Systematic Fire Solutions from Detection to Action
PRODUCT CATALOGUE
CREATEASAFEWORLD -ENJOYASMARTLIFE
SHENZHEN HTI SANJIANG ELECTRONICS CO.,LTD.
Why SANJIANG:
SANJIANG is a professional fire alarm manufacturer that has specialized in the design and manufacturing of highquality fire detection products since l985.Over the years, we have expanded our capabilities to develop sophisticated analogue addressable fire alarm control panels,detectors,and interfaces.Our integrated fire protection solutions,including fire alarm systems,gas extinguishing systems,and fire emergency indicatingand evacuation systems,are trusted by customers all over the world.With our extensive technical expertise,industry experience,complete sales channels,and mature management models,we have gained an excellent market reputation as a dependable fire alarm supplier.We provide tailored technical support,adhering to local standards and customer requirements,ensuring we meet the needsof differentmarkets.
Trustworthy Fire Detection Solutions Supplier:
In addition to design and manufacture,SANJIANG provides technical support specified to the local standards and customer requirements worldwide and provides the fire detection solutions to over 50 countries. With a commitment to meeting the needs of different markets,SANJIANG has resulted in its fire alarm systems beinginstalled in numerous scenarios across the world.
Supply Chain and Quality Assurance:
SANJIANG employs advanced modern production techniques and state-of-the-art manufacturing equipmentto ensure consistent high-quality products and timely responses to customer demands.Our fully automatic and intelligent manufacturing facility can produce over 30,ooo detectors a day,ensuring that each and every product meets the highest standards.
Key Guide
Applications
Apartment
天
Escape Routes
R
Dusty Environments
上
Car Parks& Loading Bays
□
Mediumto Large Buildings
固
Hospitals
巧
Large Hotels
Data Centres
X Restaurants
囤
Small to Medium Buildings
↑
Residence
出
Marine
匡
Factory
A
Hazardous Areas
金
Warehouse
Solutions
AddressableFire Alarm System(EN54)
□
Gas Extinguishing System
AddressableFire AlarmSystem
FireTelephoneSystem& Fire Emergency BroadcastSystem
Certificate
Contents
FIREALARMSYSTEM (EN54) 08
CONVENTIONALFIREALARMSYSTEM 20
GASEXTINGUISHSYSTEM 26
FIREALARMSYSTEM 31
LoRaWIRELESSFIREALARMSYSTEM 45
FIRETELEPHONESYSTEM/FIREEMERGENCYBROADCASTSYSTEM
MULTI-LOOP FIRE ALARM CONTROL PANEL (EN54)
SEC30o8/Multi Loop Fire Alarm Control Panel
Features
EN54-2&EN54-4complied. With 7-inch touchscreen color display to read and operate.
? Abundant accessories, supports high customization. Networkable,up to 254 panels under Ethernet protocol orup to 60 panels under CAN protocol.
←Up to 8 loops,324 points per loop.
? Up to 6 sounder outputs and 2 class change inputs.
? Up to additional 4 active outputs and 2 dry contact outputs.
+ Up to 144 zone status indicators, 5oo0 zone-set capacity.
+ Up to 10,ooo historical recordings (alarms,faults or operations).
+ Supports upgrade via U-disk and importing or exporting data to PC.
? Supports class A type wiring under CAN protocol. Supports day/night mode,which is convenient for multi-scene applications such as hotels, apartments, residences, etc.
| Specifications | |
| System Voltage | 28V±0.5VDC |
| Supply Voltage | 110/230VAC (-15%, +10%),50Hz/ 60Hz |
| Battery | 2×12V/18Ah (Standard),2x12V/24Ah (Deep,38Ah isalternative) |
| Dimension | 440×590×185mm (Standard);440×590×230mm (Deep) |
| Operating Environment | -10~55℃;Rh≤95% (40℃±2C,no condensation) |
| Protection Level | IP30; Flame retardant rating V-0 |
SEC3004/Multi Loop Fire Alarm Control Panel
Features
EN54-2& EN54-4 complied. With 7-inch touchscreen color display to read and operate.
? Abundant accessories, supports high customization. Networkable,up to 254 panels under Ethernet protocol or up to 60 panels under CAN protocol.
. Up to 4 loops,324 points per loop. Up to 6 sounder outputs and 2 class change inputs.
↑ Up to additional 4 active outputs and 2 dry contact outputs.
1 Up to 48 zone status indicators,5oo0 zone-set capacity. Up to 10,Ooo historical recordings (alarms,faults or operations).
. Supports upgrade via U-disk and importing or exporting data to PC. Supports class A type wiring under CAN protocol.
? Supports day/night mode,which is convenient for multi-scene applications such as hotels, apartments,residences,etc.
| Specifications | |
| System Voltage | 28V±0.5VDC |
| Supply Voltage | 110/230VAC (-15%,+10%),50Hz/60Hz |
| Battery | 2×12V/12Ah |
| Dimension | 440×410×155mm(W×H×D) |
| Operating Environment | -10~55C;Rh≤95%(40℃±2C,no condensation) |
| ProtectionLevel | IP30; Flame retardant rating V-0 |
SEC3000/Repeater Panel
Features
←EN 54-2& EN54-4 complied.
●With 7-inch touchscreen color display to read and operate.
←With 1 fire alarm relay and 1 fault relay output.
←Up to 10,ooo historical recordings (alarms,faults or operations).
←Supports upgrade via U-disk and importing or exporting data to PC.
Networkable,up to 254 panels under Ethernet protocol or up to 60 panels under CAN protocol.
