101
Diameter of outer connecting pipe
ODU Main pipe and branch pipes
Remark:
1. Please select the main pipe diameter of the outdoor unitfollow the above table. If the main pipe is larger ,
choose the main pipe according to larger one.
2. If the system is more than 108HP,please consult technical personnel.
Model Gas Liquid
TMV-Vd+252(280)W/N1S-C(E3) φ25.4(welding) φ12.7(welding)
TMV-Vd+335(400/450/504)W/N1S-C(E3) φ28.6(welding) φ15.8(welding)
TMV-Vd+560(615/680/730)W/N1S-C(E3) φ31.8(welding) φ19.1(welding)
TMV-Vd+785(850)W/N1S-C(E3) φ34.9(welding) φ19.1(welding)
ODU stop valve port diameter(Number: g1,g2,g3,g4)
Capacity of Outdoor
Units(HP)
Dimensions of Master Pipe, when the equivalent
lengthof all supporting pipes is less than 90 meters
Dimensions of Master Pipe, when the equivalent lengthof all
supporting pipes is 90 meters at least
Gas/Liquid-side Indoor Branch Pipe 1
(Gas/Liquid-side) Gas/Liquid-side Indoor Branch Pipe 1(Gas/Liquid-side)
8HP 19.1/9.52 Assembly BY01(G01/L01) 22.2/12.7 Assembly BY01(G01/L01)
10HP 22.2/9.52 Assembly BY01(G01/L01) 25.4/12.7 Assembly BY01(G01/L01)
12-14HP 25.4/12.7 Assembly BY01(G01/L01) 28.6/15.9 Assembly BY03(G02/L02)
16HP 28.6/12.7 Assembly BY02(G02/L01) 31.8/19.1 Assembly BY03(G02/L02)
18-22HP 28.6/15.9 Assembly BY03(G02/L02) 31.8/19.1 Assembly BY03(G02/L02)
24-26HP 31.8/19.1 Assembly BY03(G02/L02) 38.1/22.2 Assembly BY04(G03/L02)
28HP 34.9/19.1 Assembly BY04(G03/L02) 38.1/22.2 Assembly BY04(G03/L02)
30-32HP 38.1/19.1 Assembly BY04(G03/L02) 41.2/22.2 Assembly BY05(G04/L03)
34-48HP 38.1/19.1 Assembly BY04(G03/L02) 41.2/22.2 Assembly BY05(G04/L03)
50-54HP 38.1/19.1 Assembly BY04(G03/L02) 44.5/22.2 Assembly BY05(G04/L03)
56-66HP 41.2/22.2 Assembly BY05(G04/L03) 44.5/22.2 Assembly BY05(G04/L03)
68-72HP 44.5/22.2 Assembly BY05(G04/L03) 50.8/25.4 Assembly BY08(G05/G02)
74-84HP 50.8/22.2 Assembly BY05(G04/L03) 50.8/25.4 Assembly BY08(G05/G02)
86-96HP 50.8/25.4 Assembly BY08(G05/G02) 54.0/28.6 Assembly BY08(G05/G02)
98-108HP 54.0/28.6 Assembly BY08(G05/G02) 63.0/28.6 Assembly BY08(G05/G02)
102 Remark :1.The wire diameter and continuous length in the table are applicable to a maximum distance of 20 meters. If the power wiring exceeds
20 meters and the voltage drop exceeds the range of 2%, please choose a wire diameter with a larger cross-sectional area.
2.The selection of the power cord is based on the ambient temperature of 40°C.
3.The wire current carrying capacity in the attached table is only for the user's reference. The actual interception capacity of the wire
varies depending on the type and length of the cable, the way of pipe penetration, and the actual laying environment, and the correction
factor is different.
Distribution transformer
Outdoor power
Ground1 Ground2 Ground3
Building
Lightning
arrester Ground wire
Junction box
Leakage protector
Manual switch
Electrical system and installation
Please design the dedicated power supply for IDU and ODU separately.
In order to reduce interference, it is recommended to use two-core shielded cables for the signal cables of the IDU and
ODU. Please do not use multi-core cables without shielding.
The power supply should be equipped with a leakage protector and a manual switch.
During installation, the communication line and the power line must not be intertwined, and must be routed separately,
and the minimum distance should be greater than 20CM, otherwise the communication of the unit may be abnormal.
Power wiring must be entrusted to professional electricians.
The power supply, leakage protector and manual switch of the IDU connected to the same ODU are required to be
universal. (Please use the same circuit for the IDU power supply of the same system. And it must be turned on and off at
the same time, otherwise it will seriously affect the service life of the system, and unpredictable situations may occur. )
Please integrate the IDU and ODU connection wiring system and refrigerant piping system into the same system.
