CM2 / CP2 / CP2-G
DCM2 / DCP2 / DCP2-G
IN-LINE PUMPS
3
DAB PUMPS reserves the right to make modifications without notice
CM2 / CP2 / CP2-G / DCM2 / DCP2 / DCP2-G
IN-LINE PUMPS
APPLICATIONS
In-line pumps for use in commercial building service, designed for the recirculation of water in air conditioning and heating systems even in the presence
of solar collectors. Available in twin version (models with letter D).
CONSTRUCTION FEATURES OF THE PUMP
Suction and delivery ports in line and flanged PN 10 or PN 16 with threaded connectors for control pressure gauges. Pump body and motor support in
cast iron. Impeller in cast iron or technopolymer depending on the model. Standard mechanical seal according to DIN 24960 in silicon carbide / silicon
carbide with O-rings in EPDM.
CONSTRUCTION FEATURES OF THE MOTOR
Air-cooled three-phase asynchronous motor with two poles. Motor shaft in stainless steel. Electrical protection by the user.
TECHNICAL DATA
Operating range: up to 36 m3
/h with head up to 50 m.
Type of pumped liquid: clean, free of solids and abrasives, non-viscous,
non-aggressive, non-crystallised
Glycol percentage (maximum): 50%
Liquid temperature range: from -15 °C to +140 °C
Maximum ambient temperature: +50 °C
Maximum operating pressure: 16 Bar (1600 kPa)
Flanging: PN10 - PN16
Motor efficiency: IE2 up to 0,55 kW; IE3 ≥ 0,75 kW
Protection: IP 55
Insulation: class F
Impeller material: cast iron or technopolymer
Three phase power input: 3x230 V 50 Hz / 3x400 V 50 Hz
Max rpm: 2910
Type of installation: Fixed in horizontal or vertical position with motor in
up position. Only in vertical position for motor from 7,5 kW.
MATERIALS
N. PARTS MATERIALS
1 PUMP BODY CAST IRON EN GJL250 UNI EN 1561
2 SUPPORT CAST IRON EN GJL250 UNI EN 1561
3 IMPELLER CAST IRON EN GJL200 UNI EN 1561 AND ULTRASON E 2010
4 SHAFT WITH ROTOR AISI 316 + C10
5 MECHANICAL SEAL SPRING AISI 316 - ESIC / ESIC - EPDM
6 O-RING EPDM
1
2
4
3
5
6
Circulator
P = 2-pole motor
M = 4-pole motor
G = version with coupling
(DN) nominal diameter
of the flanged ports
Maximum head (cm)
Tri-phase motor
Denominations: C P2-G 32-4800 T
(example)
4
DAB PUMPS reserves the right to make modifications without notice
CM2 / CP2 / CP2-G / DCM2 / DCP2 / DCP2-G
IN-LINE PUMPS
SELECTION TABLE - CM2
SELECTION TABLE - CP2
SELECTION TABLE - DCM2
SELECTION TABLE - DCP2
MODEL
HYDRAULIC DATA
Q=m3
/h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Q=l/min 0 33 67 100 133 167 200 233 267 300 333 367 400 433 467 500 533 567 600
CM2 32-450 T
H
(mt)
4,4 4,3 4,1 3,8 3,5 3,0 2,4 1,7 0,9
CM2 32-600 T 6,0 5,9 5,7 5,4 4,9 4,3 3,6 2,8 1,9 1,0
CM2 32-800 T 7,9 7,7 7,5 7,1 6,6 6 5,3 4,5 3,6 2,6 1,5 0,3
CM2 32-1200 T 12 12 12 11 11 10 9,5 8,6 7,6 6,4 5,1 3,7 2,1 0,4