←Fully functional with Evacuate,Mute, Silence,and Reset controls,and display indications as the main control panel.
| Specifications | |
| System Voltage | 18~30VDC |
| Dimension | 370×250×125mm |
| IP Rating | IP30 |
| Operating Environment | -10~55C;Rh≤95%(40℃±2C,no condensation) |
| FlameRetardantRating | V-0 |
SEC3008_HL_9000/9000 Protocol Lo0p Board
This loop expansion card provides two loops that are inserted into the SEC3004/SEC3008 card slots to increase the number of loops of the panel.Supportsall 9000 protocol devices.
2analogue addressable loops
Supports up to 324 addressable devices per loop
Supports Sanjiang 9oo0 loop protocol Easy installation
Compatible with SEC3004/SEC3008
PS-A2907E/Power Supply Equipment
PS-A2907E meets EN54-4 standard,with charging temperature compensationand battery internal resistance faultdetection.
Individual cell voltage monitoring has undervoltage alarmand backup power undervoltage protection.This equipment has full metal jacket,is very easy to install.
Supply Voltage:110/230VAC (-15%, + 1 0 %
50Hz/60Hz
Output Voltage:28.4V±0.5V
Rated Output Current: 7.1A
Charging Current: 1A ± 0 . 3 A (CC Mode)
Operating Environment: - 1 0 ~ 5 5 ^ { \circ } C
Rh≤95% 1 4 0 ^ { \circ } C ± 2 ^ { \circ } C ,no condensation)
SEC3oo8_Modbus/Communication module
Rs485 communication module,which can be connected to a remote indicate panel and can communicatewith othermanufacturers'productsvia Modbus protocol.
RS485 data communication protocol 2interfaces,one forconnecting to remote indicating panel,one for Modbus modules Easy installation Compatible with SEC3004/SEC3008
SEC3oo8_SND/Conventional Sounder Module
Provideaclass change input interface and two additional sounder output interface. A maximum of two boards can be installed on a SEC3004/SEC3008.
2sounder outputsand 1class change input Compatible with SEC3004/SEC3008
SEC30o8_Relay/Programmable Relay Output Module
Provideadditional volt-freeandactive output interfaces. A maximum of two boards can be installed on an SEC3004/SEC3008
2active outputs and 1dry contact output :Compatiblewith SEC3004/SEC3008
SEC3008_COMS/CAN Class B Networking Module
This board is used for communicationwith other Sanjiang panels,enabling the rapid and secure transmissionofawide rangeof informationand data, including Fire, Faults, Disable, Linkage,and more
CANdatacommunicationprotocol 1 Class B type wiring Compatible with SEC3004/SEC3008
SEC3008_COMD/CAN Class A Networking Module
This board features two relatively independent CAN interfaces,which can be used to forma ring topology network. In the event of a line fault, communication with other machines remains unaffected, greatly enhancing safetyand stability.
CANdatacommunication protocol Class A type wiring * Compatible with SEC3004/SEC3008
SEC3008_COME/Ethernet Networking Module
This board features two independent Ethernet interfaces.Provides fasterand more stabledata transmission compared to CAN protocol networking.
+ Ethernet data communication protocol + Compatible with SEC3004/SEC3008
Lightning Protection Board
Provides strong electrical protection for the panels.
Provides high EMC protection + CompatiblewithSEC3004/SEC3008
02
FIRE ALARM SYSTEM (EN54)
FIREALARMSYSTEM
SEC3o02/AddressableFire Alarm Control Panel
Features
EN54-2& EN54-4 certified.
Up to 324 addresses for one loop/510 addresses for two loops.
32 programming zone manual control button.
Multi-language selection.
Intelligently monitoring detectors'conditon under circumstances such as "polluted", "missing","duplicate-programming"etc.
4.3-inch color screen LCD,resolution of 4 8 0 ^ { * } 2 7 2
Support 255 panels under Ethernet Protocol or 60 panels under CAN Protocol. Software remoteupgradeand Lifetimemaintenance.
| Specifications | |
| System Voltage | DC18.5~30V |
| Main Supply | AC 230V (-15%, +10%), 47-63Hz |
| Battery | 2×12V/12~17Ah |
| Dimension | 430×560×170mm (W×H×D) |
| Operating Environment | -10~45°C; Rh≤95% (40℃±2C,no condensation) |
SEC1ooO/Addressable Fire Alarm Control Panel
Features
. EN54-2& EN54-4 certified.
+ 16 zone Indicators.
? Up to 120 addresses each loop.
+ Supported loop type: classA& Class B.
+ Support 60 panels under CAN Protocol.
+ Multi administration levels.
+ Record capacity of 10oo historical events.
+ Individual Testing for Detectors/Modules.
1 4.3-inch color screen LCD with a resolution of 4 8 0 ^ { * } 2 7 2 + Support data import and export,data configuration via USB.
LPCB CE国 国
| Specifications | |
| System Voltage | DC 20~28V |
| Main Supply | AC 110V/230V (-15%,+10%), 50-60Hz |
| Battery | 2×12V/7Ah |
| Dimension | 400×360×104mm (W×H×D) |
| Operating Environment | -10~45C;Rh≤95% (40oC±2C,no condensation) |
LEU400/Loop Expansion Unit
Features
EN54-2& EN54-4 certified.
←Loop type: Class A.
←4 loops,up to 255 points for each loop. Workwith SEC3002 Fire Alarm Control Panel.
| Specifications | |
| System Voltage | DC 24V (22~30V) |
| Operating Current | |
| Dimension | 300×380×120mm (WxHxD) |
| Operating Environment | -10~45C; Rh≤95% (40oC±2C,no condensation) |
A9020T/Addressable Heat Detector
Features
EN54-5 certified.
Remote 3 6 0 ^ { \circ } visible LED Indicator output.
