Heat Pump Catalogue
Stabale and reliable
Heat Pump
1 Heat Pump Lineup 02
2 EU Air to water Heat Pump 03
3 Air Cooled Modular Chiller 09
4 Commercial Heat Pump 13
5 Heat Pump Water Heater 16
6 Swimming Pool Heat Pump 21
| R32 Monobloc | |||||||
| Heating Capacity(kW) | 4 | 6 | 8 | 10 | 12 | 14 | 16 |
![]() | |||||||
| R32 Swimming Pool Heat Pump | ||||||||||
| Heating Capacity(kW) | 7 | 9 | 12 | 14 | 17 | 21 | 23 | 25 | 29 | 31 |
![]() | ||||||||||
| R410A Ultra-low Temperature Commercial Heat Pump | ||||
| Heating Capacity(kW) | 35 | 88 | 160 | 320 |
| On-Off | ||||
R410A Air Cooled Modular Chiller
| Capacity(kW) | 65 | 130 |
| DC Inverter | ![]() | ![]() |
| On-Off | ![]() | ![]() |
| R410A Heat Pump Water Heater | ||||
| Capacity(kW) | 11 | 21 | 38 | 41 |
| Stanrard Series | ![]() | ![]() | ||
| Capacity(kW) | 21 | 38 | 100 | 200 |
| Low Tmperature Series | ![]() | ![]() | ![]() | ![]() |
EU Air to water Heat Pump
Thermostat
Saving
Comfortable
Environment Friendly
Application of air to water heat pump
One Stop Solution——Space heating/cooling and domestic hot water in one system.
Heating in winter and cooling in summer.
Produce domestic hot water all year.
Wide range of solutions: floor heating, radiators and fan coils.
Create great comfort at home even at low outdoor temperatures.
Environmental friendly: using R32 refrigerant.
Concept of air to water heat pump application
This series of monobloc is using the R-32 refrigerant and reached the high efficiency with A+++. It is designed for heating and cooling applications in new and existing individual homes and small businesses.
The unit is compatible with low to medium temperature emitters: underfloor heating, fan coil units,
High efficiency to match the EU standard, saving the electrical cost (Lab test data) Nominal conditions
High efficiency
High efficiency
• DC inverter rotary compressor High pressure ratio up to 13 Good performance in low ambient environment
• DC motor DC brushless fan motor Higher efficiency, lower noise
• Refrigerant cooling Keep PCB /FAN /refrigerant system working efficient Save space & excellent air path design
High efficiency BPHE
Good heat exchanger performance between water and refrigerant
Efficient for both heating and cooling
Small footprint & excellent air path design
Withstand high temperatures and high pressures
• Electrical expansion valve Precise control and regulation of refrigerant flow 0-480 pulses
• Inverter water pump High efficiency inverter water pump With high water pressure head up to 9m
Better Reliability
Refrigerant Cooling solution
• Good performance with enhanced refrigerant cooling solution
• Intelligent refrigerant control technology to protect PCB
• Quick action speed to make the main PCB working at suitable temperature rànge
• High reliability
Compared to the air- cooling system
• Space saving compact electrical box contributes to easy maintenance
• More efficient and timely Refrigerant cooling solution can cool the IPM directly with better efficient which is good to compressor control and system reliability
Low ambient performance
Operating range
o Widely operation range to prodive the hot water in whole year.
o Low ambient operation perfromance to keep the heat supply in winder.
■Our Products adapt easily to residential and light commercial applications.
From -30°C to 43°C external temperatures for heating/DHW
R-32 environmental refrigerant
AW3535
CAPACITY
4 kW – 16 kW heating
4 kW – 14 kW cooling
▪REFRIGERANT
R32 with GWP = 675
APPLICATIONS Residential and Light commercial
Extremely silent
Night mode logic Intro.
• Reduce 3 dB(A) noise emitted by the heat pump during the night
• Available by setting from controller
• Silent mode minimun sound power level 54 dB(A)
| Nightmode | Function activate | 0-Inactivate;1-Activate |
| Starting time | The time of start night mode(00:00-23:59) | |
| Exiting time | The time of exit night mode (00:00-23:59) |
Control diversity
