| 标称截面 Nominal Cross- section (mm2) | 电压等级Voltage | |||||||
| 18/30kV | 21/35kV | |||||||
| 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | |||
| 空气 In air | 埋地 Under ground | 空气 In air | 埋地 Under ground | |||||
| 1×50 | 32.4 | 1319 | 245 | 225 | 35.4 | 1622 | 245 | 225 |
| 1×70 | 34.1 | 1571 | 305 | 275 | 37.1 | 1906 | 305 | 275 |
| 1×95 | 35.9 | 1883 | 370 | 330 | 38.9 | 2227 | 370 | 330 |
| 1×120 | 37.3 | 2162 | 425 | 375 | 40.3 | 2538 | 425 | 375 |
| 1×150 | 39.1 | 2487 | 475 | 415 | 42.1 | 2860 | 475 | 415 |
| 1x185 | 40.7 | 2878 | 540 | 465 | 43.7 | 3135 | 540 | 465 |
| 1×240 | 43.1 | 3484 | 630 | 535 | 46.1 | 3929 | 630 | 535 |
| 1×300 | 45.5 | 4133 | 710 | 595 | 48.5 | 4579 | 710 | 595 |
| 1×400 | 49.3 | 5035 | 810 | 670 | 52.5 | 5551 | 810 | 670 |
| 1×500 | 53.5 | 6266 | 910 | 740 | 58.2 | 7097 | 910 | 740 |
| 1×630 | 57.1 | 7709 | 1020 | 820 | 61.8 | 8591 | 1020 | 820 |
| 3×50 | 66.9 | 4604 | 180 | 190 | 73.3 | 5665 | 180 | 190 |
| 3×70 | 70.7 | 5384 | 220 | 230 | 77.1 | 6624 | 220 | 230 |
| 3×95 | 74.4 | 6399 | 265 | 275 | 80.8 | 7848 | 265 | 275 |
| 3×120 | 77.8 | 7312 | 305 | 315 | 84.0 | 8839 | 305 | 315 |
| 3×150 | 81.4 | 8367 | 345 | 355 | 87.6 | 9972 | 345 | 355 |
| 3×185 | 85.1 | 9769 | 390 | 400 | 91.5 | 11295 | 390 | 400 |
| 3×240 | 90.0 | 11702 | 455 | 460 | 96.4 | 13385 | 455 | 460 |
| 3×300 | 95.2 | 13778 | 525 | 520 | 101.6 | 15525 | 525 | 520 |
| 3×400 | 103.3 | 16703 | 600 | 590 | 110.1 | 18676 | 600 | 590 |
| 标称截面 Cross- section (mm2) | 电压等级Voltage | |||
| 26/35kV | ||||
| 参考外径 Reference O.D | 参考重量 Reference Weight (kg/km) | Recommended current cpacity(A) | 载流量 | |
| (mm) | 埋地 Under ground | |||
| 1×50 | 26.2 | 1022 | 245 | 225 |
| 1×70 | 28.1 | 1273 | 305 | 275 |
| 1×95 | 29.7 | 1535 | 370 | 330 |
| 1×120 | 31.3 | 1832 | 425 | 375 |
| 1×150 | 32.9 | 2108 | 475 | 415 |
| 1×185 | 34.7 | 2519 | 540 | 465 |
| 1×240 | 37.1 | 3083 | 630 | 535 |
| 1×300 | 39.3 | 3691 | 710 | 595 |
| 1×400 | 43.3 | 4576 | 810 | 670 |
| 1×500 | 47.5 | 5763 | 910 | 740 |
| 1×630 | 51.5 | 7172 3398 | 1020 | 820 |
| 3×50 | 53.6 57.4 | 4181 | 180 | 190 |
| 3×70 | 61.3 | 5122 | 220 265 | 230 |
| 3×95 3×120 | 64.5 | 5997 | 305 | 275 |
| 68.1 | 7007 | 345 | 315 | |
| 3×150 | 71.8 | 8313 | 355 | |
| 3×185 | 10031 | 390 | 400 | |
| 3×240 | 76.9 81.9 | 11995 | 455 | 460 |
| 3×300 | 525 | 520 | ||
| 3×400 | 90.5 | 14986 | 600 | 590 |
| 标称截面 Cross- section (mm2) | 电压等级Voltage | |||||||
| 3.6/6kV 参考外径 参考重量 载流量 | 6/10kV 参考重量 载流量 | |||||||
| Reference O.D (mm) | Reference Weight (kg/km) | Recommended current cpacity(A) | 参考外径 Reference O.D (mm) | Reference Weight (kg/km) | Recommended current cpacity(A) | |||
| 空气 In air | 埋地 Under ground | 空气 In air | 埋地 Under ground | |||||
| 1×25 | 21.3 | 765 | 160 | 160 | 22.9 | 839 | 170 | 160 |
| 1×35 | 22.3 | 886 | 190 | 195 | 23.9 | 963 | 205 | 190 |
| 1×50 | 23.6 | 1042 | 225 | 230 | 25.2 | 1122 | 245 | 225 |
| 1×70 | 25.3 | 1286 | 275 | 280 | 26.9 | 1370 | 305 | 275 |
| 1×95 | 26.9 | 1573 | 330 | 330 | 28.5 | 1660 | 370 | 330 |
| 1×120 | 28.3 | 1844 | 375 | 375 | 29.9 | 1935 | 430 | 375 |
| 1×150 | 30.1 | 2157 | 425 | 420 | 31.7 | 2252 | 485 | 420 |
| 1×185 | 31.7 | 2539 | 480 | 475 | 33.3 | 2638 | 550 | 470 |
| 1×240 | 34.3 | 3142 | 555 | 545 | 36.9 | 3573 | 645 | 540 |
| 1×300 | 38.5 | 4173 | 630 | 610 | 39.5 | 4253 | 730 | 605 |
| 1×400 | 42.6 | 5145 | 725 | 685 | 43.4 | 5221 | 840 | 680 |
| 3×25 | 39.5 | 2419 | 121 | 140 | 43.2 | 2735 | 121 | 135 |
| 3×35 | 42.1 | 2863 | 145 | 165 | 45.5 | 3119 | 145 | 165 |
| 3×50 | 45.1 | 3376 | 170 | 195 | 48.7 | 3764 | 170 | 190 |
| 3×70 | 49.1 | 4280 | 210 | 240 | 52.8 | 4625 | 210 | 240 |
| 3×95 | 52.8 | 5233 | 265 | 285 | 56.4 | 5591 | 265 | 285 |
| 3×120 | 56.4 | 6193 | 300 | 325 | 60.0 | 6554 | 300 | 320 |
| 3×150 | 60.2 | 7208 | 340 | 370 | 63.7 | 7567 | 340 | 365 |
| 3×185 | 63.9 | 8462 | 390 | 415 | 67.5 | 8864 | 390 | 410 |
| 3×240 | 69.7 | 10456 | 455 | 480 | 72.9 | 10893 | 455 | 480 |
| 3×300 | 75.9 | 12636 | 520 | 545 | 78.2 | 13039 | 520 | 540 |
| 3×400 | 87.1 | 16618 | 600 | 615 | 88.4 | 16824 | 600 | 610 |
| 标称截面 Nominal Cross- section (mm2) | 电压等级Voltage | |||||||
| 8.7/15kV | 12/20kV | |||||||
| 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | |||
| 空气 In air | 埋地 Under ground | 空气 In air | 埋地 Under ground | |||||
| 1×25 | 24.7 | 925 | 170 | 160 | 二 | 二 | 二 | |
| 1×35 | 25.9 | 1063 | 205 | 190 | 28.3 | 1195 | 205 | 190 |
| 1×50 | 27.2 | 1225 | 245 | 225 | 29.6 | 1362 | 245 | 225 |
| 1×70 | 29.1 | 1491 | 305 | 275 | 31.3 | 1621 | 305 | 275 |
| 1×95 | 30.7 | 1787 | 370 | 330 | 33.1 | 1937 | 370 | 330 |
| 1×120 | 32.3 | 2080 | 430 | 375 | 34.7 | 2237 | 430 | 375 |
| 2388 | 420 | 37.5 | 485 | 420 | ||||
| 1×150 | 33.9 36.9 | 3135 | 485 | 470 | 39.3 | 2895 3327 | 555 | 470 |
| 1×185 1×240 | 39.1 | 3745 | 550 645 | 540 | 41.7 | 3964 | 645 | 540 |
| 41.5 | 4415 | 605 | 44.3 | 4669 | 735 | 605 | ||
| 1×300 | 45.4 | 5395 | 730 | 680 | 48.0 | 835 | ||
| 1×400 | 48.3 | 3260 | 840 | 135 | 5642 - | 680 | ||
| 3×25 | 50.6 | 126 | 56.0 | 二 | 二 | |||
| 3×35 | 53.8 | 3687 4285 | 150 | 165 190 | 59.2 | 4196 4810 | 150 180 | 160 |
| 3×50 | 57.7 | 5170 | 180 220 | 240 | 63.0 | 5691 | 220 | 190 235 |
| 3×70 3×95 | 61.7 | 6192 | 265 | 285 | 66.9 | 6733 | 265 | 285 |
| 65.2 | 7149 | 310 | 320 | 70.3 | 7727 | 310 | 320 | |
| 3×120 | 68.8 | 8197 | 365 | 73.9 | 8832 | 350 | 365 | |
| 3×150 | 72.7 | 9518 | 350 | 410 | 78.0 | 10292 | 400 | 410 |
| 3×185 | 78.0 | 11446 | 400 | 480 | 84.5 | 13008 | 465 | 475 |
| 3×240 | 84.5 | 14400 | 465 | 540 | 89.7 | 15207 | 535 | 535 |
| 3×300 3×400 | 93.3 | 17545 | 535 615 | 610 | 98.7 | 18595 | 615 | 605 |
| 标称截面 Nominal Cross- section (mm2) | 电压等级Voltage | |||||||
| 18/30kV | 21/35kV | |||||||
| 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | |||
| 空气 In air | 埋地 Under ground | 空气 In air | 埋地 Under ground | |||||
| 1×50 | 38.2 | 2248 | 245 | 225 | 35.2 | 2281 | 245 | 225 |
| 1×70 | 40.1 | 2565 | 305 | 275 | 36.9 | 2597 | 305 | 275 |
| 1×95 | 41.7 | 2906 | 370 | 330 | 38.7 | 2952 | 370 | 330 |
| 1x120 | 43.3 | 3243 | 425 | 375 | 40.1 | 3290 | 425 | 375 |
| 1x150 | 45.1 | 3620 | 475 | 415 | 41.7 | 3640 | 475 | 415 |
| 1×185 | 46.9 | 4078 | 540 | 465 | 43.5 | 4116 | 540 | 465 |
| 1×240 | 49.3 | 4749 | 630 | 535 | 45.7 | 4789 | 630 | 535 |
| 1x300 | 51.7 | 5469 | 710 | 595 | 47.9 | 5478 | 710 | 595 |
| 1×400 | 55.2 | 6468 | 810 | 670 | 51.6 | 6519 | 810 | 670 |
| 3×50 | 72.9 | 6430 | 180 | 190 | 80.9 | 7048 | 180 | 190 |
| 3×70 | 76.7 | 7313 | 220 | 230 | 84.9 | 8885 | 220 | 230 |
| 3×95 | 80.6 | 8467 | 265 | 275 | 88.6 | 10213 | 265 | 275 |
| 3×120 | 85.4 | 10323 | 310 | 315 | 92.2 | 11302 | 310 | 315 |
| 3x150 | 89.0 | 11513 | 350 | 355 | 96.0 | 12546 | 350 | 355 |
| 3×185 | 92.9 | 13102 | 400 | 400 | 99.7 | 13968 | 400 | 400 |
| 3×240 | 98.2 | 15320 | 465 | 460 | 105.0 | 16213 | 465 | 460 |
| 3×300 | 103.4 | 17601 | 535 | 520 | 110.2 | 18499 | 535 | 520 |
| 3×400 | 111.9 | 20928 | 615 | 590 | 119.1 | 21883 | 615 | 590 |
| 标称我面 Cross- section | 电压等级 Voltage | |||
| 26/35kV | ||||
| 参考外径 Reference | 参考重量 Reference (kg/km) | Recommended current cpacity(A) | 载流量 | |
| (mm) | 埋地 Under ground | |||
| 1×50 | 42.6 | 2561 | 245 | 225 |
| 1×70 | 44.5 | 2888 | 305 | 275 |
| 1×95 | 46.1 | 3235 | 370 | 330 |
| 1×120 | 47.7 | 3581 | 425 | 375 |
| 1×150 | 49.5 | 3968 | 475 | 415 |
| 1x185 | 51.3 | 4435 | 540 | 465 |
| 1×240 | 53.5 | 5095 | 630 | 535 |
| 1×300 | 56.1 | 5851 | 710 | 595 |
| 1×400 | 59.8 | 6894 | 810 | 670 |
| 3×50 | 86.0 | 8725 | 180 | 190 |
| 3×70 | 90.1 | 9849 | 220 | 230 |
| 3×95 | 93.7 | 11169 12347 | 265 | 275 |
| 3×120 | 97.4 101.2 | 13640 | 310 | 315 |
| 3×150 | 104.9 | 15097 | 350 | 355 |
| 3×185 | 400 | 400 | ||
| 3×240 | 110.2 | 17404 | 465 | 460 |
| 3×300 | 115.3 | 19758 | 535 | 520 |
| 3×400 | 124.3 | 23242 | 615 | 590 |
0.6/1kV 铝芯聚氯乙烯绝缘聚氯乙烯护套电力电缆(含普通型、阻燃型)
N-VV22 4芯电缆
产品特点及用途
铝芯聚氯乙烯绝缘聚氯乙烯护套电力电缆具有良好的电气性能和化学稳定性,结构简单,使用方便,本产品适用于交流额定电压U0/U为0.6/1kV及以下的输配电线路上
阻燃型电缆的主要特点是电缆不易着火或着火时延燃仅局限在一定上范围内,适用于电缆敷设密集程度高的发电站、地铁、隧道、高层建筑、大型工矿企业、油田、煤矿等场所。
产品标准
本产品按GB/T l2706.1或IEC60502标准组织生产,还可按用户要求的其它标准生产。阻燃型电缆除上述标准外,其阻燃性能按GB/T19666标准规定分成A、B、C、D四种不同的阻燃级别,A级别的阻燃性能最优,用户可根据需要选用。
产品型号
| VLV | 铝芯聚氯乙烯绝缘聚氯乙烯护套电力电缆(含普通型、阻燃型) |
| VLV22 | 铝芯聚氯乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型、阻燃型) |
◆阻燃型电缆型号,在普通电缆型号前加Z(A、B、C、D)
产品使用特性
(1)额定电压Uo /U为 0.6/1\mathsf{k V}_{\circ}
(2)电缆导体的最高额定温度为 170°\mathsf C. 。
(3)短路时(最长持续时间不超过5秒)电缆导体的最高温度,导体截面 <=300\mathsf{mm}^{2} 不超过 160°\mathsf C ;导体截面 >300\mathsf{mm}^{2} 不超过 140°\mathsf C 。
(4)电缆敷设时的环境温度应不低于 0°C ,其最小弯曲半径如下:单芯电缆— *20(\mathsf{D}+\mathsf{d}) ,mm多芯电缆— *15(\mathsf{D}+\mathsf{d}) ,mm(D、d分别为电缆外径与主导体的标称直径,mm)
注:括号内数值适用于截面大于 300\mathsf{mm}2
主要技术参数
电缆载流量计算条件
环境温度 25°C
电缆导体工作温度 90°\mathsf{C}
电缆埋地敷设时,土壤热阻系数g \mathsf{\Omega}_{\mathsf{I}=1.0°\mathsf{C}\mathsf{m}/\mathsf{W}} ,但尚未考虑电缆长期运行时由于水份迁移导致土壤热阻系数升高的现象。电缆埋地敷设时,电缆的轴心与地面距离为 1000\mathsf{mm} 。
多根电缆敷设时,电缆的轴心距离 S=30
| section | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||||||||||||||
| 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯4+1芯 | 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯4+1芯 | 空气 | Singie-core | Multile-cores | ||||
| Under ground | 空气 | Unter | ||||||||||||||||||
| ground | ||||||||||||||||||||
| 10 16 | 9.1 10.2 | 16.2 18.5 | 17.2 19.6 | 18.8 21.5 | 18.2 21.1 | 20.5 23.5 | 19.4 22.6 | 20.1 23.2 | 107 135 | 265 331 | 308 403 | 385 507 | 371 487 | 463 610 | 434 570 | 448 590 | 61 83 | 84 112 | 39 53 | 48 63 |
| 25 | 11.8 | 21.8 | 23.1 | 25.5 | 24.7 | 27.9 | 26.4 | 27.3 | 185 | 447 | 555 | 704 | 666 | 860 | 785 | 823 | 111 | 148 | 72 | 81 |