Simple and reliable device addressing via portable coder.
Support temperature compensationand sensor fault inspection.
| System Voltage | DC 24V (18~28V) |
| Operating Current | Quiescent current: |
| Dimension | 100×60mm (ΦxH) (with base) |
| Operating Environment | -10~50℃; Rh≤95% (40C±2C,no condensation) |
A9030T/Addressable Smoke Detector
Features
←EN54-7 certified.
Remote 3 6 0 ^ { \circ } visible LED Indicator output. Simple and reliable device addressing via portable coder. Patented designed smoke chamber reduce false alarm.
| Specifications | |
| System Voltage | DC 24V (18~28V) |
| Operating Current | Quiescent current: |
| Dimension | 100×58mm (Φ×H) (with base) |
| Operating Environment | -10~50℃; Rh≤95% (40℃±2C,no condensation) |
A9036T/Addressable Smoke & Heat Detector
Features
EN54-5& EN54-7 certified.
Remote 3 6 0 ^ { \circ } visible LED Indicator output.
←Patented designed smoke chamber reduce false Alarm. Support temperature,humidity and dust accumulation drift compensation.
| Specifications | |
| System Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 100×60mm (ΦxH) (with base) |
| Operating Environment | -10~50°℃;Rh≤95% (40C±2C,no condensation) |
A906OT/Addressable Manual Call Point
Features
EN54-11 certified.
Reusableand resettable operatingdevices.
Simpleand reliable deviceaddressing via portable coder.
Stable communication technique with high noise immunity.
| System Voltage | DC 24V (18~28V) |
| Operating Current | Quiescent current: |
| Dimension | 90×90×42mm (WxHxD) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2°C,no condensation) |
A9091T/Addressable Sounder Strobe
Features
EN54-3& EN54-23 certified.
+ Providing 16 tones.
+ Sound and light synchronized output.
+ Simpleand reliable deviceaddressingvia portable coder.
√ Highly efficient LED technology and specially designed lens.
| Specifications | |
| System Voltage | DC 24V (20~28V) |
| Sounder Output | ≥75dB@1m |
| Dimension | 100mm×100.5mm (Φ×H) (with base) |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
A9092T/Addressable Loop-powered Sounder Strobe
Features
1 EN54-3 certified.
1 Directly powered by the loop. Sound and light synchronized output.
√ Simple and reliable device addressing via portable coder.
+ Highly efficient LED technology and specially designed lens.
| Specifications | |
| System Voltage | DC 24V (20~28V) |
| Sounder Output | ≥73dB@1m |
| Dimension | 100×100.5mm (Φ×H) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2°C,no condensation) |
A9093T/High Output Sounder Strobe
Features
EN 54-3 (Indoor) complied.
With up to7 tone modes,suitable for both conventional and addressable control panel, supports multiple sounder/strobe modes.
The structure has the function of anti-demolition.
| Specifications | |
| Operating Voltage | DC 24V (22~28V) |
| Maximum Sound Output | ≥107dB@1m |
| Dimension | 112×100mm (Φ×H) (with base) |
| Protection Level | IP21C |
| Operating Environment | -10~55C; Rh≤95% (40C±2C,no condensation) |
A9093G/High Output (Weatherproof) Sounder Strobe
Features
EN54-3 (Outdoor) complied.
With up to 7 tone modes,suitable for both conventional and addressable control panel, supports multiple sounder/strobe modes.
The structure has the function of anti-demolition.
| Specifications | |
| Operating Voltage | DC 24V (22~28V) |
| Maximum Sound Output | ≥95dB@1m |
| Dimension | 100×112×133mm (with base) |
| Protection Level | IP65,VO flame retardant rating |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
A9052T/Addressable Zone Module
Features
EN54-18 certified.
←Max 30 conventional devices. Connected with conventional smoke detector and heat detector. Simple and reliable device addressing via portable coder.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 86×86×41mm (WxH×D) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40C±2C,no condensation) |
A9056T/Addressable Input/Output Module
Features
←EN54-18 certified.
←Provide high reliabilityand error detection. Simple and reliable device addressing via portable coder.
? Control of fire linkage equipments such as smoke dampers,blow valves and fire dampers.
| Operating Voltage | DC24V (20~28V) |
| Operating Current | Quiescentcurrent: |
| Dimension | 86×86×41mm (WxHxD) (with base) |
| Operating Environment | -10~55C;Rh≤95%(40℃±2C,no condensation) |
A9057T/Short CircuitIsolator
Features
? EN54-17 certified.
? Low powerconsumption.
√ Minimises disruption from short circuit.
↓ Fast activation response loop-powered.
+ Isolation of short circuitand automatic recoveryafter removal.
| Specifications | |
| Operating Voltage | DC 24V (16~28V) |
| Operating Current | Quiescent current: |
| Dimension | 86×86×41mm (WxHxD) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40o℃±2C,no condensation) |
A9058T/Addressable Loop-powered Input/Output Module
Features
EN54-18 certified.
Built-in standalone CPU.
Low power consumption.
Can be connected with conventional terminals.
| Specifications | |
| Operating Voltage | DC 24V (18~28V) |
| Operating Current | Quiescent current: |
| Dimension | 90×90×42mm (WxH×D) (with base) |
| Operating Environment | -10~55℃; Rh≤95%(40℃±2C,no condensation) |
A9097B/Addressable Sounder Strobe Base
Features
←EN54-3 certified.
? Combines the sounder beacon function to detector base. Can be equipped with smoke detector or heat detector. Super bright red LED as light sources for visual display.
