苏州追途电气设备有限公司
用
户
操
作
使
用
说
明
书
ZLJBD-35T-380V50Hz 工业机柜空调说明书
目 录
1. 安全注意事项·······················································································1
2. 安装要求 ·····························································································1
2-1 安装位置·························································································2
2-2 安装方法·························································································3
2-3 电器配线························································································6
2-4 机器排水·························································································6
3. 启动与运转···························································································6
3-1 运行前后注意事项···········································································6
3-2 机器操作说明··················································································7
4. 维护与保养·························································································7
4-1 定期清洁·······················································································7
4-2 长时间停用时注意··········································································7
5. 故障排除·····························································································8
附录
一······································································································9
附录
二······································································································9
1
1. 安 全 注 意 事 项
⑴ 当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册
中所提到的注意事项,以避免出现意外情况;
⑵ 请勿用湿手操作,以免引起触电;
⑶ 当需要保养或维护时,请先切断所有电源以免引起触电事故;
⑷ 空调器上不易放置任何物品,以免滑落造成人员伤害;
⑸ 当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受
伤或机器损坏;
⑹ 本机器不宜露天放置以免雨水进入机体内,并且也不适宜于安装在振动较
大或者移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司
咨询;
⑺ 本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请
致电本公司咨询;
⑻ 禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员
咨询,以防意外发生。
2. 安装要求
本空调器为顶置式系列(图一),为使机组能在理想的状况下工作,在安装
