2021 Product Introduction
Busway Monitoring
Eng. Zhang-18860995191
2
PART 1
Busway Introduciton
Busway Monitoring Introduction YOUR CONPANY NAME
Data center small busway modular system construction
Start Box
Straight line unit
Plug-in Box
Communicaiton
cable slot
connecting
plug
Industrial Connector
PDU
locking device
connector
90 equal
elbow unit
Hoisting struck
device
Busway Monitoring Introduction YOUR CONPANY NAME
100A,160A,200A,250A 315A,400A,500A
Standard IEC61439.1/6; GB7251.1/6
system AC3P5W(51);AC3P5W(53);DC Double
circuit
environment
temperature
-5~+40℃,The average temperature for 24
hours shall not exceed +35℃
Protection
grade
IP42
Rated
insulation
voltage
415V
Busbar current 100A; 160A;200A;250A;315A;400A;500A
Plug-in box
current
10A;16A;20A;25A;32A;40A;50A;63A
Overall
dimensions
Height×Width=154.6×84.6
Communicaiton
cable slot
Alloy profile housing
PE
conductor
Phase
conductor
Protective
gusset plate
Insulating
sheath
Busway Monitoring Introduction YOUR CONPANY NAME
Data center small busway starting box and plug-in box structure
弹性端子
插接装置
防错相定位板
合金箱体
通讯接口
锁紧机构
工业插座
微断护罩
Busway Monitoring Introduction YOUR CONPANY NAME
Data center small bus plug-in box installation
Proparation 90°plugin
clockwise
Rotation
lock
★Full point bit plug
★Easy to install, with
locking device
Busway Monitoring Introduction
7
YOUR CONPANY NAME
AMB100(start box)/AMB110(plug-in box)/AMB10(Displayer)AMB20(
adaptor)
Busway Monitoring Introduction
8
YOUR CONPANY NAME
Busway mornitoring device AMB100/110 技术参数 AMB100-A/AMB110-A AMB100-D/AMB110-D
测量参数
电压、电流、频率、有功
功率、无功功率、功率因
数、有功电能、无功电能
电压、电流、功率、电能
、开关量状态
2-63次谐波、温度、湿度
、漏电流 温度、湿度、漏电流
电压 220VAC 48VDC,240VDC,336VDC
电流
AMB100-A:5A/2.5mA
600A/100mA
AMB110-A:100A/20mA
xxxA/5V
频率 45~65Hz /
测量精度
电压/电流/有功功率/有
功电能0.5级,无功功率/
无功电能1级温度±1℃
电压/电流0.5级,功率/
电能1.0级
辅助电源 信号取电或者独立辅助电源
功
能
测温 -20~150℃ -20℃~150℃
漏电流 0~1A 3路漏电流输入,
10mA/5V
开关量 2DI、2DO 4DI、2DO
Wireless module
9
YOUR CONPANY NAME
!!!Installation:with display!!! II→I
Busway Monitoring Introduction
10
YOUR CONPANY NAME
!!!Installation:with no display,Meter built-in
installation!!!
Busway Monitoring Introduction
11
YOUR CONPANY NAME
!!!Installation:with no display,meter is installed with exposure!!!
Busway Monitoring Introduction
Busway Monitoring Introduction
12
YOUR CONPANY NAME
Busway monitoring device: an example of starting box
Busway Monitoring Introduction
13
YOUR CONPANY NAME
Busway monitoring device: an example of plug-in box
Busway Monitoring Introduction
14
YOUR CONPANY NAME
Intensive busway
Application:
1. Contact between low voltage cabinets;
2. Inlet line system of transformer
connection end;
3. Planar power distribution of the
workshop;
4. Inter-storey power supply of high-rise
buildings;
5. Direct power supply for large current
electric equipment.
Busway Monitoring Introduction
15
YOUR CONPANY NAME
Intensive busway joint
Busway Monitoring Introduction
16
YOUR CONPANY NAME
Intensive busway joint Temperature measurement AMB200
The device is directly inserted
into the busbar connector in a
manner similar to USB devices.
