Technical Parameters
| Technical Data | |
| Location of Use | Sub-Distribution Boards |
| NetworkSystems | TT,TN-S |
| Mode of Protection | L-N,N-PE |
| SurgeRatings | In= 20kA (8/20 μs) |
| IEC/EN Category | ClassII/Type2/Type1CA |
| ProtectiveElements | HighEnergyMOVandGDT |
| Housing | Pluggable Design |
| Compliance | IEC 61643-11:2011 EN 61643-11:2012 |
| IEC ELECTRICAL | ||||||||
| YRSP-A21P+N | 75 | 150 | 275 | 320 | 385 | 440 | ||
| Nominal AC Voltage (50/60Hz) | 60V | 120V | 230V | 230V | 230V | 400V | ||
| Maximum Continuous Operating Voltage (AC) | (L-N) U。 (N-PE) Uc | 75V | 150V | 275V | 320V | 385V | 440V | |
| 255V | ||||||||
| Nominal Discharge Current (8/20 μs) (L-N)/(N-PE) In | 20kA/20kA 40kA/40kA | |||||||
| Maximum Discharge Current (8/20 μs) | (L-N)/(N-PE) Imax | |||||||
| VoltageProtection Level | (L - N)/ (N -PE) Up | 0.4kV/1.5kV1.0kV/1.5kV1.5kV/1.5kV1.6kV/1.5kV1.8kV/1.5kV | 2.0kV/1.5kV | |||||
| Follow Current Interrupt Rating | (N-PE) I | none 100ARMS | ||||||
| ResidualCurrentat Uc | IPE | |||||||
| Response Time (L-N)/(N-PE) tA | ||||||||
| Back-Up Fuse (max) | 125AgL/gG | |||||||
| Short-CircuitCurrentRating (AC) TOV Withstand 5s | (L-N) IsCCR | 25kA | ||||||
| TOV120min | (L-N) UT (L-N) UT | 90V 115V | 180V 230V | 335V 440V | 335V 440V | 335V 440V | 580V 765V | |
| mode | Withstand | Withstand | Safe Fail | Safe Fail | Safe Fail | Safe Fail | ||
| TOV Withstand 200ms | (N-PE) UT | 1200V | ||||||
| Number of Ports | ||||||||
| Mechanical&Environmental | ||||||||
| Operating Temperature Range T | -40F to+158F[-40℃ to+70℃] | |||||||
| PermissibleOperating Humidity | RH 5%...95% | |||||||
| Atmospheric pressureand altitude | 80kPa...106kPa/-500m...2000m | |||||||
| Terminal Screw Torque | 39.9 Ibf-in [4.5Nm] Mmax | |||||||
| Conductor Cross Section (max) | 5AWG(Solid,Stranded)/5AWG (Flexible) | |||||||
| 16mm²(Solid,Stranded)/16 mm²(Flexible) 35mmDINRail,EN60715 | ||||||||
| Mounting | IP 20 (built-in) | |||||||
| Degree of Protection | Thermoplastic:ExtinguishingDegreeUL94V-0 | |||||||
| HousingMaterial | Yes | |||||||
| Thermal Protection | Green ok/Red defect | |||||||
| OperatingState/Fault Indication | Optional | |||||||
| Remote Contacts (RC) | ||||||||
| RC Switching Capacity | AC:250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A | |||||||
| RC Conductor Cross Section (max) | 16 AWG (Solid) /1.5 mm²(Solid) | |||||||
InternalConfiguration
Dimensions&Packaging
Unit: mm
Connection Diagram
Technical Parameters
| Technical Data | |
| Location of Use | Sub-Distribution Boards |
| NetworkSystems | TT,TN-S |
| Mode of Protection | L-N,N-PE |
| SurgeRatings | In= 20kA (8/20 μs) |
| IEC/EN Category | ClassII/Type2/Type1CA |
| ProtectiveElements | HighEnergyMOVandGDT |
| Housing | Pluggable Design |
| Compliance | IEC 61643-11:2011 EN 61643-11:2012 |
| IEC ELECTRICAL YRSP-A23P+N | 150 | 275 | 320 | 385 | 440 | ||
| Nominal AC Voltage (50/60Hz) | 120V | 230V | 230V | 230V | 400V | ||
| Maximum Continuous (L-N) U。 | 150V | 275V | 320V | 385V | 440V | ||
| Operating Voltage (AC) | (N-PE)U | 255V | |||||
| Nominal Discharge Current (8/20 μs) (L-N)/(N-PE) In | 20kA/20kA | ||||||
| Maximum Discharge Current (8/20 us) | 40kA/40kA | ||||||
| VoltageProtectionLevel | (L-N)/(N-PE) Imax (L- N)/(N -PE) Up | 1.0kV/1.5kV 1.5kV/1.5kV | 1.6kV/1.5kV | 1.8kV/1.5kV | 2.0kV/1.5kV | ||
| Follow Current Interrupt Rating | (N-PE)In | ||||||
| Residual Currentat Uc | IPE | ||||||
| Response Time (L-N)/(N-PE) tA | |||||||
| Back-Up Fuse (max) | 125AgL/gG | ||||||
| Short-Circuit Current Rating (AC) | 25kA (L-N) IsCCR | ||||||
| TOVWithstand 5s | (L-N) UT | 180V | 335V | 335V | 335V | 580V | |
| TOV120min | (L-N) UT | 230V | 440V | 440V | 440V | 765V | |
| TOV Withstand 200ms | mode | Withstand | SafeFail | Safe Fail 1200V | Safe Fail | Safe Fail | |
| Number of Ports | (N-PE) UT | ||||||
| Mechanical&Environmental | |||||||
| Operating Temperature Range | T -40°Fto+158°F[-40℃to+70C] | ||||||
| PermissibleOperating Humidity | RH 5%...95% | ||||||
| Atmospheric pressureand altitude | 80k Pa...106kPa/-500 m...2000 m | ||||||
| Terminal Screw Torque | 39.9 Ibf-in [4.5Nm] Mmax | ||||||
| Conductor Cross Section (max) | 5AWG (Solid,Stranded)/5AWG (Flexible) | ||||||
| Mounting | 16mm²(Solid,Stranded)/16 mm²(Flexible) | ||||||
| 35mmDINRail,EN60715 | |||||||
| Degree of Protection | IP 20 (built-in) | ||||||
| HousingMaterial | Thermoplastic:ExtinguishingDegreeUL94V-0 | ||||||
| Thermal Protection | Yes | ||||||
| OperatingState/FaultIndication | Greenok/Red defect | ||||||
| Remote Contacts (RC) | Optional | ||||||
| RCSwitching Capacity | AC:250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A | ||||||
| RC Conductor Cross Section (max) | 16 AWG (Solid) /1.5 mm²(Solid) | ||||||
InternalConfiguration
Dimensions&Packaging
Unit:mm
Connection Diagram
YRSP-A12SERIES Type1+2Surge ProtectiveDevice
Technical Parameters
| Technical Data | |
| Location of Use | MainDistribution Boards |
| NetworkSystems | TN-S,T-C,TT (only-) |
| Mode of Protection | L-PE,N-PE(onlyTN-S),L-PEN,L-N |
| SurgeRatings | Iimp=up to12.5kA(10/350 μs) |
| In=up to20kA(8/20 us) | |
| IEC/EN Category | Class I+II/Type1+2 |
| Protective Elements | High EnergyMOV |
| Housing | Pluggable Design |
| Compliance | IEC 61643-11:2011、EN61643-11:2012 |
| IEC ELECTRICAL | ||||||||
| YRSP-A12 | 75 | 150 | 275 | 320 | 385 440 | |||
| NominalACVoltage(50/60Hz) | U/Un | 60V | 120V 230V | 230V | 230V | 400V | ||
| Maximum Continuous Operating Voltage (AC) | Uc | 75V 150V | 275V | 320V | 385V | 440V | ||
| Nominal Discharge Current (8/20 μs) | 20kA 20kA | 20kA | 20kA | 20kA | 20kA | |||
| Maximum Discharge Current (8/20 μs) | Imax | 50kA | 50kA | 50kA | 50kA 50kA | 50kA | ||
| Impulse DischargeCurrent(10/350 μs) | limp | 7kA | 7kA | 7kA | 7kA 7kA | 7kA | ||
| limp | 12.5kA | 12.5kA | 12.5kA | 12.5kA 12.5kA | 12.5kA | |||
| Specific Energy | W/R | 39kJ/Ω | 39kJ/Ω | 39kJ/Ω | 39kJ/Ω | 25kJ/Ω | 25kJ/Ω | |
| Charge | Q | 6.25As | 6.25As | 6.25As | 6.25As | 5As | 5As | |
| VoltageProtection Level | Up | 700V | 1000V | 1500V | 1600V | 1800V | 2000V | |
| Residual Currentat UC | IPE | |||||||
