Fire Protection Solutions FPS-21
Fire Protection FPS-21
TOLCO™
fire protection
solutions Eaton Cooper Industries Middle East LLC
509 West Monroe Street PO Box 70160
Highland, IL 62249 Al Khobar - 31952
United States Kingdom of Saudi Arabia
Phone: (800) 851-7415 Phone: +966 506 395 973
Eaton.com/contactus Eaton.com
Eaton Eaton
5925 McLaughlin Road 13201 Dahlia Street
Mississauga, ON L5R 1B8 Fontana, CA
Canada United States
Phone: (800) 569-3660 Eaton.com/tolco
Eaton.com/contactca
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
B-Line Division
509 West Monroe Street
Highland, IL 62249
Phone: 800-851-7415
Fax: 618-654-1917
Eaton.com
© 2021 Eaton
All Rights Reserved Eaton is a registered trademark
Printed in USA
Publication No. CA312001EN All other trademarks are property
April 2021 web (FPS-21) of their respective owners.
U.S. Customer Service Center is staffed Monday through Friday
from 7 a.m. to 5:00 p.m. Central Standard Time.
For more information, visit Eaton.com.
Follow us on social media to get the
latest product and support information.
B-LINE
SERIES
We make what matters work.*
At Ea
of jus
dedic
mana
* aton, we believe that power is a
st about everything people do.
cated to helping our customers
age electrical, hydraulic and me
a fundamental part
That’s why we’re
find new ways to
echanical power
more efficiently, safely and sustaina
people’s lives, the communities wh
work, and the planet our future gen
upon. Because this what really matt
to make sure it works.
To learn more go to: Eaton.com/w
ably. To improve
ere we live and
erations depend
ters. And we’re here
whatmatters
We make what matters work.
Introduction
1 B-Line series Fire Protection Solutions Eaton
Manufacturers Standardization
Society of the Valve and Fitting
Industry, Inc.
For over 45 years, the TOLCO™ brand has been synonymous with innovative, labor saving pipe hanger and seismic
bracing solutions for the fire protection industry.
Products & Services
• TOLBrace™ Seismic Bracing Calculation Software
• One of the broadest lines of pipe hangers, strut and seismic bracing in the industry
Fire Protection Team
Our Fire Protection team actively participates in the fire protection industry, including:
• Membership in the NFPA Technical Committee on Hanging and Bracing of Water Based Automatic
Fire Sprinkler Systems
• MSS 403 Standards Committee for Pipe Hanging and Seismic Bracing
Product Certifications
Many of the products shown in this catalog are certified with the following:
• Listed by Underwriters Laboratories (UL) in U.S. and Canada
• Factory Mutual Engineering Approved (FM)
• Pre-approved by the State of California, Office of Statewide Health, Planning and Development
(OSHPD) as shown in our OPM-0052-13 Seismic Restraint Systems Guidelines
This catalog is intended to aid design engineers, specifying engineers, Authorities Having Jurisdiction (AHJs) and others
seeking solutions to their pipe support and seismic bracing system installations and design challenges.
For more information on B-Line series pipe hangers and supports, and TOLCO seismic bracing solutions utilized in
other applications, such as mechanical or plumbing systems, please refer to our Pipe Hangers & Supports and Strut
Systems catalogs, and the State of California OSHPD Pre-Approved Seismic Restraint Systems Guidelines OPM-0052-13.
These resources and other valuable information can be found online at www.eaton.com/tolco.
For additional support, contact your TOLCO seismic bracing specialist at, tolcosupport@eaton.com
ISO 9001:2008
B-Line Division
509 West Monroe Street
Highland, Illinois 62249-0326
Phone: 800-851-7415 www.eaton.com/pipehangers
NOTICE
Eaton reserves the right to change the specifications, materials, equipment, prices or the availability of
products at any time without prior notice. While every effort has been made to assure the accuracy of
information contained in this catalog at the time of publication, Eaton is not responsible for inaccuracies
resulting from undetected errors or omissions.
All hanger products in this catalog should be installed and serviced only as illustrated or described. Do not use them
for any purpose other than those described in this catalog. Products that are used for unintended purposes could fail,
resulting in severe personal injury or death.
Examples of misapplications which could cause severe personal injury or death include, but are not limited to:
• Using a beam clamp on a beam other than those described in the catalog;
• Using concrete inserts as anchors for pulling pipe up to the required elevation;
• Suspending clevis hangers, one under another, which could result in an accumulative load that is
greater than that which the pipe hanger will support.
Eaton B-Line series pipe hanger and support products are manufactured in accordance with industry standards. Our
customers should exercise care in using these products properly as to avoid potential damage or injury. Contact us if
you have any questions about proper installation and use of the products in this catalog.
WARNING
Table of Contents
Eaton B-Line series Fire Protection Solutions
Medium Duty ............................................................................ 86
Heavy Duty ................................................................................. 87
Brackets with U-Bolts ....................................................... 88
Upper Attachments
Ceiling Flange .......................................................................... 88
Angle Supports ............................................................ 88 - 91
Threaded Accessories
Eye Nuts ........................................................................................ 92
U-Bolts ................................................................................. 93 - 95
Rods, Bolts, Couplings,
Washers & Hardware ................................... 96 - 104
Reference Data
Anchor Load Chart Information ........................... 106
Threaded Rod Charts ..................................................... 107
Miscellaneous Charts
Piping, Tubing, etc. ............................................ 108 - 111
Beam Data Charts ............................................... 112 - 115
Trapeze Hanger Chart ...................................... 116 - 117
MSS & Federal Specification Charts .. 118 - 119
B-Line Compliances & Approvals .......... 120 - 121
Cross References
B-Line to TOLCO ................................................... 122 - 123
TOLCO to B-Line ................................................... 124 - 125
Metric Conversions ............................................ 126 - 127
Index .................................................................. 128
†
Mark shown in this document is the property of its respective owner.
Introduction ........................................................................................ 1
OSHPD Seismic Engineering ............................................... 3
TOLBrace Software Information ...................................... 4
Pictorial Index ........................................................................ 5 - 11
Beam Clamps
C-Clamps ........................................................................... 12 - 16
Retaining Straps ......................................................... 17 - 18
Bar Joist Hanger .................................................................... 19
Composite Wood Joist Clamp .................................. 20
Pipe Hangers
Clevis Hangers - NFPA ..................................................... 21
Clevis Bolt Spacer ...................................................................... 22
Band Hanger Surge Restrainer ...................................... 22
Band Hangers ................................................................ 23 - 24
Split Clamps .............................................................................. 25
‘U’ Hangers ...................................................................... 26 - 28
Pipe Clamps
Risers ............................................................................................... 29
Clamps .................................................................................................. 30
Straps .............................................................................................. 31
CPVC Hangers & Surge Restrainers
Single Fstener Strap .......................................................... 32
One-Hole Hangers ...................................................................... 33
Double Fstener Strap ................................................... 34 - 35
Speed Nuts ....................................................................................... 36
Restrainers ....................................................................... 37 - 39
Swivel Attachment ............................................................. 40
CPVC Sway Brace Attachment ................................ 41
Structural Attachment .......................................... 42 - 43
System Piping Attachment .............................. 44 - 45
Pipe Supports
Stands .................................................................................. 46 - 49
Supports .................................................................................. 50 - 51
Seismic Bracing
Sway Brace Main Pipe Attachments ....... 52 - 70
Seismic Attachments ........................................................ 71
Rod Stiffener ............................................................................. 72
Sway Bracing Pipe Clamps ............................... 73 - 78
Concrete Anchors
Seismic Wedge Anchors ................................................ 79
Concrete Deck Inserts ............................................ 80 - 81
Woodknockers™† .................................................................. 82
Bang-It™† ...................................................................................... 83
Concrete Screw Bolts & Anchors .......................... 84
Brackets
Light Duty .................................................................................... 85
2
OSHPD Seismic Engineering
3 B-Line series Fire Protection Solutions Eaton
Many TOLCO brand products are included in our OSHPD pre-approved seismic guidelines.
For specific information please visit www.eaton.com/fireprotection to view the OSHPD OPM-0052-13 catalog.
OSHPD Pre-Approved
Seismic Restraints
Systems Guidelines SEG-17
Seismic engineering
guidelines
OPM-0052-13
For mechanical, electrical, plumbing and
fire sprinkler systems
Seismic bracing in compliance with
requirements of
International Building Code (IBC) 2012
California Building Code (CBC) 2013
Fire Protection
Information
TOLBrace Software
Information
TOLBrace
4 Eaton B-Line series Fire Protection Solutions
TOLBrace Fire Protection
Software
Allows you to create a submittal sheet, with
all relevant information, at the click of a mouse!
TOLBrace™ includes a feature that will automatically update your
software when new products are added, when there are updates to
codes and standards, and/or any necessary software upgrades.
TOLBrace software assists a fire sprinkler system designer with the
following:
• Seismic force factor calculations (Fp)
• Zone of influence calculations
• Sway brace orientation and angle selection
• Structural attachment of sway braces
• Brace material selection
• Appropriate selection of UL Listed and FM Approved sway
brace components
• Creating a submittal sheet with all relevant information
TOLBrace follows the requirements of:
• NFPA 13, 2007, 2010, 2013, 2016, & 2019
• Uniform Building Code
• International Building Code
• National Building Code of Canada
• California Office of Statewide Health Planning & Development (OSHPD)
For more information, visit www.eaton.com/tolbrace.
Pictorial Index
5 B-Line series Fire Protection Solutions Eaton
Beam Clamps
Pipe Hangers
Fig. 130
Composite Wood
Joist Clamp
Page 20
B3042T
Bar Joist Hanger
Page 19
Fig. 69R
Retrofit Capable
Retaining Strap
Page 18
Fig. 69
Retaining Strap
Page 17
Fig. 67SS
(3
/4” Throat)
Fig. 68SS
(11
/4” Throat)
Reversible
Stainless Steel
C-Clamp
With Locknut
Page 16
Fig. 65XT-3
/8
Reversible
Steel C-Clamp
With Locknut
3
/4” Throat
Page 14
Fig. 65
Reversible
Steel C-Clamp
With Locknut
3
/4” Throat
Page 14
Fig. 66
Reversible
Steel C-Clamp
With Locknut
11
/4” Throat
Page 15
B3033
Wide Jaw Top
Flange C-Clamp
Page 12
B3034
Top Flange
C-Clamp
Page 13
B3037
Z-Purlin Beam Clamp
Page 12
u DURA-COPPER™ Finish
Fig. B3100
Clevis Hanger
Fig. 1NFPA
NFPA Clevis Hanger
Page 21
B3198H
Hinged Extension
Split Pipe Clamp
Page 25
u
Fig. 200 H
Heavy Duty
Trapeze
Band Hanger
Page 24
Fig. 200
Trimline Adjustable
Band Hanger
Fig. 200S
Trimline Adjustable
Band Hanger
with Removable Nut
Page 23
Fig. 200F
Felt Lined
Trimline
Adjustable
Band Hanger
Page 23
Fig. 200C
Plastic Coated
Trimline
Adjustable
Band Hanger
Page 23
Figure 120
‘U’ Hanger
Page 26
Fig. 120MJ
Mutt & Jeff
‘U’ Hanger
Page 27
Fig. 120RWA
Retrofit Wrap
Around “U”
Hanger Clamp
Page 28
Fig. 120W
Wrap Around
‘U’ Hanger
Page 27
Fig. 25
Surge Restrainer
for Fig. 200
Band Hanger
Page 22
Fig. 1CBS
Clevis Pipe
Spacer
Page 22
B3198HCT
Copper Tubing
Hinged Extension
Split Pipe Clamp
Page 25
Pictorial Index
Pictorial Index
6 Eaton B-Line series Fire Protection Solutions
Pipe Clamps
B3140
Standard Pipe Clamp
Page 30 B3140C & B3140F
Plastic Coated & Felt-Lined
Standard Pipe Clamp
Page 30
B3373C
Plastic Coated
Standard Riser Clamp
Page 29
B3373
Standard Riser Clamp
Page 29
Fig. 28M
Offset Hanger & Restrainer
for CPVC & IPS Pipe
Page 38
Fig. 29
Double Offset Hanger &
Restrainer for CPVC Pipe
Page 39
Fig. B3184
Light Duty Offset Hanger
for CPVC & IPS Pipe
Page 40
Fig. 22
Single Fastener
CPVC Strap
Page 32
Fig. 23
Double Fastener
CPVC Strap
Page 34
Fig. 22L2
One Hole Hanger/
Restrainer
for CPVC &
Steel Pipe
Page 33
Fig. 24
Double Fastener Side
Mounted CPVC Strap
Page 35
Fig. 27B
Speed Nut
Page 36
Fig. 28
Stand-Off Hanger & Restrainer
for CPVC & IPS Pipe
Page 37
B2400
Standard Pipe Strap
Page 31
CPVC Solutions
Pipe Supports
Figure 75
Swivel Attachment
Page 40
Fig. 76
Structural Attachment
For Restraint Assembly
Pages 42 & 43
Fig. 77
CPVC System
Piping Attachment
For Restraint
Assembly
See Pages
44 & 45
B3092
Adjustable Pipe Saddle
Support With Yoke
Page 50
B3093
Adjustable Pipe
Saddle Support
Page 51
B3088
Base Stand
B3088S
Seismic Base Stand
Pages 46 & 47
B3088T
Threaded Base Stand
B3088ST
Seismic Threaded
Base Stand
Pages 48 & 49
Pictorial Index
Fig. 3000
CPVC Sway Brace
Attachment
Page 41
Pictorial Index
7 B-Line series Fire Protection Solutions Eaton
Seismic Bracing
Fig. 4L
Sway Brace
Attachment
Pages 74 & 75
Fig. 800
Adjustable Sway
Brace Attachment
To Steel
Pages 58 & 59
Fig. 825
Sway Brace
Attachment
to Steel
Pages 54 & 55
Fig. 828
Universal Sway
Brace Attachment
to Steel
Pages 52 & 53
Fig. 825A
Sway Brace
Attachment to Steel
Page 56
Fig. 910
Threaded
Swivel Sway
Brace
Attachment
Page 63
Fig. 909
No-Thread
Swivel Sway
Brace
Attachment
Page 62
Fig. 907
Multi-Angle
Attachment
Page 64
Fig. 980
Universal Swivel
Sway Brace
Attachment
Pages 60 & 61
Fig. 975
Straight Sway
Brace Fitting
Page 65
Fig. 906
Sway Brace
Multi-Fastener
Adapter
Page 56
Fig. 1000
Fast Clamp Sway
Brace Attachment
Pages 68 & 69
Fig. 1001
Sway Brace
Attachment
Pages 66 & 67
Fig. 98
Rod Stiffener
Page 72
Fig. 98B
Rod Stiffener
with Break Off
Bolt Head
Page 72
SC228
Rod Stiffener
Page 72
Fig. 4B
Pipe Clamp For
Sway Bracing
Page 78
Fig. 77
CPVC System
Piping Attachment
For Restraint Assembly
See Pages
44 & 45
Fig. 2002
Sway Brace
Attachment
Page 70
Fig. 75
Swivel
Attachment
See Page 40
Fig. 76
Structural
Attachment
For Restraint
Assembly
See Pages 42 & 43
Fig. 3000
CPVC Sway Brace
Attachment
See Page 41
Pictorial Index
Pictorial Index
8 Eaton B-Line series Fire Protection Solutions
Concrete Anchors
Upper Attachments
B3061
Angle
Bracket
Page 90
Fig. 78
All Steel
Ceiling Plate
Page 89 Fig. 51NFPA
Side Beam
Bracket For
NFPA Rod
Page 89
Fig. 50
Side Beam
Bracket For
NFPA Rod &
Fastener Sizing
Page 90
Fig. 56
Tapped
Side Beam
Connector
Page 90
Fig. 58
Threaded Side
Beam Bracket
Page 91
B3066
Medium Duty
Welded Bracket
Page 86
B3065
Light Duty
Welded
Bracket
Page 85
AWSD Series
Seismic Wedge
Anchors
Page 79
ACPW Series
Wood Knocker™†II
Anchors
Page 82
B3069W
Welded
Knee Brace
Page 88
B3069E
“O” Bracket
Page 88
Brackets
† DDI™, Wood-Knocker™ & Bang-IT™ are registered trademarks used by DeWalt.
