44 Function
Code Name Setting Range Default Property
Group P3: Vector Control Parameters
P3.23
Overvoltage
modulation
coefficient
100% ~ 120% 110% ☆
P3.24 Bus voltage filter 0.000 ~ 0.100 0.000 ☆
P3.25
Selection of
Back EMF
compensation
0: Disabled
1: Enabled 0 ★
Group P5: Input Terminals
P5.00 X1
function selection
0: No function
1: Forward RUN (FWD)
2: Reverse RUN (REV)
3: Three-wire control mode
4: Forward JOG (FJOG )
5: Reverse JOG (RJOG )
8: Coast to stop
9: Fault reset (RESET )
11: External fault NO input
33: External fault NC input
48: Servo pump PID selection terminal 1
49: Servo pump PID selection terminal 2
50: CAN communication enabled
51: Slave pump enabled as master
pump
52: Switchover from pressure mode to
speed mode
53: Slave pump address selection
terminal 1
54: Slave pump address
selection terminal 2
55: Switchover from injection to pressure
holding
56: Fault reset (not allowed at
overcurrent)
1 ★
P5.01 X2
function selection 0 ★
P5.02 X3
function selection 0 ★
P5.03 X4
function selection 9 ★
P5.04 X5
function selection 0 ★
P5.10 X filter time 1 ~ 10 4 ☆
P5.11 Terminal
command mode
0: Two-line 1
1: Two-line 2
2: Three-line 1
3: Three-line 2
0 ★
P5.13 FIV1
minimum input 10.00V ~ P5.15 0.02V ☆
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group P5: Input Terminals
P5.14
Corresponding
setting of FIV1
minimum input
-100.0% ~ +100.0% 0.0% ☆
P5.15 FIV1 maximum
input P5.13 ~ +10.00V 10.00V ☆
P5.16
Corresponding
setting of FIV1
maximum input
P5.13 ~ +10.00V 100.0% ☆
P5.17 FIV1 filter time 0.000s ~ 10.000s 0.010s ☆
P5.18 FIV2 minimum
input -10.00V ~ P5.20 0.02V ☆
P5.19
Corresponding
setting of FIV2
minimum input
-100.0% ~ +100.0% 0.0% ☆
P5.20 FIV2 maximum
input P5.18 ~ +10.00V 10.00V ☆
P5.21
Corresponding
setting of FIV2
maximum input
-100.0% ~ +100.0% 100.0% ☆
P5.22 FIV2 filter time 0.000s ~ 10.000s 0.005s ☆
P5.23 FIC minimum
input -10.00V ~ P5.25 0.02V ☆
P5.24
Corresponding
setting of FIC
minimum input
-100.0% ~ +100.0% 0.0% ☆
P5.25 FIC maximum
input P5.23 ~ +10.00V 10.00V ☆
P5.26
Corresponding
setting of FIC
maximum input
-100.0% ~ +100.0% 100.0% ☆
P5.27 FIC filter time 0.000s ~ 100.00s 0.000s ☆
45
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group P6: Output Terminals
P6.01
Control board
relay (RB / RC)
0: No output
1: Servo drive running
2: Fault output
6: Servo motor overload pending
7: Servo drive overload pending
12: Accumulative running time reached
15: Ready
20: Communication setting
23: Double-discharge plunger pump
sloping switchover 1
24: Pressure control state output
25: Slave pump alarm
26: Double-discharge plunger pump
sloping switchover 2
27: Bus voltage establishment
28: Business running time reached
29: Business running time not reaching
24 hours
30: Output of Maximum reverse
rotational speed
2 ☆
function selection
P6.02
Control board
relay (TA / TC)
1 ☆
function selection
P6.03
Control board
relay (KA / KC)
0 ☆
function selection
P6.04 reserved
P6.05 reserved
P6.07 FOV1
output selection
0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
7: FIV1
8: FIV2
9: FIC
10: Feedback rotational speed (oil
pressure control mode)
11: Feedback pressure (oil
pressure control mode)
12 ~ 16: Reserved
10 ☆
P6.08 FOV2
output selection 11 ☆
P6.10 FOV1
offset coefficient -100.0% ~ +100.0% 0.00% ☆
P6.11 FOV1 gain -10.00 ~ +10.00 1.00 ☆
P6.12 FOV2
offset coefficient -100.0% ~ +100.0% 0.0% ☆
P6.13 FOV1 gain -10.00 ~ +10.00 1.00 ☆
46 Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group P7: Operation Panel and Display
P7.02 STOP/RESET
key function
0: Valid only in operation panel control
1: Stop function of the STOP key valid in
terminal control
2: Reset function of the STOP key valid
in terminal control
3: Both stop and reset functions of the
STOP key valid in terminal control
2 ☆
P7.06 Load speed
display coefficient 0.0001 ~ 6.5000 1.0000 ☆
P7.07 Heatsink
temperature 1 0.0℃~ 120.0℃ - ●
P7.09 Accumulative
running time 0h ~ 65535h - ●
P7.11 Software version - - ●
P7.12 Set running time 0h ~ 65535h 0 ☆
P7.13
Action selection
upon set running
time reached
0: Continue to run
1: Stop and report \"END2\" 0
Group P8: Manufacture Factory Setting Parameter
Group P9: Fault and Protection
P9.00
Motor overload
protection
selection
0: Disabled
1: Enabled 0 ☆
P9.01 Motor overload
protection gain 0.20 ~ 10.00 2.00 ☆
P9.02
Motor
temperature
protection
0: Disabled
1: Enabled 1 ☆
P9.03 Runaway speed
deviation 0.50Hz ~ 50.00Hz 10.00Hz ☆
P9.04 Detection time of
runaway fault 0.1s ~ 20.0s 10.0s ☆
P9.05 Startup protection
selection
0: Disabled
1: Enabled 0 ☆
47
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group P9: Fault and Protection
P9.06
Software
undervoltage
threshold
120.0V ~ 400.0V Model
dependent ☆
P9.07
Delection of shortcircuit to groung
uopn power-on
0: Disabled
1: Enabled 1 ☆
P9.08 Braking voltage 650.0V ~ 820.0V Model
dependent ☆
P9.09 Allowed braking unit
running time 0.1s ~ 3600.0s 5.0s ☆
P9.12
Power input phase
loss protection
selection
Bits: Power input phase loss
protection selection
0: Disabled 1: Enabled
1 ☆
P9.13
Power output phase
loss protection
selection
0: Disabled
1: Enabled 1 ☆
P9.14 1st Fault type
0: No fault
1: Reserved
2: Overcurrent during acceleration
3: Overcurrent during deceleration
4: Overcurrent at constant speed
5: Overvoltage during acceleration
6: Overvoltage during deceleration
7: Overvoltage at constant speed
9: Under voltage
10: Servo drive overload
12:Power input phase loss
13: Power output phase loss
14: Heatsink overheat
15: External device fault
16: Communication fault
17: Contactor fault
18: Current detection fault
19: Motor auto-tuning fault
21: EEPROM read-write fault
23: Short circuit to ground