| Response Time tA | ||||||||
| Back-Up Fuse(max) IsCCR | 160AgL/gG | |||||||
| Short-Circuit Current Rating (AC) | 25kA | |||||||
| TOVWithstand 5s | UT | 114V 180V 335V 335V | ||||||
| U | 114V | 230V | 440V | 440V | 440V | 765V | ||
| TOV120min Numberof Ports | mode | Withstand | SafeFail | Safe Fail 1 | Safe Fail | Safe Fail | Safe Fail | |
| Mechanical&Environmental | |
| Operating Temperature Range | Ta -40°Fto+158°F[-40℃to+70C] |
| Permissible Operating Humidity | RH 5%...95% |
| Atmospheric pressure and altitude | 80k Pa...106kPa/-500 m...2000m |
| TerminalScrewTorque | 39.9 Ibf-in [4.5Nm] Mmax |
| Conductor Cross Section (max) | 5AWG (Solid,Stranded)/5AWG (Flexible) |
| 16mm²(Solid,Stranded)/16mm²(Flexible) | |
| Mounting | 35mmDINRail,EN60715 |
| Degree of Protection | IP 20 (built-in) |
| Housing Material | Thermoplastic:Extinguishing DegreeUL94V-0 |
| Thermal Protection | Yes |
| OperatingState/Fault Indication | Greenok/Reddefect |
| Remote Contacts (RC) | Optional |
| RCSwitching Capacity | AC:250V/0.5A;DC:250V/0.1A;125V/0.2A;75V/0.5A |
| RC Conductor Cross Section (max) | 16 AWG (Solid) /1.5 mm²(Solid) |
Internal Configuration
Legend
LLine
NNeutral
{ ± } Protective Earth
SSignalling Contacts Optional
國國
Legend
LLine NNeutral /PE ProtectiveEarth SSignalling Contacts Optional
Legend
LLine NNeutral /PEProtectiveEarth SSignalling Contacts Optional
Legend
L Line NNeutral /PEProtectiveEarth SSignalling ContactsOptional
Dimensions& Packaging
| YRSP-A2 | 150 | 275 | 320 | 385 | 440 |
| SingleUnitDIN43880Dimension | 1CTN | ||||
| Packaging Dimensions(HxWxL) | [520×220×300mm] | ||||
| Pole | 1Pole | 2Pole | 3Pole | 4Pole | |
| MinimumOrderQuantity | 144Units | 72Units | 48Units | 36Units | |
Connection Diagram
YRL7i-125 SERIES AC Isolator Switch
TechnicalData
| Electrical Features | |
| Rated current (In) | 32A,40A,50A,63A,100A,125 |
| Pole | 1P,2P,3P,4P |
| Rated voltage (Ue) | 1P:240V~ 2/3/4P:415V- |
| Insulation voltage (Ui) | 500V |
| Ratedfrequency | 50/60Hz |
| Rated short-timewithstand current (Icw) | 12le1s |
| Ratedmakingandbreakingcapacity | 3le,1.05Ue,cos(p=0.65 |
| Rated short circuit making capacity | 20le,t=0.1s |
| Usingthecategories | AC-22A |
| Mechanical life | 10000 |
| Electrical life | 4000 |
| Terminal size top/bottom forcable | 25mm² |
| Tightening torque | 2.5Nm |
| Switching Frequency | In 25A240times/hour In 25A120times/hour |
Dimensions
Unit: mm
YRAS8O SERIES ACRotary lsolation Switch
Overview
Add-onAuxiliary Contacts
Theisolatingswitchadopts the sameauxiliary contact, andtheauxiliarycontactand themain pole of theswitch actatthesametime.Anormallyopencontactwithpredisconnect functioncan beprovidedasrequired.The isolation switch can be installed with up to fourauxiliary accessories(2onthe right,2on the left)
Terminal Shrouds
The isolation switch terminal shroud has a simple appearance design,high-quality transparent PC material,flame-retardant,high strength,nocolor changeafter long-termuse,high-qualitywaterproof and easy to install.
Rotating HandleParts
Rotating handle,with anti-misoperation padlock design to prevent misoperation,safe and reliable;using highqualityflame-retardantmaterials,insulationandimpact resistance;elegant and stylish design,beautiful and durable.
SideMountAdd-onFourthPole
Simultaneous or early contact operation of the fourth pole with respect to the switch disconnector poles.
Rod Extension
High-carbon steel material,beautiful and corrosionresistant;coupled with hightemperature treatment, evenifsuficientpressureisapplied,itcanmaintain good smoothness;the products are standardized,easy toassemble,lowcost,corrosionresistant,and costeffective.
Switch Body
Adopts compression contact opening and closing technology,and has the function of complete disconnectionindication.Itisanisolator\`abreakeror aswitch,andwithinlerlockmechanism,itcanbetoan exchage switch.
MechanicalInterlockingMechanism
Theinterior is made of high-conductivity nickelphosphorus copper,which has good conductivityand longerservice life.The shell is made of high-strength flameretardantPCmaterial,whichisfireresistantand flame-retardant,in onestep!
Technical Data
| Current(≤40℃) Agreed heating current | 16A | 20A | 25A | 32A | 40A | 63A | 80A | 100A | 100A | 125A | |
| IECrated operational current le AC-21A/B(≤690V) | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | |
| Ectratenal | 16A/16A | 20A/20A | 25A/25A | 32A/32A | 40A/40A | 63A/63A | 80A/80A | 100A/100A | 100A/100A | 125A/125A | |
| AC-22A/B IECrated | 415V 690V | 32A/40A | 40A/63A | 63A/80A | 63A/80A | 80A/100A | 100A/125A | ||||
| 415V | 16A/16A | 32A/32A 40A/40A | 63A/63A 80A/80A | 100A/100A | 100A/100A | 125A/125A | |||||
| 20A/20A 25A/25A | |||||||||||
| IECrated curratonal DC-21B | 500V | 25A/25A | 63A/63A | 80A/80A | 100A/10A | ||||||
| 110VDC | 16A | 20A | 25A① | 32A① | 40A① | 63A | 80A | 100A | 100A | 125A | |
| 250VDC | 16A | 20A | 25A | 32A | 63A② | 80A | 100A | 100A | 125A | ||
| 400VDC | 16A | 20A | 25A | 40A② 25A | 40A | 63A | |||||
| IECrated power(3phase) AC-23A/B | 415V 500V | 7.5KW | 9KW | 11KW | 15KW | 18.5KW | 30KW | 37KW | 45KW | 55KW | |
| Short circuit withstand current of fuse protection (kA rms expected value) | 690V 11KW 15KW | ||||||||||
| Fuseclass | 40A 63A | 80A | 100A | 125A | |||||||
| Rated conditional short-circuit | 415V 16A | 20A | 15kA | ||||||||
| 415V current | 10kA | ||||||||||
| Witedtshortimet | Shortcircuitwithstandcurrentofcircuitbreakerforprotection,anycircuitbreakerthatcantripwithin0.3s | 5kA | |||||||||
| Shortcircuitperformance(unprotected) | 0.3S 2.5kA | ||||||||||
| Witstshortimet 15 | 1.26kA | 2.75kA | |||||||||
| Rakinshort circuit | 1.8kA | 2.1kA | 3.9kA | ||||||||
| Cable cross section | 1.5~10mm² | 2.5~35mm² 800V | 10~70mm² | ||||||||
| RatedinsulationvoltageUi | |||||||||||
| Rated Oiulsewithstand | 8kV | ||||||||||
| Mechanical Endurance | 100000 Operating-25~+55℃ | ||||||||||
| AmbientTemperature | Storage-40~+70℃C | ||||||||||
Technical Data
| Current(eatingcurent | 63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | ||
| IECrated operational current le AC-21A/B(≤690V) | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | ||