Fig. 109DD
DDI™† Concrete
Deck Insert
Pages 80 & 81
B3064
Adjustable
Strut
Bracket
Page 86
B3068
Light Duty
Welded
Bracket
Page 85
B3067
Heavy Duty
Welded
Bracket
Page 87
ACB Series
Concrete Screw Bolts
Page 84
ATM Series
Self-Tapping Machine
Screw Anchors
Page 84
ACPD Series
Bang-It™†+ Anchors
Page 83
Pictorial Index
Pictorial Index
9 B-Line series Fire Protection Solutions Eaton
Threaded Accessories
B3234
Bevel Washer
Page 102
B3248
Steel Washer Plate
Page 102
B200
Square Washer
Page 102
HN
Hex Nut
HHN
Heavy Hex Nut
Page 103
FW
Flat Washer
Page 104
FFW
Flat Fender Washer
Page 104
LW
Lock Washer
Page 104
DS 16 x 2
#16 x 2” Drive Screw
Page 98 B3220
Malleable Iron
Rod Coupling
Page 99
B3214
Tie Bolt
Page 97
B655
Steel Rod Coupling
Page 99
B656
Steel Reducer
Rod Coupling
Page 99
B501
Light Weight U-Bolt
Page 93
B3188
Standard U-Bolt
Pages 94 & 95
B3188C
Plastic Coated
Standard U-Bolt
Pages 94 & 95
B3200
Weldless Eye Nut
Page 92
ATR
All Threaded Rod
Page 96
B3205
Machine
Threaded Rod
Page 96
B3213
Coach Screw Rod
Page 97
B3212
J-Bolt
Page 98
B3228
Hex Head Lag Bolt
Page 98
B3210
B3210L
Eye Rod
Page 100
B3211
B3211L
Welded Eye Rod
Page 100
B3210X
B3210XL
Linked Eye Rod
Page 101
B3211X
B3211XL
Linked Welded
Eye Rod
Page 101
Pictorial Index
Pictorial Index
10 Eaton B-Line series Fire Protection Solutions
Other Products www.eaton.com/pipehangers
B3148
Offset
Pipe Clamp
B3180FL
Flush Mount
Pipe Strap
B3180
Extended Leg
Pipe Strap
B3089
Pipe Support
Adjuster
B3090
Pipe Saddle
Support
With U-Bolt
B3096
Adjustable Pipe
Saddle Support
B3170CTC
Copper Tubing
Plastic Coated
Adjustable
Swivel Ring
B3170CT
Copper Tubing
Adjustable
Swivel Ring
B3198R
Extension Split
Pipe Clamp
B3198RCT
Copper Tubing
Extension Split
Pipe Clamp
B3097
Pipe Saddle
With Strap B3095
Pipe Saddle
Support
B3098
Adjustable
Pipe Support
w/U-Bolt
ATB
(TOLCO 123)
Toggle Bolt
B3082
Rod Beam
Attachment
B3223
Offset Eye
Socket
B3203
Extension Piece
B3045
Side
Beam Clamp
B3040
Adjustable
Beam Clamp
B3055
Steel
Beam Clamp
Pictorial Index
B3690
Adjustable
‘J’ Hanger
B335
Three Hole
Adjustable Hinge
B650
Seismic Retrofit
Bracket B3202
Turnbuckle
Pictorial Index
11 B-Line series Fire Protection Solutions Eaton
Pictorial Index
Other Products www.eaton.com/pipehangers
DBP
Base
DB Series
Base & Short Channel
KwikWire Clamp Wire Rope
B2500
Light Duty
Spot Insert
N2500
Steel Insert Nut B3014
Malleable Iron
Spot Insert
B3014N
Malleable Iron
Insert Nut
CHSCS Type
Spring Hanger
w/Seismic
Cushion Stop
1” & 2” Deflection
RH & RHD Type
Neoprene Hanger
1
/4” & 1
/2” Deflection
HH30SCS Type
Deflection
Combination Hanger
15° Tilt Spring &
Neoprene w/
Seismic Cushion Stop
11
/2” & 21
/2”
Deflection
Neoprene Mounts
Seismic Restraints
Isolator/Restraints
BPS Series
Snap N’Shield
For Strut Channel
BPCH Series
Snap N’Shield
For Clevis & Band
Hangers
Vibration Pads
Beam Clamps
Beam Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
12 Eaton B-Line series Fire Protection Solutions
Material: Malleable Iron
Function: Designed for attaching a 3
/8\"-16 hanger rod to the
bottom flange of a Z-purlin.
Approvals: Underwriters Laboratories Listed (cULus) for up to
4\" (100mm) pipe. Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 23 and Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 23.
Finish: Plain or Electro-Galvanized
Order By: Figure number and finish.
Weight: Approx. Wt./100 90 Lbs. (40.8kg)
Design Load: 400 Lbs. (1.78kN)
B3037 - Z-Purlin Malleable C-Clamp
Setscrew Torque: Per MSS SP-58 14.2.5 3
/8\" -16 set screws = 5 ft./lbs. (7 Nm)
Caution should be taken not to over-tighten set screws.
Set Screw and
Locknut Included
3\"
(76.2)
313/32\"
(86.5)
Throat Opening 31/32\" (24.6)
Bottom Hanger Rod
Threads
3
/8\"-16
Size Range: 3
/8\"-16 thru 3
/4\"-10 rod
Material: Cast Malleable Steel with hardened cup point set screw
and jam nut
Function: For attachment to structural shapes requiring wider throat
especially under roof with bar joist construction.
This clamp may be used with the set screw in the up or down position.
Approvals: Underwriters Laboratories Listed (cULus) and Factory
Mutual Engineering Approved (FM) for 3
/8\"-16 and 1
/2\"-13 rod sizes.
Conforms to Federal Specification WW-H-171E Type 19 & A-A-1192A,
Type 19 & 23 and Manufacturers Standardization Society ANSI/MSS
SP-69 & SP-58, Type 19 & 23. Factory Mutual Engineering Approved
only with the setscrew in the down position.
Finish: Plain. Contact customer service for alternative finishes and
materials.
Order By: Figure number, rod size and finish
Setscrew Torque: Per MSS SP-58 14.2.5 3
/8\" -16 set screws = 5 ft./lbs. (7 Nm) 1
/2\" -13 set screws = 11 ft./lbs. (15 Nm) 5
/8\" -11 set screws = 21 ft./lbs. (28 Nm)
Caution should be taken not to over-tighten set screws.
Designed to meet or exceed requirements of FM DS 2-0.
Set Screw and
Locknut Included
A
(Rod Size)
Hanger Rod
Not Included
B
D C
Throat Opening
11
/4” (31.7) for B3033-3
/8 & 1
/2
15
/16” (33.3) for B3033-5
/8 & 3
/4
B3033 - Wide Jaw Reversible C-Clamp
Part Rod Set Screw Maximum Iron Approx.
No. Size Size B C D Pipe Size Per UL Wt./100
A in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3033-3
/8 3
/8\"-16 3
/9\"-16 x 2\" 21
/4\" (57.1) 2\" (50.8) 11
/8\" (28.6) 4\" (100) 54 (24.5)
B3033-1
/2 1
/2\"-13 1
/2\"-13 x 21
/2\" 25
/16\" (58.7) 23
/16\" (55.6) 11
/4\" (31.7) 8\" (200) 51 (23.1)
B3033-5
/8 5
/8\"-11 1
/2\"-13 x 21
/2\" 25
/8\" (66.7) 21
/2\" (63.5) 13
/8\" (34.9) 8\" (200) 70 (31.7)
B3033-3
/4 3
/4\"-10 5
/8\"-11 x 21
/2\" 211/16\" (68.3) 21
/2\" (63.5) 17
/16\" (36.5) 10\" (250) 98 (44.4)
Bottom Flange Attachment
Applications
Top Flange Attachment
Applications
Beam Clamps
Beam Clamps
13 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3034 - C-Clamp
Size Range: 3
/8\"-16 thru 3
/4\"-10 rod
Material: Cast Malleable Steel with hardened cup point set
screw and jam nut
Function: Recommended for hanging from steel beam
where flange thickness does not exceed 3
/4\" (19.0mm).
Features: May be used on top or bottom flange of the beam.
Beveled lip allows hanging from top flange where clearance is
limited. May be installed with the set screw in the up or down
position. Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp. The
rear window design permits inspection of thread engagement.
Approvals: Underwriters Laboratories Listed (cULus) and
Factory Mutual Engineering Approved (FM) for 3
/8\"-16 and 1
/2\"-
13 rod sizes. Conforms to Federal Specification WW-H-171E
& A-A-1192A, Type 23 and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 19. 3
/8\"-16 is
(cULus) Listed to support up to 4\" (100mm) pipe with the
set screw in the down position, up to 3\" (75mm) pipe with
the set screw in the up position. 1
/2\"-13 is (cULus) Listed
to support up to 8\" (200mm) pipe with the set screw in the
down position, up to 6\" (150mm) pipe with the set screw in
the up position. Factory Mutual Engineering Approved only
with the setscrew in the down position.
Finish: Plain. Contact customer service for alternative
finishes and materials.
Order By: Figure number, rod size and finish
Setscrew Torque: Per MSS SP-58 14.2.5 3
/8\" -16 set screws = 5 ft./lbs. (7 Nm) 1
/2\" -13 set screws = 11 ft./lbs. (15 Nm)
Caution should be taken not to over-tighten set screws.
Set Screw and
Locknut Included
A
(Rod Size)
Hanger Rod
Not Included
B
D
C
Throat
Opening
3
/4\" (19.0)
B3034-5
/8\" and B3034-3
/4\" sizes
Attach only as shown.
Top Flange
Attachment
Applications
Bottom Flange
Attachment
Applications
Set Screw and
Locknut Included
A
(Rod Size)
Hanger Rod
Not Included
B
D
C
Throat
Opening
3
/4\" (19.0)
Part Rod Set Screw Maximum Iron Approx.
No. Size Size B C D Pipe Size Per UL Wt./100
A in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3034-3
/8 3
/8\"-16 3
/8\"-16 x 11
/2\" 15
/8\" (41.3) 2\" (50.8) 7
/8\" (19.0) 4\" (100) 30 (13.6)
B3034-1
/2 1
/2\"-13 1
/2\"-13 x 11
/2\" 113/16\" (46.0) 23
/16\" (55.6) 13
/16\" (30.2) 8\" (200) 47 (21.3)
B3034-5
/8 5
/8\"-11 1
/2\"-13 x 2\" 13
/4\" (44.5) 21
/8\" (54.0) 11
/4\" (31.7) — — 58 (26.3)
B3034-3
/4 3
/4\"-10 1
/2\"-13 x 2\" 2\" (50.8) 21
/4\" (57.2) 11
/4\" (31.7) — — 77 (35.0)
B3034-3
/8\"
shown.
Beam Clamps
Beam Clamps
Eaton 14 B-Line series Fire Protection Solutions
Size Range:
Fig. 65 - 1
/2\"-13 rod sizes, and 5
/8\"-11 rod sizes
Fig. 65XT - 3
/8\"-16 rod size (see below)
Material: Steel with hardened cup point set screw and jam nut
Function: Recommended for hanging from steel beam where flange thickness does
not exceed 3
/4\" (19.0mm).
Features: All steel construction eliminates structural deficiencies associated with
casting type beam clamps. May be used on top or bottom flange of beam. (Beveled
lip allows hanging from top flange where clearance is limited.) May be installed with
set screw in up or down position. Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp. Open design permits
inspection of thread engagement.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Exceeds requirements of the National Fire Protection Association (NFPA), pamphlet 13, 3
/8\"-16 rod will support 1
/2\" (15mm) thru 4\" (100mm) pipe 1
/2\"-13 rod will support thru 8\" (200mm) pipe
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes
and materials.
Order By: Figure number and finish
Fig. 65 Patent #4,570,885
Part Rod Size B C D E
No. A in. (mm) in. (mm) in. (mm) in. (mm)
65-1
/2 1
/2\"-13 11
/2\" (38.1) 3
/4\" (19.0) 1\" (25.4) 9
/16\" (14.3)
65-5
/8 5
/8\"-11 11
/2\" (38.1) 3
/4\" (19.0) 1\" (25.4) 9
/16\" (14.3)
Part F Approx. Wt./100
No. in. (mm) Lbs. (kg)
65-1
/2 11
/4\" (31.7) 55 (24.9)
65-5
/8 11
/4\" (31.7) 55 (24.9)
Part For Approx. Wt/100
No. Rod Size Lbs. (kg)
65XT 3
/8\"-16 28.0 (12.7)
TOLCO Fig. 65 - Reversible Steel C-Type Beam Clamp 3
/4\" (19.0mm) Throat Opening
TOLCO Fig. 65XT - Reversible Steel C-Type Beam Clamp 3
/4\" (19.0mm) Throat Opening
B
F
E
A
C
D
Feature: Extruded holes allows for more thread
engagement of threaded rod and set screw.
Finish: Plain or Electro-Galvanized
Order By: Figure number and finish
Approvals: Underwriters Laboratories Listed
(cULus) and FM Approved (FM) for up to 4\"
(100mm) pipe.
Designed to meet or exceed requirements of
FM DS 2-0 and NFPA 13.
3
/4\"
(19.0)
19
/16\"
(39.7)
1\"
(25.4)
7
/8\"
(22.2) 13
/8\"
(34.9)
Set Screw and
Locknut Included
Set Screw and
Locknut Included
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Beam Clamps
Beam Clamps
15 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16, 1
/2\"-13 rod sizes, and 5
/8\"-11 rod sizes
Material: Steel with hardened cup point set screw and jam nut
Function: Recommended for hanging from steel beam where flange
thickness does not exceed 11
/4\" (31.7mm).
Features: All steel construction eliminates structural deficiencies associated with
casting type beam clamps. May be used on top or bottom flange of beam. (Beveled
lip allows hanging from top flange where clearance is limited.) May be installed with
set screw in up or down position. Offset design permits unlimited rod adjustment by
allowing the rod to be threaded completely through the clamp. Open design permits
inspection of thread engagement.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
Exceeds requirements of the National Fire Protection Association (NFPA), pamphlet 13, 3
/8\"-16 rod will support 1
/2\" (15mm) thru 4\" (100mm) pipe 1
/2\"-13 rod will support thru 8\" (200mm) pipe
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes
and materials.
Order By: Figure number and finish
TOLCO Fig. 66 - Reversible Steel C-Type Beam Clamp 11
/4\" (31.7mm) Throat Opening
B
E
A
C
D
F
Set Screw and
Locknut Included
Part Rod Size B C D E
No. A in. (mm) in. (mm) in. (mm) in. (mm)
66-3
/8 3
/8\"-16 13
/16\" (30.2) 11
/4\" (31.7) 1\" (25.4) 7
/16\" (11.1)
66-1
/2 1
/2\"-13 11
/2\" (38.1) 11
/4\" (31.7) 1\" (25.4) 9
/16\" (14.3)
66-5
/8 5
/8\"-11 11
/2\" (38.1) 11
/4\" (31.7) 1\" (25.4) 9
/16\" (14.3)
Part F Approx. Wt./100
No. in. (mm) Lbs. (kg)
66-3
/8 1\" (25.4) 28 (12.7)
66-1
/2 11
/4\" (31.7) 55 (24.9)
66-5
/8 11
/4\" (31.7) 55 (24.9)
Beam Clamps
Beam Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
16 Eaton B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 and 1
/2\"-13 rod sizes
Material: Stainless Steel (Type 316 or 304)
Function: Recommended for hanging from steel beams where flange thickness does
not exceed 3
/4\" (19.0mm) for Fig. 67SS or 11
/4\" (31.7mm) for Fig. 68SS.