O Window design, easy to operate & view Mode control, temperature setting, heating mode, cooling mode, DHW mode Weekly timer function Electric heater
O Forced defrosting
O Sterilization
O Anti-freezing protection
Application of WUI:
① Power supply: Take power supply from IDU board (12V power supply);
② Working temperature range: -30℃\~50℃;
③ Working humidity range: RH10%\~95%
Specifications
EU Air to Water Heat Pump
| Model | EU-HEC04-BPN4-D01(E1) | EU-HEC06-BPN4-D01(E1) | EU-HEC08-BPN4-D01(E1) | EU-HEC10-BPN4-D01(E1) | EU-HEC12-BPN4-EA01(E1) | EU-HEC14-BPN4-EA01(E1) | EU-HEC16-BPN4-EA01(E1) | ||
| Heatingperformances | A+7°C; W30/35℃ | ||||||||
| Heating capacity | kW | 4.00 | 6.00 | 8.00 | 10.00 | 12.00 | 14.00 | 16.00 | |
| COP | 4.80 | 4.60 | 4.50 | 4.90 | 4.80 | 4.70 | 4.65 | ||
| A+2°C; W30/35°℃ | |||||||||
| Heating capacity | kW | 4.00 | 6.00 | 8.00 | 10.00 | 11.00 | 12.00 | 13.00 | |
| COP | 3.50 | 3.40 | 3.35 | 3.50 | 3.45 | 3.40 | 3.30 | ||
| A-7°C; W30/35℃ | |||||||||
| Heating capacity | kW | 4.00 | 6.00 | 7.50 | 10.00 | 11.00 | 12.00 | 13.00 | |
| COP | 3.00 | 2.90 | 2.75 | 3.00 | 2.90 | 2.80 | 2.70 | ||
| A+7°C: W40/45℃ | |||||||||
| Heating capacity | kW | 4.00 | 6.00 | 8.00 | 10.00 | 12.00 | 14.00 | 16.00 | |
| COP | 3.60 | 3.50 | 3.45 | 3.50 | 3.55 | 3.50 | 3.50 | ||
| A+7℃; W47/55℃ | |||||||||
| Heating capacity | kW | 4.00 | 6.00 | 7.00 | 10.00 | 11.00 | 12.00 | 13.00 | |
| COP | 2.90 | 2.90 | 2.80 | 2.90 | 2.85 | 2.75 | 2.70 | ||
| A+2°C; W47/55°℃ | |||||||||
| Heating capacity | kW | 4.00 | 6.00 | 7.00 | 9.50 | 11.00 | 12.00 | 13.00 | |
| COP | 2.45 | 2.40 | 2.30 | 2.50 | 2.45 | 2.40 | 2.30 | ||
| A-7°C; W47/55℃ | |||||||||
| Heating capacity | kW | 3.50 | 5.00 | 7.00 | 9.50 | 10.00 | 11.00 | 11.50 | |
| COP | 2.05 | 2.00 | 2.00 | 2.10 | 2.05 | 2.05 | 2.00 | ||
| A+7°C; W35°C (ErP-average) | |||||||||
| Prated-NET | 4.00 | 6.00 | 7.00 | 10.00 | 11.00 | 12.00 | 14.00 | ||
| SCOP-NET | 4.95 | 4.83 | 4.70 | 4.95 | 4.83 | 4.70 | 4.58 | ||
| ηs 30/35-NET | % | 195% | 190% | 185% | 195% | 190% | 185% | 180% | |
| Efficiency class 30/35 | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | A+++ | ||
| A+7C; W55°C (ErP-average) | |||||||||
| Prated-NET | 4.00 | 5.00 | 6.00 | 9.00 | 10.00 | 11.00 | 12.00 | ||
| SCOP-NET | 3.48 | 3.40 | 3.33 | 3.58 | 3.48 | 3.40 | 3.33 | ||
| ns 47/55-NET | % | 136% | 133% | 130% | 140% | 136% | 133% | 130% | |
| Efficiency class 47/55 | A++ | A++ | A++ | A++ | A++ | A++ | A++ | ||
| Coolingperformances | A+35°℃; W23/18℃ | ||||||||
| Cooling capacity | kW | 4.00 | 6.00 | 7.00 | 10.00 | 11.00 | 13.00 | 14.00 | |
| EER | 4.30 | 4.00 | 3.80 | 4.40 | 4.00 | 3.60 | 3.40 | ||
| SEER | 7.22 | 6.92 | 6.69 | 7.40 | 6.92 | 6.60 | 6.30 | ||
| ns 23/18 | 286% | 274% | 265% | 293% | 274% | 261% | 249% | ||
| A+35°℃; W12/7°℃ | 01 | ||||||||
| Cooling capacity | kW | 4.00 | 5.00 | 6.50 | 8.00 | 10.50 | 12.00 | 13.00 | |
| EER | KW | 3.20 | 3.00 | 2.60 | 3.30 | 3.00 | 2.70 | 2.50 | |
| SEER | 5.08 | 5.05 | 4.67 | 5.22 | 5.05 | 4.77 | 4.67 | ||
| ns 23/18 | 200% | 199% | 184% | 206% | 199% | 188% | 184% | ||
| Model | EU-HEC04-BPN4-D01(E1) | EU-HEC06-BPN4-D01(E1) | EU-HEC08-BPN4-D01(E1) | EU-HEC10-BPN4-D01(E1) | EU-HEC12-BPN4-EA01(E1) | EU-HEC14-BPN4-EA01(E1) | EU-HEC16-BPN4-EA01(E1) | |||
| Sound levels | Standard unit | |||||||||
| Sound power level (2) | dB(A) | 61 | 63 | 65 | 65 | 67 | 69 | 70 | ||
| Sound pressure level (3) | dB(A) | 51 | 51 | 53 | 53 | 54 | 56 | 58 | ||
| Dimensions | Length | mm | 1310 | 1310 | 1310 | 1394 | 1394 | 1394 | 1394 | |
| Width | mm | 390 | 390 | 390 | 399 | 399 | 399 | 399 | ||
| Height | mm | 930 | 930 | 930 | 1083 | 1083 | 1083 | 1083 | ||
| OperatingWeight (1) | Standard unit | kg | 120 | 120 | 120 | 150 | 152 | 152 | 155 | |
| Compressors | Compressor type | DC Twin-rotary | ||||||||
| Copressor qty | ||||||||||
| Refrigerant | type | R32 | ||||||||
| Charge (1) | kg | 1.5 | 1.5 | 1.5 | 1.6 | 2 | 2 | 2 | ||