Electrical wiring precautions
ODU power wiring
ODU power connection
()a
L1
L2
L3
N
PE
Model Power supply Minimum wire
diameter current(A)
Copper core PVC
insulated wire BVV
(mm2)
Copper core XLPE
insulated wire YJV
(mm2)
Manual switch (A)
capacity
Leakage
protector
TMV-Vd+252W/N1S-C(E3) 380V 3N ~ 50Hz 19.5 4.0X5 4.0X5 32
< 100mA
0.1sec
TMV-Vd+280W/N1S-C(E3) 380V 3N ~ 50Hz 21.6 4.0X5 4.0X5 32
TMV-Vd+335W/N1S-C(E3) 380V 3N ~ 50Hz 24.9 6.0X5 4.0X5 32
TMV-Vd+400W/N1S-C(E3) 380V 3N ~ 50Hz 26.5 6.0X5 4.0X5 32
TMV-Vd+450W/N1S-C(E3) 380V 3N ~ 50Hz 32.2 10.0X5 6.0X5 40
TMV-Vd+504W/N1S-C(E3) 380V 3N ~ 50Hz 34 10.0X5 6.0X5 40
TMV-Vd+560W/N1S-C(E3) 380V 3N ~ 50Hz 41.8 16.0X5 10.0X5 50
TMV-Vd+615W/N1S-C(E3) 380V 3N ~ 50Hz 42.9 16.0X5 10.0X5 50
TMV-Vd+680W/N1S-C(E3) 380V 3N ~ 50Hz 45.5 16.0X5 10.0X5 50
TMV-Vd+730W/N1S-C(E3) 380V 3N ~ 50Hz 46 16.0X5 10.0X5 50
TMV-Vd+785W/N1S-C(E3) 380V 3N ~ 50Hz 48 16.0X5 10.0X5 50
TMV-Vd+850W/N1S-C(E3) 380V 3N ~ 50Hz 56.8 25.0X3+16.0X2 16.0X5 63
Installation options
103
Signal lines must be shielded. Using other wires may cause signal interference and cause malfunction.
The shielding nets of all shielded wires are connected to each other and finally connected to the sheet metal ground at
one point.
It is forbidden to bundle signal wires, refrigerant pipes, power wires, etc. together. When the power line and the signal
line are laid in parallel, they should be kept at a distance of more than 300mm to prevent the signal source from
being disturbed.
Please use two-core shielded wire ( ≥ 0.75mm²) for the signal cable of indoor and outdoor units, without polarity.
The signal cable of indoor and outdoor units should be connected as far as possible from the end of the outdoor unit.
Signal lines cannot form a closed loop.
The signal line has no polarity, and there is no need to distinguish it when wiring.v
Remarks: The wiring diameter and continuous length in the table indicate that the voltage drop is within 2%. When the continuous wiring
length exceeds the value in the table, please follow the relevant regulations to select the wire diameter.
Remarks:
1. Please use the refrigerant piping system, the indoor unit-indoor unit room, and the indoor unit-outdoor unit connection signal line as the
same system.
2. All the internal units in the same system must be powered in a unified manner, and some internal units cannot be cut off, otherwise the
unit will fail.
3. When the power cable and the signal cable are parallel, please put the wires into their respective wire ducts, and leave a suitable distance
between the wires. (Distance between power cables: 300mm below 10A, 500mm below 50A)
4. When multiple outdoor units are connected in parallel, the main outdoor unit must be set. (Refer to the settings of the DIP switch)
IDU power wiring
Control system and installation
IDU and ODU signal line wiring
Power Leakage Protector Manual switch Junction box IDU
Model Power supply
Minimum wire diameter(mm²) Manual switch
Leakage
protector Dimensions
(Continuous Length)
Dimensions
(Continuous Length)
Ground
wire Capacity Fuse
All IDU Model 220V ~1N
50Hz
2.5
(30m)
4.0
(50m) φ1.6mm 30 15 20A、30mA
< 0.1sec
ODU(Host) ODU(Slave1) ODU(Slave2)ODU(Slave3)
Signal line between ODU
The last one needs to be shorted with a matching resistor at the RP position on the control board.
Signal line between IDU
104 Projects
Government
Business
Education
Vietnam Industrial Park
National University of Defense Technology
India Office Building Uzbekistan Electronic Factory
Customs Inspection Centre National tax building Archives center
Tianjin Nankai High School Southern University of Science and Technology
TCL CAC insists on frequency conversion and energy saving tecnology, cooperates with top enterprises in the industry,
independent innovation and technological change. TCL VRF is widely used in public places such as residences, factories,
shops, etc. The sample projects are all over the world, creating an energy-saving, comfortable and healthy living environment
for users.
\"The Growing of the Great Brand\" strategy and craftsman spirit
To create high-quality professional projects
105
Public utilities
Real estate
Transportation
Hospital
Olympic Game Stadium Shanghai World Expo Asia Game Stadium
Cambodia JINXIN International Casino Cambodia Country Hotel Changchun Wanda Plaza
Kunshan South Railway Station Nanchang West Railway Station LangZhong Railway Station
The Third People's Hospital of Shenzhen Shenzhen Guangming Hospital The First Hospital of Jiaxin
China
V26.09.17
GD TCL INTELLIGENT HEATING & VENTILATING EQUIPMENT CO.,LTD.
Address: No.7 Yuanlin Road, Nantou, Zhongshan, Guangdong, PR China
Web: cac.tcl.com E-mail: hvac@tcl.com
TCL CAC TCL CAC TCL CAC HVAC-TCL TCL- CAC