Features: All steel construction eliminates structural deficiencies associated with
casting type beam clamps. May be used on top or bottom flange of beam. May be
installed with set screw in up or down position. Offset design permits unlimited rod
adjustment by allowing the rod to be threaded completely through the clamp.
Approvals: Conforms to Manufacturers Standardization Society ANSI/MSS SP-69 &
SP-58, Type 19.
3
/8\"-16 rod will support 1
/2\" (15mm) thru 4\" (100mm) pipe at maximum NFPA 13 spacing 1
/2\"-13 rod will support thru 8\" (200mm) pipe at maximum NFPA 13 spacing
Order By: Figure number and stainless steel type.
Part Rod Size Pipe Size B C D E
No. A in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
67SS-3
/8 3
/8\"-16 1
/2\" - 4\" (15 - 100) 3\" (76,2) 7
/8\" (22.2) 1\" (25.4) 15
/8\" (41.3)
67SS-1
/2 1
/2\"-13 5\" - 8\" (125 -200) 3\" (76,2) 7
/8\" (22.2) 1\" (25.4) 15
/8\" (41.3)
Part F G Approx. Wt./100
No. in. (mm) in. (mm) Lbs. (kg)
67SS-3
/8 15
/8\" (41.3) 11
/8\" (28.6) 84 (38.1)
67SS-1
/2 15
/8\" (41.3) 11
/8\" (28.6) 170 (77.1)
Part Rod Size Pipe Size B C D E
No. A in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
68SS-3
/8 3
/8\"-16 1
/2\" - 4\" (15 - 100) 21
/16\" (52.4) 11
/8\" (28.6) 3
/4\" (19.0) 11
/4\" (31.7)
68SS-1
/2 1
/2\"-13 5\" - 8\" (125 -200) 21
/4\" (57.1) 11
/4\" (31.7) 13/16\" (20.6) 11
/4\" (31.7)
Part F Approx. Wt./100
No. in. (mm) Lbs. (kg)
68SS-3
/8 2\" (50.8) 84 (38.1)
68SS-1
/2 21
/4\" (57.1) 170 (77.1)
TOLCO Fig. 67SS - Stainless Steel Reversible C-Type Beam Clamp 3
/4\" (19.0mm) Throat Opening
TOLCO Fig. 68SS - Stainless Steel Reversible C-Type Beam Clamp Wide Mouth
Fig. 67SS
Fig. 68SS
B
G
E
A
C
D
F
Set Screw and
Locknut Included
Beam Clamps
Beam Clamps
17 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 thru 3
/4\"-10 rod
4\" (101.6mm) thru 16\" (406.4mm) lengths
Note: longer lengths are available consult factory
Material: Pre-Galvanized Steel
Function: To offer more secure fastening of various types
of beam clamps to beam where danger of movement might
be expected. NFPA 13 requires the use of retaining straps
with all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13.
Important Note: Good installation practice of a retaining
strap requires that the strap be held tightly and securely to
all component parts of the assembly. Therefore a locking
mechanism of some kind, such as a hex nut for the Fig. 69 or
the beveled locking slot of the Fig. 69R will provide a more
secure reliable installation.
Approvals: Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Approved for use with any listed B-Line
series or Tolco beam clamp.
Finish: Pre-Galvanized
Order By: Figure number, length (L), and finish.
Note: Minimum return on strap is 1\" (25.4mm).
Lengths over 16\" (406mm) are not UL Listed.
TOLCO Fig. 69 - Beam Clamp Retaining Strap
Fig. 69-5
/8-3
/4
Detail A
Fig. 69-3
/8-1
/2
D
7
/16\"
(11.1)
9
/16\"
(14.3)
Hole Dia. D For Use With Length
Part No. in. (mm)
B3033-3
/8, B3034-3
/8, B3031-3
/8, Specify
69-3
/8-1
/2-L see Detail A 65-3
/8, 65XT-3
/8, 66-3
/8
B3033-1
/2, B3034-1
/2, 65-1
/2, 66-1
/2
69-5
/8-L 11/16\" (17.5) B3033-5
/8, 65-5
/8, 66-5
/8 Specify
69-3
/4-L 13/16\" (20.6) B3033-3
/4 Specify
Beam Clamps
Beam Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
18 Eaton B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 & 1
/2\"-13 rod
4\" (101,6mm) thru 16\" (406.4mm) lengths
Note: longer lengths are available consult factory
Material: Pre-Galvanized Steel
Function: To offer more secure fastening of various types
of beam clamps to beam where danger of movement might
be expected. NFPA 13 requires the use of retaining straps
with all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13.
Features: Beveled locking slot* is precisely formed to align
with the threaded section of a hanger rod or set screw and
engage the unit securely. May be used as shown in Section
“A-A” or inverted. Allows easy installation for new construction
or retrofit applications.
Important Note: Good installation practice of a retaining
strap requires that the strap be held tightly and securely to
all component parts of the assembly. Therefore the beveled
locking slot of the Fig. 69R will provide a secure reliable
installation.
Approvals: Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Approved for use with any listed B-Line
series or Tolco beam clamp.
Finish: Pre-Galvanized
Order By: Figure number, length, and finish.
Note: Minimum return on strap is 1\" (25.4mm)
* Patent #5,947,424
TOLCO Fig. 69R - Retrofit Capable Beam Clamp Retaining Strap
A
A
A - A
Slot Width For Use With Length
Part No. in. (mm)
69R-3
/8-L 7
/16\" (11.1) B3033-3
/8, B3034-3
/8, Specify 65-3
/8, 65XT-3
/8, 66-3
/8
69R-1
/2-L 9
/16\" (14.3) B3033-1
/2, B3034-1
/2, 65-1
/2, 66-1
/2 Specify
Beam Clamps
Beam Clamps
19 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 and 1
/2\"-13 rod
Material: Steel
Function: Designed to hook on top chord of metal bar joist.
Hanger rod is threaded into product and secured with a
washer and nut.
Finish: Plain. Contact customer service for alternative finishes
and materials.
Order By: Figure number, rod size, width and thickness of bar
joist, and finish.
B3042T - Bar Joist Hanger
Rod Size For Pipe Size Approx. Wt./100
Part No. Size in. (mm) Lbs. (kg)
B3042T-3
/8 3
/8\"-16 Up to 4\" (up to 100) 50.6 (22.9)
B3042T-1
/2 1
/2\"-13 6\" (150) 50.0 (22.7)
Beam Clamps
Beam Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
20 Eaton B-Line series Fire Protection Solutions
Size Range: 130-1 = TJI 35 or equivalent
130-2 = ––
130-3 = TJI 25 or equivalent
130-4 = TJI 55, TJI 65, & TJI 560D or equivalent
130-5 = TJI 75 & TJI H90 or equivalent
130-6 = TJI 96 or equivalent
Material: Steel
Function: Designed for attachment to composite wood joist
beams. Use with eye rods, eye sockets, or angle bracket.
Approvals: Sizes 1 - 6 are Underwriters Laboratories Listed in
the USA (UL) and Canada (cUL) list through 4\" (100mm) pipe.
All Fig. 130 Beam Clamps meet requirements of
Factory Mutual Engineering (FM) and NFPA 13, through
4\" (100mm) pipe.
Finish: Electro-Galvanized or Hot-Dip Galvanized
Order By: Figure number and finish.
Designed to meet or exceed requirements of FM DS 2-0.
TOLCO Fig. 130 - Composite Wood Joist Clamp
Hardware
Included
3
/4\"
(19.0) 3
/8\"
(9.5)
1
/8\"
(3.2)
2\"
(50.8)
1\"
(25.4)
W
H A
Material Thickness
11 Gauge (3.0)
Part Hardware A H W Approx. Wt./100
No. Size in. (mm) in. (mm) in. (mm) Lbs. (kg)
130-1 3
/8\"-16 31
/4\" (82.5) 11
/2\" (38.1) 25
/16\" (58.7) 65 (29.5)
130-2 3
/8\"-16 31
/2\" (88.9) 13
/4\" (44.4) 21
/2\" (63.5) 70 (31.7)
130-3 3
/8\"-16 31
/4\" (82.5) 11
/2\" (38.1) 13
/4\" (44.4) 58 (26.3)
130-4 3
/8\"-16 31
/2\" (88.9) 11
/2\" (38.1) 31
/2\" (88.9) 83 (37.6)
130-5† 1
/2\"-13 35
/8\" (92.1) 13
/4\" (44.4) 31
/2\" (88.9) 86 (39.0)
130-6† 1
/2\"-13 41
/2\" (114.3) 21
/2\" (63.5) 37
/8\" (98.4) 101 (45.8)
‘H’ and ‘W’ are beam dimensions.
† Larger bolts and I-rods are required for 5\" (125mm) and 6\" (150mm) pipe sizes
Pipe Hangers
21 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3100 - Clevis Hanger for NFPA Sizes 3
/4\" (20mm) thru 2\" (50mm)
TOLCO Fig. 1NFPA - Clevis Hanger for NFPA Sizes 21
/2\" (65mm) thru 12\" (300mm)
B
Overall Height.
C
Bottom of hanger rod nut
to center of pipe.
D
Bottom of hanger rod nut
to top clevis bolt.
Size Range: 3
/4\" (20mm) to 12\" (300mm)
Material: Steel
Function: Recommended for the suspension of non-insulated pipe or insulated pipe with a B3151 shield.
Note: When an oversized clevis is used, a pipe spacer should be placed over the cross bolt to assure that
the lower U-strap will not move in on the bolt. When attaching seismic bracing to the clevis hangers, a 1CBS
(clevis bolt spacer) must be installed.
Order pipe sleeves Fig. 1CBS-(pipe size) separately.
Approvals: Underwriter’s Laboratories Listed in the USA (UL) and Canada (cUL) for sizes 3
/4\" (20) thru 12\"
(300). Factory Mutual Engineering Approved (FM) for 3
/4\" (20mm) thru 8\" (200mm) pipe. Conforms to Federal
Specification WW-H-171E & A-A-1192A, Type 1 and Manufacturers Standardization Society ANSI/MSS SP-69 &
SP-58, Type 1. Rod sizes per National Fire Protection Association (NFPA) Pamphlet 13.
Maximum Temperature: 650°F (343°C).
Standard Finish: Plain, Electro-Galvanized, DURA-GREEN™, or Hot-Dip Galvanized also available in
Stainless Steel
Order By: Figure number and finish
For pipe sizes under 21
/2\" (65mm) order B3100 Clevis Hanger, see chart below.
Designed to meet or exceed requirements of FM DS 2-0.
Nominal Pipe Size Rod Size B C D Approx. Wt./100
Part No. in. (mm) A in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3100-3
/4 3
/4\" (20) 3
/8\"-16 25
/8\" (66.7) 19
/16\" (39.7) 9
/16\" (14.3) 29 (13.1)
B3100-1 1\" (25) 3
/8\"-16 211/16\" (68.3) 19
/16\" (39.7) 11/16\" (17.5) 35 (15.9)
B3100-11
/4 11
/4\" 32) 3
/8\"-16 33
/16\" (81.0) 17
/8\" (47.6) 15/16\" (29.8) 40 (18.1)
B3100-11
/2 11
/2\" (40) 3
/8\"-16 33
/8\" (85.7) 115/16\" (49.2) 11
/4\" (31.7) 42 (19.0)
B3100-2 2\" (50) 3
/8\"-16 49
/16\" (115.9) 27
/8\" (73.0) 11
/8\" (28.6) 52 (23.6)
1NFPA-21
/2 21
/2\" (65) 3
/8\"-16 55
/16\" (134.9) 31
/4\" (82.5) 1\" (25.4) 124 (56.2)
1NFPA-3 3\" (80) 3
/8\"-16 515/16\" (150.8) 31
/2\" (88.9) 11
/4\" (31.7) 140 (63.5)
1NFPA-31
/2 31
/2\" (90) 3
/8\"-16 67
/16\" (163.5) 33
/4\" (95.2) 11
/4\" (31.7) 152 (68.9)
1NFPA-4 4\" (100) 3
/8\"-16 73
/8\" (187.3) 41
/4\" (107.9) 11
/2\" (38.1) 190 (86.2)
1NFPA-5 5\" (125) 1
/2\"-13 815/16\" (226.9) 51
/4\" (133.3) 11
/2\" (38.1) 235 (106.6)
1NFPA-6 6\" (150) 1
/2\"-13 913/16\" (249.2) 51
/2\" (139.7) 11
/2\" (38.1) 317 (143.8)
1NFPA-8 8\" (200) 1
/2\"-13 129
/16\" (319.1) 71
/8\" (181.0) 2\" (50.8) 428 (194.1)
1NFPA-10 10\" (250) 5
/8\"-11 161
/4\" (412.7) 95
/8\" (244.5) 31
/4\" (82.5) 918 (416.4)
1NFPA-12 12\" (300) 5
/8\"-11 189
/16\" (471.5) 1013/16\" (268.3) 31
/8\" (79.4) 1086 (492.6)
B
D
C
A
(Rod Size)
Hanger Rod Not
Included
Pipe Hangers
Pipe Hangers
Pipe Hangers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
22 Eaton B-Line series Fire Protection Solutions
Size Range: Size 1\" (25mm) thru 20\" (500mm) clevis hanger
Material: Steel
Function: Used as a spacer at a seismic brace location to
keep clevis hanger from collapsing during seismic event.
Approvals: Included in our Seismic Engineering Guidelines
approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing
and placement information relating to OSHPD projects, please refer
to our Seismic Engineering Guidelines OPM-0052-13, for 21
⁄2\" - 8\"
(B3100) only
Installation Note: Fig. 1CBS fits easily over the cross bolt
and attaches by pinching tabs down.
Finish: Pre-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number and finish.
TOLCO Fig. 1CBS - Clevis Bolt Spacer
Pipe Size Approx. Wt./100
Part No. in. (mm) lbs. (kg)
1CBS-1 1\" (25) 3.2 (1.4)
1CBS-11/4 11/4\" (32) 4.1 (1.8)
1CBS-11/2 11/2\" (40) 4.8 (2.2)
1CBS-2 2\" (50) 9.4 (4.2)
1CBS-21/2 21/2\" (65) 11.4 (5.2)
1CBS-3 3\" (75) 13.9 (6.8)
1CBS-31/2 31/2\" (90) 16.0 (7.2)
1CBS-4 4\" (100) 18.0 (8.1)
1CBS-5 5\" (125) 27.3 (12.4)
1CBS-6 6\" (150) 32.5 (14.7)
1CBS-8 8\" (200) 42.5 (19.2)
1CBS-10 10\" (250) 72.7 (32.9)
1CBS-12 12\" (300) 86.3 (39.1)
1CBS-14 14\" (350) 157.6 (71.5)
1CBS-16 16\" (400) 183.7 (83.3)
1CBS-18 18\" (450) 224.6 (101.9)
1CBS-20 20\" (500) 254.0 (115.2)
TOLCO Fig. 25 - Surge Restrainer
Size Range: — One size fits 3
⁄4\" (20mm) thru 2\" (40mm) pipe.
Material: — Pre-Galvanized Steel
Function: — Designed to be used in conjunction with Fig. 200 band hangers
to restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and
efficiently installed by snapping into a locking position on the band hanger.
This product is intended to satisfy the requirements as indicated in the
National Fire Protection Association NFPA 13, 2016 edition, 9.2.3.4.4.1 and
9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe.