| Condenser | Copper | Grooved copper tubes, | ||||||||
| Fin type | Hydrophilic aluminum foil | |||||||||
| Fans | Fan type | Axial type | ||||||||
| Fan quantity | 1 | 1 | 1 | 1 | ||||||
| Rated total air flow | m3/h | 3300 | 3300 | 3600 | 4200 | 5500 | 5500 | 5500 | ||
| Rated speed | rpm | 780 | 780 | 860 | 780 | 860 | 860 | 860 | ||
| Evaporator | Type | Brazed | plate heat exchanger | |||||||
| Water volume | L | 1.08 | 1.08 | 1.08 | 1.45 | 1.45 | 1.45 | 1.45 | ||
| Hydraulicmodule | Circulator, rel | ief valve, paddle flow swi | tch, expansion tank | |||||||
| Circulator | Cen | trifugal pump (variable speed) | ||||||||
| Expansion tank volume | L | 5 | 5 | 5 | 5 | 5 | 5 | 5 | ||
| Max. water-side operatingpressure with hydraulic module (4) | kPa | 90 | 90 | 90 | 90 | 90 | 90 | 90 | ||
| Waterconnections | Inlet diameter (MPT GAS) | inch | 1 | 1 | 1 | 1.25 | 1.25 | 1.25 | 1.25 | |
| Outlet diameter (MPT GAS) | inch | 1 | 1 | 1 | 1.25 | 1.25 | 1.25 | 1.25 | ||
| Operating limits | Operation limits in cooling | ℃ | -5~50 | -5~50 | -5~50 | -5~50 | -5~50 | -5~50 | -5~50 | |
| Operation limits in heating | ℃ | -25~35 | -25~35 | -25~35 | -25~35 | -25~35 | -25~35 | -25~35 | ||
| Operation limits in DHW | ℃ | -25~43 | -25~43 | -25~43 | -25~43 | -25~43 | -25~43 | -25~43 | ||
| Max LWT | ℃ | 63 | 63 | 63 | 63 | 63 | 63 | 63 | ||
| MAX LWT in DHW | ℃ | 60 | 60 | 60 | 60 | 60 | 60 | 60 | ||
| Max LWT @ -15C | ℃ | 55 | 55 | 55 | 55 | 55 | 55 | 55 | ||
(2) Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-2dB(A)). Measured in accordance with ISO 9614-1.
(3) Declared dualnumber noise emission values in accordance with EN12102-1 (with an associated uncertainty of+/-2dB(A)). For information, calculated from the sound power level Lw(A).
(4) Min. water-side operating pressure with variable speed hydraulic module is 40 kPa.
Air Cooled Modular Chiller
④
②
R410a DC inverter Series
Modular design
·2 basic models:65/130kW.
· Maximum 16 units can be combined as one system.
·Capacity range: 65\~2080kW
High efficiency
· Mitsubishi DC inverter compressor
· Optimally designed fan blade, large air volume and low noise.
· V-U shape heat exchanger, larger heat exchange area and higher heat transfer efficency.
High reliability
· Cycle duty function,to balance the opreating time of each module and the lifetime.
· Modular backup function.
· A variety of comprehensive protections.
High Comfort
· DC inverter technology with stepless regualtion, precise water temperature regulation.
· High precision EEV, temperature and pressure sensors.
· Smart defrosting technology, less fluctuation of water temperature.
Intelligent Control
·large screen wired controller, 1000m communication distance, single/group control.
· Data is automatically stored in black box for easy analysis and automatic diagnosis function.
·4G module is optional for remote control, running curve analysis and power monitoring.
Modular design
·2 basic models:65/130kW.
·Maximum 16 units can be combined as one system.
·Capacity range: 65\~2080kW.
High efficiency
·Well known brand scroll compressor.
· U Shape heat exchanger designed by CFD simulation.
· High efficiency shell and tube heat exchanger.
High reliability
· Compressor and module dual cycle duty function.
·Module backup function.
· A variety of comprehensive protections.
High Comfort
· High precision EEV, temperature and pressure sensors, precise adjustment of refrigerant temperature, pressure and water temperature.
· Smart defrosting and cycle defrosting technology technology, less fluctuation of water temperature.
System cycledefrostingfor 130kW model
System A operatting System B defrosting
Intelligent Control
·large screen wired controller, 1000m communication distance, single/group control.
· Data is automatically stored in black box for easy analysis and automatic diagnosis function.
·4G module is optional for remote control, running curve analysis and power monitoring.