Specifications
| Operating Voltage | DC 24V (20~28V) |
| Sounder Output | ≥73dB@1m |
| Dimension | 115mm×44mm (Φ×H) (with base) |
| Operating Environment | -10~55C;Rh≤95% (40℃±2C,no condensation) |
A9073T/Addressable Output Module
Features
←EN54-18 certified.
←Two output modes: NO and NC.
←Output through dry contacts after activation.
←Low power consumption.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 86×86×46mm (WxH×D) (withbase) |
| Operating Environment | -10~55℃; Rh≤95%(40C±2C,no condensation) |
Features
EN54-17 certified.
←Mini mises disruption from short circuit.
Isolation of short circuit,automatic recoveryafter removal. Compatible with smoke detectors, heat detectors.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 100×31.4mm (Φ×H) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40C±2C,no condensation) |
D9057M/lsolatorModule
Features
←EN54-17 certified.
Support single point isolation and zone isolation.
Short-circuit isolation is possible quickly. Be used with terminals.
| Specifications | |
| System Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 45×26×17mm (W×H×D) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2°C,no condensation) |
GSM/4G ModuleTAS-LTE-395
Features
TAS-LTE-395 is equipped with 2G/3G/4G working standardsand supports mobile phone cards and loTcards.It can upload and send messages about faults,alarmsand key actions of fire alarm controllers to users.
| Input Voltage | DC 5~36V |
| Working Current | Average: 22~45mA; Maximum: 350mAV12V |
| Dimension | 86×82×25mm (W×HxD) |
| Storage Environment | -40~85C;5~95% RH (no morning dew) |
| Standard | 2G/3G/4G (Rate: 14.4Kbps~50Mbps) |
| Standard Frequency Band | GSM900/1800,CDMA Bc0,WCDMA B1/B8,TD-CDMA B34/B39, LTEFDDB1/B3B5/B8,LTETDDB34/B38/B39/B40B41 |
CAN-DTU/Information TransferUnit
Features
Convenient to operate.
Simple and beautiful software interface.
Using PCGraphic software to set the baud rate.
Stable and reliable communication system connection.
| Specifications | |
| Operating Voltage | USB power supply |
| USB Interface | USB 3.0, 2.0, 1.1 |
| Dimension | 104×70×25mm (W×H×D) |
| Operating Environment | -10~55C;Rh≤95% (40℃±2C,no condensation) |
LS30/Loop Isolation Stabilizer
Features
Optional installation.
←Required for use with isolator base and module.
●Protect the panel core circuit and effectively resist external high voltage damage.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | ≥700mA |
| Mating Host | SEC1000 |
| Dimension | 48×81.2×42.3mm (WxH×D) |
| OperatingEnvironment | -10~55℃; Rh≤95%(40oC±2C,no condensation) |
LS90/Loop Isolation Stabilizer
Features
Optional installation.
←Required for use with isolator base and module.
Adopt common mode circuit design,effectively improve the anti-interference ability.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | ≥700mA |
| Mating Host | SEC3002 |
| Dimension | 48×81.2×42.3mm (W×H×D) |
| Operating Environment | -10~55C;Rh≤95% (40C±2C,no condensation) |
JTY-GS-T8001/Addressable Reflective Beam Detector
Features
Meet the standards of EN54-12 and GB 14003.
With real-time sampling,processing,curve tracking.
With an automatic compensation function(for dust pollution).
With laser module to locate,with infrared calibration function.
With self-diagnostic function, can monitor the internal error.
Supports addressable fire alarm control panel A104E/A108E/A220E,etc.
| Operating Voltage | DC 24V (18~32V) |
| Operating Current | Quiescent current |
| Dimension | 180×83×73mm (with base) |
| IP Rating | IP30 |
| OpticalPathLength | 5m~60m (Protection range 7m on each side) |
| Operating Environment | -10~55C; Rh≤95% (40oC±2°C,no condensation) |
03 CONVENTIONAL FIRE ALARMSYSTEM
CONVENTIONALFIREALARMSYSTEM
SEC3016C/Conventional Fire Alarm Control Panel
Features
←EN 54-2& EN54-4 complied.
? Supports 2/4/8/12/16 zones,and 32 devices per zone.
←Supports walk test function (One man test function).
Able to disable any zones or sounder circuits.
→ Supports a maximum battery capacity of 7Ah.
Supports sounder delay option,and up to 4 sounder output circuits.
+ Supports Aux 24V supplies (Sounder circuits 3 and 4).
+ Supports Repeatercommunication interface.
| Specifications | |
| System Voltage | DC26.5V~28.5V±0.5V |
| Supply Voltage | AC 110V/230V (-15%, +10%), 50-60Hz |
| Battery | 2×12V/7Ah |
| Dimension | 380×340×100mm (WxH×D) |
| Operating Environment | -10~55C;Rh≤95% (40C±2C,no condensation) |
C9030T/Conventional Smoke Detector
Features
EN54-7 complied.
With 3 6 0 ^ { \circ } visible LED Indicator output .
Can realize curve trace by data,and up to 144 historical data.
Support drift compensation (temperature,humidity&dust).
Supports connection to Remote Indicator (eg.C9069L).
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current |
| Dimension | 100×46mm (Φ×H) (with base) |
| IP Rating | IP30 |
| Operating Environment | -10~55C;Rh≤95% (40℃±2C,no condensation) |
C9021T/Conventional Heat Detector
Features
? EN 54-5 complied.
+ Real-time monitoring of temperature in protected areas.
? Non-polarity, two-cable connection. Easy for installation, commissioning and maintenance.
? Supports connection to remote indicator(eg.C9069L).