Approvals: — Underwriters Laboratories Listed only when used with band
hanger Fig. 200, in the USA (UL) and Canada (cUL).
Finish: Pre-Galvanized
Order By: Figure number and band hanger, size from 3
⁄4\" (20mm) thru 2\" (40mm).
Patent #5,344,108
Approx. Wt./100
Part No. lbs. (kg)
25 4.8 (2.2)
OPM
Sizes 2\" (50) thru 20\" (500)
Sizes 1\" (25) thru 11
/2\" (40)
Pipe Hangers
Pipe Hangers
23 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
TOLCO Fig. 200 - “Trimline” Adjustable Band Hanger
TOLCO Fig. 200F - “Trimline” Adjustable Band Hanger with Felt Lining for Copper Tubing
TOLCO Fig. 200C - “Trimline” Adjustable Band Hanger with Plastic Coated
TOLCO Fig. 200S - “Trimline” Adjustable Band Hanger with Removable Nut (For sizes 1\" thru 2\")
Size Range:
Fig. 200 - 1
/2\" (15mm) thru 8\" (200mm) pipe
Material: Steel, Pre-Galvanized
Function: For fire sprinkler and other general piping purposes. Knurled
swivel nut design permits hanger adjustment after installation.
Features:
• 1
/2\" (15mm) thru 2\" (50mm) sizes have flared edges for ease of
installation on all pipe types and protects CPVC plastic pipe from
abrasion. Captured knurled nut design (flared top) on 1\" thru 2\" sizes
keep nut from separating with hanger. Hanger is easily installed
around pipe.
• 1
/2\" (15mm), 3
/4\" (20mm), and 21
/2\" (65mm) thru 8\" (200mm)) Spring
tension on nut holds it securely in hanger before installation. Knurled
nut is easily removed.
• For 1
/2\" (15mm) and 3
/4\" (20mm) sizes with non-captured knurl nuts
order Fig. 200S
Approvals: Underwriters Laboratories listed (1
/2\" (15mm) thru 8\" (200mm))
in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and
Factory Mutual Engineering Approved (FM) (3
/4\" (20mm) thru 8\" (200mm)).
Conforms to Federal Specifications WW-H-171E & A-A-1192A, Type 10
and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58,
Type 10.
Maximum Temperature: 650°F (343°C)
Finish: Pre-Galvanized. Stainless Steel
materials will be supplied with (2) hex nuts
in place of a knurl nut.
Order By: Part number and pipe size
** Note: For metric hanger rod sizes add the
metric rod size to the figure number.
Example: 200M8-11
/2 or 200M10-11
/2
† M8 rod size is not UL Listed or FM Approved
A
B
D
Fig.
200-1 to
200-2
Fig.
200-1
/2 &
200-3
/4
Fig.
200-21
/2 to 200-8
Pipe Size Rod Size A B D Max. Rec. Load Approx. Wt./100
Part No.** in. (mm) in. mm** in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
200-1
/2 1
/2\" (15) 3
/8\"-16 M8† or M10 31
/8\" (79.4) 25
/8\" (66.7) 111/32\" (34.1) 400 (1.78) 11 (5.0)
200-3
/4 3
/4\" (20) 3
/8\"-16 M8† or M10 31
/8\" (79.4) 21
/2\" (63.5) 11
/16\" (27.0) 400 (1.78) 11 (5.0)
200-1 1\" (25) 3
/8\"-16 M8† or M10 33
/8\" (85.7) 25
/8\" (66.7) 11
/8\" (28.6) 400 (1.78) 12 (5.5)
200-11
/4 11
/4\" (32) 3
/8\"-16 M8† or M10 33
/4\" (94.0) 27
/8\" (73.0) 15
/32\" (29.3) 400 (1.78) 13 (5.9)
200-11
/2 11
/2\" (40) 3
/8\"-16 M†8 or M10 37
/8\" (98.4) 27
/8\" (73.0) 13
/16\" (30.2) 400 (1.78) 14 (6.4)
200-2 2\" (50) 3
/8\"-16 M8† or M10 41
/2\" (114.3) 39
/50\" (80.8) 13
/16\" (30.2) 400 (1.78) 15 (6.9)
200-21
/2 21
/2\" (65) 3
/8\"-16 M10 55
/8\" (142.9) 41
/8\" (104.7) 17
/16\" (36.5) 600 (2.67) 27 (12.3)
200-3 3\" (75) 3
/8\"-16 M10 57
/8\" (149.1) 4\" (101.6) 11
/4\" (31.7) 600 (2.67) 29 (13.3)
200-31
/2 31
/2\" (90) 3
/8\"-16 M10 73
/8\" (187.3) 51
/4\" (133.3) 23
/16\" (55.6) 600 (2.67) 34 (15.6)
200-4 4\" (100) 3
/8\"-16 M10 73
/8\" (187.3) 5\" (127.0) 13
/8\" (34.9) 1000 (4.45) 35 (16.0)
200-5 5\" (125) 1
/2\"-13 M12 91
/8\" (231.8) 61
/4\" (158.7) 311/32\" (84.9) 1250 (5.56) 66 (30.2)
200-6 6\" (150) 1
/2\"-13 M12 101
/8\" (257.2) 63
/4\" (171.4) 27
/32\" (56.3) 1250 (5.56) 73 (33.4)
200-8 8\" (200) 1
/2\"-13 M12 131
/8\" (333.4) 83
/4\" (222.2) 37
/32\" (81.7) 1250 (5.56) 136 (62.3)
Fig. 200C
200C-11
/2 shown
Fig. 200F
200F-11
/2 shown
Fig. 200 & Fig. 200S
shown with
non-captured nut
Fig. 200
shown with captured nut
1\" thru 2\" sizes only
A
Overall Height
B
Center of pipe to top of knurled hanger rod nut.
D
Top of pipe to bottom of hanger rod nut.
† †
Pipe Hangers
TOLCO Fig. 200H - Heavy Duty Band Hanger (For Trapeze)
Size Range: 2\" (50mm) thru 4\" (100mm) trapeze pipe size.
Material: Steel — Pre-Galvanized
Function: Designed primarily to support substantially heavier loads than
is normally intended for the nominal hanger size. Used
extensively to support trapeze installations and the increased loads from
both above and below the trapeze assembly.
Features: Furnished with 3
/8\"-16 or 1
/2\"-13 adjusting threaded ring nut.
Approvals: Underwriters Laboratories listed in the USA (UL) and
Canada (cUL). Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 10 and Manufacturers Standardization Society ANSI/
MSS SP-69 & SP-58, Type 10.
Maximum Temperature: 650°F (343°C)
Finish: Pre-Galvanized
Order By: Figure number, pipe size and rod size.
Important Design Note. Because of the increased loads applied to the
trapeze assembly, both the upper trapeze supports as well as the lower
hanging unit must be able to hold the maximum loads intended.
† If using metric rods the M8 rod size is not UL Listed
A
B
Pipe Size Rod Size A B Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) lbs. (kg)
200H-2-3
/8 2\" (50) 3
/8\"-16† 49
/16\" (115.9) 37
/32\" (81.7) 48 (21.8)
200H-2-1
/2 2\" (50) 1
/2\"-13 423/32\" (119.8) 33
/8\" (85.7) 45 (20.4)
200H-21
/2-3
/8 21
/2\" (65) 3
/8\"-16† 55
/16\" (134.9) 323/32\" (94.4) 59 (26.7)
200H-21
/2-1
/2 21
/2\" (65) 1
/2\"-13 515/32\" (138.9) 37
/8\" (98.3) 56 (25.4)
200H-3-3
/8 3\" (75) 3
/8\"-16† 53
/4\" (146.0) 327/32\" (97.6) 63 (28.6)
200H-3-1
/2 3\" (75) 1
/2\"-13 57
/8\" (148.1) 331/32\" (100.8) 60 (27.2)
200H-4-3
/8 4\" (100) 3
/8\"-16† 67
/8\" (174.6) 47
/16\" (112.7) 76 (34.5)
200H-4-1
/2 4\" (100) 1
/2\"-13 71
/32\" (178.6) 419/32\" (1116.7) 73 (33.1)
Select trapeze pipe size based on section modulus required for span of trapeze per information provided in NFPA 13.
All sizes are UL Listed to support up to 8\" pipe at max spacing per NFPA 13.
For 6\" (150mm) and 8\" (200mm) trapeze pipe, consult factory.
Pipe Hangers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
24 Eaton B-Line series Fire Protection Solutions
Fig. 200H Fig. 200H
Fig. 200H
Fig. 200
†
Pipe Hangers
B3198HCT - Hinged Extension Split Pipe Clamp
Tubing Size Rod Size C Design Load Approx. Wt./100
Part No. in. (mm) A in. (mm) Lbs. (kN) Lbs. (kg)
B3198HCT-1
/2 1
/2\" (15) 3
/8\"-16 5
/8\" (15.9) 180 (.80) 8 (3.6)
B3198HCT-3
/4 3
/4\" (20) 3
/8\"-16 13/16\" (20.6) 180 (.80) 10 (4.5)
B3198HCT-1 1\" (25) 3
/8\"-16 15/16\" (23.8) 180 (.80) 10 (4.5)
B3198HCT-11
/4 11
/4\" (32) 3
/8\"-16 11
/8\" (28.6) 180 (.80) 14 (6.3)
B3198HCT-11
/2 11
/2\" (40) 3
/8\"-16 19
/16\" (39.7) 180 (.80) 18 (8.1)
B3198HCT-2 2\" (50) 3
/8\"-16 17
/8\" (47.6) 180 (.80) 23 (10.4)
Size Range: 1
/2\" (15mm) to 2\" (50mm) copper tubing
Material: Malleable Iron
Function: A rigid support to suspend tubing
horizontally or vertically.
Approvals: Conforms to Federal Specification
WW-H-171E & A-A-1192A, Type 25 and
Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 12.
Standard Finish: DURA-COPPER™
Order By: Figure number and finish.
A
(Rod Size)
Hanger Rod
C Not Included
Size Range: 3
/8\" (10mm) to 3\" (80mm) pipe
Material: Malleable Iron
Function: Designed for suspending non-insulated pipe horizontally or vertically.
Approvals: Conforms to Federal Specification WW-H-171E & A-A-1192A, Type 25
and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 12.
Standard Finish: Plain or Electro-Galvanized
Order By: Figure number and finish.
B3198H - Hinged Extension Split Pipe Clamp
A
(Rod Size)
Hanger Rod Not
Included C
Pipe Size Rod Size C Design Load Approx. Wt./100
Part No. in. (mm) A in. (mm) Lbs. kN Lbs. kg
B3198H-3
/8 3
/8\" (10) 3
/8\"-16 31/32\" (24.6) 180 (.80) 9 (4.1)
B3198H-1
/2 1
/2\" (15) 3
/8\"-16 11
/16\" (27.0) 180 (.80) 12 (5.4)
B3198H-3
/4 3
/4\" (20) 3
/8\"-16 17
/32\" (30.9) 180 (.80) 12 (5.4)
B3198H-1 1\" (25) 3
/8\"-16 111/32\" (34.1) 180 (.80) 13 (5.9)
B3198H-11
/4 11
/4\" (32) 3
/8\"-16 119/32\" (39.7) 180 (.80) 18 (8.1)
B3198H-11
/2 11
/2\" (40) 3
/8\"-16 123/32\" (43.6) 180 (.80) 21 (9.5)
B3198H-2 2\" (50) 3
/8\"-16 2\" (50.8) 180 (.80) 44 (19.9)
B3198H-21
/2 21
/2\" (65) 1
/2\"-13 211/32\" (59.5) 300 (1.33) 73 (33.1)
B3198H-3 3\" (80) 1
/2\"-13 223/32\" (69.0) 300 (1.33) 95 (43.1)
Pipe Hangers
25 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Pipe Hangers
TOLCO Fig. 120 - “U\" Hanger
Size Range: Size 3
/4\" (20mm) thru 8\" (200mm) pipe
Material: Steel
Function: Used to support piping from wood beams
where no contraction is expected. Used extensively in
automatic fire sprinkler systems.
Approvals: Complies with requirements of National
Fire Protection Association (NFPA), Pamphlet 13.
Maximum Temperature: 750°F (399°C)
Finish: Plain. Contact customer service for alternative
finishes and materials.
Order By: Figure number, pipe size, length and finish
Length
(Specify)
A
Pipe Size A Fastener Size
Part No. in. (mm) in. (mm)
120-3
/4 3
/4\" (20) 5
/16\" (7.9) 16 x 2*
120-1 1\" (25) 5
/16\" (7.9) 16 x 2*
120-11
/4 11
/4\" (32) 5
/16\" (7.9) 16 x 2*
120-11
/2 11
/2\" (40) 5
/16\" (7.9) 16 x 2*
120-2 2\" (50) 5
/16\" (7.9) 16 x 2*
120-21
/2 21
/2\" (65) 3
/8\" (9.5) 3
/8 x 21
/2**
120-3 3\" (80) 3
/8\" (9.5) 3
/8 x 21
/2**
120-31
/2 31
/2\" (90) 3
/8\" (9.5) 3
/8 x 21
/2**
120-4 4\" (100) 3
/8\" (9.5) 1
/2 x 3**
120-5 5\" (125) 1
/2\" (12.7) 1
/2 x 3**
120-6 6\" (150) 1
/2\" (12.7) 1
/2 x 3**
120-8 8\" (200) 1
/2\" (12.7) 5
/8 x 3**
* Drive Screw
** Lag Bolt
Pipe Hangers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
26 Eaton B-Line series Fire Protection Solutions
Note: 30° leg style for some sizes. Consult factory for availability.
Pipe Hangers
TOLCO Fig. 120MJ - Mutt & Jeff “U” Hanger
Size Range: Size 3
/4\" (20mm) thru 8\" (200mm) pipe
Material: Steel
Function: Used to support piping from wood beams where
no contraction is expected. Used extensively in automatic fire
sprinkler systems. Fig. 120MJ is used when the wood beam is
on a diagonal.
Finish: Plain. Contact customer service for alternative finishes
and materials.
Order By: Figure number, side length and finish
A
Pipe Size A Fastener Size
Part No. in. (mm) in. (mm)
120MJ-3
/4 3
/4\" (20) 5
/16\" (7.9) 16 x 2*
120MJ-1 1\" (25) 5
/16\" (7.9) 16 x 2*
120MJ-11
/4 11
/4\" (32) 5
/16\" (7.9) 16 x 2*
120MJ-11
/2 11
/2\" (40) 5
/16\" (7.9) 16 x 2*
120MJ-2 2\" (50) 5
/16\" (7.9) 16 x 2*
120MJ-21
/2 21
/2\" (65) 3
/8\" (9.5) 3
/8 x 21
/2**
120MJ-3 3\" (80) 3
/8\" (9.5) 3
/8 x 21
/2**
120MJ-31
/2 31
/2\" (90) 3
/8\" (9.5) 3
/8 x 21
/2**
120MJ-4 4\" (100) 3
/8\" (9.5) 1
/2 x 3**
120MJ-5 5\" (125) 1
/2\" (12.7) 1
/2 x 3**
120MJ-6 6\" (150) 1
/2\" (12.7) 1
/2 x 3**
120MJ-8 8\" (200) 1
/2\" (12.7) 5
/8 x 3**
Pipe Size A Fastener Size
Part No. in. (mm) in. (mm)
120W-3
/4 3
/4\" (20) 5
/16\" (7.9) 16 x 2*
120W-1 1\" (25) 5
/16\" (7.9) 16 x 2*
120W-11
/4 11
/4\" (32) 5
/16\" (7.9) 16 x 2*
120W-11
/2 11
/2\" (40) 5
/16\" (7.9) 16 x 2*
120W-2 2\" (50) 5
/16\" (7.9) 16 x 2*
* Drive Screw
** Lag Bolt
* Drive Screw
TOLCO Fig. 120W - Wrap Around “U\" Hanger
Size Range: Size 3
/4\" (20mm) thru 2\" (50mm) pipe
Material: Steel
Function: Required for automatic fire protection agencies
to be used on the end of branch lines to prevent pipe from
whipping vertical and striking ceiling or beam.
