制耐候型高密度聚乙烯和耐候型聚氯乙烯绝缘,电缆安全可靠,同时又具有优良的机械物理性能和电气性能、耐电痕、耐沿面放电、耐大气等优点。电缆敷设间隙小,节约线路走廊,线路电压减小,能减少供电事故发生,确保人身安全,适用于山区、林区、矿区、城市等场合,是全天候的电缆产品。
| 型号 | 名称 | 用途架空固定敷设。电缆架设时,应考虑电缆和树木保持一定距离,电缆运行时,允许电缆和树木频繁接触 |
| JKYJ | 铜芯交联聚乙烯绝缘架空电缆 | |
| JKLYJ | 铝芯交联聚乙烯绝缘架空电缆 | |
| JKLHYJ | 铝合金芯交联聚乙烯绝缘架空电缆 | |
| JKLGYJ | 钢芯铝绞线芯交联聚乙烯绝缘架空电缆 | |
| JKTRYJ | 软铜芯交联聚乙烯绝缘架空电缆 | 用于变压器引下线 |
结构性能与要求
导体
应采用紧压圆形绞合硬铜、硬铝、铝合金或钢芯铝绞线导体,其中铜导体应采用TY型硬铜圆线,并符合GB/T3953的规定;铝导体应采用LY8或LY9型硬圆铝线,并符合GB/T3955的规定;铝合金和钢芯铝绞线导体应符合GB/T1179的规定。导体的结构尺寸,机械拉断力及导体电阻应符合GB/T12527的规定。作为变压器引下线用的架空电缆应采用TR型软铜圆线,并符合GB/T3953的规定。导体表面应光洁,无油污,无损伤屏蔽及绝缘的毛刺,锐边,以及凸起或断裂的单线。
绝缘
应采用交联聚乙烯绝缘,绝缘性能应符合GB/T12527的要求,绝缘料应采用黑色耐候料。绝缘表面应平整,色泽均匀。普通绝缘结构电缆绝缘厚度平均值不小于标称值,最薄处厚度应不小于标称值的90%-0.1mm。
架空绝缘电缆
结构尺寸
铜芯、软铜芯、铝芯、铝合金芯架空绝缘电缆结构尺寸(JKYJ、JKTRYJ、JKLYJ、JKLHYJ-1kV)
| 标称截面(mm) | 绝缘标称厚度(mm) | 参考外径nr) | 参考重量 (kg/km) | |
| JKYJ、JKTRYJ、JKLYJ、JKLHYJ-1kV | JKYJ、JKTRYJ-1kV | JKLYJ、JKLHYJ-1kV | ||
| 10 | 1.0 | 5.9 | 106.2 | 41.4 |
| 16 | 1.2 | 7.3 | 162.9 | 64.7 |
| 25 | 1.2 | 8.5 | 250.5 | 94.3 |
| 35 | 1.4 | 9.9 | 342.6 | 129.8 |
| 50 | 1.4 | 11.1 | 467.1 | 168.0 |
| 70 | 1.4 | 12.6 | 651.6 | 230.4 |
| 95 | 1.6 | 14.9 | 913.2 | 317.2 |
| 120 | 1.6 | 16.3 | 1143.5 | 391.0 |
| 150 | 1.8 | 18.1 | 1346.6 | 481.9 |
| 185 | 2.0 | 20.3 | 1647.1 | 604.2 |
| 240 | 2.2 | 23.1 | 2146.7 | 786.6 |
| 300 | 2.2 | 25.2 | 2850.9 | 961.7 |
| 400 | 2.2 | 28.1 | 3520.4 | 1211.5 |
钢芯铝绞线芯架空绝缘电缆结构尺寸(JKLGYJ-1kV)
| 铝芯/钢芯标称截面(mm) | 绝缘标称厚度(mm) | 参考外径(mm) | 参考重量 (kg/km) |
| JKLGYJ-1kV | JKLGYJ-1kV | ||
| 10/2 | 1.0 | 6.2 | 56 |
| 16/3 | 1.2 | 7.7 | 87 |
| 25/4 | 1.2 | 9.1 | 130 |
| 35/6 | 1.4 | 10.6 | 178 |
| 50/8 | 1.4 | 11.9 | 235 |
| 70/10 | 1.4 | 13.7 | 325 |
| 95/15 | 1.6 | 16.1 | 447 |
| 120/20 | 1.6 | 17.6 | 549 |
| 150/20 | 1.8 | 19.4 | 641 |
| 185/25 | 2.0 | 21.7 | 809 |
| 240/30 | 2.2 | 24.5 | 1053 |
| 300/40 | 2.2 | 26.8 | 1288 |
