Pipe Supports
Pipe Supports
49 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3088ST - Threaded Seismic Base Stand
Size Range: 1\" (25mm) thru 4\" (100mm) pipe
Material: Steel
Function: Designed as a threaded base stand where vertical
adjustment is required for pipe supports B3089, B3092, and
B3093, to meet requirements of 12X anchor diameter hole
spacing for seismic applications. The standard B3088-3 &
B3088-6 already meet this requirement.
Finish: Plain or Electro-Galvanized. Contact customer service
for alternative finishes and materials.
Order By: Figure number, height and finish.
H
4 Holes
Plate Size
Stand Pipe Size
TL
Thread Length
A
A
**Specify
Height
**Height from
top of pipe to
bottom of plate.
Plate Size Stand Pipe Size A Dia. H TL
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3088ST-1 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 1\" (25) 1\" (25.4) 9
/16\" (14.3) 11
/2\" (38.1)
B3088ST-11
/4 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 11
/4\" (32) 1\" (25.4) 9
/16\" (14.3) 11
/2\" (38.1)
B3088ST-11
/2 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 11
/2\" (40) 1\" (25.4) 9
/16\" (14.3) 11
/2\" (38.1)
B3088ST-2 1
/4\" x 8\" x 8\" (6.3 x 203.2 x 203.2) 2\" (50) 1\" (25.4) 9
/16\" (14.3) 11
/2\" (38.1)
B3088ST-21
/2 3
/8\" x 81
/2\" x 81
/2\" (9.5 x 215.9 x 215.9) 21
/2\" (65) 11
/4\" (31.7) 9
/16\" (14.3) 11
/2\" (38.1)
B3088ST-4 1
/2\" x 131
/2\" x 131
/2\" (12.7 x 342.9 x 342.9) 4\" (100) 11
/2\" (38.1) 15/16\" (23.8) 2\" (50.8)
*Based on a height of 18\" (457.2mm).
Approx. Wt./100*
Part No. Lbs. (kg)
B3088ST-1 708 (321.1)
B3088ST-11
/4 798 (362.0)
B3088ST-11
/2 858 (389.2)
B3088ST-2 993 (450.4)
B3088ST-21
/2 1638 (743.0)
B3088ST-4 4202 (1906.0)
Note: Match B3088TS part number with dimension ‘D’ from B3092, and B3093 charts.
Pipe Supports
Pipe Supports
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
50 Eaton B-Line series Fire Protection Solutions
Size Range: 3
/4\" (20mm) thru 36\" (900mm) pipe
Material: Steel with cast iron reducer
Function: Designed to support horizontal pipe from floor
stanchion where vertical adjustment is required. U-bolt
and hex nuts are provided to hold pipe securely to saddle.
To complete floor stanchion, use with B3088T (page 42)
threaded pipe stand.
Approvals: Conforms to Federal Specification
WW-H-171E & A-A-1192A and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 37.
Finish: Plain. Contact customer service for alternative
finishes and materials.
Order By: Figure number and finish
Notes: Order with B3088T for complete stanchion support.
4\" (100mm) thru 12\" (300mm) fits both steel and ductile iron
pipe. For other ductile iron pipe sizes specify B3092DI - size.
3\" (80mm) Ductile Iron uses B3092-31
/2
E
U-Bolt Dia.
Steel Size
Gussets on sizes
B3092-8 and larger.
A
Schedule 40 Pipe Size
B
Center of pipe to
bottom of pipe reducer.
C
Center of pipe to
bottom lip of support.
D
Nominal pipe size of base stand -
not included.
E
U-Bolt Dia.
A
D
C
B
Pipe Size Maximum O.D. of Pipe A Minimum B Maximum
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3092-3
/4 3
/4\" (19) 13
/8\" (34.9) 3
/4\" (19) 53
/4\" (146.0) 101
/4\" (260.3)
B3092-1 1\" (25) 13
/8\" (34.9) 3
/4\" (19) 529/32\" (150.0) 1013/32\" (264.3)
B3092-11
/4 11
/4\" (32) 111/16\" (42.9) 3
/4\" (19) 65
/64\" (154.4) 1037/64\" (268.7)
B3092-11
/2 11
/2\" (38) 2\" (50.8) 3
/4\" (19) 61
/4\" (158.7) 103
/4\" (273.0)
B3092-2 2\" (50) 27
/16\" (61.9) 3
/4\" (19) 67
/16\" (163.5) 1015/16\" (277.8)
B3092-21
/2 21
/2\" (65) 27
/8\" (73.0) 11
/2\" (40) 67
/8\" (174.6) 113
/8\" (288.9)
B3092-3 3\" (80) 31
/2\" (88.9) 11
/2\" (40) 73
/16\" (182.6) 1111/16\" (296.9)
B3092-31
/2 31
/2\" (90) 4\" (101.6) 11
/2\" (40) 77
/16\" (188.9) 1115/16\" (303.2)
B3092-4 4\" (100) 47
/8\" (123.8) 21
/2\" (65) 713/16\" (198.4) 125
/16\" (312.7)
B3092-5 5\" (125) 55
/8\" (142.9) 21
/2\" (65) 89
/32\" (210.3) 1225/32\" (324.6)
B3092-6 6\" (150) 629/32\" (175.4) 21
/2\" (65) 91
/16\" (230.2) 139
/16\" (344.5)
B3092-8 8\" (200) 91
/8\" (231.8) 21
/2\" (65) 101
/2\" (266.7) 15\" (381.0)
B3092 - Adjustable Pipe Saddle Support with Yoke
C D (Not Supplied) E Saddle Steel Size Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3092-3
/4 2\" (50.8) 11
/2\" (38) 1
/4\" (6.4) 1
/4\" x 11
/2\" (6.3 x 38.1) 247 (112.0)
B3092-1 25
/32\" (54.8) 11
/2\" (38) 1
/4\" (6.4) 1
/4\" x 11
/2\" (6.3 x 38.1) 257 (116.6)
B3092-11
/4 221/64\" (59.1) 11
/2\" (38) 3
/8\" (9.5) 1
/4\" x 2\" (6.3 x 50.8) 289 (131.1)
B3092-11
/2 21
/2\" (63.5) 11
/2\" (38) 3
/8\" (9.5) 1
/4\" x 2\" (6.3 x 50.8) 306 (138.8)
B3092-2 211/16\" (68.3) 11
/2\" (38) 3
/8\" (9.5) 1
/4\" x 2\" (6.3 x 50.8) 326 (147.9)
B3092-21
/2 31
/8\" (79.4) 21
/2\" (65) 1
/2\" (12.7) 1
/4\" x 3\" (6.3 x 76.2) 651 (295.3)
B3092-3 37
/16\" (87.3) 21
/2\" (65) 1
/2\" (12.7) 1
/4\" x 3\" (6.3 x 76.2) 716 (324.8)
B3092-31
/2 311/16\" (93.7) 21
/2\" (65) 1
/2\" (12.7) 1
/4\" x 3\" (6.3 x 76.2) 717 (325.2)
B3092-4 41
/4\" (107.9) 3\" (80) 1
/2\" (12.7) 3
/8\" x 31
/2\" (9.5 x 88.9) 1286 (583.3)
B3092-5 49
/16\" (115.9) 3\" (80) 1
/2\" (12.7) 3
/8\" x 31
/2\" (9.5 x 88.9) 1321 (599.2)
B3092-6 51
/2\" (139.7) 3\" (80) 5
/8\" (15.9) 1
/2\" x 31
/2\" (12.7 x 88.9) 1595 (723.5)
B3092-8 7\" (177.8) 3\" (80) 5
/8\" (15.9) 1
/2\" x 31
/2\" (12.7 x 88.9) 1815 (823.3)
Pipe Supports
Pipe Supports
51 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 1\" (25mm) thru 36\" (900mm) pipe
Material: Steel with cast iron reducer
Function: Designed to support horizontal pipe from
floor stanchion where vertical adjustment is required.