Finish: Plain. Contact customer service for alternative finishes
and materials.
Order By: Figure number, side length and finish
Length
(Specify)
Length
(Specify)
A
Pipe Hangers
27 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Note: 30° leg style for some sizes. Consult factory for availability.
Pipe Hangers
TOLCO Fig. 120RWA - (Model B) Retrofit Wrap Around “U\" Hanger Clamp
Size Range: 1\" (25mm) thru 6\" (150mm) pipe
Material: Steel
Function: Designed to restrain movement of the pipe within standard
U-hangers as required by NFPA 13. Where retrofit capability is crucial, the
Fig. 120RWA is a labor efficient alternative to the standard B-Line series
Fig. 120W wrap around U-hanger.
Fig. 120RWA can also be used in new installations.
Features Installs easily by tightening two hex nuts. Features a unique
bracing slot that locks onto a standard U-hanger to become a solid unit that
will stabilize the pipe during seismic activity or sprinkler head activation.
Designed to be used in retrofit or new construction applications. Will clamp
to existing U-Hangers without restriction to leg angle.
Approvals: Underwriters Laboratories listed in the USA (UL) and Canada
(cUL) as a restrainer. NFPA 13 (2016) 9.3.6.3.
Finish: Plain and Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, type numbers and pipe size
Ordering Note: Order by the following type and pipe size:
Type 1 — (1\" (25mm) and 11
/4\" (32mm) pipe size)
Type 2 — (11
/2\" (40mm) and 2\" (50mm) pipe size)
Type 3 — (21
/2\" (65mm) and 3\" (80mm) pipe size)
Type 4 — (4\" (100mm) pipe size)
Type 6 — (5\" (125mm) and 6\" (150mm) pipe size)
Important Note: The bracing slot feature is sized to fit the U-Hanger rod
schedule as required by NFPA 13 as follows:
5
/16\" (7.9mm) rod for up to 2\" (50mm) pipe 3
/8\" (9.5mm) rod for 21
/2\" (65mm) - 6\" (160mm) pipe
For other rod size requirements consult factory.
Type Pipe Size
Part No. in. (mm)
120RWA-TYPE1-1 1 1\" (20)
120RWA-TYPE1-11
/4 1 11
/4\" (25)
120RWA-TYPE2-11
/2 2 11
/2\" (40)
120RWA-TYPE2-2 2 2\" (50)
120RWA-TYPE3-21
/2 3 21
/2\" (65)
120RWA-TYPE3-3 3 3\" (80)
120RWA-TYPE4-31
/2 4 31
/2\" (90)
120RWA-TYPE4-4 4 4\" (100)
120RWA-TYPE6-5 6 5\" (125)
120RWA-TYPE6-6 6 6\" (150)
Pipe Hangers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
28 Eaton B-Line series Fire Protection Solutions
Pipe Clamps
B3373 - Standard Riser Clamp
B3373C - PVC Coated Standard Riser Clamp
Bolts and Nuts Included
Bolt Size
L
Pipe Size L Approx. Wt./100
Part No. in. (mm) in. (mm) Bolt Size Lbs. (kg)
B3373-1
/2 1
/2\" (15) 9\" (228.6) 3
/8\"-16 x 11
/4\" 101 (45.9)
B3373-3
/4 3
/4\" (20) 91
/4\" (234.9) 3
/8\"-16 x 11
/4\" 105 (47.7)
B3373-1 1\" (25) 99
/16\" (242.9) 3
/8\"-16 x 11
/4\" 109 (49.4)
B3373-11
/4 11
/4\" (32) 10\" (254.0) 3
/8\"-16 x 11
/4\" 112 (50.9)
B3373-11
/2 11
/2\" (40) 101
/4\" (260.3) 3
/8\"-16 x 11
/2\" 113 (51.1)
B3373-2 2\" (50) 103
/4\" (273.0) 3
/8\"-16 x 11
/2\" 165 (75.0)
B3373-21
/2 21
/2\" (65) 111
/4\" (285.7) 3
/8\"-16 x 11
/2\" 180 (81.6)
B3373-3 3\" (80) 1115/16\" (303.2) 3
/8\"-16 x 11
/2\" 195 (88.4)
B3373-31
/2 31
/2\" (90) 123
/8\" (314.3) 1
/2\"-13 x 13
/4\" 217 (98.5)
B3373-4 4\" (100) 127
/8\" (327.0) 1
/2\"-13 x 13
/4\" 228 (103.5)
B3373-5 5\" (125) 14\" (355.6) 1
/2\"-13 x 13
/4\" 480 (217.7)
B3373-6 6\" (150) 153
/16\" (385.8) 1
/2\"-13 x 2\" 526 (238.6)
B3373-8 8\" (200) 173
/4\" (450.8) 5
/8\"-11 x 21
/2\" 957 (434.1)
B3373-10 10\" (250) 197
/16\" (493.7) 5
/8\"-11 x 21
/2\" 1101 (499.4)
B3373-12 12\" (300) 2111/16\" (550.9) 5
/8\"-11 x 3\" 1622 (735.7)
B3373-14 14\" (350) 239
/16\" (598.5) 5
/8\"-11 x 3\" 1732 (785.6)
B3373C
Size Range: (B3373) 1
/2\" (15mm) thru 30\" (760mm) pipe
(B3373C) 1
/2\" (15mm) thru 6\" (150mm) pipe
Material: Steel
Function: Used for supporting vertical piping.
Approvals: Underwriters Laboratories Listed in the USA (UL), Canada (cUL) 3
/4\" (20mm) - 8\" (200mm). Factory Mutual Engineering Approved (FM), 3
/4\" (20mm)
thru 8\" (200mm). Conforms to Federal Specification WW-H-171E & A-A-1192A, Type
8, and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 8.
Maximum Temperature: 650°F (343°C)
Finish: Plain. Contact customer service for alternative finishes and materials.
Order By:
Figure number, pipe size and finish.
Designed to meet or exceed requirements of FM DS 2-0.
Notes: For ductile iron
(D.I.) pipe use part
number B3373DI-pipe
size. Contact B-Line
Engineering for more
information.
For larger sizes, consult
the full line pipe hanger
catalog.
Pipe Clamps
29 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Pipe Clamps
B3140 - Standard Pipe Clamp
B3140C - Standard Pipe Clamp PVC Coated
B3140F - Standard Pipe Clamp Felt Lined
Size Range: B3140/B3140C Size 1
/2\" (15mm) thru 12\" (300mm) pipe.
Material: Steel
Function: Recommended for the suspension of non-insulated pipe
or insulated pipe with B3151 shields. (Use B3200 weldless eye nut,
B3210 eye rod or B3211 welded eye rod.) B3140F and B3140C are
designed to help reduce noise and vibration and/or prevent electrolysis.
Approvals: Underwriters Laboratories Listed in the USA (UL), Canada
(cUL) 3
/4\" (20mm) - 12\" (300mm), and approved by Factory Mutual
Engineering (FM), 3
/4\" (20mm) - 8\" (200mm). Federal Specification
WW-H-171E & A-A-1192A, Type 4, and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 4.
Note: For piping that requires sway bracing refer to Fig. 4A.
Maximum Temperature: — 750°F (399°C)
Finish: Plain. Contact customer service for alternative finishes
and materials.
Order By: Figure number, pipe size and finish.
Order Note: When ordering B3140F allow for 3
/16\" (4.8mm) felt on
each half of clamp.
Designed to meet or exceed requirements of FM DS 2-0.
C
C
A
Bolt Size
B
B
Pipe Approx.
Part Size A B C Bolt Wt./100
No. in. (mm) in. (mm) in. (mm) in. (mm) Size lbs. (kg)
B3140-1
/2 1
/2\" (15) 3
/8\" (9.5) 31/32\" (24.6) 117/32\" (38.9) 5
/16\"-18 30 (13.6)
B3140-3
/4 3
/4\" (20) 9
/16\" (14.3) 13
/32\" (27.8) 121/32\" (42.0) 5
/16\"-18 31 (14.0)
B3140-1 1\" (25) 9
/16\" (14.3) 15
/16\" (33.3) 17
/8\" (47.6) 5
/16\"-18 33 (14.5)
B3140-11
/4 11
/4\" (32) 17/32\" (13.5) 17
/16\" (36.5) 2\" (50.8) 5
/16\"-18 39 (17.7)
B3140-11
/2 11
/2\" (40) 19/32\" (15.1) 121/32\" (42.0) 27
/32\" (56.4) 5
/16\"-18 41 (18.6)
B3140-2 2\" (50) 9
/16\" (14.3) 21
/8\" (54.0) 23
/4\" (69.8) 1
/2\"-13 118 (53.5)
B3140-21
/2 21
/2\" (65) 5
/8\" (15.9) 221/32\" (67.5) 39
/32\" (83.3) 1
/2\"-13 130 (58.9)
B3140-3 3\" (75) 5
/8\" (15.9) 215/16\" (74.6) 39
/16\" (90.5) 1
/2\"-13 150 (68.0)
B3140-31
/2 31
/2\" (90) 5
/8\" (15.9) 35
/32\" (80.1) 325/32\" (96.0) 1
/2\"-13 158 (71.6)
B3140-4 4\" (100) 3
/4\" (19.0) 39
/16\" (90.5) 45
/16\" (109.5) 5
/8\"-11 239 (108.4)
B3140-5 5\" (125) 3
/4\" (19.0) 41
/8\" (104.8) 47
/8\" (123.8) 5
/8\"-11 272 (123.4)
B3140-6 6\" (150) 7
/8\" (22.2) 415/16\" (125.4) 513/16\" (147.6) 3
/4\"-10 541 (245.4)
B3140-8 8\" (200) 1\" (25.4) 61
/16\" (154.0) 615/16\" (176.2) 3
/4\"-10 642 (291.2)
B3140-10 10\" (250) 1\" (25.4) 73
/8\" (187.3) 811/16\" (220.7) 7
/8\"-9 1366 (619.6)
B3140-12 12\" (300) 1\" (25.4) 87
/16\" (214.3) 93
/4\" (247.6) 7
/8\"-9 1543 (699.9)
Pipe Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
30 Eaton B-Line series Fire Protection Solutions
B3140
B3140C B3140F
Pipe Clamps
Pipe Clamps
31 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B2400 - Standard Pipe Strap
Part No. Pipe Size A B C T W
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B2400-1
/2 1
/2\" (15) 5
/16\" (7.9) 7
/16\" (11.1) 213/16\" (71.4) 10 Ga. (3.4) 15
/8\" (41.3)
B2400-3
/4 3
/4\" (20) 5
/16\" (7.9) 7
/16\" (11.1) 3\" (76.2) 10 Ga. (3.4) 15
/8\" (41.3)
B2400-1 1\" (25) 5
/16\" (7.9) 7
/16\" (11.1) 317/32\" (89.7) 10 Ga. (3.4) 15
/8\" (41.3)
B2400-11
/4 11
/4\" (32) 5
/16\" (7.9) 7
/16\" (11.1) 33
/4\" (95.2) 10 Ga. (3.4) 15
/8\" (41.3)
B2400-11
/2 11
/2\" (40) 5
/16\" (7.9) 7
/16\" (11.1) 41
/16\" (103.2) 10 Ga. (3.4) 15
/8\" (41.3)
B2400-2 2\" (50) 7
/16\" (11.1) 11/16\" (17.4) 521/32\" (143.6) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-21
/2 21
/2\" (65) 7
/16\" (11.1) 11/16\" (17.4) 65
/32\" (156.3) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-3 3\" (80) 7
/16\" (11.1) 11/16\" (17.4) 625/32\" (172.2) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-31
/2 31
/2\" (90) 7
/16\" (11.1) 11/16\" (17.4) 79
/32\" (184.9) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-4 4\" (100) 9
/16\" (14.3) 11/16\" (17.4) 725/32\" (197.6) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-5 5\" (125) 9
/16\" (14.3) 11/16\" (17.4) 87
/8\" (225.4) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-6 6\" (150) 9
/16\" (14.3) 11/16\" (17.4) 915/16\" (252.4) 1
/4\" (6.3) 15
/8\" (41.3)
B2400-8 8\" (200) 9
/16\" (14.3) 11/16\" (17.4) 1131/32\" (304.0) 1
/4\" (6.3) 15
/8\" (41.3)
Bolt Size
A
B
T
C
W
* Design
Load 2
* Design
Load 1
Pipe Size Size Range: 1
/2\" (15mm) thru 24\" (600mm) pipe
Material: Steel
Function: Designed for supporting pipe runs from
strut supports.
Approvals: Underwriters Laboratories Listed (UL), Canada
(cUL) for B2400-3
/4\" thru B2400-8\". Conforms to Federal
Specification WW-H-171E & A-A-1192A, Type 26 and
Manufacturers Standardization Society ANSI/MSS SP-69
& SP-58, Type 26. Included in our Seismic Engineering
Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating
to OSHPD projects, please refer to our Seismic Engineering
Guidelines OPM-0052-13
Finish: Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, pipe size and finish
Note: Ductile iron sizes available.
Special “B\" dimensions available on request, consult factory.
For larger sizes, consult the full line pipe hanger catalog.
* See OPM-0052-13 for design loads.
OPM
* Design
Load 3
CPVC Clamps
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
32 Eaton B-Line series Fire Protection Solutions
TOLCO Fig. 22 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe
Single Fastener Strap
Size Range: 3
/4\" (20mm) thru 2\" (50mm) CPVC pipe
Material: Pre-Galvanized Steel
Function: Intended to perform as a hanger to support CPVC piping used
in automatic fire sprinkler systems. The product acts as a hanger when tab
is upward and the fastener screw is in the horizontal position. Fig. 22 can
be installed on the top of a beam, but in this situation acts as a guide to the
piping which is supported by the beam itself. It is not intended to support
CPVC pipe from under a flat horizontal surface, such as a ceiling.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge (0.9mm) steel
using (1) 1
/4\" x 1\" tek type screw. Meets and exceeds the requirements of
NFPA 13,
13R and 13D.
Features: Fig. 22 incorporates features which protect the pipe and ease
installation. The flared edge design protects CPVC pipe from any rough
surface. It is easily attached to the building structure using the special UL
Listed hex head self threading screw* furnished with the product. It
is recommended that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No impact tools (such as a
hammer) are allowed. Damage has been known to result from installations
using impact type tools. No pre-drilling of a pilot hole in wood is
required.
Finish: Pre-Galvanized
Order By: Figure number and pipe size.
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
C
A
B
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing Head Size Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg)
22-3
/4 3
/4\" (20) 27
/16\" (61.9) 15
/16\" (33.3) 13
/16\" (30.2) 5’-6\" (1.67) 5
/16\" (7.9) 9 (4.1)
22-1 1\" (25) 211/16\" (68.3) 17
/16\" (36.5) 13
/16\" (30.2) 6’-0\" (1,83) 5
/16\" (7.9) 9 (4.1)
22-11
/4 11
/4\" (32) 31
/16\" (77.8) 15
/8\" (42.3) 13
/16\" (30.2) 6’-6\" (1.98) 5
/16\" (7.9) 11 (5.0)
22-11
/2 11
/2\" (40) 35
/16\" (84.1) 13
/4\" (44.4) 13
/16\" (30.2) 7’-0\" (2.13) 5
/16\" (7.9) 12 (5.4)
22-2 2\" (50) 33
/4\" (95.2) 21
/8\" (54.6) 13
/16\" (30.2) 8’-0\" (2.44) 5
/16\" (7.9) 15 (6.8)
IPS Max. Hanger
Pipe Size Spacing
Part No. in. (mm) Ft. (m)
22-3
/4 3
/4\" (20) 1’-9\" (1.67)
22-1 1\" (25) 1’-10\" (1.83)
22-11
/4 11
/4\" (32) 2-4\" (1.98)
22-11
/2 11
/2\" (40) 2-9\" (2.13)
22-2 2\" (50) 3-6\" (2.44)
Reduced Spacing For IPS Pipe
CPVC Clamps
CPVC Clamps
33 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
TOLCO Fig. 22L2 - One Hole Hanger/Restrainer for CPVC & Steel Pipe
Size Range: 3
/4\" (20mm) thru 2\" (50mm) CPVC & steel pipe
Material: Pre-Galvanized Steel
Function: cULus Listed to perform as a hanger and restrainer for CPVC or IPS
piping systems. The innovative design also allows for a preferred installation
location close to a CPVC fitting without applying damaging compression forces on the pipe which could result in serious Mechanical ESC (Environmental
Stress Cracking).