| 型号 | JKYJ、JKLYJ、JKLHYJ、JKLGYJ、JKTRYJ-1kV | |||||
| 芯数 | 单芯 | |||||
| 导体 | 铜芯 | 铝芯/钢芯铝绞线芯 | 铝合金芯 | 铜芯 | 铝芯/钢芯铝绞线芯 | 铝合金芯 |
| 截面(mm) | 不受太阳照射 | 直接受太阳照射 | ||||
| 10 | 87 | 68 | 64 | 82 | 64 | 61 |
| 16 | 115 | 93 | 87 | 110 | 87 | 82 |
| 25 | 155 | 125 | 115 | 145 | 115 | 110 |
| 35 | 195 | 150 | 145 | 180 | 140 | 135 |
| 50 | 240 | 185 | 175 | 220 | 175 | 165 |
| 70 | 300 | 235 | 225 | 280 | 220 | 215 |
| 95 | 375 | 295 | 275 | 345 | 270 | 255 |
| 120 | 435 | 345 | 320 | 405 | 315 | 300 |
| 150 | 505 | 395 | 370 | 465 | 365 | 345 |
| 185 | 585 | 460 | 430 | 535 | 425 | 400 |
| 240 | 695 | 550 | 515 | 640 | 505 | 475 |
日照强度取1000(W/m²)。
单芯电缆间距取200(mm)。
电缆表面吸收系数:交联聚乙烯取0.4。
环境温度不同于基准温度下载流量修正系数为:
| 导体温度(°C) | 环境温度 (C) | |||||||||
| 10 | 15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | |
| 90 | 1.32 | 1.26 | 1.21 | 1.16 | 1.11 | 1.05 | 1.00 | 0.93 | 0.89 | 0.80 |
额定电压10kV及以下架空绝缘电缆
执行标准及应用范围
产品执行GB/T14049-2008及企业标准,适用于额定电压10kV及以下架空电力线路中,可作为固定敷设或引户线。该产品是在紧压铜、铝、铝合金、钢芯铝绞线芯导体外挤制耐候型绝缘,电缆安全可靠,同时又具有优良的机械物理性能和电气性能、耐电痕、耐沿面放电、耐大气等优点。电缆敷设间隙小,节约线路走廊,线路电压减小,能减少供电事故发生,确保人身安全,适用于山区、林区、矿区、城市等场合,是全天候的电缆产品。
| 型号 | 名称 | 用途 |
| JKYJ | 铜芯交联聚乙烯绝缘架空电缆 | 架空固定敷设。电缆架设时,应考虑电缆和树木保持一定距离,电缆运行时,允许电缆和树木频繁接触 |
| JKLYJ | 铝芯交联聚乙烯绝缘架空电缆 | |
| JKLHYJ | 铝合金芯交联聚乙烯绝缘架空电缆 | |
| JKLGYJ | 钢芯铝绞线芯交联聚乙烯绝缘架空电缆 | |
| JKTRYJ | 软铜芯交联聚乙烯绝缘架空电缆 | 用于变压器引下线 |
结构性能与要求
导体
应采用紧压圆形绞合硬铜、硬铝、铝合金或钢芯铝绞线导体,其中铜导体应采用TY型硬铜圆线,并符合GB/T3953的规定;铝导体应采用LY8或LY9型硬圆铝线,并符合GB/T3955的规定;铝合金和钢芯铝绞线导体应符合GB/T1179的规定。导体的结构尺寸,机械拉断力及导体电阻应符合GB/T14909的规定。作为变压器引下线用的架空电缆应采用TR型软铜圆线,并符合GB/T3953的规定。导体表面应光洁,无油污,无损伤屏蔽及绝缘的毛刺,锐边,以及凸起或断裂的单线。
导体屏蔽
导体表面除轻型薄绝缘结构外,电缆必须具有导体屏蔽,所用半导电料为交联型,半导电屏蔽层应均匀地包覆在导体上,表面应光滑,无明显绞线凸纹,不应有尖角、颗粒、烧焦或擦伤的痕迹,半导电屏蔽料性能应符合GB/T14049的规定。
绝缘
绝缘应采用交联聚乙烯绝缘,绝缘性能应符合GB/T14049的要求,绝缘料应采用黑色耐候料。绝缘应紧密地挤包在导体屏蔽层上,绝缘表面应平整,色泽均匀。普通绝缘结构电缆绝缘厚度标称值应不小于3.4mm,最薄处厚度应不小于标称值的90%-0.1mm。
结构尺寸
| 标称截面(m) | 绝缘标称厚度(mm) | 参考外径 (mm) | 参考重量(kg/km) | |