Air Cooled Modular Chiller
| Model | CGRF-65SN1 | CGRF-130SN1 | CGRF-65BPSN1 | CGRF-100BPSN1 | CGRF-130BPSN1 | ||
| Pow er supply | 380-415V~, 3Ph, 50Hz | ||||||
| Cooling A35W7 | Capacity | kW | 65 | 130 | 65 | 100 | 130 |
| Pow er input | kW | 19.55 | 39.52 | 19.40 | 29.80 | 38.80 | |
| EER | 3.32 | 3.29 | 3.35 | 3.36 | 3.35 | ||
| Heating A7W45 | Capacity | kW | 72 | 143 | 72 | 110 | 140 |
| Pow er input | kW | 20.60 | 41.00 | 20.50 | 31.40 | 40.00 | |
| COP | 3.50 | 3.49 | 3.51 | 3.50 | 3.50 | ||
| IPLV(C) | 3.90 | 3.90 | 4.49 | 4.49 | 4.49 | ||
| Maximun pow er input | kW | 30.10 | 60.20 | 30.10 | 46.50 | 60.20 | |
| Maximum running current | A | 55.0 | 110.0 | 55.0 | 85.0 | 110.0 | |
| Compressor | Type | EVI Scroll Compressor | DC Inverter Rotary | ||||
| Quantity | 1 | 2 | 2 | 4 | 4 | ||
| Fan | Type | AC motor / Axial | |||||
| Quantity | 2 | 2 | 2 | 2 | 2 | ||
| Air-sideheat-exchanger | Hydrophilic aluminum & Inner groove copper tube | ||||||
| Water-sideheat-exchanger | Type | Shell and tube | Plate heat exchanger | ||||
| Water flow rate | /h | 11.2 | 22.4 | 11.2 | 17.2 | 22.4 | |
| Water resistance | kPa | 48 | 60 | 40 | 50 | 60 | |
| Design pressure | Pa | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | |
| Inlet/outlet w ater pipes size | DN65 | DN65 | DN50 | DN65 | DN65 | ||
| Refrigerant | Type | R410a | |||||
| Factory charging | kg | 8.5 | 17.0 | 9.5 | 19.0 | 19.0 | |
| Throttling type | Electronic expansion valve | ||||||
| Sound pow er level | dB(A) | 63 | 68 | 65 | 68 | 68 | |
| Running ambienttemperarure range | Heating | °C | -15~24 | ||||
| Cooling | °C | 15~48 | |||||
| Outlet w atertemperature range | Heating | °C | 30~50 | ||||
| Cooling | °C | 5~17 | |||||
| Dimensions(W×D×H) | Unit | mm | 1995*960*1890 | 2200*1120*2370 | 1110*1170*2000 | 2305*1170*2000 | 2305*1170*2000 |
| Packing | mm | 2085*980*2030 | 2300*1180*2500 | 1150*1210*2120 | 2345*1210*2120 | 2345*1210*2120 | |
| Weight | Net | kg | 530 | 590 | 400 | 800 | 800 |
| Operating | kg | 573 | 952 | 420 | 830 | 830 | |
| Notes:The specification may be changed for product improvement, please refer to the nameplate of product. | |||||||
Commercial Heat Pump
Ultra low temperature R410a series
Product overview
EVI technology and enhanced heating capacity
· Fully enclosed scroll EVI compressor, which can operate safely and stably at -35℃
· Strong heating capacity even in cold climate, maximum outlet water temperature is as high as 60C.
· Wierd controller for single unit and group control
. 4G module is optional for remote control and monitoring.
· Can be connected to BMS system for linkage control with ventilation and fire alarm system.
Specifications
Ultra low temperature R410a
| Model | CGDCH-E35SN1 | CGDCH-E88SN1 | CGDCH-E160SN1 | CGDCH-E320SN1 | ||
| Pow er supply | 380-415V~, 3Ph, 50Hz | |||||
| Heating A7W45 | Capacity | kW | 35 | 88 | 155 | 310 |
| Pow er input | kW | 10.87 | 22.85 | 41.46 | 84.32 | |
| COP | 3.22 | 3.85 | 3.74 | 3.68 | ||
| Heating A-12W55 | Capacity | kW | 23 | 52 | 103 | 206 |
| Pow er input | kW | 12.09 | 25.80 | 51.41 | 104.02 | |
| COP | 1.90 | 2.02 | 2.00 | 1.98 | ||
| Heating A-20W55 | Capacity | kW | 20.00 | 42.00 | 79.00 | 158.00 |
| Pow er input | kW | 11.34 | 25.60 | 47.95 | 97.10 | |
| COP | 1.76 | 1.64 | 1.65 | 1.63 | ||
| Cooling A35W7 | Capacity | kW | 24.00 | 71.00 | 138.00 | 276.00 |
| Pow er input | kW | 9.24 | 20.95 | 42.48 | 85.26 | |
| EER | 2.60 | 3.39 | 3.25 | 3.24 | ||
| Maximun pow er input | kW | 15.50 | 33.70 | 67.50 | 135.00 | |
| Maximum running current | A | 27.0 | 60.0 | 120.3 | 240.6 | |
| Compressor | Type | EVI Scroll Compressor | ||||
| Quantity | 1 | 1 | 2 | 4 | ||
| Fan | Type | AC motor / Axial | ||||
| Quantity | 2 | 2 | 2 | 4 | ||
| Air-side | Hydrophilic aluminum & Inner groove copper tube | |||||
| Water-sideheat-exchanger | Type | Double-pipe | Shell and tube | |||
| Water flow rate | m³/h | 6.02 | 12.2 | 23.8 | 47.6 | |
| Water resistance | kPa | 62 | 45 | 65 | 80 | |
| Design pressure | Pa | 1.6 | 1.0 | 1.0 | 1.0 | |
| Inlet/outlet w ater pipes size | DN32 | DN65 | DN65 | DN100 | ||
| Refrigerant | Type | R410a | ||||
| Factory charging | kg | 5.2 | 12.0 | 26.0 | 52.0 | |
| Throttling type | Electronic expansion valve | |||||
| Sound pow er level | dB(A) | 62 | 67 | 69 | 71 | |
| Running ambienttemperarure range | Heating | °℃ | -35~30 | |||
| Cooling | °C | 15~48 | ||||
| Dimensions(W×D×H) | Unit | mm | 1120*400*1560 | 1995*960*1890 | 2200*1120*2370 | 2700*2200*2370 |
| Packing | mm | 1250*472*1570 | 2050*980*2030 | 2300*1180*2500 | 2900*2300*2500 | |
| Weight | Net | kg | 175 | 550 | 970 | 1890 |
| Packing | kg | 186 | 570 | 985 | 1920 | |
| for prod | vet imnrevemont, plee | ce rofor te the name | ||||
Heat Pump Water Heater
Hot Spring Series - For mild region
Modular design
·3 basic models: 11/21/38kW.
·Maximum 16 units can be combined as one system.
·Capacity range: 11\~608kW.
