苏州博图制冷设备有限公司
用
户
操
作
使
用
说
明
书
BCW-1500URD 工业机柜空调说明书
目 录
1. 安全注意事项·······················································································1
2. 安装要求 ·····························································································1
21 安装位置2
2-2 安装方法·························································································3
2-3 电器配线························································································6
2-4 机器排水·························································································6
3 启动与运转···························································································6
3-1 运行前后注意事项···········································································6
3-2 机器操作说明··················································································7
4 维护与保养10
4-1 定期清洁·······················································································10
4-2 长时间停用时注意10
5. 故障排除·····························································································10
附录一······································································································11
附录二11
1,安 全 注 意 事 项
⑴ 当用户对本空调器进行各种操作时,请先详读本使用手册,并注意本手册
中所提到的注意事项,以避免出现意外情况;
⑵ 请勿用湿手操作,以免引起触电;
⑶ 当需要保养或维护时,请先切断所有电源以免引起触电事故;
⑷ 空调器上不易放置任何物品,以免滑落造成人员伤害;
⑸ 当机器在运转时,请勿将手指或任何物品伸入进、出风口,以避免人员受
伤或机器损坏;
⑹ 本机器露天放置宜做好密封措施以免雨水进入机体内,并且也不适宜于安装在振动较大或者
移动的设备上,当客户必需安装在此种条件下时,请务必致电本公司咨询;
⑺ 本空调器为工业用设备,当须用于动植物或食品等方面之特殊用途时,请致电本公司咨询;
⑻ 禁止自行改装、修理、拆卸或者移装,欲进行上述动作前请先向专业人员咨询,以防意外发
生。
1. 安装要求
本空调器为户外半嵌式系列,半嵌式(图一),为使机组能在理想的状况下工作,在安装上请注
意以下要求:
图一 半嵌式
空调器