| 35 | 12.9 | 23.9 | 25.5 | 28.1 | 26.7 | 30.9 | 30.9 | 29.7 | 224 | 540 | 675 | 865 | 797 | 1052 | 915 | 984 | 133 | 180 | 90 | 99 |
| 50 | 14.7 | 27.5 | 29.3 | 32.6 | 30.9 | 35.8 | 35.8 | 34.7 | 290 | 692 | 933 | 1140 | 1042 | 1405 | 1241 | 1323 | 170 | 222 | 107 | 127 |
| 70 | 16.6 | 30.9 | 33.1 | 36.9 | 34.9 | 41.0 | 41.0 | 39.7 | 375 | 861 | 1181 | 1492 | 1341 | 1853 | 1583 | 1718 | 206 | 271 | 134 | 154 |
| 95 | 18.8 | 35.5 | 38.1 | 42.8 | 41.0 | 47.3 | 47.1 | 45.7 | 487 | 1221 | 1563 | 2009 | 1826 | 2481 | 2105 | 2289 | 254 | 320 | 165 | 184 |
| 120 | 20.6 | 38.9 | 42.3 | 46.9 | 45.0 | 51.9 | 51.7 | 50.4 | 590 | 1460 | 1929 | 2412 | 2230 | 2999 | 2622 | 2814 | 297 | 369 | 192 | 208 |
| 150 | 22.5 | 43.2 | 46.6 | 51.6 | 51.6 | 57.4 | 57.2 | 57.2 | 705 | 1754 | 2400 | 2927 | 2615 | 3680 | 3056 | 3342 | 339 | 415 | 221 | 240 |
| 185 | 24.8 | 47.7 | 51.6 | 57.2 | 57.2 | 63.6 | 63.4 | 63.4 | 863 | 2132 | 2906 | 3658 | 3275 | 4466 | 3793 | 4115 | 392 | 462 | 254 | 270 |
| 240 | 28.0 | 54.2 | 58.5 | 65.1 | 64.9 | 72.1 | 71.9 | 71.9 | 1106 | 2817 | 3714 | 4694 | 4173 | 5804 | 4813 | 5292 | 472 | 547 | 302 | 302 |
| 300 | 30.9 | 59.9 | 64.6 | 71.9 | 71.7 | 79.7 | 79.5 | 79.5 | 1348 | 3389 | 4503 | 5711 | 5036 | 6676 | 5811 | 6396 | 546 | 611 | 350 | 336 |
| 400 | 34.4 | 67.0 | 72.1 | 80.5 | 80.3 | 89.4 | 89.0 | 89.2 | 1687 | 4132 | 5566 | 7143 | 6341 | 8931 | 7355 | 8116 | 641 | 718 | 403 | 378 |
| 500 | 38.4 | 74.9 | 80.5 | 89.9 | 89.7 | 99.8 | 99.4 | 99.6 | 2105 | 5380 | 7024 | 9105 | 8079 | 10846 | 9063 | 9905 | 753 | 812 | 550 | 513 |
| 42.1 | - | - | - | 2548 | - | - | 880 | 930 | ||||||||||||
| 630 | ||||||||||||||||||||
| 标称截面 Nominal Cross- | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||||||||||
| section | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯 | 4+1芯 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯 | 4+1芯 | 空气 | Ungderground | |
| 10 | 19.7 | 20.6 | 22.2 | 21.3 | 24.0 | 22.4 | 23.1 | 477 533 | 631 | 616 | 730 | 696 | 715 | 39 | 48 | |
| 16 | 21.7 | 22.8 | 24.7 | 23.9 | 26.7 | 25.4 26.0 | 561 | 646 | 774 | 754 | 901 | 861 | 881 | 54 | 63 | |
| 25 | 25.0 | 26.4 | 28.7 | 27.5 31.2 | 31.2 | 30.1 | 718 | 842 | 1019 | 982 | 1206 | 1130 | 1168 | 72 | 82 | |
| 35 | 27.2 | 28.7 | 31.3 | 29.5 | 34.3 | 34.1 33.9 | 836 | 990 | 1212 | 1144 | 1449 | 1296 | 1381 | 91 | 99 | |
| 50 | 30.7 | 32.5 | 36.0 | 35.2 | 40.7 | 39.3 38.9 | 1031 | 1294 | 1558 | 1458 | 2262 | 1720 | 1783 | 111 | 127 | |
| 70 | 34.3 | 36.4 | 41.5 | 39.1 | 45.2 | 45.2 | 43.3 1257 | 1589 | 2371 | 1831 | 2802 | 2532 | 2667 | 139 | 153 | |
| 95 | 40.1 | 42.7 | 47.0 | 44.7 | 51.6 | 51.4 | 49.4 | 2069 2469 | 3002 | 2818 | 3567 | 3190 | 3373 | 168 | 183 | |
| 120 | 43.6 | 46.4 | 51.2 | 47.0 | 56.4 | 56.0 | 56.2 2387 | 2888 | 3499 | 3317 | 4197 | 3791 | 3986 | 198 | 207 | |
| 150 | 47.5 | 50.7 | 56.1 | 41.2 | 61.7 | 61.5 | 61.5 2758 | 3453 | 4147 | 3809 | 4987 | 4361 | 4647 | 225 | 235 | |
| 185 | 52.2 | 55.7 | 61.5 | 61.5 | 67.9 | 67.7 67.7 | 3262 | 4069 | 4981 | 4596 | 5897 | 5222 | 5544 | 257 | 265 | |
| 240 | 58.4 | 62.6 | 69.4 | 69.2 | 76.4 | 76.2 | 76.2 4067 | 5028 | 6188 | 5665 | 7419 | 6426 | 6905 | 292 | 298 | |
| 300 | 64.1 | 68.7 | 76.2 | 76.0 | 83.9 | 83.7 83.7 | 4766 | 5951 | 7358 | 6681 | 8457 | 7590 | 8175 | 328 | 327 | |
| 400 | 71.3 | 76.3 | 86.0 | 84.6 | 94.8 | 93.2 | 94.6 | 5670 7216 | 9806 | 8180 | 11840 | 9351 | 11023 | 377 | 368 | |
| 500 | 79.1 | 84.8 | 95.4 | 95.2 | 105.3 | 105.0 | 105.0 | 7095 8864 | 12075 | 11047 | 14140 | 12351 | 13196 | 515 | 498 | |
0.6/1kV 铝芯交联聚乙烯绝缘电力电缆(含普通型、阻燃型、低烟无卤型)
YJV交联电缆结构示意图
YJV 3{+}1 芯交联电缆结构示意图
产品特点及用途
铝芯交联聚乙烯绝缘电力电缆具有高机械强度,耐环境应力好,优良的电气性能和耐化学腐蚀等特性,重量轻,结构筒单,使用方便,本产品适用于交流额定电压U0/U为0.6/1kV及以下的输配电线路上阻燃型电缆的主要特点是电缆不易着火或着火时延燃仅局限在一定上范围内,适用于电缆敷设密集程度高的发电站、地铁、隧道、高层建筑、大型工矿企业、油田、煤矿等场所。
产品标准
本产品按GB/T l2706.1或IEC60502标准组织生产,还可按用户要求的其它标准生产。阻燃型电缆除上述标准外,其阻燃性能按GB/T19666标准规定分成A、B、C、D四种不同的阻燃级别,A级别的阻燃性能最优,用户可根据需要选用。
产品型号
| YJLV | 铝芯交联聚乙烯绝缘聚氯乙烯护套电力电缆(含普通型、阻燃型) |
| YJLY | 铝芯交联聚乙烯绝缘聚乙烯聚乙烯护套电力电缆(含普通型、阻燃型、低烟无卤型) |
| YJLV22 | 铝芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型、阻燃型) |
| YJLY23 | 铝芯交联聚乙烯绝缘钢带铠装聚乙烯护套电力电缆(含普通型、阻燃型、低烟无卤型) |
◆阻燃型电缆型号,在普通电缆型号前加Z(A、B、C、D)
产品使用特性
在普通电缆型号前加Z(A、B、C、D)
4、产品使用特性
(1)额定电压Uo /U为 10.6/1\mathsf{k V}_{\circ}
(2)电缆导体的最高额定温度为 90°\mathsf{C}_{\circ}
(3)短路时(最长持续时间不超过5秒)电缆导体的最高温度不超过 250°\mathsf C. 。
(4)电缆敷设时的环境温度应不低于 {*}0°{\mathsf{C}} ,其最小弯曲半径如下:单芯电缆— *20(\mathsf{D}+\mathsf{d}) ,mm多芯电缆— *15(\mathsf{D}+\mathsf{d}) ,mm(D、d分别为电缆外径与主导体的标称直径,mm)
主要技术参数
电缆载流量计算条件
环境温度 25°C
电缆导体工作温度 90°C
电缆埋地敷设时,土壤热阻系数g \mathsf{\Omega}_{=1.0°\mathsf{C}\mathsf{m}/\mathsf{W}} ,但尚未考虑电缆长期运行时由于水份迁移导致土壤热阻系数升高的现象。电缆埋地敷设时,电缆的轴心与地面距离为1000mm。
多根电缆敷设时,电缆的轴心距离 S=3D
| section | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | Recommende流et paitA) | |||||||||||||||||
| 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯4+1芯 | 1芯 | 2芯 | 3芯 | 4芯 3+1芯 | 5芯 | 3+2芯4+1芯 | Single-core 空气 | Unter | Multile-cores 空气 | Unter | ||||
| 10 | 8.5 | 15.0 | 16.7 | 17.3 | 16.8 | 18.9 | 17.8 | 18.5 | 86 | 260 | 374 | 62 | ||||||||
| 16 | 9.6 | 17.3 | 19.1 | 20.0 | 19.6 | 21.8 | 21.0 | 21.6 | 111 | 231 292 | 347 | 322 434 | 311 416 | 385 520 | 362 484 | 502 | 75 99 | 98 129 | 49 66 | 82 |
| 25 | 11.2 | 20.6 | 21.8 | 24.0 | 23.2 | 26.3 | 24.8 | 25.7 | 154 | 397 | 481 | 607 | 575 | 740 | 677 | 708 | 124 | 168 | 88 | 106 |
| 35 | 12.3 | 22.7 | 24.0 | 26.6 | 25.2 | 29.2 | 29.2 | 28.1 | 189 | 484 | 593 | 756 | 697 | 917 | 799 | 858 | 155 | 202 | 108 | 127 |
| 50 | 13.9 | 25.9 | 26.9 | 30.6 | 29.1 | 33.7 | 33.7 | 32.6 | 241 | 611 | 814 | 983 | 900 | 1210 | 1074 | 1142 | 190 | 242 | 134 | 154 |
| 70 | 16.0 | 29.7 | 31.5 | 35.4 | 33.4 | 39.3 | 39.3 | 38.1 | 324 | 780 | 1061 | 1333 | 1194 | 1631 | 1409 | 1510 | 240 | 299 | 170 | 198 |
| 95 | 17.8 | 33.5 | 35.2 | 40.3 | 38.7 | 44.6 | 44.4 | 43.1 | 410 | 1095 | 1376 | 1739 | 1578 | 2146 | 1817 | 1977 | 290 | 358 | 210 | 227 |
| 120 | 19.8 | 37.3 | 39.3 | 45.0 | 43.2 | 49.8 | 49.6 | 48.4 | 511 | 1334 | 1741 | 2137 | 1977 | 2658 | 2326 | 2494 | 340 | 409 | 247 | 259 |
| 150 | 21.7 | 41.6 | 43.6 | 49.7 | 46.9 | 55.2 | 55. 0 | 55.0 | 612 | 1605 | 2178 | 2601 | 2324 | 3273 | 2720 | 2971 | 390 | 458 | 286 | 291 |
| 185 | 24.0 | 46.1 | 48.2 | 55.3 | 52.5 | 61.4 | 61.2 | 61.2 | 752 | 1957 | 2644 | 3270 | 2917 | 3982 | 3370 | 3662 | 450 | 520 | 331 | 328 |
| 240 | 27.0 | 52.2 | 54.2 | 62.7 | 59.5 | 69.4 | 69.2 | 69.2 | 962 | 2586 | 3369 | 4187 | 3722 | 5173 | 4293 | 4718 | 535 | 605 | 393 | 381 |
| 300 | 29.7 | 57.5 | 59.1 | 69.0 | 65.7 | 76.4 | 76.2 | 76.2 | 1169 | 3099 | 4071 | 5079 | 4477 | 5890 | 5169 | 5683 | 615 | 680 | 463 | 433 |
| 400 | 33.2 | 64.6 | 66.7 | 77.6 | 73.4 | 86.1 | 85.7 | 85.9 | 1474 | 3791 | 5057 | 6395 | 5679 | 7999 | 6595 | 7270 | 730 | 791 | 543 | 539 |
| 500 | 37.2 | 72.5 | 74.9 | 87.0 | 82.2 | 96.6 | 96.2 | 96.4 | 1855 | 4980 | 6426 | 8223 | 7289 | 9748 | 8147 | 8898 | 850 | 909 | 625 | 605 |
| 630 | 41.3 | - | - | - | 2298 | - | - | - | 940 | 965 | - | |||||||||
| 标称截面 Nominal Cross- | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||||||||||
| 2芯 3芯 | 4芯 | 3+1芯 | 5芯 3+2芯 | 4+1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯 | 4+1芯 | 空气 | Underground | |||
| section 10 | 18.5 | 19.3 | 21.0 | 20.3 | 22.6 | 21.3 21.9 | 424 | 464 | 544 | 533 | 626 | 603 | 615 | 49 | 60 | |
| 16 | 20.5 | 21.5 | 23.5 | 22.9 25.4 | 24.3 | 24.8 | 502 | 569 | 677 | 659 | 784 | 749 | 767 | 66 | 79 | |
| 25 | 23.8 | 25.1 | 27.5 | 26.5 29.8 | 28.1 | 29.0 | 647 | 746 | 897 | 866 | 1057 | 994 | 1026 | 88 | 103 | |
| 35 | 26.0 | 27.4 | 30.1 | 28.5 33.0 | 32.5 | 31.5 | 759 | 885 | 1077 | 1018 | 1284 | 1151 | 1225 | 108 | 123 | |
| 50 | 29.1 | 30.8 | 35.6 | 32.6 | 39.0 35.8 | 37.3 | 923 | 1146 | 1366 | 1282 | 1649 | 1495 | 1560 | 133 | 149 | |
| 70 | 33.1 | 35.1 | 40.4 | 38.1 44.1 | 42.4 | 42.2 | 1152 | 1442 | 1774 | 1634 | 2530 | 1878 | 2408 | 168 | 184 | |
| 95 | 36.9 | 40.5 | 45.1 | 42.8 | 49.5 48.7 | 47.3 | 1513 | 2200 | 2662 | 2501 | 3156 | 2823 | 2984 | 212 | 221 | |
| 120 | 42.0 | 44.7 | 49.5 | 47.4 | 54.6 53.9 | 52.5 | 2191 | 2625 | 3165 | 3005 | 3792 | 3430 | 3602 | 247 | 252 | |
| 150 | 45.9 | 48.9 | 54.6 | 54.0 | 60.1 59.3 | 59.3 | 2536 | 3152 | 3763 | 3485 | 4520 | 3961 | 4213 | 285 | 283 | |
| 185 | 50.6 | 54.0 | 60.2 | 59.6 | 66.5 65.5 | 65.5 | 3009 | 3722 | 4538 | 4180 | 5356 | 4736 | 5030 | 326 | 320 | |
| 240 | 56.4 | 60.4 | 69.0 | 66.8 | 75.9 73.5 | 71.9 | 3743 | 4583 | 5617 | 5147 | 73.7 | 5833 | 6259 | 389 | 372 | |
| 300 | 61.7 | 66.1 | 75.5 | 73.1 | 83.1 80.5 | 78.9 | 4369 | 5404 | 6654 | 6046 | 80.7 | 6865 | 7382 | 456 | 423 | |
| 400 | 68.9 | 73.8 | 83.8 | 81.7 | 93.8 | 90.0 91.4 | 5216 | 6585 | 8169 | 7446 | 91.6 | 8513 | 10072 | 519 | 505 | |
| 500 | 76.7 | 82.2 | 94.4 | 91.1 | 104.3 | 101.7 | 101.9 6574 | 8137 | 11104 | 9274 | 102.1 | 11328 | 12091 | 618 | 605 | |
6-35kV 铝芯交联聚乙烯绝缘电力电缆(含普通型、阻燃型、低烟无卤型)
产品特点及用途
铝芯交联聚乙烯绝缘电力电缆具有高机械强度,耐环境应力好,优良的电气性能和耐化学腐蚀等特性,重量轻,结构筒单,使用方便,本产品适用于交流额定电压U0/U为0.6/1kV及以下的输配电线路上阻燃型电缆的主要特点是电缆不易着火或着火时延燃仅局限在一定上范围内,适用于电缆敷设密集程度高的发电站、地铁、隧道、高层建筑、大型工矿企业、油田、煤矿等场所。
产品标准
本产品按GB/T l2706.2或GB/T12706.3标准组织生产,还可按用户要求的其它标准生产。阻燃型电缆除上述标准外,其阻燃性能按GB/T19666标准规定分成A、B、C、D四种不同的阻燃级别,A级别的阻燃性能最优,用户可根据需要选用。
产品型号
| YJLV | 铝芯交联聚乙烯绝缘聚氯乙烯护套电力电缆(含普通型、阻燃型) |
| YJLY | 铝芯交联聚乙烯绝缘聚乙烯聚乙烯护套电力电缆(含普通型、阻燃型、低烟无卤型) |
| YJLV22 | 铝芯交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型、阻燃型) |
| YJLY23 | 铝芯交联聚乙烯绝缘钢带铠装聚乙烯护套电力电缆(含普通型、阻燃型、低烟无卤型) |
◆阻燃型电缆型号,在普通电缆型号前加Z(A、B、C、D)
产品使用特性
(1)额定电压Uo /U为3.6/6~26/35kV。
(2)电缆导体的最高额定温度为 90°\mathsf{C}_{\circ} 。
(3)短路时(最长持续时间不超过5秒)电缆导体的最高温度不超过 250°\mathsf C.
