Product Specification
Name: EMS- Smart Microgrid controller Model: HMQ-EMS-300 series
Thank you for choosing our products, please read this product manual carefully before use.
contents
1. Safety precautions ...
1.1. Universal safety ...
1.2. Grounding safety ....
1.3. Personal safety ....
1.4. Equipment safety ...
1.5. Personnel requirement ...
2. Production introduction .. 4
2.1. Production appearance . 4
2.2. Structure size . 7
2.3. Production order description .. 8
2.4. Specification parameter . 9
3. Interface and display distribution ... .12
3.1. Power interface ... 12
3.2. HDMI output interface ... . 14
3.3. Ethernet interface .. 15
3.4. Audio interface ... .. 15
3.5. USB interface .... . 16
3.6. Memory card socket ... . 16
3.7. WIFI antenna interface ... 17
3.8. 4G antenna interface . .17
3.9. KEY .... .18
3.10. Communication interface ... 18
3.11. DI input interface . .20
3.12. DO output interface ... .21
3.13. Indicator light .... . 24
4. Packing List . 25
5. Connect . 26
1. Safety precautions
Notice
• The EMS-smart microgrid controller has been designed and tested in accordance with safety regulations. However, as an electrical device, you must follow the safety instructions before performing any operation on the device. Improper operation may result in serious injury or property damage.
1.1. Universal safety
Danger
• The document content may be updated from time to time due to product version upgrade or other reasons. Without special agreement, the document content cannot replace the safety precautions on the product label. All descriptions in this document are for use only.
• Read this document carefully to understand the product and precautions before installing and using the device.
• The manufacturer shall not be liable for device damage or personal injury caused by failure to install, use, or configure the device in accordance with the requirements of this document or the corresponding user manual.
1.2. Grounding safety
| Danger |
| ·When installing a device that needs to be grounded, install the PGND cable first. ·Remove the PGND cable before removing the device. |
| Warn |
| · Ground the device nearby. · Device protection grounding You are advised to select the ground point of the chassis shell. |
1.3. Personal safety
| Danger |
• Use insulation tools and wear personal protective equipment to ensure personal safety. • When the device is short-circuited, do not touch the device and turn off the power immediately. • Before connecting the device, turn off all upper-level switches to ensure that the device is not powered on.
1.4. Equipment safety
| Danger |
| ·Before installing the device, ensure that the installation position is reliable and secure. |
| · It is strictly prohibited to install, use and operate outdoor equipment in severe weather such as |
| lightning,rain, snow, and strong winds above six degrees. |
| Cables (including but not limited to handling equipment, operating equipment and cables, |
| plugging and unplugging signals connected to outdoor ports, |
| Aerial work, outdoor installation, door opening, etc.). |
| · Do not installthe device in an environment that is exposed to direct sunlight, dust, smoke, |
| volatile gas, corrosive gas,infrared radiation, organic solvents, or excessive salt. |
| · Do not place the device near a heat source or fire source, such as fireworks,candles, heaters or |
| other heating equipment. Heat may cause damage to the device or cause fire. |
| · Do not install it under water pipes,air conditioning outlets,air vents,and cable Windows in the |
| equipment room. This prevents liquid from entering the device and causing device faults or short |
| circuits. |
| · Do not install the device in an environment with metal conductive dust and magnetic |
| conductive dust. |
| · Do not install the equipment in an area that is prone to breeding fungi, mold and other |
| microorganisms. |
| · Do not installthe device in areas interfered by strong vibrations, strong noise sources, and |
| strong electromagnetic fields. |
Warn
• Store the device in an appropriate temperature and humidity environment and in a clean, dry and well-ventilated area.
• When installing and maintaining the equipment, use the appropriate tools and follow the correct
operation procedures.
• When operating the device, strictly comply with local standards and safety regulations to ensure safety.
• After installing the device, remove empty packaging materials, such as cartons, foam, plastic, and cable ties, from the device area.
• Unauthorized removal or modification of the equipment may cause damage to the equipment, which is not covered by the warranty.
1.5. Personnel requirement
Notice • Equipment installation and maintenance personnel must receive rigorous training, fully understand the safety precautions of various products, and master the correct operation methods. • Only qualified professionals or trained personnel are allowed to install, operate, maintain, and replace the equipment. • Personnel other than those operating the equipment should stay away from the equipment to ensure safety.
2. Production introduction
EMS- Smart microgrid controller, designed for modern microgrid systems, with a variety of models and configuration options, designed to meet the energy management needs of different energy storage plants, can significantly improve the efficiency and stability of energy storage plants.