| JKYJ、JKTRYJ、JKLYJ、JKLHYJ-10kV | JKYJ、JKTRYJ-10kV | JKLYJ、JKLHYJ-10kV | ||
| 10 | 3.4 | 11.9 | 123.6 | 194.0 |
| 16 | 3.4 | 12.9 | 151.4 | 256.2 |
| 25 | 3.4 | 14.1 | 192.0 | 356.1 |
| 35 | 3.4 | 15.1 | 230.1 | 3701.4 |
| 50 | 3.4 | 16.3 | 278.2 | 1063.9 |
| 70 | 3.4 | 17.8 | 352.8 | 1510.7 |
| 95 | 3.4 | 19.8 | 452.1 | 2309.8 |
| 120 | 3.4 | 21.3 | 537.0 | 452.8 |
| 150 | 3.4 | 22.7 | 628.1 | 788.8 |
| 185 | 3.4 | 24.4 | 750.5 | 588.7 |
| 240 | 3.4 | 26.8 | 934.6 | 1310.0 |
| 300 | 3.4 | 28.9 | 1122.4 | 1808.8 |
| 400 | 3.4 | 31.8 | 1389.7 | 3012.4 |
| 铝芯/钢芯标称截面(mm) | 绝缘标称厚度(mm) | 参考外径 (mm) | 参考重量 (kg/km) |
| JKLGYJ-10kV | JKLGYJ-10kV | ||
| 10/2 | 3.4 | 12.0 | 140 |
| 16/3 | 3.4 | 13.1 | 177 |
| 25/4 | 3.4 | 14.5 | 232 |
| 35/6 | 3.4 | 15.6 | 284 |
| 50/8 | 3.4 | 16.9 | 351 |
| 70/10 | 3.4 | 18.7 | 456 |
| 95/15 | 3.4 | 20.9 | 592 |
| 120/20 | 3.4 | 22.4 | 706 |
| 150/20 | 3.4 | 23.8 | 798 |
| 185/25 | 3.4 | 25.7 | 966 |
| 240/30 | 3.4 | 28.1 | 1210 |
| 300/40 | 3.4 | 30.4 | 1460 |
架空绝缘电缆
| 型号 | JKYJ、JKLYJ、JKLHYJ、JKLGYJ、JKTRYJ-10kV | |||||
| 芯数 | 单芯 | |||||
| 导体 | 铜芯 | 铝芯/钢芯铝绞线芯 | 铝合金芯 | 铜芯 | 铝芯/钢芯铝绞线芯 | 铝合金芯 |
| 截面(mm) | 不受太阳照射 | 直接受太阳照射 | ||||
| 10 | 98 | 77 | 72 | 90 | 71 | 66 |
| 16 | 125 | 100 | 95 | 120 | 94 | 88 |
| 25 | 170 | 135 | 125 | 155 | 120 | 115 |
| 35 | 205 | 160 | 150 | 190 | 150 | 140 |
| 50 | 250 | 195 | 185 | 230 | 180 | 170 |
| 70 | 315 | 245 | 230 | 285 | 225 | 210 |
| 95 | 380 | 300 | 280 | 350 | 275 | 260 |
| 120 | 445 | 350 | 330 | 405 | 320 | 300 |
| 150 | 510 | 400 | 375 | 465 | 365 | 345 |
| 185 | 585 | 460 | 435 | 535 | 420 | 395 |
| 240 | 695 | 550 | 515 | 635 | 500 | 470 |
| 300 | 805 | 635 | 615 | 735 | 580 | 560 |
日照强度取1000(W/m²)。
单芯电缆间距取200(mm)。
电缆表面吸收系数:交联聚乙烯取0.4。
环境温度不同于基准温度下载流量修正系数为:
| 导体温度(°C) | 环境温度 (C) | |||||||||