(4)电缆敷设时的环境温度应不低于 {:}0°{\mathsf{C}} ,其最小弯曲半径如下单芯电缆— *20(\mathsf{D}+\mathsf{d}) ,mm多芯电缆— *15(\mathsf{D}+\mathsf{d}) ,mm(D、d分别为电缆外径与主导体的标称直径,mm)
主要技术参数
电缆载流量计算条件
环境温度 25°C
电缆导体工作温度 90°C
电缆埋地敷设时,土壤热阻系数g {\mathsf{\tau}}=1.0°\mathsf{C m}/\mathsf{W} ,但尚未考虑电缆长期运行时由于水份迁移导致土壤热阻系数升高的现象。电缆埋地敷设时,电缆的轴心与地面距离为 1000\mathsf{mm} 。
多根电缆敷设时,电缆的轴心距离 S=30
| 标称截面 Nominal Cross- secton | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Sine-core | 单芯 Single-core | 3芯 Three-cores | ||||||
| Thre-cores | Sing-core | Thre-coes | Under ground | Under ground | ||||
| 25 | 22.4 | 43.31 | 490 | 1727 | 123 | 120 | 92 | 108 |
| 35 | 23.4 | 45.66 | 545 | 1924 | 160 | 150 | 115 | 138 |
| 50 | 24.7 | 48.66 | 616 | 2173 | 190 | 175 | 138 | 161 |
| 70 | 26.6 | 52.73 | 734 | 2615 | 235 | 215 | 172 | 196 |
| 95 | 28.4 | 56.37 | 863 | 3040 | 290 | 255 | 207 | 234 |
| 120 | 29.9 | 59.59 | 972 | 3422 | 335 | 290 | 239 | 266 |
| 150 | 31.4 | 63.03 | 1092 | 3849 | 380 | 330 | 271 | 299 |
| 185 | 33.2 | 66.68 | 1258 | 4377 | 435 | 370 | 310 | 341 |
| 240 | 35.8 | 71.82 | 1489 | 5135 | 515 | 435 | 363 | 392 |
| 300 | 37.8 | 76.76 | 1720 | 5960 | 595 | 490 | 413 | 441 |
| 400 | 41.8 | 84.70 | 2105 | 7303 | 695 | 565 | 491 | 511 |
| 500 | 45.8 | 94.36 | 2597 | 8920 | 810 | 650 | 562 | 582 |
| 630 | 49.6 | 3145 | 950 | 745 | ||||
电压等级: 8.7/15KVVoltage 8.7/15KV
| 标称截面 Nominal Cross- secton | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Singe-core | Three-cores | Singecore | Thre-ores | 单芯 Single-core | 3芯 Three-cores | |||
| 25 | 25.8 | 48.31 | 775 | 2809 | 132 | Underground 117 | 94 | Undergyround 109 |
| 35 | 26.8 | 50.66 | 855 | 3061 | 155 | 145 | 115 | 133 |
| 50 | 28.1 | 54.06 | 943 | 3435 | 180 | 170 | 141 | |
| 70 | 30.0 | 57.93 | 1085 | 3950 | 175 | 161 | ||
| 95 | 31.6 | 61.77 | 1223 | 4497 | 225 280 | 210 250 | 197 234 | |
| 120 | 33.3 | 65.19 | 1364 | 4995 | 325 | 285 | 211 242 | |
| 150 | 34.8 | 68.83 | 1506 | 5543 | 370 | 325 | 266 | |
| 185 | 37.8 | 72.68 | 2034 | 6204 | 425 | 365 | 273 312 | 297 |
| 240 | 40.4 | 77.82 | 2301 | 7102 | 505 | 430 | 369 | 337 |
| 300 | 42.6 | 84.36 | 2602 | 8943 | 585 | 485 | 421 | 393 |
| 400 | 46.6 | 92.50 | 3097 | 10633 | 685 | 560 | 503 | 444 517 |
| 500 | 51.0 | 102.16 | 3743 | 12626 | 800 | 645 | ||
| 630 | 54.6 | 4357 | 940 | 740 | 573 | 588 | ||
| 标称截面 Nominal Cross- sectien | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Sing-core | Singe-core | 单芯 Single-core | 3芯 Three-cores | |||||
| Thre-cores | Thre-cores | Underground | Under gyround | |||||
| 50 | 37.7 | 78.4 | 1357 | 4840 | 190 | 170 | 146 | 141 |
| 70 | 39.4 | 82.2 | 1500 | 5401 | 235 | 215 | 175 | 170 |
| 95 | 41.2 | 85.9 | 1669 | 6108 | 275 | 255 | 202 | 194 |
| 120 | 42.7 | 89.1 | 1806 | 6609 | 330 | 290 | 245 | 229 |
| 150 | 44.4 | 92.7 | 1981 | 7207 | 375 | 325 | 278 | 257 |
| 185 | 46.0 | 96.6 | 2166 | 7905 | 430 | 370 | 319 | 292 |
| 240 | 48.6 | 101.5 | 2450 | 8880 | 505 | 430 | 374 | 343 |
| 300 | 50.8 | 106.7 | 2750 | 9911 | 580 | 490 | 426 | 391 |
| 400 | 54.6 | 114.6 | 3218 | 11500 | 680 | 565 | 486 | 434 |
| 500 | 60.4 | 127.7 | 4089 | 14647 | 790 | 645 | 560 | 491 |
| 630 | 64.0 | 4692 | 910 | 740 | ||||
| 标称截面 Nominal setion | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Singecore | Singecore | 单芯 Single-core | 3芯 Three-cores | |||||
| Thre-cores | Thre-cores | Underground | Under ground | |||||
| 50 | 42.5 | 85.7 | 2279 | 7875 | 180 | 160 | 134 | 129 |
| 70 | 44.2 | 89.7 | 2483 | 8629 | 226 | 205 | 166 | 154 |
| 95 | 46.0 | 93.4 | 2672 | 9473 | 265 | 244 | 195 | 187 |
| 120 | 47.7 | 97.0 | 2865 | 10192 | 319 | 280 | 236 | 225 |
| 150 | 49.4 | 100.8 | 3086 | 10986 | 363 | 313 | 263 | 244 |
| 185 | 51.2 | 104.5 | 3334 | 11783 | 418 | 358 | 301 | 278 |
| 240 | 53.6 | 109.8 | 3651 | 13060 | 495 | 417 | 364 | 334 |
| 300 | 56.0 | 115.0 | 4038 | 14302 | 568 | 479 | 415 | 377 |
| 400 | 59.8 | 123.3 | 4597 | 16329 | 670 | 555 | 515 | 456 |
| 500 | 66.0 | 136.8 | 5680 | 20159 | 778 | 635 | 564 | 499 |
| 630 | 69.8 | 6412 | 905 | 730 | ||||
预制分支电缆(聚氯乙烯,交联聚乙烯)
我们只做高质量线缆
产品特点及用途
经济建设高速发展,现代建筑日新月异,建筑配电的复杂性已成为建筑设计、投资、施工单位普遍关注的一个问题。为顺应市场潮流,紧跟世界先进技术,预制分支电缆的诞生给建筑物中的供电线路带来新的选择。其具有综合成本低、工厂制作质量保证、现场安装施工方便、供电安全可靠、免维护保养等特点。是高质量、高效率、高回报的理想产品。
分支电缆配电的技术先进性
(1)可使配电简化成最简单的二级配电,符合规范中配电级数越少越好的原则。(2)具有最高的配电可靠性,适用于各种重要场合甚至是特别重要场合的配电。(3)分支电缆是一种经过预制的电力电缆,其外形和结构特征具备电缆特性,且接头经过密封绝缘处理,对环境要求低、能适用于潮湿、盐雾酸碱等环境,适用范围相当广泛。
特长
( 1 )采用预制分支电缆可大幅度减轻现场施工劳动强度,缩短施工时间。
( 2 )使用分支电缆,可保证大长度及复杂场所施工。
( 3 )缩小敷设使用空间。
( 4 )因在工厂内预制,可靠性得到保证。
( 5 )分支连接部分采用模压或浇注加工,防水防潮性能好,可长期使用免维修保养。
用途
(1) 中高层住宅楼配电
(2) 小区、厂房建设
(3) 防灾设备
(4) 桥梁、隧道照明
(5) 各种场合可代替中小容量的母线槽
品种、型号和规格
标准主电缆和分支电缆都是以XLPE或PVC为绝缘(IEC、GB、JIS、BS……),PVC材料包覆其外的低压电力电缆,一般主电缆是单芯或拧绞形多芯电缆(二芯至五芯电缆),分支电缆用单芯电缆,亦可按照需要采用具有耐火、阻燃性能的电缆。
| 序号 No | 电缆名称 Cable appellation | 型号 Type | |||
| 单芯 Single-core | 3芯拧绞式 Three-core coil buckling | 4芯拧绞式 Four-core coil buckling | 5芯拧绞式 Five-core coil buckling | ||
| 1 | 聚氯乙烯绝缘聚氯乙烯护套分支电缆 | FZ-VV | FZ-VV-3 | FZ-VV-4 | FZ-VV-5 |
| 2 | 聚氯乙烯绝缘聚氯乙烯护套阻燃分支电缆 | FZ-Z(A,B,C)-VV | FZ-Z(A,B,C)-VV-3 | FZ-Z(A,B,C)-VV-4 | FZ-Z(A,B,C)-VV-5 |
| 3 | 聚氯乙烯绝缘聚氯乙烯护套耐火分支电缆 | FZ-N-VV | FZ-N-VV-3 | FZ-N-VV-4 | FZ-N-VV-5 |
| 4 | 交联聚乙烯绝缘聚氯乙烯护套分支电缆 | FZ-YJV | FZ-YJV-3 | FZ-YJV-4 | FZ-YJV-5 |
| 5 | 交联聚乙烯绝缘聚氯乙烯护套阻燃分支电缆 | FZ-Z(A,B,C)-YJV | FZ-Z(A,B,C)-YJV-3 | FZ-Z(A,B,C)-YJV-4 | FZ-Z(A,B,C)-YJV-5 |
| 6 | 交联聚乙烯绝缘聚氯乙烯护套耐火分支电缆 | FZ-N-YJV | FZ-N-YJV-3 | FZ-N-YJV-4 | FZ-N-YJV-5 |
电缆技术参数
| 导线 Conductor | ||||||||
| 标称截面 Nominal Cross-section | 直径 Diamter mm | 绝缘厚度 Insulation thichness mm | 护套厚度 Thickness of sheath mm | 外径(约) O.D mm | 重量(约) weight kg/km | 交流试验电压 kv/5分钟 Test voltage : kv/5 minutes ( AV ) | 最大导体直流电阻 Max.resistance of conductor 20°℃ (Ω/km ) | 40℃载流量 Reference at 40℃ (A) |
| (mm2) 6 | 2.7 | 0.8 | 1.5 | 7.3 | 98 | 3.5 | 3.08 | 61 |
| 10 | 3.9 | 0.8 | 1.5 | 8.5 | 145 | 3.5 | 1.83 | 85 |
| 16 | 5.0 | 0.8 | 1.5 | 9.6 | 205 | 3.5 | 1.15 | 113 |
| 25 | 6.2 | 1.0 | 1.5 | 11.2 | 304 | 3.5 | 0.727 | 150 |
| 35 | 7.3 | 1.0 | 1.5 | 12.3 | 396 | 3.5 | 0.524 | 180 |
| 50 | 8.7 | 1.1 | 1.5 | 13.9 | 525 | 3.5 | 0.387 | 265 |
| 70 | 10.4 | 1.2 | 1.6 | 16.0 | 730 | 3.5 | 0.268 | 290 |
| 95 | 12.3 | 1.2 | 1.6 | 17.9 | 975 | 3.5 | 0.193 | 345 |
| 120 | 13.8 | 1.3 | 1.7 | 19.8 | 1216 | 3.5 | 0.153 | 405 |
| 150 | 15.3 | 1.5 | 1.7 | 21.7 | 1488 | 3.5 | 0.124 | 460 |
| 185 | 17.2 | 1.7 | 1.8 | 24.2 | 1852 | 3.5 | 0.0991 | 530 |
| 240 | 19.7 | 1.8 | 1.9 | 27.1 | 2405 | 3.5 | 0.0754 | 640 |
| 300 | 22.1 | 1.9 | 2.0 | 29.9 | 2981 | 3.5 | 0.0601 | 725 |
| 400 | 24.9 | 2.1 | 2.1 | 33.3 | 3780 | 3.5 | 0.0470 | 845 |
| 500 | 28.3 | 2.3 | 2.2 | 37.3 | 4816 | 3.5 | 0.0366 | 970 |
| 630 | 30.0 | 2.5 | 2.3 | 39.6 | 6200 | 3.5 | 0.0283 | 1120 |
载流量的电缆敷设修正系数
载流量的温度修正系数
(1)单层敷设:修正系数 {\tt\Omega}=1.0 Single-ayer laying: Corrective coefficient {\tt\Omega}=1.0
(2)两层敷设:修正系数 =0.9 Double-layer laying: Corrective coefficient =0.9
| 空气温度 Air temperature | 导体最高温度 Max.temperature | |
| ℃ | 70°℃ | 90°℃ |
| 10.0 | 1.41 | 1.26 |
| 15.0 | 1.35 | 1.22 |
| 20.0 | 1.29 | 1.18 |
| 25.0 | 1.22 | 1.14 |
| 30.0 | 1.15 | 1.09 |
| 35.0 | 1.08 | 1.04 |
| 40.0 | 1.00 | 1.00 |
| 45.0 | 0.91 | 0.94 |
| 50.0 | 0.81 | 0.89 |
(3)拧绞型单根敷设:修正系数 =0.8 Coil bucking single-cable laying \because Corrective coefficient _{=0.8}
(4)拧绞型多根敷设:修正系数 =0.76 Coil bucking multiple-cable laying \because Corrective coefficient =0.76
分支连接的结构
分支电缆安装示意图
IEC,GB电缆
额定电流和电压降
| 主电缆 Main cable | 分支电缆 Branch cable | 参考尺寸(mm) Reference size ( mm) | ||
| mm² | mm² | D1 | D2 | L |
| 16 | 6~16 | 72 | 40 | 190 |
| 25 | 6~25 | |||
| 35 | 10~25 | |||
| 50 | 10~35 | |||
| 70 | 10~35 | |||
| 95 | 10~50 | |||
| 120 | 10~70 | 87 | 82 | 255 |
| 150 | 10~70 | |||
| 185 | 10~95 | |||
| 240 300 | 10~120 | |||
| 10~120 10~150 | 114 | 72 | 375 | |
| 400 500 | 10~185 | |||
| 630 | 10~185 | |||
设定干线时,除要考虑电缆载流量外,还应考虑电压降。当干线中间有几处分支时,从电源到最终负载的电压降,要根据各分支的间隔按以下公式计算求出:
E_{d}=K Z_{n}\sum\*{\imath}_{n}|_{n}=K Z_{n}\sum\*L_{n}|_{n}[\mathsf{V}]
公式中,
\mathsf{E}_{d} :电压降[V](相连接)
K:配电常数
单相2线式: \mathsf{K}{=}2 单相3线式: \mathsf{K}=1
三相4线式: \mathsf{K}=1 三相5线式: \mathsf{K}=1
\left.\vert_{_{\mathsf{n}}}\right\vert_{_{\mathsf{n}}} :区间n的负载电流[A] \boldsymbol{\mathfrak{l}}_{\mathfrak{n}}\boldsymbol{\mathsf{L}}_{\mathfrak{n}} :区间n的长度[km]
Z:电缆的阻抗[Q/km]=Rcos \Theta+ Xsin θR:交流电阻[ \Omega/\upkappam] cOSθ:负载攻率因数
X:电抗[ \Omega/\upkappam] sin \scriptstyle{\Theta={√(1-\cos^{2)θ}}}
电缆夹紧装置
电缆的顶端Top end lthe cable主要缆顶端通常用防水化合物粘接在端头上,再盖上一个用PVC材料制成的帽,用热缩管加强,可永久使用。
Normally,the top end of the main cables are coated with the water-proof chemicals,covered with a PVC cap and reinforced with the heat shrink pipe so as to achieve long-term use.