上请注意以下要求:
图一 顶置式
电控箱
冷气机
2
2-1 安装位置
⑴ 空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、
可燃性气体、粉尘类气体、油污类气体等品质较差的空气中;
⑵ 空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会
排出热量,如果空调器周围排气不畅很容易导致其周围的温度升高,这将影
响空调器的制冷效果。见图二,空调器进、排风口离墙面的间距应大于
500mm;
⑶ 空调器周围请勿放置杂物,以保持空气畅通流通;
⑷ 本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影
响冷却效果。
⑸ 请安装本空调器于周围温度在 45℃以下的范围之内高温系列 55℃以下;
⑹ 本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必
须保持垂直,其倾斜角不大于 5°如图三所示;
⑺ 控制箱内正对出风口的电器元件与出风口的最小距离应大于 200mm,因
距离太近电器元件表面易产生水膜现象,从而导致电器故障的发生。若无法
避免,请在电器元件前增加一块隔热材料;并且箱内出风口四周的电器元件
与出风口应保持一定的距离,以便减小箱内空气的流通阻力。
⑻ 当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便
箱体内空气的温、湿度能控制在较为理想的状态下。
图二
3
图 三
错 误 正 确 错 误 正 确
2-2 安装方法
⑴ 当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设
备长期放在露天场所;
⑵ 为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上或顶
上(根据用户所选机型来决定),请勿采用风管的形式进行送风,如若确实
需要采用风管送风,请先咨询本公司技术工程师;
⑶ 空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免
4
造成人员受伤及设备损坏,当安装在电气柜门上时,最好该扇箱门能固定不
动,当需要打开时请先确认好加在门上的重量不会使整个电气柜倾倒;
⑷ 电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参
见图五;
⑸ 箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划
伤机组;
⑹ 当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有
可能导致机器掉落而损坏;
⑺ 具体的安装方式如下:
-5-
安装方式一:
起吊环
电控箱
XPE 保温棉
开口
a. 准备好该类安装方式的空
调器
b. 按照开口尺寸在电控箱顶部开好
口,并粘贴好 XPE 保温绵(若机器
底部自带,则不需),然后拧下机组
底部四角上的螺帽,并确定好螺栓的
伸出长度(约 15mm)。
电控箱
排水口
C 通过起吊环用起吊机吊起机组(若
无起吊环则需人工搬装),把电源线从
电线孔伸入电控箱内,然后对好螺栓孔
轻轻放下机器,随后在电控箱内的螺栓
上垫上垫圈并拧紧螺帽。
电控箱内侧
d 在机组侧面排水口处连接好排水
管,用抱箍固定好,另一端请引入排水
沟或蓄水桶内,检测电源是否与机组匹
配,然后接上电源即可开机使用。
排水管
-6-
2-3 电器配线:
⑴ 机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或
过低,若所提供的电压在额定值±10%以内,本机组可正常使用;
⑵ 空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一
根电源线,当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;
⑶ 在机组的电器回路上请自行安装断路器或保护装置;
⑷ 请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电
源超出负载,引发事故。
2-4 机器排水:
本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这
部分水气就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请
注意以下几点:
⑴ 请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连
