In the G0 zone, press the button on the S page to enter the setting page,After adjusting the required
pressure using button, press the button to confirm.
4) Enter the St zone
In the G0 zone P page, press and hold and for 3 seconds at the same time. In the ST parameter
group, press again for 3 seconds at ST-01 to exit the St zone.
5) Lock screen function
In the G0 zone P page, press and hold and for 3 seconds at the same time. The \"Manual\" light
flashes for 2 seconds, indicating that the setting is successful. After the \"Lock Screen\" function is turned on,
only some operations can be performed (setting pressure, frequency setting in manual mode, starting and
stopping, checking the status of G0 zone), and it is impossible to enter G2~G7 zoneea. When the operation
enters the secondary menu, \"Alarm 1\" flashes for 1 second as a reminder. The unlocking steps are the
same as locking. After successful unlocking, the \"Manual\" light flashes.
5.2.4 Basic parameters setting
Chapter 5 Operation
3) Pressure setting
Setting range
0.0~45.0 bar / 0.00~4.50 Mpa
0.0~45.0 bar / 0.00~4.50 Mpa
0~480 hz
0.0~100.0 kW
0~1000 V
0.0~100.0 A
-5.0~ 45.0 bar / -0.50~ 4.50 Mpa
0.0 ~ 5.0 m
Display Name
G0-01
G0-02
G0-03
G0-04
G0-05
G0-06
G0-07
G0-08
Measuring pressure
Pressure setting
Output Hz
Output Power
DC Voltage
Output Current
Inlet pressure
Inlet water level
33
25
Chapter 6 Function Table and Description
6. Function Table and Description
Modify
or not
Link
or not Remark
The outlet pressure sensor with small ID number is mainly.
The outlet pressure sensor with a higher ID number is auxiliary.
Name
Actual pressure X O
O O
△ X
X X
X X
X X
X O
X O
Pressure setting
Output Hz
Output power
DC voltage
Output current
Inlet pressure
Inlet water level
Parameter Display
P
S
H
o
U
A
I
L
6.1 Status List
Can be set on any device.
Output power of the inverter.
-
-
Displayed when there is no selection in the system:----
Displayed when there is no selection in the system:----
In automatic mode, you can only view but not modify.
In manual mode, it becomes settable (target frequency).
Note: If “inlet water pressure” and “inlet water level” are not defined in the system, they can be hidden.
34
26
Chapter 6 Function Table and Description
Parameter
linkage Display
G2-01
G2-02
G2-03
G2-04
G2-05
G2-06
G2-07
G2-08
G2-09
G2-10
G2-11
G2-12
G2-13
G2-14
G2-15
G2-18
G2-19
G2-20
G2-21
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
○
Change
during
running
Description
×
×
×
×
×
×
○
○
×
×
○
○
○
○
○
×
Control mode 0:Manual 1:Automatic
0:Normal operation
1:Average distribution operation
0: ID sequence 1:Accumulated
power 2:Accumulated time
Auxiliary water pump filling waiting
time
Conditions for entering energy
saving mode
Conditions for entering energy
saving mode
Time to enter energy saving mode
Pressure deviation value at startup
Minimum output frequency at startup
Minimum output frequency at
shutdown
PID proportional constant
PID integral constant
PID differential constant
0:Not used 1~36 H forced alternating
operation time
Conditional frequency when alternating
from main pump to auxiliary pump
Conditional time when alternating from
main pump to auxiliary pump
Number of water pumps that can be
put into use
Number of resets after alarm
Waiting time for reset after alarm
Operation mode
Switch mode
Pump adding delay
Energy-saving frequency
Energy-saving current
Energy-saving delay
Pressure deviation
value set
Start frequency
percentage
Minimum frequency
percentage
P
I
D
Forced alternating timing
Main pump switching to
auxiliary pump percentage
Main pump switching
to auxiliary pump delay
Alarm recovery delay
Name Setting range
0~1
0~1
0~2
0~600 sec
1~100%
1~100%
0~600 sec
0.0~3.0 bar
0.00~0.30 Mpa
0~80%
0~70%
0.0~100.0
0.0~100.0
0.0~100.0
0~36 H
1~100%
1~6 units
0~600 sec
Factory
value
1
0
0
15
50
100
30
0.3bar
0.03Mpa
50%
40%
2.0
1.0
0.0
24
60%
10 ○ ○
6
G2-16
○ ×
Number of running
units limit
0~100 times 3
G2-17
○ ×
Alarm recovery times
0~600 sec 5
Forced alternation function at
scheduled time
Forced alternating
mode ○ × 0:Duration
1:Time 0
Setting function at scheduled time Forced alternating
time 00:00~23:59 02:00 ○ ×
6.2 Pump control area
35
27
Chapter 6 Function Table and Description
Value setting Parameter name
Normal operation
Average distribution operation
0
1
Value setting Setting range
15(Factory value) 0~600 sec
Value setting Parameter name Association parameter
ID sequence
Accumulated power
Accumulated time
0
1
2
Parameter name Related parameters
Manual
Automatic
(Factory value)
G0-03
G4-03
G4-01
G5-01
G5-03
G5-04
G5-02
Output Hz
Frequency input method
Communication ID
Outlet sensor mode
Outlet sensor minimum value
Outlet sensor maximum value
Outlet sensor correction value
Target frequency input
Target frequency input method setting
Set communication ID
Configure outlet sensor
Value setting
0
1
6.2.1 Pump control area function description
1:Control mode
Set the pump control mode.
2:Operation Mode
To further improve the energy saving effect function.Normal operation is to use one driver as the main controller and
only one pump in PID control variable frequency mode. The average distribution operation mode is an operation mode
in which all linked pumps distribute the total output rate to all linked pumps according to the PID control method. The
average distribution mode operation function can only be used when the diameters of the system pipes are the same,
and it has the advantage of preventing the main driver from running continuously for a long time.
3:Mode Switching
Pump changing sequence in linkage operation.
4:Pump Adding Delay
Specially refers to the function of delaying the adding of pumps when the standby pump is in linkage
operation. It is a preventive measure to prevent the high pressure event caused by the operation pressure
lag and the standby pump operate when a pump reaches the maximum output frequency.
G2-14: Forced standby timing
If the forced alternation time is set to 0,
the pump changing mode will be invalid.
36
28
Value setting Setting range
100(Factory value) 1~100%
Value setting Setting range
30(Factory value) 0~600 sec
Value setting Setting range
0.3(Factory value) 0~3.0
Chapter 6 Function Table and Description
6:Energy-saving current
Value setting Setting range
50(Factory value) 1~100%
5:Energy-saving frequency
7:Energy-saving delay
8:Set pressure deviation value
Value setting Setting range
50%(Factory value) 0~80%
9:Startup frequency percentage
Value setting Setting range
40%(Factory value) 0~70%
10:Minimum frequency percentage
ㆍThe minimum output frequency of the drive when it stops.
Note: The minimum output frequency must be less than the start output frequency.
ㆍSensing low flow. If the output frequency% is lower than the energy-saving frequency%, it is considered a low flow state.
ㆍExample: After the operating pressure reaches the set pressure, the output frequency is lower than the energy-saving
frequency% and is considered a low flow.
ㆍSensing low flow, if the output current is lower than the energy-saving current, it is considered a low flow state.
ㆍExample: After the operating pressure reaches the set pressure, the output current is lower than the energy-saving
current, which is considered a low flow.
ㆍCurrent Pressure<pressure setting value-The pump starts running when the pressure deviation value is set.
ㆍCurrent Pressure≥pressure setting value-The pump starts to stop at the set pressure deviation value.
ㆍThe initial output frequency of the driver when it starts.