| AC-22A/B | 415V | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | |
| 690V | 40A/63A | 63A/80A | 63A/80A | 40A/63A | 63A/80A | 63A/80A | 40A/63A | 63A/80A | 63A/80A | ||
| IECrated curreatonal AC-23A/B | 415V | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | 63A/63A | 80A/80A | 100A/100A | |
| 500V | 63A/63A | 63A/63A | 63A/63A | ||||||||
| 690V | 40A/40A | 40A/40A | 40A/40A | ||||||||
| IECrated currational DC-21B | 110VDC | 63A① | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | |
| 250VDC | 63A② | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | ||
| 400VDC | 40A | 40A | 40A | ||||||||
| IECrated power(3phase) AC-23A/B | 415V 500V 690V | 30KW | 37KW | 45KW | 30KW | 37KW | 45KW | 30KW | 37KW | 45KW | |
| Short circuit withstand current of fuse protection (kA rms expected value) | |||||||||||
| Fuse class | 415V | 63A | 80A | 100A | 63A | 80A | 100A | 63A | 80A | 100A | |
| Rated conditional short-circuit 415V current | |||||||||||
| Shortcircuitwithstandcurrentofcircuitbreakerforprotection,anycircuitbreakerthatcantripwithin0.3s | 15kA | ||||||||||
| Witestshort-timet 0.35 | |||||||||||
| Short circuitperformance (unprotected) | |||||||||||
| Witedtshortutimet 1S | |||||||||||
| Rakidshortcircuit | 1.4kA | ||||||||||
| Cable cross section RatedinsulationvoltageUi | 2.5~35mm2 800V | ||||||||||
| Ratedimiulsewithstand | 8kV | ||||||||||
| Mechanical Endurance | 100000 | ||||||||||
| AmbientTemperature | Operating-25~+55C Storage-40~+70C | ||||||||||
YRAS80ACIsolatorAddon
| Fourthpole,simultaneous closing operationas switch poles | ||||||
| Type | YRAS80-PS40 | YRAS80-PSR40 | YRAS80-PS80 | YRAS80-PSR80 | YRAS80-PS125 | YRAS80-PSR125 |
| Ith | 40A | 40A | 80A | 80A | 125A | 125A |
| Width | 11mm | 11mm | 16mm | 16mm | 21.3mm | 21.3mm |
| Appliedto | YRAS80-16~ YRAS80-40 | YRAS80-PM16~ YRAS80-PM40 | YRAS80-63~ YRAS80-80 | YRAS80-PM63~ YRAS80-PM80 | YRAS80-100~ YRAS80-125 | YRAS80-PM100~ YRAS80-PM125 |
| Function | 7L4 8 1 8T4 | 7L4 8 8T4 | 7L4 18 | |||
| Fourthpole,early-make closing operationwith respecttoswitch poles | ||||||
| Type | YRAS80-PD40 | YRAS80-PDR40 | YRAS80-PD80 | YRAS80-PDR80 | YRAS80-PD125 | YRAS80-PDR125 |
| Ith | 40A | 40A | 80A | 80A | 125A | 125A |
| Width | 11mm | 11mm | 16mm | 16mm | 21.3mm | 21.3mm |
| Appliedto | YRAS80-16~ YRAS80-40 | YRAS80-PM16~ YRAS80-PM40 | YRAS80-63~ YRAS80-80 | YRAS80-PM63~ YRAS80-PM80 | YRAS80-100~ YRAS80-125 | YRAS80-PM100~ YRAS80-PM125 |
| Function | TL4 8 1 | TL4 8 11 8T4 | TL4 8 | |||
YRAS80 ACIsolatorAddon
| Neutral plateterminal | |||||||
| Type | YRAS80-PN40 | YRAS80-PNR40 | YRAS80-PN80 | YRAS80-PNR80 | YRAS80-PN125 | YRAS80-PNR125 | |
| Ith | 40A | 40A | 80A | 80A | 125A | 125A | |
| Width | 11mm | 11mm | 16mm | 16mm | 21.3mm | 21.3mm | |
| Appliedto | YRAS80-16~ YRAS80-40 | YRAS80-PM16~ YRAS80-PM40 | YRAS80-63~ YRAS80-80 | YRAS80-PM63~ YRAS80-PM80 | YRAS80-100~ YRAS80-125 | YRAS80-PM100~ YRAS80-PM125 | |
| Function | N 6 N | N N | N 6 | ||||
| Earth/Ground Plate terminal | ||||||
| Type | YRAS80-PE40 | YRAS80-PER40 | YRAS80-PE80 | YRAS80-PER80 | YRAS80-PE125 | YRAS80-PER125 |
| Ith | 40A | 40A | 80A | 80A | 125A | 125A |
| Width | 11mm | 11mm | 16mm | 16mm | 21.3mm | 21.3mm |
| Appliedto | YRAS80-16~ YRAS80-40 | YRAS80-PM16~ YRAS80-PM40 | YRAS80-63~ YRAS80-80 | YRAS80-PM63~ YRAS80-PM80 | YRAS80-100~ YRAS80-125 | YRAS80-PM100~ YRAS80-PM125 |
| Function | PE d | PE d | PE | |||
YRAS80 AC IsolatorAddon
| Add-onAuxiliaryContacts | |||||||
| Oneonlyadd-onblocksuitablefor alteEutiss | . / 一 □ | ||||||
| withtheswitch poles. Type | YRAS80-P1 | YRAS80-P2 | YRAS80-P1R | ||||
| Contacts | 1NO+1NC | 2NO | 1NO+1NC | 2NO | YRAS80-P2R | ||
| Width | 9mm | 9mm | 9mm | ||||
| Parameter | AC-13:10A,230V~ AC-15: 6A,230V~ | AC-13:10A,230V~ AC-15:6A,230V~ | 9mm | ||||
| Function | 1N0+1NC 1321 | 2N0 1323 | 1NO+1NC 1321 4 | 2N0 1323 | |||
| Description | 1422 1424 ForDB,DC,EL, | 1422 | 1424 | ||||
| ForPM | |||||||
MechanicalCombinationSystem
Overalland InstallationDimension
YRAS80-PS40RYRAS80-PN40R YRAS80-PD40R YRAS80-PE40R
YRAS80-PS125RYRAS80-PN125RYRAS80-PD125R YRAS80-PE125R
OverallandInstallationDimension
Auxiliarycontact
Unit: mm
YRAS69 SERIES ACRotary lsolation Switch
Technical Data
| Type | YRAS69EL/20/4R | YRAS69EL/32/4R | YRAS69EL/40/4R | YRAS69EL/63/3R | YRAS69EL/80/3R | ||
| Rated carry current | 20A | 32A | 40A | 63A | 80A | ||
| Ac-d operating current | 16A | 25A | 32A | 45A | 45A | ||
| Rated operating current | 12A | 23A | 30A | 37A | 37A | ||
| Rated powercontrol AC-23A | 240V | 4KW | 7.5KW | 9KW | 15KW | 15KW | |
| 440V | 7.5KW | 12.5KW | 16KW | 22KW | 22KW | ||
| Rated power control AC-3 | 240V | 3KW | 5.5KW | 7.5KW | 11KW | 11KW | |
| 440V | 5.5KW | 11KW | 15KW | 18.5KW | 18.5KW | ||
| UL-CSA Motor load | 240V | 3KW | 5KW | 5KW | 10KW | 10KW | |
| 440V | 7.5KW | 10KW | 10KW | 20KW | 20KW | ||
| Wited shorttimet | 250A | 400A | 500A | 600A | 850A | ||
| Cable | 0.5-10MM² | 1-16MM2 | |||||
| Screw torque | 0.8-1.7N·m | 1.5-2N·m | |||||
| Rated insulation voltage | 690V | ||||||
Overall and Installation Dimension
Unit:mm
YRAS69 SERIES ManualTransferSwitch
Overview
YRAS69-XX/X3 series manual transfer switch is mainly used for50/60Hz,AC ratedvoltagebelow440Vorbelow DC 240Vand rated currentbelow16oAelectrical circuit.This is used asa manual circuit for infrequent connection or disconnection,for control or switching purposes,and can also be used to directly control three-phase asynchronous motors and asa main signal control and circuit measurement.
Working conditions
⊚ Thealtitude must not exceed 2 0 0 0 0 m
The ambient air temperature should not exceed + 4 0 ^ { \circ } \mathsf { C } (204号 and theaverage temperaturewithin24 hours should notexceed + 3 5 ^ { \circ } C ,thelowest temperatureshould not be lower than - 2 5 ^ { \circ } C :
When themaximum temperatureis + 4 0 ^ { \circ } \mathsf { C } ,therelative humidity of theair should notexceed 50 % Atlower temperatures,higherrelative humiditycanbeallowed, forexample,up to 90 % .Special measuresshould be takento prevent condensation thatmayoccurdue to temperaturechanges.
