User Manual
(ForAVR Series Voltage Stabilizer)
ProductIntroduction .1/9
Installation Wiring.. .3/9
Operation Guide. .4/9
Equipment Cautions. .6/9
Maintenance&Fault. .7/9
ImportantNotice:
When the voltage stabilizer's LCD displays an alarm and the buzzer sounds,immediately save the device data,shut down the equipment, and arrange for professionals to inspect the power grid lines and troubleshoot. The voltage stabilizer willcut off the main power supply within 5 minutes!!!
1. Product Introduction
1-1. Overview and Characteristics
This product isanewlydeveloped next-generation inteligentvoltage stabilizer.ItemploysDSP-based measurementchip control,fstACmplig,rosigrntsicngndapdmpeatioageablionoytating intellientinstrumentation,fastvoltagesabilzation,ndfultdagnosisfunctions.Teoreconfigurationicludesaniolation transformer, SVC voltage stabilization module,MCU control core ^ + high-precision sampling components,and safety protection devices,oferingadvantages insfety,eficiency,precision,energyconservation,andenvironmental protection.
(1)SmartLCD display:The smart meter provides real-time readings of line voltage,phase voltage,current,frequency, temperature,andoperational status with highresolution.Featuringa thin-filmbutton for intuitive operation,it ensures safety and reliability.
(2)Three-phase demodulation: The output voltage imbalance is less than 1 % ,ensuring the accuracy of the output voltage for each phase remains constant.
(3)Wideapplicability:Thevoltage regulationrange isbroad,whichcanmetthe needsofpowersupplyand grid quality is poor, voltage fluctuation range is large places and equipment.
(4) Intelligent sampling: The microcontroller-based sampling circuit ensures precise sampling.
(5)The protector features comprehensive protection:it displays and safeguards against faults includingoverload, overvoltage,undervoltage,shortcircuit,andoverheating,ensuring safeoperationofboth the voltagestabilizerandits load.
(6)Powerful preset features: Protection limits can be set freely.
(7)High overload capacity: The system employs premium components with excelent performance,capable of continuous operation at 80 % rated load and enduring a 1-minute instantaneous overload (1.5 times rated load) without damage.
(8)Adaptability:Ithas strongadaptability to powergridand load,andcan work reliablyandcontinuouslyunder various harsh power grid and complex load conditions.
(9)No distortion: Compensated voltage regulation method,no waveform distortion
(10)Low power loss:The system achieves minimal energy consumption with no-load loss below 0 . 5 % ,delivering substantial savings on electricity bills for customers.
(11)Bypass function for easy maintenance:Switchesbetween'voltagestabilization'and'direct bypass power supply'for convenient troubleshooting.
1-2.Environmental Requirements
(1)The voltage regulator should be used indoors with good ventilation and a flat,solid floor.
(2)No conductive or explosive dust,nocorrosive metals,or gases,vapors,oroil mists that may damage insulation. (3)The rated capacity decreases with altitude.(If the altitude exceeds 1 0 0 0 { m } ,the rated capacity is reduced.)
(4) The ambient temperature ranges from- 5 ^ { \circ } C to + 4 0 ^ { \circ } \mathsf C ,with adaily average <= 3 0 ^ { \circ } C and an annual average <= 2 5 ^ { \circ } C .The temperature variation rate of the working environment should be <= 5 { K / h } .(Note: The overload capacity will decrease.) (5)Relative humidity: { <= } 9 0 % { R H } (no condensation at 4 0 ^ { \circ } { C } ~ ± ~ 2 ^ { \circ } { C } )
(6)The waveform of the power supply voltage is approximately a sine wave (THD <= 4 % )
(7)The transient peak voltage (Vp-p) in the power grid is <= 2 0 0 0 { V } , and there are no lightning strikes.
(8)Exposure to radioactive radiation should be avoided.
(9)Avoid abnormal mechanical stresses such as impact and vibration.
(10)Multiple voltage stabilizers should not be operated in parallel.