U-bolt and hex nuts are provided to hold pipe securely
to saddle. To complete floor stanchion, use with
B3088T (page 42) threaded pipe stand.
Approvals: Conforms to Federal Specification
WW-H-171E & A-A-1192A, Type 38 and
Manufacturers Standardization Society ANSI/MSS
SP-69 & SP-58, Type 37.
Finish: Plain. Contact customer service for alternative
finishes and materials.
Order By: Figure number and finish
Note: Order with B3088T for complete stanchion
support.
B3093 - Adjustable Pipe Saddle Support
Steel Size
Gussets on sizes
B3093-8 and larger.
A
D
C
B
Pipe Size Maximum O.D. of Pipe A Minimum B Maximum C
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3093-1 1\" (25) 15
/16\" (33.3) 3
/4\" (20) 521/32\" (143.6) 105
/32\" (257.9) 129/32\" (48.4)
B3093-11
/4 11
/4\" (32) 111/16\" (42.9) 3
/4\" (20) 553/64\" (148.0) 1021/64\" (2262.3) 25
/64\" (52.8)
B3093-11
/2 11
/2\" (40) 129/32\" (48.4) 3
/4\" (20) 6\" (152.4) 101
/2\" (266.7) 21
/4\" (58.1)
B3093-2 2\" (50) 23
/8\" (60.3) 3
/4\" (20) 63
/16\" (157.2) 1011/16\" (271.5) 27
/16\" (61.9)
B3093-21
/2 21
/2\" (65) 27
/8\" (73.0) 11
/2\" (40) 65
/16\" (160.3) 1013/16\" (274.6) 29
/16\" (65.1)
B3093-3 3\" (80) 31
/2\" (88.9) 11
/2\" (40) 65
/8\" (168.3) 111
/8\" (282.6) 27
/8\" (73.0)
B3093-31
/2 31
/2\" (90) 4\" (101.6) 11
/2\" (40) 67
/8\" (174.6) 113
/8\" (288.9) 31
/8\" (79.4)
B3093-4 4\" (100) 47
/8\" (123.8) 21
/2\" (65) 71
/4\" (184.1) 113
/4\" (298.4) 31
/2\" (88.9)
B3093-5 5\" (125) 59
/16\" (141.3) 21
/2\" (65) 725/32\" (197.6) 129
/32\" (311.9) 41
/32\" (102.4)
B3093-6 6\" (150) 7\" (177.8) 21
/2\" (65) 87
/16\" (214.3) 1215/16\" (328.6) 411/16\" (119.1)
B3093-8 8\" (200) 91
/8\" (231.8) 21
/2\" (65) 101
/4\" (260.3) 143
/4\" (374.6) 61
/2\" (165.1)
Note:
4\" (100) thru 12\" (300) fits both steel and ductile iron pipe.
For other ductile iron pipe sizes specify B3093DI - size.
3\" (80) Ductile Iron uses B3093-31
/2
D (Base Stand Approx. Wt./100
Not Supplied) Saddle Steel Size Complete Saddle Only
Part No. in. (mm) in. (mm) Lbs. (kg) Lbs. (kg)
B3093-1 11
/2\" (40) 1
/4\" x 13
/4\" (6.3 x 44.4) 189 (85.7) 49 (22.2)
B3093-11
/4 11
/2\" (40) 1
/4\" x 13
/4\" (6.3 x 44.4) 221 (100.2) 81 (36.7)
B3093-11
/2 11
/2\" (40) 1
/4\" x 13
/4\" (6.3 x 44.4) 228 (103.4) 88 (39.9)
B3093-2 11
/2\" (40) 1
/4\" x 13
/4\" (6.3 x 44.4) 234 (106.1) 94 (42.6)
B3093-21
/2 21
/2\" (65) 1
/4\" x 3\" (6.3 x 76.2) 567 (257.2) 167 (75.8)
B3093-3 21
/2\" (65) 1
/4\" x 3\" (6.3 x 76.2) 576 (261.3) 176 (79.9)
B3093-31
/2 21
/2\" (65) 1
/4\" x 3\" (6.3 x 76.2) 588 (266.7) 188 (85.3)
B3093-4 3\" (80) 1
/4\" x 4\" (6.3 x 101.6) 1064 (482.6) 364 (165.1)
B3093-5 3\" (80) 1
/4\" x 4\" (6.3 x 101.6) 1081 (490.3) 381 (172.8)
B3093-6 3\" (80) 3
/8\" x 4\" (9.5 x 101.6) 1234 (559.7) 534 (242.2)
B3093-8 3\" (80) 3
/8\" x 4\" (9.5 x 101.6) 1496 (678.6) 796 (361.1)
A
Schedule 40 Pipe Size
B
Center of pipe to bottom of pipe
reducer.
C
Center of pipe to bottom lip of
support.
D
Nominal pipe size of base stand
- not included.
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
52 Eaton B-Line series Fire Protection Solutions
Size Range: One size accommodates all Fig. 900 Series sway brace
attachments. Fits from 3
/8\" (9.4mm) to 7
/8\" (22.2mm) thick steel structure.
For thicknesses less than 3
/8\" (9.4mm) refer to Fig. 825 and Fig. 825A.
Material: Steel
Function: To attach sway bracing and/ot hangers to various types of steel
structural members.
Features: Permits secure non-friction connection without drilling or welding.
Unique design allows offset placement on wide flange beam, C-channel, open
web, welded steel trusses, etc. Secures brace to structure either across or
along the beam. Break-off set bolts allow for visual verification of proper
installation torque.
Approvals: Underwriters Laboratories Listed in the USA and Canada (cULus).