敷设施工方法
垂直干线的预制组装式分支电缆,一般应按以下要领进行敷设:
(1)将电缆盘放在放线架上 ( 通常电缆盘放在楼下,将电缆提拉上去 )
(2)提升用的绳索通过卷绕机与电缆相连接
(3)开动卷绕机将电缆提升上去
(4)提升用的电缆网套到达房顶时,将网套挂在事先准备好的吊钩上
(5)对中间部进行固定
(6)将分支线端头与电流表或断流器相接
(7)进行与横向干线或主干线板的连接
施工中的注意事项
预制组装式分支电缆敷设时需注意以下事项:
(1)事先确认运送方法 ( 车辆大小,停车场等 )
(2)确认预制分支部分是否能安全通过贯通孔洞
(3)采取预防措施,防止提升过程中,分支部份的贯通孔洞受损伤
(4)提升过程中不要对分支施加张力
(5)使用电缆重量 4 倍以上强度的提升用绳索
(6)事先考虑避雨对策及空盘的处理方法
(7)电缆提升完毕后,应立即用适当的方法加以固定,以免电缆坠落受损
(8)单芯电缆禁止使用铁质夹具
订货须知
为了设计您需求的分支电缆,提供下列资料:
(1)系统图
垂直主电缆和各分支电缆的长度,分支连接的布置
(2)配电系统
单相双线,单相 3 线,三相 3 线,三相 4 线和三相 5 线
(3)垂直主电缆 (XLPE/PVC 线 )
电缆型号、单芯或单芯拧绞型、导线尺寸、是否使用直通连接
(4)分支电缆 (XLPE/PVC 单芯电缆 )
导线尺寸(5)敷设方法
从地面上拉起或由楼顶拉下。
(6)上端支承
用或不用电缆夹装置或悬吊绝缘装置(7)附件
夹具、托架等
(8)电缆盘具
允许的电缆盘具尺寸和毛重
(9)其它您认为需要的项目
控制电缆CONTROL CABLE
VV 铜芯聚氯乙烯绝缘聚氯乙烯护套控制电缆(含普通型 阻燃型) 70-70
KVV22 铜芯聚氯乙烯绝缘聚氯乙烯护套钢带铠装控制电缆(含普通型 阻燃型) 70-70
KVVP2 铜芯聚氯乙烯绝缘聚氯乙烯护套铜带屏蔽控制电缆(含普通型 阻燃型) 71-71
KVVP2-22 铜芯聚氯乙烯绝缘聚氯乙烯护套铜带屏蔽钢带铠装控制电缆(含普通型 阻燃型) 71-71
VVR 铜芯聚氯乙烯绝缘聚氯乙烯护套控制软电缆(含普通型 阻燃型) 72-72
聚氯乙烯绝缘聚氯乙烯护套控制电缆(普通型 阻燃型 耐火型)
Z(A、B、C)-KVV及KVV结构示意图
聚氯乙烯绝缘聚氯乙烯护套控制电缆(普通型 阻燃型 耐火型)
产品特点及用途
聚氯乙烯绝缘和护套控制电缆适用于交流额定电压U0/U为450/750V及以下控制、监控回路及保护线路等场合,作为电气装备之间的控制接线。
阻燃电力电缆的主要特点是不易着火或着火时延燃仅局限在一定范围内,适用于对阻燃性能要求较高的场合。
耐火控制电缆的主要特点是电缆除了能在正常的工作条件下传输电力外,电缆在着火燃烧时能保持一定时间的正常运行,适用于对耐火特性有要求的场合。
产品标准
本产品按GB/T9330标准组织生产,还可按用户要求的其它标准生产。
阻燃型电缆除按上述标准外,其阻燃性能按GB/T19666标准规定分成A类、B类、C类和D类四个级别,A类的阻燃性最优,用户可根据需要选用。
耐火型电缆按GB/T19666标准生产。
产品型号
| KVV | 铜芯聚氯乙烯绝缘聚氯乙烯护套控制电缆 |
| KVV22 | 铜芯聚氯乙烯绝缘聚氯乙烯护套钢带铠装控制电缆 |
| KVVP2 | 铜芯聚氯乙烯绝缘聚氯乙烯护套铜带屏蔽控制电缆 |
| KVVP2-22 | 铜芯聚氯乙烯绝缘聚氯乙烯护套铜带屏蔽钢带铠装控制电缆 |
| KVVR | 铜芯聚氯乙烯绝缘聚氯乙烯护套控制软电缆 |
◆ 阻燃型电缆型号,在普通电缆型号前加ZA,ZB,ZC;
* 耐火型电缆型号,在普通型电力电缆型号前加N。
产品使用特性
(1) 额定电压U0/U为450/750V。
(2) 电缆导体的长期允许工作温度为 170°\mathsf{C} 。
(3) 电缆敷温度不低于 {:}0°{\mathsf{C}} ,推荐的允许弯曲半径如下:无铠装层的电缆,应不小于电缆外径的6倍有铠装或铜带屏蔽结构的电缆,应不小于电缆外径的12倍有屏蔽层结构的软电缆,应不小于电缆外径的6倍
主要技术参数
电缆载流量计算条件
环境温度 25°C
电缆导体工作温度 70°\mathsf{C}
电缆埋地敷设时,土壤热阻系数g {\mathsf{\tau}}=1.0°\mathsf{C m}/\mathsf{W} (电缆长期运行时由于水分迁移会导致土壤热阻系数升高)。电缆埋地敷设时,电缆的轴心与地面距离为 1000\mathsf{mm} 。
多根电缆敷设时,电缆的轴心距离 \angle=30
| 芯数 | 标称截面 Nominal Cross-section(mm2) | |||||||||||
| 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | |||||||
| Re考外 O.D | Rerile Weight | Ret考外 O.D | Re老e Weight | e考外 O.D | Reene Weight | Re考外径 O.D | Reternle Weight | Re考外径 O.D | Reternle Weight | Re考外径e O.D | Reernle Weight | |
| 2 | (mm) 7.6 | (kg/km) 71 | (mm) 7.9 | (kg/km) 79 | (mm) 8.8 | (kg/km) 101 | (mm) 10.0 | (kg/km) 135 | (mm) 10.9 | (kg/km) 174 | (mm) 11.9 | (kg/km) 224 |
| 3 | 8.0 | 83 | 8.3 | 95 | 9.3 | 122 | 10.6 | 168 | 11.5 | 221 | 12.6 | 289 |
| 4 | 8.6 | 100 | 9.0 | 114 | 10.1 | 149 | 11.5 | 207 | 12.6 | 276 | 14.4 | 386 |
| 5 | 9.3 | 117 | 9.7 | 135 | 10.9 | 178 | 12.5 | 249 | 14.3 | 355 | 15.6 | 467 |
| 7 | 10.0 | 137 | 10.4 | 159 | 11.8 | 221 | 14.1 | 336 | 15.5 | 451 | 17.0 | 601 |
| 8 | 11.0 | 155 | 11.6 | 181 | 13.1 | 251 | 15.7 | 381 | 17.3 | 513 | 19.0 | 683 |
| 10 | 12.3 | 186 | 12.9 | 218 | 15.3 | 310 | 17.6 | 469 | 19.5 | 634 | 21.8 | 844 |
| 12 | 12.7 | 212 | 13.3 | 250 | 15.8 | 355 | 18.2 | 535 | 20.5 | 749 | 22.6 | 983 |
| 14 | 13.3 | 238 | 14.6 | 304 | 16.5 | 402 | 19.1 | 605 | 21.5 | 850 | 23.7 | 1143 |
| 16 | 14.5 | 290 | 15.3 | 341 | 17.4 | 452 | 20.5 | 704 | 22.6 | 961 | 25.0 | 1273 |
| 19 | 15.2 | 328 | 16.0 | 387 | 18.3 | 518 | 21.6 | 804 | 23.8 | 1104 | 26.3 | 1494 |
| 24 | 17.6 | 404 | 18.5 | 479 | 21.6 | 665 | 25.1 | 1003 | 27.8 | 1382 | 31.4 | 1895 |
| 27 | 17.9 | 441 | 18.9 | 525 | 22.1 | 730 | 25.6 | 1102 | 28.4 | 1524 | 32.1 | 2095 |
| 30 | 18.5 | 481 | 19.6 | 573 | 22.8 | 799 | 26.5 | 1206 | 29.5 | 1672 | 33.2 | 2305 |
| 37 | 19.9 | 572 | 21.4 | 671 | 24.6 | 951 | 28.6 | 1448 | 32.4 | 2043 | 34.3 | 2779 |
| 44 | 22.7 | 694 | 23.9 | 829 | 27.5 | 1128 | 32.7 | 1761 | 二 | 二 | 二 | 二 |
| 23.0 | 743 | 24.3 | 890 | 27.9 | 1215 | 33.3 | 1885 | 二 | 二 | 二 | 二 | |
| 48 | 23.6 | 795 | 25.0 | 953 | 28.7 | 1304 | 34.2 | 2024 | 二 | |||
| 52 61 | 25.0 | 911 | 26.4 | 1095 | 31.0 | 1550 | 36.7 | 2373 | - | - | - | |
| 导体电阻 Max esistance at 20°℃ (2/km) | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | ||||||
| 芯数 | 标称截面 Nominal Cross-section(mm2) | |||||||||||||||
| 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 | ||||||||||
| 参考外径 Core Reference O.D | 参考重量 Weight | 参考外径 O.D | 参考重量 Reference Reference Reference Weight | 参考外径 O.D | 参考重量 Weight | 参考外径 O.D | 参考重量 Weight | 参考外径 ReferenceReference ReferenceReference Reference O.D | 参考重量 Weight Reference | 参考外径 O.D Reference | 参考重量 Weight | 参考外径 Reference ReferenceReference O.D | 参考重量 Weight | |||
| 4 | (mm) 11.9 | (kg/km) 226 | (mm) 12.3 | (kg/km) 246 | (mm) 13.3 | (kg/km) 296 | (mm) 14.7 | (kg/km) 373 | (mm) 15.8 | (kg/km) 457 | (mm) 17.0 | (kg/km) 561 | (mm) 22.0 | (kg/km) 873 | ||
| 5 | 12.5 | 252 | 13.0 | 276 | 14.2 | 335 | 15.7 | 428 | 16.9 | 530 | 18.9 | 685 | 23.8 | 1022 | ||
| 7 | 13.2 | 282 | 13.7 | 311 | 15.0 | 391 | 16.8 | 508 | 18.7 | 668 | 20.2 | 837 | 25.6 | 1276 | ||
| 8 | 14.3 | 314 | 14.8 | 348 | 16.4 | 439 | 19.0 | 601 | 20.9 | 775 | 22.6 | 969 | 28.3 | 1444 | ||
| 10 | 15.6 | 363 | 16.2 | 404 | 18.6 | 522 | 21.3 | 736 | 23.1 | 907 | 25.1 | 1140 | 32.3 | 1796 | ||
| 12 | 15.9 | 394 | 16.6 | 441 | 19.1 | 596 | 21.9 | 810 | 23.8 | 1031 | 25.8 | 1289 | 二 | 二 | ||
| 14 | 16.5 | 428 | 17.2 | 482 | 19.8 | 630 | 22.7 | 893 | 24.8 | 1146 | 26.9 | 1446 | 二 | 二 | ||
| 16 | 17.2 | 467 | 18.0 | 528 | 21.0 | 712 | 23.8 | 986 | 25.9 | 1272 | 28.2 | 1611 | - | - | ||
| 19 | 17.9 | 514 | 19.3 | 611 | 21.9 | 790 | 24.8 | 1101 | 27.1 | 1431 | 29.6 | 1832 | 二 | 二 | ||
| 24 | 21.2 | 670 | 22.2 | 759 | 24.9 | 958 | 28.4 | 1347 | 31.7 | 1786 | 34.7 | 2315 | - | - | ||
| 27 | 21.6 | 712 | 22.6 | 810 | 25.3 | 1030 | 28.9 | 1453 | 32.3 | 1941 | 35.3 | 2524 | - | |||
| 30 | 22.2 | 761 | 23.2 | 868 | 26.1 | 1108 | 30.4 | 1615 | 33.3 | 2106 | 38.1 | 3136 | - | |||
| 37 | 23.6 | 872 | 24.7 | 1001 | 27.8 | 1291 | 32.5 | 1889 | 35.7 | 2489 | 40.7 | 3689 | 二 | |||
| 44 | 25.9 | 1005 | 27.2 | 1158 | 31.4 | 1546 | 36.4 | 2242 | 二 | 二 | 二 | - | - | |||
| 48 | 26.3 | 1059 | 27.6 | 1224 | 31.8 | 1639 | 38.1 | 2735 | - | - | ||||||
| 52 | 26.9 | 1119 | 28.2 | 1295 | 32.6 | 1739 | 39.0 | 2898 | - | 二 | - | |||||
| 61 | 28.3 | 1254 | 29.7 | 1457 | 34.3 | 1965 | 41.1 | 3261 | - | - | - | - | ||||
| 导体电阻 Max ofestancor at 20°℃ | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 | |||||||||
| 芯 | 标称截面 Nominal Cross-section(mm2) | |||||||||||||||
| 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 | ||||||||||
| Re考外径 O.D | Reterle Weight | Ret老外径 O.D | 参考重量 Weight Reference | O.D | Retey外Retrnee Weight | O.D | Re考外径etnle | Re考外径e O.D | 参考重量 Reference | Rete外径e O.D | Retele Weight | Re外径 O.D | 参考重量 Reference | |||
| (mm) 9.0 | (kg/km) 116 | (mm) 9.4 | (kg/km) | (mm) | (kg/km) | (mm) | Weight (kg/km) | (mm) | Weight (kg/km) | (mm) | (kg/km) | (mm) | Weight (kg/km) | |||
| 4 5 | 9.6 | 134 | 10.1 | 131 153 | 10.5 11.3 | 169 199 | 11.9 12.8 | 230 274 | 13.0 14.7 | 301 384 | 14.8 16.0 | 414 477 | 18.8 20.9 | 655 778 | ||
| 7 | 10.4 | 156 | 10.8 | 180 | 12.2 | 245 | 14.5 | 364 | 15.9 | 482 | 17.4 | 616 | 22.7 | 1011 | ||
| 8 | 11.4 | 176 | 12.0 | 204 | 14.1 | 278 | 16.1 | 413 | 17.7 | 548 | 19.4 | 722 | 25.5 | 1148 | ||
| 10 | 12.7 | 211 | 13.3 | 244 | 15.7 | 335 | 18.0 | 505 | 19.9 | 651 | 22.2 | 881 | 28.9 | 1415 | ||
| 12 | 13.1 | 237 | 14.3 | 298 | 16.2 | 381 | 18.6 | 572 | 20.9 | 769 | 22.9 | 1022 | 二 | |||
| 14 | 14.2 | 286 | 15.0 | 333 | 16.9 | 429 | 19.5 | 645 | 21.9 | 895 | 24.1 | 1167 | ||||
| 16 | 14.9 | 319 | 15.7 | 372 | 17.8 | 481 | 20.9 | 746 | 23.0 | 986 | 25.4 | 1317 | - | |||
| 19 | 15.6 | 358 | 16.4 | 420 | 18.7 | 549 | 22.0 | 848 | 24.2 | 1135 | 26.7 | 1522 | ||||
| 24 | 18.0 | 440 | 18.9 | 517 | 22.0 | 702 | 25.5 | 1056 | 28.2 | 1413 | 31.8 | 1950 | ||||
| 27 | 18.3 | 478 | 19.3 | 564 | 22.4 | 768 | 26.0 | 1156 | 28.8 | 1560 | 32.5 | 2152 | ||||
| 18.9 | 519 | 20.0 | 613 | 23.2 | 838 | 26.9 | 1261 | 29.8 | 1712 | 33.6 | 2364 | |||||
| 30 | 20.3 | 613 | 21.8 | 751 | 24.9 | 1001 | 29.0 | 1509 | 32.8 | 2113 | 36.7 | 2893 | - | |||
| 37 44 | 23.1 | 741 | 24.3 | 879 | 27.9 | 1177 | 33.1 | 1830 | - | - | - | |||||
| 23.4 | 791 | 24.7 | 941 | 28.3 | 1264 | 33.7 | 1955 | 二 | 二 | 二 | ||||||
| 48 52 | 24.0 | 844 | 25.4 | 1005 | 29.1 | 1355 | 34.6 | 2097 | - | - | - | - | ||||
| 61 | 25.4 | 963 | 26.8 | 1131 | 31.4 | 1605 | 37.1 | 2451 | - | - | ||||||
| 导体电阻 Max | 24.5 | 18.1 | 7.41 | 4.61 | ||||||||||||
| ofecstanctor at 20°℃ (2/km) | 12.1 | 3.08 | 1.83 | |||||||||||||
| 芯数 | 标称截面 Nominal Cross-section(mm2) | |||||||||||||||
| 0.75 | 1 | 1.5 | 2.5 | 4 | 6 | 10 | ||||||||||
| O.D | Weight | 考外径外径外径外径 O.D | Weight | (O.D | Weight | O.D | 参考重量 Weight Reference | Re老外径e O.D | 参考重量 Weight Reference | e考外径 O.D | Weight | Ref考外径e O.D | 参考重量 Weight Reference | |||
| 4 | (mm) 12.4 | (kg/km) 253 | (mm) 12.8 | (kg/km) 274 | (mm) 13.9 | (kg/km) 327 | (mm) 15.3 | (kg/km) 384 | (mm) 16.4 | (kg/km) 467 | (mm) 17.6 | (kg/km) 573 | (mm) 22.0 | (kg/km) 876 | ||
| 5 | 13.0 | 281 | 13.5 | 306 | 14.7 | 368 | 16.2 | 441 | 17.5 | 542 | 19.2 | 669 | 23.7 | 1026 | ||