(11)Suffcientspace forheatdissipationand maintenance shouldbereservedaroundandonthetopofthevoltageregulator. ■Note: If anyspecialusage conditions that do not meet theabove requirements aply,please negotiate with the seller during ordering or contact us at any time during use
1-3.Technical Parameters
| Rated capacity:see the nameplate on the fuselage | Phase: Three-phase or single-phase | Output voltage: See label |
| Input voltage range: | Three-phaseV ±15%|Three-phaseV ±20%|Three-phaseV ±30% | |
| Single-phaseV ±15%|Single-phaseV ±20%|Single-phaseV ±30% | ||
| Voltage regulation accuracy: ± | Efficiency:≥99% | Frequency: The input/output frequency is 45 to 65Hz |
| 2% Response time: | Stabilization speed:100 ms | Insulation resistance:The overall insulation resistance to ground exceeds 5MΩ. |
| Insulation class: E | Display: LCD screen digital display | Output waveform: The output waveform is |
| Instantaneous overload capacity:1.5 times rated | Cooling method: Temperature-controlled | Protection functions: overload, overvoltage, undervoltage,phase loss,and short-circuit |
| Mode: Long-term | forced air cooling protection Insulation strength:25ooV/sinusoidal AC voltage for1 minute without flashover or | |
2. Installation Wiring
·Before installing and wiring,always disconnect the power supply to prevent electric shock and accidents.
·The product must be installed and tested by trained electricians with proper certification.
2-1.Pre-installation Check
(1)Check if the product model and specifications match yourorder details,especially capacity and input/output voltage values.
(2)Check whether the factory documents (manual, certificate of conformity,etc.) and the items agreed to be delivered under the order are complete.
(3) Check whether the electrical components in the voltage regulator cabinet are damaged during transportation.
(4)Ensure all fasteners are securely fastened and wiring remains intact.Tighten the control plug to prevent poor contact.
(5)Upon delivery,users should unpack,inspect,and install the voltage stabilizer within one month to prevent quality degradation from prolonged storage.
Attached wiring diagram:
ill TIIIIIII ④+++ RSTNUVWNG= InputPower OutputPower
PowerSwitch
2-2. Installation Wiring
(1) Positioning:
Afterpassing inspection, the equipment shall be stably positioned to prevent damage to the housing and internal components;the chassis shall bear uniform loads,with sufficient ventilation and maintenance space reserved around it.
(2) Cable selection:
Cableselection:Selectcompatiblecablesand connectors (to ensure reliable connections),considering factors such as load rate,current-carrying capacity,heat dissipation,environmental conditions,installation method, and transmission length.The wire gauge should be determined based on the voltage regulator's capacity(with adequate margin).Copper wire is recommended,with a selection standard of 3 . 5 { A } / {mm } ^ { 2 } :
(3) Cable connections:
Cable connections: Connect the input line to the "Input (R/S/T)" terminal,the load line to the "Output (U/V/W)" terminal,and the neutral line to the "N" terminal (no neutral connection required for no-load circuits).The chassis ground wire should be connected to the "=" marked position.
4 1.The wiring diagram is for reference only; the actual voltage regulator markings shall prevail.
2.Strictly folow terminal markings for wiring:Do not reverse input/output and phase/neutral wires,avoid CAUTION confusing neutral with ground,and never omit the ground wire.Incorrect connections may cause equipment failure or damage.
3.The neutral wire must be properly connected (please specify any equipment thatdoes not require a neutral wire when placing your order).
4.The wiringand connections from thepower supply tothevoltage regulatorand fromthevoltageregulator to the load must ensure good contact,be sturdyand reliable,andbe capable ofcarrying the equipment's rated current.
3.Operation Guide
3-1.Function Operation Instructions:
Main features:
① Input voltage display;
② Output voltage indication;
③ AC current display;
④ SET:Function menu key and confirmation key;
⑤ Decrease↓: The key to reduce;
⑥ Increase↑:The key to increase;
⑦ Manual/automaticmode switching;
⑧ Voltage stabilization and bypass; ⑨ Switch: The key to toggle display mode;
{10} Parameterdisplayarea:
① Status display area:
Temperature, frequency,overcurrent, overvoltage, undervoltage,phase loss,motor and other fault indicators.
{12} The voltage regulator power switch;
{ 1 3 } Input terminals (R/S/T);
{14} Output terminals (U/V/W);
{15} Manual bypass switch;
3-2. Control Panel Settings:
All voltage settings must be phase voltage settings.Do not use line voltage settings.Remember!
1) Set the stable voltage for U, V,and W phases:
4/9
@ Copyright 2025
This functionsets the stableoutput voltage foreachphase.It is presetbydefaultandcanbereset as needed.Theoperation is as follows:
1.Hold the SETbutton for 5seconds,thenrelease.Wait until thevoltage setting,Aphase,and 2OV indicators flash simultaneously. Adjust the value using the plus/minus keys to complete the U phase seting.