The device takes power
directly from the busbar
without any pipeline
construction, and the device
supports live operation and
installation.
The high-precision sensors of each monitoring unit are directly inserted into the
connecting part of the bus bar by the way of hot swapping, and contact with the
copper bar of the bus bar to detect the true temperature and humidity of the bus
bar. The perceived signals are transmitted to the monitoring system through the
analog to digital conversion and wireless communication.
Busway Monitoring Introduction
17
YOUR CONPANY NAME
Intensive busway joint Temperature measurement AMB200
Busway Monitoring Introduction
18
YOUR CONPANY NAME
Intensive busbar connector temperature measurement AMB200 mounting
dimensions
Busway Monitoring Introduction
19
YOUR CONPANY NAME
Infrared temperature measurement of intensive busbar joint AMB300 single point temperature measurement, multi-point temperature measurement (in development)
Measure A/B/C/N 4-
channel temp
Measure A/B/C/N,4*16 points
temp
Busway Monitoring Introduction
20
YOUR CONPANY NAME
Intensive busbar joint infrared temperature measurement AMB300
technical parameters
◆ 2- bus system adopts the network port design scheme: 1
in 1 out
◆ 2 core terminals connected with an external NTC
temperature measurement
Busway Monitoring Introduction
21
YOUR CONPANY NAME
Design of AMB300 Cover Plate for Infrared
Temperature Measurement of Intensive Bus Joint
Cover plate is
made of rivet nut
Busway Monitoring Introduction
22
YOUR CONPANY NAME
Infrared temperature measuring system
diagram of intensive bus joint
Busway Monitoring Introduction
23
YOUR CONPANY NAME
Infrared temperature measurement of intensive busbar joint local touch
screen parameters
Busway Monitoring Introduction
24
YOUR CONPANY NAME
Intelligent bus monitoring system
Mobile
APP
Power &
Environment
Monitoring
certer
Local
monitoring
platform
Ethernet
cable
Busway Monitoring Introduction
25
YOUR CONPANY NAME
Intelligent bus monitoring system
Busway Monitoring Introduction
26
YOUR CONPANY NAME
Intelligent bus monitoring system
Busway Monitoring Introduction
27
YOUR CONPANY NAME
Intelligent bus monitoring and
communication box 350*250*45
Busway Monitoring Introduction
28
YOUR CONPANY NAME
Installation method - hoisting
Busway Monitoring Introduction
29
YOUR CONPANY NAME
Installation mode - top and bottom
Busway Monitoring Introduction
30
YOUR CONPANY NAME
Traditional array cabinet+Power supply and
distribution mode of cable
New generation of busway power
supply and distribution mode
Array cabinet VS Busway
Busway Monitoring Introduction
31
YOUR CONPANY NAME
Array cabinetVS Busway
Array cabinet +
cable
◆Construction is difficult period is long
◆Gathering temperature rise, fire hazard
◆Maintenance difficulties
◆Flexibility is poor
◆Array cabinet occupies the
cabinet position Intelligent bus
system
◆Convenient installation, short construction
period
◆Top installed easy to maintenance
◆Fast heat dissipation, low temperature rise,
more safe
32
PART 2
Bus monitoring products
Selection of cases
33
YOUR CONPANY NAME
It can be seen from the above figure that there are 2 busbars, and each busbar has 5 plug-in boxes +1 starting
box, so the configuration of 2 in and 2 out can be judged.
Customer's electrical diagram
Selection of cases
34
YOUR CONPANY NAME
Configuration solution
AC bus monitoring moduleAMB100/110-A
35
YOUR CONPANY NAME
Communication port: network cable
connection
Communication port needs to use RJ45 network shielding
cable.
When connect the detecting modules
the former RS485 (Ⅰ) connect with latter RS485 (Ⅱ);
!!!When the detection module connect with the
displayer!!!