接处;
⑵ 根据实际情况排水软管长度适当即可,过长部分请切除;
⑶ 排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内
产生淤水严重时产生外溢,引起空调器或者电气柜故障。
3. 启动与运行
3-1 运行前后注意事项
⑴ 启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插
上电源开始工作;
⑵ 当在运转中需重新启动空调器时,请间隔 3 分钟以上,倘若频繁启动且间隔时间过
短会引起机器损伤;
⑶ 当空调器倾斜时请勿开启,避免漏水、触电等情况发生;
⑷ 空调器在出厂时温度点已经设定好为 30℃,若需重新设定时请控制在允许范围之内
设定,以免引起机器运行不正常;
⑸ 当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人
员进行检查维修
-7-
使用说明 V1.0.0
简介:
BTW-289+系列温控器采用小型化、IP65 等级面板防护设计,体积小重量轻,操作简捷安装方便。适用于小型机柜空
调系统的温度控制。
主要功能
1. 制冷,风机自动控制
2. 压缩机智能保护
3. 多种故障告警,超高温,低温告警,系统高压报警,缺氟报警
4. 外部开关量输入检测,继电器输出告警,常开,常闭点自由配置
5. 标准 RS485 通讯接口,Modbus RTU 通讯协议
规格尺寸
1.前面板尺寸: 长 78 x 宽 34.5(毫米) 2.安装开孔尺寸:长 71 x 宽 29(毫米)
3.整机尺寸: 长 78 x 宽 34.5 x 深 71(毫米) 4.传感器线长:1 米(含探头长度)
主要技术指标
感温元件:NTC 3435/10K 电源电压:交流型:AC220V±20% 50HZ
设定范围:0 ~50℃ 接线端子:连接 2*1.5mm 2显示范围:-40~99℃ 或 1*2.5mm 2
的导线
工作环境:-10~45℃ 负载电流:压缩机 16A,风机 10A,告警 5A
存储温度:-30~70℃ 外 壳:PC + ABS 阻燃
湿 度:5~85%RH (不结露) 防护等级:IP65(前面板)
操作指南
显示说明
显示屏信号说明
图标 功能 亮 灭 闪烁
压缩机 启动 停止 准备制冷,压缩机正在延时保护
电加热 运行 ---- 加热延时开启
风机 运行 停止 风机延时开启
set 设置 参数设置状态 测控状态 ----
+ 强启动 强制启动压缩机 退出强启动 ----面板数码管说明
3 位彩色数码管显示测量温度值和告警代码;
告警代码
序 号 显示代码 说 明
1 “E01” 温控传感器故障(短路或断路)
3 “E02” 蒸发器传感器故障(短路或断路)
3 “E03” 系统缺氟保护
4 “Hi” 高温告警
5 “Lo” 低温告警
8 “LA” 外部无源数字量输入告警(系统高压告警)
10 “FrE 蒸发器冻结保护
-8-
按键操作
系统参数设置
·系统参数设置界面进入:
设置温度:
测控状态下,长按[set]3s,出现[St],再按[set],出现制冷温度,按〖▲〗或〖▼〗键可对参数进行设置,设置
完成后再按[RST]键,或者 30s 无按键操作,自动保存并回到正常测控状态。
设置内部参数:
测控状态下,长按[set]3s,出现[St], 按〖▲〗出现 Po,再按[set],显示 0,按〖▲〗或〖▼〗键将 Po 设置
到 55,再按[set],返回 Po,此时按上下键,即可选择其他参数进行配置。
工作参数代码及设置说明如下表所示:
参数代码 设置功能 设定范围 说明 出厂设定值
St 制冷温度设定 15~50℃ 30
Po 密码 0~99 55 固定不可调 0
管理员参数(需要正确的密码,Po=55)
F00 温差 1~ 20℃ 5
F01 高温报警温度-5~60℃
高温/低温
设定间隔 1℃
50
F02 低温报警温度 5
F03 蒸发风机温度设定 0~40℃ 26
F04 蒸发风机温差 1~ 9℃ 2
F05 温控探头校正 -9~9℃ 0
F06 蒸发器探头校正 -9~9℃ 0
F07 高温报警失效 0~1 0:禁用;1:启用 1
F08 低温报警失效 0~1 0:禁用;1:启用 1
F09 系统缺氟失效 0~1 0:禁用;1:启用 1
F10 蒸发器探头使能设定 0~1 0:禁用;1:启用 0
F11 压缩机工作模式 0~1
0:自动模式(启用压缩机)
1:禁用模式
0
F12 风机工作模式 0~1
0:温控模式
1:常开模式
1
F13 外部输入告警模式 0~1
0:常闭;
1:常开
0
F14 蜂鸣器报警 0~1 0:禁用;1:启用 1
F15 压缩机开机延时时间 1~5 分钟 3
F16 压缩机最短持续运行时间 1~5 分钟 3