MODEL
HYDRAULIC DATA
Q=m3
/h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Q=l/min 0 33 67 100 133 167 200 233 267 300 333 367 400 433 467 500 533 567 600
CP2 32-550 T
H
(mt)
5,5 5,5 5,2 4,9 4,4 3,9 3,3 2,7 2,2 1,7 1,4
CP2 32-750 T 7,4 7,2 6,9 6,6 6,2 5,6 5,1 4,4 3,7 2,8 1,9 1,0
CP2 32-1100 T 10,6 10,4 10,1 9,7 9,3 8,7 8,1 7,4 6,5 5,6 4,5 3,3 2,0 0,5
CP2 32-1400 T 14,3 14,0 13,7 13,3 12,8 12,3 11,7 10,9 10,1 9,2 8,2 7,1 5,8 4,4 2,9 1,3
CP2 32-1800 T 17,8 17,7 17,4 17,0 16,6 16,1 15,5 14,7 13,9 13,0 12,0 10,9 9,7 8,3 6,9 5,3 3,6 1,8
CP2 32 2200 T 21,9 21,8 21,6 21,2 20,8 20,2 19,5 18,7 17,7 16,7 15,5 14,1 12,7 11,1 9,3 7,4 5,4 3,2 0,8
CP2 32-2100 T 21,5 20,9 19,9 18,4 16,4 13,8 10,6 6,8 2,1
CP2 32-2700 T 26,7 26,5 26,3 25,9 25,4 24,9 24,3 23,7 23,0 22,3 21,5 20,7 19,9 19,1
CP2 32-3600 T 36,4 36,7 36,8 36,6 36,3 35,7 35,0 34,2 33,3 32,2 31,1 29,9 28,8 27,6 26,4 25,2 24,1 23,1 22,2
CP2 32-4000 T 40,3 40,6 40,7 40,6 40,2 39,7 39,0 38,2 37,3 36,2 35,1 33,9 32,6 31,2 29,9 28,5 27,2 25,8 24,5
CP2-G 32-4800 T 49,1 49,0 48,9 48,7 48,4 48,0 47,6 47,0 46,3 45,5 44,6 43,5 42,3 41,0 39,6 37,9 36,2 34,3 32,2
MODEL
HYDRAULIC DATA
Q=m3
/h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Q=l/min 0 33 67 100 133 167 200 233 267 300 333 367 400 433 467 500 533 567 600
DCM2 32-450 T
H
(mt)
4,8 4,7 4,4 4,0 3,5 2,8 2,0 1,0
DCM2 32-600 T 6,0 6,0 5,7 5,3 4,7 4,0 3,1 2,0 0,8
DCM2 32-800 T 8,0 7,9 7,8 7,5 7,1 6,6 5,9 5,2 4,4 3,5 2,5 1,5 0,4
DCM2 32-1200 T 11,1 11,0 10,7 10,4 9,9 9,3 8,6 7,8 6,9 5,8 4,6 3,3 1,9 0,4
MODEL
HYDRAULIC DATA
Q=m3
/h 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Q=l/min 0 33 67 100 133 167 200 233 267 300 333 367 400 433 467 500 533 567 600
DCP2 32-550 T
H
(mt)
5,6 5,4 5,1 4,7 4,1 3,4 2,5 1,5 0,4
DCP2 32-750 T 7,5 7,2 6,9 6,4 5,9 5,1 4,3 3,3 2,1 0,8
DCP2 32-1100 T 10,7 10,5 10,2 9,7 9,1 8,4 7,5 6,5 5,4 4,1 2,7 1,1
DCP2 32-1400 T 14,2 14,0 13,7 13,2 12,7 12,0 11,2 10,2 9,2 7,9 6,5 5,0 3,2 1,3
DCP2 32-2100 T 22,2 21,4 20,2 18,4 16,0 12,9 9,0 4,2
DCP2 32-1800 T 17,9 17,8 17,5 17,0 16,5 15,8 15,0 14,0 13,0 11,8 10,4 9,0 7,3 5,6 3,7 1,7
DCP2 32-2200 T 22,3 22,2 21,9 21,5 20,9 20,2 19,3 18,2 17,0 15,7 14,2 12,7 10,9 9,1 7,1 5,1 2,9 0,6
DCP2 32-2700 T 27,3 27,2 26,9 26,6 26,1 25,5 24,9 24,1 23,2 22,2 21,0 19,8 18,4 16,9 15,3 13,6 11,8 9,8 7,7
DCP2 32-3600 T 36,8 36,8 36,6 36,3 35,9 35,3 34,5 33,7 32,7 31,7 30,5 29,3 28,0 26,6 25,2 23,7 22,2 20,6 19,1
DCP2 32-4000 T 41,0 41,0 40,8 40,5 40,0 39,4 38,7 37,8 36,8 35,7 34,5 33,2 31,8 30,3 28,8 27,2 25,6 23,9 22,1
DCP2-G 32-4800 T 49,6 49,5 49,2 48,9 48,4 47,8 47,1 46,3 45,3 44,3 43,2 41,9 40,6 39,1 37,6 35,9 34,2 32,3 30,4
5
DAB PUMPS reserves the right to make modifications without notice