Included in our Seismic Engineering Guidelines approved by the State of California
Office of Statewide Health Planning and Development (OSHPD). For additional
load, spacing and placement information relating to OSHPD projects, please refer
to our Seismic Engineering Guidelines, OPM-0052-13.
For FM Approval information refer to FM Approved page 53.
Installation Instructions: The Fig. 828 is the structural attachment component
of a longitudinal or lateral sway brace assembly. It is intended to be combined
with a TOLCO transitional attachment, “bracing pipe\" and a TOLCO “braced pipe”
attachment to form a complete bracing assembly. NFPA 13 guidelines should
be followed.
To Install: Slide the Fig. 828 on the flange of the beam, truss, or girder. Be
sure the attachment is fully engaged to the rear of the opening. Tighten the
cone point set screws until the heads break off. Remove the flange nut from
the carriage bolt. Install a TOLCO swivel fitting (Fig, 909, 910, 980, *986).
Use flange nut to secure the swivel fitting.
*Not UL listed when used in combination with Fig. 986
Finish: Plain or Electro-Galvanized
Approx. Weight/100: 341 Lbs. (154.7 kg)
Order By: Figure number and finish
Patent Pending
Note: Retaining strap not required.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 828 - universal sway brace attachment to steel (UL listed)
OPM
Beam, truss
or girder
May pivot
in any
direction
Fig. 828
Fig. 828
Flange
thickness
Maximum
UL Rated load
.375\" – .499\" 1090 lbs. (4.84kN)
.500\" – .875\" 1370 lbs. (6.09kN)
Set Screws
and 1
/2\" Attachment
Bolt and Nut
Included
Updated 4-6-21
Seismic Bracing
Seismic Bracing
53 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: One size accommodates all Fig. 900 Series sway brace attachments. Fits
from 3
/8\" (9.4mm) to 7
/8\" (22.2mm) thick steel structure. For thicknesses less than 3
/8\" (9.4mm)
refer to Fig. 825.
Material: Steel
Function: To attach sway bracing and/or hangers to various types of steel structural
members.
Features: Permits secure non-friction connection without drilling or welding. Unique
design allows offset placement on wide flange beam, C-channel, open web,
welded steel trusses, etc. Secures brace to structure either across or along the beam.
Break-off set bolts allow for visual verification of proper installation torque.
Approvals: Factory Mutual Approved (FM). Included in our Seismic Engineering
Guidelines approved by the State of California Office of Statewide Health Planning and
Development (OSHPD). For additional load, spacing and placement information relating to
OSHPD projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13.
For UL Listed information refer to UL Listed page 52.
Installation Instructions: The Fig. 828 is the structural attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with a TOLCO™
transitional attachment, “bracing pipe” and a TOLCO “braced pipe” attachment to form a
complete bracing assembly. NFPA 13 or FM guidelines should be followed.
To Install: Slide the Fig. 828 on the flange of the beam, truss, or girder. Be sure the
attachment is fully engaged to the rear of the opening. Tighten the cone point set screws
until the heads break off. Remove the flange nut from the carriage bolt. Install a TOLCO
swivel fitting (Fig, 909, 910, 980, *986). Use flange nut to secure the swivel fitting.
*Not UL listed when used in combination with Fig. 986
Finish: Plain or Electro-Galvanized
Approx. Weight/100: 341 Lbs. (154.7kg)
Order By: Figure number and finish
Patent Pending
Designed to meet or exceed requirements of FM DS 2-8.
Note: Retaining strap not required.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 828 - Universal sway brace attachment to steel (FM approved)
OPM
Beam, truss
or girder
May pivot
in any
direction
Fig. 828
Fig. 828
Set Screws
and 1
/2\" Attachment
Bolt and Nut
Included
Updated 4-6-21
FM Approved Allowable Horizontal Load
With Brace Perpendicular To Beam
Brace Angle (degrees from vertical)
30°-44° 45°-59° 60°-74° 75°-90°
980 2220 3340 4040
(4.350kN) (9.780kN) (14.850kN) (17.970kN)
FM Approved Allowable Horizontal Load
With Brace Parallel To Beam
Brace Angle (degrees from vertical)
30°-44° 45°-59° 60°-74° 75°-90°
820 1270 1490 1650
(3.640kN) (5.640kN) (6.620kN) (7.330kN)
FM Approved design loads are based on ASD
design method.
Size Range: One size accommodates all
Fig. 900 Series sway brace attachments.
Material: Steel
Function: To attach sway bracing and hanger assemblies
to steel members.
Features: This product’s design incorporates a concentric
attachment point which is critical to the performance of
structural seismic connections. NFPA 13 indicates the
importance of concentric loading of connections and
fasteners. Permits secure non-friction connection without
drilling or welding. Unique design reinforces point of
connection to joist. Break off head set bolt design assures verification of proper
installation torque (min. 31 ft.-lbs.).
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
UL listed with Fig. 909, 910, and 980 series attachments and the following brace
member type pipes: Sch. 40, KSD 3562. Included in our Seismic Engineering
Guidelines approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13. For FM Approval information refer to FM Approved page 55.
Installation Instructions: Fig. 825 is the structural attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with
a TOLCO™ transitional attachment, “bracing pipe” and a TOLCO “braced pipe”
attachment, to form a complete bracing assembly. NFPA 13 guidelines should be
followed.
To Install: Place the Fig. 825 on the steel beam, tighten the cone point set bolts
until heads break off. Attach other TOLCO transitional attachment fitting, Fig. 980,
910, 909, or any other TOLCO approved
transitional fitting. Transitional fitting
attachment can pivot for adjustment to
proper brace angle.
Finish: Plain, Electro-Galvanized and HDG
Approx. Wt./100: 247.5 Lbs. (112.2kg)
Order By: Figure number and finish
US Patent #6,098,942
Canada Patent #2,286,659
Retaining strap not required.
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
54 Eaton B-Line series Fire Protection Solutions
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 825 - bar joist sway brace attachment to steel (UL listed)
Front View
May pivot in any
direction
Shown with
Fig. 910
Bar joist shown attached to
various roof materials
Top View
1\" (25.4mm)
1
/2\" Bolt & Nut
Furnished
Fig. 825
Fig. 980
Brace
I-Beam
3
/8\"
(9.5)
Set Bolts & Hardware
Included
OPM
Fig. 4L
Fig. 825
Fig. 825
Fig. 1001 Fig. 1001
Fig. 980
Fig. 980
Maximum Design Load
825W/909-1370 lbs (5.78 KN)
825W/910-1500 lbs (7.11 KN)
825W/980-1600 lbs (8.45 KN)
UL Listed as Hanger Attachment for
6\" (150mm) pipe at Maximum Spacing
Updated 5-24-21
Seismic Bracing
Seismic Bracing
55 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: One size accommodates all
Fig. 900 Series sway brace attachments.