The detection module in the cabinet of RS485 (Ⅱ)
connected to the display RS485 (Ⅰ)
Displayer of RS485 (Ⅱ) connected to a box after detection
module of RS485 (Ⅰ)
AC bus monitoring moduleAMB100/110-A
36
YOUR CONPANY NAME
Signal interface: power supply & voltage & current access
L/N take MCB inlet side
UA/UB/UC/UN take MCB outlet
side
Switching state can be
determined by voltage
current>600A current<600A
AC bus monitoring moduleAMB100/110-A
37
YOUR CONPANY NAME
Function interface: switching & temperature & leakage
Monitor CB status with auxiliary
contacts
Monitor SPD status
Drive fault indicator & buzzer
starting box 8-way temp measurement
plug-in box 4-way temp measurement
AC bus monitoring moduleAMB100/110-A
38
YOUR CONPANY NAME
Matching accessories: CT& temperature probe & leakage current sensor
Optional leakage
CT
Default aperture 8mm,
Length 1m
Adaptor
DC bus monitoring module AMB100/110-D
39
YOUR CONPANY NAME
Communication port: network cable connection, same
with the AC module
Communication port needs to use RJ45 network shielding
cable.
When connect the detecting modules
the former RS485 (Ⅰ) connect with latter RS485 (Ⅱ);
!!!When the detection module connect with the
displayer!!!
The detection module in the cabinet of RS485 (Ⅱ)
connected to the display RS485 (Ⅰ)
Displayer of RS485 (Ⅱ) connected to a box after detection
module of RS485 (Ⅰ)
DC bus monitoring module AMB100/110-D
40
YOUR CONPANY NAME
Signal interface: power supply & voltage & current access
Power supplier take CB inlet side, U+/U- take CB outlet side,
switching state is determined by voltage
±12V/G give Power to the Hall sensor
DC bus monitoring module AMB100/110-D
41
YOUR CONPANY NAME
Function interface: switching & temperature & leakage
Monitor CB status with
auxiliary contacts
Monitor the status of thunder
Drive fault indicator &
buzzer
DC bus monitoring module AMB100/110-D
42
YOUR CONPANY NAME
Auxiliary components: Hall sensor & temperature probe & leakage current sensor
Optional
Bus monitoring displayer AMB10(选配)
43
YOUR CONPANY NAME
Displayer: for display and parameter configuration (with front and rear Ethernet)
It can be embedded and mounted on the
plug-in box/starting box
Voltage/current data can be checked
Corresponding parameters such as
address and baud rate can be configured
Wireless networking module AWT100(optional)
44
YOUR CONPANY NAME
Wireless extension: for wireless networking LoRa Wireless networking
The recommended
transmission distance is not
more than 200m(In theory,)
DC24V power supply
A receiver needs to be
configured
The receiver is connected to
the touch screen by RS485
Data Collection Gateway ANET (optional)
45
YOUR CONPANY NAME
Communication management machine: centralized data acquisition and transmission to the
power and environment monitoring system
ANet-2E8S1
8 RS485 Port
2 Ethernet Port
DC24V/AC220V
power supplier
USB export
SD card storage
DIN35mm
installation
ANet-1E2S1-4G
2 RS485 Port
1Ethernet Port
DC24V/AC220V
power supplier
4G wireless
transmission
SD card storage
DIN35mm
installation
Local monitoring touch screen ATP010(optional)
46
YOUR CONPANY NAME
Touch screen: local monitoring system
Local monitoring touch screen accessory(optional)
47
YOUR CONPANY NAME
Touch screen wiring/connector
Local monitoring touch screen accessory(optional)
48
YOUR CONPANY NAME
Switching power supply: Power supply to touch screen
AC220V convert to 24V output,
output power is 30W;
DIN35mm installation
Starting box/plug-in box production
49
YOUR CONPANY NAME
Starting box/plug-in box production
50
YOUR CONPANY NAME
!!!The communication address of the corresponding monitoring module must be affixed on the
conspicuous position of the box body (you can see it by looking up)!!!
!!!Auxiliary power takes form CB inlet side!!!
!!!Voltage input takes from CB outlet side!!!