Note: The startup output frequency must be greater than the minimum output frequency.
ㆍDelay deceleration and shutdown conditions which are met energy-saving frequency/energy-saving power.
37
29
Chapter 6 Function Table and Description
Value setting Setting range
2.0(Factory value) 0~100.0
11:P
ㆍThe ‘P’ value in PID is the proportional constant.
Value setting Setting range
1.0(Factory value) 0~100.0
12: I
ㆍThe ‘I’ value in PID is the integral constant.
Value setting Setting range
0.0(Factory value) 0~100.0
13: D
ㆍThe ‘D’ value in PID is the differential constant.
Value setting Setting range
24(Factory value) 0:Not used 1~36 H
14:Forced alternating timing
ㆍWhen forced alternating timing is set, the pump will switch to another mode after the time is reached.
Value setting Setting range
60(Factory value) 1~100%
15:Main pump switching to auxiliary pump percentage
ㆍSpecially set the main pump switching to auxiliary pump conditions for energy-saving operation.
Value setting Setting range
10(Factory value) 0~600 sec
16:Main pump switching to auxiliary pump delay
ㆍSpecially set the main pump switching to auxiliary pump delay for energy-saving operation.
Value setting Setting range
6(Factory value) 1~6 units
17:Limit on the number of units that can be run
ㆍSet a limit on the number of units that can be run in automatic operation.
ㆍThe system will determine the maximum number of units that can be run based on the set value during operation.
38
30
Chapter 6 Function Table and Description
Value setting Setting range
3(Factory value) 0~100 times
18:Alarm recovery times
Value setting Setting range
5(Factory value) 0~600 sec
19:Alarm recovery times
ㆍFault reset based on alarm recovery delay after alarm。
Value setting Setting range
0(Factory value) 0:Duration 1:Time
20:Forced alternation mode
Value setting Setting range
02:00(Factory value) 00:00~23:59
21:Forced alternation time
ㆍForced alternation is realized according to the set time (hour/minute).
Parameter
linkage Display
G3-01
G3-02
G3-03
G3-04
G3-05
G3-06
G3-07
G3-08
○
○
○
○
○
○
×
○
Change
during
running
○
○
×
○
○
○
×
×
Outlet high pressure alarm deviation value
Outlet high pressure alarm delay
Outlet ultra-high pressure alarm absolute
value
Outlet low pressure alarm value
Outlet low pressure judgment number
Outlet low pressure alarm delay
Low water level probe detection
Low water level probe delay
Name Setting range
0.5~3.0 bar 0.50~0.30 Mpa
0~600 sec
0.0~45.0 bar 0.00~4.50 Mpa
0~25.0 bar 0~2.50 Mpa
0~600 sec
1~6 units
0~600 sec
0:Not used 1:Used
Factory value
2.0bar 0.2Mpa
5
16.0bar 1.60Mpa
0.5bar 0.05Mpa
1
20
0
3
6.3 Parameter protection area
ㆍThe number of times the machine can automatically restart after an alarm shutdown.
ㆍWhen the alarm times exceed the restart times setting value, the system will not be able to automatically restart when the
alarm occurs again.
ㆍForced alternation is realized according to the set time (hour/minute) or according to the duration (timing).
39
31
Chapter 6 Function Table and Description
Value setting Setting range
2(Factory value) 0.5~3.0
Value setting Setting range
5(Factory value) 0~600 sec
6.3.1 Function description of parameter protection area
1:Outlet high pressure alarm deviation value
2:Outlet high pressure alarm delay
G3-23
G3-24
Patrol start time
0:Not used 1:Used
-5~40℃
10∼25 %
1∼20 times 1 times ○ ×
○ ×
G3-22 1∼9999 H 120 H ○ ×
0
G3-25 Antifreeze frequency percentage
Antifreeze ambient temperature
setting
Patrol number
25% ○ ×
G3-26
Antifreeze function
1℃ ○ ×
G3-18
G3-19
○ ×
Inlet low water level alarm
recovery deviation value
Outlet pressure sensor diagnosis 0:Not used 1:Used
0:Not used 1:Used
0∼600 sec
0.6 ○ ×
5.0
G3-16
○ ×
Inlet high water level alarm value
5
G3-17
○ ×
Inlet high water level alarm delay
0
G3-20 Pressure setting limit 16.0bar 1.60Mpa ○ ○
G3-21 Patrol function 0 ○ ×
G3-14
G3-15
○
○
×
×
Inlet low water level alarm value
Inlet low water level alarm delay
Inlet sensor minimum to maximum value
Inlet sensor minimum to maximum value
Inlet sensor minimum to maximum value
0∼600 sec
0.6
5
G3-09
G3-10
G3-11
G3-12
G3-13
○
○
○
○
○
×
×
×
×
×
Inlet low pressure alarm value
Inlet low pressure alarm delay
Inlet low pressure alarm
recovery deviation value
Inlet high pressure alarm value
Inlet high pressure alarm delay
0~600 sec
Inlet sensor minimum to maximum value
0 to maximum value of inlet sensor
0 to maximum value of inlet sensor
Inlet sensor minimum to maximum value
0∼600 sec
0.3bar 0.03Mpa
5
0.3bar 0.03Mpa
16.0bar 1.60Mpa
5
ㆍSet the high pressure alarm function.
Note: If the outlet high pressure alarm deviation value is set to 2, the high pressure alarm value will automatically change
according to the set pressure value + 2bar.
ㆍWhen the high pressure alarm value is reached and the high pressure is maintained for more than the set time, the high
pressure alarm will be issued and the machine will be shut down.
40
32
Chapter 6 Function Table and Description
Value setting Setting range
16(Factory value) 0.0~45.0 bar
3:Outlet ultra-high pressure alarm absolute value
Value setting Setting range
0.5(Factory value) 0~25.0 bar
4:Outlet low pressure alarm value
ㆍOutlet low pressure alarm target value setting, also called explosion-proof pipe protection.
Value setting Setting range
1(Factory value) 1~6
5:Number of outlet low pressure judgment units
ㆍNumber of outlet low pressure alarm judgment units.
Value setting Setting range
20(Factory value) 0~600 sec
6:Outlet low pressure alarm delay
ㆍOutlet low pressure alarm alarm delay.
Value setting
0(Factory value)
7:Low water level probe detection
Setting range
0:Not used 1:Used
Value setting
3(Factory value)
8:Low water level probe delay
ㆍLow water level alarm signal maintenance time setting
Setting range
0~600 sec
Value setting
0.3(Factory value)
9:Inlet low pressure alarm value
Setting range
ㆍWhen the operating pressure reaches the outlet ultra-high pressure alarm absolute value, the alarm is
triggered.
Note: The alarm cannot be automatically reset.
ㆍThe low water level sensor will determine whether there is water in the pipe according to whether it is on or
off.
ㆍThe target pressure value that needs to be set when the inlet pressure sensor judges the low pressure
alarm.
Note: The inlet low pressure alarm value cannot be higher than the inlet high pressure alarm value.
Inlet sensor minimum to maximum value
41
33
Chapter 6 Function Table and Description
Value setting
0.3(Factory value)
11:Inlet low pressure alarm recovery deviation value
Setting range
0~Maximum value of inlet sensor
Value setting
16(Factory value)
12:Inlet high pressure alarm value
Setting range
Inlet sensor minimum to maximum value
Value setting
5(Factory value)
13:Inlet high pressure alarm delay
Setting range
0~600 sec
Value setting
5(Factory value)
15:Inlet low water level alarm delay
Setting range
0~600 sec
Value setting
0.6(Factory value)
14:Inlet low water level alarm value
Setting range
Inlet sensor minimum to maximum value
Value setting
5(Factory value)
10:Inlet low pressure alarm delay
ㆍWhen the inlet pressure sensor judges the low pressure alarm, the alarm signal maintain time setting
Setting range
0~600 sec
ㆍWhen the inlet pressure sensor alarms low pressure, restore the judgment setting.