Technical Data
| TypeCode | YRAS69-20 | YRAS69-32 | YRAS69-63 | YRAS69-125 | YRAS69-160 |
| UiV | 660 | 660 | 660 | 660 | 660 |
| IthA | 20 | 32 | 63 | 125 | 160 |
| UeV | 24,110,240,440 | 240,440 | 240,440 | 240,440 | 240,440 |
| AC-21AAC-22A A | 10,10 | 32,32 | 63,63 | 100,100 | 150,150 |
| AC-23A A | 7.5,7.5 | 30,30 | 57,57 | 90,90 | 135,135 |
| AC-2 | A 7.5,7.5 | 30,30 | 57,57 | 90,90 | 135,135 |
| AC-3 A | 5.5,5.5 | 22,22 | 36,36 | 75,75 | 95,95 |
| AC-4 A | 1.75,1.75 | 11,11 | 15,15 | 30,30 | 55,55 |
| AC-15 A | 2.5, 1.5 | 14,6 | |||
| DC-13 A | 120.4,0.4 | ||||
| AC-23A KW | 1.8,3 | 7.5/4,15/7.5 | 15/10,30/18.5 | 30/15,45/22 | 37/22,75/37 |
| AC-2 KW | 2.5,3.7 | 7.5,15 | 18.5,30 | 30,45 | 37,55 |
| AC-3 KW | 1.5,2.2 | 5.5, 11/5.5 | 11/6, 18.5/11 | 15/7.5,30/13 | 22/11,37/18.5 |
| AC-4 KW | 0.37,0.55 | 2.7/1.5,5.5/3 | 5.5/2.4,7.5/4 | 6/3,12/5.5 | 10/4,15/7.5 |
Dimension and Installation Size
| TypeCode | AuxiliaryContact | Pole | ||||||
| A | B | C1 | C2 | D1 | D2 | D3 E | ||
| YRAS69EL-20/23 | 68.5 | 70.5 | 6.5 | Φ18 | Φ5 | 44 1-2 | ||
| YRAS69EL-20/43 | 68.5 | 122.5 | 6.5 | - | 18 | - Φ5 | 44 | 1-7 |
| YRAS69EL-63/23 | 113 | 107.5 | 18 | 23.5 | 27 | Φ21 5 | 78 | 1-3 |
| YRAS69EL-63/43 | 113 | 158.5 | 18 | 23.5 | Φ27 | Φ21 Φ5 | 78 | 1-6 |
| YRAS69EL-125/43 | 137 | 206.5 | 18 | 23.5 | Φ27 | Φ21 | Φ5 78 | 1-4 |
| YRAS69EL-160/43 | 137 | 206.5 | 18 | 23.5 | 27 | Φ21 | Φ5 78 | 1-4 |
YRQ2CB-63/125SERIES DualPowerTransferSwitch For AC Power System
Application
YRQ2CB-63/125 series micro-breaking dual power transfer switchissuitable forAC50/6oHzdual powersupolysystem with rated operating voltage of 4ooVamd rated operating current form16\~125A.Optional transferof dual power can bemade according to requirement.
Advantages
⊚ Complete protective fun ctions,including short circuit, overload,open phase and loss-of-voltage protection. ⊚ Reliableremotedouble-breakwithEPsfireprotectin powersupply interfaceDC12-24V ⊚ Noiseless,energysaving,simple installation,easy operation,raliableandstableperformance
ProductPerformance
| MainParameters | |
| Rated short circuit breaking capacity | 3/6kA |
| Rated shortcircuit making capacity | 3/6kA |
| Transfertime | 3S |
| Control voltageoftransferswitch | AC230V |
| Mechanical lifeof transferswitch | Mechanicallife:3000 times |
| (transferof normal and reserve power) | Electric life:1500 times |
| Ratedinsulationvoltage | U=500V |
| Rated working current | 10A,16A,20A,32A,40A,50A,63A,80A,100A,125A |
| MakingandBreakingCapacuy | ||||||
| Utilization Category | Makingand BreakingTestCondition | |||||
| AC-B33 | I/le | U/Ue | CosΦ | Electrical time(s) | Durationofcycle(min) | Numberofoperatingcycles |
| 6.0 | 1.05 | 0.5 | 0.05 | ≤5 | 12 | |
| Note:AC-B33motorloadorcombinedloadinccludingmotorandresistanceloadunderinfrequentoperationcondition | ||||||
DifferencesbetweenClassAand ClassB
ClassAcontains Circuit Breaker inside with overload and short-circuit protection.
⊚ ClassB contains disconnector switch inside without overload and short-circuit.
Dimensions
Note:Whenyou install the4PATSas3P,terminal No.3andNo.6mustconnecttheneutral line. Theterminalstoindicatoris 2 2 0 V , donot connectthepowersupplytotheterminals! NPower NPowerNO NNeutral 刀 RPowerNO RNeutral ? ? ? Power ? 1 2 3 4 5 6
YRQ2CB-125SERIES AutomaticTransferSwitch
Application
YRQ2CB-125seriesautomatictransferswitch (hereinafterreferredtoasATS),itissuitableforthepowersupplysystemofAC 50/60Hz,ratedvoltage40oV,ratedcurrentof125Aandbelow.Choiceandconversionbetween twopowersupplyaccording to theneeds.ATShaveprotectionfunctionsofoverload,shortcircuitunder-voltage,butalsohavefunctionsoffiredouble breakingandoutputclosingsignal.Particularlyapplicabletothelightinglinesinoficebuildings,shoppingmals,banksig risebuildingsand other places with needs of the fire.
YRQ2CB-125Automatic Transfer Switch complies with EN/IEC 60947-6-1 standard.
Normal workingconditions
Thealtitude of the installation site should notexceed 2 0 0 0 \mathsf { m }
Ambientairtemperature Ambient air temperature does not exceed the upper limit is + 4 0 ^ { \circ } C ; theaverage ambient air temperature in 24h does not exceed + 3 5 ^ { \circ } C Theambient air temperature lower limit is not less than - 5 ^ { \circ } C
Atmospheric conditions
0 Humidity At themaximum temperature of + 4 0 ^ { \circ } \mathsf C , theair relative humidityis less than 5 0 % ,there isa higherrelative humidity allowed at lower temperatures,for example,up to 9 0 % at 2 0 ^ { \circ } C Special measures should be taken for gel that is occasionally generated due to changes of humidity.
\circ Pollution degree:3
⊚ Installation conditions Installedintheplacewithoutshockand invasionofrainandsnow;theupper terminalconnecttothepowerside,the lowrterminalconnecttothe load side;theinclination between productsand verticalplane is not more than 5 ^ { \circ }
Installation category:IⅢ
Theexternalmagneticfield neartheinstalationsitedoesnotexceed5timesthegeomagneticfield inanydirection.
ProductPerformance
| MainParameters | ||
| Meetthe standards | EN/IEC 60947-6-1 | |
| ATSclass | CBclass | |
| Usecategories | AC-33iB | |
| Ratedoperating voltage Ue | AC230V-400V | |
| Rated operating frequency | 50Hz/60Hz | |
| RatedoperatingcurrentIe | 6A,10A,16A,2A,25A,2A,4A,5A63A10A | |
| Switching control voltage | AC230V | |
| Rated insulationvoltage Ui | AC690V | |
| Conversion operation time | ≤3s(Notadjustable,the factory hasbeenadjusted) | |
| Life | Electrical life | 1500times |
| Mechanaical life | 6000times | |
| Rated short-timemaking capacityIcm | 7.5kA | |
| Ratedshort-timebreakingcapacityIcn | 5kA | |
| RatedcurrentIn(A) | 6 | 10 | 1620 | 25 | 32 | 4050 | 63 |
| Wertionalaperbarmm2 | 1.0 | 1.5 | 2.5 | 4.0 | 6.0 | 10 | 16 |
Dimensions
Unit: mm
| Specification | W | W1 | L | L1 | H |
| 63/1252PDtype | 174 | 160 | 134 | 123 | 120 |
| 63/1253PDtype | 210 | 193 | 134 | 123 | 120 |
| 63/1254PDtype | 245 | 228 | 134 | 123 | 120 |
Terminalwiringschematicdiagram
N Closing R Closing 区 8 NPower RPower 区 ? 5 N Zero line RZero line 6
1:Commonclosing indication
2:Commonpower indication
3:Common indicator zero line
4:Standbyclosing indication
5:Standbypowersupply indication
6:Standby indicatorzero line
Note:1,2,4and5haveAC220Vpoweroutput, pleasedonotconnectexternalpowersupply.
OptionalfunctionOnlyavailableforbelow63A
7:Firesignal zero line input
8:Thefire signal is DC24V (nonstandard voltage signalcanbecustomized)
9-10:generatoroil enginesignal output
Note:when the double power supplyis three pole,
pleasesend:
Commonzerolineaccessterminal3
Standbyzero lineconnectedtoterminal6
Note:Whenyou installthe4PATSas3P,terminal No.3and No.6must connecttheneutral line. Theterminalstoindicatoris22oV,donot connectthepowersupplytotheterminals!
N NPowerNO NNeutral 刀 RPowerNO RNeutral 区 Power ? ? 1 2 3 4 5 6
YRQ4CBMCCBSERIES Automatic Transfer Switch
Application
YRQ4seriesautomatictransferswitch(hereinafterreferredtoasATSswitch,alsoknownashometransferswitch)fordual powersupplysystemofAC50Hz,ratedvoltageof380V,ratedcurrntof63A\~630A,useautomaticormanualoperationmodes toswitch betweenthecommonpowersupplyandstandbypowersuply.Thehometransferswitchismainlyusedforhospitals, shops,banks,chemicalindustrymetallurgy,highrsebuildings,militaryfacilitiesandtherimportantoccasions.