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. Can be installed in wood or into minimum
20 gauge (0.9mm) steel using (1) 1
/4\" x 1\" tek type screw. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Installation Note: Comes in open position for easier installation. Because of
multi – structural installation possibilities, specific fastener not included; see
notes below for various applications.
For Concrete Installation — UL requires a minimum test load of 340 lbs
for CPVC hangers and 750 lbs for steel pipe hangers; verify anchors meet or
exceed these requirements.
For Wood Installation — #14 x 11
/2\" wood screws will support the required
load for cULus.
For Steel Installation — 1
/4\" x 1\" (min. 20ga steel) Tek type screw will
support required UL load.
Finish: Pre-Galvanized
Order By: Part number
C
A
B
CPVC or Steel Max. Hanger Max. Hanger Approx.
Pipe Size A B C Spacing - CPVC Spacing - Steel Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) Ft. (m) Lbs. (kg)
22L2-3
/4 3
/4\" (20) 23
/16\" (55.6) 15/16\" (23.8) 3
/4\" (19.0) 51
/2 (1.67) NA (NA) 9 (4.1)
22L2-1 1\" (25) 21
/2\" (63.5) 11
/8\" (28.6) 3
/4\" (19.0) 6 (1,83) 12 (3.66) 9 (4.1)
22L2-11
/4 11
/4\" (32) 213/16\" (71.4) 11
/4\" (31.7) 3
/4\" (19.0) 61
/2 (1.98) 12 (3.66) 11 (5.0)
22L2-11
/2 11
/2\" (40) 31
/8\" (79.4) 17
/16\" (36.5) 3
/4\" (19.0) 7 (2.13) 15 (4.57) 12 (5.4)
22L2-2 2\" (50) 39
/16\" (90.5) 15
/8\" (41.3) 3
/4\" (19.0) 8 (2.44) 15 (4.57) 15 (6.8)
TAB DOWN
or TAB UP
SPRINKLER
HEAD
HANGER/RESTRAINER
FITTING OD
MOUNTING SURFACE
PIPE OD
HANGER/RESTRAINER
OFFSET
DESIGN
Tab Down
or Tab Up
Sprinkler
Head
Hanger/Restrainer
Hanger/Restrainer Fitting
OD
Pipe OD
Mounting
Surface
Offset
Design
Patent Pending
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
34 Eaton B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 23 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe
Double Fastener Strap (B-Line B3182)
Size Range: 3
/4\" (20mm) thru 3\" (80mm) CPVC pipe
Material: Pre-Galvanized Steel
Function: Intended to perform as a hanger to support CPVC piping
used in automatic fire sprinkler systems. Fig. 23 can be installed
on the top, bottom or side of a beam.
Approvals: Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL) sizes 3
/4\" (20mm) thru 2\" (50mm) to support fire
sprinkler piping. May be installed in wood using fasteners supplied
with product, or into minimum 20 gauge (0.9mm) steel using (2) 1
/4\"
x 1\" tek type screw. Meets and exceeds the requirements of NFPA
13, 13R and 13D.
Features: Fig. 23 incorporates features which protect the pipe
and ease installation. The flared edge design protects the CPVC
pipe from any rough surface. It also incorporates snap restrainers
allowing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws*
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as
installation tools. No impact tools (such as a hammer) are allowed.
Damage has been known to result from installations using impact
type tools. No pre-drilling of a pilot hole in wood is required.
Finish: Pre-Galvanized
Order By: Figure number and pipe size
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
A
C
B
B
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing Head Size Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg)
23-3
/4 3
/4\" (20) 31
/8\" (79.4) 19
/16\" (39.7) 13
/16\" (30.2) 51
/2 (1.67) 5
/16\" (7.9) 9 (4.1)
23-1 1\" (25) 33
/8\" (85.7) 111/16\" (42.9) 13
/16\" (30.2) 6 (1,83) 5
/16\" (7.9) 9 (4.1)
23-11
/4 11
/4\" (32) 43
/16\" (106.4) 23
/32\" (53.1) 13
/16\" (30.2) 61
/2 (1.98) 5
/16\" (7.9) 11 (5.0)
23-11
/2 11
/2\" (40) 47
/16\" (112.7) 27
/32\" (56.3) 13
/16\" (30.2) 7 (2.13) 5
/16\" (7.9) 12 (5.4)
23-2 2\" (50) 47
/8\" (123.8) 27
/16\" (61.9) 13
/16\" (30.2) 8 (2.44) 5
/16\" (7.9) 15 (6.8)
23-21
/2 21
/2\" (65) 53
/8\" (136.5) 211/16\" (68.3) 13
/16\" (30.2) Consult Factory 5
/16\" (7.9) 22 (10.0)
23-3 3\" (80) 6\" (152.4) 3\" (76.2) 13
/16\" (30.2) Consult Factory 5
/16\" (7.9) 25 (11.3)
IPS Max. Hanger
Pipe Size Spacing
Part No. in. (mm) Ft. (m)
23-3
/4 3
/4\" (20) 1’-9\" (1.67)
23-1 1\" (25) 1’-10\" (1.83)
23-11
/4 11
/4\" (32) 2-4\" (1.98)
23-11
/2 11
/2\" (40) 2-9\" (2.13)
23-2 2\" (50) 3-6\" (2.44)
23-21
/2 21
/2\" (65) Consult Factory
23-3 3\" (80) Consult Factory
Reduced Spacing For IPS Pipe
CPVC Clamps
35 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe
Double Fastener Strap Side Mounted (B-Line B3183)
Size Range: 3
/4\" (20mm) thru 2\" (50mm) CPVC pipe
Material: Pre-Galvanized Steel
Function: Intended to perform as a hanger to support CPVC piping used in
automatic fire sprinkler systems. Can be installed on the top or on the bottom
of a beam.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge (0.912mm) steel
using (2) 1
/4\" x 1\" tek type screws. Meets and exceeds the requirements of
NFPA 13, 13R and 13D.
Features: Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the
two UL Listed hex head self threading screws* furnished with the
product. It is recommended that rechargeable electric drills fitted with
a hex socket attachment be used as installation tools. No impact
tools (such as a hammer) are allowed. Damage has been known to
result from installations using impact type tools. No pre-drilling of a
pilot hole in wood is required.
Finish: Pre-Galvanized
Order By: Figure number and pipe size
* Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
C
A
B
B
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing Head Size Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg)
24-3
/4 3
/4\" (20) 25
/16\" (58.7) 15
/32\" (27.8) 13
/16\" (30.2) 51
/2 (1.67) 5
/16\" (7.9) 9 (4.1)
24-1 1\" (25) 25
/8\" (66.7) 15
/16\" (33.3) 13
/16\" (30.2) 6 (1.83) 5
/16\" (7.9) 9 (4.1)
24-11
/4 11
/4\" (32) 3\" (76.2) 11
/2\" (38.1) 13
/16\" (30.2) 61
/2 (1.98) 5
/16\" (7.9) 11 (5.0)
24-11
/2 11
/2\" (40) 31
/4\" (82.5) 15
/8\" (42.3) 13
/16\" (30.2) 7 (2.13) 5
/16\" (7.9) 12 (5.4)
24-2 2\" (50) 311/16\" (93.7) 127/32\" (43.6) 13
/16\" (30.2) 8 (2.44) 5
/16\" (7.9) 15 (6.8)
IPS Max. Hanger
Pipe Size Spacing
Part No. in. (mm) Ft. (m)
24-3
/4 3
/4\" (20) 1’-9\" (1.67)
24-1 1\" (25) 1’-10\" (1.83)
24-11
/4 11
/4\" (32) 2-4\" (1.98)
24-11
/2 11
/2\" (40) 2-9\" (2.13)
24-2 2\" (50) 3-6\" (2.44)
Reduced Spacing For IPS Pipe
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
36 Eaton B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 27B - Speed Nut
Size Range: — Fits screws supplied with all CPVC hangers.
Material: — Steel
Finish: — Pre-Galvanized (Zinc)
Function: — To be used anywhere a screw cannot achieve full embedment due to
thickness of wood structural material when installed. Fig. 27B allows full pull out load
capacity of screws when installed to the standard screws supplied with all CPVC
hangers (Fig. 22, Fig. 22L2, Fig. 23, Fig. 24, Fig. 28, Fig. 28M, Fig. 29, and B3184).
Hanger Application Hanger and Restraint
Application
Hanger and Restraint
Application
Fig. 27B
(2) Required
Fig. 27B
(2) Required
Fig. 27B
(1) Required High
Side of Hanger
Application
Fig. 27B
(1) Required High Side of
Hanger Application
Hanger Application
Approx. Wt./100
Part No. lbs. (kg)
27B 1.2 (0.5)
CPVC Clamps
37 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 28 - “Stand-Off“ Hanger & Restrainer for CPVC Plastic Pipe & IPS Steel Pipe
Size Range: — 3
/4\" (20mm) through 2\" (50mm)
Material: — Steel, Pre-Galvanized
Function: — Designed to be used as a hanger and restrainer for CPVC piping where the
“stand-off“ design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
• Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation.
• The “Stand-Off“ design eliminates the need for wood block extension.
• Can be installed on horizontal or vertical piping regardless of mounting surface orientation.
• Attaches easily to wood structure with two hex head self-threading screws furnished with
product.
• Installs easily using rechargeable electrical driver with 5
/16\" (7.9mm) extension socket
eliminating impact tool damage to pipe.
• Attaches easily to steel, minimum 18 gauge (1.024mm) with (2) 1
/4\" x 1\" tek type self drilling
tapping screws.
• UL Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals: — Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) to
support automatic fire sprinkler systems. May be installed into wood using fasteners supplied
with product, or into minimum 18 gauge steel using (2) 1
/4\" x 1\" tek type screws. Meets and
exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint
requirement where needed. UL Listed as a hanger and vertical restraint when installed on 3
/8\"
(9.5mm) composite wood material. Use two Fig. 27B (page 36) Speed Nuts when used as a
hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as
a hanger only.
Order by: — Figure number and pipe size.
Pat. # 7,455,268, Pat. # 7,832,248
C
A
B
CPVC A B C Max Hanger Approx.
Pipe Size Spacing Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) lbs. (kg)
28-3
/4 3
/4\" (20) 31
/32\" (77.0) 2\" (50.8) 31
/2\" (88.9) 51
/2 (1.67) 18 (8.1)
28-1 1\" (25) 35
/16\" (84.1) 23
/16\" (55.6) 31
/2\" (88.9) 6 (1.83) 21 (9.5)
28-11
/4 11
/4\" (32) 35
/8\" (92.1) 23
/8\" (60.3) 31
/2\" (88.9) 61
/2 (1.98) 23 (10.4)
28-11
/2 11
/2\" (40) 4\" (101.6) 21
/2\" (63.5) 31
/2\" (88.9) 7 (2.13) 31 (14.0)
28-2 2\" (50) 41
/2\" (114.3) 211/16\" (68.3) 35
/8\" (92.1) 8 (2.44) 34 (15.4)
Hanger Application Hanger and Restraint
Application
Fig. 27B
(2) Required Fig. 27B
(1) Required High
Side of Hanger
Application
IPS Max. Hanger
Pipe Size Spacing
Part No. in. (mm) Ft. (m)
28-3
/4 3
/4\" (20) 1’-9\" (1.67)
28-1 1\" (25) 1’-10\" (1.83)
28-11
/4 11
/4\" (32) 2-4\" (1.98)
28-11
/2 11
/2\" (40) 2-9\" (2.13)
28-2 2\" (50) 3-6\" (2.44)
Reduced Spacing For IPS Pipe
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
38 Eaton B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 28M - Offset Hanger & Restrainer for CPVC Plastic Pipe and IPS Steel Pipe
Size Range: 3
/4\" (20mm) thru 2\" (32mm)
Material: Steel, Pre-Galvanized
Function: Designed to be used as a hanger and restrainer for CPVC piping or steel piping
where the “stand-off\" design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces
• Unique snap-on design holds pipe firmly in place and allows retrofit type of installation
• The “Stand-Off“ design eliminates the need for wood block extension
• Can be installed on horizontal or vertical piping regardless of mounting surface
orientation
• Attaches easily to wood structure with two hex head self-threading screws furnished
with product
• Installs easily using rechargeable electrical driver with 5
/16\" (7.9mm) extension socket
eliminating impact tool damage to pipe
• Attaches easily to steel, minimum 18 gauge (1.024mm) with (2) 1
/4\" x 1\" tek type self
drilling tapping screws
• (cULus) Listed as a hanger and a restrainer for fire sprinkler piping
Installation Note: When installed in wood structural members and threads from the
#10 x 1\" screws are exposed, use Fig. 27B (page 36) speed nut to secure
Approvals: Underwriters Laboratory Listed in the USA (UL) and Canada (cUL)
to support automatic fire sprinkler systems. May be installed into wood using fasteners
screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies
the UL vertical restraint requirements where needed.
Order By: Figure number and pipe size
Patent #7,744,042
C
A
B
CPVC Pipe Size A Hole Dia. B C Max Spacing* Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg)
28M-3
/4 3
/4\" (20) 2\" (50.8) 3
/16\" (4.8) 35
/16\" (84.1) 5’-6\" (1676) 9 (4.1)
28M-1 1\" (25) 21
/8\" (54.0) 3
/16\" (4.8) 31
/2\" (88.9) 6’-0\" (1829) 12 (5.4)
28M-11
/4 11
/4\" (32) 25
/16\" (58.7) 3
/16\" (4.8) 31
/2\" (88.9) 6’-6\" (1981) 13 (5.9)
28M-11
/2 11
/2\" (49) 27
/16\" (61.9) 3
/16\" (4.8) 37
/8\" (98.4) 7’-0\" (2133) 14 (6.3)
28M-2 2\" (50) 25
/8\" (66.7) 3
/16\" (4.8) 47
/16\" (112.7) 8’-0\" (2438) 15 (6.8)
* Required per NFPA 13 for CPVC plastic pipe
Hanger and Restraint
Application
Restraint
Restraint
Detail A
Hanger Application
Fig. 27B
(2) Required
Fig. 27B
(1) Required
High Side of Hanger
IPS Pipe Size Max. Hanger Spacing
Part No. in. (mm) Ft. (m)
28-3
/4 3
/4\" (20) 1’-9\" (1.67)
28-1 1\" (25) 1’-10\" (1.83)
28-11
/4 11
/4\" (32) 2-4\" (1.98)
28-11
/2 11
/2\" (40) 2-9\" (2.13)
28-2 2\" (50) 3-6\" (2.44)
Reduced Spacing For IPS Pipe
CPVC Clamps
39 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 29 - double offset hanger & restrainer for CPVC plastic pipe & IPS steel pipe
Size Range: Available in 3
/4\" (20mm) and 1\" (25mm) pipe sizes
Material: Pre-Galvanized Steel
Function: Intended to perform as a hanger and restrainer for CPVC, plastic fire sprinkler
pipe. Provides double offset 11
/2\" (20mm) x 11
/2\" (20mm) from mounting surface. This
design will ease installation by eliminating the need for wood block extension and allow
retro-fit attachment of hanger to sprinkler pipe.