Example: Actual inlet pressure >inlet low pressure alarm value + inlet low pressure alarm recovery deviation
value.
ㆍThe target pressure value to be set when the inlet pressure sensor judges the high pressure alarm.
Note: The inlet high pressure alarm value cannot be lower than the inlet low pressure alarm value.
ㆍWhen the inlet pressure sensor judges the high pressure alarm, the alarm signal maintenance time setting.
ㆍThe target water level value to be set when the inlet water level sensor judges the low water level alarm.
Note: The inlet low water level alarm value cannot be higher than the inlet high water level alarm value.
ㆍWhen the inlet water level sensor judges the low water level alarm, the alarm signal maintenance time
setting.
42
34
Chapter 6 Function Table and Description
Value setting
5(Factory value)
18:Inlet high water level alarm delay
Setting range
0~600 sec
Value setting
0(Factory value)
19:Outlet Pressure Sensor Diagnostics
ㆍSet the outlet pressure sensor diagnostic alarm settings.
Setting range
0:Not used 1:Used
Value setting
16(Factory value)
20:Pressure setting limits
ㆍThe set pressure range that can be set.
Setting range
0~Maximum value of outlet sensor
Value setting
0(Factory value)
21:Inspection function
ㆍA protective function to prevent the pump from malfunctioning due to long-term non-operation.
Setting range
0:Not used 1:Used
Value setting
0.6(Factory value)
16:inlet low water level alarm recovery deviation value
Setting range
0~Maximum value of inlet sensor
Value setting
0.3(Factory value)
17:Inlet high water level alarm value
Setting range
Inlet sensor minimum to maximum value
ㆍWhen the inlet water level sensor alarms low water level, restore the judgment setting.
Example: Actual inlet water level > inlet low water level alarm value +inlet low water level alarm recovery
deviation value.
ㆍThe target water level value to be set when the inlet water level sensor judges the high water level alarm.
Note: The inlet high water level alarm value cannot be lower than the inlet low water level alarm value.
ㆍWhen the inlet water level sensor judges the high water level alarm, the alarm signal maintenance time
setting.
43
35
Chapter 6 Function Table and Description
Value setting
25%(Factory value)
25:Antifreeze frequency percentage
ㆍSet the operating frequency percentage when the inspection/antifreeze function is activated.
Setting range
10~25 %
Value setting
1(Factory value)
26:Antifreeze environment temperature setting
ㆍSet the starting temperature of the antifreeze function.
Setting range
-5~40℃
Value setting
120(Factory value)
22:Inspection start time
ㆍTo prevent the pump from malfunctioning due to long-term non-operation, set the start time.
Setting range
1~9999 H
Value setting
1(Factory value)
23:Inspection times
ㆍTo prevent the pump from malfunctioning due to long-term non-operation, set the start times.
Setting range
1~20 times
Value setting
0(Factory value)
24:Antifreeze function
ㆍTo prevent the water pump from freezing due to low ambient temperature.
Setting range
0:Not used 1:Used
44
36
Chapter 6 Function Table and Description
6.4 Drive parameter area
Display
×
○
×
×
×
×
×
×
×
×
×
×
Name Setting range Factory value
×
×
×
×
×
×
×
×
×
×
×
×
×
×
G4-01 CAN communication ID 0~6
G4-02 Start and stop mode 0: Operation panel/RS485 communication
1: DI terminal
G4-03 Frequency input mode 0: Operation panel/RS485 communication
1: Analog
G4-04 Motor rated power
0:0.55 kW
1:0.75 kW
2:1.1 kW
3:1.5 kW
4:2.2 kW
5:3.0 kW
6:4.0 kW
7:5.5 kW
8:7.5 kW
9:11 kW
10:15 kW
11:18.5 kW
12:22 kW
G4-05 Motor pole number 2 pole 4pole 6pole 8 pole 12 pole
16pole
G4-06 Motor rated current 0.0 ~99.9 A
G4-07 Motor rated speed 0~9999 rpm
G4-08 Motor rated voltage 200 ~500 V
G4-09 Motor rated frequency
0:50hz
1:60hz
2:100hz
3:120hz
4:150hz
5:180hz
6:200hz
7:240hz
8:300hz
9:360hz
10:400hz
11:480hz
0
0
0
5
2 pole
14.5 A
2900 rpm
380 V
0
G4-10 Motor rotation direction 0: Counterclockwise 1: Clockwise
G4-11 Motor shutdown and
standby 0: Free stop 1: Integral stop
G4-12 Acceleration time 0~600 sec
G4-13 Deceleration time 0~600 sec
0
1
10 sec
10 sec
Parameter
linkage
Change
during
running
45
37
Chapter 6 Function Table and Description
Value setting Setting range
0(Factory value) 0:Single mode 1-6: Online mode
6.4.1 Function description of drive parameter area
1:CAN communication ID
ㆍCAN communication ID during linkage operation.
ㆍWhen setting, please avoid the same ID, CAN communication ID during linkage operation.
Value setting Setting range
0(Factory value) 0: Operation panel/RS485 communication 1: DI terminal
2:Start and stop mode
ㆍRun/stop via the drive keyboard.
ㆍWhen the DI terminal is selected, the operation command is executed according to the external input.
Value setting Setting range
0(Factory value) 0: Operation panel/RS485 communication 1: Analog
3:Frequency input method
ㆍ Used in manual mode.
ㆍControl the frequency of the inverter by selecting the input method.
Setting range Factory value
G4-20 Fan rotation mode
0: Start when power is on
1: Output frequency starts
G4-21 Heat sink temperature -10 ~ 200℃ 0
2
2: Start when temperature is abnormal
× ×
× ×
G4-22 IGBT temperature -10 ~ 200℃ 0 × ×
× ×
○ ×
× ×
× ×
× ×
G4-14 Water pump type 1: Main pump 2: Auxiliary pump × ×
G4-15 Motor overcurrent alarm
value 50~200%
G4-16 Motor overcurrent alarm
delay 0~200 sec
G4-17 Torque bias 2~10%
G4-18 Maximum operating
frequency percentage 1~100%
G4-19 Switching frequency 5 kHz 10 kHz 12 kHz
14 kHz 16 kHz
1
110%
60 sec
2%
100%
5 kHz
Parameter
linkage
Change
during
running
Display Name
46
38
Chapter 6 Function Table and Description
Value setting
2 pole(Factory value)
5:Motor pole number
Note: Set according to the motor nameplate.
Setting range
2pole 4pole 6pole 8pole 12pole 16pole
Value setting
14.5(Factory value)
6:Motor rated current
Note: Set according to the motor nameplate.
Setting range
0.0 ~ 99.9 A
Value setting
2900(Factory value)
7:Motor rated speed
Note: Set according to the motor nameplate.
Setting range
0 ~ 9999 rpm
Value setting
380(Factory value)
8:Motor rated voltage
Note: Set according to the motor nameplate.
Setting range
200 ~ 500 V
Value setting
0(Factory value)
9:Motor rated frequency
Note: Set according to the motor nameplate
Setting range
0:50hz 1:60hz 2:100hz 3:120hz 4:150hz 5:180hz
6:200hz 7:240hz 8:300hz 9:360hz 10:400hz 11:480hz
Value setting Setting range
0: 0.55kW 1: 0.75kW 2: 1.1kW 3:1.5 kW 4:2.2kW 5: 3.0kW 6: 4.0kW
7: 5.5kW 8: 7.5kW 9: 11kW 10: 15kW 11: 18.5kW 12: 22kW
5(Factory value)
4:Motor rated power
ㆍSet motor capacity
ㆍThis value is set when the pump leaves the factory.