电
控
箱
回风
(热)
出风
(冷)
2-1 安装位置
⑴ 空调器需安装在周围空气品质良好的环境中,请勿放置于有腐蚀性气体、可燃性气体、粉尘
类气体、油污类气体等品质较差的空气中;如果确实需要在粉尘及油污等品质较差的环境中安装
空调器,则一定要每天做好空调器的清洁和保养工作。
⑵ 空调器应安装在通风良好且热量易于排放的地方,因为空调器运行时会排出热量,如果空调
器周围排气不畅很容易导致其周围的温度升高,这将影响空调器的制冷效果。见图三,空调器进、
排风口离墙面的间距应大于 500mm;
⑶ 空调器周围请勿放置杂物,以保持空气畅通流通;
⑷ 本空调器不宜放置于阳光可以直射的地方,避免因阳光照射而吸热,影响冷却效果。
⑸ 请安装本空调器于周围温度在 45℃以下的范围之内高温系列 55℃以下;
⑹ 本机安装时请注意上下位置摆放正确,绝对不能倒置安装,前后左右必须保持垂直,其倾斜
角不大于 5°如图四所示;
⑺ 控制箱内正对出风口的电器元件与出风口的最小距离应大于 200mm,因距离太近电器元件表
面易产生水膜现象,从而导致电器故障的发生。若无法避免,请在电器元件前增加一块隔热材料;
并且箱内出风口四周的电器元件与出风口应保持一定的距离,以便减小箱内空气的流通阻力。
⑻ 当空调器工作时,电控箱四周应该密封,箱门尽量较少打开次数,以便箱体内空气的温、湿
度能控制在较为理想的状态下。
图三
电
控
箱
冷气机
图 四
错 误 正 确 错 误 正 确
2-2 安装方法
⑴ 当机组在搬运、装卸时,请始终保持设备处于垂直直立状态,不要将设备长期放在露天场所;
⑵ 为使空调器的冷却效果最佳,请将机组直接安装在电气柜的外壁上,请勿采用风管的形式进
行送风,如若确实需要采用风管送风,请先咨询本公司技术工程师;
⑶ 空调器在安装之前,请先确认好安装位置的强度是否能承载机组,以免造成人员受伤及设备
损坏,当安装在电气柜门上时,最好该扇箱门能固定不动,当需要打开时请先确认好加在门上的
重量不会使整个电气柜倾倒;
⑷ 电气柜上必须开孔,以便使冷风能进入电控箱内,具体的开口尺寸请参见图五;
⑸ 箱体开孔时请严格参照开口尺寸进行,孔口处的毛刺必须清除,以免划伤机组;
⑹ 当长期使用时请注意安装螺栓是否损坏或脱落,若有而未加处理,将有可能导致机器掉落而
损坏;
⑺ 具体的安装方式如下
安装示意图:
2-3 电器配线:
⑴ 机组安装好后请先检查电源电压值是否保持在容许额定值内,请避免电压值过高或过低,若
所提供的电压在额定值±10%以内,本机组可正常使用;L,N,PE ,为电源输入引线
经常在超过额定电压值的环境中使用,将会大大缩短压缩机和其他电气设备及元件的使用寿命,此类损坏不属于我公司包修范围,只负责收费维修。请用户千万注意
⑵ 空调的电器箱在机体内部,非专业维修人员请勿打开电器箱进行操作。机组引出一根电源线,
当安装好后无需另外接线,将插头插入电控箱内的电源插座即可;
⑶ 在机组的电器回路上请自行安装断路器或漏电保护装置;
⑷ 请准备本机专用电源插座,不要在同一个插座上使用过多电器装置,否则容易使电源超出负
载,引发事故。
面板端子接线示意图:
第一排 X1 针型端子排从左往右依次为电源接口 L,N,PE,后方 P1 和 P2 端子为空调运行输出信号。此
触点输出电压为交流 220 伏,空调待机或者断电状态下没有电压输出,在开启制冷状态,空
调运行工作下,此触点闭合,输出 220 电压,电流最大负载为 5 安培。第二排 X2 端子从左往
右依次为 485 通讯接口 A,B,G.后方 COM,NO 端子为空调告警信号,为无源常开型触点,有
告警时闭合。
2-4 机器排水:(户外机型无以下排水管项目)
本机器自身有除湿功能,当机器运行时,它会慢慢除去电控箱内空气中的部分水分,这部分水气