Features:
• Thumb tab provides protection to restrain pipe in rough job site conditions. Tab is
not required to be bent for listed installation.
• Offset edge eliminates abrasion.
• Attaches easily to wood structure with two special #10 x 1\" hex head self-threading
screws furnished with product.
• Can be used as a single offset hanger by aligning “dimples” with top of mounting
surface and utilizing two fasteners in two of the three holes provided.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) as a
hanger and restrainer to support fire sprinkler systems. Meets and exceeds requirements
of NFPA 13, 13R and 13D.
Finish: Pre-Galvanized
Order By: Figure number and pipe size.
Patent # US2008/0129040A1
Install using a rechargeable electric drill fitted with a 5
/16\" (7.9mm) socket attachment with the special hex head self-tapping
screws provided. Install screws until they bottom out. Pipe can be “snapped“ into hanger before or after installation of
the screws to the mounting surface. “Thumb tab“ may be bent up to provide additional protection to the pipe, but is not
required for performance of the hanger / restrainer function.
Double Offset Single Offset
1.5\"
(38.1mm)
1.5\"
(38.1mm)
1.5\"
(38.1mm)
1.5\"
(38.1mm)
CPVC Max Hanger Approx.
Pipe size Spacing Wt./100
Part No. in. (mm) Ft. (m) lbs. (kg)
29-3
/4 3
/4\" (20) 5'-6\" (1.67) 18 (8.1)
29-1 1\" (25) 6'-0\" (1.83) 19 (8.6)
IPS Max. Hanger
Pipe Size Spacing
Part No. in. (mm) Ft. (m)
29-3
/4 3
/4\" (20) 1'-9\" (1.67)
29-1 1\" (25) 1'-10\" (1.83)
Reduced Spacing For IPS Pipe
Updated 5-18-21
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
40 Eaton B-Line series Fire Protection Solutions
Size Range: — 3
/8\"-16 Rod Attachment
Material: Steel
Function: Three recommended applications for this product:
• May be used as a branch line restraint for structural attachment to anchor bolt,
beam clamp, etc.
• May be used as an upper attachment with short hanger rod to omit seismic bracing.
• May be used in a pitched or sloped roof application, to meet requirements
of NFPA 13 (2010) 9.1.2.6.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) to
support up to 4\" (100mm) pipe.
Finish: Electro-Galvanized
Weight: Approx. Wt./100 - 13.3 Lbs. (6.0kg)
Order By: Part number
Patent: #7,887,248
B3184 - Offset Hanger for CPVC Plastic Pipe and IPS Pipe
TOLCO™ Fig. 75 - Swivel Attachment
Size Range: 3
/4\" (20mm) thru 2\" (32mm)
Material: Pre-Galvanized Steel
Function: Designed to be used as a hanger for CPVC piping or steel piping where the
“stand-off“ design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces
• The “Stand-Off“ design eliminates the need for wood block extension
• Can be installed on horizontal or vertical piping regardless of mounting
surface orientation
• Attaches easily to wood structure with two hex head self-threading
screws furnished with product
• cULus Listed as a hanger for fire sprinkler piping
Installation Note: When installed in wood structural members and threads from the
#10 x 1\" screws are exposed, use Fig. 27B speed nut to secure
Approvals: Underwriters Laboratory Listed in the USA (UL) and Canada (cUL) 3
/4\" (20mm)
thru 2\" (50mm) to support automatic fire sprinkler systems. May be installed into wood
using fasteners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D.
Order By: Part number and pipe size
H
L
Pipe Size
CPVC H L Max. Hanger Fastener Hex Approx.
Pipe Size Overall Overall Spacing Head Size Wt./100
Part No. in. (mm) in. (mm) in. (mm) ft. (m) in. (mm) Lbs. (kg)
B3184-3
/4 3
/4\" (20) 29
/16\" (65.1) 41
/4\" (107.9) 51
/2 (1.67) 5
/16\" (7.9) 9.0 (4.1)
B3184-1 1\" (25) 213/16\" (71.4) 41
/2\" (114.3) 6 (1,83) 5
/16\" (7.9) 10.0 (4.5)
B3184-11
/4 11
/4\" (32) 33
/16\" (81.0) 45
/8\" (117.5) 61
/2 (1.98) 5
/16\" (7.9) 12.0 (5.4)
B3184-11
/2 11
/2\" (40) 37
/16\" (87.3) 5\" (127.0) 7 (2.13) 5
/16\" (7.9) 12.0 (5.4)
B3184-2 2\" (50) 37
/8\" (98.4) 5\" (127.0) 8 (2.44) 5
/16\" (7.9) 15.0 (6.8)
Fig. 75 Swivel
Attachment
3
/8\" All Threaded Rod
Fig. 25 Surge Restrainer
Fig. 200
“Trimline\"
Adjustable
Band Hanger
May be used as a structural attachment
component of a branch line restraint
Fig. 78 All Steel
Ceiling Plate
Fig. 75 Swivel
Attachment
All Threaded Rod
May be used as a upper attachment with
short hanger rod to omit seismic bracing
B3100
Clevis Hanger
Fig. 75 Swivel
Attachment
All Threaded Rod
W-Beam
Pitched Roof
May be used with a pitched roof
application, to meet requirements of
NFPA 13 (2010-2016) Sec. 9.1.2.6.
Fig. 65XT Reversible
Beam Clamp
CPVC Clamps
CPVC Clamps
41 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
TOLCO Fig. 3000 - CPVC and steel sway brace attachment
Size Range: Pipe size to be braced: in 1\" (25mm) thru 3\" (80mm) except
65mm pipe sizes
Pipe size used for bracing 1\" (25mm) Schedule 40 IPS
Material: Steel
Function: For bracing CPVC and steel pipe against sway and seismic
disturbance. The pipe attachment component of a sway brace system:
Fig. 3000 is used in conjunction with a Fig. 900 Series fitting and joined
together with bracing pipe per NFPA 13, forming a complete sway brace
assembly.
Features: The Fig. 3000 is UL Listed as a sway brace for bracing 1\"
(25mm) through 3\" (80mm) CPVC and (IPS) steel sprinkler pipe, except
65mm diameter pipe. The unique design does not compress the
CPVC pipe, and the brace pipe to system pipe offset keeps the brace pipe
from leaving harmful residue and oils on the CPVC pipe. Field adjustable,
making critical pre-engineering of bracing pipe length unnecessary and
requires no threading of bracing pipe. Comes assembled and ready for
installation. Has a built-in visual verification of correct installation.
See the following installation note.
Installation Instructions: Slide the Fig. 3000 bracket over the brace
member. Place the Fig. 3000 clamp over the pipe being braced, align
the holes, and tighten the supplied bolts until the underside of the bolt
bottoms out against the Fig. 3000 clamp. The sway brace fitting is
intended to be used with any Tolco 900 series transitional or 800 series
structural attachments.
Note: Brace member may be over or under the braced pipe.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). UL Listed for the following sprinkler type pipes: Sch. 40
(and as brace member), Sch. 10, CPVC, DIN 2448, KSD 3562 (and as
brace member), KSD 3507.
Finish: Electro-Galvanized
Order By: Figure number and pipe size.
H
W
2\"
(50.8mm)
15
/8\"
(41.3mm)
CPVC or Steel H W Max. Design Load Approx.
Pipe Size Height Width UL Listed Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
3000-1 1\" (25) 37
/10\" (94.0) 43
/4\" (120.7) 700 (3.11) 120 (54.4)
3000-11
/4 11
/4\" (32) 4\" (101.6) 5\" (127.0) 700 (3.11) 129 (58.5)
3000-11
/2 11
/2\" (40) 43
/10\" (109.2) 51
/4\" (133.4) 700 (3.11) 136 (61.6)
3000-2 2\" (50) 47
/10\" (119.4) 61
/2\" (165.1) 700 (3.11) 204 (92.5)
3000-21
/2 21
/2\" (65) 54
/25\" (131.1) 7\" (177.8) 700 (3.11) 226 (102.5)
3000-3 3\" (80) 54
/5\" (147.3) 71
/2\" (190.5) 700 (3.11) 252 (114.3)
Brace
Member
Fig. 3000 Bracket
Fig. 3000 Clamp
Supplied Bolts
Pipe c c
a
b
brace member
braced
pipe
(steel or
CPVC)
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
42 Eaton B-Line series Fire Protection Solutions
CPVC Clamps
Fig. 74 - TOLCO Structural Attachment for Branch Line Restraint Assembly (UL Listed)
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are combined with products not provided by Eaton.
Size Range: 3
⁄8\" and 1
⁄2\" all threaded rod (ATR)
Material: Steel
Function: Structural attachment for restraint (sway brace) or hanger assembly
Features: The Fig. 74 has multiple sized fastener holes to accommodate multiple
types of fasteners for various types of structures (concrete, wood and steel) see table
below. Barrel rolls freely to allow installation angles from 0° to 90° from the mounting
surface. Multiple holes to allow various fasteners to attach to the structure. Larger
hole accommodates 3
⁄8\" (9.5mm) fastener, and smaller hole accomodates 1
⁄4\" (6.4mm)
or #10 fasteners. It is UL listed both as a restraint and as a hanger attachment for up
to 4\" (IPS) pipe size.
Installation Instructions: Install all threaded rod (ATR), (brace member) to TOLCO™
Fig. 74 structural attachment. Bottom out 1
/2\" ATR in barrel nut or thread 3
/8\" ATR
through to back side of barrel nut for proper engagement. Install Fig. 74 structural
attachment to the building structure. Follow fastener manufacturer and NFPA 13 guidelines
to install appropriate fastener for the structural type (i.e. concrete, wood, steel). For more
information visit our website for the most up to date instructions sheets.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
For FM Approval information refer to FM Approved page 43.
Finish: Zinc plated.
Order By: Figure number.
Structural Attachment for Branch Line Restraint
Fasteners to use with Fig 76 (Up to 2\" IPS pipe size) per NFPA 13
Structure Fastener Fastener Fastener NFPA 13 (2013 & 2016)
Type Type Diameter Embedment Reference
Concrete Through Bolt 3
/8\" N/A 9.1.3.10.1
Concrete Post Installed Various Various 9.1.3 - 9.1.3.8
Anchors
Steel Through Bolt 3
/8\" N/A 9.1.4.5.1
UL Listed Beam
Steel Beam Clamp 3
/8\" N/A Clamp with
Retaining Strap
Wood (1) 3/8\" lag screw 3
/8\" 2 1
/2\" 9.1.5.3.1
Wood (2) #10 wood screws #10 1\"
All Thread Rod Maximum Restraint Lengths
Rod Root Least Radius Maximum Unbraced Length L - (in.) Max. Horizontal Load @ 45° (lbs.)**
of Gyration
Size (in) Dia. (in) r (in) l/r=100 l/r=200 l/r=300 l/r=400† l/r=100 l/r=200 l/r=300 l/r=400†
3
/8 0.300 0.075 7 14 22 30 300 186 82 44
1
/2 0.404 0.101 10 20 30 40 300‡ 300‡ 152 85
† l/r = 400 NFPA 13 2010, Sec 9.3.6.1 (5) † l/r = 400 NFPA 13 2013 & 2016,Sec 9.3.6.1 (5) & NFPA (2016) TABLE 9.3.11.8(a)(b)(c)(d)(e)(f)
**Per NFPA 13 (2013) Table 9.3.5.11.8 (a)(b)(c), consult for maximum allowable load information on ATR.
‡Max load governed by Fig. 74/77 Max horizontal load.
UL listed maximum allowable loads (horizontal)
Product Sch. 10, Sch. 40, Dynaflow & CPVC
3
/8\" Rod (9.5mm) 1/2\" Rod (12.7mm)
Fig. 74 (sway brace) 300 lbs. (1.344 kN) 300 lbs. (1.344 kN)
Fig. 74 (hanger) 1500 lbs. (6.672 kN) 1500 lbs. (6.672 kN)
Updated 5-24-21
CPVC Clamps
43 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
Maximum Allowable Loads (FM Approved)
Part No. 30°-44° 45°-59° 60°-74° 75°-90°
3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod
lbs. lbs. lbs. lbs. lbs. lbs. lbs. lbs.
Fig. 74 790 790 810 810 620 620 680 680
Fig. 74 - TOLCO Structural Attachment for Sway Brace Assembly (FM Approved)
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Size Range: 3
⁄8\" and 1
⁄2\" all threaded rod (ATR)
Material: Steel
Function: Structural attachment for restraint (sway brace) assembly
Features: The Fig. 74 has multiple sized fastener holes to accommodate multiple
types of fasteners for various types of structures (concrete, wood and steel) see table
below. Barrel rolls freely to allow installation angles from 0° to 90° from the mounting
surface. Multiple holes to allow various fasteners to attach to the structure. Larger
hole accommodates 3
⁄8\" (9.5mm) fastener, and smaller hole accomodates 1
⁄4\" (6.4mm)
or #10 fasteners. It is UL listed both as a restraint and as a hanger attachment for up
to 4\" (IPS) pipe size.
Installation Instructions: Install all threaded rod (ATR), (brace member) to TOLCO™
Fig. 74 structural attachment. Bottom out 1
/2\" ATR in barrel nut or thread 3
/8\" ATR
through to back side of barrel nut for proper engagement. Install Fig. 74 structural
attachment to the building structure. Follow fastener manufacturer and NFPA 13 guidelines
to install appropriate fastener for the structural type (i.e. concrete, wood, steel). For more
information visit our website for the most up to date instructions sheets.
Approvals: Approved by FM.
For UL Listed information refer to UL Listed page 42.
Finish: Zinc plated.
Order By: Figure number.
Loads shown are axial ASD loads.
Fasteners to use with Fig 76 (Up to 2\" IPS pipe size) per NFPA 13
Structure Fastener Fastener Fastener NFPA 13 (2013 & 2016)
Type Type Diameter Embedment Reference
Concrete Through Bolt 3
/8\" N/A 9.1.3.10.1
Concrete Post Installed Various Various 9.1.3 - 9.1.3.8
Anchors
Steel Through Bolt 3
/8\" N/A 9.1.4.5.1
FM Approved
Steel Beam Clamp 3
/8\" N/A Beam Clamp with
Retaining Strap
Wood (1) 3
/8\" lag screw 3
/8\" 2 1
/2\" 9.1.5.3.1
Wood (2) #10 wood #10 1\"
screws
All Thread Rod Maximum Restraint Lengths
Rod Root Least Radius Maximum Unbraced Length L - (in.) Max. Horizontal Load @ 45° (lbs.)**
of Gyration
Size (in) Dia. (in) r (in) l/r=100 l/r=200 l/r=300 l/r=400† l/r=100 l/r=200 l/r=300 l/r=400†
3
/8 0.300 0.075 7 14 22 30 300 186 82 44
1
/2 0.404 0.101 10 20 30 40 300‡ 300‡ 152 85
† l/r = 400 NFPA 13 2010, Sec 9.3.6.1 (5) † l/r = 400 NFPA 13 2013 & 2016,Sec 9.3.6.1 (5) & NFPA (2016) TABLE 9.3.11.8(a)(b)(c)(d)(e)(f)
**Per NFPA 13 (2013) Table 9.3.5.11.8 (a)(b)(c), consult for maximum allowable load information on ATR.
‡Max load governed by Fig. 74/77 Max horizontal load.