ㆍConfirm the motor capacity set by the current pump controller.
47
39
Chapter 6 Function Table and Description
Value setting
0(Factory value)
11:Motor stop standby method
ㆍMotor stop method setting.
Setting range
0: Free stop 1: Integral stop
Value setting
10(Factory value)
12:Acceleration time
ㆍSpecially refers to the time required to increase the output frequency from 0[Hz] to the maximum.
ㆍWhen the acceleration time is set too short, the motor is prone to overcurrent.
Setting range
0 ~ 600 sec
Value setting
10(Factory value)
13:Deceleration time
ㆍSpecially refers to the time required from the maximum output frequency to 0[Hz].
ㆍIf the deceleration time is set too short, the motor is prone to overvoltage.
Setting range
0 ~ 600 sec
Value setting
1(Factory value)
14:Pump type
ㆍMain pump and auxiliary pump. When setting the auxiliary pump, the system will default to operating
according to the auxiliary pump priority.
Note: A maximum of 2 auxiliary pumps can be set in the system.
Setting range
1: Main pump 2: Auxiliary pump
Value setting
110(Factory value)
15:Motor overcurrent alarm value
ㆍThis function is set to protect the motor.
ㆍWhen the output current is greater than 110% of the motor rated current, an alarm will occur.
Setting range
50 ~ 200 %
Value setting Setting range
0(Factory value) 0: Counterclockwise 1: Clockwise
10:Motor rotation direction
ㆍWater pump rotation direction setting.
ㆍIn order for the water pump to operate normally, please confirm the direction before use.
48
40
Chapter 6 Function Table and Description
Value setting
2(Factory value)
17:Torque bias
ㆍThe amount of torque used for the initial operation of the controller.
ㆍWhen the load is running and the starting torque is insufficient, increasing this value can increase
the torque.
Setting range
2% 4% 6%
Value setting
100%(Factory value)
18:Maximum operating frequency percentage
ㆍThe maximum frequency that can limit the drive operation.
Note: Do not exceed the rated frequency of the motor.
Setting range
1 ~ 100 %
Value setting
5(Factory value)
19:Switching frequency
ㆍWhen the interference or ambient temperature is high, the frequency needs to be reduced.
ㆍAs the switching frequency decreases, the motor noise increases, but the interference or motor
leakage current decreases.
Setting range
5 kHz 10 kHz 12 kHz 14 kHz 16 kHz
Value setting
2(Factory value)
20:Fan rotation mode
ㆍSetting the operation mode of the cooling fan.
Setting range
0: Start when power is on 1: Output frequency starts
2: Start when temperature is abnormal
21:Heat sink temperature
ㆍDisplays the current heat sink temperature.
22:IGBT temperature
ㆍDisplays the current IGBT temperature.
Value setting
60(Factory value)
16:Motor overcurrent alarm time value
ㆍSet the motor rated current overload level time function.
Setting range
0 ~ 200 sec
49
41
Chapter 6 Function Table and Description
6.5 Signal parameter area
Display
×
×
○
○
×
×
×
×
×
×
×
×
×
×
×
Name Setting range Factory value
×
×
×
×
×
×
×
×
×
× ×
× ×
Parameter
linkage
Change
during
running
G5-01
G5-02
G5-03
G5-04
G5-05
G5-06
G5-07
G5-08
G5-09
G5-10
G5-11
G5-12
Outlet sensor mode 0:Not used
1:Outlet pressure sensor 0
Outlet sensor minimum
value 0 0
16.0 bar 1.60 Mpa
0 bar 0 Mpa
Pressure unit selection 0:bar 1:Mpa 0
0:Not used
1:Inlet pressure sensor
2:Inlet water level sensor
-5.0~45.0 bar 0 bar
-0.5~4.50 Mpa 0 Mpa
0.0~5.0 m 0 m
-5.0~45.0 bar 16 bar
-0.5~4.50 Mpa 1.6 Mpa
0.0~5.0 m 5.0 m
-2.0~2.0 0 bar
-0.20~0.20 0 Mpa
-1.0~1.0 m 0 m
0: Current input 1: Voltage input
Analog input minimum
value 0~Motor rated frequency 0
Analog input maximum
value 0~Motor rated frequency 50
G5-13
G5-14
Minimum input analog
value 0.00~8.00mA 0.00~4.00V 4.00mA 0.00V
Minimum input analog
value 16.00~24.00mA 6.00~14.00V 20.00mA 10.00V
Inlet sensor correction
value
Analog input mode 0
Inlet sensor mode 0
Inlet sensor minimum
value
Inlet sensor maximum
value
Outlet sensor maximum
value 0~45.0 bar 0~4.50 Mpa
Outlet sensor correction
value -2.0~2.0 -0.20~0.20
Value setting Setting range
0(Factory value) 0:Not used 1:Outlet pressure sensor
6.5.1 Signal parameter area function description
1:Exit sensor mode
ㆍActivate whether to use the exit sensor.
Note: At least 1 exit sensor needs to be configured in the system.
50
42
Chapter 6 Function Table and Description
Value setting
0(Factory value)
2:Outlet sensor minimum value
ㆍThe lowest value of the outlet sensor signal.
Setting range
0
Value setting Setting range
16(Factory value) 0 ~ 45.0 bar 0 ~ 4.50 Mpa
3:Maximum value of outlet sensor
ㆍEnter the maximum pressure value that the pressure sensor can measure.
ㆍTo ensure that the pump can operate normally, please correctly enter the sensor related parameters.
Note: The maximum value of the outlet sensor cannot be less than the minimum value of the outlet sensor.
Value setting Setting range
16(Factory value) -5.0 ~ 45.0 bar -0.5 ~ 4.50 Mpa 0.0 ~ 5.0 m
7:Inlet sensor minimum value
ㆍThe minimum value of the inlet sensor can be set.
ㆍTo ensure that the pump can operate normally, please enter the sensor related parameters correctly.
Note: The inlet sensor minimum value cannot be greater than the inlet sensor maximum value.
Value setting
0(Factory value)
4:Maximum value of outlet sensor
ㆍCorrect the error between the pressure gauge and the sensor installed on the pipeline.
Setting range
-2.0 ~ 2.0 -0.20 ~ 0.20
Value setting
0(Factory value)
5:Pressure unit selection
ㆍThe pressure unit of the outlet sensor can be set.
Setting range
0:bar 1:Mpa
Value setting
0(Factory value)
6:Inlet sensor mode
ㆍInlet sensor properties can be set.
Setting range
0:Not used 1:Inlet pressure sensor 2:Inlet water level sensor
51
43
Chapter 6 Function Table and Description
Value setting Setting range
16(Factory value) -5.0 ~ 45.0 bar -0.5 ~ 4.50 Mpa 0.0 ~ 5.0 m
8:Inlet sensor maximum value
ㆍThe maximum value of the inlet sensor can be set.
ㆍTo ensure the normal operation of the pump, please correctly enter the sensor related parameters.
Note: The inletsensor maximum value cannot be less than the inlet sensor minimum value.
Value setting
0(Factory value)
9:Inlet sensor calibration value
ㆍCorrect the error between the pressure gauge and the sensor installed on the pipeline.
Setting range
-2.0 ~ 2.0 -0.20 ~ 0.20 -1.0 ~ 1.0 m
Value setting
0(Factory value)
10:Analog input mode
ㆍIn manual mode and when the frequency input method is \"analog\", the output frequency can be set
according to the external input current or voltage.