| 10 | 15 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | |
| 90 | 1.32 | 1.26 | 1.21 | 1.16 | 1.11 | 1.05 | 1.00 | 0.93 | 0.89 | 0.80 |
轨道交通1500V及以下直流牵引电力电缆
执行标准及应用范围
本产品执行国标GB/T28429-2012《轨道交通1500V及以下直流牵引电力电缆及附件》。
轨道交通电缆是随着城市交通的发展而诞生的一种新型特种电线电缆产品。它可广泛用于城市架空轻轨、地铁、地面铁道、隧道、地下防空工程、机车车辆、高速铁路等。轨道交通电缆有直流和交流两种,直流牵引用轨道交通电缆一般为单芯1500V及750V,有铠装型和非铠装型。轨道交通电缆通过合理的结构设计和原材料的选用,具有低烟、无卤、阻燃、防水、防昆虫噬咬及防紫外线等多种功能,满足人流密集、设施重要场合对电缆清洁、环保、阻燃等特殊要求。
型号及名称
| 名称 | 型号 | 电压等级 | 规格(mm) |
| 铜芯乙丙橡胶绝缘铝塑综合护层聚烯烃护套直 流牵引电力电缆 | GD-EA3 | 750V | 95-400 |
| 1500V | |||
| 铜芯交联聚乙烯绝缘铜带铠装聚烯烃护套直流 牵引电力电缆 | GD-YJY33 | 750V | 95-400 |
| 1500V |
结构尺寸
| 标称截面(mm) | 20C时导体直流电阻Ω/km | 导体参考外径(mm) | 标称绝缘厚度(mm) | 标称护套厚度(mm) | 参考外径(mm) | 工作电容(μF/km) | 参考重量(kg/km) |
| 95 | 0.193 | 11.4 | 2.0 | 1.8 | 22.0 | 0.462 | 1234 |
| 120 | 0.153 | 12.9 | 2.0 | 1.8 | 23.5 | 0.515 | 1474 |
| 150 | 0.124 | 14.4 | 2.0 | 1.8 | 25.0 | 0.567 | 1740 |
| 185 | 0.0991 | 16.1 | 2.0 | 1.8 | 26.8 | 0.626 | 2122 |
| 240 | 0.0754 | 18.5 | 2.0 | 1.9 | 29.5 | 0.710 | 2700 |
| 300 | 0.0601 | 20.6 | 2.0 | 1.9 | 31.8 | 0.783 | 3285 |
| 400 | 0.0470 | 23.3 | 2.0 | 2.0 | 35.0 | 0.878 | 4102 |
轨道交通电缆
| 标称截面(mm) | 20C时导体直流电阻(Ω/km) | 导体参考外径(mm) | 标称绝缘厚度(mm) | 标称护套厚度(mm) | 参考外径(mm) | 工作电容(μF/km) | 参考重量(kg/km) |
| 95 | 0.206 | 13.3 | 2.4 | 1.8 | 25.1 | 0.541 | 1336 |
| 120 | 0.161 | 15.3 | 2.4 | 1.8 | 27.2 | 0.570 | 1481 |
| 150 | 0.129 | 17.3 | 2.4 | 1.9 | 29.1 | 0.681 | 1909 |
| 185 | 0.106 | 18.9 | 2.4 | 1.9 | 31.1 | 0.737 | 2132 |
| 240 | 0.0801 | 21.8 | 2.4 | 2.0 | 34.6 | 0.838 | 2700 |
| 300 | 0.0641 | 24.4 | 2.4 | 2.1 | 37.1 | 0.929 | 3307 |
| 400 | 0.0486 | 27.9 | 2.6 | 2.2 | 41.1 | 0.976 | 4361 |
使用导则
电缆导体正常运行时的最高温度为90C,短路时最高温度不超过250℃(最长持续时间不超过5s)。
电缆径向阻水试验(15℃\~30℃,72h):绝缘层无水纹。
电缆燃烧性能:满足GB/T19666规定的成束燃烧A类试验,满足GB31247-2014规定的燃烧性能B1级,燃烧滴落 物达到d0级,烟气毒性达到t0级,腐蚀性能达到a1级。
电气性能:通过直流6.5kV/5min耐压试验,4U₀的4h浸水耐压试验,峰值40kV的冲击电压试验绝缘不击穿。