| 7 | 13.8 | 312 | 14.2 | 343 | 15.6 | 397 | 17.3 | 526 | 18.7 | 657 | 20.6 | 843 | 25.5 | 1281 | ||
| 8 | 14.8 | 347 | 15.4 | 382 | 16.9 | 446 | 19.3 | 595 | 20.9 | 764 | 22.6 | 957 | 28.7 | 1482 | ||
| 10 | 16.1 | 399 | 16.7 | 421 | 18.5 | 523 | 21.2 | 723 | 23.1 | 911 | 25.0 | 1145 | 32.7 | 1840 | ||
| 12 | 16.5 | 410 | 17.1 | 458 | 19.4 | 574 | 21.8 | 801 | 23.7 | 1017 | 25.7 | 1294 | ||||
| 14 | 17.0 | 446 | 17.8 | 501 | 20.1 | 632 | 22.7 | 887 | 24.7 | 1134 | 26.9 | 1453 | ||||
| 16 | 17.7 | 486 | 18.5 | 547 | 21.0 | 714 | 23.7 | 980 | 25.8 | 1260 | 29.2 | 1649 | ||||
| 19 | 18.4 | 533 | 19.2 | 604 | 21.9 | 793 | 24.8 | 1098 | 27.0 | 1423 | 30.5 | 1916 | - | |||
| 24 | 21.2 | 662 | 22.1 | 751 | 24.8 | 963 | 29.3 | 1372 | 32.0 | 1828 | 34.40 | 2363 | - | |||
| 27 | 21.5 | 704 | 22.5 | 802 | 25.2 | 1035 | 29.8 | 1482 | 32.6 | 1984 | 37.3 | 2608 | - | |||
| 30 | 22.1 | 752 | 23.2 | 860 | 26.0 | 1114 | 30.7 | 1646 | 33.6 | 2151 | 38.4 | 3185 | - | |||
| 37 | 23.5 | 864 | 24.6 | 994 | 28.1 | 1328 | 32.8 | 1925 | 37.6 | 2574 | 41.1 | 3743 | ||||
| 44 | 25.9 | 998 | 27.1 | 1150 | 31.7 | 1588 | 37.9 | 2620 | 二 | - | ||||||
| 48 | 26.2 | 1052 | 27.5 | 1216 | 32.1 | 1682 | 38.5 | 2769 | 二 | 二 | - | |||||
| 52 | 26.8 | 1112 | 28.2 | 1288 | 32.9 | 1783 | 39.4 | 2932 | 二 | - | - | |||||
| 61 | 28.6 | 1277 | 30.6 | 1483 | 35.0 | 2013 | 41.5 | 3298 | - | - | - | - | ||||
| 导体电阻 Max ofestanctor at 20°℃ (2/km) | 24.5 | 18.1 | 12.1 | 7.41 | 4.61 | 3.08 | 1.83 | |||||||||
| 芯数 Core | ||||||||||
| 0.5 | 0.75 | 标称截面 Nominal Cross-section(mm2) 1 | 1.5 | 2.5 | ||||||
| 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 参考外径 Reference O.D (mm) | 参考重量 Weight (kg/km) Reference | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 参考外径 Reference O.D | 参考重量 Reference Weight | 参考外径 Reference O.D | 参考重量 Reference Weight | |
| 4 | 8.5 | 90 | 8.9 | 103 | 9.2 | 116 | (mm) 10.4 | (kg/km) 151 | (mm) 12.0 | (kg/km) 211 |
| 5 | 9.2 | 105 | 9.6 | 121 | 10.0 | 137 | 11.3 | 179 | 13.1 | 253 |
| 7 | 9.8 | 120 | 10.3 | 140 | 10.7 | 161 | 12.2 | 222 | 14.8 | 340 |
| 8 | 10.9 | 136 | 11.4 | 159 | 11.9 | 183 | 14.2 | 273 | 16.5 | 386 |
| 10 | 12.1 | 163 | 12.7 | 191 | 13.9 | 241 | 15.9 | 334 | 18.5 | 475 |
| 12 | 12.5 | 184 | 13.1 | 217 | 14.4 | 273 | 16.4 | 354 | 19.1 | 540 |
| 14 | 13.1 | 206 | 14.3 | 266 | 15.0 | 307 | 17.2 | 400 | 20.5 | 630 |
| 16 | 14.4 | 252 | 15.1 | 298 | 15.8 | 344 | 18.1 | 450 | 21.6 | 710 |
| 19 | 15.0 | 283 | 15.8 | 336 | 16.5 | 390 | 19.0 | 515 | 22.7 | 809 |
| 24 | 17.3 | 348 | 18.2 | 415 | 19.1 | 482 | 22.5 | 661 | 26.4 | 1009 |
| 27 | 17.7 | 379 | 18.6 | 453 | 19.5 | 528 | 23.0 | 726 | 27.0 | 1106 |
| 30 | 18.3 | 411 | 19.2 | 493 | 20.6 | 597 | 23.8 | 793 | 28.0 | 1209 |
| 37 | 19.6 | 487 | 21.1 | 608 | 22.1 | 711 | 25.6 | 950 | 30.8 | 1497 |
| 44 | 22.3 | 593 | 23.5 | 712 | 24.7 | 834 | 28.7 | 1118 | 34.5 | 1765 |
| 48 | 22.7 | 633 | 23.9 | 762 | 25.1 | 895 | 29.2 | 1203 | 35.1 | 1887 |
| 52 | 23.3 | 675 | 24.5 | 815 | 25.8 | 958 | 30.0 | 1290 | 36.5 | 2063 |
| 61 | 24.6 | 771 | 26.0 | 934 | 27.3 | 1100 | 32.4 | 1535 | 38.7 | 2374 |
| 导体电阻 Max ofestancor at 20°℃ (2/km) | 39 | 26 | 19.5 | 13.3 | 7.98 | |||||
矿物绝缘电缆 MINERAL INSULATED CABLE
0.6/1kV 及以下金属护套无机矿物绝缘电缆(YTTW、YTTWV、WD-YTTWY) 79-81
0.6/1kV 隔离型柔性矿物绝缘铝护套防火电缆(BTLY、BTLV) 82-84
.6/1kV 隔离型柔性矿物绝缘防火电缆(BBTRZ) 85-87
750V 及以下金属护套氧化镁矿物绝缘电缆(BTTZ) 88-89
0.6/1kV BTLY
矿物绝缘电缆的组成
(1)电缆导体:由高导电率的金属铜作导体。(2)绝缘层:采用耐高温、不燃烧的无机矿物质作绝缘材质。(3)金属护套:采用金属管作护套,经特殊加工有良好的连续性和弯曲特性,并可作为接地线使用。(4)外护套:必要时,在金属护套外面挤包一层塑料外护层,采用低烟无毒的塑性材质,有良好的防腐蚀特性。
矿物绝缘电缆具有以下优越性能
矿物绝缘电缆主要特点是电缆除了能在正常的工作条件下传输电力外电缆不易着火,且电缆在着火燃烧时仍能保持一定时间的正常运行,电缆燃烧时不会产生腐蚀性气体和有毒烟雾。
1、防火性能优越,耐火等级不仅满足国标GA306.2中ⅠA类950℃~1000℃90min,还可满足英国BS6387中规定的A级 650°C3{h} 、B级 750°C3\mathsf{h} 、 C级 950°\mathsf{C}3\mathsf{I} 要求;同时,在燃烧中还能耐受水喷与机械撞击。
2、燃烧时无烟无毒,燃烧时不会产生任何有害气体,不会产生二次污染,是真正的环保绿色产品。
5、备具有良好的防鼠、防蚁、防辐射功能,可保证电缆具有稳定性、耐久性。
3、电缆载流量大,且具有较大的过载能力,电缆护套温度可提高到1 25°C 。过载时长期工作温度可达 250°\mathsf C
6、耐化学腐蚀,即使在电缆易遭受化学品腐蚀或工业污染严重的地方,它仍然安全。
4、使用寿命长,耐高温不易老化,在正常工作状态下,使用寿命在70年以上。
7、机械强度高,即使经受剧烈的机械破坏,也不会损伤电缆性能。
矿物绝缘电缆与常规耐火电缆耐火性能比较
| 项目 | YTTW YTTWG | BTLY | BBTRZ | BTTZ BTTQ | 耐火电缆 |
| 燃烧性能 | 不燃 | 不燃 | 不燃 | 不燃 | 阻燃 |
| 烟度 | 无烟 | 无烟 | 无烟 | 无烟 | 有卤浓烟 |
| 毒性 | 无毒 | 无毒 | 无毒 | 无毒 | 有卤高毒性 |
| 耐火特性 | 750 ~80 | ||||
| 喷淋试验 | 通过 | 通过 | 通过 | 通过 | 不能通过 |
| 振动试验 | 通过 | 通过 | 通过 | 通过 | 不能通过 |
| 生产长度 | 长度无限制 | 长度无限制 | 长度无限制 | 不超过10米 | 长度无限制 |
| 敷设条件 | 无限制 | 无限制 | 无限制 | 固定不可移动 | 无限制 |
四 产品型号
| YTTW | 铜芯轧纹铜护套无机矿物绝缘电缆 |
| YTTWG | 铜芯光面铜护套无机矿物绝缘电缆 |
| YTTWV | 铜芯轧纹铜护套无机矿物绝缘聚氯乙烯外护套电缆 |
| WD-YTTWY | 铜芯轧纹铜护套无机矿物绝缘无卤低烟聚烯烃外护套电缆 |
| YTTWGV | 铜芯铜护套无机矿物绝缘聚氯乙烯外护套电缆 |
| WD-YTTWGY | 铜芯铜护套无机矿物绝缘无卤低烟聚烯烃外护套电缆 |
| BTLY | 隔离型柔性矿物绝缘铝护套低烟无卤聚烯烃外护套防火电缆 |
| BTLV | 隔离型柔性矿物绝缘铝护套聚氯乙烯外护套防火电缆 |
| BBTRZ | 隔离型柔性矿物绝缘防火电缆 |
| BTTZ | 重型铜芯铜护套矿物绝缘电缆 |
| BTTQ | 轻型铜芯铜护套矿物绝缘电缆 |
| BTTVQ | 轻型铜芯铜护套矿物绝缘聚氯乙烯外套矿物绝缘电缆 |
| BTTVZ | 重型铜芯铜护套矿物绝缘聚氯乙烯外套矿物绝缘电缆 |
| WD-BTTYQ | 轻型铜芯铜护套矿物绝缘无卤低烟外套矿物绝缘电缆 |
| WD-BTTYZ | 重型铜芯铜护套矿物绝缘无卤低烟外套矿物绝缘电缆 |
矿物绝缘电缆用途
公共娱乐场所、高层建筑、会展中心、体育场馆、市政大楼、宾馆饭店、医院、学校、银行、商场、会馆、机场、车站、港口、冶金工业、焦碳工业、船舶工业、钢铁工业、玻璃工业、石油化工工业、炼油厂、化学工业、核电站、医药工业、矿业、军事工业、地铁、地下仓库、隧道、地下广场、运输和交通枢纽。
产品使用特性
(1)额定电压U0/U为0.6/-1kV。
(2)根据布线要求电缆表面温度小于或等于 .70°\mathsf{C} ;如果布线不可触摸,也不能与可燃建筑材料相接触时,电缆表面温度可达到 \mathsf{L05°C} ;过载短路时5秒可承受温度高达 250°\mathsf C 。
(3)电缆最小弯曲半径20D(D为电缆外径)。
产品执行标准
| 型号 | 执行标准 |
| YTTW | 依照JG/T313标准组织生产 |
| YTTWG | |
| YTTWV | |
| WD-YTTWY | |
| YTTWGV | |
| WD-YTTWGY | |
| BTLY | 依照Q/XXDL9标准组织生产 |
| BTLV | 依照Q/XXDL10标准组织生产 |
| BBTRZ | |
| BTTZ BTTQ | |
| BTTVQ | 依照GB/T13033标准组织生产 |
| BTTVZ | |
| WD-BTTYQ | |
| WD-BTTYZ | |
矿物绝缘电缆要求
1.导体
YTTW、YTTWG、YTTWV、WD-YTTWY、YTTWGV、WD-YTTWGY、BTLY、BTLV、BBTRZ由多根铜线绞合而成,具有良好的弯曲特性。
BTTZ、BTTQ、BTTVQ、BTTVZ、WD-BTTYZ使用单根铜导体,电缆外径小。
2.绝缘层
YTTW、YTTWG、YTTWV、WD-YTTWY、YTTWGV、WD-YTTWGY、BTLY、BTLV、BBTRZ采用耐高温,不燃烧的无机矿物绝缘材质。BTTZ、BTTQ、BTTVQ、BTTVZ、WD-BTTYQ、WD-BTTYZ采用耐高温,不燃烧的氧化镁绝缘材质。
3.金属护套
YTTW、YTTWG、YTTWV、WD-YTTWY、YTTWGV、WD-YTTWGY、BTTZ、BTTQ、BTTVQ、BTTVZ、WD-BTTYQ、WD-BTTYZ采用铜质材料,经特殊加工有良好的弯曲特性,并且可以作为PE线。BTLY、BTLV采用铝质材料,电缆重量轻,经济性好,也可以作为PE线。
4.外护层
采用低烟无毒的塑性材质,有良好的防腐蚀特性。
矿物绝缘电缆的敷设的一般要求
◆电缆在敷设前,均应检查电缆是否完好,绝缘电阻是否达到标准要求。
◆电缆敷设时,其固定点之间的间距,除支架敷设在支架处固定外,其余可按照国家相关规范中的数值固定在明敷部位,如果相同走向的电缆大、中、小规格都有,从整齐、美观方面考虑,可按最小规格电缆标准要求固定,也可分档距离固定。当电线倾斜敷设时,电缆与垂直方向成30度及以下时,按垂直间距固定;大于30度时,按水平间距固定。
◆电缆敷设时,在转弯、中间连接器两侧,有条件固定的应加以固定。
◆计算敷设电缆所需长度时,应考虑留有1%的余量。
◆对电缆在运行中可能遭受到机械损伤的部位,应采取适当的保护措施。
◆单芯电缆敷设时,应逐根敷设,待每组布齐并矫直后,再作排列绑扎,绑扎间距以1-1.5M为宜。
◆有腐蚀作用的环境中敷设铜护套电缆时,或在部分埋地或穿管敷设时,应采用聚氯乙烯外护套或低烟无卤外护套。
◆布线过程中,电缆锯断后应立即对其端部进行临时性密封。
◆电缆全长均为直线敷设或联接用电器可能产生振动时,要在允许场合设置膨胀环。
◆一般矿物绝缘电缆无需穿管敷设,特殊场合必须穿管(单芯电缆不允许单独穿金属管敷设)。
◆可以埋地敷设,但最好不要有中间接头,如无法避免,则接头外需做好防水处理。
◆储存期3个月。
电缆设计的一些注意事项
◆根据负荷性质、环境条件、应用场所等条件选择适当的型号,根据环境条件及选择的电缆型号确定适当的敷设方式根据载流量选择截面
1)确定用电设备的功率(短时工作制设备换算为统一负载持续率下的功率)
2)根据需要系数法、利用系数法等方式确定计算负荷和计算电流
3)根据环境条件、敷设方式确定电缆载流量系数
4)查找与电缆型号、敷设方式对应的载流量表,选择适当的导体截面,使载流量满足负荷计算电流的要求
◆根据电压损失校验截面
1)根据负荷性质确定允许的导体末端最大电压损失 )查找与电缆型号、敷设方式对应的电压损失表,校验所选截面是否满足电压损失的要求
3)如不满足,则增大导体截面直至校验通过
◆根据热稳定校验截面
1)根据配电系统计算线路最大短路电流
2)查找热稳定短路电流表,校验所选截面是否满足短路热稳定的要求
3)如不满足,则增大导体截面直至校验通过
◆依据经济寿命内总费用最少选择截面
1)获取电缆价格、安装成本、附件成本,确定初期费用
2)计算电缆寿命期内长期运行电能损耗费用
3)比较所选截面及邻近截面总费用数值,作为选择截面的辅助依据
十一 主要技术参数
(1)载流量计算条件
(2)安装温度 0{-}40°\mathsf{C}
(3)电缆工作温度 90°C
(4)电压降是按照导体 90°C 条件下计算得出
0.6/1kV 及以下金属护套无机矿物绝缘电缆
YTTW、YTTWV、
WD-YTTWY
单芯电缆参数及其载流量
(续上表)
YTTW、YTTWV、
WD-YTTWY
多芯电缆参数及其载流量
| 标称截面 Nominal Cross- section (mm) | 铜护套截面积 Copper sheath cross-sectional area(mm) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) | |
| 1×10 | 12.81 | 0.8 | 12.2 | 1.83 | 97 | 77 |
| 1x16 | 14.07 | 0.9 | 13.4 | 1.15 | 125 | 100 |
| 1×25 | 16.08 | 0.9 | 15.0 | 0.727 | 165 | 130 |
| 1x35 | 17.71 | 0.9 | 16.3 | 0.524 | 200 | 160 |
| 1×50 | 24.34 | 0.9 | 17.8 | 0.387 | 245 | 195 |
| 1×70 | 21.48 | 1.0 | 20.0 | 0.268 | 305 | 245 |
| 1×95 | 30.62 | 1.0 | 22.0 | 0.193 | 375 | 300 |
| 1×120 | 35.33 | 1.0 | 25.0 | 0.153 | 435 | 350 |
| 1×150 | 38.47 | 1.1 | 27.2 | 0.124 | 500 | 400 |
| 1x185 | 42.39 | 1.1 | 29.7 | 0.0991 | 580 | 465 |
| 1×240 | 55.39 | 1.2 | 32.4 | 0.0754 | 685 | 550 |
| 1x300 | 59.16 | 1.2 | 34.4 | 0.0601 | 795 | 635 |
| 1x400 | 66.69 | 1.3 | 38.6 | 0.0470 | 930 | 745 |
| 1×500 | 74.23 | 1.4 | 42.8 | 0.0366 | 990 | 860 |
| 标称截面 Nominal Cross- section | 铜护套截面积 Copper sheath cross-sectional area(mm) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Ω2/km) | 载流量 Recommended current capacity (A) |
| (mm) 2×2.5 | 12.81 | 0.9 | 12.4 | 7.41 | 33 |
| 2×4 | 12.81 | 0.9 | 12.4 | 4.61 | 44 |
| 2×6 | 16.08 | 0.9 | 15.0 | 3.08 | 57 |
| 2×10 | 19.59 | 1.0 | 18.0 | 1.83 | 78 |
| 2×16 | 22.11 | 1.0 | 20.0 | 1.15 | 104 |
| 2×25 | 32.97 | 1.1 | 23.7 | 0.727 | 135 |
| 2×35 | 35.33 | 1.1 | 25.2 | 0.524 | 168 |
| 2×50 | 38.47 | 1.1 | 27.2 | 0.387 | 204 |
| 2×70 | 38.47 | 1.2 | 27.4 | 0.268 | 263 |
| 2x95 | 42.39 | 1.2 | 29.9 | 0.193 | 320 |
| 2×120 | 46.32 | 1.2 | 32.4 | 0.153 | 373 |
| 2×150 | 59.16 | 1.2 | 34.4 | 0.124 | 413 |
| 2×185 | 66.69 | 1.3 | 38.6 | 0.0991 | 458 |
| 2×240 | 78.00 | 1.4 | 44.8 | 0.0754 | 530 |
| 3×2.5 | 12.81 | 0.9 | 12.4 | 7.41 | 29 |
| 3x4 | 16.08 | 0.9 | 15.0 | 4.61 | 38 |
| 3x6 | 16.08 | 0.9 | 15.0 | 3.08 | 46 |
| 3×10 | 19.59 | 1.0 | 18.0 | 1.83 | 65 |