就会以液态的形式排出,排水管就起到排出这部分水的作用,排水管的连接请注意以下几点:
⑴ 请先在机器排水口上连接好短接头,然后把配给的软管连接上,再用抱箍紧固好连接处;
⑵ 根据实际情况排水软管长度适当即可,过长部分请切除;
⑶ 排水软管请勿折弯、压扁、阻塞或出口高于进口,以免排水不畅,从而导致机器内产生淤水
严重时产生外溢,引起空调器或者电气柜故障。
2. 启动与运行
3. 3-1 运行前后注意事项
⑴ 启动前请先检查排水管是否已经连接到位,电控箱门是否关严,若均已到位即可插上电源开
始工作;
⑵ 当在运转中需重新启动空调器时,请间隔 3 分钟以上,倘若频繁启动且间隔时间过短会引起
机器损伤;
⑶ 当空调器倾斜时请勿开启,避免漏水、触电等情况发生;
⑷ 空调器在出厂时温度点已经设定好为 30℃,若需重新设定时请控制在允许范围之内设定,以
免引起机器运行不正常;如果空调器有加热功能,出厂时设置为 5℃
⑸ 当机器有异常噪音或异味(焦臭)等现象出现时,请马上关闭空调器,并请专业人员进行检
查维修。
简介:
ZL-696 温控器采用小型化、IP65 等级面板防护设计,体积小重量轻,操作简捷安装方便。适用于小型机柜空调系统的温度控制。
主要功能
温度测量 电加热控制
温度显示 系统缺氟保护
温度校正 高温、低温告警
压缩机延时保护 传感器故障告警
蜂鸣器告警输出 无源数字量输入
RS485 通讯
规格尺寸
1前面板尺寸: 长 78 x 宽 345(毫米) 2安装开孔尺寸:长 71 x 宽 29(毫米)
3.整机尺寸: 长 78 x 宽 34.5 x 深 71(毫米) 4.传感器线长:1 米(含探头长度)
主要技术指标
感温元件:NTC 3470/10K 电源电压:ZL696AR+ : AC10V~12V 300Ma(外置电源变压器)
设定范围:0 ~50℃ ZL696ALR+: DC14V-60V 300mA
显示范围:-40~130℃ 接线端子:连接 2*15mm
2 或 1*25mm
P 2
的导线
工作环境:-10~45℃ 负载电流:5 ~ 16A/250Vac, (阻性负载)
存储温度:-30~70℃ 外 壳:PC + ABS 阻燃
湿 度:5~85%RH (不结露) 防护等级:IP65(前面板)
操作指南
显示说明
显示屏信号说明
图标 功能 亮 灭 闪烁
压缩机 启动 停止 准备制冷,压缩机正在延时保护
AUX 电加热 运行 风机 运行 停止 ----维修 有故障 无故障 ----报警 有报警 无报警 通讯 ---- ---- 正在通讯
HACCP 压缩机强制 强制运行 ---- ----面板数码管说明
4 位红色数码管显示测量温度值和告警代码;
显示代码说明
序 号 显示代码 说 明
1 E01 温控温度传感器故障(短路或断路)
2 E02 蒸发器温度传感器故障(短路或断路)
3 Hi 高温告警
4 Lo 低温告警
5 HP 系统高压保护
6 LP 系统低压保护
7 SmK 烟感报警
8 LOF 系统缺氟保护
9 VENT 系统换气
10 Err 密码输入错误
11 UnL 恢复默认出厂密码“1111”
按键操作
制冷、制热参数设置
按〖S〗键并保持 3 秒钟,进入参数设置状态,这时数码管显示『Cool』,用〖▲〗或〖▼〗键选择参数代码,选定一个参数
后按〖S〗键显示该参数的设定值,这时再按〖▲〗或〖▼〗键可对参数进行设置,设置完成后再按〖S〗键,回到显示参数
代码状态。
序号 参数代码 设置功能 设定范围 说明 出厂设定值
01 CooL 制冷温度设定 0~ 50℃ 制冷、制热温度设定 22
02 HEAT 制热温度设定 0~ 30℃ 间隔 1℃ 8
当参数设置完成后必须长按〖S〗键 3 秒, 系统退出参数设置状态,此次参数设置被保存。在参数设置状态如果连续 30 秒