Material: Steel
Function: To attach sway bracing and hanger assemblies
to steel members.
Features: This product’s design incorporates a concentric
attachment point which is critical to the performance
of structural seismic connections. NFPA 13 indicates
the importance of concentric loading of connections
and fasteners. Permits secure non-friction connection
without drilling or welding. Unique design reinforces point
of connection to joist. Break off head set bolt design assures verification of proper
installation torque (min. 31 ft.-lbs.).
Approvals: Approved by Factory Mutual Engineering (FM).
Included in our Seismic Engineering Guidelines approved by the State of California
Office of Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to our
Seismic Engineering Guidelines, OPM-0052-13
For UL Listed information refer to UL Listed page 54.
Installation Instructions: Fig. 825 is the structural attachment componentof a
longitudinal or lateral sway brace assembly. It is intended to be combined with
a TOLCO™ transitional attachment, “bracing pipe” and a TOLCO “braced pipe”
attachment, to form a complete bracing assembly. NFPA 13 or FM guidelines should
be followed.
To Install: Place the Fig. 825 on the steel beam, tighten the cone point set bolts until
heads break off. Attach other TOLCO transitional attachment fitting, Fig. 980, 910, 909,
or any other TOLCO approved transitional fitting. Transitional fitting attachment can
pivot for adjustment to proper brace angle.
Finish: Plain, Electro-Galvanized and HDG
Approx. Wt./100: 247.5 Lbs. (112.2kg)
Order By: Figure number and finish
US Patent #6,098,942,
Canada Patent #2,286,659
Designed to meet or exceed
requirements of FM DS 2-8.
Retaining strap not required.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 825 - bar joist sway brace attachment to steel (FM approved)
Fig. 4L
Top View
1\"
(25.4mm) 1
/2\" Bolt & Nut
Furnished
Fig. 825
Fig. 825
Fig. 825
Fig. 1000
Fig. 1001
Side View
Fig. 980
Fig. 980
Fig. 980
3
/8\"
(9.5)
FM Approved design loads are based
on ASD design method.
Set Bolts & Hardware
Included
Fig. 825
Fig. 980
Brace
I-Beam
FM Approved Design Loads
30°-44° 45°-59° 60°-74° 75°-90°
lbs. / (kN) lbs. / (kN) lbs. / (kN) lbs. / (kN)
Maximum Perpendicular to 990 1360 1670 1860 3
/8\" Thick Flange Structural Member (4.40) (6.05) (7.43) (8.27)
Maximum Parallel to 460 630 770 860 3
/8\" Thick Flange Structural Member (2.04) (2.80) (3.42) (3.82)
OPM
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
56 Eaton B-Line series Fire Protection Solutions
Size Range: One size accommodates all Fig. 900 Series sway brace attachments.
Material: Steel
Function: To attach sway bracing and/or hanger to steel structural members.
Features: This product’s design incorporates a concentric attachment point which
is critical to the performance of structural seismic connections. NFPA 13 indicates
the importance of concentric loading of connections and fasteners. Permits secure
non-friction connection without drilling or welding. Unique design reinforces point
of connection to joist. Break off head bolt design assures verification of proper
installation.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
UL listed with Fig. 909, 910, and 980 series attachments and the following brace
member type pipes: Sch. 40, KSD 3562. Included in our Seismic Engineering
Guidelines approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
Installation Instructions: Fig. 825A is the structural attachment component of
a longitudinal or lateral sway brace assembly. It is intended to be combined with
a TOLCO™ transitional attachment, “bracing pipe” and a TOLCO “braced pipe”
attachment to form a complete bracing assembly. NFPA 13 guidelines should
be followed.
To Install: Place the Fig. 825A on the steel beam, tighten the cone point set
bolts until heads break off. Attach other TOLCO transitional attachment fitting,
Fig. 980, 910, 909, or any other TOLCO approved transitional fitting. Transitional
fitting attachment can pivot for adjustment to proper brace angle.
Finish: Plain or Electro-Galvanized
Approx. Wt./100: 154.5 Lbs. (70.1kg)
Order By: Figure number and finish
Patent #6,098,942
Retaining strap not required.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Shown with
Fig. 910
Shown with
Fig. 1001
May pivot in any
direction
Bar joist shown attached to
various roof materials
TOLCO Fig. 825A - bar joist sway brace attachment to steel
Maximum Design Load
825A 700 lbs. (3.11kN)
UL Listed as Hanger
Attachment for 8\" (200mm)
Pipe at Maximum Spacing
3
/8\"
(9.5)
Set Bolts & Hardware
Included
OPM
Updated 5-24-21
Seismic Bracing
Seismic Bracing
57 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Material: Steel
Application: Allows sway brace fittings to develop greater
load carrying ability by providing multiple fastener attachments
for steel and wood. The National Fire Protection (NFPA)
provides information on fastener loads to various structures.
Refer to NFPA 13 (2016) 9.3.5.9.1.
Approvals: Underwriters Laboratories Listed in the USA
(UL) and Canada (cUL) only when used with TOLCO™ Fig. 900
Series Earthquake Brace Attachments. Included in our Seismic
Engineering Guidelines approved by the State of California
Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to our
Seismic Engineering Guidelines, OPM-0052-13.
Installation Instructions: Fig. 906 is a multiple fastener
structural attachment component of a longitudinal or lateral
sway brace assembly. It is intended to be combined with a
TOLCO transitional attachment, “bracing pipe” and a TOLCO
“braced pipe” attachment to form a complete bracing
assembly. NFPA 13 guidelines should be followed.
To Install: Attach the Fig. 906 to the structural surface as
per fastener design guidelines. Attach other TOLCO
transitional attachment fitting, Fig. 980, 910, 909, or any
other TOLCO approved transitional fitting. Transitional fitting
attachment can pivot for adjustment to proper brace angle.
Finish: Plain or Electro-Galvanized. Contact customer
service for alternative finishes and materials.
Order By: Figure number and specify dimensions H1 and H2.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 906 - sway brace multi-fastener adapter
Part A B C D H1 H2 Approx. Wt./100
Number in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
906 12\" (305.0) 9\" (228.6) 2.5\" (63.5) 1
/4\" (6.3) Specify Specify 394 (178.7)
906-12 15\" (381.0) 12\" (304.8) 2.5\" (63.5) 1
/4\" (6.3) Specify Specify 494 (224.1)
Load Note: Actual design load determined by anchor and concrete strength, not to exceed the UL Listed maximum
load of 1200 lbs (5.33kN).
Load is for Fig. 906. If combined load of anchors is less, must reduce to anchor maximum capacity.
C
C
A
D
B
H1
H1
H2
Mounting Hardware
Is Not Included
OPM
Seismic Bracing
Size Range: 4\" (101.6mm) thru 18\" (457.2mm) beam width
Material: Steel
Function: Seismic brace attachment to steel.