24: Reserved
25: Reserved
26:Accumulative running time reached
27: Business running time reached
40: Wave-chasing current limiting fault
42: CAN communication interrupted
- ●
P9.15 2nd Fault type - ●
48 Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group P9: Fault and Protection
P9.16 3rd (Iatest)
Fault type
43: Resolver fault during motor auto-tuni
ng
44: Speed deviation protection fault
45: Motor overheat
46: Servo pump sensor fault
47: Slave fault spending
48: CAN address conflicted
49: Cable between resolver and PG
card disconnected
52: Multi-master fault in
multi-pump convergent flow
58: Parameter restoration fault
59: Back EMF abnormal fault
61: Brake pipe in braking
protection state for long time
63: Reverse running time reached
- ●
P9.17
Frequency
@ 3rd (Iatest)
fault
- - ●
P9.18
Current
@ 3rd (Iatest)
fault
- - ●
P9.19
Bus Voltage
@ 3rd (Iatest)
fault
- - ●
P9.20
Input
terminal state
@ 3rd (Iatest)
fault
- - ●
P9.21
Input
terminal state
@ 3rd (Iatest)
fault
- - ●
Group PA: Servo Pump PID Control Parameters
PA.00 FI zero drift auto
correction
0: Disabled
1: Enabled 0 ☆
PA.02
Oil pressure
PID algorithm
selection
0 ~ 2 0 ★
49
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group PA: Servo Pump PID Control Parameters
PA.03 Oil pressure
control Kp1 0.0 ~ 800.0 210.0 ☆
PA.04 Oil pressure
control Ti 1 0.001s ~ 10.000s 0.100s ☆
PA.05 Oil pressure
control Td 1 0.000s ~ 1.000s 0.000s ☆
PA.06 Oil pressure
control Kp 2 0.0 ~ 800.0 210.0 ☆
PA.07 Oil pressure
control Ti 2 0.001s ~ 10.000s 0.100s ☆
PA.08 Oil pressure
control Td 2 0.000s ~ 1.000s 0.000s ☆
PA.09 Oil pressure
control Kp 3 0.0 ~ 800.0 210.0 ☆
PA.10 Oil pressure
control Ti 3 0.001s ~ 10.000s 0.100s ☆
PA.11 Oil pressure
control Td 3 0.000s ~ 1.000s 0.000s ☆
PA.12 Oil pressure
control Kp 4 0.0 ~ 800.0 210.0 ☆
PA.13 Oil pressure
control Ti 4 0.001s ~ 10.000s 0.100s ☆
PA.14 Oil pressure
control Td 4 0.000s ~ 1.000s 0.000s ☆
PA.15
Max. value of
Integral limit
deviation
0.0kg/cm² ~ PA.20 45.0kg/
cm2 ☆
PA.16 Integral limit
mode selection 0 ~ 1 0 ☆
PA.17 Oil pressure
control mode
0: Non-oil pressure control mode
1: Oil pressure control mode 1 (CAN
setting)
2: Oil pressure control mode (AI Setti
ng)
3: CAN oil pressure control mode 2
4: Reserved
0 ★
50 Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group PA: Servo Pump PID Control Parameters
PA.18 Max. motor speed Motor speed corresponding to max.
frequency lower limit to 30000 rpm 2000 rpm ☆
PA.19 Reverse pressure
relief speed 0.0% ~ 100.0% 10.0% ☆
PA.20 System oil
pressure
0.0kg/cm² to Maximum oil pressure
(PA.21) 175kg/cm² ☆
PA.21 Max. oil pressure System oil pressure (PA.20) to 500.0kg/
cm² 250kg/cm² ☆
PA.22 Minimum flow 0.0% ~ 50.0% 0.50% ☆
PA.23 Minimum
pressure 0.0 kg/cm² ~ 50.0 kg/cm² 0.5kg/ cm² ☆
PA.24
Oil pressure
reference ramp
time
0.000s ~ 2.000s 0.020s ☆
PA.25
S-curve rise filter
time of set oil
pressure
0.001s ~ 10.000s 0.030s ☆
PA.26
S-curve fall filter
time of set oil
pressure
0.001s ~ 1.000s 0.030s ☆
PA.27
Min. pressure of
reverse pressure
relief
0.0kg/cm² ~ PA.20 0 ☆
PA.28
Long-time running
protective time of
reverse pressure
relief
0.001s ~ 5.000s 0.000s ☆
Group PB: Servo Pump Control Auxiliary Parameters
PB.00
Pressure sensor
fault detection
current lower limit
0% ~ 300%(P2.03) 100% ☆
PB.01
Pressure sensor
fault detection
speed upper limit
0% ~ 100%(PA.18) 50% ☆
51
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group PB: Servo Pump Control Auxiliary Parameters
PB.02
Fault detection
time of oil
pressure sensor
0.000s: Detection invalid
0.001s ~ 60.000s 0.500s ☆
PB.03
Setting of max.
speed in pressure
control
0.0% ~ 100.0% 10.0% ☆
PB.04
Setting of min.
oil pressure in
pressure control
0.0% ~ 100.0% 60.0% ☆
PB.05
Delay of pressure
control state
output
0.000s ~ 10.000s 0.100s ☆
PB.06
Overshoot
suppression
detection level
0 ~ 2000 200 ☆
PB.07
Overshoot
suppression
coefficient
0 ~ 3.000 0.200 ☆
PB.08 Oil pressure loop
gain coefficient 0.20 ~ 5.00 1.00 ☆
PB.09
Oil pressure
deviation of
oil pressure
suppression
disabled
0.0kg/cm² ~ PA.20 10.0kg/cm² ☆
PB.10 Pressure loop
output upper limit 0 ~ 50.0 2.0 ☆
PB.11 Pressure loop
output upper limit 50.0% ~ 250.0% 160.0% ☆
PB.12
Injection valve
opening delay
time
0.000s ~ 0.500s 0.00s ☆
PB.13
Start valve
pressure relief
delay
0.001 ~ 5.000s 0.100s ☆
PB.14
Exit valve
pressure relief
delay
0.001 ~ 5.000s 0.100s ☆
PB.15
Pressure
deviation lower
limit of start valve
pressure relief
0.0 ~ PA.20( system oil pressure) 0.0kg ☆
52 Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Injection Overshoot Suppression Coefficient
PB.16
Pressure lower
limit of start valve
pressure relief
0.0 ~ PA.20(system oil pressure) 0.0kg ☆
PB.17 Rotational speed
filter time 0s ~ 5.000s 0.005s ☆
PB.18 Current filtering time 0s ~ 5.000s 0.010s ☆
PB.19 Flow rise filtering
time 0s ~ 1.000s 0.100s ☆
PB.20 Flow fall filter time 0s ~ 1.000s 0.100s ☆
PB.21 Flow leakage
compensation 0.0% ~ 50.0% 0.0% ☆
PB.22 Injection S-curve rise
time 0.001s ~ 1.000s 0.030s ☆
PB.23 Injection S-curve fall
time 0.001s ~ 1.000s 0.030s ☆
PB.24 Injection flow rise
slope 0.001s ~ 5.000s 0.100s ☆
PB.25 Injection flow fall
slope 0.001s ~ 5.000s 0.100s ☆
PB.26 Oil pressure
reference rise time 0.000s ~ 2.000s 0.020s ☆
PB.27 Oil pressure
reference fall time 0.000s ~ 2.000s 0.020s ☆
PB.28
Injection overshoot
suppression
detection level
0 ~ 2000 200 ☆
PB.29
Injection overshoot
suppression
coefficient
0.000s ~ 3.000s 0.200s ☆
Group PC: Multi-pump Oil Pressure Control Parameters
PC.01
Master judges
whether to send
slave speed enabled
in multi-pump
0: Forbid enabling the slave speed
1: Allow enabling the slave speed 0 ★
53