内无按键操作,系统退出参数设置状态,但此次参数设置无效,控制器仍按原来的参数运行;
系统参数设置
·系统参数设置界面进入:
使用一组密码进入参数设置状态(出厂默认密码为 1111),按〖P〗键并保持 3 秒钟,数码管显示『---0』,按〖▼〗键循环
选择密码当前位,按〖▲〗键设置当前位密码值, 密码设置完成后按〖S〗键确认。如果密码错误,显示『Err』蜂鸣器响三声
后退出参数设置状态;如果密码输入正确,蜂鸣器响一声,进入参数设置状态,这时数码管显示『U00』,用〖▲〗或〖▼〗
键选择参数代码,选定一个参数后按〖S〗键显示该参数的设定值,这时再按〖▲〗或〖▼〗键可对参数进行设置,设置完
成后再按〖S〗键,回到显示参数代码状态。
·系统参数设置界面退出:
当参数设置完成后必须长按〖P〗键 3 秒, 系统退出参数设置状态,此次参数设置被保存。在参数设置状态如果连续 30 秒
内无按键操作,系统退出参数设置状态,但此次参数设置无效,控制器仍按原来的参数运行;工作参数代码及设置说明如下表所示:
序号 参数代码 设置功能 设定范围 说明 出厂设定值
1 U00 制冷启动温度 0~ 50℃ 22
2 U01 制热启动温度 0~ 30℃ 8
3 U02 制冷/制热温差 10~ 100℃ 2
4 U03 蒸发风机启动温度 0~ 50℃ 16
5 U04 蒸发风机温差 1.0~ 10.0℃ 3
6 U05 高温报警
-50~90℃
高温/低温
设定间隔 1℃
50
7 U06 低温报警 5
8 U09 柜温传感器校正 -9.9~+9.9℃ 0
9 U10 内盘温度传感器校正 -9.9~+9.9℃ 0
10 U16 蒸发器温度传感器使能设定 0~1 0:禁用;1:启用 1
11 U18 电加热工作模式 0~1
1:启用电加热
1
0:禁用模式
12 U22 高压告警输入模式 0~1
0:常闭;
1
1:常开
13 U23 低压告警输入模式 0~1
0:常闭;
1
1:常开
14 U24 烟感告警输入模式 0~1
0:常闭;
1
1:常开
15 U25 蜂鸣器报警 0~1 0:禁用;1:启用 1
16 U26 压缩机最短停机时间 0-10 分钟 3
17 U27 压缩机最短运行时间 0-10 分钟 3
18 U29 换气周期 0180 小时 24
19 U30 换气时间 0-99 分钟 5
20 U33 系统开关机 ON,OFF
ON:开机,
OFF:关机
ON
21 U34 RS485 波特率设定 0~3
0:2400bps
3
1:4800bps
2:9600bps
3:19200bps
22 U35 设备地址 1~99 1
23 U99 密码 0000 ~ 9999 ---- 1111
24 End 设定结束
查看蒸发器温度
在显示当前温度时按住〖▲〗键, 数码管显示蒸发器传感器温度值,松开则恢复显示当前温度值。
控制逻辑
■蒸发风机控制(有蒸发风机控制点时有效)
系统上电后 3 秒钟后检测柜内温度是否满足启动蒸发风机的条件:
蒸发风机启动条件:1、柜内温度 ≥ [蒸发风机启动温度]
2、电加热启动时,蒸发风机同时启动,电加热停止时,蒸发风机延时 1 分钟停止。
3、压缩机启动时,蒸发风机同时启动,压缩机停止时,蒸发风机延时 1 分钟停止。
蒸发风机停止条件:柜内温度 ≤ [蒸发风机启动温度] [蒸发风机温差] ■压缩机控制
系统上电后 3 秒钟后检测柜内温度是否满足启动压缩机的条件:
压缩机启动条件:柜内温度 ≥ [制冷温度]
压缩机停止条件:柜内温度 ≤ [制冷温度] - [制冷/制热温差]
压缩机开启时开启蒸发风机;当压缩机关闭时,根据蒸发风机温度开启点(默认 16 度),判断开关蒸发风机。
冷凝风机与压缩机同点控制
压缩机启停还需要满足如下条件:
满足压缩机最短运行时间和最短停机时间的要求。
■电加热控制
系统上电 3 秒钟后检测柜内温度是否满足启动电加热的条件:
电加热启动条件:柜内温度 ≤ [制热温度]
电加热停止条件:柜内温度 ≥ [制热温度] + [制冷/制热温差]
电加热开启时开启蒸发风机;当电加热关闭时,延时 1 分钟停止。
■换气阀控制
系统缺省为每间隔 24 小时换气 5 分钟,参数可设置。
当机组运行时间到达[换气间隔]时间后,关闭电加热,压缩机,开启换气阀,机组进行换气,当到达[换气时间]时间后,关换气
阀,满足压缩机最短停机时间,开电加热,压缩机,完成一个换气周期。
蜂鸣器功能
每按键一次蜂鸣器鸣叫一声,在参数设置确认时长鸣一次,在进行无效操作时蜂鸣器鸣叫三声;当系统出现故障或有外
部报警输入时,如果参数U28=0,关闭蜂鸣器报警功能,蜂鸣器不鸣叫报警;如果参数U28=1,则蜂鸣器连续鸣叫报警; 系
统恢复正常后,自动消除蜂鸣器报警状态温度值校正功能
当测量温度值与传感器安装位置实际温度有误差,可通过【温度修正参数】进行校正,校正范围±99℃;按一次〖▲〗
或〖▼〗键调整温度校正值增或减 0.1℃,按住不放则快速调整;
系统缺氟(漏氟)保护:
当压缩机启动 5 分钟后,检测温控传感器、蒸发器传感器温度,如果温控传感器温度高于蒸发器传感器温度 5 度以
上温差,判定系统正常,否则认定为缺氟保护(漏氟),并显示报警代码“LOF”。强制关闭压缩机。
1 小时内如果连续发生 3 次缺氟保护,需要手动重新上电解除告警。
系统防冻结保护:
当压缩机启动 1min 后,检测蒸发器传感器温度,如果蒸发器传感器温度小于等于-1 度并保持 5sec,判定系冻结保护。系统
强制关闭压缩机,当蒸发器温度上升 8 度以上,系统恢复正常制冷;
干接点告警输出
当发生传感器故障、高温、低温、高压/低压报警、烟感报警、缺氟保护时,干接点继电器动作, 输出告警信号;
信号名称 说明
NO 故障输出(故障时断开,正常时闭合)
NC 故障输出(故障时闭合,正常时断开)
COM 公共端
恢复出厂参数与密码:
控制器在运行状态下,同时按下〖P〗与〖▲〗键不放并保持 5 秒后蜂鸣器响一音调声,数码管显示『UnL』,此时再按 2 次〖▼〗
键后,蜂鸣器响一音调声,控制器自动恢复出厂参数与默认密码「1111」;
产品信息查询:
控制器在运行状态下,同时按下〖S〗与〖▲〗键不放并保持 3 秒后蜂鸣器响一音调声,数码管滚动显示产品型号和版本信息;故障检测及保护
压缩机保护
压缩机除了高压和低压保护之外,还具备如下保护:
压缩机最短停机时间为 3 分钟,压缩机停止后最少要 3 分钟才能重新启动。
故障检测及动作
根据系统设置,各故障点常闭表示故障点如果和该排插座的 DCOM(公共端)形成回路则表示正常,如果断开则表示故障。没有用到
的故障点,请将其设置为常开,以免引起不必要的报警。故障报警时,显示屏故障指示灯点亮,蜂鸣器发出报警声。故障消音可按任
意键。
序号
报警
代码
故障 推迟时间
持续
时间
复位操作 备注
1 E01 柜内温度传感器故障 0 秒 5 秒 自动 报警,停压缩机、加热器,开蒸发风机。
2 E02 蒸发器传感器故障 0 秒 5 秒 自动 报警,取消防冻结、缺氟保护。
3 HP 高压报警 0 秒 5 秒 自动 报警, 停压缩机
4 LP 低压报警 压缩机启动 30 秒 5 秒 自动 报警,停压缩机
5 SmK 烟感报警 0 秒 5 秒 手动 报警, 停整机
6 Hi 高温报警 0 秒 5 秒 自动 报警
7 Lo 低温报警 0 秒 5 秒 自动 报警
8 LOF 缺氟报警 0 秒 5 秒 手动 报警、停压缩机
9 --- 冻结保护 压缩机启动 2 分 自动 停压缩机,开蒸发风机
故障复位后压机启动需满足压缩机停机时间大于[压缩机最短停机时间];