Setting range
0: Current input 1: Voltage input
Value setting
0(Factory value)
11:Analog input minimum value
ㆍThe minimum frequency corresponding to the current or voltage value.
Setting range
0~Motor rated frequency
Value setting
0(Factory value)
12:Maximum analog input value
ㆍThe maximum frequency corresponding to the current or voltage value.
Setting range
0~Motor rated frequency
Value setting
4.00mA 0.00V
13:Minimum input analog value
ㆍSet the minimum value of external input.
Setting range
0.00~8.00 mA 0.00~4.00V
Value setting
20.00mA 10.00V
14:Maximum input analog value
ㆍSet the maximum value of external input.
Setting range
16.00~24.00 mA 6.00~14.00V
52
44
Chapter 6 Function Table and Description
6.6 Fault Log Parameter Area
Display
×
Name Setting range Factory value
Alarm 0 ×
category
G6-01
Er-00 No alarm
Er-02 Abnormal outlet sensor
Er-03 Abnormal number of outlet sensors
Er-04 Too - high outlet pressure
Er-05 Extremely high outlet pressure
Er-06 Too - low outlet pressure
Er-07 High outlet sensor differential pressure
Er-08 Low water level of inlet probe
Er-09 Abnormal inlet sensor
Er-10 Too - high inlet water level
Er-11 Too - low inlet water level
Er-12 Too - high inlet pressure
Er-13 Too - low inlet pressure
Er-14 CAN communication ID repetition
Er-15 RS485 communication abnormality
Er-16 Excessive number of auxiliary pumps
Er-17 Too - high DC bus voltage
Er-18 Too - low DC bus voltage
Er-19 Drive overheating
Er-20 Drive overload
Er-21 Motor overcurrent
Er-22 Motor overheat
Er-23 IGBT driver IC failure
Er-24: Output phase loss
Er-25 Emergency stop
Er-26 Exceeded trial time
Er-27 CAN communication abnormality
Er-28 Anormal CAN_BPS setting
Er-29 Current sensor failure
Parameter
linkage
Change
during
running
53
45
Chapter 6 Function Table and Description
Display
×
×
×
×
×
×
Name Setting range Factory value
Output frequency
Output current
Year
Month/Day
Hour/Minute
G6-01
0 ~ 60 Hz 0
0
0
0.0 ~ 99.9A
Fault code Fault content
No alarm
Abnormal outlet sensor
Abnormal number of outlet sensors
Too - high outlet pressure
Extremely high outlet pressure
Too - low outlet pressure
High outlet sensor differential pressure
Low water level of inlet probe
Abnormal inlet sensor
Too - high inlet water level
Too - low inlet water level
Too - high inlet pressure
Too - low inlet pressure
CAN communication ID repetition
RS485 communication abnormality
Excessive number of auxiliary pumps
Too - high DC bus voltage
Too - low DC bus voltage
Er-00
Er-02
Er-03
Er-04
Er-05
Er-06
Er-07
Er-08
Er-09
Er-10
Er-11
Er-12
Er-13
Er-14
Er-15
Er-16
Er-17
Er-18
6.6.1 Function description of fault log parameter area
1:Recent Faults 1
ㆍThe number of times a fault has occurred recently is displayed.
ㆍWhen the same type of fault occurs repeatedly, the number of times the fault occurs is recorded.
2:Fault type
Parameter
linkage
Change
during
running
54
46
Chapter 6: Function Table and Description
Fault code Fault content
Drive overheating
Drive overload
Motor overcurrent
Motor overheat
IGBT driver IC failure
Output phase loss
Emergency stop
Exceeded trial time
CAN communication abnormality
Abnormal CAN_BPS setting
Current sensor failure
Er-19
Er-20
Er-21
Er-22
Er-23
Er-24
Er-25
Er-26
Er-27
Er-28
Er-29
3:Output frequency
ㆍThe current output frequency archived when an alarm occurs.
4:Output current
ㆍThe current output current as recorded when an alarm occurs.
5:Date/Time
ㆍCurrent date/time of the alarm.
29
47
Chapter 6: Function Table and Description
Setting Value
0(Factory value)
6.7.1 Display Settings Area Function Description
1:Parameter initialization
ㆍInitialize all or each functional area.
Setting Range
0: Not used 1: G2 Zone 2: G3 Zone 3: G4 Zone
4: G5 Zone 5: G6 Zone 6: G7 Zone 7: Full Initialization
6.7 Display settings area
Display
× ×
×
×
×
×
×
Name Setting Range Factory Value
×
×
×
×
××
××
××
×
×
×
×
×
×
×
0: Not used
1: G2 Zone
2: G3 Zone
3: G4 Zone
4: G5 Zone
5: G6 Zone
6: G7 Zone
7: Full Initialization
G7-02
G7-01
Year Setting
Parameter Initialization
0 22
0
G7-03 Month/Day Setting Jan. 1 0
G7-04 Time Setting 0:00 0
0:Not used 1:Used
G7-06 Software version 0.01 0.01
G7-07 Accumulated electricity 0 ~999999kWh 0
G7-08 Power-up time 0~999999 h 0
G7-09 Number of runs 0 ~ 999999(times) 0
G7-10 Running time 0~999999 h 0
G7-11 Alarm Accumulation number 0~65535(times) 0
G7-12 Inverter output voltage 0~400V 0
G7-05 Lock screen feature 0
Parameter
linkage
Change
during
running
30
48
Chapter 6: Function Table and Description
Setting Value
22(Factory value)
2:Year Setting
ㆍCurrent year setting.
Setting Range
0000
Setting Value
01/01(Factory value)
3:Month/Day setting
ㆍCurrent month/day setting.
Setting Range
01/01
Setting Value
00:00(Factory value)
4:Time setting
ㆍCurrent time setting
Setting Range
00:00
Setting Value
0(Factory value)
5:Screen Lock Feature
ㆍActivate the lock screen function. Unlocking requires a key combination, and you need to unlock again
each time you enter the parameter group.
Setting Range
0:Not used 1:Used
Setting Value
1.0(Factory value)
6:Software version
ㆍDisplay the current software version.
Setting Range
0.01
31
49
Chapter 6: Function Table and Description
Fault code Fault content Automatically reset
Er-00
Er-02
Er-03
Er-04
Er-05
Er-06
Er-07
Er-08
Er-09
Er-10
Er-11
Er-12
Er-13
Er-14
Er-15
Er-16
Er-17
Er-18
Er-19
Er-20
Er-21
Er-22
Er-23
Er-24:
Er-25
Er-26
Er-27
Er-28
Er-29
6.8 List of Protective Functions
○
×
○
×
○
○
○
○
○
○
○
○
×
×
×
○
○
○
○
○
○
×
×
×
×
×
×
×
Drive overheating
Drive overload
Motor overcurrent
Motor overheat
IGBT driver IC failure
Output phase loss
Emergency stop
Exceeded trial time
CAN communication abnormality
Abnormal CAN_BPS setting
Current sensor failure
No alarm
Abnormal outlet sensor
Abnormal number of outlet sensors
Too - high outlet pressure
Extremely high outlet pressure
Too - low outlet pressure
High outlet sensor differential pressure
Low water level of inlet probe
Abnormal inlet sensor
Too - high inlet water level
Too - low inlet water level
Too - high inlet pressure
Too - low inlet pressure
CAN communication ID repetition
RS485 communication abnormality
Excessive number of auxiliary pumps
Too - high DC bus voltage
Too - low DC bus voltage
32
50
Chapter 6: Function Table and Description
6.8.1 Faults and Alarm Release Methods
Alarm contents are displayed on the keypad when an alarm occurs.