护套材料燃烧时的PH值≥4.3;护套材料燃烧时的电导率≤10μs/mm;电缆燃烧时烟密度试验:透光率≥60%。
防护性能:防白蚁达到1级,防鼠效果优良,满足1008h的人工气候老化试验。
采用乙丙橡胶绝缘的电缆固定敷设时最小弯曲半径6D(D为电缆直径),采用交联聚乙烯绝缘的电缆固定敷设时最小弯曲半径20D。
电气化铁路27.5kV单相交流交联聚乙烯绝缘电缆
执行标准及应用范围
本产品执行国标GB/T28427-2012《电气化铁路27.5kV单相交流交联聚乙烯绝缘电缆及附件》。电气化铁路的供电系统(又称牵引供电系统)是将电能从电力系统传送给电力机车的电力装置的总称,其主要由牵引变电所和接触网两大部分组成。牵引变电所将电力系统输电线路电压从110kV(或220kV)降到27.5kV,经馈电线将电能送至接触网;接触网沿铁路上空架设,电力机车升弓后便可从其取得电能,用以牵引列车。产品适用于额定电压为27.5kV的电气化铁道供电线、自藕变压器供电线以及牵引所、分区所、开闭所、自藕变压器所引出的馈电线等,具有电缆承载短路电流能力强、防水性能优异、安全性能和环保性能等优异特点。
型号及名称
| 型号 | 名称 | 额定电压 | 规格 (mm) |
| TDDD-YJY72 | 铜芯交联聚乙烯绝缘铝丝铠装低烟低卤阻燃护套电力电缆 | 27.5kV | 150-400 |
| TDWD-YJY73 | 铜芯交联聚乙烯绝缘铝丝铠装低烟无卤阻燃护套电力电缆 | 27.5kV | 150-400 |
结构尺寸
| 型号 | 标称截面(m) | 绝缘标称厚度(mm) | 参考外径(mm) | 参考重量(kg/km) | 导体 20C直流电阻(Ω/km) |
| TDDD-YJY72、TDWD-YJY7327.5kV | 150 | 11.0 | 59.1 | 4710 | 0.124 |
| 185 | 11.0 | 61.6 | 5180 | 0.0991 | |
| 240 | 11.0 | 64.0 | 5861 | 0.0754 | |
| 300 | 11.0 | 67.8 | 6809 | 0.0601 | |
| 400 | 11.0 | 71.0 | 7958 | 0.0470 |
| 标称截面(mm) | 150 | 185 | 240 | 300 | 400 |
| 最大允许故障短路电流 (kA) | 21.4 | 26.4 | 34.3 | 42.9 | 57.2 |
| 额定电压(U) | 例行电压 | 局部放电试验 | 电缆 4h 电压试验 | 冲击试验后工频耐压试验 | 冲击电压试验 | |
| 电压 | 时间 | |||||
| U。kV | 3.5U。kV | min | 1.73U。kV | 4U。kV | 2.5U。kV | kV |
| 27.5 | 97 | 5 | 48 | 110 | 69 | 250 |
允许持续载流量
| 序号 | 敷设条件 | 单位 | 标称截面(mm) | ||||
| 150 | 185 | 240 | 300 | 400 | |||
| 1 | 1) 电缆导体工作温度:90℃2) 环境温度:40℃3) 敷设在空气中4) 平面排列,电缆中心间距为 2D5) 金属屏蔽和铠装单端接地 | A | 490 | 565 | 665 | 760 | 890 |
| 2 | 1)电缆导体工作温度:90℃2)环境温度:25℃3)敷设在土壤中,热阻系数为1.04)平面排列,电缆中心间距为2D5)金属屏蔽和铠装单端接地 | A | 425 | 485 | 565 | 635 | 730 |
| 3 | 1) 电缆导体工作温度:90C2)环境温度:40℃3)敷设在空气管道中4) 平面排列,电缆中心间距为 2D5)金属屏蔽和铠装单端接地 | A | 385 | 440 | 520 | 590 | 685 |
| 4 | 1)电缆导体工作温度:90℃2)环境温度:25℃3)敷设在土壤管道中4)平面排列,电缆中心间距为 2D5)金属屏蔽和铠装单端接地 | A | 370 | 420 | 490 | 560 | 640 |
| 导体工作温度(C) | 环境温度(空气中)(℃) | |||||||
| 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 | |