| 3×16 | 24.62 | 1.0 | 22.0 | 1.15 | 85 |
| 3×25 | 35.33 | 1.1 | 25.2 | 0.727 | 118 |
| 3×35 | 38.47 | 1.2 | 27.4 | 0.524 | 150 |
| 3×50 | 42.39 | 1.2 | 29.9 | 0.387 | 192 |
| 3×70 | 59.16 | 1.2 | 34.4 | 0.268 | 228 |
| 3×95 | 66.69 | 1.3 | 38.6 | 0.193 | 273 |
| 3×120 | 78.00 | 1.4 | 44.8 | 0.153 | 314 |
| 3x150 | 83.65 | 1.4 | 47.8 | 0.124 | 335 |
| 3×185 | 87.42 | 1.5 | 50.0 | 0.0991 | 390 |
| 3×240 | 94.95 | 1.5 | 54.0 | 0.0754 | 435 |
| 4×2.5 | 16.08 | 0.9 | 15.0 | 7.41 | 29 |
| 4x4 | 16.08 | 0.9 | 15.0 | 4.61 | 38 |
| 4×6 | 17.71 | 1.0 | 16.5 | 3.08 | 46 |
| 4x10 | 22.11 | 1.0 | 20.0 | 1.83 | 65 |
| 4×16 | 32.97 | 1.1 | 23.7 | 1.15 | 85 |
| 4×25 | 38.47 | 1.2 | 27.4 | 0.727 | 118 |
| 4x35 | 42.39 | 1.2 | 29.9 | 0.524 | 150 |
| 标称截面 Nominal Cross- section (mm) | 铜护套截面积 Copper sheath cross-sectional area(mm²) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20℃导体最大电阻 Max Conductor Resistance at 20°℃ ( Q2/km) | 载流量 Recommended current capacity (A) |
| 4×50 | 46.32 | 1.2 | 32.4 | 0.387 | 192 |
| 4×70 | 66.69 | 1.3 | 38.6 | 0.268 | 228 |
| 4×95 | 78.00 | 1.4 | 44.8 | 0.193 | 273 |
| 4×120 | 78.00 | 1.4 | 44.8 | 0.153 | 314 |
| 4×150 | 87.42 | 1.5 | 50.0 | 0.124 | 335 |
| 4x185 | 94.95 | 1.5 | 54.0 | 0.0991 | 390 |
| 3×16 +1×10 | 32.97 | 1.1 | 23.7 | 1.15 | 85 |
| 3x25 +1x16 | 38.47 | 1.2 | 27.4 | 0.727 | 118 |
| 3×35 +1×16 | 42.39 | 1.2 | 29.9 | 0.524 | 150 |
| 3×50 +1×25 | 46.32 | 1.2 | 32.4 | 0.387 | 192 |
| 3×70 +1×35 | 66.69 | 1.3 | 38.6 | 0.268 | 228 |
| 3x95 +1×50 | 78.00 | 1.4 | 44.8 | 0.193 | 273 |
| 3×120 +1×70 | 78.00 | 1.4 | 44.8 | 0.153 | 314 |
| 3x150 +1×70 | 87.42 | 1.5 | 50.0 | 0.124 | 335 |
| 3×185 +1×95 | 94.95 | 1.5 | 54.0 | 0.0991 | 390 |
| 3×240 +1×120 | 111.91 | 1.6 | 63.2 | 0.0754 | 435 |
| 4x16 +1×10 | 35.33 | 1.1 | 25.2 | 1.15 | 85 |
| 4x25 +1×16 | 42.39 | 1.2 | 29.9 | 0.727 | 118 |
| 4×35 +1×16 | 59.16 | 1.2 | 34.4 | 0.524 | 150 |
| 4×50 +1×25 | 59.16 | 1.2 | 34.4 | 0.387 | 192 |
| 4×70 +1×35 | 70.46 | 1.3 | 40.6 | 0.268 | 228 |
| 4x95 +1×50 | 78.00 | 1.4 | 44.8 | 0.193 | 273 |
| 4×120 +1×70 | 83.65 | 1.4 | 47.8 | 0.153 | 314 |
| 4×150 +1×70 | 91.19 | 1.5 | 52.0 | 0.124 | 335 |
| 4x185 +1×95 | 102.49 | 1.6 | 58.2 | 0.0991 | 390 |
| 4×240 +1×120 | 119.45 | 1.8 | 67.6 | 0.0754 | 435 |
| 3×16 +2×10 | 35.33 | 1.1 | 25.2 | 1.15 | 85 |
| 3×25 +2×16 | 42.39 | 1.2 | 29.9 | 0.727 | 118 |
| 3×35 +2×16 | 59.16 | 1.2 | 34.4 | 0.524 | 150 |
| 3×50 +2×25 | 59.16 | 1.2 | 34.4 | 0.387 | 192 |
| 3×70 +2×35 | 70.46 | 1.3 | 40.6 | 0.268 | 228 |
| 3x95 +2×50 | 78.00 | 1.4 | 44.8 | 0.193 | 273 |
| 3×120 +2×70 | 83.65 | 1.4 | 47.8 | 0.153 | 314 |
| 3×150 +2×70 | 91.19 | 1.5 | 52.0 | 0.124 | 335 |
| 3×185+2×95 | 102.49 | 1.6 | 58.0 | 0.0991 | 390 |
| 3×240 +2×120 | 119.45 | 1.8 | 67.6 | 0.0754 | 435 |
0.6/1kV 隔离型柔性矿物绝缘铝护套防火电缆
| 标称截面 Nominal Cross- section (mm²) | 铝护套截面积 Aluminum sheath cross-section (mm²) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference O.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) | |
| 1x10 | 18.84 | 1.1 | 19.6 | 1.83 | 97 | 77 |
| 1x16 | 23.74 | 1.1 | 22.2 | 1.15 | 125 | 100 |
| 1x25 | 23.74 | 1.1 | 22.2 | 0.727 | 165 | 130 |
| 1x35 | 26.19 | 1.1 | 23.5 | 0.524 | 200 | 160 |
| 1×50 | 29.01 | 1.2 | 25.2 | 0.387 | 245 | 195 |
| 1x70 | 32.78 | 1.2 | 27.4 | 0.268 | 305 | 245 |
| 1×95 | 36.55 | 1.3 | 29.6 | 0.193 | 375 | 300 |
| 1×120 | 39.38 | 1.4 | 31.3 | 0.153 | 435 | 350 |
| 1x150 | 42.20 | 1.4 | 33.0 | 0.124 | 500 | 400 |
| 1x185 | 45.97 | 1.5 | 35.2 | 0.0991 | 580 | 465 |
| 1×240 | 60.01 | 1.6 | 38.6 | 0.0754 | 685 | 550 |
| 1x300 | 64.40 | 1.6 | 40.6 | 0.0601 | 795 | 635 |
| 1×400 | 73.19 | 1.7 | 45.0 | 0.0470 | 930 | 745 |
| 1×500 | 98.47 | 1.8 | 51.2 | 0.0366 | 990 | 860 |
| 标称截面 Nominal Cross- section | 铝护套截面积 Aluminum sheath cross-section | 护套厚度 Sheath thickness | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) |
| (mm) 2×2.5 | (mm) 23.74 | (mm) 1.1 | 22.8 | 7.41 | 33 |
| 2×4 | 23.74 | 1.1 | 22.8 | 4.61 | 44 |
| 2×6 | 26.19 | 1.1 | 24.2 | 3.08 | 57 |
| 2×10 | 32.78 | 1.2 | 28.0 | 1.83 | 78 |
| 2×16 | 36.55 | 1.3 | 30.2 | 1.15 | 104 |
| 2×25 | 45.97 | 1.4 | 33.5 | 0.727 | 135 |
| 2×35 | 45.97 | 1.4 | 35.6 | 0.524 | 168 |
| 2×50 | 51.62 | 1.4 | 38.2 | 0.387 | 204 |
| 2×70 | 64.40 | 1.5 | 40.9 | 0.268 | 263 |
| 2×95 | 77.59 | 1.6 | 46.6 | 0.193 | 320 |
| 2×120 | 93.45 | 1.6 | 48.6 | 0.153 | 373 |
| 2×150 | 103.49 | 1.6 | 52.6 | 0.124 | 413 |
| 2×185 | 116.15 | 1.8 | 58.2 | 0.0991 | 458 |
| 2×240 | 163.28 | 2.0 | 64.8 | 0.0754 | 530 |
| 3×2.5 | 23.74 | 1.1 | 22.8 | 7.41 | 29 |
| 3×4 | 26.19 | 1.1 | 24.2 | 4.61 | 38 |
| 3×6 | 29.01 | 1.1 | 25.7 | 3.08 | 46 |
| 3×10 | 32.78 | 1.2 | 27.9 | 1.83 | 65 |
| 3×16 | 39.38 | 1.3 | 31.5 | 1.15 | 85 |
| 3×25 | 45.97 | 1.4 | 35.3 | 0.727 | 118 |
| 3×35 | 45.97 | 1.5 | 35.2 | 0.524 | 150 |
| 3×50 | 64.40 | 1.5 | 40.5 | 0.387 | 192 |
| 3×70 | 73.19 | 1.6 | 44.7 | 0.268 | 228 |
| 3×95 | 93.45 | 1.7 | 49.1 | 0.193 | 273 |
| 3×120 | 98.47 | 1.8 | 51.2 | 0.153 | 314 |
| 3x150 | 111.03 | 2.0 | 56.8 | 0.124 | 335 |
| 3×185 | 126.10 | 2.0 | 62.8 | 0.0991 | 390 |
| 3×240 | 178.98 | 2.0 | 70.0 | 0.0754 | 435 |
| 4x2.5 | 26.19 | 1.1 | 24.2 | 7.41 | 29 |
| 4x4 | 29.01 | 1.1 | 25.7 | 4.61 | 38 |
| 4x6 | 32.78 | 1.2 | 25.7 | 3.08 | 46 |
| 4×10 | 36.55 | 1.3 | 30.0 | 1.83 | 65 |
| 4×16 | 45.97 | 1.4 | 33.3 | 1.15 | 85 |
| 4×25 | 50.68 | 1.5 | 38.0 | 0.727 | 118 |
| 4×35 | 50.68 | 1.6 | 38.1 | 0.524 | 150 |
(续上表)
BTLY、BTLV
多芯电缆参数及其载流量
| 标称截面 Nominal Cross- section | 铝护套截面积 Aluminum sheath cross-section | 护套厚度 Sheath thickness | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ | 载流量 Recommended current capacity (A) |
| (mm) 4×50 | (mm) 68.80 | (mm) 1.6 | 42.6 | (Q2/km) 0.387 | 192 |
| 4×70 | 93.45 | 1.7 | 47.1 | 0.268 | 228 |
| 4×95 | 103.49 | 1.8 | 53.4 | 0.193 | 273 |
| 4×120 | 111.03 | 1.8 | 56.4 | 0.153 | 314 |
| 4×150 | 126.10 | 2.0 | 62.8 | 0.124 | 335 |
| 4x185 | 178.98 | 2.0 | 70.0 | 0.0991 | 390 |
| 4×240 | 200.96 | 2.2 | 77.4 | 0.0754 | 435 |
| 3x16 +1x10 | 42.20 | 1.4 | 33.3 | 1.15 | 85 |
| 3×25+1×16 | 50.68 | 1.5 | 38.0 | 0.727 | 118 |
| 3×x35 +1×16 | 50.68 | 1.6 | 38.1 | 0.524 | 150 |
| 3×50 +1×25 | 64.40 | 1.6 | 40.6 | 0.387 | 192 |
| 3×70 +1×35 | 77.59 | 1.7 | 47.1 | 0.268 | 228 |
| 3×95 +1×50 | 98.47 | 1.8 | 51.2 | 0.193 | 273 |
| 3×120 +1×70 | 111.03 | 1.8 | 56.4 | 0.153 | 314 |
| 3×150 +1×70 | 121.08 | 2.0 | 60.8 | 0.124 | 335 |
| 3x185 +1×95 | 169.56 | 2.0 | 67.0 | 0.0991 | 390 |
| 3×240 +1×120 | 185.26 | 2.2 | 72.0 | 0.0754 | 435 |
| 4x16 +1×10 | 45.97 | 1.5 | 35.5 | 1.15 | 85 |
| 4×25 +1×16 | 64.40 | 1.6 | 40.7 | 0.727 | 118 |
| 4x35 +1x16 | 68.80 | 1.6 | 42.9 | 0.524 | 150 |
| 4×50 +1×25 | 77.59 | 1.6 | 46.7 | 0.387 | 192 |
| 4×70 +1×35 | 103.98 | 1.8 | 53.4 | 0.268 | 228 |
| 4×95 +1×50 | 111.03 | 1.8 | 56.4 | 0.193 | 273 |
| 4x120 +1x70 | 121.08 | 2.0 | 60.8 | 0.153 | 314 |
| 4×150 +1×70 | 169.56 | 2.0 | 67.0 | 0.124 | 335 |
| 4x185 +1×95 | 214.02 | 2.0 | 70.0 | 0.0991 | 390 |
| 3×16 +2×10 | 45.97 | 1.5 | 35.5 | 1.15 | 85 |
| 3×25 +2×16 | 50.68 | 1.6 | 38.2 | 0.727 | 118 |
| 3×35 +2×16 | 64.40 | 1.6 | 40.9 | 0.524 | 150 |
| 3×50 +2×25 | 73.19 | 1.6 | 44.6 | 0.387 | 192 |
| 3×70 +2×35 | 98.47 | 1.8 | 51.2 | 0.268 | 228 |
| 3x95 +2×50 | 111.03 | 1.8 | 56.4 | 0.193 | 273 |
| 3×120 +2×70 | 116.05 | 2.0 | 58.8 | 0.153 | 314 |
| 3x150 +2×70 | 126.10 | 2.0 | 62.8 | 0.124 | 335 |
| 3×185 +2×95 | 178.98 | 2.1 | 70.0 | 0.0991 | 390 |
0.6/1kV 隔离型柔性矿物绝缘防火电缆
| 标称截面 Nominal Cross- section | 电缆近似重量 Approximate weight of cable | 护套厚度 Sheath thickness | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) | |
| (mm) 1x10 | (kg/km) 227.58 | (mm) 1.0 | 11.4 | 1.83 | 97 | 77 |
| 1x16 | 300.79 | 1.0 | 12.6 | 1.15 | 125 | 100 |
| 1x25 | 413.52 | 1.0 | 14.1 | 0.727 | 165 | 130 |
| 1x35 | 510.16 | 1.1 | 14.6 | 0.524 | 200 | 160 |
| 1×50 | 661.87 | 1.1 | 16.4 | 0.387 | 245 | 195 |
| 1x70 | 889.82 | 1.2 | 18.3 | 0.268 | 305 | 245 |
| 1×95 | 1152.22 | 1.2 | 19.9 | 0.193 | 375 | 300 |
| 1x120 | 1398.26 | 1.2 | 21.4 | 0.153 | 435 | 350 |
| 1x150 | 1694.69 | 1.3 | 23.1 | 0.124 | 500 | 400 |
| 1x185 | 2060.64 | 1.4 | 25.1 | 0.0991 | 580 | 465 |
| 1×240 | 2629.48 | 1.4 | 27.5 | 0.0754 | 685 | 550 |
| 1x300 | 3244.69 | 1.6 | 30.2 | 0.0601 | 795 | 635 |
| 1x400 | 4082.02 | 1.7 | 33.2 | 0.0470 | 930 | 745 |
| 1x500 | 5211.54 | 1.8 | 40.0 | 0.0366 | 990 | 860 |
| 标称截面 Nominal Cross- section | 电缆近似重量 Approximate weight of cable (kg/km) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) |
| (mm) 2×2.5 | 244.38 | 1.0 | 12.54 | 7.41 | 33 |
| 2×4 | 297.61 | 1.1 | 13.45 | 4.61 | 44 |
| 2×6 | 363.73 | 1.0 | 14.44 | 3.08 | 57 |
| 2×10 | 551.12 | 1.0 | 17.55 | 1.83 | 78 |
| 2x16 | 762.40 | 1.1 | 20.15 | 1.15 | 104 |
| 2×25 | 1051.28 | 1.2 | 22.93 | 0.727 | 135 |
| 2×35 | 1269.92 | 1.2 | 23.85 | 0.524 | 168 |
| 2×50 | 1710.52 | 1.3 | 27.67 | 0.387 | 204 |
| 2×70 | 2274.84 | 1.5 | 31.07 | 0.268 | 263 |
| 2×95 | 2986.53 | 1.6 | 34.67 | 0.193 | 320 |
| 2×120 | 3634.87 | 1.6 | 37.67 | 0.153 | 373 |
| 2×150 | 4360.00 | 1.8 | 40.67 | 0.124 | 413 |