Structural Attachment for Restraint (Sway Brace)
Updated 5-24-21
CPVC Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
44 Eaton B-Line series Fire Protection Solutions
CPVC Clamps
Size Range: 3
⁄8\" and 1
⁄2\" all threaded rod (ATR)
Material: Steel
Function: System attachment for restraint (sway brace) assembly
Features: The Fig. 77 is UL Listed to be used with both (IPS) steel and CPVC fire
sprinkler pipe, in 1\" through 2\" diameters. It fits multiple rod diameters allowing for
field adjustment if longer brace material is needed. Its sturdy break-off bolt will not
strip and verifies proper installation. Its snap on design has many advantages. It can
be installed with one-hand, can easily position the brace all thread rod over the top
of the pipe being braced or underneath the pipe being braced to accommodate the
desired brace angle. It can be fixed in place or moved to a new location by sliding
along the pipe or snapping on or off and relocating. An entire prefabricated assembly
(Fig. 74 & 77 joined with ATR) can be pre-assembled to save time and labor and later
be field installed and adjusted to fit.
Installation Instructions: Install TOLCO™ Fig. 77 system attachment to sprinkler
pipe branch line to be restrained. You can position with the rod engagement either
above or below the sprinkler pipe. Rod must extend a min. of 1\" (25.4) past the
edge of the Fig. 77. The attachment can be slid along the pipe to position close to
where the Fig. 74 structural attachment will be fastened to the structure. The snap
on design allows maximum adjustability during this stage of the installation process.
Engage ATR (previously attached to the Fig. 74 structural attachment to the rod
engagement portion of the Fig. 77 system attachment. Tighten set bolt on Fig. 77
system attachment until head breaks off verifying proper installation torque. For
more information visit our website for the most up to date instructions sheets.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
For FM Approved information refer to FM Approved page 45.
Finish: Pre-Galvanized.
Order By: Figure number and pipe size.
TOLCO Fig. 77 - System Piping Attachment for Restraint Assembly (UL Listed)
For CPVC & Steel Pipe
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Pipe Attachment for Branch Line Restraint
US Patent No. 9,797,527
Max.Design Loads (UL Listed)
Part No. Pipe Size 3
/8\" Rod 1
/2\" Rod
in. (mm) lbs. (kN) lbs. (kN)
77-1 1 (25)
77-11
/4 11
/4 (32) 300 (1.33) 300 (1.33)
77-11
/2 11
/2 (40)
77-2 2 (50)
* These loads apply to IPS steel, Sch.10, Sch. 40, engineered lightwall piping, and
CPVC plastic pipe. Loads shown are axial ASD loads.
§ All other trademarks are property of their respective owners.
All Thread Rod Maximum Restraint Lengths
Rod Root Least Radius Maximum Unbraced Length L - (in.) Max. Horizontal Load @ 45° (lbs.)**
Size Dia. of Gyration
r l/r=100 l/r=200 l/r=300 l/r=400† l/r=100 l/r=200 l/r=300 l/r=400†
in. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN)
3
/8-16 0.300 (7.6) 0.075 (1.9) 7 (177.8) 14 (355.6) 22 (558.8) 30 (763.0) 300 (1.33) 186 (0.82) 82 (0.36) 44 (0.19)
1
/2-13 0.404 (10.2) 0.101 (2.5) 10 (254.0) 20 (508.0) 30 (762.0) 40 (1016.0) 300‡ (1.33)‡ 300‡ (1.33)‡ 152 (0.67) 85 (0.38)
† l/r = 400 NFPA 13 2010, Sec 9.3.6.1 (5) † l/r = 400 NFPA 13 2013 & 2016,Sec 9.3.6.1 (5) & NFPA (2016) TABLE 9.3.11.8(a)(b)(c)(d)(e)(f)
**Per NFPA 13 (2013) Table 9.3.5.11.8 (a)(b)(c), consult for maximum allowable load information on ATR.
‡Max load governed by Fig. 74/77 Max horizontal load.
Updated 5-24-21
CPVC Clamps
45 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
CPVC Clamps
Size Range: 3
⁄8\" and 1
⁄2\" all threaded rod (ATR)
Material: Steel
Function: System attachment for restraint
Features: The Fig. 77 is to be used with both (IPS) steel and CPVC fire sprinkler
pipe, in 1\" through 2\" diameters. It fits multiple rod diameters allowing for field
adjustment if longer brace material is needed. Its sturdy break-off bolt will not strip
and verifies proper installation. Its snap on design has many advantages. It can be
installed with one-hand, can easily position the brace all thread rod over the top of the
pipe being braced or underneath the pipe being braced to accommodate the desired
brace angle. It can be fixed in place or moved to a new location by sliding along the
pipe or snapping on or off and relocating. An entire prefabricated assembly (Fig. 74
& 77 joined with ATR) can be pre-assembled to save time and labor and later be field
installed and adjusted to fit.
Installation Instructions: Install TOLCO™ Fig. 77 system attachment to sprinkler
pipe branch line to be restrained. It can be positioned with the rod engagement either
above or below the sprinkler pipe. Rod must extend a min. of 1\" past the edge of
the Fig. 77. The attachment can be slid along the pipe to position close to where the
Fig. 74 structural attachment will be fastened to the structure. The snap on design
allows maximum adjustability during this stage of the installation process. Engage
ATR (previously attached to the Fig. 74 structural attachment to the rod engagement
portion of the Fig. 77 system attachment. Tighten set bolt on Fig. 77 system
attachment until head breaks off verifying proper installation torque. For more
information visit our website for the most up to date instructions sheets.
Approvals: Approved by FM.
For UL Listed information refer to UL Listed page 44.
Finish: Pre-Galvanized.
Order By: Figure number and pipe size.
TOLCO Fig. 77 - System Piping Attachment for Sway Brace Assembly (FM Approved)
For CPVC & Steel Pipe
Maximum Allowable Loads (FM Approved)*
Part No. Pipe Size 30°-44° 45°-59° 60°-74° 75°-90°
3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod 3
/8\" Rod 1
/2\" Rod
in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN)
77-1 1 (25) 140 (0.62) 160 (0.71) 200 (0.89) 230 (1.02) 250 (1.11) 280 (1.24) 280 (1.24) 320 (1.42)
77-11
/4 11
/4 (32) 140 (0.62) 170 (0.75) 200 (0.89) 250 (1.11) 250 (1.11) 300 (1.33) 280 (1.24) 340 (1.51)
77-11
/2 11
/2 (40) 130 (0.58) 160 (0.62) 190 (0.84) 230 (1.02) 230 (1.02) 280 (1.24) 260 (1.15) 320 (1.42)
77-2 2 (50) 120 (0.53) 150 (0.67) 170 (0.75) 210 (0.93) 210 (0.93) 260 (1.15) 240 (1.07) 290 (1.29)
* Loads shown are axial ASD loads.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
All Thread Rod Maximum Restraint Lengths
Rod Root Least Radius Maximum Unbraced Length L - (in.) Max. Horizontal Load @ 45° (lbs.)**
Size Dia. of Gyration r l/r=100 l/r=200 l/r=300D l/r=400†D l/r=100 l/r=200 l/r=300D l/r=400†D
in. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN)
3
/8-16 0.300 (7.6) 0.075 (1.9) 7 (177.8) 14 (355.6) 22 (558.8) 30 (763.0) 300 (1.33) 186 (0.82) 82 (0.36) 44 (0.19)
1
/2-13 0.404 (10.2) 0.101 (2.5) 10 (254.0) 20 (508.0) 30 (762.0) 40 (1016.0) 300‡ (1.33)‡ 300‡ (1.33)‡ 152 (0.67) 85 (0.38)
† l/r = 400 NFPA 13 2010, Sec 9.3.6.1 (5) † l/r = 400 NFPA 13 2013 & 2016,Sec 9.3.6.1 (5) & NFPA (2016) TABLE 9.3.11.8(a)(b)(c)(d)(e)(f) D l/r = 300 for bracing
**Per NFPA 13 (2013) Table 9.3.5.11.8 (a)(b)(c), consult for maximum allowable load information on ATR. D l/r = 400 for restraint
‡Max load governed by Fig. 74/77 Max horizontal load.
Pipe Attachment for Restraint (Sway Brace)
US Patent No. 9,797,527
Updated 5-24-21
Pipe Supports
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
46 Eaton B-Line series Fire Protection Solutions
Size Range: 3
/4\" (20mm) thru 6\" (150mm) pipe
Material: Steel
Function: Designed as an unthreaded base stand for pipe
supports B3090, B3094, B3095, B3096, B3097 and B3098.
Finish: Plain or Electro-Galvanized. Contact customer
service for alternative finishes and materials.
Order By: Figure number, height and finish.
B3088 - Base Stand
*Based on a height of 18\" (457.2mm).
H
** Specify 4 Holes
Height
Plate Size
Stand Pipe Size
A
A
Plate Size Stand Pipe Size A Dia. H
Part No. in. (mm) in. (mm) in. (mm) in. (mm)
B3088-3
/4 1
/4\" x 6\" x 6\" (6.3 x 152.4 x 152.4) 3
/4\" (20) 7
/8\" (22.2) 3
/4\" (14.3)
B3088-1 1
/4\" x 6\" x 6\" (6.3 x 152.4 x 152.4) 1\" (25) 7
/8\" (22.2) 3
/4\" (14.3)
B3088-11
/4 1
/4\" x 6\" x 6\" (6.3 x 152.4 x 152.4) 11
/4\" (32) 7
/8\" (22.2) 3
/4\" (14.3)
B3088-11
/2 1
/4\" x 6\" x 6\" (6.3 x 152.4 x 152.4) 11
/2\" (40) 7
/8\" (22.2) 3
/4\" (14.3)
B3088-2 1
/4\" x 6\" x 6\" (6.3 x 152.4 x 152.4) 2\" (50) 7
/8\" (22.2) 3
/4\" (14.3)
B3088-21
/2 3
/8\" x 8\" x 8\" (9.5 x 203.2 x 203.2) 21
/2\" (65) 11
/4\" (31.7) 13/16\" (14.3)
B3088-3 3
/8\" x 12\" x 12\" (9.5 x 203.2 x 203.2) 3\" (80) 11
/2\" (38.1) 13/16\" (20.6)
B3088-4 1
/2\" x 12\" x 12\" (12.7 x 304.8 x 304.8) 4\" (100) 11
/2\" (38.1) 15/16\" (23.8)
B3088-6 1
/2\" x 18\" x 18\" (12.7 x 304.8 x 304.8) 6\" (150) 11
/2\" (38.1) 11
/8\" (28.6)
Approx. Wt./100*
Part No. Lbs. (kg)
B3088-3
/4 420 (190.5)
B3088-1 480 (216.0)
B3088-11
/4 590 (267.6)
B3088-11
/2 655 (297.1)
B3088-2 1211 (549.3)
B3088-21
/2 2376 (1077.7)
B3088-3 3137 (1422.9)
B3088-4 4338 (1967.7)
B3088-6 7378 (3346.6)
**Height from top of pipe
to bottom of plate.
Note: See Pipe Hangers & Supports catalog for attachments
Pipe Supports
Pipe Supports
47 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3088T - Threaded Base Stand
Note: Match B3088T part number with dimension ‘D’ from B3092, and B3093 charts.
Plate Size Stand Pipe Size A Dia. H TL
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3088T-1 1
/4\"x 6\"x 6\" (6.3 x 152.4 x 152.4) 1\" (25) 7
/8\" (22.2) 3
/4\" (19.0) 11
/2\" (38.1)
B3088T-11
/4 1
/4\"x 6\"x 6\" (6.3 x 152.4 x 152.4) 11
/4\" (32) 7
/8\" (22.2) 3
/4\" (19.0) 11
/2\" (38.1)
B3088T-11
/2 1
/4\"x 6\"x 6\" (6.3 x 152.4 x 152.4) 11
/2\" (40) 7
/8\" (22.2) 3
/4\" (19.0) 11
/2\" (38.1)
B3088T-2 1
/4\"x 6\"x 6\" (6.3 x 152.4 x 152.4) 2\" (50) 7
/8\" (22.2) 3
/4\" (19.0) 11
/2\" (38.1)
B3088T-21
/2 3
/8\"x 8\"x 8\" (9.5 x 203.2 x 203.2) 21
/2\" (65) 11
/4\" (31.7) 13/16\" (20.6) 11
/2\" (38.1)
B3088T-3 3
/8\"x 12\"x 12\" (9.5 x 304.8 x 304.8) 3\" (80) 11
/2\" (38.1) 13/16\" (20.6) 11
/2\" (38.1)
B3088T-4 1
/2\"x 12\"x 12\" (12.7 x 304.8 x 304.8) 4\" (100) 11
/2\" (38.1) 15/16\" (23.8) 2\" (50.8)
OPM
H
4 Holes
Plate Size
Stand Pipe Size
TL
Thread Length
A
A
**Specify
Height
**Height from top
of pipe to bottom of
plate.
Size Range: 1\" (25mm) thru 6\" (150mm) pipe
Material: Steel
Function: Designed as a threaded base stand where vertical adjustment
is required for pipe supports B3089, B3092, and B3093.
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, height and finish.
Approvals: Included in our Seismic Engineering Guidelines approved by
the State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating to
OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
Refer to pages 15.1 - 15.3B in Seismic Engineering Guidelines OPM-0052-13.
*Based on a height of 18\" (457.2mm).
Approx. Wt./100*
Part No. Lbs. (kg)
B3088T-1 495 (224.5)
B3088T-11
/4 583 (264.4)
B3088T-11
/2 649 (294.4)
B3088T-2 785 (356.1)
B3088T-21
/2 1524 (691.3)
B3088T-3 2624 (1190.2)
B3088T-4 3594 (1630.2)
Note: See Pipe Hangers & Supports catalog for attachments
Pipe Supports
Pipe Supports
Pipe Supports
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
48 Eaton B-Line series Fire Protection Solutions
B3088S - Seismic Base Stand
H
4 Holes **Specify
Height
Plate Size
Stand Pipe Size
A
A
**Height from top of pipe
to bottom of plate.
Size Range: 3
/4\" (20mm) thru 4\" (100mm) pipe
Material: Steel
Function: Designed as an unthreaded base stand for
pipe supports, B3090, B3094, B3095, B3096, B3097 and
B3098, to meet requirements of 12X anchor diameter
hole spacing for seismic applications. The standard
B3088-3 & B3088-6 already meet this requirement.
Finish: Plain or Electro-Galvanized. Contact customer
service for alternative finishes and materials.
Order By: Figure number, height and finish.
*Based on a height of 18\" (457.2mm).
Plate Size Stand Pipe Size A Dia. H
Part No. in. (mm) in. (mm) in. (mm) in. (mm)
B3088S-3
/4 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 3
/4\" (20) 1\" (25.4) 9
/16\" (14.3)
B3088S-1 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 1\" (25) 1\" (25.4) 9
/16\" (14.3)
B3088S-11
/4 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 11
/4\" (20) 1\" (25.4) 9
/16\" (14.3)
B3088S-11
/2 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 11
/2\" (32) 1\" (25.4) 9
/16\" (14.3)
B3088S-2 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 2\" (50) 1\" (25.4) 9
/16\" (14.3)
B3088S-21
/2 3
/8\" x 81
/2\" x 81
/2\" (9.5 x 215.9 x 215.9) 21
/2\" (65) 11
/4\" (31.7) 9
/16\" (14.3)
B3088S-4 1
/2\" x 131
/2\" x 131
/2\" (12.7 x 342.9 x 342.9) 4\" (100) 11
/2\" (38.1) 15/16\" (23.8)
Approx. Wt./100*
Part No. Lbs. (kg)
B3088-3
/4 618 (280.3)
B3088-1 708 (321.1)
B3088-11
/4 798 (362.0)
B3088-11
/2 858 (389.2)
B3088-2 993 (450.4)
B3088-21
/2 1638 (743.0)
B3088-4 4202 (1906.0)
Note: See Pipe Hangers & Supports catalog for attachments