Product overview
Side discharge structure, compact size and space-saving.
High precision EEV, 500-steps regulation and rapid response.
Optimally designed fan blade, large air flow volume and low noise.
Refrigerant cooling PCB, reliable and long life.
Well-known brand DC inverter compressor,
Double pipe heat exchanger, high efficiency, low water pressure drop.
Hot water solution
Tap water inlet
Other features
· Smart defrosting and cycle defrosting, less fluctuation of water temperature.
·3-steps of automatical anti-freezing function.
·Wired controller and remote control.
·Refrigerant temperature / pressure, voltage, over-current, water flow, water shortage protection.
Hot Flame Series - For cold region
Modular design
·4 basic models: 21/38/100/200kW.
·Maximum 16 units can be combined as one system.
·Capacity range: 21\~3200kW.
(38KW)
EVI technology, stable operatiing at -35℃
·Enhanced vapor injection (EVl) technology, well known brand compressor.
·Strong heating capacity even in cold climate.
Other features
· Double pipe heat exchanger, high efficiency, low water pressure drop and good anti-freeze performance.
·Smart defrosting and cycle defrosting, less fluctuation of water temperature.
·3-steps of automatical anti-freezing function.
·Refrigerant temperature / pressure, voltage, over-current,
water flow, water shortage protection.
·Wired controller and remote control system.
| Model | CGRH-E11BPCN1 | CGRH-E21BPCN1 | CGRH-E21BPSCN1 | CGRH-E38BPSCN1 | ||
| Pow er supply | 220V~50Hz | 380V,3N~50Hz | ||||
| Heating capacity | kW | 11.0 | 21.0 | 21.0 | 38.0 | |
| Pow er input | kW | 2.53 | 4.87 | 4.87 | 8.72 | |
| COP | 4.35 | 4.31 | 4.31 | 4.36 | ||
| Maximum pow er input | kW | 3.86 | 7.50 | 7.50 | 13.50 | |
| Maximum current | A | 19 | 35 | 13 | 23 | |
| Hot Water yield | m3/h | 0.236 | 0.451 | 0.451 | 0.817 | |
| Circulating w ater flow | m3/h | 1.89 | 3.61 | 3.61 | 6.54 | |
| Water resistance | kPa | 32 | 58 | 58 | 65 | |
| Maximum w ater pressure | MPa | 1.60 | ||||
| Water side heat exchanger | Double pipe heat exchanger | |||||
| Operation temperature range | °℃ | -15~46 | ||||
| Setting w ater temperature range | °C | 20~55 | ||||
| Refrigerant pressure | MPa | 3.00 | ||||
| Refrigerant | Type | R410a | ||||
| Charged volume | g | 970 | 1600 | 1600 | 3000 | |
| Compressor | Type | DC Inverter, rotary | ||||
| Quantity | 1 | 1 | 1 | 1 | ||
| Fan motor | Type | AC motor, axial | ||||
| Quantity | 1 | 1 | 2 | 2 | ||
| Sound pressure level | dB(A) | 49~58 | 52~60 | 52~60 | 54~63 | |
| Water pipe connection | mm | DN25 | DN25 | DN25 | DN32 | |
| Maximum combined unit | 16 | |||||
| Controller | Wired controller | |||||
| Dimension(L×W×H) | Unit | mm | 1040*410*850 | 1040*410*850 | 1040*410*850 | 1120*400*1560 |
| Packing | mm | 1145*550*890 | 1145*550*890 | 1145*550*890 | 1270*550*1720 | |
| Net Weight | kg | 79 | 95 | 96 | 157 | |
Capacities are based on the follow ing conditions:
Inlet/outlet temperature 15°C/55C; Outdoor temperature 20℃ DB / 15CWB;
The specification may be changed for product improvement, please refer to the nameplate of product.
| Model | CGDH-E21BPSCN1 | CGDH-E38BPSCN1 | CGDH-E100SN1 | CGDH-E200SN1 | ||
| Pow er supply | 380V, 3N~50Hz | |||||
| Rated Heating | Capacity | kW | 21 | 38 | 98 | 195 |
| Pow er input | kW | 4.73 | 8.32 | 22.46 | 45.06 | |
| COP | 4.44 | 4.57 | 4.36 | 4.33 | ||
| Nominal Heating | Capacity | kW | 17.5 | 31 | 77 | 152 |
| Pow er input | kW | 4.89 | 8.03 | 20.86 | 41.22 | |
| COP | 3.58 | 3.86 | 3.69 | 3.69 | ||
| Maximum pow er input | kW | 8.28 | 14.92 | 33.70 | 71.40 | |
| Maximum current | A | 14 | 25 | 60 | 120 | |
| Rated hot Water yield | m3/h | 0.451 | 0.817 | 2.107 | 4.192 | |
| Nominal hot Water yield | m3/h | 0.327 | 0.580 | 1.439 | 2.841 | |
| Circulating w ater flow | m3/h | 3.61 | 5.33 | 13.24 | 26.14 | |
| Water resistance | kPa | 55 | 50 | 75 | 85 | |
| Refrigerant pressure (Max. / Min.) | MPa | 1.60 | ||||
| Water side heat exchanger | Double pipe heat exchanger | |||||
| Operation temperature range | °℃ | -35~46 | ||||
| Setting w ater temperature range | °℃ | 20~55 | ||||
| Refrigerant | Type | R410a | ||||
| Charged volume | g | 1750 | 3300 | 10500 | 19000 | |
| Compressor | Type | DC Inverter, rotary | Fixed speed, scroll | |||
| Quantity | 1 | 1 | 1 | 1 | ||
| Fan motor | Type | AC motor, axial | ||||
| Quantity | 1 | 1 | 1 | 2 | ||
| Sound pressure level | dB(A) | 52~60 | 54~63 | 68.00 | 70.00 | |
| Water pipe connection | mm | DN25 | DN32 | DN65 | DN65 | |
| Maximum combined unit | 16 | |||||
| Controller | Wired controller | |||||
| Dimension(L×W×H) | Unit | mm | 1040*410*850 | 1120*400*1560 | 1995*960*1890 | 2200*1120*2370 |
| Packing | mm | 1145*550*890 | 1270*550*1720 | 2085*980*2030 | 2300*1180*2500 | |
| Net Weight | kg | 115 | 190 | 600 | 1010 | |
| Notes:Capacities are based on the follow ing conditions:Inlet/outlet temperature 15C/55C; Outdoor temperature 20℃ DB / 15CWB;The specification may be changed for product improvement, please refer to the nameplate of product. | ||||||
Swimming Pool Heat Pump
Refrigerant
Tech
WiFi
Feature
Feature
R32
Inverter
EVI technology conquers all climates
The EVI compressor allows the gas to be re-injected into the compressor in an optimal way, achieving higher temperatures in low ambient. The main advantages of this technology are:
1. Improvement of performance and output water temperature.
2. Improvement of the seasonal performance.
3. Higher utilization of the heating capacity of the system.
The EVI Inverter heat pump can reach temperatures of over 6 0 ^ { \circ } \mathsf { C } with no additional electrical support, even at the most extreme temperatures.
Inverter technology
Stable water temperature
Precise control of the compressor speed ensures that the water temperature remains within a small fluctuation around the set temperature.
Quick start-up
Inverter system outputs power according to the energy demand, it starts quickly by adjusting motor rotary frequency, and reaches a comfortable state in a short time.
Less frequent start/stop
The ability to vary compressor speed means fewer start/stop cycles for the compressor, extending compressor life.
All-season fun
Unique EVI technology by means of the Flash Tank system allowingto offer the best performances even in the most unfavourable conditions from ambient - 2 5 ^ { \circ } C to 4 3 ^ { \circ } C making it fit for all-year-round swim.
High efficiency
Specially developed with the most cutting-edge technology and modern design to meet stringent requirements for effciency, EVI inverter heat pump is featured with top energy rating COP up to 15. The unit is currently most energy efficient and can greatly reduce energy bills for customers.
Quiet operation
Extremely quiet operation, compressor and fan work at low speed when maintaining the temperature, cut the noise level to around 38 dB(A) at midnight.
| Model | ZOWE-07HI | ZOWE-09HI | ZOWE-12HI | ZOWE-14HI | ZOWE-17HI | |
| Condintion 1: (A26℃, RH70% / W26℃/28℃) | Heating capacity, kW | 1.63 - 7.25 | 1.98 - 9.25 | 2.72 - 12.2 | 3.41 - 14.33 | 4.33 - 17.45 |
| Power input, kW | 0.14 - 1.17 | 0.15 - 1.27 | 0.18 - 1.97 | 0.22 - 2.33 | 0.30 - 2.87 | |
| Current, A | 0.6 - 5.2 | 0.7 - 5.6 | 0.82 - 8.95 | 1.0 - 10.2 | 1.3 - 12.6 | |
| COP | 11.64 - 6.20 | 13.20 - 7.28 | 15.1 - 6.47 | 15.5 - 6.15 | 14.43 - 6.08 | |
| Condintion 2: (A15℃, RH70% / W26℃/28℃) | Heating capacity, kW | 1.50 - 5.87 | 1.84 - 7.71 | 2.51 - 10.35 | 3.28 - 12.25 | 4.01 - 14.92 |
| Power input, kW | 0.18 - 1.10 | 0.23 - 1.36 | 0.27 - 1.85 | 0.39 - 2.27 | 0.49 - 2.68 | |
| COP | 8.33 - 5.34 | 8.00 - 5.67 | 9.30 - 6.10 | 8.41 - 5.40 | 8.18 - 5.57 | |
| Condintion 3: (A7℃, RH70% / W26℃/28℃) | Heating capacity, kW | 1.31 - 5.10 | 1.60 - 6.71 | 2.18 - 9.32 | 2.85 - 10.66 | 3.49 - 12.98 |
| Power input, kW | 0.17 - 1.01 | 0.21 - 1.24 | 0.25 - 1.35 | 0.36 - 2.08 | 0.45 - 2.45 | |
| COP | 7.91 - 5.07 | 7.60 - 5.39 | 8.83 - 7.80 | 7.98 - 5.13 | 7.77 - 5.29 | |
| Condintion 4: (A35℃,W28℃/26℃) | Cooling capacity, kW | 1.70 - 3.65 | 1.80 - 4.60 | 2.45 - 7.10 | 3.20 - 7.90 | 3.90 - 9.80 |
| Power input, kW | 0.22 - 0.81 | 0.28 - 1.20 | 0.33 - 1.71 | 0.43 - 1.80 | 0.51 - 2.42 | |
| EER | 7.73 - 4.51 | 6.43 - 3.83 | 7.42 - 4.47 | 7.44 - 4.39 | 7.65 - 4.05 | |
| Power supply V~/Ph/Hz | 220-240/1/50 | |||||
| Water flow, m³/h | 3 - 4 | 3 - 5 | 4 - 6 | 5- 7 | 6 - 8 | |
| Running temperature range | -25℃~43℃ | |||||
| Advised pool size (Isothermal cover @ night), m³ | 15~30 | 20~40 | 25~50 | 30~60 | 35~70 | |
| R32 refrigerant, kG | 0.8 | 0.8 | 0.94 | 1.3 | 1.5 | |
| CO2 equivalent, T | 0.5 | 0.5 | 0.6 | 0.9 | 1.0 | |