Function Code Table Function Code Table
Function
Code Name Setting Range Default Property
Group PC: Multi-pump Oil Pressure Control Parameters
PC.02
Pressure holding
control gain
in multi-pump
convergent flow
20 ~ 800 100 ☆
PC.03
Pressure
deviation for
decreasing PI
to de-twitter
in multi-pump
injection mode
0.0 ~ 50.0kg 5.0kg ☆
PC.04
Flow lower limit
for decreasing
PI to de-twitter
in multi-pump
injection mode
0 ~ 30000rpm 0rpm ☆
PC.05
Flow detection
time for
decreasing PI
to de-twitter
in multi-pump
injection mode
0.200s ~ 2.000s 0.400s ☆
PC.06
Pressure
deviation of slave
pump not working
in the CAN multipump mode
0 ~ 50.0kg 5.0kg ☆
PC.07
Flow lower limit
of slave pump
not working in the
CAN multi-pump
mode
-100.0% ~ 100.0% 0 ☆
PC.08
Judgment delay
of slave pump
to stop without
speed reference
0.010s ~ 5.000s 1.000s ☆
PC.09
Deceleration time
of slave pump
to stop without
speed reference
0.001s ~ 5.000s 0.200s ☆
54 Function Code Table Function Code Table
55
Function
Code Name Setting Range Default Property
Group PC: Multi-pump Oil Pressure Control Parameters
PC.10 Slave min. input -100.0% ~ PC.12 0.0% ☆
PC.11
Corresponding
setting of slave
min. input
-100.0% ~ 100.0% 0.0% ☆
PC.12 Slave medium
input PC.10 ~ PC.14 10.0% ☆
PC.13 Slave medium
input -100.0% ~ 100.0% 0.0% ☆
PC.14 Slave max. input PC.12 ~ 100.0% 100.0% ☆
PC.15
Corresponding
setting of slave
max. input
-100.0% ~ 100.0% 100.0% ☆
Group PD: Communication Parameters
PD.00 Baud rate
0:300BPS
1:600BPS
2:1200BPS
3:2400BPS
4:4800BPS
5:9600BPS
6:19200BPS
7:38400BPS
8:57600BPS
9:115200BPS
5 ☆
PD.01 Data format
0: No check, data format <8, N, 2>
1: Even parity check, data format<8, E,
1> 2:
Odd Parity check, data format<8,O,1>
3: No check data format <8, N, 1> Valid
for Modbus
0 ☆
PD.02 PD.01
1 ~ 200
0: Broadcast address
1 ☆
PD.03 Response delay 0ms ~ 20ms 2 ☆
Function Code Table Function Code Table
Function
Code Name Name Default Property
Group PD: Communication Parameters
PD.04 Timeout
duration
0.0:Invalid
0.1s ~ 60.0s 0.0 ☆
PD.05 Communication
protocol 0:Standard Modbus protocol 0 ☆
PD.06 CAN baud rate
0:20k
1:50k
2:125k
3:250k
4:500k
5:1M
4 ☆
PD.07
CAN
communication
address
1 ~ 30 1 ☆
PD.08
CAN continuous
communication
time
0.0s(invalid )
0.1s ~ 600.0s 0.3S ☆
PD.09 CAN multi-pump
mode
0: Broadcast mode
1: Multi- master mode 0 ☆
PD.10 CAN slave
address 1 0 ~ 65535 0 ☆
PD.11 CAN slave
address 2 0 ~ 65535 0 ☆
PD.12 CAN slave
address 2 0 ~ 65535 0 ☆
PD.13 CAN slave
address 4 0 ~ 65535 0 ☆
Group PP: User Function Code
PP.00 User Password 0 ~ 65535 0 ☆
PP.01 Parameter
initialization
0: No operation
01: Restore default setting (excluding
servo motor parameters)
02: Clear fault records
0 ★
PP.02
Password for
user storage
operation
0 ~ 65535 0 ☆
PP.03 User storage
mode
0: No operation
1: Store user parameters 0 ☆
56 Function Code Table Function Code Table
If PP.00 is set to a non-zero number parameter protection is enabled. You must enter the correct user
password to enter the menu. To cancel the password protection function enter with password and set PP.00 to
0.
Function Code Name Min. Unit
Group D0: View Servo Drive Parameters
D0.00 Running frequency (Hz) 0.01Hz
D0.01 Set frequency (Hz) 0.01Hz
D0.02 Bus voltage (V) 0.1V
D0.03 Output voltage (V) 1V
D0.04 Output current (A) 0.01A
D0.05 Output power (kW) 0.1kW
D0.06 Output torque (%) 0.1%
D0.07 X input state -
D0.08 X input state -
D0.09 FIV1 voltage (after correction) -10.00V ~ 10.000V
D0.10 FIV2 voltage (after correction) -10.00V ~ 10.000V
D0.11 FIC voltage (after correction) -10.00V ~ 10.000V
D0.30 FIV1 voltage (before correction) -10.00V ~ 10.000V
D0.31 FIV2 voltage (before correction) -10.00V ~ 10.000V
D0.32 FIC voltage (before correction) -10.00V ~ 10.000V
D0.34 FIC voltage (before correction) 0.000V ~ 10.000V
D0.35 FOV2 output voltage 0.000V ~ 10.000V
57
Function Code Table Function Code Table
Function Code Name Min. Unit
Group D01: View Servo Pump Parameters
D1.00 Real-time angle 0.0° ~ 359.9°
D1.01 Set oil pressure 0.0kg to system oil pressure
D1.02 Feedback oil pressure 0.0kg to maximum oil pressure
D1.03 Motor speed -9999rpm ~ 30000rpm
D1.04 FIV1 analog voltage -10.00V ~ 10.000V
D1.05 FIV2 analog voltage -10.00V ~ 10.000V
D1.06 FIC analog voltage -10.00V ~ 10.000V
D1.07 FIC analog voltage -10.00V ~ 10.000V
D1.08 FIV2 zero drift -10.00V ~ 10.000V
D1.09 FIC zero drift -10.00V ~ 10.000V
D1.10 Reference flow 0.00Hz ~ maximum frequency
D1.11 Resolver signal interference degree 0 ~ 1000
D1.12 Oil pressure reference of host computer 0.0kg ~ system oil pressure
D1.13 CAN communication interference status 0 ~ 128
D1.14 Number of CAN messages sent 0 ~ 65535
D1.15 Number of CAN messages received 0 ~ 65535
D1.16 CAN buffer use ratio 0 ~ 1.00%
58 Function Code Table Function Code Table
Chapter 5
Fault Checking & Troubleshooting
5.1 Fault Alarm & Troubleshooting
The PH300 series servo drive provides alarm information and protective functions. When
a fault occurs, PH300 serie servo drives implement the protective function, stop output, makes
the fault relay act, and displays the fault code on the operation panel. Before contacting Physis
for technical support, you can first determine the fault type, analyze the causes, and perform
troubleshooting according to the description in this chapter. If the fault can’t be rectified, please
contact the agent or Physis.
The OUOC in the warning message is a hardware overcurrent or overvoltage signal. In
most cases, the hardware overvoltage fault causes the OUOC alarm.
Symptom Fault Display Possible Causes Solutions
Overcurrent
during
acceleration
OC1
The servo drive output circuit
is earthed or short circuited.
Eliminate external faults.