Core functions: data collection, reporting and analysis, monitoring and control, mode policy configuration, parameter configuration, device control management, alarm management, communication and other functions.
Features: It can adjust the charge and discharge strategy of the energy storage device in real time according to the demand and load of the power grid. By coordinating the relationship between supply and demand, the energy regulation function of the energy storage equipment is fully exerted, the utilization efficiency of energy is improved, and the stable operation of the energy storage power station is provided with a strong guarantee. It is closely integrated with the energy storage system, transformer and distribution system and auxiliary system, which can further improve the operation efficiency and stability of the energy storage power station.
2.1. Production appearance
P2-1 Front view with screen
P2-3 Dc power input without screen
Note: The appearance of the product is subject to the actual product, and this document is only for illustration.
2.2. Structure size
P2-6 Product assembly dimensions drawing
Note: Product size for reference, specific to the physical subject.
2.3. Production order description
This article mainly involves the following HMQ-EMS-300 order number:
The meanings of order fields and letters are as follows:
T2-1 Model + order number identification description
| No. | Implication | Note |
| 1 | name | HMQ-EMS-300:EMS-Smart microgrid controller |
| 2 | Hardware display label | N: none L: with TFT-LCD H: with HDMI-LCD |
| 3 | Power supply matching label | A: AC\DC D:DC |
| 4 | Extended feature label | 10: Support DO output 01: Support Dl output |
| 5 | Region label | CN: China EU:Europe NH: Japan KR: Korea AU:Australia GL: Globe |
2.4. Specification parameter
T2-2 Parameter list
| Specification Name | Parameter Description | NOTE |
| name | EMS-Smart microgrid controller | Production order: HMQ-EMS-300LD11CN(D、With screen) HMQ-EMS-300ND11CN(D、Without screen) HMQ-EMS-300LA11CN(A、With screen) |
| Industrial processor T113-i | HMQ-EMS-300NA11CN(A、Without screen) Dual-core ARM Cortex-A7 main processing core, main frequency 1.2GHz Xuantie C906 RISC-V(64bit), main frequency | |
| Industrial grade core board | 1008MHzHiFi4 DSP coprocessing core, main frequency 600MHz Connect to eMMC via SMHC (Host Controller) : | |
| Industrial eMMC Industrial DRAM | Capacity 64Gbit. Connect 1 DDR3L via a dedicated SDRAM bus: | |
| Ac/DC dual power | Capacity 4Gbit. Isolated AC input power (full load) : 178-265VAC Isolated AC input power (light load) : 120-265VAC | |
| Controller power | input interface (optional) Dc power input port | Maximum output power: 25W - 30W Isolated DC input power supply: 12V-24VDC |
| Maximum output power: 10W Isolated DC input power supply: 12V-24VDC | ||
| (Optional) Backup power supply | Maximum output power: 10W Full time: about 15 minutes Maximum instantaneous discharge current: 3A | |
| (Supercapacitor) 2 DC power output ports (Optional) | Discharge time: Theoretical value 1~1.5 minutes (optional) The first isolated external output power supply: 12VDC The second isolated external output power supply: | |
| Hardware parameter | size | 24VDC Maximum output power: 5W 271.6 × 134.9 × 50.2 mm (length × width × height) |
| Approximate weight | HMQ-EMS-300LD11CN: 1.32 kg HMQ-EMS-300ND11CN: 1.26 kg HMQ-EMS-300LA11CN: 1.45 kg |
| HMQ-EMS-300NA11CN: 1.39 kg | ||
| Power consumption | No more than 7W (without output load) | |
| Wireless network | 4G Full Netcom (Yuyuan EC200A) | Support full Netcom 4G LTE Cat.4 antenna (50Ω/SMA) |
| Ethernet | Line 2 Ethernet | 100 Mbit Ethernet, isolation protection RJ45 port |
| Gigabit Ethernet, isolation protection RJ45 port 4G antenna (50Ω/SMA) | ||
| 4G antenna interface Ethernet interface | SIM card slot | |