| 2×185 | 5365.25 | 2.0 | 44.87 | 0.0991 | 458 |
| 2×240 | 6831.27 | 2.1 | 49.67 | 0.0754 | 530 |
| 3×2.5 | 286.29 | 1.0 | 13.42 | 7.41 | 29 |
| 3×4 | 353.33 | 1.0 | 14.40 | 4.61 | 38 |
| 3×6 | 437.49 | 1.0 | 15.47 | 3.08 | 46 |
| 3×10 | 671.67 | 11 | 19.00 | 1.83 | 65 |
| 3×16 | 935.94 | 1.2 | 21.78 | 1.15 | 85 |
| 3×25 | 1310.38 | 1.2 | 24.76 | 0.727 | 118 |
| 3x35 | 1607.09 | 1.3 | 25.74 | 0.524 | 150 |
| 3×50 | 2174.24 | 1.5 | 30.04 | 0.387 | 192 |
| 3×70 | 2921.45 | 1.6 | 33.67 | 0.268 | 228 |
| 3×95 | 3858.47 | 1.7 | 37.52 | 0.193 | 273 |
| 3×120 | 4731.56 | 1.8 | 40.95 | 0.153 | 314 |
| 3×150 | 5725.38 | 2.0 | 44.35 | 0.124 | 335 |
| 3×185 | 7016.27 | 2.1 | 48.62 | 0.0991 | 390 |
| 3×240 | 8951.62 | 2.3 | 53.76 | 0.0754 | 435 |
| 4×2.5 | 340.20 | 1.0 | 14.42 | 7.41 | 29 |
| 4x4 | 424.45 | 1.0 | 15.52 | 4.61 | 38 |
| 4x6 | 532.91 | 1.0 | 16.72 | 3.08 | 46 |
| 4×10 | 830.79 | 1.2 | 20.84 | 1.83 | 65 |
| 4×16 | 1171.97 | 1.2 | 23.95 | 1.15 | 85 |
| 4×25 | 1644.26 | 1.3 | 27.27 | 0.727 | 118 |
| 4×35 | 2053.50 | 1.4 | 28.54 | 0.524 | 150 |
| 4×50 | 2773.95 | 1.6 | 33.32 | 0.387 | 192 |
| 标称截面 Nominal Cross- section (mm) | 电缆近似重量 Approximate weight of cable (kg/km) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q2/km) | 载流量 Recommended current capacity (A) |
| 4×70 | 3709.99 | 1.7 | 37.15 | 0.268 | 228 |
| 4×95 | 4937.38 | 1.9 | 41.62 | 0.193 | 273 |
| 4×120 | 6095.37 | 2.0 | 45.65 | 0.153 | 314 |
| 4×150 | 7317.66 | 2.1 | 49.00 | 0.124 | 335 |
| 4×185 | 9001.87 | 2.3 | 53.95 | 0.0991 | 390 |
| 4×240 | 11591.47 | 2.5 | 60.08 | 0.0754 | 435 |
| 3×16 +1×10 | 1134.80 | 1.2 | 23.83 | 1.15 | 85 |
| 3x25 +1×16 | 1584.62 | 1.3 | 27.15 | 0.727 | 118 |
| 3×35 +1×16 | 1919.72 | 1.4 | 28.42 | 0.524 | 150 |
| 3×50 +1×25 | 2629.94 | 1.6 | 33.24 | 0.387 | 192 |
| 3×70 +1×35 | 3496.92 | 1.6 | 36.87 | 0.268 | 228 |
| 3x95 +1×50 | 4618.94 | 1.8 | 41.34 | 0.193 | 273 |
| 3×120 +1×70 | 5752.25 | 1.9 | 45.37 | 0.153 | 314 |
| 3x150 +1×70 | 6795.30 | 2.0 | 48.72 | 0.124 | 335 |
| 3×185 +1×95 | 8425.95 | 2.2 | 53.68 | 0.0991 | 390 |
| 3×240 +1×120 | 10794.54 | 2.4 | 59.80 | 0.0754 | 435 |
| 4×16 +1×10 | 1372.02 | 1.2 | 25.88 | 1.15 | 85 |
| 4x25 +1×16 | 1964.25 | 1.4 | 29.96 | 0.727 | 118 |
| 4×35 +1×16 | 2375.21 | 1.5 | 31.13 | 0.524 | 150 |
| 4×50 +1×25 | 3233.08 | 1.6 | 36.25 | 0.387 | 192 |
| 4×70 +1×35 | 4389.01 | 1.8 | 40.90 | 0.268 | 228 |
| 4×95 +1×50 | 5798.27 | 2.0 | 45.82 | 0.193 | 273 |
| 4×120 +1×70 | 7157.20 | 2.0 | 49.87 | 0.153 | 314 |
| 4×150 +1×70 | 8554.66 | 2.2 | 53.98 | 0.124 | 335 |
| 4×185 +1×95 | 10579.76 | 2.4 | 59.44 | 0.0991 | 390 |
| 4×240 +1×120 | 13540.77 | 2.6 | 65.98 | 0.0754 | 435 |
| 3×16 +2×10 | 1344.00 | 1.2 | 25.88 | 1.15 | 85 |
| 3×25 +2×16 | 1915.05 | 1.4 | 29.96 | 0.727 | 118 |
| 3×35 +2×16 | 2237.74 | 1.4 | 30.93 | 0.524 | 150 |
| 3×50 +2×25 | 3097.38 | 1.6 | 36.25 | 0.387 | 192 |
| 3×50 +2×35 | 3242.91 | 1.6 | 36.25 | ||
| 3×70 +2×35 | 4183.42 | 1.7 | 40.70 | 0.268 | 228 |
| 3×95+2×50 | 5488.24 | 1.9 | 45.62 | 0.193 | 273 |
| 3×120 +2×70 | 6846.94 | 2.0 | 49.87 | 0.153 | 314 |
| 3×150 +2×70 | 8042.21 | 2.1 | 53.78 | 0.124 | 335 |
| 3×185 +2×95 | 10014.78 | 2.3 | 59.24 | 0.0991 | 390 |
| 3×240+2×120 | 12756.15 | 2.5 | 65.78 | 0.0754 | 435 |
750V 及以下金属护套氧化镁矿物绝缘电缆
| 标称截面 Nominal Cross- section (mm) | 铜护套截面积 Copper sheath cross-sectional area(mm²) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q2/km) | 载流量 Recommended current capacity (A) |
| 1x1.5 | 5.78 | 0.4 | 4.9 | 12.1 | 30 |
| 1x2.5 | 6.44 | 0.4 | 5.3 | 7.41 | 39 |
| 1x4 | 7.70 | 0.5 | 5.9 | 4.61 | 51 |
| 1x6 | 8.92 | 0.5 | 6.4 | 3.08 | 63 |
| 1x10 | 10.68 | 0.5 | 7.3 | 1.83 | 81 |
| 1x16 | 13.16 | 0.5 | 8.3 | 1.15 | 107 |
| 1×25 | 16.96 | 0.6 | 9.6 | 0.727 | 139 |
| 1x35 | 20.22 | 0.6 | 10.7 | 0.524 | 168 |
| 1×50 | 24.72 | 0.7 | 12.1 | 0.387 | 207 |
| 1×70 | 30.88 | 0.8 | 13.7 | 0.268 | 251 |
| 1×95 | 36.68 | 0.8 | 15.4 | 0.193 | 300 |
| 1x120 | 42.57 | 0.9 | 16.8 | 0.153 | 344 |
| 1x150 | 49.46 | 0.9 | 18.4 | 0.124 | 388 |
| 1x185 | 57.44 | 0.9 | 20.4 | 0.0991 | 434 |
| 1×240 | 69.35 | 1.0 | 23.3 | 0.0754 | 483 |
| 1×300 | 84.51 | 1.1 | 26.0 | 0.0601 | 795 |
| 1x400 | 105.92 | 1.2 | 30.0 | 0.0470 | 948 |
| 标称截面 Nominal Cross- section (mm) | 铜护套截面积 Copper sheath cross-sectional area(mm) | 护套厚度 Sheath thickness (mm) | 电缆参考外径 Reference 0.D(mm) | 20°℃导体最大电阻 Max Conductor Resistance at 20°℃ (Q/km) | 载流量 Recommended current capacity (A) |
| 2x1 | 10.87 | 0.5 | 7.3 | 18.1 | 17.5 |
| 2x1.5 | 12.48 | 0.5 | 7.9 | 12.1 | 23.5 |
| 2x2.5 | 14.55 | 0.6 | 8.7 | 7.41 | 32 |
| 2x4 | 17.60 | 0.6 | 9.8 | 4.61 | 42 |
| 2×6 | 20.92 | 0.7 | 10.9 | 3.08 | 54 |
| 2x10 | 26.73 | 0.7 | 12.7 | 1.83 | 74 |
| 2x16 | 34.09 | 0.8 | 14.7 | 1.15 | 98 |
| 2×25 | 43.37 | 0.9 | 17.1 | 0.727 | 128 |
| 3x1 | 11.93 | 0.5 | 7.7 | 18.1 | 15 |
| 3x1.5 | 13.61 | 0.6 | 8.3 | 12.1 | 20 |
| 3x2.5 | 16.14 | 0.6 | 9.3 | 7.41 | 27 |
| 3x4 | 19.33 | 0.6 | 10.4 | 4.61 | 36 |
| 3×6 | 23.10 | 0.7 | 11.5 | 3.08 | 46 |
| 3x10 | 30.26 | 0.8 | 13.6 | 1.83 | 62 |
| 3x16 | 38.06 | 0.8 | 15.6 | 1.15 | 83 |
| 3x25 | 47.34 | 0.9 | 18.2 | 0.727 | 108 |
| 4x1 | 13.79 | 0.6 | 8.4 | 18.1 | 14.5 |
| 4x1.5 | 15.77 | 0.6 | 9.1 | 12.1 | 20.5 |
| 4x2.5 | 18.46 | 0.6 | 10.1 | 7.41 | 27 |
| 4x4 | 22.89 | 0.7 | 11.4 | 4.61 | 36 |
| 4x6 | 26.73 | 0.7 | 12.7 | 3.08 | 46 |
| 4x10 | 34.34 | 0.8 | 14.8 | 1.83 | 61 |
| 4x16 | 44.39 | 0.9 | 17.3 | 1.15 | 80 |
| 4x25 | 55.98 | 0.9 | 20.1 | 0.727 | 104 |
铝合金电缆 ALUMINUM ALLOY CABLE
0.6/1kV YJLHV 铝合金导体交联聚乙烯绝缘聚氯乙烯护套电力电缆(含普通型 阻燃型) 95-95
0.6/1kV YJLHY 铝合金导体交联聚乙烯绝缘聚烯烃护套电力电缆(无卤低烟) 95-95
0.6/1kV YJLHV22 铝合金导体交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型 阻燃型) 95-95
0.6/1kV YJLHY23 铝合金导体交联聚乙烯绝缘钢带铠装聚烯烃护套电力电缆(无卤低烟) 95-95
8.7/15kV YJLHV 铝合金导体交联聚乙烯绝缘聚氯乙烯护套电力电缆(含普通型 阻燃型) 96-96
8.7/15kV YJLHY 铝合金导体交联聚乙烯绝缘聚烯烃护套电力电缆(无卤低烟) 96-96
8.7/15kV YJLHV22 铝合金导体交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型 阻燃型) 96-96
8.7/15kV YJLHY23 铝合金导体交联聚乙烯绝缘钢带铠装聚烯烃护套电力电缆(无卤低烟) 96-96
26/35kV YJLHV 铝合金导体交联聚乙烯绝缘聚氯乙烯护套电力电缆(含普通型 阻燃型) 97-97
26/35kV YJLHY 铝合金导体交联聚乙烯绝缘聚烯烃护套电力电缆(无卤低烟) 97-97
26/35kV YJLHV22 铝合金导体交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆(含普通型 阻燃型) 97-97
26/35kV YJLHY23 铝合金导体交联聚乙烯绝缘钢带铠装聚烯烃护套电力电缆(无卤低烟) 97-97
铝合金电缆用途
可广泛应用于高层建筑、民用建筑、星级酒店、医院、剧场、会议中心、图书馆、博物馆、政府机关、金融中心、广电中心、体育中心、工矿、石油化工、机场、隧道、地铁、轻轨、地下车库、人防、船舶、海上石油平台、航空航天、钢铁冶金、购物中心、停车场等场合。
铝合金电缆与铜芯电缆对比
◆经济性对比
使用铝合金电缆取代铜电缆,可以减少电缆的重量,同时相应降低安装成本,减少设备和电缆的磨损,使安装工作更为轻松。价格比铜电缆低 30% -50% ,使用铝合金电缆具备有绿色环保特性。
| 铝合金电缆 | 铜电缆 | ||
| 铝合金电缆线芯 截面/mm² | 90℃铝合金电缆载流量 (托盘、梯架敷设) | 铜电缆线芯 截面/mm² | 90℃铜芯电缆载流量 (托盘、梯架敷设) |
| 25 | 123 | 16 | 120 |
| 35 | 153 | 25 | 159 |
| 50 | 184 | 35 | 195 |
| 70 | 230 | 50 | 237 |
| 120 | 324 | 70 | 301 |
| 150 | 374 | 95 | 362 |
| 185 | 431 | 120 | 419 |
| 240 | 516 | 150 | 481 |
| 300 | 594 | 185 | 556 |
| 400 | 655 | 240 | 662 |
| 2x150 | 748 | 300 | 774 |
| 2x185 | 862 | 300 | 774 |
| 2x185 | 862 | 400 | 917 |
| 2×240 | 1032 | 400 | 917 |
铝合金电缆的型号及使用特性
◆产品型号
(1) 普通型电缆型号
| YJLHV | 铝合金导体交联聚乙烯绝缘聚氯乙烯护套电力电缆 |
| YJLHV22 | 铝合金导体交联聚乙烯绝缘钢带铠装聚氯乙烯护套电力电缆 |
| YJLHY | 铝合金导体交联聚乙烯绝缘聚烯烃护套电力电缆(无卤低烟) |
| YJLHY23 | 铝合金导体交联聚乙烯绝缘钢带铠装聚烯烃护套电力电缆(无卤低烟) |
(2) 阻燃型电缆型号,在普通电缆型号前加Z(A、B、C、D)。
◆产品使用特性
(1) 额定电压U0/U为 10.6/1~26/35\mathsf{k V}_{\circ}
(2) 电缆导体的最高额定温度为 90°\mathsf C. 。
(3) 短路时(最长持续时间不超过5秒)电缆导体的最高温度不超过 250°\mathsf C. 。
(4) 电缆敷设时的环境温度应不低于 {*}0°{\mathsf{C}} ,其最小弯曲半径如下:单芯电缆— .20(\mathsf{D}+\mathsf{d}) ,mm多芯电缆—15 (\mathsf{D}+\mathsf{d}) ,mm(D、d分别为电缆外径与主导体的标称直径,mm)
企业优势
◆产品执行标准
本产品按GB/T31247标准组织生产,还可按用户要求的其它标准生产。
阻燃型电缆除上述标准外,阻燃型电缆除按上述标准外,其阻燃性能按GB/T19666标准规定分成A类、B类、C类和D类四个级别,A类的阻燃性最优,用户可根据需要选用。
耐火型电缆的耐火性能按GB/T19666标准规定分成A类耐火、耐火两种不同的耐火类别( 950°\mathsf C. —1000℃/90min,750℃—800℃/90min)和Ⅰ、Ⅱ、Ⅲ、Ⅳ四个级别,用户可根据使用场合及需求选用。
\diamond 生产设备
生产设备采用自动控制,电脑实时检测电缆的制造过程,实现高度自动化生产,彻底消除影响产品质量的人为因素。
◆生产工艺
每一项流程都有专业的工程师进行检测,确保电缆的生产质量。电缆的生产全程采用封闭式电脑管理,以保证每根电缆都与我们的标准分毫不差。
◆铝合金性能
1、导体性能
在满足相同导电性能的前提下,铝合金电缆的重量是同样载流量的铜缆的一半。通过独特的合金成分比例,先进的导体压紧工艺,成熟的退火控制,通过适当放大截面,完全可以约达到铜电缆的载流量,而且当铝合金电缆的导体面积是铜缆的1.5倍时,其电气性能基本相当。铝固有的防腐蚀性能源自当铝表面与空气接触时立即形成的薄而坚固的氧化层。这种氧化层特别耐受各种形式的腐蚀。铝能承受恶劣环境的特点使其被广泛应用于盘内电缆的导体,以及许多工业元件和容器。腐蚀的产生通常与不同的金属在潮湿环境中连接有关,可使用相应的保护措施来防止腐蚀的发生,比如使用润滑油、抗氧化剂和保护涂层。直埋敷设的导体应使用绝缘层或护套来防止腐蚀。在含硫的环境中,例如铁路隧道、污水处理等和其他类似地方,铝的抗腐蚀性能大大优于铜。
2、绝缘性能
合金电缆采用 90°C 交联聚乙烯绝缘,能在 90°C 的条件下正常工作,具有高温运行稳定的优点。所有截面规格的电缆,均有颜色标志。它们由3个强耐久模压塑料条组成,均匀地放置在黑色抗紫外绝缘层的外部,以保证无论从哪个角度,都能够看到导体的色标。
3、铠装性能
铝合金电缆铠装采用AA8030系列合金,坚固的合金能够有效保护电缆内部结构。
铝合金电缆联锁型铠装电缆的机械和电气性能符合IEC关于线缆的各项规范标准,具有散热好、耐腐蚀、低烟无卤的特点。铝合金电缆铠装结构采用无重金属、非磁性材料制造,在保护环境的同时,由于非磁性材料的特性,不会像普通钢带铠装那样产生涡流,造成不必要的电能浪费,减少安全隐患。
铝合金电缆使用的联锁型铠装技术使得其电缆比常规电缆更具有柔韧性,弯曲半径更大,安装方便,且节约空间。
4、护套性能
铝合金电缆通过了国家电线电缆质量监督检验中心的耐低温性能测试,在- .40°C 条件下,成品电缆低温弯曲及低温冲击实验中,均无裂纹出现,从而证明了其护套卓越的耐低温性能。在我国东北及西北等寒冷地区的室外应用中,具有极大优势。
铝合金电缆同时还通过了国家电线电缆质量监督检验中心的抗紫外线性能测试(人工气候老化试验)。在氙灯气候老化箱中,电缆护套材料经过1008小时老化后的抗张强度和断裂伸长率的变化率均符合要求。因此,具有优秀的耐候性,适宜直接在室外敷设。
铝合金电力电缆绝缘及外护套不含重金属,清洁环保。与同类其它产品相比,对环境污染小得多。
铝合金电缆护套外部有明显的产品名称标识,方便您选择电缆
◆服务
一、产品质量的售后服务
1)质保期为使用该产品一年内,时间从电缆验收合格日起,在此期间本公司提供免费保养。
2)如果用户需要, 48小时内向用户提供电缆备品;如出现质量问题,公司组织有关技术服务人员 在接到通知后8小时内到达现场进行处理,直到故障除,电缆完全恢复正常使用为止。