| 90 | 1.23 | 1.17 | 1.12 | 1.06 | 1.00 | 0.94 | 0.87 | 0.81 |
| 导体工作温度(C) | 环境温度(土壤中)(C) | |||||
| 10 | 15 | 20 | 25 | 30 | 35 | |
| 90 | 1.11 | 1.07 | 1.04 | 1.00 | 0.96 | 0.92 |
| 电压(kV) | 土壤热阻系数(K.m/W) | |||
| 0.8 | 1.0 | 1.2 | 1.5 | |
| 27.5 | 1.06 | 1.0 | 0.94 | 0.80 |
使用特性
电缆额定电压27.5kV。
电缆在正常运行时导体允许的长期最高温度为90℃;短路时(最长持续时间不超过5s),电缆导体允许的最高温度为250℃。
安装时电缆最小弯曲半径为15倍电缆外径。
低卤低烟阻燃电缆要求:烟气最小透光率≥30%,燃烧时释放气体的PH值≥2.5,电导率≤30μs/mm,卤酸气体逸出量≤100mg/g。无卤低烟阻燃电缆要求:烟气最小透光率≥60%,燃烧时释放气体的PH值≥4.3,电导率≤10μs/mm。
电缆符合GB/T18380.35 C类阻燃特性要求。
电缆具有径向防水性能。
电缆不允许敷设在铁质管道中,允许在非磁性管道中敷设。
阻燃/耐火/无卤低烟阻燃电缆说明
概述
随着科技不断进步及对安全需求的提高,在各类型建筑中,对于电线电缆的安全提出了更高的要求。公司在原有电线电缆产品基础上,衍生出阻燃、耐火、阻燃耐火、无卤低烟阻燃、无卤低烟阻燃耐火等各类型电线电缆。
型号组成
阻燃、耐火、阻燃耐火、无卤低烟阻燃、无卤低烟阻燃电线电缆的型号由产品燃烧特性代号和相关电线电缆型号两部分组成:
产品燃烧特性代号说明
| 系列名称 | 代号 | 名称 | 执行标准 | |
| 阻燃系列 | 有卤 | ZAZBZCZDb | 阻燃A 类阻燃B类阻燃C类阻燃D类 | GB/T19666-2005 |
| 无卤 | WDZªWDZAWDZBWDZCWDZDb | 无卤低烟阻燃无卤低烟阻燃A类无卤低烟阻燃B类无卤低烟阻燃C类无卤低烟阻燃D类 | ||
| 耐火系列 | 有卤 | NZANZBNZCNZDN | 耐火阻燃 A 类耐火阻燃 B 类耐火阻燃C 类耐火阻燃 D 类耐火 | |
| 无卤 | WDZNWDZANWDZBNWDZCNWDZDN | 无卤低烟阻燃耐火无卤低烟阻燃 A 类耐火无卤低烟阻燃 B 类耐火无卤低烟阻燃 C 类耐火无卤低烟阻燃 D 类耐火 | ||
阻燃电缆特性
1. 阻燃电缆(ZA-、ZB-、ZC-、ZD-)
阻燃电缆在着火后不延燃,应用于核电站、地下设施、隧道、高层建筑及广播电视台等场合。
阻燃电线电缆应同时符合表2阻燃性能要求(单根)和表3阻燃性能要求(成束)。
| 代号 | 名称 | 性能 | 合格指标 | 试验方法 |
| Z | 阻燃 | 单根阻燃性能 | 试样烧焦应不超过距上夹具下缘 | IEC60332-1、GB/T18380.1、 |
| 要求 | 50mm〜540mm的范围之外 | GB/T18380.2 |
| 代号 | 名称 | 试样非金属材料体积/ (L/m) | 供火时间/s | 合格指标 | 试验方法 |
| ZA | 阻燃A类 | 7 | 40 | 1) 试样上炭化的长度不应超过距喷嘴底边向上2.5m;2)停止供火后试样上的有焰燃烧时间不应超过1h | IEC60332-3、GB/T18380.3 |
| ZB | 阻燃B类 | 3.5 | 40 | ||
| ZC | 阻燃C类 | 1.5 | 20 |
2. 耐火电缆(N-)
耐火电缆在着火情况下仍能保持一定时间内继续运行,特别适用于火灾报警和紧急照明线路。不推荐铝芯及铝合金耐火电线电缆,因铝及铝合金熔点仅为660°C,低于耐火电缆耐火测试温度750C的要求。
耐火性能必须符合表4的要求:
| 代号 | 名称 | 供火时间+冷却时间/min | 试验电压/V | 合格指标 | 试验方法 |
| N | 耐火 | 90+15 | 额定值 | 1)2A 熔断器不断;2)指示灯不熄 | IEC60331-21、GB/T19216.21 |
3. 阻燃耐火电缆(ZAN-、ZBN-、ZCN-、ZDN-)