Specifications
| Operating Voltage | DC 24V (18V~30V) |
| Operating Current | Quiescent current |
| Dimension | 100×60mm (Φ×H) (with base) |
| IP Rating | IP30 |
| Operating Environment | -10~50°C; Rh≤95% (40C±2°C,nocondensation) |
C9020T/Conventional Heat Detector
Features
. EN54-5 certified. Two mode selectting:A2R& A2S.
. Real-time temperature monitoring. Support temperature compensationand sensor fault inspection.
| Specifications | |
| Operating Voltage | DC 24V (18~30V) |
| Operating Current | Quiescent current: |
| Dimension | 100×60mm (Φ×H) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40°℃±2C,no condensation) |
C9097B/Conventional Sounder Base
Features
EN54-3 complied.
Combines the sounder function to detector base.
Workwith smoke detector or heat detector.
External DC 24V for power supply.
| Specifications | |
| Operating Voltage | DC24V (20V~28V) |
| Sounder Output | 86dB(A)@1m |
| Dimension | 115×44mm (Φ×H) (with base) |
| Protection Level | IP21C; Flame retardant rating V-0 |
| Operating Environment | -10~55°C; Rh≤95% (40C±2°C,no condensation) |
C9092T/Conventional Sounder Strobe
Features
←EN54-3(Type A-indoor) complied.
←Simple and convenient for installation,commissioning and maintenance.
←High brightness, long life,low power consumption.
√ With up to 7 tone modes, with anti-tamper function.
| Specifications | |
| Operating Voltage | DC 24V (22~28V) |
| Maximum Sound Output | ≥90dB(A)@1m (Tone1@90°) |
| Dimension | 111×111×50mm (with base) |
| Protection Level | IP21C; Flame retardant rating V-0 |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
C9091T/Conventional Sounder Strobe
Features
EN54-3& EN54-23 certified.
Providing 16 tones.
Sound and light synchronized output.
Highly efficient LED technology and specially designed lens.
| Specifications | |
| Operating Voltage | DC 24V (20V~28V) |
| Sounder Output | ≥75dB@1m |
| Dimension | 100×100.5mm (Φ×H) (with base) |
| Operating Environment | -10~55C;Rh≤95% (40C±2C,no condensation) |
C906OT/Conventional Manual Call Point
Features
? EN54-11 complied.
? Re-settable operating element.
Non-polarity,two-cable connection for easy installation and maintenance.
| Specifications | |
| Operating Voltage | DC 24V (20V~28V) |
| Operating Current | Quiescent current=0mA;Alarm current |
| IP Rating | IP30 |
| Dimension | 90×90×42mm (WxH×D) (with base) |
| Operating Environment | -10~55°C; Rh≤95% (40℃±2°C,no condensation) |
Features
Designed with an upper cover and a lower cover,simple and convenient maintenance. Non-polarity, two-cable connection for easy installation and maintenance. Optional mounting back plate (need order separately).
| Specifications | |
| Operating Voltage | DC 5V (4V~5V) |
| Operating Current | Quiescent current=0mA; Alarm current: 1mA~30mA |
| IP Rating | IP30 |
| Dimension | 64×64×30mm (W×H×D) |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
04
ECP10oO/Gas Extinguishing Control Panel
Features
EN12094-1,EN54-2&EN54-4certified.
+ Class A and Class B.
←255 addresses for single loop.
←2 conventional zones (Supports 32 conventional detectors per zone).
←4.3-inch color LCD display,providing clearer status indication.
←Indicates with a countdown before the gas begins to be released.
←Support data import and export, data configuration with USB.
←Fire alarm cause&effect and configuraiton can be ←Programmed on the control panel or PC-set.
+ Networkable,support 60 panels under CAN Protocol or 255 panels under Ethernet Protocol, support7 RSU100 under RS485 Protocol.
Support modbus public protocol(by Rs485).
| Specifications | |
| Supply Voltage | AC 110V/230V,50-60Hz |
| Operating Current | S.C.OUT (+,-) Max.output current 500mA |
| Battery | 2x12V/7Ah |
| Dimension | 410×460×92mm (W×H×D) |
| Operating Environment | -10~45C; Rh≤95% (40C±2C,no condensation) |
RSU100/Remote Status Unit
Features
EN12094-1 certified Networkable,up to 7 RSU100 per extinguishing panel (RS-485 Protocol). : Easy installation with four-wire connection. Provide LED indicator of system status. Optional auto/manual key switches and manual release push-buttons. Acountdown is displayed in the form of a digital tube before the gas is released. Communication distance is up to 1200 meters. With robust and steel enclosure. Can get a loud alarm tone with the 24V buzzer. The device address can be set easily.
| Specifications | |
| System Voltage | DC 24V (21~30V) |
| QuiescentCurrent | 0.02A |
| IP Degree | IP30 |
| Dimension | 200×140×50mm (W×H×D) |
| Operating Environment | -10~45C; Rh≤95% (40oC±2°C,no condensation) |
QM-ZSD-O1E Gas Releasing Indicator
Features
+ EN12094-1 meet.
? Conventional design without address,easy to install.
+ Ultra-bright display with low power consumption.
? Easy installation and maintenance(The cover structural design).
? Low current consumption and long lifespan.
| Specifications | |
| Operating Voltage | DC 18~24V |
| Trigger Current | ≤150mA |
| Dimension | 140×111×35mm (W×H×D) |
| Operating Environment | -10~55℃;Rh≤95% (40o℃±2C,no condensation) |
Features
EN12094-1 certified.
Shrouded push-button to prevent inadvertent operation.
Compatiblewith ECP1000 Panel.
Robust and steel enclosure.