ㆍCheck the fault information in the G6 group when there is a fault or alarm.
ㆍPress the “Set” button to cancel the alarm.
ㆍAutomatically disarm and restart. If the alarm is canceled when the conditions for canceling the alarm
are not met, the alarm will occur again.
6.8.2 Causes and measures of fault
Er-02: Abnormal outlet sensor
Cause:
ㆍDefective sensor.
ㆍDefective controller.
ㆍDefective sensor terminal.
ㆍCommunication ID is not set at linkage.
Measures:
ㆍReplace the sensor.
ㆍReplace the controller.
ㆍ 确认传感器端子缺陷,或传感器配置信息。
Er-03: Abnormal number of export sensors
Cause:
ㆍ Sensor configuration error.
ㆍCommunication ID is not set at linkage.
Measure:
ㆍConfirm the information of outlet sensor configuration .
ㆍSet the communication ID during linkage.
Functional Area
Signal parameter G5
No.
01
Name
Outlet sensor mode
Setting Value
0(Factory value)
Setting Range
0:Not used 1:Export pressure sensor
Functional Area
Signal parameter G4
No.
01
Name
CAN Communication
ID
Setting Value
0(Factory value)
Setting Range
0:Standalone mode 1~6 :Online mode
Signal parameter G5 01 Outlet sensor mode 0(Factory value) 0:Not used 1:Outlet pressure sensor
33
51
Chapter 6: Function Table and Description
Er-04:Too - high outlet pressure
Cause:
ㆍThe pressure during operation is 2 bar higher than the set pressure, exceeding the outlet highpressure alarm.
ㆍThe system will stop running after a delay and the alarm will be displayed on the LCD screen.
Measure:
ㆍCheck the set pressure and alarm level.
ㆍThe controller automatically resets when the current pressure is lower than the high pressure alarm pressure.
Functional Area
Potection
parameter G3
No.
01
Name
Outlet high pressure
alarm deviation value
Setting Value
2(Factory value)
Setting Range
0.5~3.0 bar 0.50~0.30 Mpa
02 Outlet high pressure
alarm delay 5(Factory value) 0~600 sec
Er-05:Extremely high outlet pressure
Cause:
ㆍWhen running 3 bar higher than the set pressure during operation, operation stops and an alarm is displayed
on the LCD screen.
Measure:
ㆍConfirm the set pressure and alarm level.
ㆍIt cannot be reset automatically, it needs to be reset manually by human.
Functional Area
Potection parameter G3
No.
03
Name
Outlet overpressure alarm
absolute value
Setting Value
3(Factory value)
Setting Range
16.0 bar
Er-06:Too - low outlet pressure
Cause:
ㆍAlarms when operating at actual pressure below the low pressure alarm level.
Alarms are restarted after the “Fault Recovery Time” has elapsed. The controller will not restart after the “Alarm
Recovery Time” has elapsed in order to protect the controller.
Measure:
ㆍConfirm that the amount of water in the water tank (cistern) is sufficient.
ㆍCheck if there is air in the pump.
ㆍCheck if there is water flowing through the air opening.
ㆍPress the “Set” button to cancel the alarm and press the RUN button to start the pump.
Functional Area
Potection
parameter G3
No.
04
05
06
Name
Outlet low voltage alarm value
Setting Value
0.5 bar(Factory value)
Setting Range
0~25.0 bar
Number of exported
low-pressure judgment units 1(Factory value) 1~6 unit
Outlet low voltage alarm delay 20(Factory value) 0~600 sec
34
52
Chapter 6: Function Table and Description
Er-08:Low water level of inlet probe
Cause:
ㆍDisconnection of the low water level terminal causes a trigger fault.
ㆍInternal terminal is damaged.
Measure:
ㆍVerify that the low water line is not disconnected.
ㆍReplace the control board.
Functional Area
Potection parameter G3
Signal parameter G5
No.
07
Name
Low water level probe detection
Setting Value
0
Setting Range
0:Not used 1:used
08 Low water level probe delay 3(Factory value) 0~600 sec
Er-07: High outlet sensor differrential pressure
Cause:
ㆍAn alarm will be triggered when the difference between the sampling values of outlet sensor 1
and outlet sensor 2 reaches a certain value.
Measure:
ㆍConfirm 2 outlet sensor sampling values.
ㆍReplace the outlet sensors.
ㆍCheck outlet sensor parameters.
ㆍPress “Set” to cancel the alarm and press “RUN” to start the pump.
Functional Area
Potection parameter
G3
Signal parameter G5
No.
19
Name
Outlet Pressure Sensor
Diagnosis
Setting Value
0(Factory value)
Setting Range
0:Not used 1:used
03 Maximum value of the
outlet sensor
16.0 bar(Factory value)
1.60 Mpa(Factory value)
0 ~ 45.0 bar
0 ~ 4.50 Mpa
Er-09:Abnormal inlet sensor
Cause:
ㆍDefective sensor.
ㆍDefective controller.
ㆍDefective sensor terminal.
Measure:
ㆍReplace the sensor.
ㆍReplace the controller.
ㆍConfirm sensor terminal defects, or sensor configuration information.
35
53
Chapter 6: Function Table and Description
Er-10:Too-high inlet water level
Cause:
ㆍThe inlet water level is higher than the alarm value.
ㆍSensor damage
Measure:
ㆍReplace the sensor.
ㆍConfirm the alarm level of the inlet water level.
Functional Area
Potection parameter G3
No.
17
Name
Inlet high water level
alarm value
Setting Value
5.0(Factory value)
Setting Range
Inlet sensor minimum value ~
maximum value
18 Inlet high water level
alarm delay 5(Factory value) 0~600 sec
Er-11:Too-low inlet water level
Cause:
ㆍThe inlet water level is below the alarm value.
ㆍSensor damage.
Measure:
ㆍReplace the sensor.
ㆍConfirm the inlet water level of the alarm level.
Functional Area
Potection parameter G3
No.
14
Name
Inlet low water level
alarm value
Setting Value
0.6(Factory value)
Setting Range
Inlet sensor minimum value ~
maximum value
15 Inlet low water level
alarm delay 5(Factory value) 0~600 sec
Er-12:Too-high inlet pressure
Cause:
ㆍ The Inlet pressure is higher than the alarm value.
ㆍ Sensor damage.
Measure:
ㆍ Replace the sensor.
ㆍ Confirm the inlet pressure alarm level.
Functional Area
Signal parameter
G5
No.
06
Name
Inlet sensor mode
Setting Value
0(Factory value)
Setting Range
0:Not used 1:Inlet pressure
sensor 2:Inlet water level sensor
36
54
Chapter 6: Function Table and Description
Er-13:Too-low inlet pressure
Cause:
ㆍ The Inlet pressure is below the alarm value.
ㆍ Sensor damage.
Measure:
ㆍ Replace the sensor.
ㆍ Confirm the inlet pressure alarm level.
Functional Area
Potection parameter
G3
No.
12
Name
Inlet high-pressure alarm
value
Setting Value
16.0(Factory value)
Setting Range
Inlet sensor minimum value ~
maximum value
13 Inlet high-pressure alarm
delay 5(Factory value) 0~600 sec
Functional Area
Potection parameter
G3
No.
09
Name
Inlet low-pressure alarm
value
Setting Value
0.3(Factory value)
Setting Range
Inlet sensor minimum value ~
maximum value
10 Inlet low-pressure alarm
delay 5(Factory value) 0~600 sec
Er-14:CAN communication ID repetition
Cause:
ㆍBad CAN communication cable connection.
ㆍBad controller CAN communication IC.