Motor auto-tuning is not
performed properly. Perform motor auto-tuning.
The acceleration time is too
short.
Increase the acceleration time.
The customized torque boost
or V/F curve is not proper.
Adjust the customized torque boost
or V/F curve properly.
The input voltage of the
servo drive is too low.
Adjust the input voltage to the normal
range.
The rotating motor is
restarted.
Remove the sudden load.
The rotating motor is
restarted.
Remove the sudden load.
The capacity level of the
servo drive is too low.
Increase the capacity level of the
servo drive.
59
Fault checking & Troubleshooting Fault Alarm & Troubleshooting
Symptom Fault Display Possible Causes Solutions
Overcurrent
during
deceleration
OC2
The servo drive output circuit
is earthed or short circuited.
Eliminate external faults.
Motor auto-tuning is not
performed properly. Perform motor auto-tuning.
The deceleration time is too
short.
Increase the deceleration time.
The input voltage of the servo
drive is too low.
Adjust the input voltage to the normal
range.
A sudden load is added during
deceleration.
Remove the sudden load.
The braking unit and braking
resistor are not installed.
Eliminate external faults. Install an
output reactor if the cable is too long.
Overcurrent
at constant
speed OC3
The servo drive output circuit
is earthed or has leakage
current.
Eliminate external faults. Install an
output reactor if the cable is too long.
Motor auto-tuning is not
performed properly. Perform motor auto-tuning.
The input voltage of the servo
drive is too low.
Adjust the input voltage to the normal
range.
A sudden load is added during
deceleration.
Increase the capacity level of the
servo drive.
The capacity level of the servo
drive is too low.
Increase the capacity level of the
servo drive.
Overvoltage
during
acceleration
OU1
The input voltage of servo
drive is too high.
Adjust the input voltage to the normal
range.
An external force drives the
motor during acceleration.
Remove the external force or install a
braking resistor.
The acceleration time is too
short. Increase the acceleration time .
The braking unit and braking
resistor are not instalIed.
Install the braking unit and braking
resistor.
Overvoltage
during
deceleration
OU2
The input voltage of servo
drive is too high.
Adjust the input voltage to the normal
range.
An external force drives the
motor during deceleration.
Remove the external force or install a
braking resistor.
The deceleration time is too
short. Increase the deceleration time .
The braking unit and braking
resistor are not instalIed.
Install the braking unit and braking
resistor.
60 Fault checking & Troubleshooting Fault Alarm & Troubleshooting
Symptom Fault Display Possible Causes Solutions
Overvoltage at
constant
speed
OU3
The input voltage of servo
drive is too high.
Adjust the input voltage to the
normal range.
An external force drives the
motor during acceleration.
Remove the external force or install
a braking resistor.
Control power
supply fault POF
The input voltage of the servo
drive is not in the allowable
range.
The input voltage of the servo drive
is not in the allowable range.
Undervoltage LU
Instantaneous power failure
occurs Perform the reset operation.
The input voltage of the servo
drive is not in the allowable
range.
Adjust the input voltage to the
normal range.
The DC bus voltage is
abnormal.
Contact the agent or Physis.
The rectifier bridge and
snubber resistor are abnormal.
The drive board is abnormal.
The main control board is
abnormal.
Servo drive
overload OL2
The load is too heavy or the
motor is blocked.
The capacity level of the servo
drive is too low.
The capacity level of the servo
drive is too low.
Increase the capacity level of the
servo drive.
Motor
overload OL1
The load is too heavy or the
motor is blocked.
Set the motor parameters correctly.
Reduce the load and check the
motor and connected machine.
The capacity level of the servo
drive is too low.
Increase the capacity level of the
servo drive.
Phase loss on
input side LI
The three-phase power supply
is abnormal. Eliminate external faults.
The drive board is abnormal.
Contact the agent or Physis.
The anti-thunder board is
abnormal.
The main control board is
abnormal.
61
Fault checking & Troubleshooting Fault Alarm & Troubleshooting
62 Symptom Fault Display Possible Causes Solutions
Phase loss on
output side Lo
The power cables between
the servo drive and the servo
motor are abnormal.
Eliminate external faults.
Three phase outputs of the
servo drive are unbalanced
in the V/F mode without the
motor connected.
Three-phase winding of the motor
is abnormal and eliminate the fault.
The drive board is abnormal.
Contact the agent or Physis. The main control board is
abnormal.
Module
overheat OH
The ambient temperature is
too temperature. Reduce ambient temperature.
The air filter is blocked. Clean the air filter.
The cooling fan is damaged. Replace the cooling fan.
The module thermistor is
damaged. Replace the thermistor.
The inverter module is
damaged. Replace the inverter module.
Motor overheat OH2
Wiring of the PTC sensor for
motor overheat protection is
incorrect.
Eliminate the wiring fault.
The motor temperature is too
high.
Reduce the load of the motor, add
cooling fans or increase the motor
capacity.
Motor demagnetization Contact the agent or Physis.
External device
fault EF
External fault signal is input
via a X terminal. Eliminate external faults.
External fault signal is input
via a virtual IO function. Perform the reset operation.
Communication
fault EF
The host computer is not
working. Check wiring of the host computer.
The wiring for communication
is abnormal.
Check wiring of the communication
cable.
The communication
parameters in group PD are
set improperly.
Set the communication parameters
properly.
Fault checking & Troubleshooting Fault Alarm & Troubleshooting
Symptom Fault Display Possible causes Solutions
Contactor fault RAy
The drive board and power
supply are abnormal.
Replace the drive board or power
board.
The contactor is abnormal. Replace the contactor.
Current detection
fault IE
The HALL device is
abnormal. Replace the HALL devices.
The drive board is
abnormal. Replace the drive board.
Current detection
fault TE
The motor parameters are
not set according to the
nameplate.
Set the motor parameters correctly.
The motor auto-tuning
times out.
Check wiring between the servo
drive and the servo motor.
Encoder fault PG
The encoder model don’t
match the servo drive. Select the adapted encoder.
The encoder wiring is
incorrect. Eliminate the wiring fault.
The encoder is damaged. Replace the encoder.
The PG card is faulty. Replace the PG card.
EEPROM fault EEP The Chip of EEPROM is
damaged. Replace the main control board.
Servo drive
hardware fault OUOC Overvoltage Deal with overvoltage fault
Overcurrent Deal with overcurrent fault
Short circuit to
ground GND The motor is short circuited
to the ground Replace the cable or motor
Accumulative
running time
reached
END1
The accumulative running
time is equal to or greater
than set accumulative
running time
Clear the record through the
parameter initialization function
Accumulative
business running
time reached
END2
Accumulative business
running time is equal to or
greater than set business
running time.
Clear the record through the
parameter initialization function
PID feedback
lost during
running
PIDE PID feedback lost during
running Contact the agent or Physis.
Wave-chasing
current limit fault CBC
The load is too heavy or
the motor is blocked.
Reduce the load and check the motor
and connected machine.
Reduce the load and check
the motor and connected
machine.
Increase the capacity level of the
servo drive.
63
Fault checking & Troubleshooting Fault Alarm & Troubleshooting
Symptom Fault Display Possible causes Solutions
Too large speed
deviation ESP
The encoder parameters are
set incorrectly.
The encoder parameters are set
incorrectly.
The motor auto-tuning is not
performed.
Reduce the load and check the
motor and connected machine.
P9.03 and P9.04 are set
incorrectly.