| WIFI antenna | Two-way isolation protects the RJ45 port | |
| interface Micro SD card | 1 WIFI antenna (50Ω/SMA), support STA, AP mode | |
| interface USB DRD | One MicroSD card interface card slot | |
| USB HOST | USB DRD,TYPE-C interface | |
| DEBUG | USB Host 2.0,USB-interface,ESD level 3 USB output for program debugging printing, using | |
| Audio interface | TYPE-C interface | |
| Hardware interface/peripheral | 1 3.5mm audio interface 1 channel standard HDMI 1.4, support 60Hz 1080p | |
| HDMI/TFT interface | 8-bit HDMI (HDMI-LCD interface and TFT-LCD interface are the same interface,and only one of the two interfaces can be selected at the same time.) | |
| RTC Temperature and | Onboard CR2032 battery | |
| humidity collection | Onboard temperature and humidity sensor | |
| Industrial RS485 serial port | 5 isolation high-speed RS485(communication baud rate up to 115200bps), power 3KV isolation, ESD3 level, EFT level 3 | |
| CAN bus | 2 isolation CAN, power 3KV isolation, ESD3 level, EFT level 3 | |
| DI、DO | (Optional Mode 1) 4-way optocoupler isolated wet contact input, 2-way relay isolated output (contact capacity: 5A 250VAC, 5A 30VDC) |
| (Optionalmoc -Wayoptocouplerisolatedwet contact input, 8-way relay isolated output (contact capacity: 5A 250VAC, 5A 30VDC) | ||
| Reset Key | reset | |
| Key | program | |
| LED Indicator light Electrostatic | power、run、warn、4G、CAN1、CAN2、485/1-5、 DO、DI | |
| discharge immunity test | GB/T 17626.2-2018/IEC 61000-4-2:2008,level 4 | |
| EMC indicator | Electrical fast transient pulse group immunity test | GB/T 17626.4-2018/IEC 61000-4-4:2012, level 4 |
| Surge immunity test Conductive | GB/T 17626.5-2019 /IEC 61000-4-5:2014, level 4 | |
| disturbance induced by RF field immunity test | GB/T17626.6-2017 /IEC 61000-4-6:2013,level 3 10V150kHz~80MHz | |
| Radiofrequency electromagnetic field radiation immunity test | GB/T 17626.3-2023 /IEC 61000-4-3:2020,level 3 10V/m 80MHz~1000MHz | |
| Radiation disturbance | GB/T 9254.1-2021, class A 40dB(uV/m) 30~230MHz 47dB(uV/m) 230~1000MHz | |
| Physical | Power frequency magnetic field | GB/T 17626.8-2017/IEC 61000-4-8:2001,level 3 |
| immunity test shockproof | IEC60068-2-27 | |
| vibration | GB/T 2423.10-2019/IEC60068-2-6:2007 | |
| characteristics | fall | IEC60068-2-32 |
| Temperature change test | GB/T 2423.22-2012/IEC60068-2-14:2009 | |
| MTBF Normal operating | > 100000 hour | |
| Other | temperature | -25℃ ~ +60C(except LCD) |
| Extreme operating temperature | -40℃ ~+85C(except LCD) |
| storage temperature | -40°℃~+85℃ | |
| operating humidity |
3. Interface and display distribution
P3-2 Appearance of the back-end interface
Note: The specific port style of the product will vary according to the selected configuration, and the specific object shall prevail.
3.1. Power interface
EMS- The power supply of the smart microgrid controller is optional. The power supply can be automatically switched between AC and direct power supplies or DC power supplies.
The interface terminals of the DC input power supply are 3-pin green sockets with 3 . 8 {mm } spacing. The sockets are equipped with screw holes and connected to the DC2.0 round core jack. The DC power input is equipped with a 24VDC sliding switch. For power cables, use 0.2 to 1 . 5 {mm } ^ { 2 } copper cables or 24AWG to 16AWG dual-core copper cables. The PGND cable uses 4 to 6 {mm } ^ { 2 } copper cables or 12AWG to 10AWG outdoor copper cables.
The interface terminals of the AC input power supply are 3-pin green sockets with a distance of 7 . 5 {mm } . The sockets are provided with screw holes. Power input installed 220VAC boat type switch. Power cables are connected to copper cables with a diameter of 2 . 5 {mm } ^ { 2 } . The PGND cable uses 4 to
6 {mm } ^ { 2 } copper cables or 12AWG to 10AWG outdoor copper cables.