| Water side heat-exchanger | Titanium heat-exchanger with PVC casing | |||||
| Sound pressure level at 1m, dB(A) | 44 | 47 | 47 | 48 | ||
| Controller | LCD, built-in Wifi module | 50 | ||||
| Unit/Packing dimension (L×D×H), mm | 865×400×665 / 985×403×820 | 990×425×670/1120×452x845 | ||||
| Net/Gross weight, kG | 41 / 53 | 41 / 53 | 53 / 70 | 53 / 70 | 57 / 74 | |
| Loading quantity 40HQ | 180 | 180 | 142 | 142 | 142 | |
| Model | ZOWE-21HI | ZOWE-23HI | ZOWE-25HI | ZOWE-29HI | ZOWE-31HI | |
| Condintion 1: (A26℃, RH70% / W26℃/28℃) | Heating capacity, kW | 4.80- 21.15 | 5.71 - 23.00 | 6.20 - 25.15 | 6.60 - 29.00 | 7.70 - 31.80 |
| Power input, kW | 0.33 - 3.31 | 0.38 - 3.78 | 0.43 - 4.08 | 0.45 - 4.73 | 0.54 - 5.33 | |
| Current, A | 1.4 - 14.5 | 1.7 - 16.6 | 1.9 - 17.9 | 2.0 - 20.8 | 2.4 - 23.4 | |
| COP | 14.55 - 6.39 | 15.03 - 6.08 | 14.42 - 6.16 | 14.67 - 6.13 | 14.26 - 5.97 | |
| Condintion 2: (A15℃, RH70% / W26℃/28℃) | Heating capacity, kW | 4.30 - 17.00 | 5.33 - 18.55 | 5.92 - 21.26 | 6.24 - 24.35 | 6.86 - 27.00 |
| Power input, kW | 0.50 - 2.88 | 0.64 - 3.68 | 0.69 - 3.80 | 0.77 - 4.38 | 0.91 - 4.95 | |
| COP | 8.60 - 5.90 | 8.33 - 5.04 | 8.58 - 5.59 | 8.10 - 5.56 | 7.54 - 5.45 | |
| Condintion 3: (A7℃, RH70% / W26℃/28℃) | Heating capacity, kW | 3.74 - 14.79 | 4.64 - 16.14 | 5.15 - 18.49 | 5.42 - 21.18 | 5.95 - 23.45 |
| Power input, kW | 0.46 - 2.64 | 0.59 - 3.38 | 0.63 - 3.48 | 0.71 - 4.01 | 0.83 - 4.54 | |
| COP | 8.17 - 5.60 | 7.91 - 4.78 | 8.15 - 5.31 | 7.69 - 5.28 | 7.16 - 5.17 | |
| Condintion 4: (A35℃,W28℃/26℃) | Cooling capacity, kW | 4.30 - 11.55 | 5.30 - 13.10 | 5.80 - 14.00 | 6.20 - 16.20 | 7.30 - 17.50 |
| Power input, kW | 0.56 - 2.61 | 0.73 - 3.34 | 0.80 - 3.38 | 0.82 - 3.75 | 0.99 - 4.16 | |
| EER | 7.68 - 4.43 | 7.26 - 3.92 | 7.25 - 4.14 | 7.56 - 4.32 | 7.37 - 4.21 | |
| Power supply V~/Ph/Hz | 220-240/1/50 | |||||
| Water flow, m³/h | 7- 9 | 8 - 10 | 8 - 11 | 9 - 12 | 12 - 15 | |
| Running temperature range | -25℃~43℃ | |||||
| Advised pool size (Isothermal cover @ night), m³ | 40~80 | 60~100 | 65~110 | 70~130 | 80~150 | |
| R32 refrigerant, kG | 2.1 | 2.1 | 2.1 | 2.7 | 3 | |
| CO2 equivalent, T | 1.4 | 1.4 | 1.4 | 1.8 | 2.0 | |
| Water side heat-exchanger | Titanium heat-exchanger with PVC casing | |||||
| Sound pressure level at 1m, dB(A) | ||||||
| Controller | 51 | 53 | 54 LCD, built-in Wifi module | 57 | 60 | |
| Unit/Packing dimension (L×D×H), mm | 1085×480×725/ 1180×500×880 | 1216×451×822 / 1351×515×957 | ||||
| 77 / 95 | 77 / 95 | 77 / 95 | 90 / 105 | 98 / 113 | ||
| Net/Gross weight, kG Loading quantity 40HQ | 80 | 80 | 80 | 66 | 66 | |
Pego series Inverter swimming pool heat pump
| Model | ZOPego-70HI | ZOPego-90HI | ZOPego-125HI | ZOPego-170HI | |
| Condintion 1: (A26℃, RH70% / W26℃/28℃) | Heating capacity, kW | 1.5~7.21 | 1.84~8.82 | 3.23~12.60 | 4.09~16.53 |
| Power input, kW | 0.12~1.22 | 0.14~1.58 | 0.25~2.45 | 0.31~3.06 | |
| COP | 13.55~5.65 | 13.27~5.63 | 13.16~5.54 | 13.05~5.4 | |
| Heating capacity, kW Condintion 2: (A15℃, RH70% / | 1.2~4.72 | 1.55~6.43 | 2.72~10.26 | 3.32~12.44 | |
| W26℃/28℃) | Power input, kW | 0.17~1.06 | 0.22~1.46 | 0.40~2.29 | 0.50~2.83 |
| COP | 4.50~7.21 | 4.45~7.12 | 4.41~6.84 | 4.37~6.70 | |
| Cooling capacity, kW | 1.6~3.6 | 1.75~4.46 | 3.04~7.48 | 3.71~9.12 | |