Set P9.03 and P9.04 correctly
according to the actual situation.
Motor overspeed fault oSP
Incorrect encoder parameter
setting.
Set the encoder parameter
correctly.
The motor auto-tuning is not
performed.
Set parameters correctly according
to the actual situation.
Initial position
fault INI
The motor parameter are
not set based on the actual
situation.
Check that the motor parameters
are set correctly and whether the
setting of rated current is too small.
Pressure
sensor fault AL. 46
Wiring of the pressure sensor
is incorrect. Eliminate the wiring fault.
The power supply of
pressure sensor is abnormal. Eliminate the power supply fault.
Output of pressure sensor is
abnormal. Replace the pressure sensor.
CAN
communication
interrupted
CAN
CAN communication
parameters are set
incorrectly.
Set correct CAN communication
parameters.
The wiring of CAN
communication is incorrect. Eliminate the wiring fault.
64 Fault checking & Troubleshooting Fault Alarm & Troubleshooting
5.2 Eliminate Wiring Fault
The following symptoms may occur during use of the servo drive. When these symptoms
occur, perform simple analysis based on the following table.
SN Fault Possible Causes Solutions
01 No display upon
power-on.
There is no power supply to the servo
drive or the power input to the servo
drive is too low.
Check the power input.
The switch of power supply on the drive
board is Faulty. Check the power input.
Components inside the servo drive are
damaged. Contact the agent or Physis.
02
\"PH300\" is
displayed at poweron.
The cable connecting the control board
and the drive board is in poor contact.
Contact the agent or Physis.
Components on the control board are
damaged.
The motor or the motor cable is short
circuited to the ground.
The HALL device is faulty.
The power input to the servo drive is
too low.
03 \"GND\" is displayed
at power-on.
The motor or the motor output cable is
short circuited to the ground.
Check the insulation status
of the motor and the output
cable with a megger.
The servo drive is damaged. Contact the agent or Physis.
04
The servo drive
display is normal
upon power- on, but
displays \"PH300\"
after running and
stops immediately.
The external control terminal cable is
short circuited. Eliminate external fault
The cooling fan is damaged or does not
rotate. Replace the cooling fan.
Table 5-1 Symptoms and Diagnostics
65
Fault checking & Troubleshooting Eliminate the wiring fault
SN Fault Possible Causes Solutions
05
OH (IGBT
overheat) fault is
reported frequently.
The carrier frequency is set too
high.
Reduce the carrier frequency
(P017).
The cooling fan is damaged, or the
air filter is blocked.
Replace the cooling fan and
clean the air filter.
Components (thermal coupler or
others) inside the servo drive are
damaged.
Contact the agent or Physis.
06
The motor does
not rotate after the
servo drive runs.
Check the cable between the servo
drive and the servo motor
Ensure the cable between the
servo drive and the motor is
normal.
The motor is damaged or locked
rotor occurs.
Replace the motor or rectify
mechanical fault.
The motor is damaged or locked
rotor occurs.
Check and set the motor
parameters again.
The control board is faulty. Contact the agent or Physis.
07 X terminals are
disabled.
The related parameters are set
incorrectly.
Check and set the parameters in
group P5 again.
The jumper across OP and +24 V
becomes loose. Re-connect the cables.
The jumper across OP and +24 V
becomes loose. Contact the agent or Physis.
08
In CLVC mode, the
motor speed can’t
be rise.
The encoder is damaged or the
encoder wiring is incorrect.
Replace the encoder and correct
the wiring.
The PG card is faulty. Replace the PG card.
The drive board is faulty. Contact the agent or Physis.
09
The servo drive
reports overcurrent
and overvoltage
fault frequently.
The motor parameters are set impro
perly.
Set the motor parameters or
perform motor auto-tuning again.
The acceleration / deceleration time
is improper.
Set proper acceleration
/ deceleration time .
The load fluctuates. Contact the agent or Physis.
10
rAy is reported
upon power- on or
running.
The soft startup contactor is not
closed.
Check whether the contactor
cable is loose;
Check whether the contactor is
faulty;
Check whether the contactor
24V power supply is faulty;
Contact the agent or Physis;
66 Eliminate the wiring fault Fault checking & Troubleshooting
67
Chapter 6 Maintenance
Warning
● Maintenance must be performed according to designated maintenance methods.
● Maintenance inspection and replacement of parts must be performed only by qualified professionals.
● Must shut off power supply and wait for 10 minutes before maintenance or inspection.
● Do not touch components directly of PCB board, otherwise servo drive can be damaged by static
electricity
● Ensure all screws must be tightened after maintenance.
6.1 Daily Maintenance
In order to avoid the potential faults and ensure servo drive proper operation, prolong
service life of the servo drive, it’s necessary to carry out routine and periodic maintenance.
Check the following items of daily maintenance:
Inspection Items Inspection Points
Temperature /
Humidity
Ambient temperature : 0℃ to 40 ℃
Humidity:0% to 95% and no condensation
Oil stain / Dust Ensure no oil stain, dust in servo drive.
Servo drive
Check whether the servo drive is overheat or vibration.
Check whether the servo drive is overheat or vibration.
Ensure voltage input and frequency is in correct range.
Motor Check whether the servo motor whether is overheat or vibration,
whether abnormal noise and phase loss.
6.2 Periodic Inspection
Customer should perform period inspection within 6 months as followings.
Maintenance Daily Maintenance & Periodic Inspection
Inspection Items Inspection content Methods
Screws of control
terminals Whether the screws are loose. Tighten the screws
PCB board Dust and smudginess Clean the dust and smudginess
with compressed air drying
Fan Dust and smudginess Debris removal;
Replace the cooling fan
Electrolytic
capacitor Discoloration or odor Replace the electrolytic capacitor
Radiator Dust and smudginess Clean the dust and smudginess
with compressed air drying
Components and
parts Dust and smudginess Clean the dust and smudginess
with compressed air drying
Vulnerable components of the servo drive include the cooling fan and filter electrolytic
capacitor. Their service life is related to the operation environment and maintenance status.
Generally, the service life is shown as follows:
◆ Fan: Must be replaced when using up to 20,000 hours.
◆ Electrolytic Capacitor: Must be replaced when using up to 30,000-40,000 hours.
Physis will provide 12-month warranty from date of manufacturing for the failure or damage
under normal use conditions.
6.3 Replacement of Vulnerable Components
6.4 Warranty Agreement
68 Replacement of Vulnerable Components & Warranty Agreement Maintenance
69
Chapter 7 Selection of Peripheral Electrical Devices
7.1 AC Input Reactor
Name Description
Moulded case circuit breaker
(MCCB) or earth leakage circuit
breaker (ELCB)
Protect the wiring of servo drives, and to be beneficial to
installation and maintenance.
Electromagnetic contractor (MC) It’s convenient for servo drives’ power on and off, to
ensure safety.
Surge absorber Absorbing electromagnetic and control surge current of
relays
Isolation transformer Decrease interference
AC Reactor Protect servo drive, prevent the high harmonics and
surge voltage.
Absorb regenerated energy. Absorb regenerated energy.
Decrease of electromagnetic
interference which is caused by
servo drive.
Decrease of electromagnetic interference which is
caused by servo drive.
Ferrite ring Decrease of electromagnetic interference which is
caused by servo drive.