G + 12-24MDC-IN OFFON12-24VDC-IN 24VDC开关面面面
P3-4 DC power interface
The following table describes the meanings of interface terminals:
| No. | Label | Function |
| 12-24VD-IN 3-core terminal pin 1 | G | system protection of ground |
| 12-24VD-IN 3-core terminal pin 2 | 24VGND | 12-24VDC power of ground |
| 12-24VD-IN 3-core terminal pin 3 | +24VDC | 12-24VDC Power supply positive |
| DC2.0 DC input terminal | 12-24VDC-IN | 12-24VDC DC power input Used to connect a power adapter |
| 24VDC Dip switch No. | OFF | 12-24VDC power off |
| ON | 12-24VDC power on | |
| Label | Function | |
| 220VAC Hull switch | I | 220VAC power on |
| 0 | 220VAC power off | |
| 220VAC-IN 3-core terminal pin 1 | L | firewire access terminal |
| 220VAC-IN 3-core terminal pin 2 | N | zero line access terminal |
| 220VAC-IN 3-core terminal pin 3 | G | system protection of ground |
The EMS- Smart microgrid controller provides two 5W power outputs, one 12VDC output, and the other 24VDC output, for 220VAC AC power supply if AC/DC power supply is automatically switched. The interface terminals are two 3-pin green sockets with 3 . 8 {mm } spacing. The sockets have screw holes. For power cables, use 0.2 to 1 . 5 {mm } ^ { 2 } copper cables or 24AWG to 16AWG dual-core copper cables.
| Appearance | No. | Label | Function | |
| 24N N 24VDC-OUT | 24VDC-OUT 3-core terminal pin 1 | +24VDC | 24VDC power supply positive | |
| 24VDC-OUT 3-core terminal pin 2 | 24VGND | 24VDC power of ground | ||
| 24VDC-OUT 3-core terminal pin 3 | NC | null | ||
| Appearance | No. | Label | ||
| 12VDC-OUT 石石 | 12VDC-OUT 3-core terminal pin 1 | +12VDC | 12VDC power supply positive | |
| 12VDC-OUT 3-core terminal pin 2 | 12VGND | 12VDC power of ground | ||
| 12VDC-OUT 3-core terminal pin 3 | NC | null | ||
3.2. HDMI output interface
The EMS- Smart Microgrid controller provides a standard HDMI interface that can be used to connect to the HDMI interface display. The HDMI interface is the same as the on-board TFT-LCD interface. Only one of the two interfaces can be selected at the same time.
| Appearance | Function | Note |
| HDMI | HDMI output interface | connect the HDMI port display |
3.3. Ethernet interface
The EMS- Smart Microgrid controller provides 2 Ethernet interfaces, and the physical interface uses an RJ45 with isolation LED indicator.Gigabit ETH is the core board native Ethernet port, and 100 megabit ETH is the PRG extended Ethernet port.
| Appearance | Function | Note |
| 千兆ETH | 10/100/1000M adaptive Gigabit Ethernet port | native Ethernet port on the core board |
| 百兆ETH | 10/100M adaptive Gigabit Ethernet port | extended Ethernet port |
| LEDNetwork indicator light | Function | Note |
| yellow | Active | blinking during network communication |
| green | LINK | the network connection is normally on |
3.4. Audio interface
The EMS- Smart Microgrid controller provides a 3 . 5 {mm } audio interface that can be used to connect the 3 . 5 {mm } GB audio plug.
| Appearance | Function | Note |
| 3.5mm audio interface | audio interface |
3.5. USB interface
EMS- Smart Microgrid controller provides three USB interfaces, the interface definition and functions are as follows:
| Appearance | Function | Note |
| USB-C | USBDRD | TYPE-C interface, core board native USB2.0 DRD interface, support high-speed mode (480Mbps), full speed mode (12Mbps), low speed mode (1.5Mbps) |
| USB-Test | DEBUG | TYPE-C interface,converted from UART interface to USB interface, used for program debugging printout |
| USB-A | USBHOST | USB - A interface, USB Host 2.0 for USB HUB chip CH334H extension |
3.6. Memory card socket
The EMS- Smart Microgrid controller provides a standard MicroSD card socket for system debugging, firmware writing, startup, and firmware upgrade. After the system is started, users can read and write the SD card.
T3-7 Memory card socket description
| Appearance | Function | Note |
| SD卡 | Micro SD card socket | The MicroSD card socket works in 4-bit cable |
| mode |
Note: The SD card is recommended to be an appropriate brand and the storage space is 64 GB or 128GB.