Features: This product’s design incorporates a concentric attachment point which
is critical to the performance of structural seismic connections. NFPA 13 indicates
the importance of concentric loading of connections and fasteners. Permits secure
connection to steel where drilling and/or welding of brace connection could present
structural issues.
Installation Instructions: Fig. 800 is the structural attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with
a TOLCO™ transitional attachment, “bracing pipe” and a TOLCO “braced pipe”
attachment to form a complete bracing assembly.
NFPA 13 guidelines should be followed.
To Install: Place the Fig. 800 on the steel beam, tighten the cone point set bolts
on flange until the heads break off. Tighten hex head bolts into clamp body until
lock washers are fully flat. Attach other TOLCO transitional attachment fitting, Fig.
980, 910, 909, or any other TOLCO approved transitional fitting. Transitional fitting
attachment can pivot for adjustment to proper brace angle.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
UL listed with Fig. 909, 910, 980, 909 series attachments and the following brace
member type pipes: Sch. 40, KSD 3562. Included in our Seismic Engineering
Guidelines approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
For FM Approval information refer to FM Approved page 59.
Finish: Plain, Electro-Galvanized and Hot Dip Galvanized. Contact customer service
for alternative finishes and materials.
Order By: Figure number, type number and size number.
Example: FIG. 800 TYPE2X14-16
TOLCO Fig. 800 - adjustable sway brace attachment to steel (UL listed)
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Shown with Fig. 980
brace fitting to
pipe brace
(Lateral - Perpendicular
to Braced Pipe)
Shown with Fig. 980 brace
fitting to pipe brace
(Longitudinal - Parrallel
to Braced Pipe)
Set Bolts & Hardware
Included
Fits Beam Flange
Type Thickness
in. (mm)
800 TYPE1 Up to 3
/4\" (Up to 19.0)
800 TYPE2 3
/4\" to 11
/4\" (19.0 to 31.7)
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
58 Eaton B-Line series Fire Protection Solutions
OPM
Fits Flange Width Range Max.Design Loads (cULus)
Along or Across Beam
Part # in. (mm) Fig. 909
lbs. (kN)
Fig. 910
lbs. (kN)
Fig. 980
lbs. (kN)
800-1 4\"-6\" (101.6-152.4)
1270~ (5.65) 1400~ (6.23) 1400~ (6.23)
800-2 6\"-8\" (152.4-203.2)
800-3 8\"-10\" (203.2-254.0)
800-4 10\"-12\" (254.0-304.8)
800-5 12\"-14\" (304.8-355.6) 1270~ (5.65) 1300~ (5.78) 1300~ (5.78)
800-6 14\"-16\" (355.6-406.4)
900~ (4.00) 900~ (4.00) 900~ (4.00) 800-7 16\"-18\" (406.4-457.2)
Seismic Bracing
Size Range: 4\" (101.6mm) thru 18\" (457.2mm) beam width
Material: Steel
Function: Seismic brace attachment to steel.
Features: This product’s design incorporates a concentric attachment point which
is critical to the performance of structural seismic connections. NFPA 13 indicates
the importance of concentric loading of connections and fasteners. Permits secure
connection to steel where drilling and/or welding of brace connection could present
structural issues.
Installation Instructions: Fig. 800 is the structural attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with
a TOLCO™ transitional attachment, “bracing pipe” and a TOLCO “braced pipe”
attachment to form a complete bracing assembly.
NFPA 13 guidelines should be followed.
To Install: Place the Fig. 800 on the steel beam, tighten the cone point set bolts
on flange until the heads break off. Tighten hex head bolts into clamp body until
lock washers are fully flat. Attach other TOLCO transitional attachment fitting,
Fig. 980, 910, 909, or any other TOLCO approved transitional fitting. Transitional
fitting attachment can pivot for adjustment to proper brace angle.
Approvals: Approved by Factory Mutual Engineering (FM).
Included in our Seismic Engineering Guidelines approved by the State of California
Office of Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to our
Seismic Engineering Guidelines, OPM-0052-13.
For UL Listed information refer to UL Listed page 58.
Finish: Plain, Hot Dip Galvanized or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, type number and size number.
Example: FIG. 800 TYPE2X14-16
Designed to meet or exceed requirements of FM DS 2-8.
TOLCO Fig. 800 - adjustable sway brace attachment to steel (FM approved)
Fits Beam Max.Design Loads (FM)*
Type Flange Thickness Laterial - Parallel to Structural Member Longitudinal - Perpendicular to Structural Member
30°-44° 45°-59° 60°-74° 75°-90° 30°-44° 45°-59° 60°-74° 75°-90°
in. (mm) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN) lbs./(kN)
800 TYPE1 Up to 3
/4\" (Up to 19.0) 1430 1970 1980 NR 930 1310 1610 1800
(6.36) (8.76) (8.81) (NR) (4.13) (5.82) (7.16) (8.00)
800 TYPE2 3
/4\" to 11
/4\" (19.0 to 31.7) NR NR NR NR NR NR NR NR
(NR) (NR) (NR) (NR) (NR) (NR) (NR) (NR)
* The loads listed are axial loads on the brace. The horizontal
load capacity, H, of the brace is: H = F x sin ?, where ? is
the installation angle measured from the vertical.
FM Approved design loads are based on ASD design method.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Shown with Fig. 980
brace fitting to pipe brace
(Lateral - Perpendicular to
Braced Pipe)
Shown with Fig. 980
brace fitting to pipe brace
(Longitudinal - Parrallel to
Braced Pipe)
Set Bolts & Hardware
Included
Seismic Bracing
59 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Fits
Flange Width Range
in. (mm)
4-6 4\"-6\" (101.6-152.4)
6-8 6\"-8\" (152.4-203.2)
8-10 8\"-10\" (203.2-254.0)
10-12 10\"-12\" (254.0-304.8)
12-14 12\"-14\" (304.8-355.6)
14-16 14\"-16\" (355.6-406.4)
16-18 16\"-18\" (406.4-457.2)
OPM
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
60 Eaton B-Line series Fire Protection Solutions
Size Range: One size fits bracing pipe 1\" (25mm) thru 2\" (50mm), B-Line series
12 gauge (2.6mm) channel.
Material: Carbon steel
Function: Multi-functional attachment to structure or braced pipe fitting.
Features: This product’s design incorporates a concentric attachment opening which
is critical to the performance of structural seismic connections and in accordance with
NFPA 13, 2019 Section 18.5.11.5. The Fig. 980 mounts to any surface angle and the
break off bolt head assures verification of proper installation.
Installation: Fig.980 is the structural or transitional attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with the
“bracing pipe” and TOLCO™ “braced pipe” attachment, Fig. 1001, 2002, 3000, 4L or
approved attachment to pipe to form a complete bracing assembly. NFPA 13 guidelines
should be followed.