Voltage Level Motor Output
(kW)
Parameters of AC Input Reactor
Remark
Rated Currency (A) Inductance Value (mH)
220Vac
7.5 40 0.3
Option
11 60 0.2
15 80 0.14
18.5 90 0.12
22 120 0.1
30 150 0.07
37 200 0.06
45 250 0.05
55 250 0.04
75 330 0.03
90 400 0.025
Selection of Peripheral Electrical Devices AC input reactor
Voltage level Motor Output
(kW)
Parameters of AC Input Reactor
Remark
Rated Currency (A) Inductance Value (mH)
380Vac
7.5 20 0.75
Option
11 30 0.6
15 40 0.42
18.5 50 0.35
22 60 0.28
30 80 0.19
37 90 0.16
45 120 0.13
55 150 0.1
75 200 0.12
90 250 0.06
110 250 0.06
132 290 0.04
160 330 0.04
185 400 0.04
200 490 0.03
220 490 0.03
250 530 0.03
280 600 0.02
315 660 0.02
350 800 0.0175
400 800 0.0175
450 1000 0.014
70 AC input reactor Selection of Peripheral Electrical Devices
71
7.2 AC Output Reactor
Voltage level Motor Output
(kW)
Parameters of AC Output Reactor
Remark
Rated Currency (A) Inductance Value (mH)
220Vac
7.5 40 0.15
Option
11 60 0.1
15 80 0.07
18.5 90 0.06
22 120 0.05
30 150 0.035
37 200 0.03
45 250 0.025
55 250 0.02
75 330 0.015
90 400 0.013
380Vac
7.5 20 0.13
11 30 0.087
15 40 0.066
18.5 50 0.052
22 60 0.045
30 80 0.032
37 90 0.03
45 120 0.023
55 150 0.019
75 200 0.014
90 250 0.011
110 250 0.011
132 290 0.008
Selection of Peripheral Electrical Devices AC output reactor
Voltage level Motor Output
(kW)
Parameters of AC Output Reactor
Remark
Rated Currency (A) Inductance Value (mH)
380Vac
160 330 0.008
Option
185 400 0.005
200 490 0.004
220 490 0.004
250 530 0.003
280 600 0.003
315 660 0.002
350 800 0.002
400 800 0.002
450 1000 0.0012
7.3 Applied Braking Resistor Specification
Voltage
Level
Motor
Output
(kW)
Brake Resistor Brake
Unit
CDBR
Braking
Torque
(10%ED)
Motor
Output
Power (W) Resistance Value(Ω) (kW)
220Vac
7.5 1000W 16
Built-in 125
7.5
11 1500W 11 11
15 2500W 8 15
18.5 3.7KW 6.7 18.5
22 4.5KW 6.7 22
30 5.5KW 5 30
37 7.5KW 3.3 37
45 4.5KW*2 5*2 45
55 5.5KW*2 5*2 55
72 Applied Braking resistor Specification Selection of Peripheral Electrical Devices
73
Voltage
Level
Motor
Output
(kW)
Brake Resistor Brake
Unit
CDBR
Braking
Torque
(10%ED)
Motor
Output
Power (W) Resistance Value(Ω) (kW)
220Vac
75 16KW 3.3 Built-in
125
75
90 6.5KW*3 6.3*3 External 90
380Vac
7.5 1000W 65
Built-in
7.5
11 1500W 43 11
15 2000W 32 15
18.5 4KW 24 18.5
22 4.5KW 24 22
30 6KW 19.2 30
37 7KW 14.8 37
45 9KW 12.8 45
55 11KW 9.6 55
75 15KW 6.8 75
90 9KW*2 9.3*2 90
110 11KW*2 9.3*2 110
132 13KW*2 6.2*2 132
160 16KW*2 6.2*2 160
185 19KW*2 2.5*2
External
185
200 19KW*2 2.5*2 200
220 21KW*2 2.5*2 220
250 24KW*2 2.5*2 250
280 27KW*2 2.5*2 280
315 20KW*3 2.5*3 315
350 23KW*3 2.5*3 350
400 26KW*3 2.5*3 400
450 29KW*3 2.5*3 450
Note:The braking resistor value is related to the DC voltage when the servo drive is braking.
For 380V power supply, DC voltage is 800V-820V and for 220V system, the DC voltage is 400V.
Selection of Peripheral Electrical Devices Applied Braking resistor Specification
Calculate of Braking resistor value:
The braking resistor value is related to braking torque Mbr% , and for the different braking
torque, the braking resistor values are different.
The calculation formula is as follows:
Udc——DC voltage of brake ;PMotor ——Motor power ;Mbr——Braking torque ;
ηMotor ——Motor efficiency ;η Driver ——Drive efficiency 。
The braking power is related to braking torque and braking frequency, as the calculation
formula above indicates the braking torque is 125% , the frequency is 10%. However, according
to the different load, the values in the calculation formula are just for reference only.
74 Motor Driver Motor
Applied Braking resistor Specification Selection of Peripheral Electrical Devices
75
Note: You can ensure the same motor speed through the communication.
Chapter 8
Multi-pump Control of IMM
Due to the limit of motor power and pump displacement, single pump can’t meet the
requirements of displacement, large tonnage injection molding machine needs multi-pump in
parallel to converge maximum flow.
The parallel pump control is classified into multi-pump convergent flow and multi pump
distributed flow.
Multi-pump convergent flow:A servo motor is used as the master drive, and the other
drives are used as slave drives connected in parallel. The host computer outputs a set of flow
and pressure analog signals.
Multi pump distributed flow:Multiple servo drives may work in multi-pump convergent flow
mode or multi pump distributed flow mode (distributed PID control based on the oil pressure).
The host computer outputs multiple sets of flow and pressure analog signals.
8.1 Parallel Pump Control
◆ Structure diagram of multi pump combined flow
The following figure shows the multi-pump convergent flow structure chart.
Master drive Slave drive Slave drive
CAN bus
Pressure
reference 1
Flow reference 1
Pressure
feedback 1
Oil inlet
Pump
#1
Pump
#2
Pump
#3
Oil outlet
Pressure sensor 1
Selection of Peripheral Electrical Devices Parallel Pump Control
Note: You can ensure the same motor speed through the communication.
The convergent flow and distributed flow of pump 3 can be controlled by energizing
solenoid valves ○1○2○3○4.
In the convergent flow control, the pressure reference, flow reference and pressure
feedback signal received by the drive are invalid.
In the distributed flow, the CAN communication command received by the drive are
invalid.
◆ Multi pump shunt structure
The following figure shows the multi pump distributed flow structure chart.
76 Pressure
reference 1
Flow reference 1
Pressure
feedback 1
Pressure
reference 2
Flow
reference 2
Pressure
feedback 2
Pressure
reference 3
Flow
reference 3
Pressure
feedback 3
CAN bus
Oil inlet
Pressure sensor 1 Pressure sensor 2 Pressure sensor 3
Master drive Slave drive Slave drive
Oil outlet 1 Oil outlet 2 Oil outlet 3
Parallel Pump Control Selection of Peripheral Electrical Devices
77
8.2 Multi–pump Control Mode
PD.09 CAN multi-pump
mode
0 Multi-pump 1 (broadcast mode)
1 Multi-pump 2 (multi-master mode)
Multi-pump 1:
● This mode is broadcast mode and is applicable to simple multi-pump control.
● When the slave pump is switched over to the master pump, the slave pump can’t be
controlled.
● To enable the multi-pump mode, set the DI terminal for 50# function.