3.7. WIFI antenna interface
The EMS-Smart Microgrid Controller provides 1 WIFI antenna interface, with the onboard WIFI module being the industrial-grade B-LINK BL-R8188EU2, featuring an SMA interface with an input impedance of 5 0 \Omega , and an external 2.4G WIFI module antenna.
| Appearance | Function | Note |
| wifi | WIFI antenna interface | WIFI antenna (50 Ω /SMA), can be externally connected to a 2.4G WIFI module antenna, supports STA, AP mode |
3.8. 4G antenna interface
The EMS- Smart Microgrid controller provides a 4G antenna interface and is matched with a Micro SIM card holder. The 4G module expansion interface uses the onboard Mini PCIe slot, which can be compatible with a variety of LTE Cat1 and LTE Cat4 wireless communication modules such as Yiyuan, Youfang, and Guanghetong
| Appearance | Function | Note |
| 4G | 4G antenna interface | 4G antenna (50Ω/SMA), can be externally connected to a frequency range of 820MHz - 2700MHz 50Ω/SMA 4G antenna |
| sim卡 | Micro SIM card socket|card self - ejection form |
3.9. KEY
The EMS- smart microgrid controller provides two buttons. The Reset Key button is used to control system reset and power off of the PSU, and the other Upgrade Key button is used to upgrade programs.
| Appearance | Function | Note |
| KEY | Upgrade Key | used to upgrade |
| RST | Reset Key | used to reset and control the power board off on |
3.10.Communication interface
The EMS-Smart Microgrid Controller provides 2 isolated CAN interfaces and 5 isolated RS-485 interfaces.
The interface terminal uses a 14Pin, 3 . 8 {mm } pitch green socket with screw holes. Both CAN and RS485 use 2-core shielded copper twisted pair cables, with a wire diameter of 0.5 to 0.75 square millimeters and a twist pitch of 20 millimeters. Strip the outer insulation of the wire ends to 7 . 1 0 {mm } , and it is recommended to connect the shielding layer to the control terminal ground.
A1 B1 A2 B2 A3 B3 A4 B4 A5 B5 H1 L1 H2 L2 · 西西西西西西西商西酒
P3-5 Communication interface
The meanings of interface terminals are as follows:
| No. | Label | Function | Note |
| 14 core terminals pin 1 | A1 | 1 RS-485 A signal | High speed, isolation |
| 14 core terminals pin 2 | B1 | 1 RS-485 B signal | High speed, isolation |
| 14 core terminals pin 3 | A2 | 2 RS-485 A signal | High speed, isolation |
| 14 core terminals pin 4 | B2 | 2 RS-485 B signal | High speed, isolation |
| 14 core terminals pin 5 | A3 | 3 RS-485 A signal | High speed, isolation |
| 14 core terminals pin 6 | B3 | 3 RS-485 B signal | High speed, isolation |
| 14 core terminals pin 7 | A4 | 4 RS-485 A signal | High speed, isolation |
| 14 core terminals pin 8 | B4 | 4 RS-485 B signal | High speed, isolation |
| 14 core terminals pin 9 | A5 | 5 RS-485 A signal | High speed, isolation |
| 14 core terminals pin 10 | B5 | 5 RS-485 B signal | High speed, isolation |
| 14 core terminals pin 11 | H1 | 1 CAN H signal | Isolation |
| 14 core terminals pin 12 | L1 | 1 CAN L signal | Isolation |
| 14 core terminals pin 13 | H2 | 2 CAN H signal | Isolation |
| 14 core terminals pin 14 | L2 | 2 CAN L signal | Isolation |
3.11.DI input interface
EMS-Smart Microgrid Controller can provide 4 or 8 channels of optocoupler isolated DI input interfaces. The interface terminal is a 1-channel 4Pin, 3 . 8 {mm } pitch green socket with built-in screw holes. It is recommended to use 2-core copper shielded wire for DI, with a wire diameter of 0.5 to 0.75 square millimeters. DI's -DI_COM are all connected.
DI1DI2DI3DI4COM西西西西面
P3-6 DI Input interface (Optional 1)
DI1DI2DI3DI4COM西西西西西
DI5DI6DI7DI8C0M西西西西面
P3-7 DI Input interface (Optional 2)
The meanings of interface terminals are as follows:
| Label | Function | Note | Remark |
| +DI_1 | DI_1 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_2 | DI_2 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_3 | DI_3 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_4 | DI_4 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_5 | DI_5 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_6 | DI_6 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_7 | DI_7 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| +DI_8 | DI_8 signal input+ | Connect to the optocoupler LED+ pole | wet contact,+11~24V |
| COM | DI signal ground | Connect to the optocoupler LED- pole | wet contact negative pole |
P3-8 EMU-1000-10 Schematic diagram of circuit principle of wet contact DI
3.12.DO output interface
EMS-Smart Microgrid Controller can provide 2 or 8 channels of relay-isolated passive DO (Digital Output) interfaces, which can be used to control the power on/off of external devices or as switches, etc. When the number of DI (Digital Input) input interfaces is 4, the number of DO output interfaces is 2; if the number of DI input interfaces is selected as 8, then the number of DO output interfaces is also 8. The interface terminal is a 1-channel 6Pin, 3 . 8 {mm } pitch green socket with screw holes. It is recommended to use single-core multi-strand wire with a diameter of 0 . 5 { ~ } 1 square millimeters for DO, and each channel of DO is independent.