Measure:
ㆍConfirm CAN communication connection status.
ㆍReplace the controller
Er-15:RS485 communication abnormality
Cause:
ㆍDuring communication, an abnormal data stream triggers a fault.
Measure:
ㆍAfter the data stream returns to normal, the alarm prompt is lifted.
Er-16:Excessive number of auxiliary pumps
Cause:
ㆍIn the system, only a maximum of 2 auxiliary pumps of type G4-14 (pump type) are allowed
exceeding 2 triggers.
Measure:
ㆍThe number of auxiliary pumps needs to be reasonably set (only up to 2 units can be operated).
37
55
Chapter 6: Function Table and Description
Er-17:Too-high DC bus voltage
Cause:
ㆍWhen the power supply voltage is high.
ㆍWhen connecting to a load greater than the power supply voltage.
Measure:
ㆍCheck the input voltage of the controller.
ㆍConfirm the power supply capacity.
Note: Please confirm the DC link voltage G0-05 in the parameter table.
Er-18:Too-low DC bus voltage
Cause:
ㆍWhen the power supply voltage is low.
ㆍWhen connected to a load smaller than the power supply voltage.
Measure:
ㆍCheck the input voltage of the controller.
ㆍConfirm the power supply capacity.
Note: Please confirm the DC Link voltage G0-05 in the parameter table.
Er-19:Drive overheating
Cause:
ㆍInverter temperature is too high.
ㆍFan damage.
ㆍTemperature sensor damage.
Measure:
ㆍCheck if the controller fan is blocked and replace the fan.
ㆍReplace the temperature probe.
Er-20:Drive overload
Cause:
ㆍWhen the load ratio controller exceeds its rated capacity.
Functional Area
Drive parameter G4
No.
14
Name
Pump type
Setting Value
1(Factory value)
Setting Range
1: Main Pump 2: Auxiliary Pump
Functional Area
Drive parameter G4
No.
13
Name
Deceleration time
Setting Value
6(Factory value)
Setting Range
0~600 sec
38
56
Chapter 6: Function Table and Description
Er-22:Motor overheat
Cause:
ㆍShort acceleration and deceleration time.
ㆍMotor restarts in Free Run mode.
ㆍMotor damage.
Measure:
ㆍAdjust the acceleration and deceleration time.
ㆍConfirm whether the controller capacity matches the motor capacity.
ㆍCheck the load, motor, and output wiring.
ㆍIf the same alarm occurs, please consult the operation and maintenance service department.
Er-23:IGBT driver IC fault
Cause:
ㆍAdjust the acceleration and deceleration time.
ㆍConfirm whether the controller capacity matches the motor capacity.
ㆍCheck the load, motor, and output wiring.
ㆍIf the same alarm occurs, please consult the operation and maintenance service department.
Measure:
ㆍPlease use a controller with a higher capacity ratio than the load.
ㆍConfirm the overload protection alarm level of the driver.
Er-21:Motor overcurrent
Cause:
ㆍThe actual operating current of the motor is compared with the rated current and an alarm is triggered based
on different levels.
Measure:
ㆍConfirm the motor rated current (nameplate), confirm the set motor rated current.
Note: Confirm the output current on the main interface
Functional Area
Drive parameter G4
No.
06
15
16
Name
Motor rated current
Setting Value
14.5(Factory value)
Setting Range
0.0 ~ 99.0 A
Motor overcurrent alarm value 110%(Factory value) 50 ~ 200 %
Motor overcurrent alarm delay 60 sec 0 ~ 200 sec
39
57
Chapter 6: Function Table and Description
Measure:
ㆍExpand the acceleration time.
ㆍVerify whether the motor is damaged, insulation condition.
ㆍSeparate the motor wires from the controller and test, if the same alarm occurs there may be a short
circuit in the IGBT, consult the O&M service department for this type of phenomenon.
Er-24:Output phase loss
Cause:
ㆍBad output cable.
ㆍBad output terminal release.
Measure:
ㆍConfirm the output wiring.
ㆍConfirm the output terminal release status.
Er-25:Emergency stop
Cause:
ㆍAn alarm caused by an external signal.
Measure:
ㆍConfirm the external signal.
Er-26:Exceeded trail time
Cause:
ㆍTrial period exceeds the allowed value.
Measure:
ㆍConsult the Operations and Maintenance Services Department for such phenomena.
Er-27:CAN communication abnormality
Cause:
ㆍA fault is triggered when CAN communication is abnormal.
Measure:
ㆍAfter communication is restored, the fault is resolved.
Functional Area
Drive parameter G4
No.
12
Name
Acceleration time
Setting Value
10(Factory value)
Setting Range
0~600 sec
40
58
Chapter 6: Function Table and Description
6.9 RS485 Communication
Adopting the communication standards of the Electronic Industries Association (EIA).
6.10 MODBUS RTU Communication Protocol
1、Data format
Follow the principle that the host sends commands and the slave returns the corresponding ones.
1) Command Frames
(1)
3.5 character
pause
(2)
Slave Address
(Inverter)(1byte)
(3)
Function
code(1byte)
(4)
Data area
(5)
CRC-16 check digit
(2byte)
(6)
3.5 character
pause
Project
Protocols
Communication distance
Communication method
Communication speed
Check digit
Data length
Stoppages
Communciation code
Specification
MODBUS RTU Communication Protocol
500meters (recommended distance)
2-wire semi-doubles, can be multiple.
2400,4800,9600,19200,38400bps
None, Even Check, Odd Check
8 bit
1bit, 2bit
Binary
Er-28:Abnormal CAN_BPS setting
Cause:
ㆍCAN communication speed setting is abnormal.
Measure:
ㆍThe CAN communication speed setting is abnormal. Modify the communication speed and clear the
fault after the network is connected.
Er-29:Current sensor failure
Cause:
ㆍThe current sensor triggers an alarm when the output is abnormal.
Measure:
ㆍWhether the power failure restart is lifted or not.
ㆍConsult the operation and maintenance service department.
41
59
Chapter 6: Function Table and Description
(1) A pause of more than 3.5 character times.
(2) Slave address (inverter) range: 1 to 250.
(3) Function code:
(4) Data area: stores the data required for the function code.
(5) CRC-16 check digit.
Function code
10H
06H
03H
Function code Type
Read
Write
Write
Read data from the specified address, can read one or more at a time.
Write data into the specified address, can write one or more at a time.
Write data into the specified address, only one piece of data can be
written at a time.
Discription
Decimal
point
Address Parameter Range Content
number
Name
Operational parameters
Command
Type Runtime Downtime
1000
1001
1002
1003
G0-01
G0-02
G0-07
G0-08
Inlet pressure
Inlet water level
R
R/W
R
R
1
1
1
1
0~450
0~450
0~500
0~500
Bit15-Bit0
Bit15-Bit12 backup
Bit11,10:
6Inverter,00Shutdown,10Standby,
01Run Bit9,8:
5Inverter,00Shutdown,10Standby,
01Run Bit7,6:
4Inverter,00Shutdown,10Standby,
01Run Bit5,4:
3Inverter,00Shutdown,10Standby,
01Run Bit3,2:
2Inverter,00Shutdown,10Standby,
01Run Bit1,0:
1Inverter,00Shutdown,10Standby,
01Run
0~45.0(bar)
0~4.50(Mpa)
0~45.0(bar)
0~4.50(Mpa)
-5.0~45.0(bar)
-0.50~4.50(Mpa)
0.0~5.0M
0 : STOP(All stops)
1 : RUN(Frequency output)
2 : READY(All standby)
3 : Fault(Out-of-order)
1005
1006
1004
Null
Null
System mode R
R
R
R
R/W
R
R
R
R
R
R
R/W
R
R
R
R
Null System status R
1
0
0~1
0~26
1 0~3
0:Automatic
1:Manual
Trip Content
0~29
0~0x3F Run the
command
1007 Null W W W
Host failure
information
Measure
pressure
Set the pressure
42
60
Chapter 6: Function Table and Description
Operational parameters
1000
1009
1010
1011
1012
1013
1014
1015
1016
1017
1018
1019
1020
1021
1022
1023
1024
1025
1026
Low byte: bit0-5: main pump
configuration, (corresponding to ID1~6
inverter)
High byte: bit0-5: auxiliary pump
configuration, (corresponding to ID1~6
inverter)
In automatic mode, only
reading is allowed.