Thishome transferswitchmeetsGB/T14048.11-2005"ow-voltageswitchgearandcontrolgear-automatictransferswitching equipment"standard.Thisproductelectrical levelisCB-class.
Normalworkingconditions
Ambientair temperature: - 5 ^ { \circ } C ~ + 4 0 ^ { \circ } C , andaverage temperature in 24h is less than + 3 5 ^ { \circ } C ; (204
Atmosphericrelative humidityisnotmore than 5 0 % atambientairtemperatureof + 4 0 ^ { \circ } C ,thereishigherrelative humidityinthe low temperature.The average maximum relative humiditywetestmonth ofthewettest month is 9 0 % , while the averageminimum temperature of thismonth is + 2 5 ^ { \circ } C .Taking into account the condensationon the surface of the product due to temperature changes;
Altitude of installation site is not more than 2 0 0 0 \mathsf { m } :
⊚ Installation category:IV;
⊚ This ATS switch should be installed in the place without severe vibration,shock and corrosion;
Use category:A;
⊚ When the above conditions can notbe met,should be resolvedby userand manufacturer through consultation.
Basicstructure
YRQ4seriesATSswitchismainlycomposedofpowerconversioncircuitbreaker,switchworkhasthreestatuspositionsforthe usertochoose:commonpower(N)closing,double-opening,standbypower(R)closing,thehometransferswitchassal size,light weight,stable operation,easy to use and so on.
Installation and use
When wiring,thecommonpowersuplyNshouldbeconnected to thecommon powersupplycircuit breakerQN,and the standbypowersupplyRshould beconnected tothe standbypowersupplycircuitbreakerQR.WhenQNand QRarefour-wire circuit breakers,theconnectionmodeisaccordingtothewiringdiagram,the1,3,5ofQNandQRarethree-phase(A,B,C) inletterminals,istrole(Netteralistrolnoutetterinal.Ifticteakristeicit breaker,itisecessarythathezerolineNNofthecommonpowersupply(N)andthezerolineNRofthestandypowerupply (R)mustbeconnectedtothethree-polespecialzerolineterminalKG.Specificoperationseewiringdiagram.Thepower supply DualpowerswitchautomaticcontrolertakeinletlineA-phaseandzerolineNofcircuitbreakerQNandQR,ifusethe three-polecircuitbreaker,mustbeconnectedtothezerolineNNandNR,thethre-polededicatedzeroterminalisbetween twocircuitbreakers,intheinstalationandwiringofautomaticpowerswitch,donotmakethelocalcontrolerlineconectedto inletterminal of the circuit breaker forgotten,break orhave short circuit.
Use operation
Whetherthecommon powersupplyand standbypowersuply voltage,both canusemanual operation.When the manual operation,themanual-automaticbutonshouldbeplacedinthemanualoperationposition,whenpushing handleclockwise to theterminal,thestandbypowersupplycircuitbreakerQRisopening,thecommonpowercircuitbreakerQNisclosing;when pushing handlecounterclockwise totheterminal,thestandbypowersupplycircuitbreakerQRisclosing,commonpower supply circuitbreakerQNisopening.
Onthepanel,tepowerdicator(ed),ifthelightisoton,ndicatingthattheutomaticcontrolboxpowersupplyhsfilure cannotoperatetheATSswitchAfterreparedtoormal,anual-automaticbutonisontheautomaticposition,ifthecommon power supplyis normal,theswitch willautomatically inputcommonpowersupply circuit breaker QNin closing state,N indicator(yellow)isnontepanel;ifthecommonpowersupplyisotnormalthnATSswitchwillautomaticallyswitchtothe standby powersupply QR for power supply,standby power supply R indicatorlight (green) is on.
Note:Theactual sizeshall prevail,theabovedata isforreferenceonly.
Dimensions
| Specification | ||||||
| L | L1 | W | W1 | H | D | |
| 63/3 | 290 | 255 | 220 | 200 | 135 | 11 |
| 63/4 | 290 | 255 | 220 | 200 | 135 | 11 |
| 100/3 | 320 | 285 | 240 | 225 | 140 | 11 |
| 100/4 | 320 | 285 | 240 | 225 | 140 | 11 |
| 225/3 | 370 | 335 | 240 | 225 | 160 | 11 |
| 225/4 | 370 | 335 | 240 | 225 | 160 | 11 |
| 400/3 | 525 | 465 | 330 | 300 | 190 | 13 |
| 400/4 | 525 | 465 | 330 | 300 | 190 | 13 |
| 630/3 | 650 | 585 | 330 | 300 | 190 | 13 |
| 630/4 | 650 | 585 | 330 | 300 | 190 | 13 |
YRQ4PC-63SERIES
Uninterrupted Dual Power Automatic Transfer Switch
Application
YRQ4PC-63seriesuninterrupteddualpowerautomatictransferswitchisaPCclassinfrequentchange-overswitch,withtwo stationdesign (commonlyusedforAandstandbyforB),suitableforACsystems withAC50-60Hzandratedcurrent6-63A.
Themain functionof theautomatic transferswitch iswhenthemain power(commonpowersupplyA)fails,theATSwil automatically switch to the backup power(Backup power supply B)to continue working (switching speed \scriptstyle < 5 0 millisoconds), which can effectively solve the troubles caused by power outages.
ProductPerformance
| MainParameters | |
| Case grade | 63A |
| Ratedoperatingcurrent le(A) | 6A,10A,6A,2A,5A,2A,4A,A, |
| Rated insulation voltage Ui | 690V |
| Rderd impulsewithstand voltage Uimp | 8kV |
| Rated working voltage Ue | AC220/AC110V |
| Rated frequency | 50/60Hz |
| Class | PC class:can be switched on an loaded without generating short-circuit current |
| Polenumber | 2P,4P |
| Rated short-circuit current Iq | 50kA |
| Shortcircuit protectiondevice(fuse) | RT16-00-63A |
| Rated impulse withstand voltage | 8kV |
| Control circuit | RatedcontrolvoltageUs:AC220V.50Hz Normalworkingconditions:85%Us-110%Us |
| Auxiliary circuit | AC220V/110V 50Hzle=5A |
| Contactorchange-overtime | □50ms |
| Operation change-over time | □50ms |
| Returnchange-overtime | □50ms |
| MainParameters | |
| Poweroff time | □50ms |
| Change-overoperationtime | □50ms |
| Mechanicallife | □5000Times |
| Electrical life | □1500Times |
| Usagecategory | AC-31B |
Dimensions
Unit: mm
Wiring Instructions
YRQ2PC-125SERIES
Uninterrupted Dual Power AutomaticTransferSwitch
YRO
Foron-grid powerand generator Note:Mustn'tconnectto PV inverter
Application
YRQ2PC-125series uninterupteddualpowerautomatic transferswitch isdesignedfor householdaplication.It is mainly used forsingle-phase household.Itcanrealize milisecondcontinuous power switching,and can beusedasautomatic switchingequipmentforconventionallinesandstandbycircuits torealizemillsecondswitchingof uninteruptible power supply.
TheYRQ2PC-125isdesignedforcitypowerandgeneratorwith lessthan 50ms transfertime.Eitheron-gridcitypoweror generatorcan be the main powerorbackup power.
「he workingvoltage of the ATS is 8 5 % Usto 1 1 0 % Us.So you must make sure the operation voltage will not lower than 180V, stherwise theATSwill bedamaged.
ProductPerformance
| MainParameters | |
| RatedWorking Current | 32 63100125A |
| Insulation Voltage | 690VAC |
| Frequency | 50/60Hz |
| RatedWorking Voltage | 110V/230VAC |
| Rated Short Circuit Current Iq | 50kA |
| Impact-resistantVoltage | 8kV |
| Conversion Time of Contactor | |
| Life | Electricallife:2000times |
| Manualoperation:50o0times | |
Dimensions
Wiring Instructions
YRQ2PC-125PVSERIES
DualPowerTransferSwitch (For PV Inverter and on-grid Power)
Application
YRQ2PV-125PVATSisdesignedforsolarinverterandon-gridcitypowerwithundervoltagedetectoroftheinverterACoutput voltage.Forthismodel,themainpowermustbesolarinverterandthebackuppower mustbeon-gridcitypower.The backup powershould always bepoweredon,otherwise theYRQ2PV-125PVATS can't work.Thetransfertimefrommain powerto backuppowerisabout40msandthetransfertimefrombackuppowertomainpowerwiltakeabout2seconds,that'sbecause theATS has todetecte if thevoltage of the inverteroutputisabove180V.
The working voltage of the ATS is 8 5 % Usto 1 1 0 % Us.So you must make sure the operation voltage will not lower than 180V, otherwise theATSwillbedamaged.