CM2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
MODEL A B B1 B2 C1 D D1 S1 D2 S2 D3 DNA DNM H H1 L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
CM2 32-450 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 21,9
CM2 32-600 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 21,6
CM2 32-800 T 110 150 129 120 180 80 100 14 90 19 140 32 33 459 90 320 165 155 10 0,52 0,29 0,7 0,11 27
CM2 32-1200 T 110 150 129 120 180 80 100 14 90 19 140 32 33 459 90 320 165 155 10 0,52 0,29 0,7 0,11 27
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
CM2 32-450 T
260
DN 32 PN 16
DN 32 PN 10
230-400V 0,26 0,25 0,34 1,2 A 0,7 A
CM2 32-600 T 230-400V 0,33 0,25 0,34 1,3 A 0,8 A
CM2 32-800 T
320
230-400V 0,51 0,37 0,50 2,0 A 1,2 A
CM2 32-1200 T 230-400V 0,73 0,55 0,75 2,4 A 1,4 A
C1
L2 L1
L
B1
B2
A
DNM
D3
H1
H
D DNA
B
S1 S2
D2
D1
M
0 4 8 12 16 20 24 28 32 Q m3
/h
0
2
4
6
8
10
12
H
m
0
20
40
60
80
100
120
P
kPa
0 80 160 240 320 400 480 560 Q l/min
0 2 4 6 8 Q l/s
0
5
10
15
20
25
30
35
40
H
ft
0 16 32 48 64 80 96 112 128 144 Q US gpm
0 16 32 48 64 80 96 112 Q IMP gpm
CM2
CM2 32-1200 T
CM2 32-800 T
CM2 32-600 T
CM2 32-450 T
6
DAB PUMPS reserves the right to make modifications without notice
CP2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
MODEL A B B1 B2 C1 D D1 S1 D2 S2 D3 DNA DNM H H1 L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
CP2 32-550 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 22,6
CP2 32-750 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 22,6
CP2 32-1100 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 22,6
CP2 32-1400 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 24,7
CP2 32-1800 T 110 150 102 95 140 78 100 14 90 19 140 32 33 445 98 260 135 125 10 0,53 0,3 0,46 0,07 25,5
CP2 32-2200 T 113 160 102 95 140 78 100 14 90 19 140 32 33 453 98 260 135 125 10 0,53 0,3 0,46 0,07 25
CP2 32-2100 T 113 160 102 95 140 78 100 14 90 19 140 32 33 453 98 260 135 125 10 0,53 0,3 0,46 0,07 25
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
CP2 32-550 T
260 DN 32 PN 16
DN 32 PN 10
230-400V 0,37 0,25 0,34 1,7 A 1 A
CP2 32-750 T 230-400V 0,48 0,37 0,50 1,9 A 1,1 A
CP2 32-1100 T 230-400V 0,73 0,55 0,75 2,4 A 1,4 A
CP2 32-1400 T 230-400V 1,07 0,75 1,02 3,5 A 2 A
CP2 32-1800 T 230-400V 1,48 1,1 1,50 5,6 A 3,2 A
CP2 32-2200 T 230-400V 1,83 1,5 2,04 6,3 A 3,6 A
CP2 32-2100 T 230-400V 0,85 0,75 1,02 3 A 1,7 A
C1
L2 L1
L
B1
B2
A
DNM
D3
H1
H
D DNA
B
S1 S2
D2
D1
M
0 Q m3 4 8 12 16 20 24 28 32 36 /h
0
H
m
0
40 4
8 80
12 120
16 160
20 200
24 240
P
kPa
0 100 200 300 400 500 600 Q l/min
0 2 4 6 8 10 Q l/s
0
20
40
60
80
H
ft
0 20 40 60 80 100 120 140 160 Q US gpm
0 20 40 60 80 100 120 Q IMP gpm
CP2
CP2 32-2200 T
CP2 32-1800 T
CP2 32-2100 T
CP2 32-1400 T