阻燃耐火电缆适用于火灾报警和消防设备、通讯排烟设备及紧急通道运输、照明等应急设施的供电线路中要求耐火的场合。
阻燃耐火电缆应同时符合阻燃电缆和耐火电缆要求。
4. 无卤低烟阻燃电缆(WDZA-、WDZB-、WDZC-、WDZD-)
无卤低烟阻燃电缆具有无卤、低烟、阻燃、低毒、能见度高等优良特点,特别适用于地铁、地下商场、高层建筑、车站、电站等人流密集、安全要求高的场合。
无卤低烟阻燃电缆阻燃特性符合阻燃电缆要求,表卤特簍表5要求,低烟特性符合表6要求。
| 代号 | 名称 | pH加权值 | 电导率加权值/μ s/mm | 试验方法 |
| W | 无卤 | ≥4.3 | ≤10 | IEC60754-2、GB/T17650.2 |
| 代号 | 名称 | 最小透光率 | 试验方法 |
| D | 低烟 | ≥60% | IEC61034-2、GB/T17651.2 |
5. 无卤低烟阻燃耐火电缆(WDZAN-、WDZBN-、WDZCN-、WDZDN-)
无卤低烟阻燃耐火电缆具有无卤、低烟、阻燃、耐火、低毒、能见度高等优良特点,特别适用于地铁、地下商场、高层建筑、车站、电站等人流密集、安全要求高的场合,特别适用于火灾报警和紧急照明线路。
无卤低烟阻燃耐火电缆燃烧特性符合无卤低烟阻燃电缆要求,耐火特性符合表4要求。
电缆安装注意事项
电缆安装应由专职人员担任,电缆安装时需注意以下事项:
运输、保管
电缆应避免在露天存放,电缆盘不允许平放。
运输途中严禁从高处扔下装有电缆的电缆盘,严禁机械损伤电缆。
吊装电缆时,严禁几盘同时吊装。在车辆、船舶等运输工具上,电缆盘必须放稳并固定,防止互撞和翻倒。
电缆存放时,应仔细检查端头是否密封,严防端头进水或吸潮。
安装前的准备
1.检验电缆
除了环境温度低于电缆允许敷设温度外,一般电缆盘需提前搬运到施工现场。在搬运前,核对电缆盘上标识,如电压、截面、型号等是否符合工程设计书上的要求。
2.穿越道路导管
电缆线路全长中经常需要穿越多处公共道路或桥梁等场所,为了避免牵引电缆时对公共交通的影响,横越道路部分的一般事先埋置多孔导管。导管顶部一般不少于地坪1m,导孔孔数需留有50%的备用孔。
3.材料工具
为了缩短为敷设电缆所开挖的电缆沟对公众交通影响的时间,所需的材料如:电缆盘、电缆保护砖盖板、标志牌或带以及各类施工工具,如电缆滚轮、汲水泵、牵引卷扬机、电缆盘支架以及安全牌等需在敷设电缆前送至施工现场电动工具在搬运前要进行检查,防止使用时失灵和浪费牵引电缆时间。
4.人员组织
敷设电缆需要统一指挥又需明确分工,通常电缆盘的管理为一组,土方的挖掘为一组,卷扬机、牵引为另一组,此外辅以接头和测绘组。
5.注意事项
敷设电缆前,电缆线路通过的建筑结构,施工应完毕,应检查电缆沟及隧道等土建部分转弯处的弯曲半径是否符合要求,为了减少差错,在电缆支架、沟道、隧道、坚井的进出口,转弯处和适当部位应挂上电缆敷设断面图。塑料电缆在低温下将变硬。这种变硬的电缆不易弯曲,敷设时,电缆的塑料绝缘易损坏。因此冬季施工,如果电缆存放地点在敷设前24h内的平均温度以及敷设现场的温度低于0℃及以下时,应采取措施将电缆预热升温后才能敷设。电缆预热的方法有两种,一种是提高周围空气温度的方法,即将电缆放在有暖气的室内(或装有防火电炉的帐蓬里),使室内温度提高以加热电缆。这种方法需要时间较长,室内温度为5一10℃时,需要72h,室内温度为25℃时,需要24—36h。另一种方法是电流加热法,用电流通过电缆导线来加热。加热电流不能大于电缆额定电流。电流加热法所用设备一般是小容量的三相低压变压器或交流电焊机,高压侧额定电压为380V,低压侧能提供加热电缆所需的电流。加热时,将电缆一端三相导电线芯短接,另一端接至变压器低压侧。电源部分应有可以调节电压的装置和适当的保险设备,以防电缆过载而损伤。加热过程中,电缆的表面温度不超过40C。加热后电缆表面的温度应根据各地气候条件来决定,但不得低于5℃。电缆加热后应尽快敷设,放置时间不宜超过1h。
电缆望缆明敷设一般采用的方法有支架、吊架、托盘、桥架、钢索等方式。明敷设电缆不宜交叉敷设,要排列整齐,当其水平安装除首末和转弯支架上设固定卡子,交流单芯电缆及分相后的分相铅包电缆不应采用铁质夹具固定。托盘、桥架水平敷设时电缆要排放在里面,当托盘和桥架垂直布置时,同样要用固定件把电缆加以固定。