● After disconnecting the DI terminal set for 50# function of the slave pump, the slave pump is
switched over to the master pump.
Multi-pump 2 :
◆ Wiring(Multi-pump convergent flow)
This mode is the multi-master mode and can satisfy more complicated multipump convergent and distributed flow control. It supports a maximum of 4 multi-pump
distributed flow control combinations.
Multi-pump distributed flow:
Set the corresponding parameter in group P6.02=25 (slave alarm output) and connect this
signal to the system computer for alarm display.
Set the corresponding parameter in group P6.02=25 (slave alarm output) and connect this
signal to the system computer for alarm display.
Note: High-pressure without cause occurs on the oil channel of the slave pump in the
pressure control when leakage of the check valve is large while the inner discharge of the
slave pump is small. To relieve the high-pressure state of the oil channel, do as follows:
Reduce the discharge of the slave pump to reasonable range.
Decrease the torque upper limit of the slave drive to reasonable range.
Set the speed response curve according to the max. discharge speed of the master
pump, ensuring that the slave drive implements automatic pressure relief t low-speed
holding pressure. For detailed parameter setting, refer to the following “ Parameter Setting
for Slave Pump Response to Master Pump Reference” part.
●
●
●
Selection of Peripheral Electrical Devices Multi–pump Control Mode
◆ CAN Communication Wiring
The CAN bus connection of all pumps is shown in the following figure.
Note:
● Connect the CANH and CANL terminals on the boards of all drives together
● Connect the GND terminal together through the shield.
● The first drive and the end drive at the CAN bus must connect the CAN communication
terminal resistor.
◆ Parameter Setting for Slave Pump Response to Master Pump Reference
Function Code Parameter Name Default Description
PC.10 Slave min. input 0.0%
The slave
pump drive
setting
PC.11 Corresponding setting of slave min. input 0.0%
PC.12 Slave medium input 0.0%
PC.13 Corresponding setting of slave medium input 0.0%
PC.14 Slave max. input 100.0%
PC.15 Corresponding setting of slave max. input 100.0%
The setting of PC.10 to PC.15 can implement automatic pressure relief of the slave pump
when the master pump is in the low-speed pressure holding state, avoid occurrence of holding
high pressure on the slave pump and ensure the system flow linearity.
78 Master drive Slave drive 1 Slave drive 2
Multi–pump Control Mode Selection of Peripheral Electrical Devices
79
Note : The two multi-pump modes have the same parameter setting for the slave pump response to the
master pump speed reference.
For example:
Condition 1 : Suppose the max. pressure holding speed of the master is 50 rpm/min, the max.
speed of the master is 2000 rpm/min.
Condition 2: At pressure holding, the master works and the slave stops.
Condition 3: To ensure flow linearity, the master is over 100 rpm/min., and the slave keeps the
same speed.
When the mater group is below 50 rpm/min., the slave pump stops running. When the master
pump is above 100 rpm/min, the master pump and the slave pump keep the same speed.
The speed reference of the master pump is 0% to 100%. You can set PC.10 to PC.15 to get the
three-point curve to make the slave pump respond to the speed reference as follows:
( PC.10, PC11 ) = Slave pump input reference: 50 rpm/min., slave response reference: 0 rpm/
min. = 2.5%, 0.0%
( PC.12, PC13 ) = Slave pump input reference: 100 rpm/min., slave response reference: 100
rpm/min. = 5.0%, 5.0%
( PC.14, PC15 ) = Slave pump input reference: 2000 rpm/min., slave response reference: 2000
rpm/min. = 100%, 100%
100%)
Slave pump receiving
t h e m a s t e r p u m p
speed
100.0%
2.5%5.0% 100.0%
5.0%
0.0%
Slave pump
responding the
master pump
speed
Selection of Peripheral Electrical Devices Multi–pump Control Mode
Function Code Parameter Name Setting Description
Pd.07 CAN communication address 1
Pd.09 Multi-pump mode 1 0
P5.00~P5.04 Multi-pump control enabled 50
P6.02 Relay on the control board
output selection 25 Slave alarm output
(normally – open)
Function Code Parameter Name Setting Description
P5.00~P5.04 Slave pump address
selection terminal 1 53 In multi-pump distributed flow
control, these parameters are
used to set which slave pumps
the master pump selects for
convergent flow.
P5.00~P5.04 Slave pump address
selection terminal 2 54
P6.02 Slave pump address
selection terminal 2 25 Slave alarm output (normallyopen)
Pd.07 CAN communication
address 1
Pd.09 Multi-pump mode 2 1
Pd.10 CAN slave address 1 0 Together with the two X
terminals set for the 53#
and 54# functions, the four
combined distributed flow
control can be implemented.
Pd.11 CAN slave address 2 0
Pd.12 CAN slave address 3 0
Pd.13 CAN slave address 4 0
◆ Multi-pump mode 2 (Pd.09=1)
80 8.3 Parameter Setting on Master Drive
◆ Multi-pump mode1 (Pd.09=0)
The parameter setting is simple. For all servo drives, allocate a X terminal and set the
parameter to 50.
The servo drive with address 1 must be the master pump. A maximum of four combined
distributed flow control can be implemented. The related parameter settings are as follows:
Parameter Setting on Master Drive Selection of Peripheral Electrical Devices
◆ Slave pump address X terminal input selection
Setting of X Terminal for
54# Function
Setting of X Terminal for
54# Function CAN Slave Address Selection
0 0 Pd.10 : CAN slave address 1
0 1 Pd.11 : CAN slave address 2
1 0 Pd.12 : CAN slave address 3
1 1 Pd.13 : CAN slave address 4
81
◆ Description of slave pump address setting
Pd.10~Pd.13 Bit0 Bit1 Bit2 Bit3 Bit4 Bit5
Station No 1 2 3 4 5 6
Value Setting 20
=1 21
=2 22
=4 23
=8 24
=16 25
=32
Pd.10~Pd.13 Bit6 Bit7 Bit8 Bit9 Bit10 Bit11
Station No 7 8 9 10 11 12
Station No. 26
=64 27
=128 28
=256 29
=512 210=1024 211=2048
Pd.10~Pd.13 Bit12 Bit13 Bit14
Station No 13 14 15
Station No. 212=4096 213=8192 214=16384
● Bit0 corresponds to the slave pump station No.1, Bit1 corresponds to station No.2, by
that analogy, Bit14 corresponds to station No.15.
● When address station number is 1, it indicates that the slave pump of the address
station No.
● The PH300 series servo drives support the setting of a total 15 slave pump addresses.
For example, 1# is the master pump, Pd.10=1x2¹+1x2²+1x2³=14, indicating that 1# is the
master pump, and works with slave pumps 2#, 3# and 4#.
Selection of Peripheral Electrical Devices Parameter Setting on Master Drive
◆ Multi – pump mode 1 (Pd.09 = 0)
Function Code Parameter Name Setting Description
PD.07 CAN communication
address >1 Slave drive
P5.00~P5.04 Multi – pump control
enabled 50 Slave pump may switch over to
master pump control.
If the slave pump switches over to master pump, disconnect the X terminal set for the 50# function of
slave pump.
8.4 Parameter Setting on Slave Drive
The following table lists the parameter setting of the slave drive. Perform the same parameter
setting as you do in the common servo pump mode.
◆ Multi – pump mode 2 (Pd.09 = 1)
The following table lists the parameter setting of the slave drive. Perform the same parameter
setting as you do in common servo pump mode.