CP2 32-1100 T
CP2 32-750 T
CP2 32-550 T
7
DAB PUMPS reserves the right to make modifications without notice
CP2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
MODEL A B B1 B2 C1 D D1 S1 D2 S2 D3 DNA DNM H H1 L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
CP 2 32-2700 T 118 160 102 94 140 80 100 14 90 19 140 32 33 526 90 320 165 155 10 0,52 0,29 0,7 0,11 37
CP 2 32-3600 T 135 193 130 125 180 80 100 14 90 19 140 32 33 535 90 320 165 155 10 0,52 0,29 0,7 0,11 45
CP 2 32-4000 T 135 193 130 125 180 80 100 14 90 19 140 32 33 535 90 320 165 155 10 0,52 0,29 0,7 0,11 45
CP 2-G 32-4800 T 202 258 129 120 180 80 100 14 90 19 140 32 33 689 90 320 165 155 10 0,7 0,6 1,1 0,46 74
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
CP2 32-2700 T
320 DN 32 PN 16
DN 32 PN 10
230-400V 2,9 2,2 2,99 9 A 5,2 A
CP2 32-3600 T 230-400V 4,08 3 4,08 12,3 A 7,1 A
CP2 32-4000 T 230-400V 4,95 4 5,44 15,1 8,7 A
CP2-G 32-4800 T 230-400V 6,5 5,5 7,48 18,2 A 10,5 A
C1
L2 L1
L
B1
B2
A
DNM
D3
H1
H
D DNA
B
S1 S2
D2
D1
M
CP2-G 32-4800 T
CP2 32-4000 T
CP2 32-3600 T
CP2 32-2700 T
0 3 6 9 12 15 18 21 24 27 30 33 36 39 Q m3
/h
0
5
10
15
20
25
30
35
40
45
50
55
60
H
m
0
100
200
300
400
500
600
P
kPa
0 100 200 300 400 500 600 Q l/min
0 1 2 3 4 5 6 7 8 9 10 11 Q l/s
0
20
40
60
80
100
120
140
160
180
200
H
ft
0 20 40 60 80 100 120 140 160 Q US gpm
0 20 40 60 80 100 120 140 Q IMP gpm
CP2
8
DAB PUMPS reserves the right to make modifications without notice
DCM2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
DCM2 32-450 T
260
DN 32 PN 16
DN 32 PN 10
230-400V 0,26 0,25 0,34 1,2 A 0,7 A
DCM2 32-600 T 230-400V 0,33 0,25 0,34 1,3 A 0,8 A
DCM2 32-800 T
320
230-400V 0,51 0,37 0,50 2,0 A 1,2 A
DCM2 32-1200 T 230-400V 0,73 0,55 0,75 2,4 A 1,4 A
0 4 8 12 16 20 24 28 32 Q m3
/h
0
2
4
6
8
10
12
H
m
0
20
40
60
80
100
120
P
kPa
0 80 160 240 320 400 480 560 Q l/min
0 2 4 6 8 Q l/s
0
5
10
15
20
25
30
35
40
H
ft
0 16 32 48 64 80 96 112 128 144 Q US gpm
0 16 32 48 64 80 96 112 Q IMP gpm
DCM2
DCM2 32-1200 T
DCM2 32-800 T
DCM2 32-600 T
DCM2 32-450 T
A
D DNA
C1
L1 L2
L
DNM
S1
D1
D2
S2
D3
C2
B1 B2
B
H
H1
I
M (4)
MODEL A B B1 B2 C1 C2 D D1 S1 D2 S2 D3 DNA DNM H H1 I L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
DCM2 32-450 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCM2 32-600 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCM2 32-800 T 110 609 305 305 113 463 78 100 14 90 19 140 33 33 459 90 350 320 150 170 10 684 426 834 0,245 54,5
DCM2 32-1200 T 110 609 305 305 113 463 78 100 14 90 19 140 33 33 459 90 350 320 150 170 10 684 426 834 0,245 54,5
9
DAB PUMPS reserves the right to make modifications without notice
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
0 Q m3 4 8 12 16 20 24 28 32 36 /h