ProductPerformance
| MainParameters | |
| RatedWorking Current | 3263100125A |
| Insulation Voltage | 690VAC |
| Frequency | 50/60Hz |
| RatedWorking Voltage | 110V/230VAC |
| Rated Short Circuit Current Iq | 50kA |
| Impact-resistant Voltage | 8kV |
| Conversion Time of Contactor | |
| Life | Electricallife:2000times |
| Manual operation:50o0times | |
Dimensions
Wiring Instructions
YRQ4PC-250SERIES Automatic Transfer Switch
Application
YRQ4PC-250 seriesautomatic transfer switch,TSE-typePC-class;for powersupplysystemofAC 50Hz,ACrated voltage of 380V,rated currentof 3150A,three-phase four-wire.
Toachieveautomaticand manual switching between common and standby power supply,in the process of switching power supply,to cut off the power supply to the load.
Used for theoccasion with requirements of two-way powersupplyand high powerquality.There are16A\~200amp automatic transfer switch and 250A\~3150A switches produced.
YRQ4PC-250 seriesautomatic transfer switch complies with GB14048.3and GB14048.11,IEC 60947-3 and IEC 60947-6-1 standards.
Normalworkingconditions
The ambientair temperature is not higher than + 4 0 ^ { \circ } \mathsf C , not lower than - 5 ^ { \circ } C
\odot The altitude of the installation site shall not exceed 2 0 0 0 \mathsf { m }
Humidity:the maximum temperature of + 4 0 ^ { \circ } \mathsf C _ { \iota } therelative humidity of airdoes not exceed 5 0 % atalower temperature canallowa higher.
Relative humidity,for example 9 0 % at20 & It;O>C.Special precautions should be taken for condensation thatmay occuroccasionallyasa resultoftemperature changes.
The pollution level of the surrounding environment is Grade 3.
Transfer Switch should beinstalledin theabsence ofsignificantshaking,shockand norainand snowinvasion of the place,while theinstalationsiteshould beno explosion hazard medium,and the mediaisnot enough to corrode the metal and damage the insulation of gases and dust.
ProductPerformance
| Conventionel hestingcurrent(A) | 16,20,25,32 40,63,80,100 | 125 160 | 200 250 | 315,400 630 | 800 | 1000,1250 1600 | 2000,2500 3150 | ||
| Rated insulationvoltage (V) | 660 | 800 | |||||||
| Rated impulsewithstendvoltage(V) | 8 | 12 | |||||||
| Rated voltege (V) | Rated operating voltage:38ov;Control power supply voltage:220V | ||||||||
| Retedoperatingcurrent (A) | 16,20,25,32 40,63,80,100 | 125 200 160 250 | 315,400 630 | 800,1000 1250,1600 | 2000,2500 3150 | ||||
| Reted making end breoking capacity | 6Ie | ||||||||
| Rsted short-time withstand current (kA) | 5 | 10 | 12.6 | 26 | 32 | 55 | |||
| Conversion time I-II or II-I | ≤4s | ||||||||
| Rated control power(W) | Start | 300 | ≤3s | 325 | 355 | 400 | 400 | 600 | |
| Normal | 55 | 62 | 74 | 90 | 98 | 120 | |||
| Operating force(N) | 30~50 | 40 ~ 60 | 65 ~ 100 | 75~120 | 200~300 | 250~400 | |||
Controlcharacteristics
Theswitch has three-pole,four-pole (three-pole ^ + neutral pole can be on or off) product.
rtypes of control (common type,I,Il,Ill),commonly used is "common type".
Operationmodeof theautomaticconversionoperatingmechanismisselectedbythekeyswitch,and thepositioncanbe maintainedby the padlock.
Control characteristic ofcommon-type switch:
Switchisusedfortheautomaticchangeandautomaticrecoveryof main powersupply-standbypowersupplysystem.
ControlcharacteristicofI-typeswitch:
Switchisusedfortheautomaticchangeandnon-automaticrecovery,mutualstandbyofelectricsupply-electricsupplymainstandbypowersupplysystem.Themainpowertothestandbypower(Continuousadjustabledelay1\~999s),standbypowerto themainpower supply(Continuousadjustabledelay1\~999s).Thereisphase loss detectionandover-undervoltage protection function.
Control characteristic of Il-type switch:
Switchisusedfortheautomaticchangeandautomaticrecoveryof electricsuppy-electricsupplymain-standbypower supplysystem.Themain powertothestandbypower(Continuousadjustabledelay1\~999s),standbypower tothemain powersupply(Continuousadjustabledelay1\~99s).Thereisphase loss detectionandover-undervoltage protection function.
Controlcharacteristic of Ill-typeswitch:
Switchisusedfortheautomaticchangeandautomaticrecoveryofelectricsupply-oilmachine(haveautomaticstartingand receiving signal function,ordinary oil generatorsare not available) powersupply system.
Whenthecommonpowersupplyisapliedtotheoilmachinepowersuplysystem,theswitchwiltransmitsignalofstarting oil machineatfirst,theoilmachine startsafterchip warming up(Continuous adjustable delay 0\~999s) Oilmachinebacktoelectricsupply,theoilmachineisclosedaftercoolingmachines(Continuousadjustabledelay0\~999s). There is phase lossdetectionand over-undervoltage protection function.
AbovethreekindsswitchesofI,Il,Illhave:
⊚ Automatic,remotecontrol,manualcontrol ⊚ Delay 0.5s to detect signal,to prevent malfunction. ⊚ Theautomatic status has the remote control "O"position. ⊚ Keyswitch selects the operating mode.
Productstructure
100A/3ordinaryty;A/ndA/4fthe,Ity;othemmotyealty
Icommonly used power
Control voltage Il standby power supply
Model and its specificatp 101-106switch control terminal
Position indication 301-306 switch working status indication terminal
Electrical key lock 廿 401-406switch operatingstatus indication
Mechanical padlock terminal(reserved)-only for315Aandabove 501-506electricalkey lock,mechanical padlock statusindicationterminal-onlyfor315Aandabove
Switch main body Operating handle
a.Electrickeylock:internalcontrolinepowerofcontrolswitch,theelectricallockisinthe"automaticposition",theswitch achievesautomatic,remotecontroloperation,electricallockisinthe"manual"position,theswitchcanonlybemanually operated;
b.Operating handle:when using theoperating handletooperate theswitch,you must close theelectricallock;
c.Mechanicalpadlock:whenmaintenance,firstlyusetheoperatinghandletomakeswitchintheOposition,pullupthe padlock structureand padlock,thencan be checked:(puling themechanicalpadlockwillcutoffteinternalcontrol power of switch,the switch can not be electric,and can not be manual);
d.Position indication:Indicates the position of the switch operating status ( \ I ; 0 ; \ \mathbb { π } ) :
e.Control voltage:switch control voltagelevel220VAC;
f.Switchbody:thefrontpartis-wayoectto"ommopower";thelaterpartis-wayonnectto"standbyower."