2.电缆在敷设,在电缆的两端和电缆接头端设置标志牌,在上面有明显的线路编号并写明型号、规格和起止位置,如电缆线路并联,那么还应有电缆的顺序号,字迹应清楚,标志牌要统一规格,挂靠牢固,不易腐蚀。
3.明敷设电缆相互间距尺寸,无铠装电缆在室内明敷设于非专用层间时,水平安装至地面距离不应小于2.5m,垂直安装时不应小于1.8m,1kV和1kV以上的电力电缆和控制电缆应分开安装,如并行安装时,其净距离不应小于150mm。明敷设电缆与热力管道的净距离不应小于1m,如小于1m则要加隔热措施,与一般管道的净距离不应小于0.5m。
4.当电缆沿墙外穿过楼板层时或垂直安装在距地面1.8m以下部分时应加保护管以防机械损伤。
5.电缆在放线前应检查电缆的绝缘电阻,合格后才能敷设,用托架将电缆架空,应注意将电缆从盘的上端引出,不应从下部引出,在电缆落地部位开始设置滚轮,将电缆放置在滚轮上,再用人力或机械牵引,以防电缆被地面摩擦损坏保护层,滚轮之间距离一般为2.5m。
电缆暗敷设
通常采用管道内敷设,电缆沟敷设等,电缆管道通常用钢管、塑料管等,管道质量要过关,内壁光滑无毛刺等不良现象,管道弯曲半径不应小于所穿入电缆允许的弯曲半径的规定。
1.电缆穿管敷设
每一根管只能穿一根电缆,而交流电的单芯电缆不应穿钢管敷设。
裸铠装控制电缆不能和其它外护套的电缆穿入同一根管内。
入陶土管、混凝土管中的电缆,最好使用塑料护套电缆或钢带外护层的电缆。
电缆在电缆沟内敷设时,电缆沟应考虑有排水措施,在沟底一般有不小于0.5%的坡度,将积水排入下水道。
2.电缆敷设在支架上
电缆敷设在支架上除按本节一般要求外,尚应注意下列几点:
电缆托架与热表面(如管道保护层)的距离不得小于200mm,电缆托架之间的垂直距离不得小于250mm。
当同一侧电缆支架上敷设几种电压等级的电力电缆时,应按电压等级的高低自上层往下层排列。电力电缆和控制电缆一般应分开排列,当电力电缆和控制电缆敷设在同一侧的支架上时,应将电力电缆放在控制电缆的上面。如果布置在同一托架上,但电缆之间的距离不得小于150mm。
垂直电缆支架装设在交通道旁边时,应设保护罩将电缆支架保护起来。保护高度距地面至少2m。保护罩应考虑空气流通,使电缆有足够的自然通风。
在可能积水、积尘、积油的电缆沟中,电缆应敷设于电缆架上。
敷设电缆时,一般先将电缆平放在靠近电缆支架的地上,然后自首端逐段将电缆托上支架,这样敷设效率高。电缆终端头和中间接头附近应留有备用长度。
在隧道及沟道内敷设电缆后,应及时清除杂物,盖好盖板。可能有水、油、灰侵入的地方,应将盖板的缝隙封堵。
3.直埋于地下的电缆敷设
直埋电缆必须埋于冻土层以下。为了防止电缆遭受损坏,电缆的埋设深度应不小于0.7m,穿越农田时应不小于1m。
电缆与管道及建筑物问的最小距离应符合下表的要求。
| 序号 | 项目 | 最小允许净距 (m) | 备注 | ||
| 平行 | 交叉 | ||||
| 1 | 电力电缆之间及其与控制电缆间 | 10kV及以下 | 0.10 | 0.50 | 当电缆穿管或用隔板隔开时,平行净距可降低为0.1m,交叉净距可降低为0.25m |
| 10kV及以上 | 0.25 | 0.50 | |||
| 2 | 热管道及热力设备 | 2.00 | 0.50 | ① 应采取隔热措施,使电缆周围土壤的温升不超过10℃;② 当交叉净距不能满足要求时,可将电缆穿入管中,其净距可减为0.25m。 | |
| 3 | 油管道 | 1.00 | 0.50 | ||
| 4 | 可燃气体及易燃液体管道 | 1.00 | 0.50 | ||
| 5 | 其他管道 | 0.50 | 0.50 | ||
| 6 | 铁路路轨 | 3.00 | 1.00 | ||
| 7 | 电气化铁路路轨 | 交流 | 3.00 | 1.00 | |
| 直流 | 10.00 | 1.00 | 如不能满足要求,应采取适当防蚀措施 | ||
| 8 | 公路 | 1.50 | 1.00 | ||
| 9 | 城市街道路面 | 1.00 | 0.70 | ||
| 10 | 建筑物基础 | 0.60 | -- | ||
| 11 | 排水沟 | 1.00 | 0.50 | ||
生产基地:长沙市普瑞西路一段888号衡阳市黄白路121号服务热线:400-8856-919网址:www.hengfeicable.com