0
H
m
0
40 4
8 80
12 120
16 160
20 200
24 240
P
kPa
0 100 200 300 400 500 600 Q l/min
0 2 4 6 8 10 Q l/s
0
20
40
60
80
H
ft
0 20 40 60 80 100 120 140 160 Q US gpm
0 20 40 60 80 100 120 Q IMP gpm
DCP2
DCP2 32-2200 T
DCP2 32-1800 T
DCP2 32-2100 T
DCP2 32-1400 T
DCP2 32-1100 T
DCP2 32-750 T
DCP2 32-550 T
A
D DNA
C1
L1 L2
L
DNM
S1
D1
D2
S2
D3
C2
B1 B2
B
H
H1
I
M (4)
DCP2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
MODEL A B B1 B2 C1 C2 D D1 S1 D2 S2 D3 DNA DNM H H1 I L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
DCP2 32-550 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCP2 32-750 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCP2 32-1100 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCP2 32-1400 T 110 485 243 243 92 377 80 100 14 90 19 140 36 37 445 98 285 260 130 130 10 540 420 610 0,138 46
DCP2 32-1800 T 114 238 242 480 92 377 80 100 14 90 19 140 36 37 453 98 285 260 130 130 10 540 420 610 0,138 49
DCP2 32-2200 T 114 238 242 480 92 377 80 100 14 90 19 140 36 37 453 98 285 260 130 130 10 540 420 610 0,138 49
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
DCP2 32-550 T
260 DN 32 PN 16
DN 32 PN 10
230-400V 0,37 0,25 0,34 1,7 A 1 A
DCP2 32-750 T 230-400V 0,48 0,37 0,50 1,9 A 1,1 A
DCP2 32-1100 T 230-400V 0,73 0,55 0,75 2,4 A 1,4 A
DCP2 32-1400 T 230-400V 1,07 0,75 1,02 3,5 A 2 A
DCP2 32-1800 T 230-400V 1,48 1,1 1,50 5,6 A 3,2 A
DCP2 32-2200 T 230-400V 1,83 1,5 2,04 6,3 A 3,6 A
10
DAB PUMPS reserves the right to make modifications without notice
DCP2 - IN-LINE PUMPS FOR CIRCULATION SYSTEMS
Liquid temperature range: from -15°C to +140°C - Maximum operating pressure: 16 bar (1600 kPa)
MODEL A B B1 B2 C1 C2 D D1 S1 D2 S2 D3 DNA DNM H H1 I L L1 L2 M
PACKING DIMENSIONS VOLUME
(mc)
WEIGHT
Kg L/A L/B H
DCP2 32-2700 T 118 609 305 305 113 463 78 100 14 90 19 140 33 33 526 90 350 320 150 170 10 684 426 834 0,245 71,5
DCP2 32-3600 T 135 609 305 305 113 463 78 100 14 90 19 140 33 33 535 90 350 320 150 170 10 684 426 834 0,245 90
DCP2 32-4000 T 135 609 305 305 113 463 78 100 14 90 19 140 33 33 535 90 350 320 150 170 10 684 426 834 0,245 90
DCP2-G 32-4800 T 202 609 305 305 113 463 78 100 14 90 19 140 33 33 689 90 350 320 150 170 10 926 668 1237 0,765 168
MODEL
ELECTRICAL DATA
CENTRE DISTANCE PUMP CONNECTIONS POWER INPUT
50 HZ
P1 MAX
[kW]
P2 NOMINAL In [Ah]
kW HP 230 400
DCP2 32-2700 T
320 DN 32 PN 16
DN 32 PN 10
230-400V 2,9 2,2 2,99 9 A 5,2 A
DCP2 32-3600 T 230-400V 4,08 3 4,08 12,3 A 7,1 A
DCP2 32-4000 T 230-400V 4,95 4 5,44 15,1 8,7 A
DCP2-G 32-4800 T 230-400V 6,5 5,5 7,48 18,2 A 10,5 A
The performance curves are based on kinematic viscosity values =
1 mm2
/s and density equal to 1000 kg/m3
. Curve tolerance according to ISO 9906.