Product structure
Wiringdiagramof16A\~100A 4-polecommontypemainswitch
WiringmethodofNo.2terminalaccordingtodifferentwaysisasfollows
(double powersupplyare cutoff)
Wiring Instructions
Outline and installation dimensions
| MainParameters | Installation dimensions | |||||||||||||
| Current | A | A1 | B | C | E | J | K | L | N | P | R | Y | (mm) Y1 | |
| 16A/3,4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 32A/3,4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 40A/3.4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 63A/3,4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 80A/3,4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 100A/3,4 | 305 | 245 | 106 | 170 | 133 | 234 | 84 | 7 | 75 | 30 | 14 | 6 | 36 | 86 |
| 125A/3 | 380 | 282 | 135 | 240 | 208 | 275 | 78/108 | 7 | 87 | 36 | 20 | 9 | 58 | 135 |
| 160A/3 | 380 | 282 | 135 | 240 | 208 | 275 | 78/108 | 7 | 87 | 36 | 20 | 9 | 58 | 135 |
| 125A/4 | 410 | 320 | 135 | 240 | 208 | 312 | 78/108 | 7 | 87 | 36 | 20 | 9 | 58 | 135 |
| 160A/4 | 410 | 320 | 135 | 240 | 208 | 312 | 78/108 | 7 | 87 | 36 | 20 | 9 | 58 | 135 |
| 200A/3 | 420 | 330 | 170 | 240 | 208 | 312 | 78/108 | 7 | 87 | 50 | 25 | 11 | 60 | 140 |
| 250A/3 | 420 | 330 | 170 | 240 | 208 | 312 | 78/108 | 7 | 87 | 50 | 25 | 11 | 60 | 140 |
| 200A/4 | 470 | 380 | 170 | 240 | 208 | 358 | 78/108 | 7 | 87 | 50 | 25 | 11 | 60 | 140 |
| 250A/4 | 470 | 380 | 170 | 240 | 208 | 358 | 78/108 | 7 | 87 | 50 | 25 | 11 | 60 | 140 |
| 315A/3 | 455 | 382 | 240 | 315 | 270 | 365 | 180 | 11 | 95 | 65 | 32 | 11 | 84 | 195 |
| 400A/3 | 455 | 382 | 240 | 315 | 270 | 365 | 180 | 11 | 95 | 65 | 40 | 13 | 84 | 195 |
| 630A/3 | 455 | 382 | 260 | 315 | 270 | 165 | 180 | 11 | 95 | 65 | 40 | 13 | 84 | 195 |
| 315A/4 | 515 | 450 | 240 | 315 | 270 | 430 | 180 | 11 | 95 | 65 | 32 | 11 | 84 | 195 |
| 400A/4 | 515 | 450 | 240 | 315 | 270 | 430 | 180 | 11 | 95 | 65 | 32 | 11 | 84 | 195 |
| 630A/4 | 515 | 450 | 260 | 315 | 270 | 430 | 180 | 11 | 95 | 65 | 40 | 13 | 84 | 195 |
| 800A/3 | 900 | 520 | 310 | 368 | 320 | 500 | 220 | 11 | 85 | 120 | 60 | 13 | 108 | 252 |
| 1000A/3 | 900 | 520 | 310 | 368 | 320 | 500 | 220 | 11 | 85 | 120 | 60 | 13 | 108 | 252 |
| 1250A/3 | 900 | 520 | 360 | 368 | 320 | 500 | 220 | 11 | 85 | 120 | 70 | 13 | 108 | 252 |
| 1600A/3 | 900 | 520 | 360 | 368 | 320 | 500 | 220 | 11 | 85 | 120 | 80 | 13 | 108 | 252 |
| 800A/4 | 1010 | 635 | 310 | 368 | 320 | 610 | 220 | 11 | 85 | 120 | 60 | 13 | 108 | 252 |
| 1000A/4 | 1010 | 635 | 310 | 368 | 320 | 610 | 220 | 11 | 85 | 120 | 60 | 13 | 108 | 252 |
| 1250A/4 | 1010 | 635 | 360 | 368 | 320 | 610 | 220 | 11 | 85 | 120 | 70 | 13 | 108 | 252 |
| 1600A/4 | 1010 | 635 | 360 | 368 | 320 | 310 | 220 | 11 | 85 | 120 | 80 | 13 | 108 | 252 |
YRQ5PC SERIES AutomaticTransferSwitch
Application
Thisseriesofdualpowerautomaticswitchisahigh-techproductdevelopedbyourcompanyusing thelatesttechnology.It complieswiththeGB14048.1andGB/T14048.11standards,andalsomets the"High-rsecivilbuildingfirecode","Codefor FireProtectionof Building Design”,"GuidetoDesignofEmergencyLighting","ElectricalDesignofCivil Buildings Specification"etc.
Thecomponentsoftheproductundergostrictagingscreening,andthefinishedproductispoweredonfor72hours.After passing the inspection,ltcan bepackaged.Thereby ensuring thereliabilityand safetyofthe product.
Thisproductismainlyusedfortheprimaryandsecondaryloadsspecifiedbythestate,andiswidelyusedinanimportantplace tosupplypowrotioslyuchsfireotectionotdteecomicatios,ommicationospitalsotesb railtransit,high-rise buildings,industrial assembly lines,television stations,etc.
Themainandbackuppowersourcescanbethepowergrid,theself-startinggeneratorset,thebaterygroupandsoon.
Normal workingconditions
Ambientair temperature:ambientair temperature . 5 ^ { \circ } \mathsf { C } to + 4 0 ^ { \circ } \mathsf { C } ,and the 24-hour average temperaturevalue does not exceed + 3 5 ^ { \circ } \mathsf { C } .withambientair temperaturesabove + 4 0 ^ { \circ } \mathsf { C } orbelow- . 5 ^ { \circ } \mathsf { C } ,Users should consult with the manufacturer.
Airhumidity:when the maximum temperature is + 4 0 ^ { \circ } \mathsf { C } ,therelative humidityisnot more than 5 0 % .Monthlymaximumrelative humidity 9 0 % .It cantolerate the influence of humid airatseaand allwatlowertemperatures.With higherrelative humidity, special measures should be taken for the occasional condensation produced by temperature changes.
Installationheight:theinstalationsiteisnotmorethan20o0metersabovesealevel.Forhigherheight,consideringthe decreaseindielectricstrengthandcooling effctofairathigheraltitudes.Usersshould consult with themanufacturer.
Pollution level: the environmental pollution level of the installation site is level 3.
Installation Category: Installation Category is IV.
\mathfrak { o } Mounting inclination:The productis fixedly installed in the cabinet with a maximum inclination of ± 2 2 . 5 ^ { \circ }
\odot Arcing distance:The arcing distance is 8 0 \mathsf {mm } when AC is 40oV.Thearcing distance can be ignored when using below 125A.
Use category:AC-33B
Productstructure
⊚ The product consists of two parts:switch body and intelligent ATS controller.
⊚ Theswitch body with an electrical and mechanical interlock.
⊚ The closing indication is used as an indicator of the isolation function.
\mathfrak { e } The productused solenoid actuate,double wire loop DC pulse operation, \diamond The operationpoweroftheconversion controllradopts thelinevoltage20Vofmainpowerand standbypowersupply.
No need to additional control power.
ProductPerformance
| Specification(A) | 16/20 25/32 | 32/40/50/63 80/100/125 | 160/180 200/250 | 250/315 350/400 | 500/630 | |
| Rated control powersupply voltage (V) | AC220 | AC220 | AC220 | AC220 | AC220 | |
| Rated control supplycurrent (A) | 3.5 | 3.5 | 7 | 7 | 7 | |
| Rated short-time withstand current (KA) | 10 | 10 | 10 | 10 | 10 | |
| Service life | Mechanical | 20000 | 20000 | 17000 | 17000 | 17000 |
| Electricat | 6000 | 6000 | 600 | 600 | 600 | |
| Operating cycle (1 minute /times) | 10 | 10 | 12 | 15 | 15 | |
Terminalwiringinstructions
a:Power gridsto Powergrids
b:Power gridstogenerator
① NA:Itisneutralterminal of normalpowerfor 3polesATS; ④ LP3:Standby Power indicatorlight;
② LP1:Normal Powersupplyindicator light; ⑤ LP4:StandbyPowersupplyindicator light;
③ LP2:Normal Power indicator light; ⑥ NB:Itisneutral terminal ofstandbypower for3polesATS;
Outline and installation dimensions
| Dimension | B | D | E | F | G | H | 」 | K | |||||||
| Type | 2P | 3P | 2P | 3P 4P | C | ||||||||||
| 32A | 216 | 243 | 270 | 196 | 223 | 250 | 184 | 167 | 12 | 27 | 3 | 110 | 9 | ||
| 125A | 237 | 274 | 311 | 217 | 254 | 291 184 | 167 | 20 | 37 | 3 | 110 | 8 | 9 | ||
| 250A | / | 322 | 372 | / | 302 | 352 290 | 200 | 20 | 49 | 5 | 146 | 8 | 10 | ||
| 400A | / | 352 | 402 | / | 332 | 382 | 294 | 200 | 30 | 59 | 6 | 146 | 10 | 10 | |
| 630A | / | 352 | 412 | / | 332 | 392 294 | 200 | 35 | 59 | 6 | 146 | 12 | 10 | ||
YMTS-63SERIES ManualTransferSwitch
Application
Thepurposeof the ManualTransfer Switch istomanually transferpowertoanalternatesource.Themostcommon application is transferring power froma backuppowersource to the load during utility failures.
Wheninstalledproperly,the ManualTransferSwitchprovidesaneasy meansfortransfering loadstoanalternatesource in the event of another power source failure.
Features
Manual Transfer Switch has a high voltage range of 1-600VAC.
⊚ Adequate durabilityhas beenensured bytestingagainst theIEC60947-3 standardin thespecificationof endurance requirements.
⊚ The manual transfer switch isoperated viaa handle fixed directly on the switch.
⊚ The16 to 63Ampere sizes can be snapped-on toa DINrail and the front fits in the 4 5mm consumer unit cut-out.
⊚ Clearly marked powerpostions with Indicatorlights toeasily understand which power sourceis being utilized.
⊚ Labelwindow for easy and clear labeling of power sources.