The button color is optional(red or green).
| Specifications | |
| Trigger Resistor | 10K,1W |
| IP Degree | IP30 |
| Dimension | 90×90×70mm (W×H×D) |
| Operating Environment | -10~55℃;Rh≤95% (40℃±2C,no condensation) |
05
FIRE ALARM SYSTEM
JB-QBL-A108E/Addressable Fire Alarm ControlPanel
Features
+ GB 4717& GB 16806 certified.
? Support the two-bus system.
? 10-inch color LCD with a resolution of 1024\*600.
? Support mouse or keyboard connection for ? programming onsite.
+ 8 loops,up to 324 addresses per loop.
? The maximum capacity of the multi-line linkage control unit is 22 points.
+ Support CAN Protocol and Ethernet Protocol.
+ Ul is similar to the Windows system,making it easy to use and learn.
+ Simple construction and convenient wiring method.
| Specifications | |
| Supply Voltage | AC 220V/50Hz (187V~242V) |
| Operating Current | 10A |
| Battery | 2x12V/14Ah |
| Dimension | 570×750×158mm (W×H×D) |
| Operating Environment | -10~45C; Rh≤95% (40oC±2C,no condensation) |
JB-QBL-A104E/Addressable Fire Alarm Control Panel
Features
GB 4717& GB 16806 certified.
7 Support the two-bus system application. 4.3-inch color LCD with a resolution of 480\*272.
7 Support mouse or keyboard connection for programming onsite. 4 loops,up to 324 points per loop.
1 Multi-line linkage control unit is up to 6 points. Support CAN Protocol and Ethernet Protocol. Ul is similar to the Windows system,making it easy to use and learn. Simple construction and convenient wiring method.
| Specifications | |
| Supply Voltage | AC 220V/50Hz (187V~242V) |
| Operating Current | 4A |
| Battery | 2×12V/14Ah |
| Dimension | 410×490×100mm (W×H×D) |
| Operating Environment | -10~45℃; Rh≤95% (40C±2C,no condensation) |
JB-QBL-A220E/Addressable Fire Alarm Control Panel
Features
GB 4717 certified. + Support the two-bus system application. 2.8-inch color LCD with a resolution of 2 4 0 ^ { \ast } 3 4 0 Support copying or restoring the system's setup files and history files. Single loop,up to 200 points. User-definable device types for easy system integration. Support CAN Protocol.(optional). Ul is similar to the Windows system,making it easy to use and learn. Simple construction and convenient wiring method.
| Specifications | |
| Supply Voltage | AC 220V/50Hz (187V~242V) |
| Operating Current | 1A |
| Battery | 12V/2.8Ah |
| Dimension | 273×385×112mm (W×H×D) |
| Operating Environment | -10~45°C; Rh≤95% (40℃±2C,no condensation) |
JTY-GD-A30E/Addressable Smoke Detector
Features
GB4715 certified.
Electronic encoding method allows onsite readdressing via an encoder.
The microchip performs real-time sampling and data processing to calculate smoke concentration.
Features temperature,humidity,and dust accumulation drift compensation.
Specifications
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Dimension | 105×43mm (ΦxH)(with base) |
| Operating Environment | -10~55℃;Rh≤95% (40℃±2C,no condensation) |
JTW-ZD-A20E/Addressable HeatDetector
Features
GB4716 certified.
? Fully electronic encodingallows for on-site rewriting via an encoder. The microchip performs real-time temperature sampling and data processing. Features temperature compensationand sensor failure detection.
| Specifications | |
| Operating Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Product Category | A2 (operating temperature:54C~70℃) |
| Dimension | 105×43mm (ΦxH) (with base) |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
JS-A51E/Addressable Input Module
Features
GB16806 certified. Fully electronic encoding allows for on-site rewriting via an encoder. It can interface with various passive normally open switching devices,such as water flow indicator,pressure switches, signal valve,flow switches.
| Specifications | |
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Dimension | 86×86×35mm (WxHxD) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40C±2C,no condensation) |
JK-A52E/Addressable Input Module
Features
GB 16806 certified.
Fully electronic encoding allows for on-site rewriting viaan encoder.
← Non-polarity two-bus technology. Up to 25 conventional detectors.
| Specifications | |
| System Voltage | DC 24V (20~28V) |
| Operating Current | Quiescent current: |
| Dimension | 86×86×46mm (WxH×D) (with base) |
| Operating Environment | -10~55℃;Rh≤95% (40℃±2C,no condensation) |
GL-A59E/Short Circuit lsolator
Features
Isolation of short circuit and automatic recovery after removal.
Stable communication technique with high noise immunity.
Fast activation response loop-powered.
Designed with plug and play structure,easy and convenient for construction and maintenance.
Specifications
| Operating Current | Quiescent current: |
| Trigger Action Current | >2A |
| TriggerAction Voltage | |
| Dimension | 86×86×35mm (WxHxD) (with base) |
| OperatingEnvironment | -10~55°℃; Rh≤95% (40°C±2C,no condensation) |
KZJ-A55E/Addressable Input/Output Module
Features
GB16806 certified.
←Fully electronic encoding allows for on-site rewriting via an encoder.
←Non-polarity two-bus connection for easy installation and maintenance.
? It can interface with various devices,such as water flow indicator,flow switches.
Specifications
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Output Capacity | DC34V/1.5A/25msorDC24V/18mA |
| Dimension | 86×86×40mm (WxHxD) (with base) |
| Operating Environment | -10~55C;Rh≤95%(40℃±2C,no condensation) |
KZJ-A76E/Addressable Input/Output Module
CCC
Features
GB16806 certified.
←Fully electronic encoding allows for on-site rewriting via an encode.
←Non-polarity two-bus technology and convenient wiring.