DCP2-G 32-4800 T
DCP2 32-4000 T
DCP2 32-3600 T
DCP2 32-2700 T
0 6 12 18 24 30 36 42 48 54 Q m3
/h
0
5
10
15
20
25
30
35
40
45
50
55
60
H
m
0
100
200
300
400
500
600
P
kPa
0 100 200 300 400 500 600 700 800 900 Q l/min
0 1 2 3 4 5 6 7 8 9 10 12 13 14 15 16 Q l/s
0
20
40
60
80
100
120
140
160
180
200
H
ft
0 20 40 60 80 100 120 140 160 180 200 220 240 Q US gpm
0 20 40 60 80 100 120 140 160 180 200 Q IMP gpm
DCP2
A
D DNA
C1
L1 L2
L
DNM
S1
D1
D2
S2
D3
C2
B1 B2
B
H
H1
I
M (4)
60209274 - 11/2022
Via Marco Polo, 14 - 35035 Mestrino (PD) Italy - Tel. +39.049.5125000 - Fax +39.049.5125950
www.dabpumps.com
On-line selection tool
DAB PUMPS LTD.
6 Gilberd Court
Newcomen Way
Severalls Business Park
Colchester
Essex
CO4 9WN - UK
salesuk@dwtgroup.com
Tel. +44 0333 777 5010
DAB PUMPS B.V.
Albert Einsteinweg, 4
5151 DL Drunen - Nederland
info.netherlands@dwtgroup.com
Tel. +31 416 387280
Fax +31 416 387299
DAB PUMPS SOUTH AFRICA (PTY) LTD
Twenty One industrial Estate,
16 Purlin Street, Unit B, Warehouse 4
Olifantsfontein -1667 - South Africa
info.sa@dwtgroup.com
Tel. +27 12 361 3997
DAB PUMPS GMBH
Am Nordpark 3
D - 41069 Mönchengladbach - Germany
info.germany@dwtgroup.com
Tel. +49 2161 47388-0
Fax +49 2161 47388-36
DAB PUMPS POLAND Sp. z o.o.
Ul. Janka Muzykanta 60
02188 Warszawa - Poland
polska@dabpumps.com.pl
DAB PUMPS BV
‘tHofveld 6 C1
1702 Groot Bijgaarden - Belgium
info.belgium@dwtgroup.com
Tel. +32 2 4668353
DAB PUMPS IBERICA S.L.
Calle Verano 18-20-22
28850 - Torrejón de Ardoz - Madrid
Spain
Info.spain@dwtgroup.com
Tel. +34 91 6569545
Fax: + 34 91 6569676
DAB PUMPS INC.
3226 Benchmark Drive
Ladson, SC 29456 - USA
info.usa@dwtgroup.com
Tel. 1- 843-797-5002
Fax 1-843-797-3366
DAB PUMPS HUNGARY KFT.
H-8800
Nagykanizsa, Buda Ernő u.5
Hungary
Tel. +36 93501700
DAB PUMPS (QINGDAO) CO. LTD.
No.40 Kaituo Road, Qingdao Economic
& Technological
Development Zone
Qingdao City, Shandong Province - China
PC: 266500
sales.cn@dwtgroup.com
Tel. +86 400 186 8280
Fax +86 53286812210
DAB PUMPS DE MÉXICO, S.A. DE C.V.
Av Amsterdam 101 Local 4
Col. Hipódromo Condesa,
Del. Cuauhtémoc CP 06170
Ciudad de México
Tel. +52 55 6719 0493
DAB PUMPS OCEANIA PTY LTD
426 South Gippsland Highway,
Dandenong South VIC 3175 – Australia
info.oceania@dwtgroup.com
Tel. +61 1300 378 677
PT DAB PUMPS INDONESIA
Satrio Tower lantai 26
unit C-D, Jl. Prof. Dr. Satrio Kav. C4,
Kel. Kuningan Timur, Kec. Setiabudi, Kota Adm.
Jakarta Selatan, Prov. DKI Jakarta. - Indonesia
Tel. +62 2129222850