F17 系统开关机 0:通电关机,1:通电开机 1
F18 RS485 波特率设定 0~3
0:4800bps
1:9600bps
2:19200bps
3:115200bps
3
F19 设备地址 1~64 1
查看蒸发器温度
在显示当前温度时按一下〖▲〗键, 数码管显示制冷设置温度值,1S 后恢复显示当前温度值。
在显示当前温度时按一下〖▼〗键, 数码管显示蒸发器探头温度值,1S 后恢复显示当前温度值。
控制功能说明:
压缩机控制
◇当测量温度 ≥【制冷设定温度】 + 【温差】,且压缩机停机时间大于【压缩机开机延时时间】,压缩机开启;
◇当测量温度 ≤【设定温度】,且压缩机开机时间大于【压缩机最短持续运行时间】,压缩机关闭;
例如:【制冷设定温度】为 25 度, 【温差】为 2 度,则当温控传感器检测温度高于 27 度时启动压缩机,温度
低于 25 度时关闭压缩机,将温度控制在 25~27 度之间;
◇压缩机强制启动:
1.在压缩机关闭情况下,按住〖RST〗键 5 秒不放,可以强制启动压缩机。在压缩机强制启动状态下,按住〖RST〗
键 5
秒不放,可以取消强制启动压缩机,压缩机恢复正常运行。
-9-
2.压缩机在强制启动状态下持续运行 30min 后,压缩机恢复正常运行。
压缩机延时保护
◇运行过程中压缩机停机,必须经过【压缩机开机延时时间】才能再次启动;
◇运行过程中压缩机开启,必须经过【压缩机最短持续运行时间】才能以实际情况停机;
风机控制:
控制器在运行过程中,风机按照如下规则运行:
如果风机设定为常开,则送风机始终开启;
如果风机设定为温控则风机根据温控传感器温度进行控制。控制条件如下:
◇当测量温度 ≥【蒸发风机设定温度】 + 【蒸发风机温差】,且风机已经停机时间大于 1 分钟,风机开启;
◇当测量温度 ≤【蒸发风机设定温度】,且风机开机时间大于 1 分钟,风机关闭;
例如:【蒸发风机设定温度】为 23 度, 【蒸发风机温差】为 2 度,则当温控传感器检测温度高于 25 度时启动风机,
温度低于 23 度时关闭风机,将温度控制在 23~25 度之间;
蜂鸣器功能
每按键一次蜂鸣器鸣叫一声,在参数设置确认时长鸣一次,在进行无效操作时蜂鸣器鸣叫三声;当系统出现故
障
或有外部报警输入时,如果参数 F13=0,关闭蜂鸣器报警功能,蜂鸣器不鸣叫报警;如果参数 F13=1,则蜂鸣器
连续鸣叫报警; 系统恢复正常后,自动消除蜂鸣器报警状态.高温、低温超温告警
1.当测量温度 ≥ 【高温报警温度】,将产生高温报警, 当测量温度 ≤ 【高温报警温度】,控制
器取消高温告警;
2.当测量温度 ≤ 【低温报警温度】,将产生低温报警, 当测量温度 ≥ 【低温报警温度】+ 2 度,控制
器取消低温告警;
外部输入告警 (系统高压告警)
外部数字量有以下几种输入方式:;
常开:表示在正常情况下外部告警输入信号为开路状态,闭合则产生告警。
常闭:表示在正常情况下外部告警输入信号为闭合状态,开路则产生告警。
系统高压告警: 如果 1 小时内连续出现 3 次压力告警,将一直关闭压缩机。手动重新上电可以解除告警。
温度值校正功能
当测量温度值与传感器安装位置实际温度有误差,可通过【温度修正参数】进行校正,校正范围±9.9℃;按一
次〖▲〗
或〖▼〗键调整温度校正值增或减 0.1℃,按住不放则快速调整;
系统缺氟(漏氟)保护:
当压缩机启动 5 分钟后,检测温控传感器、蒸发器传感器温度,,如果温控传感器温度高于蒸发器传感器温度 5
度以
上温差,判定系统正常,否则认定为缺氟保护(漏氟),并显示报警代码“E03”。强制关闭压缩机。
如果 1 小时内连续出现 3 次缺氟保护,将一直关闭压缩机。手动重新上电可以解除告警。
蒸发器冻结保护:
当压缩机启动 1 分钟后,检测蒸发器传感器温度,如果蒸发器传感器温度小于等于-1 度并保持 5 秒,判定蒸发器
冻结保护,并显示报警代码“FrE”。控制器强制关闭压缩机并开启送风机。当蒸发器的温度上升 8 度以上,退出冻
结保护,控制器恢复正常工作。
告警输出
告警列表说明
故 障
检测
条件
推迟
持续
时间
复位
操作
动作
温控传感器故障 随时 0s 2s 自动
开压缩机、停电加热,温控模式下开蒸发风机;
取消缺氟保护告警
-10-
蒸发温度传感器故障 随时 0s 2s 自动 取消缺氟保护告警
压力保护 随时 0s 5s 手动 停压缩机
缺氟保护 压缩机启动 5min 5s 手动 停压缩机
高温告警 随时 0s 5s 自动 只告警
低温告警 随时 0s 5s 自动 只告警
蒸发冻结保护 压缩机启动 1min 5s 自动 停压缩机,开始送风机
告警接口说明
信号名称 说明
NO 故障输出(故障时断开,正常时闭合)
NC 故障输出(故障时闭合,正常时断开)
C 公共端
控制器接线示意图