| Condintion 3: (A35℃,W28℃/26℃) Power supply | Power input, kW | 0.24~0.88 | 0.26~1.10 | 0.46~1.88 | 0.56~2.39 |
| EER | 4.08~6.73 | 4.05~6.78 | 3.97~6.68 | 3.82~6.66 | |
| V~/Ph/Hz 230/1/50 | |||||
| Water flow, m³/h Running temperature range | 2~4 3~5 5~7 | ||||
| -15℃~43℃ | |||||
| Advised pool size (isothermal cover @ night), m³ | 15~30 | 20~40 | 30~60 | 40~70 | |
| R32 refrigerant, kG CO2 equivalent, T | 0.3 | 0.4 | 0.55 | 0.6 | |
| Water side heat -exchanger | 0.2 | 0.3 | 0.4 | 0.4 | |
| Titanium heat-exchanger with PVC casing | |||||
| Sound pressure level at 1m, dB(A) Controller | 34~42.1 | 35.1~43.2 | 36.2~44.3 | 37.1~45.4 | |
| LCD, built-in Wifi module | |||||
| Unit/Packing dimension (L×D×H), mm | 710×333×515 / 810×360×645 | 862×365×660 / 950×385×785 | |||
| Unit/Packing weight, kG | 36 / 43 | 42 / 47 | 46 / 53 | ||
| Loading quantity 40HQ 261 | 33 / 38 | 261 | 144 | 144 | |
| Model | ZOPego-210HI | ZOPego-245HI | ZOPego-170HI-T | ZOPego-210HI-T | ZOPego-245HI-T | |
| Condintion 1: (A26℃,RH70% / W26℃/28℃) | Heating capacity, kW | 4.56~20.54 | 5.89~24.55 | 4.09~16.53 | 4.56~20.54 | 5.89~24.55 |
| Power input, kW | 0.35~3.52 | 0.45~4.40 | 0.31~3.06 | 0.35~3.52 | 0.45~4.40 | |
| COP | 13.10~5.72 | 13.07~5.58 | 13.05~5.4 | 13.10~5.72 | 13.07~5.58 | |
| Condintion 2: (A15℃,RH70% / W26℃/28℃) | Heating capacity, kW | 3.57~14.73 | 4.89~17.81 | 3.32~12.44 | 3.57~14.73 | 4.89~17.81 |
| Power input, kW | 0.53~3.27 | 0.71~3.98 | 0.50~2.83 | 0.53~3.27 | 0.71~3.98 | |
| COP | 6.77~4.59 | 6.88~4.42 | 6.70~4.37 | 6.77~4.59 | 6.88~4.42 | |
| Condintion 3: (A35℃,W28℃/26℃) | Cooling capacity, kW | 4.09~10.35 | 5.51~13.21 | 3.71~9.12 | 4.09~10.35 | 5.51~13.21 |
| Power input, kW | 0.61~2.63 | 0.85~3.53 | 0.56~2.39 | 0.61~2.63 | 0.85~3.53 | |
| EER | 6.73~3.94 | 6.50~3.74 | 6.66~3.82 | 6.73~3.94 | 6.50~3.74 | |
| Power supply | V~/Ph/Hz | 230/1/50 | 380/3/50 | |||
| Water flow, m³/h | 7~9 | 8~11 | 6~8 | 7~9 | 8~11 | |
| Running temperature range | ||||||
| Advised pool size (isothermal cover @ night), m³ | 60~90 | 80~110 | -15℃~43℃ 40~70 | 80~110 | ||
| R32 refrigerant, kG | 0.7 | 1.0 | 0.6 | 60~90 0.7 | 1.0 | |
| CO2 equivalent, T | 0.5 | 0.7 | 0.4 | 0.5 | 0.7 | |
| Water side heat-exchanger | Titanium heat-exchanger with PVC casing | |||||
| Sound pressure level at 1m, dB(A) | 41.7~50.9 | 37.1~45.4 | ||||
| Controller | 38.3~48.7 | LCD, built-in Wifi module | 38.3~48.7 | 41.7~50.9 | ||
| Unit/Packing dimension (L×D×H), mm | 990×395×660/ 1075×410×785 | 862×365×660 / 950×385×785 | 990×395×660/ 1075×410×785 | |||
| Unit/Packing weight, kG | 62 / 69 | 47 / 54 | 56 / 63 | |||
| Loading quantity 40HQ | 55 / 62 111 | 111 | 144 | 111 | 64 / 71 111 | |
· As the technical performance of products is constantly updated, the technical parameters, appearance and performance of the products mentioned in the advertising materials may be slightly different from the actual products, and shall be subject to the actual products.
·All documents have been carefully reviewed. If there are any printing errors and omissions, the information indicated on product nameplates shall prevail, and we will not bear the responsibility
FOSHAN CHIGO INTELLIGENT ENVIRONMENTAL EQUIPMENT CO, . LTD
Add: No.1, Shengli Industrial Park, Lishui Town, Nanhai District, Foshan City, Guangdong Province, P.R.china
URL:http://www.icongogroup.com/en/