D01+ D01-D02+ D02-西西西面
DO1+DO1-DO2+DO2-DO3+DO3-DO4+DO4-D05+D05-DO6+D06-D07+DO7-DO8+D08西西西酒西西酒酒西面
P3-10 DO output interface(optional 2)
The meanings of interface terminals are as follows:
T3-13 DO output interface description
| Label | Function | Note |
| +DO_1 | DO_1 signal output positive pole | relay isolated,normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_1 | DO_1 signal output negative pole | |
| +DO_2 | DO_2 signal output positive pole | relay isolated,normally open contact, resistive load 3A/5A |
| -DO_2 | DO_2 signal output negative pole | 250VAC/30VDC |
| +DO_3 | DO_3 signal output positive pole | |
| -DO_3 | DO_3 signal output negative pole | 250VAC/30VDC |
| +DO_4 | DO_4 signal output positive pole | relay isolated, normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_4 | DO_4 signal output negative pole DO_5 signal output | |
| +DO_5 | positive pole DO_5 signal output | relay isolated, normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_5 | negative pole DO_6 signal output | |
| +DO_6 | positive pole DO_6 signal output | relay isolated,normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_6 | negative pole DO_7signal output | |
| +DO_7 | positive pole DO_7 signal output | relay isolated, normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_7 | negative pole | |
| +DO_8 | DO_8 signal output positive pole | relay isolated,normally open contact, resistive load 3A/5A 250VAC/30VDC |
| -DO_8 | DO_8 signal output negative pole |
3.13.Indicator light
The EMS-Smart Microgrid Controller offers an optional TFT-LCD touch display screen, and the LED indicator system covers the status display of power, operation, alarm, 4G, CAN1, CAN2, 485/1-5, DO, and DI. For the 300LD11CN model, there are two optional configurations for DO and DI: Configuration One includes DO/1-2 and DI/1-4 indicators; Configuration Two does not include these indicators. The design of these indicators aims to facilitate users in understanding the system's operational status under any circumstances.
P3-11 Indicator light
The meanings of indicators are as follows:
| Label | Function | Note |
| power | power indicator light, red | on: power on off: power off |
| run | running indicator light, green | blinking: device runs normal off: device not started. |
| warn | warning indicator light, red | on: The device has abnormal alarm off: The device has no abnormal alarm information |
| 4G | 4G communication data indicator, | blinking: 4G online |
| 485/1 | RS485-1 Communication indicator light, red and green | Red and green flashing: RS485 normal communication |
| 485/2 | RS485-2 Communication indicator light, red and green | Red and green flashing: RS485 normal communication |
| 485/3 | RS485-3 Communication indicator light, red and green | Red and green flashing: RS485 normal communication |
| 485/4 | RS485-4 Communication indicator light, red and green | Red and green flashing: RS485 normal communication |
| 485/5 | RS485-5 Communication indicator light, red and green | Red and green flashing: RS485 normal communication |
| CAN/1 | CAN-1 Communication indicator light, red and green | Red and green flashing: CAN normal communication |
| CAN/2 | CAN-2 Communication indicator light, red and green | Red and green flashing: CAN normal communication |
| DI/1~DI/4 | DI1~4 signal input indicator light, red | on: DI1~4 detected input signal off: DI1~4 no input signal |
| DO/1~DO/2 | DO1~2 signal output indicator light, red | on: DO1~2 relay contact closure off: DO1~2 relay contact disconnected |
4. Packing List
| No. | Name | Num. | Note |
| 1 | EMS- Smart microgrid controller | 1 | |
| 2 | antenna | 2 | 4G、WIFI |
| 3 | wiring terminal | HMQ-EMS-300LD11CN: 4 HMQ-EMS-300ND11CN: 4 HMQ-EMS-300LA11CN: 7 HMQ-EMS-300NA11CN: 7 | matching terminal plug |
| 4 | qualification | 1 | |
| 5 | specification | 1 |