Function Code Parameter Name Setting Description
Pd.07 CAN communication
address >1 Slave drive
P5.00~P5.04 Slave pump address
selection terminal 1 53
When the slave pump is used
as the master pump, it need to
be triggered by the terminal.
For the slave pump address
setting, refer to section 8.3
“Parameter Setting on Master
Drive”
P5.00~P5.04 Slave pump address
selection terminal 2 54
82 Parameter Setting on Slave Drive Selection of Peripheral Electrical Devices
8.5 Applications of Multi-pump Convergent and Distributed
Flow Control
◆ Multi-pump Mode 1 (Pd.09 = 0)
For example, the IMM servo pump system consists of the three pumps with the address set
as 1#, 2# and 3#. In the multi-pump mode 1, when a slave pump is used as the master pump,
the slave pump doesn’t follow its speed.
And there are the following 2 combinations:
● Combination 1: 3-pump convergent flow
● Combination 2: 2+1 combination for distributed flow control
The following describes the wiring and setting of the above two combinations:
83
■ Combination 1: 3-pump convergent flow
COM
RUN enabled DO
Distributed flow signal DO1
Host
computer
COM
RUN enabled X
50# X
Master
drive 1#
Slave
drive 2#
Slave
drive 3#
COM
RUN enabled X
50# X
COM
RUN enabled X
50# X
Selection of Peripheral Electrical Devices Applications of multi-pump Convergent and Distributed Flow Control
Note:
The 1# master pump is followed by the 2# slave pump, and you can switch over the 3#
pump to the master pump by disconnect the X terminal set for the 50# function of the slave
pump.
Note:
Because the 1# pump is always the master pump and the 2# pump always the slave pump,
directly short the X terminal set for 50# function.
The 3# pump switches over to the master pump in the following combination 2, which
requires an external switches signal. When the host computer sends the closing signal, the X
terminal set for the 50# function of the slave pump closes to process the multi-pump convergent
flow.
■ Combination 2: 2+1 combination for distributed flow control
84 The 1# master pump is followed by the 2# slave pump, and the 3# pump switches over to the master
pump.
COM
RUN enabled DO
Distributed flow signal DO1
Host
computer
COM
RUN enabled X
50# X
Master
drive 1#
Slave
drive 2#
Slave
drive 3#
COM
RUN enabled X
50# X
COM
RUN enabled X
50# X
Applications of multi-pump Convergent and Distributed Flow Control Selection of Peripheral Electrical Devices
85
◆ Multi-pump Mode 2 (Pd.09 = 1)
For example, the IMM servo pump system consists of four pumps with the address set as
1#, 2#, 3# and 4#.
● Combination 1: 4-pump convergent flow
● Combination 2: 2+2 combination for distributed flow control
● Combination 3: 3+1 combination for distributed flow control
■ Combination 1: 4-pump convergent flow
COM
RUN enabled DO
Distributed flow signal DO1
Host
computer
Distributed flow signal DO1
COM
RUN enabled X
53# X
Master
drive 1#
54# X
COM
RUN enabled X
53# X
Slave
drive 2#
54# X
COM
RUN enabled X
53# X
Slave
drive 3#
54# X
COM
RUN enabled X
53# X
Slave
drive 4#
54# X
Note:
The convergent flow control requires very simple wiring including CAN bus and X terminal
wiring.
The 1# pump is the master pump, and the 2#, 3# and 4# pumps are slave pumps. The
setting of address of corresponding slave pumps is Pd.10=1x2¹+1x2²+1x2³=14.
Selection of Peripheral Electrical Devices Applications of multi-pump Convergent and Distributed Flow Control
■ Combination 2: 2+2 combination for distributed flow control
86 Note:
The host computer provides the distributed flow signal. Connect the distributed flow signal
to the X terminal set for the 53# function of the master drive. The master pump identifies the
salve pump address through the 53# X signal. The slave pump switches over to the master
pump and identifies the slave pump address by using the 53# X signal.
In this combination, the 1# pump and 3# pump are the master pump. The slave pump
changes and the address of the salve pump needs to be set. The slave pump of the 1# master
pump is 2# pump, the setting of address of 1# master pump is Pd.11=1x21=2. The slave pump
of the 3# master pump is 4# pump, the setting of address of 3# master pump is Pd.11=1x23=8.
The 1# master pump is followed by the 2# slave pump, and the 3# pump works as the
master pump which is followed by the 4# slave pump.
COM
Distributed flow signal DO1
Host
computer
Distributed flow signal DO1
COM
RUN enabled X
53# X
Master
drive 1#
54# X
COM
RUN enabled X
53# X
Slave
drive 2#
54# X
COM
RUN enabled X
53# X
Slave
drive 3#
54# X
COM
RUN enabled X
53# X
Slave
drive 4#
54# X
Applications of multi-pump Convergent and Distributed Flow Control Selection of Peripheral Electrical Devices
87
Note:
The host computer provides the distributed flow signal. Connect the distributed flow signal
to the X terminal set for the 54# function of the master drive. The master pump identifies the
salve pump address through the 54# X signal. The slave pump switches over to the master
pump and identifies the slave pump address by using the 54# X signal.
Disconnect the X terminal set for the 53# function in the second combination.
In this combination, the 1# pump and 4# pump are the master pump. The slave pump
changes and the address of the salve pump needs to be set. The slave pump of the 1# master
pump are 2# pump and 3# pump, the setting of address of 1# master pump is Pd.12=1x21
+1x22=6. After the 4# slave pump switches over to the master pump, no slave pump follows it,
therefore, Pd.11 doesn’t need to be set, that is Pd.11=0.
■ Combination 3: 3+1 combination for distributed flow control
The 1# master pump is followed by the 3# and 4# slave pumps, and the 2# slave pump
switches over to the master pump.
COM
Distributed flow signal DO1
Host
computer
Distributed flow signal DO1
COM
RUN enabled X
53# X
Master
drive 1#
54# X
COM
RUN enabled X
53# X
Slave
drive 2#
54# X
COM
RUN enabled X
53# X
Slave
drive 3#
54# X
COM
RUN enabled X
53# X
Slave
drive 4#
54# X
RUN enabled DO
Selection of Peripheral Electrical Devices Applications of multi-pump Convergent and Distributed Flow Control
Appendix
Company & Sales Area Information
PHYSIS HEADQUARTER
Ningbo Physis Technology Co., Ltd.
No.308, Xiaogang Anju Road, Beilun District, Ningbo, China
Tel:+0086-(0)574-26922600
Domestic Sales
Tel:+0086-(0)574-26922572
E-mail:lois @physis.com.cn
MANUFACTURING BASE
Physis Motion Control Ningbo Co., Ltd.
No.248, 2nd Binhai Road, Hangzhou Bay New Zone, Ningbo China
Tel:+0086-(0)574-23459000
Overseas Sales
Tel:+0086-(0)574-23459168
E-mail:andy@physis.com.cn
After Sales
Tel:+0086-(0)574-23459183
E-mail:hjs@physis.com.cn
Version Change Record
Date Version Update Content
2019-09 PHSDOM1909-V01 ● First edition release
2020-04 PHSDOM2004-V02 ● Content update
● Layout rearrangement
2020-07 PHSDOM2007-V03 ● Logo update
● Content update
Version:PHSDOM2506-V05
PERPETUAL MOTION