安 装步骤
第1步: 将控制器嵌入孔中;
第2步: 通过在设备的导轨方向
滑动支架来固定控制器,直到将控制器压实在面板上;
电气连接
敬告:
◆电气接线操作必须由有资质的技术人员来完成。
◆使用规定电源类型以外的电源可能会给系统带来严重损害;
◆尽可能将传感器、开关量输入信号线与感性负载线、电源线分开排线,以避免电磁干扰。绝不能将电源线(包括电力线)
和
485 通讯协议
本产品支持标准 Modbus RTU 协议,支持标准 RS485 接口,可与所有支持标准 RS485 接口的设备通讯。
1. 通讯参数:默认9600,N,8,1,波特率可选;
2. 支持保持寄存器读写,支持03,06,16功能码;
3. 建议应答超时时间设置大于1000ms;
4 建议轮询时间间隔设置大于100ms;
5. R:只读,W:只写,R/W:可读可写。
6. 下表格是具体寄存器参数及说明:
地址 功能说明 預設 範圍 单位 读写
0 柜温探头温度(实际温度×10) - -400~990 ℃ R
1 蒸发器探头温度(实际温度×10) - -400~990 ℃ R
2 制冷继电器状态 - 0:断开 1:闭合 - R
3 风机继电器状态 0:断开 1:闭合 R
-11-
4 报警继电器状态 - 0:断开 1:闭合 - R/W
5 制冷温度设定值 30 15~50 ℃ R/W
6 控制回差设定值 5 1~20 ℃ R/W
7 高温报警温度 50 1~60 ℃ R/W
8 低温报警温度 5 1~60 ℃ R/W
9 蒸发风机温度设定 26 0~40 ℃ R/W
10 蒸发风机温差 2 1~5 ℃ R/W
11 蒸发器探头使能设定 0 0:禁用 1:启用 - R/W
12 压缩机工作模式 0 0:自动 1:禁用 - R/W
13 风机工作模式 1 0:受控 1:常开 - R/W
14 外部输入告警模式 0 0:常闭 1:常开 - R/W
15 蜂鸣器报警 1 0:禁用 1:启用 - R/W
16 压缩机开机延时时间 3 1~5 Min R/W
17 压缩机最短持续运行时间 3 1~5 Min R/W
18 系统上电开关机 1
0:通电关机
1:通电开机
- R/W
19 RS485 波特率设定 1
0:4800
1:9600
2:19200
3:115200
- R/W
20 从机地址(注意:更改之后,上位机读取
软件要相应的更改从机地址)
1 1~64 - R/W
21 远程开关机(注意:远程关机状态下,长
按[SET]键开机)
1
0:关机
1:开机
- R/W
4.维护与保养
请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空
气过滤网和冷凝器。对于机器上安装的是尼龙滤网的可直接从侧面拔出
4-1 定期清洁
⑴ 本公司滤网有两种样式,一种为尼龙滤网,可直接从侧面拆下,用洗涤水清洗干净,
并晾干后按原样装回,一般每周需清洗一次;另一种为滤芯式滤网(见图九),当环境
油污或粉尘大滤芯清洗不干净时,需要更换新的滤芯,一般半月需要更换一次,;
⑵ 请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,
以防发生触电事故;
4-2 长时间停用时注意
⑴ 请切断电源,以防意外;
⑵ 清理冷凝器、过滤网及内部油污;
⑶ 请对机器采取防尘措施,延长机器使用寿命。
5. 故障排除
故障状况 1 电源接通后,室内、室外风机不运转,温控器不显示
可能原因 ※保险丝熔断
-12-
※停电或无电源
状况排除
※更换保险丝
※检查电源状况
故障状况 2 过载指示灯亮
可能原因
※环境温度过高,导致压缩机热保护
※过滤网堵塞或者冷凝器过脏,导致压缩机热保护
状况排除
※改善周边环境,使散热畅通
※对过滤器及冷凝器进行清洗
故障状况 3 冷媒指示灯亮
可能原因
※压缩机损坏
※制冷剂泄露
状况排除
※更换压缩机,重新抽真空充注制冷剂
※查出泄露处,并重新抽真空加制冷剂
◇若上述措施均不能排除故障,请致电本公司咨询!
6. 注意警告:
顶置式空调进出风口下部严禁放置重要元气件及电器零件,防止漏水损坏重要部件!
附录 1:产品技术参数
型号:ZLJBD-35T-380V50Hz
运行电流: 6.55A
功 率: 1650W
制冷剂: R134a
制冷量: 3500W
防护等级:IP54
允许机柜内温度设定范围:25--38℃(出厂设定 30℃)
允许使用环境温度范围:-25-45℃
循环风量: 内循环 920m ³/h 外循环:1250m ³/h
噪音:65dB
附录 2:电气原理图
-13-
室内风机 室外风机 压缩机
M1 M2 M3
C2 C3
L
N
PE
t℃温控器
苏 州 追 途 电 气 设 备 有 限 公 司
电话:17311128188