In manual mode, reading
and writing are permitted.
Unit:kW
Unit:V
Null
G0-03
G0-04
G0-05
Inverter
configuration
P1 Output power
P2 Output power
P3 Output power
P4 Output power
P5 Output power
P6 Output power
P1 DC voltage
P2 DC voltage
P3 DC voltage
P4 DC voltage
P5 DC voltage
P6 DC voltage
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
0
0
0
0
0
0
1
1
1
1
1
1
0
0
0
0
0
0
0~60
0~60
0~60
0~60
0~60
0~60
0.0~100.0
0.0~100.0
0.0~100.0
0.0~100.0
0.0~100.0
0.0~100.0
0~1000
0~1000
0~1000
0~1000
0~1000
0~1000
R R R 1 0~5
Decimal
point
Address Parameter Range Content
number
Name Command
Type Runtime Downtime
P1 Output
frequency
P2 Output
frequency
P3 Output
frequency
P4 Output
frequency
P5 Output
frequency
P6 Output
frequency
43
61
Chapter 6: Function Table and Description
Operational parameters
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
1040
1041
1042
1043
1044
Unit:A
0: Shutdown
1: Operation
2: Standby
Unit:V
Null
G0-06
Null
Null
Null
1045
1046
P1 Output current
P2 Output current
P3 Output current
P4 Output current
P5 Output current
P6 Output current
Inverter1status
Inverter 2 status
Inverter 3 status
Inverter 4 status
Inverter 5 status
Inverter 6 status
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.0~99.9
0.0~99.9
0.0~99.9
0.0~99.9
0.0~99.9
0.0~99.9
0 ~ 2
0 ~ 2
0 ~ 2
0 ~ 2
0 ~ 2
0 ~ 2
0~500
0~500
0~500
0~500
0~500
0~500
0~65535
0~65535
P1 Inverter output voltage OV
P2 Inverter output voltage OV
P3 Inverter output voltage OV
P4 Inverter output voltage OV
P5 Inverter output voltage OV
P6 Inverter output voltage OV
Decimal
point
Address Parameter Range Content number
Name Command
Type Runtime Downtime
P1 Accumulate number of
alarm times
P2 Accumulate number of
alarm times
44
62
Chapter 6: Function Table and Description
Operational parameters
1047
1048
1049
1050
1051
1052
1053
1054
1055
1056
1057
1058
1059
1060
1061
1062
1063
1064
1065
1066
Unit:A
Unit:kWh
Unit: hour
Null
Null
Null
P1 Accumulated electricityH
P1 Accumulated electricityL
P2 Accumulated electricityH
P2 Accumulated electricityL
P3 Accumulated electricityH
P3 Accumulated electricityL
P4 Accumulated electricityH
P4 Accumulated electricityL
P5 Accumulated electricityH
P5 Accumulated electricityL
P6 Accumulated electricityH
P6 Accumulated electricityL
P1 Power-on time H
P1 Power-on time L
P2 Power-on time H
P2 Power-on time L
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
1
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0~65535
0~65535
0~65535
0~65535
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
R
R
0
0
R
R
R
R
Decimal
point
Address Parameter Range Content number
Name Command
Type Runtime Downtime
P3 Accumulate number
of alarm times
P4 Accumulate number
of alarm times
P5 Accumulate number
of alarm times
P6 Accumulate number
of alarm times
45
63
Chapter 6: Function Table and Description
Operational parameters
1067
1068
1069
1070
1071
1072
1073
1074
1075
1076
1077
1078
1079
1080
1081
1082
1083
1084
1085
1086
Unit: hour
Null
Null
Null
P3 Power-on time H
P3 Power-on time L
P4 Power-on time H
P4 Power-on time L
P5 Power-on time H
P5 Power-on time L
P6 Power-on time H
P6 Power-on time L
P1 Number of runs H
P1 Number of runs L
P2 Number of runs H
P2 Number of runs L
P2 Number of runs L
P3 Number of runs L
P4 Number of runs H
P4 Number of runs L
P5 Number of runs H
P5 Number of runs L
P6 Number of runs H
P6 Number of runs L
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0
0
0
0
0
0
0
0
0
0
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
Decimal
point
Address Range Content Parameter
number Name Command
Type Runtime Downtime
46
64
Chapter 6: Function Table and Description
Operational parameters
1087
1088
1089
1090
1091
1092
1093
1094
1095
1096
1097
1098
Null Unit: hour
P1 Run time H
P1 Run time L
P2 Run time H
P2 Run time L
P3 Run time H
P3 Run time L
P4 Run time H
P4 Run time L
P5 Run time H
P5 Run time L
P6 Run time H
P6 Run time L
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
0
0
0
0
0
0
0~999999
0~999999
0~999999
0~999999
0~999999
0~999999
Decimal
point
Address Parameter Range Content
number
Name Command
Type Runtime Downtime
47
65
NOTE
48
Product name NSQ Drive II / T
Model
Distributor
Address
Warranty Period 1 year
Purchase date
Validity period
Telephone
Product Warranty
This product is guaranteed to be a qualified product according to our strict quality control,
inspection and testing.Within one year from the date of purchase, the product itself due to
the quality of the failure of the product in accordance with the provisions of the warranty
unconditional repair and replacement.
Warranty provisions:
1. If the product malfunctions, the maintenance fee will be waived within 1 year from the
date of purchase, please contact the dealer or our after-sales service department.
2. If the following conditions occur during the warranty period, they are not covered by the
free repair fee.
ㆍMalfunctions caused by improper use by the user (not following the instruction manual).
ㆍMalfunctions caused by repairing, remodeling, or dismantling outside of the company's
designated locations.
ㆍMalfunctions caused by natural disasters such as fire
ㆍMalfunctions caused by improper storage (high temperature, humidity, or places with
organic substances).
ㆍIn the absence of this warranty
ㆍDealer and date of purchase have been changed.
ㆍAccessories and consumables are not included in the warranty.
ㆍWe are not responsible for damages caused by malfunction of our products.
Note:
1.This guarantee provides for free or paid repairs in accordance with the abovementioned
guarantee provisions, but it does not legally limit the rights of customers.
2.If you have any questions about the content of this guarantee, please contact the dealer
or our company's after-sales service center.
3. Please register the dealer and the date of purchase on the guarantee.
4.This guarantee will not be reissued if lost. Please keep it properly.
SHANGHAI ZHONGHAN DOOCH PUMP MFG CO., LTD.
Address: No. 239, Zhangliantang Road, Liantang Industrial Zone,
Qingpu District, Shanghai
Phone: +86.21.67679390 Fax: +86.21.67679396
NSQ II/T-M-EN-20260720
NSQDrive II/T
Address: No. 239, Zhangliantang Road, Liantang Industrial Zone, Qingpu District, Shanghai
Phone: +86.21.67679390 Fax: +86.21.67679396
www.doochpump.com.cn
SHANGHAI ZHONGHAN DOOCH PUMP MFG CO., LTD.