控制器装配
敬告:
请尽量避免将控制器安装在以下环境中:
◆相对湿度大于90%或存在凝露的地方;
◆强烈振动或敲击;
◆暴露在连续的水雾喷射下;
◆暴露在侵蚀性和污染气体下(例如:含有硫和氨的烟气、盐雾、烟雾),以防止侵蚀和氧化;
◆含有易爆物品或可燃混合气体的环境;
安装步骤
第1步: 将控制器嵌入孔中;
第2步: 通过在设备的导轨方向滑动支架来固定控制器,直到将控制器压实在面板上;
电气连接
敬告:
◆电气接线操作必须由有资质的技术人员来完成。
◆使用规定电源类型以外的电源可能会给系统带来严重损害;
◆尽可能将传感器、开关量输入信号线与感性负载线、电源线分开排线,以避免电磁干扰。绝不能将电源线(包括电力线)和传感器
信号线布在同一管道中。不能将传感器线安装在电源设备(接触器、断路器或类似设备)的紧邻区域;
◆尽可能的降低传感器接线的长度,并避免在电源设备周围形成螺旋形线路。
◆安装时避免直接接触内部电子元件。
◆需直接连接到设备以及完成布线和检查布线时,请仔细阅读并遵照下面的指导进行操作,并仔细注意给出的图示:如果连接
错误,可能会危害到用户安全,也可能导致连接设备和元件出现故障。请务必为设备配备所有机电安全保护装置,这些装置
是为保证设备正常运行和用户的绝对安全而必需配备的。
电气接线图
4.维护与保养
请定期检查排水管,并确定无堵塞现象,若排水不良易造成空调器漏水。请定期清洗空气过滤网和冷凝器。对于机
器上安装的是尼龙滤网的可直接从侧面拔出
4-1 定期清洁
本机的滤网材质为尼龙滤网,可直接从网罩上面拉出,用洗涤水清洗干净,并晾干后按原样装回,
一般每周需清洗一次;(户外型为网孔型过滤形式)
⑵ 请用中性清洗剂擦拭机体,避免使用硬刷及酸性清洗剂清洗,严禁用水冲洗空调器,以防发
生触电事故;
4-2 长时间停用时注意
⑴ 请切断电源,以防意外;
⑵ 清理冷凝器、过滤网及内部油污;
⑶ 请对机器采取防尘措施,延长机器使用寿命。
4. 故障排除
故障状况 1 电源接通后,室内、室外风机不运转
可能原因
※保险丝熔断
※停电或无电源
状况排除
※更换保险丝
※检查电源状况
故障状况 2 在运行中突然停机,电控箱内温度高于设定点温度两度以上
可能原因
※环境温度过高,导致压缩机热保护
※过滤网堵塞或者冷凝器过脏,导致压缩机热保护
状况排除
※改善周边环境,使散热畅通
※对过滤器及冷凝器进行清洗
故障状况 3 机器正常运转,却不制冷
可能原因
※压缩机损坏
※制冷系统泄露
※机组蒸发器大面积结霜
状况排除
※更换压缩机,重新抽真空充注制冷剂
※查出泄露处,并重新抽真空加制冷剂
※立即停机,把设定温度调高到 35℃,十分钟后重新开机
◇若上述措施均不能排除故障,请致电本公司咨询!
附录 1:产品技术参数
型号:BCW-1500URD
工作电源: 交流 220V ±10% 频率 50Hz ±4%
运行电流: <365A 制冷输入电气功率: 590W 制热输入电气功率: 1080W
制冷剂: R134a 制冷量: 1500W 制热量:1000W
防护等级: IP55 允许机柜内温度设定范围:25-38℃(出厂设定 30℃)
允许使用环境温度范围:-25--45℃ 运行噪音:55dB
附录 2:电气原理图
室内风机 室外风机 压缩机
M1 M2 M3
C2 C3
L
N
PE
t℃温控器
BCW1主50回0U路RD 电路图
苏 州 博 图 制 冷 设 备 有 限 公 司
地址:苏州市吴江区太湖新城镇黄沙路 23 号
电话:0512-63172851 0512-63172852
传真:0512-63102853 邮编:215223
全国统一服务热线: 400-920-7382
网址 www.botuzl.com Email:botu@botuzl.com