To Install: Place the Fig. 980 onto the “bracing pipe”. Tighten the set bolt until the
head breaks off. Attachment can pivot for adjustment to proper brace angle.
Approvals: —Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
UL Listed for the following brace member type pipes: Sch. 40, KSD 3562. Ask the
factory for additional information as it may vary by product size. Included in our Seismic
Engineering Guidelines approved by the State of California Office of Statewide Health
Planning and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to our Seismic Engineering
Guidelines, OPM-0052-13. For FM Approval information refer to FM Approved page 61.
Note: Fig. 980 Swivel Attachment and Fig. 1001, 2002, 3000, 4L, or approved
attachment to pipe make up a sway brace system of UL Listed attachments and bracing
materials which satisfies the requirements of Underwriters Laboratories and the National
Fire Protection Association (NFPA)
Finish: Plain, Electro-Galvanized or Stainless Steel.
Contact customer service for alternative finishes.
Order By: Figure number and finish.
Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174,
Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730,
Pat. #7,669,806
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Longitudinal Brace
Fig. 980 - TOLCO Universal swivel sway brace attachment -3
/8\"-16 to 3
/4\"-10 rods
Fig. 980H - TOLCO Universal swivel sway brace attachment -7
/8\"-9 to 11
/4 \"-7
Mounting Hardware
Is Not Included
Set Bolt
Included
Fig. 4B
shown
Fig. 980
Fig. 980
OPM
Lateral Brace
Brace
Fig. 1001
Fig. 980
A
D
B B
D
A
980
A B D** Max. Design
Load (cULus)
lbs./(kN)
Approx.Wt./100
Catalog # in. (mm) in. (mm) in. (mm) lbs. (kg)
*980-3
/8
49
/16 (114.9) 21
/16 (52.4)
7
/16 (11.1) 1600 (7.12) 149 (67.6)
*980-1
/2 9
/16 (14.3) 2100 (9.34) 148 (67.1)
*980-5
/8 11/16 (17.5) 2100 (9.34) 147 (66.7)
*980-3
/4 13/16 (20.6) 2100 (9.34) 146 (66.2)
980H-7
/8
63
/4 (171.4) 31
/2 (88.9)
15/16 (23.8) Fig. 980H
is not
UL Listed
or FM
Approved
402 (182.3)
980H-1 11
/16 (27.0) 400 (181.4)
980H-11
/8 13
/16 (30.2) 397 (180.1)
980H-11
/4 15
/16 (33.3) 390 (176.9)
* Sizes available in stainless steel (980S-3
/8, 980S-1
/2, 980S-5
/8, and 980S-3
/4) and have the same
UL rating as what is listed.
** Mounting attachment hole size.
Seismic Bracing
Seismic Bracing
61 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: One size fits bracing pipe 1\" (25mm) thru 2\" (50mm), B-Line series
12 gauge (2.6mm) channel.
Material: Carbon steel
Function: Multi-functional attachment to structure or braced pipe fitting.
Features: This product’s design incorporates a concentric attachment opening
which is critical to the performance of structural seismic connections and in
accordance with NFPA 13, 2019 Section 18.5.11.5. The Fig. 980 mounts to
any surface angle and the break off bolt head assures verification of proper
installation.
Installation: Fig.980 is the structural or transitional attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with
the “bracing pipe” and TOLCO™ “braced pipe” attachment, Fig. 1000, 1001,
3000, 4L, or other TOLCO approved attachment to pipe to form a complete
bracing assembly. NFPA 13 guidelines should be followed.
To Install: Place the Fig. 980 onto the “bracing pipe”. Tighten the set bolt until
the head breaks off. Attachment can pivot for adjustment to proper brace angle.
Approvals: —Approved by Factory Mutual Engineering (FM). Included in our
Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to
our Seismic Engineering Guidelines, OPM-0052-13.
For UL Listed information refer to UL Listed page 60.
Note: Fig. 980 Swivel Attachment and Fig. 1000, 1001, 4L or other TOLCO
approved attachment to pipe that make up a sway brace system of bracing
materials which satisfies the requirements of Factory Mutual Engineering and
the National Fire Protection Association (NFPA)
Finish: Plain, Electro-Galvanized or Stainless Steel.
Contact customer service for alternative finishes.
Order By: Figure number and finish.
Pat. #6,273,372, Pat. #6,517,030, Pat. #6,953,174,
Pat. #6,708,930, Pat. #7,191,987, Pat. #7,441,730,
Pat. #7,669,806
Designed to meet or exceed requirements of FM DS 2-8.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Lateral Brace
Longitudinal
Brace
Fig. 4L
Fig. 1001
Fig. 980
Fig. 980
Brace
OPM
Mounting Hardware
Is Not Included
Set Bolt
Included
A
D
B B
D
A
980
Fig. 980 - TOLCO Universal swivel sway brace attachment -3
/8\"-16 to 3
/4\"-10 rods
Fig. 980H - TOLCO Universal swivel sway brace attachment -7
/8\"-9 to 11
/4 \"-7
A B D** Max. Design Load*** (FM) Approx.Wt./100
Catalog # in. (mm) in. (mm) in. (mm) 30°-44°
lbs./(kN)
45°-59°
lbs./(kN)
60°-74°
lbs./(kN)
75°-90°
lbs./(kN) lbs. (kg)
980-3
/8
49
/16 (114.9) 21
/16 (52.4)
7
/16 (11.1)
2370
(10.54)
2790
(12.41)
3360
(14.94)
3750
(16.68)
149 (67.6)
980-1
/2 9
/16 (14.3) 148 (67.1)
980-5
/8 11/16 (17.5) 147 (66.7)
980-3
/4 13/16 (20.6) 146 (66.2)
980H-7
/8
63
/4 (171.4) 31
/2 (88.9)
15/16 (23.8) 402 (182.3)
980H-1 11
/16 (27.0) 400 (181.4)
980H-11
/8 13
/16 (30.2) 397 (180.1)
980H-11
/4 15
/16 (33.3) 390 (176.9)
** Mounting attachment hole size.
*** Installed with 1\" or 11
/4 \"schedule 40 brace pipe.
Fig. 980H is not UL Listed
or FM Approved
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
62 Eaton B-Line series Fire Protection Solutions
Size Range: 1\" (25mm) bracing pipe. For brace pipe sizes larger than
1\" (25mm), use Fig. 980. Available with holes for 3
⁄8\", 1
⁄2\" or 5
⁄8\" attachment.
Material: Steel, hardened cone point set bolt
Function: The structural component of a sway and seismic bracing system.
Features: This product’s design incorporates a concentric attachment opening
which is critical to the performance of structural seismic connections. NFPA 13
indicates clearly that fastener table load values are based only on concentric
loading. No threading of the bracing pipe is required. Open design allows for
easy inspection of pipe engagement.