3)由用户组织,电缆投入使用半年后,公司派出技术人员到用户现场,对产品投入应用的情况进行全面的了解,并征求用户的同意,对电缆进行全面的检查工作。任何在检查过程中发现的电缆和附件本体存在的异常现象,技术人员均以报告的形式向用户反馈,并提出相关的维护、保养方法。
4)由用户要求,在质保期结束前,由公司的专业技术工程师和用户代表对电缆线路进行一次全面检查工作。
5)质保期后因用户使用、管理不当所造成的损失由用户承担,本公司可提供免费的技术服务工作。)质保期后的故障维修,经权威部门鉴定属于寿命异常问题时,本公司负责免费更换或维修。
7)质保期满后,如用户要求,公司可按照订购合同的价格和参考届时的市场价格,优惠向用户提供电缆。
二、提供对产品安装现场技术服务
用户有需要,本公司在接到电缆安装通知后的两天内派出两名技术人员到现场进行调试技术服务工作,这些工作的开展将注重以下
1)电缆敷设安装过程中注意事项和技术要求的现场督导。
2)电缆附件安装环境、安装要求、注意事项的现场督导。
3)对电缆敷设、安装和调试过程中出现的难点向施工单位提出解决方案,并协助解决。
4)电缆户外和户内终端安装说明及电缆中间接头安装说明。
三、提供对产品知识的培训服务
如果需方要求,本公司将提供相关的培训服务。
1)培训主要以现场培训为主,培训对象是施工人员。
2)授课人为到施工现场工作的技术人员,培训资料由本公司提供。
3)现场培训结束后,了解说明书内容和正确使用各种工具和材料的技能。
电缆设计的一些注意事项
◆根据负荷性质、环境条件、应用场所等条件选择适当的型号,根据环境条件及选择的电缆型号确定适当的敷设方式根据载流量选择截面
1)确定用电设备的设备功率(短时工作制设备换算为统一负载持续率下的功率)
2)根据需要系数法、利用系数法等方式确定计算负荷和计算电流
3)根据环境条件、敷设方式确定电缆载流量系数
4)查找与电缆型号、敷设方式对应的载流量表,选择适当的导体截面,使载流量满足负荷计算电流的要求
◆根据电压损失校验截面
1)根据负荷性质确定允许的导体末端最大电压损失
2)查找与电缆型号、敷设方式对应的电压损失表,校验所选截面满足电压损失的要求
3)如不满足,则增大导体截面直至校验通过
◆根据热稳定校验截面
1)根据配电系统计算线路最大短路电流
2)查找热稳定短路电流表,校验所选截面是否满足短路热稳定的要求
3)如不满足,则增大导体截面直至校验通过
◆依据经济寿命内总费用最少选择截面
1)获取电缆价格、安装成本、附件成本,确定初期费用
2)计算电缆寿命期内长期运行电能损耗费用
3)比较所选截面及邻近截面总费用数值,作为选择截面的辅助依据
主要技术参数
◆载流量计算条件
◆环境温度 25°C
◆电缆导体工作温度 90°\mathsf{C}
◆电缆埋地敷设时,土壤热阻系数g {\mathsf{\tau}}=1.0°\mathsf{C m}/\mathsf{W} ,但尚未考虑电缆长期运行时由于水分迁移导致土壤热阻系数升高的现象。◆电缆埋地敷设时,电缆的轴心与地面距离为 1000\mathsf{mm} 。
◆多根电缆敷设时,电缆的轴心距离 S=3D
| 标称截面 Nomsinal section (mm) | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | Recommende流ent cpacity(A) | |||||||||||||||||
| 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯|4+1芯 | 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 | 5芯 | 3+2芯4+1芯 | Single-core | Multile-cores | |||||
| 空气 | Under ground | 空气 | Under | |||||||||||||||||
| ground | ||||||||||||||||||||
| 10 16 | 8.7 9.7 | 15.8 18.0 | 16.7 19.1 | 18.3 | 17.6 20.3 | 19.9 22.9 | 18.8 21.8 | 19.3 22.3 | 89 115 | 239 287 | 254 342 | 316 430 | 321 430 | 378 515 | 366 496 | 385 497 | 86 115 | 101 118 | 72 85 | 93 118 |
| 25 | 11.0 | 20.5 | 21.8 | 20.9 24.0 | 23.2 | 26.3 | 25.0 | 25.6 | 154 | 391 | 476 | 602 | 858 | 750 | 678 | 714 | 140 | 150 | 112 | 151 |
| 35 | 12.0 | 22.5 | 24.0 | 26.4 | 25.1 | 29.0 | 26.9 | 27.8 | 190 | 479 | 590 | 755 | 706 | 917 | 801 | 868 | 170 | 177 | 145 | 184 |
| 50 | 13.3 | 25.3 | 26.9 | 29.9 | 28.4 | 33.1 | 32.7 | 31.8 | 237 | 602 | 792 | 975 | 892 | 1203 | 1058 | 1146 | 210 | 215 | 173 | 223 |
| 70 | 15.4 | 29.4 | 31.5 | 35.0 | 33.0 | 39.0 | 38.4 | 37.2 | 321 | 777 | 1085 | 1336 | 1196 | 1655 | 1406 | 1531 | 298 | 287 | 273 | 283 |
| 95 | 17.1 | 32.8 | 35.2 | 39.3 | 37.2 | 43.6 | 42.9 | 41.7 | 416 | 1108 | 1378 | 1767 | 1599 | 2172 | 1830 | 1998 | 337 | 325 | 317 | 333 |
| 120 | 18.9 | 36.5 | 39.3 | 43.7 | 43.1 | 48.5 | 47.4 | 46.7 | 505 | 1318 | 1734 | 2149 | 1989 | 2646 | 2313 | 2482 | 380 | 370 | 352 | 356 |
| 150 | 21.0 | 40.7 | 43.6 | 48.6 | 48.1 | 54.0 | 53.2 | 53.2 | 626 | 1595 | 2161 | 2630 | 2349 | 3296 | 2735 | 2990 | 447 | 430 | 410 | 412 |
| 185 | 23.1 | 45.0 | 48.2 | 53.8 | 53.4 | 59.8 | 59.0 | 59.0 | 759 | 1959 | 2632 | 3339 | 2972 | 4034 | 3399 | 3703 | 510 | 484 | 453 | 456 |
| 240 | 25.9 | 50.5 | 54.2 | 60.5 | 59.6 | 67.2 | 65.9 | 65.9 | 958 | 2559 | 3341 | 4210 | 3739 | 5167 | 4274 | 4705 | 583 | 555 | 521 | 525 |
| 300 | 28.1 | 55.0 | 59.1 | 65.9 | 65.8 | 73.3 | 72.8 | 72.8 | 1166 | 3086 | 4065 | 5143 | 4527 | 5932 | 5182 | 5711 | - | - | ||
| 400 | 31.7 | 62.1 | 66.7 | 74.5 | 74.2 | 82.9 | 82.1 | 82.3 | 1476 | 3774 | 5053 | 6471 | 5747 | 8055 | 6636 | 7318 | ||||
| 500 | 35.5 | 69.7 | 74.9 | 83.7 | 83.0 | 93.2 | 92.0 | 92.2 | 1862 | 4961 | 6425 | 8319 | 7363 | 9873 | 8228 | 9001 | - | - | - | - |
| 39.5 | - | - | 2354 | - | - | - | ||||||||||||||
| 630 | 二 | |||||||||||||||||||
| section (mm) | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | Recommende流iret cpaity(A) Multipe-cores | |||||||||||||
| 1芯 | 2芯 | 3芯 | 4芯 | 3+1芯 5芯 | 3+2芯4+1芯 | 1芯 | 2芯 | 3芯 | 4芯 3+1芯 | 5芯 | 3+2芯4+1芯 | 空气 | Upter | |||
| 10 | 13.1 | 19.3 | 20.2 21.7 | 21.0 | 23.4 | 22.2 | 22.8 | 206 | 426 | 466 547 | 535 | 629 | 605 | ground | ||
| 16 | 14.2 | 21.7 | 22.7 24.3 | 23.7 | 26.3 | 25.3 | 25.8 | 244 | 507 | 575 685 | 666 | 793 | 756 | 617 775 | 70 84 | 90 120 |
| 25 | 15.6 | 24.2 | 25.5 27.6 | 26.9 | 29.9 | 28.7 | 29.3 | 308 | 652 | 753 907 | 875 | 1069 | 1005 | 1037 | 111 | 143 |
| 35 | 16.7 | 26.2 | 27.6 30.4 | 28.7 | 33.2 | 30.9 | 31.9 | 356 | 766 | 895 1090 | 1029 | 1299 | 1163 | 1238 | 143 | 165 |
| 50 | 18.2 | 29.0 | 31.0 34.0 | 32.6 | 37.2 | 34.8 | 35.8 | 426 | 928 | 1153 1374 | 1290 | 1657 | 1503 | 1572 | 170 | 205 |
| 70 | 20.3 | 33.4 | 35.5 39.0 | 37.1 | 42.0 | 41.5 | 42.7 | 538 | 1166 | 1462 1798 | 1656 | 2549 | 1902 | 2425 | 270 | 270 |
| 95 | 20.8 | 36.8 | 39.2 42.3 | 43.3 | 46.3 | 47.2 | 47.2 | 645 | 1524 | 2206 2656 | 2505 | 3171 | 2827 | 2994 | 314 | 305 |
| 120 | 20.8 | 40.4 | 42.4 46.8 | 47.4 | 51.3 | 51.7 | 51.9 | 786 | 2170 | 2595 3147 | 2986 | 3759 | 3412 | 3583 | 350 | 345 |
| 150 | 20.8 | 43.8 | 46.7 51.6 | 52.4 | 57.1 | 57.5 | 57.5 | 917 | 2531 | 3152 3766 | 3461 | 4526 | 3964 | 4218 | 404 | 400 |
| 185 | 20.8 | 48.0 | 51.4 57.2 | 57.6 | 62.9 | 63.3 | 63.3 | 1082 | 3020 | 3740 4567 | 4200 | 5394 | 4757 | 5061 | 447 | 450 |
| 240 | 20.8 | 54.0 | 57.8 64.1 | 63.8 | 70.5 | 70.2 | 70.2 | 1313 | 3706 | 4547 5579 | 5106 | 6681 | 5786 | 6218 | 509 | 515 |
| 300 | 20.8 | 58.6 | 62.8 69.6 | 70.0 | 76.6 | 77.1 | 77.1 | 1561 | 4348 | 5395 6651 | 6033 | 7602 | 6849 | 7378 | - | |
| 400 | 20.8 | 65.6 | 70.3 78.0 | 78.4 | 87.1 | 86.4 | 87.8 | 1912 | 5194 | 6576 8168 | 7443 10777 | 8514 | 10038 | |||
| 500 | 20.8 | 73.2 | 78.4 88.3 | 87.3 | 97.2 | 97.4 | 97.6 | 2717 | 6547 | 8127 11065 | 9259 | 12916 | 11267 | 12042 | - | - |
| 630 | 20.8 | 3294 | ||||||||||||||
| 标称截面 Nominal Cross- secton | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Singecore | Thre-cores | Singe-core | Thre-cores | 单芯 Single-core | 3芯 Three-cores | |||
| Under ground | Underground | |||||||
| 25 | 22.4 | 43.0 | 486 | 1716 | 130 | 125 | 95 | 105 |
| 35 | 23.4 | 45.3 | 541 | 1912 | 160 | 150 | 115 | 125 |
| 50 | 24.7 | 48.3 | 612 | 2161 | 190 | 175 | 135 | 150 |
| 70 | 26.6 | 52.4 | 730 | 2602 | 240 | 215 | 170 | 185 |
| 95 | 28.4 | 56.0 | 859 | 3026 | 290 | 260 | 205 | 220 |
| 120 | 29.9 | 59.2 | 967 | 3408 | 335 | 295 | 235 | 250 |
| 150 | 31.4 | 62.7 | 1087 | 3834 | 385 | 330 | 270 | 280 |
| 185 | 33.2 | 66.3 | 1253 | 4361 | 430 | 370 | 310 | 320 |
| 240 | 35.8 | 71.5 | 1484 | 5117 | 510 | 430 | 370 | 375 |
| 300 | 37.8 | 76.4 | 1714 | 5941 | 580 | 480 | 420 | 425 |
| 400 | 41.8 | 84.3 | 2100 | 7282 | 675 | 550 | 485 | 485 |
| 500 | 45.8 | 94.0 | 2591 | 8898 | 770 | 620 | 二 | |
| 630 | 49.6 | 3139 | 875 | 695 | ||||
| 标称截面 Nominal Cross- secton | 参考外径 Reference O.D(mm) | 参考重量 Reference Weight(kg/km) | 载流量 Recommended current cpacity(A) | |||||
| Singe-core | Singe-core | 单芯 Single-core | 3芯 Three-cores | |||||
| Thre-cores | Thre-cors | Underground | Under ground | |||||
| 25 | 25.8 | 48.0 | 775 | 2789 | 130 | 125 | 96 | 105 |
| 35 | 26.8 | 50.3 | 855 | 3041 | 160 | 150 | 115 | 125 |
| 50 | 28.1 | 53.7 | 943 | 3414 | 190 | 175 | 140 | 150 |
| 70 | 30.0 | 57.6 | 1085 | 3927 | 240 | 215 | 170 | 185 |
| 95 | 31.6 | 61.4 | 1223 | 4473 | 290 | 260 | 205 | 220 |
| 120 | 33.3 | 64.8 | 1364 | 4970 | 335 | 295 | 240 | 250 |
| 150 | 34.8 | 68.5 | 1506 | 5518 | 385 | 330 | 270 | 280 |
| 185 | 37.8 | 72.3 | 2034 | 6178 | 430 | 370 | 310 | 320 |
| 240 | 40.4 | 77.5 | 2301 | 7074 | 510 | 430 | 360 | 375 |
| 300 | 42.6 | 84.0 | 2602 | 8911 | 580 | 480 | 420 | 425 |
| 400 | 46.6 | 92.1 | 3097 | 10599 | 675 | 550 | 485 | 485 |
| 500 | 51.0 | 101.8 | 3743 | 12590 | 770 | 620 | ||
| 630 | 54.6 | 4357 | 875 | 695 | ||||
| 标称截面 Nominal Cross- section (mm) | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | |||
| 单芯 Single-core | 3芯 Three-cores | |||||
| ai | 埋地 Under ground | 埋地 Under ground | ||||
| 50 | 37.7 | 1357 | 190 | 175 | 140 | 145 |
| 70 | 39.4 | 1500 | 235 | 215 | 170 | 180 |
| 95 | 41.2 | 1669 | 290 | 255 | 205 | 215 |
| 120 | 42.7 | 1806 | 330 | 290 | 235 | 245 |
| 150 | 44.4 | 1981 | 375 | 325 | 270 | 275 |
| 185 | 46.0 48.6 | 2166 | 425 | 370 | 305 | 310 |
| 240 | 50.8 | 2450 2750 | 500 | 425 | 355 | 360 |
| 300 | 54.6 | 570 | 475 | 410 | 410 | |
| 400 | 60.4 | 3218 | 655 | 540 | 470 | 465 |
| 500 630 | 64.0 | 4089 4692 | 750 855 | 610 680 | ||
| 标称截面 Nominal Cross- section (mm) | 参考外径 Reference O.D (mm) | 参考重量 Reference Weight (kg/km) | 载流量 Recommended current cpacity(A) | |||
| 单芯 Single-core | 3芯 Three-cores | |||||
| 空气 In air | 埋地 Under ground | inair | 埋地 Under ground | |||
| 50 | 42.5 | 2279 | 190 | 175 | 140 | 145 |
| 70 | 44.2 | 2483 | 235 | 215 | 170 | 180 |
| 95 | 46.0 | 2672 | 290 | 255 | 205 | 215 |
| 120 | 47.7 | 2865 | 330 | 290 | 240 | 245 |
| 150 | 49.4 | 3086 | 375 | 325 | 270 | 275 |
| 185 | 51.2 | 3334 | 425 | 370 | 310 | 310 |
| 240 | 53.6 | 3651 | 500 | 425 | 360 | 360 |
| 300 | 56.0 | 4038 | 570 | 475 | 420 | 410 |
| 400 | 59.8 | 4597 | 655 | 540 | 485 | 465 |
| 500 | 66.0 | 5680 | 750 | 610 | ||
| 630 | 69.8 | 6412 | 855 | 680 | ||