Mainly used to control fire broadcasting and background music.
| Specifications | |
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Output Capacity | Current: |
| Dimension | 86×86×40mm (WxHxD) (with base) |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
J-SAP-M-A62E/Addressable Manual Call Point
Features
. GB 19880 certified.
+ Simple and reliable device addressing via portable coder.
+ Stable communication technique with high noise immunity.
+ Reusable and resettable operating elements.
Specifications
| Operating Voltage | Loop24V |
| Operating Current | Quiescent current: |
| Dimension | 90×90×43mm (WxHxD) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2°C,no condensation) |
SG-A92E/Addressable Sounder Strobe
Features
GB 26851 certified.
Fully electronic encoding allows for on-site rewriting via an encoder.
Light display using several ultra-bright white LED light sources,display eye-catching,long life, low power consumption.
| Specifications | |
| OperatingVoltage | Loop 24V |
| Operating Current | Quiescent current: |
| Sounder Output | ≥80dB@3m |
| Dimension | 111×50mm (Φ×H) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40C±2C,no condensation) |
JTF-GDM-936E/Addressable Smoke & Heat Detector
Features
GB4715&GB4716certified Fully electronic encoding allows for on-site rewriting via an encoder. Dual sensing technology. Shift compensation function and contamination report function for dust accumulation.
| Specifications | |
| Operating Current | Loop 24V |
| Trigger Action Current | Quiescent current: |
| Trigger Action Voltage | A2(Operating temperature:54C~70℃) |
| Dimension | 100×100×55mm (WxH×D) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2°C,no condensation) |
JB-FSD-A82E/Fire Indicating Panel
Features
GB 17429 certified.
Fully electronic encoding allows for on-site rewriting via an encoder.
Emitan alarm sound and display relevant information. A maximum of 999 alarms.
Specifications
| OperatingVoltage | Loop24V |
| Operating Current | Quiescent current: |
| Dimension | 180×110×31mm (WxHxD) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40oC±2C,no condensation) |
JTY-GD-A30KE/Conventional Smoke Detector
Features
GB 4715 certified.
The microchip performs real-time sampling and data processing to calculate smoke concentration.
Features temperature,humidity,and dust accumulation drift compensation,as wellas sensor failure detection (fault information reported to the panel).
| Specifications | |
| Operating Voltage | DC 24V |
| Operating Current | Quiescent current: |
| Dimension | 105×43mm (ΦxH) (with base) |
| Operating Environment | -10~55°C; Rh≤95% (40C±2C, no condensation) |
JTW-ZD-A20KE/Conventional Heat Detector
Features
GB 4716 certified.
The microchip performs real-time temperature sampling and data processing,tracking the on-site situation with curves.
Real-time monitoring,and accurate judgment.
| Specifications | |
| Operating Voltage | DC 24V |
| Operating Current | Quiescent current: |
| Product Category | A2 (operating temperature:54C~70℃) |
| Dimension | 105×43mm (Φ×H) (with base) |
| Operating Environment | -10~55C;Rh≤95% (40C±2C,no condensation) |
J-SAP-M-A62KE/Conventional Manual Call Point
CCC
Features
GB 19880 certified.
Comeswithatwo-wire fire telephone jack.
The manual alarm provides passive output contacts,which can directly control external devices through an intermediate relay.
Resettable press button.
Specifications
| OperatingCurrent | DC24V |
| TriggerActionCurrent | Quiescent current: |
| Dimension | 90×90×43mm (WxHxD) (with base) |
| Operating Environment | -10~55C;Rh≤95% (40oC±2C,no condensation) |
JTY-GD-A30E-Ex/Addressable Intrinsically Safe Smoke Detector
Features
GB4715&GB/T3836.1&GB/T3836.4certified.
Explosion-proof type: Intrinsic safety.
Fully electronic encoding allows for on-site rewriting via an encoder.
Themicrochip performs real-time sampling and data processing to calculate smoke concentration.
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Explosion-proof sign | Ex ib IIC T6 Gb |
| Dimension | 105×43mm (Φ×H) (with base) |
| Operating Environment | -10~55C; Rh≤95% (40C±2C,no condensation) |
JTW-ZD-A2OE-Ex/Addressable Intrinsically Safe Heat Detector
Features
GB4716&GB/T3836.1&GB/T3836.4certified.
Explosion-proof type: Intrinsic safety.
Fully electronic encoding allows for on-site rewriting via an encoder.
The microchip performs real-time temperature sampling and data processing,tracking the on-site situation with curves.
Specifications
| Product Category | A2R |
| Operating Current | Quiescent current: |
| Explosion-proof sign | Ex ib IIC T6 Gb |
| Dimension | 105×43mm (Φ×H) (with base) |
| Operating Environment | -10~55℃;Rh≤95% (40C±2C,no condensation) |
SG-A92E-Ex/Addressable Intrinsically Safe Sounder Strobe
Features
:GB 268511& GB/T3836.1& GB/T 3836.4 certified.
←Explosion-proof type: Intrinsic safety.
●Fully electronic encoding allows for on-site rewriting via an encoder.
Display using several ultra-bright,long life,and low power consumption.
| Specifications | |
| Flash Frequency | 1.0Hz~1.5Hz |
| Operating Current | Quiescent current: |
| Explosion-proof sign | Ex ib IIC T6 Gb |
| Sounder Output | ≥70dB@3m |
| Dimension | 105×50mm (φ×H) (with base) |
J-SAP-M-A62E-Ex/Addressable Intrinsically Safe Manual Call Point
Features
GB19880&GB/T3836.1&GB/T3836.4certified.
Explosion-proof type: Intrinsic safety.
Fully electronic encoding allows for on-site rewriting via an encoder.
The manual alarm can directly control external devices.