ApJ54plication Note: Fig. 909 is used in conjunction with the Fig. 1001 or
Fig. 4L or other approved TOLCO attachment to pipe, and joined together
with bracing pipe. Sway brace assemblies are intended to be installed in
accordance with NFPA 13. The required type, number and size of fasteners
used for the structure attachment fitting shall be in accordance with NFPA 13.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). UL Listed for the following brace member type pipes: Sch. 40, KSD
3562. Included in our Seismic Engineering Guidelines approved by the State of
California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD
projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13.
Installation Instructions: Place Fig. 909 onto the bracing pipe. Tighten the
set screw until the head bottoms out on surface. When using in combination
with a Fig. 825A, Fig. 825, Fig. 828, or Fig. 906, refer to those instruction
sheets, otherwise select an anchor that is sized appropriately for the intended
use and follow anchor manufacturer’s instructions regarding structural thickness
and embedment requirements. The required type, number and size of fasteners
used for the structure attachment fitting shall be in accordance with NFPA 13.
Once the anchor is installed per the manufacturer’s direction, secure the
Fig. 909 to the anchor. Attachment can pivot for adjustment to proper
brace angle.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, fastener attachment size and finish.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 909 - no-thread swivel sway brace attachment (UL listed)
Part Mounting Hole Brace Max. Design Approx.
Number D Pipe Size B Load Wt./100
in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
909-3
/8 7
/16\" (11.1) 1\" (25) 15
/8\" (41.3) 1370 (6.09) 90 (40.8)
909-1
/2 * 17/32\" (13.5) 1\" (25) 15
/8\" (41.3) 1370 (6.09) 91 (41.3)
909-5
/8 11/16\" (17.5) 1\" (25) 15
/8\" (41.3) 1370 (6.09) 90 (40.8)
B
D
Mounting Hardware
Is Not Included
Set Bolt
Included
* Standard size.
OPM
Seismic Bracing
Seismic Bracing
63 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 1\" (25mm) bracing pipe. For brace pipe sizes larger than 1\" (25mm),
use Fig. 980. Available with holes for 1
⁄2\" fastener attachment.
Material: Steel
Function: The Fig. 910, is the structural or transitional attachment component
of a longitudinal or lateral sway brace assembly. It is intended to combined with
a 1\" “bracing pipe”, and TOLCO™ “braced pipe” attachment to form a complete
bracing assembly. Sway brace assemblies are intended to be installed in
accordance with NFPA 13 and the manufacturer’s installation instructions
Features: This product’s design incorporates a concentric attachment opening
which is critical to the performance of structural seismic connections. NFPA 13
(2010) 9.3.5.8.4 and (2013-2016) 9.3.5.11.5 indicates that fastener table load
values are based only on concentric loading. Universal swivel design allows Fig.
910 to be attached at any surface angle.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). (cUL). UL Listed for the following brace member type pipes: Sch. 40.
Included in our Seismic Engineering Guidelines approved by the State of
California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
Installation Instructions: Thread the 1\" brace pipe into the Fig. 910 until pipe
threads are visible through inspection site hole. When using in combination with
a Fig. 825A, Fig. 825, Fig. 828, or Fig. 906 refer to those instruction sheets,
otherwise select an anchor that is sized appropriately for the intended use and
follow anchor manufacturer’s instructions regarding structural thickness and
embedement requirements. The required type, number and size of fasteners used
for the structure attachment fitting shall be in accordance with NFPA 13. Once
the anchor is installed per the manufacturer’s direction, secure the Fig. 910 to the
anchor. Attachment can pivot for adjustment to proper brace angle.
Note: Fig. 910 swivel attachment and Fig. 1001, 2002, 3000 or 4L pipe clamps
make up a sway brace system of UL Listed attachments and bracing materials
which satisfies the requirements of Underwriters Laboratories and the National
Fire Protection Association (NFPA).
Finish: Electro-Galvanized. Contact customer service for alternative finishes and
materials.
Order By: Figure number, pipe size and finish.
F
E
C
A
B D
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 910 - threaded swivel sway brace attachment (UL listed)
Part Brace Mounting Max. Design Approx.
Number Pipe Size A B C Hole D E F Load Wt./100
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
910-1 X 1
/2 1\" (25) 17
/10\" (43.2) 11
/5\" (30.5) 215
/16\"(74.7) 9
/16\" (14.3) 111/16\" (42.9) 21
/20\" (52) 1600 (8.96) 105 (47.6)
B
A
D
F
E
C
Mounting Hardware
Is Not Included
OPM
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
64 Eaton B-Line series Fire Protection Solutions
Size Range: 1\" (25.4mm) x 1\" (25.4mm), 1\" (25.4mm) x 11
⁄4\" (31.7mm) and
11
⁄4\" (25.4mm) x 11
⁄4\" (25.4mm) bracing pipe.
Material: Steel, hardened cone (or cup) point set bolt
Function: For attaching two pieces of pipe together at various angles.
To Install: Attach the Fig. 907 over one piece of pipe and adjust to
desired position. Tighten set bolt until head bottoms out on surface, then
repeat the process for the second pipe.
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, bracing pipe sizes and finish.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 907 - multi-angle attachment
Part Number Brace Pipe Size A B Max. Design Load Approx. Wt./100
in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
907-1 X 1 1\" x 1\" (25 x 25) 43
/4\" (120.6) 43
/4\" (120.6) 655 (2.91) 103 (46.7)
907-1 X 11
/4 1\" x 11
/4\" (25 x 32) 53
/16\" (128.6) 413/16\" (122.2) 655 (2.91) 107 (48.5)
907-11
/4 X 11
/4 11
/4\" x 11
/4\" (32 x 32) 53
/8\" (136.5) 51
/4\" (133.1) 655 (2.91) 109 (49.4)
B
A
Set Bolts
Included
Fig. 1000
Brace Pipe
Shown
With
Fig. 909
Shown
With
Fig. 909
Shown
With
Fig. 909
Fig. 907 Can Be Attached On Either
Side Of The Pipe Being Braced
Fig. 1000
Fig. 907
Fig. 909
4-Way Riser Brace
Seismic Bracing
Seismic Bracing
65 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 1\" (25mm) bracing pipe. For brace pipe sizes larger than 1\" (25mm), use
Fig. 980. Available with holes for 1
⁄2\", 5
⁄8\", or 3
⁄4\" fastener attachment.
Material: Steel
Function: The Fig. 975 is the structural or transitional attachment component of a
longitudinal or lateral sway brace assembly. It is intended to be combined with a 1\"
“bracing pipe” and TOLCO™ “braced pipe” attachment to form a complete bracing
assembly. Sway brace assemblies are intended to be installed in accordance with
NFPA 13 and the manufacturer’s installation instructions
Features: Open design allows for easy checking of thread engagement.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL).
UL Listed for the following brace member type pipes: Sch. 40.