Model andmeaning
Technical Parameters
| Technical Data | |
| Rated Voltage | 230/400V~ |
| Rated Current | 63A |
| RatedFrequency | 50/60Hz |
| NumberofPoles | 1P,2P,3P,4P |
| Indicator | 1-0-2(1=MainPowerON,0=OFF,2=StandbyPowerON) |
| IndicatorWindow1=Red,0=Green,2=Yellow(Customizable) | |
| ElectricalFeatures | |
| ShortCircuitCurrent | 1200A |
| MechanicalLife | 10000 Cycles |
| IP Rating | IP20 |
| Operating Temperature | -5C~50℃ |
| CableSize | Max10mm² |
| Mounting | DIN 35mm Rail |
Circuit Diagram
Dimensions
YMTS-125SERIES Manual Transfer Switch
Application
Thepurposeof the ManualTransfer Switchistomanuallytransferpowertoanalternatesource.Themostcommon application is transferring power froma backup power source to the load during utility failures.
Wheninstalledproperlythe ManualTransferSwitchprovidesaneasymeansfortransfering loads toanalternatesource in the event ofanother powersource failure.
Features
Manual Transfer Switch has a high voltage range of 1-600VAC.
⊚ Adequate durabilityhas been ensured by testingagainstthe IEC60947-3 standard in thespecificationof endurance requirements.
⊚ The manual transfer switch is operated viaa handle fixed directly on the switch.
⊚ The 16 to 63Ampere sizes can be snapped-on toa DIN rail and the front fits in the 4 5mm consumer unit cut-out.
⊚ Clearly marked power postions with Indicatorlights toeasily understand which powersource is being utilized.
⊚ Label window for easy and clear labeling of powersources.
Model andmeaning
Technical Parameters
| Technical Data | |
| Rated Voltage | 230/400V~ |
| Rated Current | 125A |
| RatedFrequency | 50/60Hz |
| NumberofPoles | 1P,2P,3P,4P |
| Indicator | 1-0-2(1=Main PowerON,0=OFF,2=Standby PowrON) |
| IndicatorWindow1=Red,0=Green,2=Yellow(Customizable) | |
| ElectricalFeatures | |
| ShortCircuitCurrent | 3000A |
| MechanicalLife | 10000 Cycles |
| IP Rating | IP20 |
| Operating Temperature | -5C~50℃ |
| CableSize | Max50mm² |
| Mounting | DIN 35mm Rail |
Circuit Diagram
Dimensions
Unit: mm
YRMTS-63 SERIES
ManualTransferSwitch (lnter-lock Circuit Breaker)
Application
YRMTS-63 series manual transfer switch (solar transfer switch)isanew circuit breaker with interlocking mechanism developedbyourcompanythesolartransferswitchadds ininterlocking functionbasedonoriginalYRCB-63miniature circuitbreakers,thatis,theothersideofthecircuitbreakercanonlykeepopeningstatewhenthesideofthecircuitbreaker closing,toachievelineswitchingandotherprotection.Thesolartransferswitchdevelopedbyourcompanyhasthefunctions ofoverload,shortcircuit protectionandcircuit conversion.Thesolartransferswitch hasreasonableandreliabledesign, beautifulappearanceandlightweight.Itismainlyusedforswitchingandoverloadandshortcircuitprotectionofothercontrol circuit.
YRMTS-63 series manualtransfer switches comply with GB10963 and IEC60898 standards. Thereare6A/10A/16A/20A/25A/32A/40A/50/63A/80A/100A/125Aamptransferswitches
Technical Parameters
Rated short-circuit breaking capacity:40ooA;cosΦ0.45\~0.50.
lnstruction window. Mechanical Contact Indication Window,Definite disconnection instructions. The windowis green,the contacts are open;The windowis red,the contacts are closed.
OTripping characteristics. C-curve:protectconventionalloadsanddistributioncables,the magnetictripunitissettooperatewithin therangeof 8 . 5 1 { n } ± 2 0 % # D-curve:toprotectshock loadswith largestartingcurrent (suchastransformers,etc.),themagnetictripunitissetto operatein the rangeof 12 1 n ± 2 0 % V.
Humidity and heat resistance: Class 2(temperature 5 5 ^ { \circ } \mathsf { C } ,relative humidity 9 5 % 0
⊚ Wiring:Use terminal blocks with clips,and the cross-sectionalarea ofthe fixed cablecan be less than 5 0 \mathsf { m } \mathsf { m } ^ { 2 }
⊚ Mountingrail:TH35-7.5 standardsteel mounting.
| Technical Data | |
| Rated Current | 10A,16A,32A,40A,63A |
| Poles | 1P,1P+1P,2P,2P+2P,3P,3P+3P,4P,4P+4P |
| RatedVoltage Ue | AC230V/AC400V |
| Rated Insulation Voltage | 660V |
| Indication Window | GreenWindow(Disconnected),Red Window(Closed) |
| Rated BreakingCapacity | 4500A/6KA |
| Protection Class | IP20 |
| Thermo-Magnetic Release Characteristic | C-Curve (5-10ln), D-Curve (10-14IIn) |
| ElectricalLife | 4000 |
| Mechanical Life | 20000 |
| ReferenceTemperatureForSetting OfThermal Element | 30℃ |
| Ambient Temperature | -5~+40℃ |
| Terminal Connection Type | PhillipsScrews |
| AdapterCable | 80-125A8-35mm²16-2AWG |
| Tightening Torque | 3.0N.m |
| CombinationWithAccessoriesAuxillaryContact | |
| AuxillaryContact Yes | |
| Alarm Contact | |
| Shunt Release | Yes |
| UnderVoltage Release | Yes Yes |
Tripping CharacteristicCurve--CDType
Outline and installation dimensions
Unit: mm
| YRMTS-63 | |||||
| Poles | H1(mm) | H2(mm) | H3(mm) | W(mm) | L(mm) |
| 1P+1P | 45 | 72 | 35.5 | 36 | 80 |
| 2P+2P | 45 | 75 | 35.5 | 72 | 80 |
| 3P+3P | 45 | 75 | 35.5 | 108 | 80 |
| 4P+4P | 45 | 75 | 35.5 | 144 | 80 |
| YRMTS-63N | |||||
| Poles | H1(mm) | H2(mm) | H3(mm) | W(mm) | L(mm) |
| 1P+1P | 45 | 72 | 35.5 | 45 | 80 |
| 2P+2P | 45 | 75 | 35.5 | 81 | 80 |
| 3P+3P | 45 | 75 | 35.5 | 117 | 80 |
| 4P+4P | 45 | 75 | 35.5 | 153 | 80 |
YRMTS-125SERIES
ManualTransferSwitch (lnter-lock Circuit Breaker)
Application
YRMTS-125series manualtransferswitch(interlockingconversionserieshighbreaking miniaturecircuitbreaker).Itisanew typeproductwiththree functionofoverload,shortcircuit protectionand powerlineconversion.Itcanbeusedas handoperatedminiaturedual-powerswitch.Thecircuit breakerontheothersidecanonlybe keptoffwhenthesideof circuit breakerisclosed,toachieveprotection functionsofswitching betweennormalandstandbypowerline,feelcomfortable whenoperating,powerisup-inanddow-out,inlinewiththepowerlinecharacteristics.Thereare100amptransferswitch, 125ampandothers.
YRMTS-25seriesmanualtransferswitchesarecompact,haverationalandreliabledesign,beautifulappearance,light weight,fastoperation,easyinstallation,affordable! YRMTS-125 series manualtransferswitches complywith standards of GB10963and IEC60898.
Technical Parameters
| Technical Data | |
| RatedCurrent | 80A,100A,125A |
| Poles | 1P+1P,2P+2P,3P+3P,4P+4P |
| RatedVoltageUe | AC230V/AC400V |
| RatedInsulationVoltage | 660V |
| Indication Window | GreenWindow(Disconnected),Red Window(Closed) |
| Rated Breaking Capacity | 7.5kA/10kA |
| Protection Class | IP20 |
| Thermo-Magnetic Release Characteristic | C-Curve (5-10ln), D-Curve (10-14lIn) |
| Electrical Life | 4000 |
| Mechanical Life | 20000 |
| ReferenceTemperatureForSettingOfThermal Element | 30°℃ |
| Ambient Temperature | -5~+40℃ |
| Terminal Connection Type | PhillipsScrews |
| AdapterCable | 80-125A8-35mm²16-2AWG |
| Tightening Torque | 3.0N.m |
| CombinationWithAccessoriesAuxillaryContact | |
| AuxillaryContact | Yes |
| Alarm Contact | Yes |
| ShuntRelease | Yes |
| UnderVoltageRelease | Yes |
Outline and installation dimensions
| Poles | H1(mm) | H2(mm) | H3(mm) | W(mm) | L(mm) |
| 1P+1P | 45 | 76 | 35.5 | 63 | 80 |
| 2P+2P | 45 | 76 | 35.5 | 117 | 80 |
| 3P+3P | 45 | 76 | 35.5 | 171 | 80 |
| 4P+4P | 45 | 76 | 35.5 | 225 | 80 |