2.Pressthe SETbuttonagainuntilthe "Voltage Setting","BPhase"and "22OV"indicatorsflash.Usethe plus/minus keysto adjust and finalize the V-phase setting.
3.Pressthe SETkeyuntil the voltage seting,Cphase,and22OVindicators flash,thenadjust withtheplus/minus keys to finalize the W phase configuration.
After completing the three-phase parameter settings,press the Switch button to save and exit.
2) Overcurrent protection threshold setting:
This function ensures thesafeoperationof thevoltage stabilizerand load.The protection value is presetbydefault and can be reset as needed.The operation is as follows: Holdthe SETkeyfor5seconds,thenrelease.Press theSETkeyfourtimes insuccessionuntil the'CurrentSeting' indicator in the lowerright cornerflashes.Adjustthe value using the plus/mius keys,then press the Switch keytosave and exit.
3) Overvoltage and undervoltage protection threshold settings:
Thisfunction prevents thevoltageregulator fromexceeding itsoutput range,ensuringsafe loadoperation.Theprotection threshold is preset by the manufacturer and can be reset as needed.The operation is as follows: HoldtheSETkey for5seconds,then release.Press the SETkeysix times in succession until the "Overvoltage Seting" indicatorin the lower rightcornerflashes.Adjust the value using the plus/minus keys.Pressthe SETkeyagain until the "Undervoltage Setting" indicatorflashes.Adjust the value using the plus/minus keys.Finall,pressthe Switch keyto save and exit.
4) Voltage stabilization accuracy setting:
This parameter is factory presetand canbereset as needed.Toreset: Holdthe SETbutton for5seconds,then release.Pres the SETbutonrepeatedlyuntilthe8th pressand waitforthe'Precision Seting'indicatorinthelowerrightcorertoflash. Adjust the value using the plus/minus keys (where n represents ± \mathsf { n V } output voltage).Finally, press the Switch button to save and exit.
5) Voltagecalibration
Iftheoutputphasevoltagedifersfromthedisplayedvoltage,calibrationcanbeperformed.Thefactorypresetisasfollows: Holdthe SETbuttonfor5seconds,thenrelease.Pressthe SETbutoncontinuouslyuntilthe1Othpress,whenthe'A'iconin the upperright corner willflash.Adjust thedisplayed value using the plus/minus keys until it matches the actual output voltage of phase U relative to phase N.
Pressthe SETkeyagain,andthe'B'willflashattheupperrightcorner.Usetheup/down keystoadjust thedisplayedvalue until the current voltage matches the output voltage relative to N.
Press theSETkeyagain,and the'C'willflashattheupperrightcorner.Adjust the displayed value using theup/down keys until the current voltage matches the output voltage relative to N.
Pressthe SETkeyagain,and the'ABC'willflashattheupperrightcorner(input voltage).Adjustthe displayvalueusing the up/down buttons until the current voltage reading matches the input voltage relative to N.
Note: Calibrate by monitoring the voltage withamultimeter inreal time.Switch to manual mode foroperation.Avoid adjustments unless necessary to prevent numerical errors that may affect voltage stabilization.
6) Display voltage switching operation:
Pressthe "switch"button for2seconds,thenreleaseit.The system willsequentiallydisplaythevoltage valuesofthenext phase,and you can switch between the phase voltage and line voltage display values.
7) Switching operation between "AVR" and "BY PASS" for voltage regulation and bypass:
Pressand holdthe "AVR/PASS"button for3seconds,then release to enter manual bypass mode with the "PASS" indicator light on.Pressand holdthe "AVR/PASs"buton for another 3 seconds,then release to activate the "AVR" voltage stabilization mode with the "AVR"indicator light illuminated!
8) Manual and automatic mode switching:
Pressand holdthe "AUTO/MANUAL"butonfor3 secondsto switch tomanual mode.Pressand hold the "AUTO/MANUAL"buton for another3 seconds to activate the "AVR"voltage stabilization mode.In manual mode,you can manually adjust the voltage by pressing the increase/decrease buttons.
4. Equipment Cautions
The following special precautions are esential for your personal safety and the safe use of the product and connected devices.Please read them carefully before use and strictly follow them during use.