Resettable press button.
| Operating Voltage | Loop 24V |
| Operating Current | Quiescent current: |
| Explosion-proof sign | Ex ib IIC T6 Gb |
| Dimension | 90×90×43mm (WxHxD) (with base) |
| Operating Environment | -10~55°C; Rh≤95% (40oC±2°C,no condensation) |
SJ-AQS-O1E/Bus-lsolatedBarrier
Features
The design employsan isolated safety barrer solution for connecting intrinsically safe products that need to be connect to the loop. Up to 32 intrinsically safe coding terminals can be connected.
| Specifications | |
| Operating Current | Loop:24V (15~36V); Power bus: DC 24V (DC 15~48V) |
| Operating Current | Loop: |
| Dimension | 132×35×89mm (WxHxD) (with base) |
| Operating Environment | -10~55℃; Rh≤95% (40C±2C,no condensation) |
CODER-F100E/Handheld encoder
5 10! !
Features
Easyto carryand operate. Ultra-low power consumption,address more than 50,0o0 points. ? With the function of adding one address automatically,it can continuously code the equipmentand improve theefficiency of project installation.
Specifications
| Operating Voltage | DC5V |
| Output Capacity | Constant output: 200mA; Pulse output: 500mA@50ms |
| Operating Environment | -20~60°C; Rh≤95% (40℃±2C,no condensation) |
FHH-SG01/FHH-SAP01/Waterproof Cover
D 1
Features
Optional installation.
The Sounder Strobe Cover prevents water molecules from passing through while allowing the transmission of sound.
There are knock-out cable entry holes on the top,bottom,and back sides to accommodate wiring from different directions.
| Specifications | |
| FHH-SG01 | SG-A92E |
| FHH-SAP01 | JS-A51E/JK-A52E/KZJ-A55E/KZJ-A76E/J-SAP-M-A62E/ GL-A59E/J-SAP-M-A63E/J-SAP-M-A62KE |
Weatherproof Sounder Beacon Base WPB-9092
Features
Protect sounder beacon from splash water. Deep base accessory lP43 rating. Compatible with SANJIANG sounder beacons A9092T,A9091T,C9091T.
| Specifications | |
| Protection Rating | IP43 |
| Material | Abs |
| Wiring Hole | Two konck out holesΦ20.6mm |
| Dimension | 124.6×104.6×57.2mm |
| Accessory | One standard M20x1.5mmwaterproof connector |
BOX-M6SE/ModuleCabinet
Features
Supported installations:6 input or input/output modules,24V relays,24-position terminal block.
Install Series A modules.
| Specifications | |
| Adaptation Product | KZJ-A76E/KZJ-A55E/JS-A51E/JK-A52E |
| Dimension | 262mm×329mm×68.6mm (W×H×D) |
06
LoRa WIRELESS FIREALARMSYSTEM
In thissolution,thesounderbeaconworksasarepeater.Thestand-alonedetectorsand MCPsareconnectedtothesounder beacon,to formalocalarea network(LAN).Maximumof3Odevicescanbe involved intheLANnetwork.
Operating frequency:444.4MHz-444.8MHz Customizable frequency:430MHz-510MHz Signal penetration:up to 5 floors
●Point to point information transmission distance:150m ●Supports a maximum 6-level repeater network topology ●Low power consumption,up to 5 years service life
JTY-GD-620L-VN/Wireless Heat Detector
Low power consumption (with voltage monitoring circuit) and strong interference resistance.
Supports temperature compensation and sensor fault detection ability.
With built-in buzzer, when the fire alarm, the buzzer alarm sound.
JTY-GD-630L-VN/Wireless Smoke Detector
Low power consuhmptionand strong interference resistance.
Patentdesignof smoke chamber with backward scatering principle,providing asuperior response threshold to minimize false alarms in practical use.
Witha tamperdetection feature that reportsa fault if the detector is removed.
Built-in buzzer indicates fire locally.
JTY-GD-66OL-VN/WirelessManual CallPoint
Low power consumption,and equipped with a battery voltage detection circuit.
With high reliability(The connector and the circuit boardare welded in contact; non-glass break,lever reusable).
Add silicone rubber sleeve on thealarm buttn,furtherimprove product reliabilityand moisture-proof anti-corrosion performance.
JTY-GD-692L-VN/Wireless Sounder Strobe
:Low power consumption and long life (witha DC12Vmain power adapter).
Ultra-brightLED sourceandhigh volume sound (adopts large sizepiezoelectricbuzzerand high eficiencydriving circuit.
Plug-and-play for installation with the structure design of upper and lower covers.
This solution is equipped with a control panel that uploads all system information to the cloud platformviaa 4G DTU module oruser information transmission device,and synchronizes it to the user's mobile phone in real time,achieving real-time early warning.
JB-QBL-610O/LoRa Wireless Fire Alarm Control Panel
Features
Equipped with one internal wireless repeater,and supports to add 50pcs
of external wireless repeaters to expand the system up to 2550 wireless nodes.
Wireless system is networkable,and supports networking of 254 panels (via Ethernet) or 60 panels (via CAN).
It is equipped with a printer and supports manual start/stop function of a module device, making it convenientfor on-site commissioning and testing.
With 4.3-inch tn color display to read and operate.
| Specifications | |
| System Voltage | Main: AC220V/50Hz (187V~242V); Backup: DC24V/BAT12V/5Ah*2 |
| Frequency Band | 470MHz~510MHz |
| Transmission Parameters | Power≤20dBm,maximum communicationdistance 1000m. |
| Dimension | 440×340×99mm (W×H×D) |
| Operating Environment | 0~40°℃C;Rh≤95% (40C±2C,no condensation) |