(1)Onlycertified electricians may install,operate,or maintain thisequipment.Unauthorizedpersonnelarestrictly prohibited from handling it.
(2)Before instalationor maintenance,completely disconnect the input power supply.Ensure all wiring issecurely fastened to prevent disconnection,sparking,contact oxidation,orautomatic bypass.Arange the wiring rationall to avoid tripping or abrasion.
(3)Proper grounding mustbeensured.The grounding wire must notbe connected to public utilities such as heating,water
supply,or gas.Anysafety incidents caused byfailure to ground the wire shall be theuser's sole responsibility.
(4)Do not disassemble the chasis,touch internal components,orunplug cables during operation.Avoid handling the devicewith wet hands.Never standon the chassis orplace heavy objects inside.Strictly preventconductive debris from entering the enclosure.
(5)Unauthorized disassemblyor modification is prohibited.Do not clean with corrosive orcorrosive solvents.Do not pile items around the equipment. Ensure good ventilation.
(6)Ifthe device is not used foralongtime,the power switch should be turnedoffand the external wiring removed.
(7)Select equipment based on actual power consumption with a margin, ensuring voltage harmonic content <= 1 0 % .If the power factor or voltage is too low,reduce the capacity.
(8)The input voltage may fluctuate within ± 1 5 % to 30 % (based on the product specifications).
(9)Lightning protectiondevices must be installed inareas prone tolightning strikes.Please specifythis requirement when placing your order.
5.Maintenance & Fault
5-1.Daily Maintenance:
4 CAUTION
Before performing maintenance, always disconnect the power supply to prevent electric shock or other safety hazards.
Conduct regular inspections of the voltage stabilizer's operational status during use:
Duringinspection,verifywhether thevoltagedisplayedbythevoltagestabilizer,theload(notexceedingtheratedvalue), andthe inputvoltage(not exceedingtheallwablefluctuationange)arenormal.Ifabnormalitiesaredetectedaddress tem promptly.For issues thatcannotberesolved immediatelynotify the supplieror manufacturer tocoordinateasolution to prevent equipment damage.
Regular maintenance of the voltage stabilizer is recommended, including:
Regularlyclean the voltage regulatorsstabilizingcomponents (removingdustanddirt to prevent moisture-inducedcontrol circuit failures),inspectthechais'sfastenersandconnection terminals (addressaylosenessorpoorcontact promptly), and repair or replace faulty/damaged components immediately.
5-2. Fault Handling:
4 CAUTION
Before performing maintenance,always disconnect the power supply to prevent electric shock or other safety hazards.
| Phenomenon | Cause | ProcessingMethod |
| The output voltage is unstable. | 1.The voltage setting may be incorrect. 2.The output voltage display value differs from the actual measured value. | Check if the system voltage setings are correct. Use a multimeter to measure the output voltage of each phase of the three-phase system and verify if it matches the displayed value.If not,refer to the voltage calibration method. |
| Systembypass | The machine is malfunctioning. | ①Re-circuit breaker; if an alarm occurs, check the alarm message. |
| Overvoltage alarm Undervoltage alarm Phase loss alarm | ① Input phase loss, ② The input voltage is too low. ③ The output display value is different from the measured value. | ①Check for phase loss in the input signal. If detected, the cause should be investigated bya qualified technician. ② Verify if the input voltage falls within the regulator's minimum input range; if not, replace with a device offering a higher voltage regulation range. ③ Use a multimeter to measure the output three-phase voltage and confirm it matches the displayed value; if discrepancies exist,refer to the voltage |
| Overcurrent alarm The voltage regulator has an odor. | Overload. The transformer coil overheats and | calibration procedure. You need to upgrade to a larger model. Report the issue to the manufacturer. |
| The display panel shows no values after startup, but voltage regulation is normal. | ① Poor contact of the communication cable between the display board and the motherboard; ② Display panel malfunction; | ① Reconnect the display cable; ②Replace the display panel; |
| Unstable voltage after new installation | The wiring is incorrect, or the neutral wire is not properly connected. | Check if the phase and neutral wires are properly connected and if the neutral wire is properly connected. |
| switch trip | The front-end switch current is insufficient,or there is a wiring error. | Check the wiring for accuracy and verify that the switch's rated capacity matches the machine's rated current,ensuring the switch exceeds the machine's rated current. |