Installation: Thread the Fig. 975 onto the 1\" threaded bracing pipe. When using
in combination with the Fig. 906, refer to that instruction sheet, otherwise select
an anchor that is sized appropriately for the intended use and follow anchor
manufacturer’s instructions regarding structural thickness and embedment
requirements. The required type, number and size of fasteners used for the
structure attachment fitting shall be in accordance with NFPA 13. Once the anchor
is installed per the manufacturer’s direction, secure the Fig. 975 to the anchor.
Attachment can pivot for adjustment to proper brace angle. (Bending of plate not
permitted).
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes
and materials.
Order By: Figure number and
finish.
Note: Bending of this fitting alters
the material strength and voids the
cULus Listing. Use Fig. 980, 910,
909, or any other TOLCO fitting
when angled fitting is required.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Lateral Brace
TOLCO Fig. 975 - straight sway brace fitting (UL listed)
Part Brace Mounting Hole Max. Design Approx.
Number Pipe Size A B C D Load Wt./100
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
975-1
/2 * 1\" (25) 4\" (101.6) 31
/2\" (88.9) 11
/2\" (38.1) 9
/16\" (14.3) 2100 (9.34) 88 (39.9)
975-5
/8 1\" (25) 4\" (101.6) 31
/2\" (88.9) 11
/2\" (38.1) 11/16\" (17.5) 2100 (9.34) 87 (39.4)
975-3
/4 1\" (25) 4\" (101.6) 31
/2\" (88.9) 11
/2\" (38.1) 13/16\" (20.6) 2100 (9.34) 86 (39.0)
B
D
C
A
Mounting Hardware
Is Not Included
* Standard size.
Fig. 975 Brace Pipe
Fig. 1001
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
66 Eaton B-Line series Fire Protection Solutions
Size Range: Pipe size to be braced: 1\" (25mm) thru 8\" (200mm) IPS.
Pipe size used for bracing: 1\" (25mm) and 11
⁄4\" (32mm) Schedule 40 IPS.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance. The pipe attachment
component of a sway brace system: Fig. 1001 is used in conjunction with a Fig. 900 Series
fitting and joined together with bracing pipe per NFPA 13, forming a complete sway brace
assembly.
Features: Can be used to brace schedule 7 through schedule 40 IPS. Field adjustable,
making critical pre-engineering of bracing pipe length unnecessary. Unique design requires no
threading of bracing pipe. Comes assembled and ready for installation. Fig. 1001 has
built-in visual verification of correct installation. See installation note below.
Installation Note: Position Fig. 1001 over the pipe to be braced and tighten two hex head
cone point set bolts until heads bottom out. A minimum of 1\" (25mm) pipe extension is
recommended. Brace pipe can be installed on top or bottom of pipe to be braced.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). UL Listed
for the following sprinkler type pipes: Sch. 40 (and as brace member), Sch. 10, Bull Moose
Eddy Flow, Wheatland Mega Flow, DIN 2448, KSD 3562 (and as brace member), KSD
3507. Ask the factory for additional information as it may vary by product size. Included in
our Seismic Engineering Guidelines approved by the State of California Office of Statewide
Health Planning and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13. For FM Approval information refer to FM Approved page 67.
Finish: Plain, Electro-Galvanized or Hot Dip Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Order by figure number, pipe size to be braced, followed by pipe size used for
bracing (1\" (25mm) or 11
⁄4\" (32mm)), and finish.
TOLCO Fig. 1001 - sway brace attachment (UL listed)
Set Bolts
Included
Pipe Part Number & Approx. Wt./100 Design Load - Lbs.
Size 1\" (25mm) Brace Pipe 11
/4\" (32mm) Brace Pipe For Brace Pipe Size 1\" / 11
/4\"
Sch. 7 Sch. 10 Sch. 40
in. (mm) Lbs. (kg) Lbs. (kg) 1\" / 11
/4\" 1\" / 11
/4\" 1\" / 11
/4\"
1\" (25) 1001-1 X 1 104.6 (47.4) 1001-1 X 11
/4 122.2 (55.4) — / — — / — 1000 / 1000
11
/4\" (32) 1001-11
/4 X 1 105.2 (47.7) 1001-11
/4 X 11
/4 122.6 (55.6) 1000 / 1000 1000 / 1000 1000 / 1000
11
/2\" (40) 1001-11
/2 X 1 107.0 (48.5) 1001-11
/2 X 11
/4 124.7 (56.6) 1500 / 1500 1500 / 1500 1500 / 1500
2\" (50) 1001-2 X 1 112.6 (51.1) 1001-2 X 11
/4 129.2 (58.6) 1500 / 1500 1500 / 1500 1500 / 1500
*21
/2\" (65) 1001-21
/2 X 1* 136.3 (61.8) 1001-21
/2 X 11
/4* 154.4 (70.0) 2000 / 2000 2000 / 2000 2000 / 2000
3\" (80) 1001-3 X 1 145.0 (65.8) 1001-3 X 11
/4 163.1 (74.0) 2000 / 2000 2000 / 2000 2000 / 2000
4\" (100) 1001-4 X 1 158.6 (71.9) 1001-4 X 11
/4 176.7 (80.1) 2000 / 2000 2000 / 2000 2000 / 2000
5\" (100) 1001-5 X 1 173.2 (78.6) 1001-5 X 11
/4 191.4 (86.8) — / — 2000 / 2000 2000 / 2000
*6\" (150) 1001-6 X 1* 190.0 (85.2) 1001-6 X 11
/4* 206.0 (93.4) 2000 / 2000 2000 / 2000 2000 / 2000
*8\" (200) 1001-8 X 1* 217.4 (111.5) 1001-8 X 11
/4* 265.3 (120.3) — / — 2000 / 2000 2000 / 2000
*Note: Metric sizes available for 65mm, 150mm, 200mm pipe size with 25mm and 32mm brace pipe size.
Contact the factory.
OPM
Fig. 1001
Seismic Bracing
Seismic Bracing
67 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: Pipe size to be braced: 1\" (25mm) thru 8\" (200mm) IPS. Pipe size used
for bracing: 1\" (25mm) and 11
⁄4\" (32mm) Schedule 40 IPS.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance. The pipe
attachment component of a sway brace system: Fig. 1001 is used in conjunction
with a Fig. 900 Series fitting and joined together with bracing pipe per NFPA 13,
forming a complete sway brace assembly.
Features: Can be used to brace schedule 7 through schedule 40 IPS. Field
adjustable, making critical pre-engineering of bracing pipe length unnecessary.
Unique design requires no threading of bracing pipe. Can be used as a component
of a four-way riser brace. Comes assembled and ready for installation. Fig. 1001
has built-in visual verification of correct installation. See installation note below.
Installation Note: Position Fig. 1001 over the pipe to be braced and tighten two
hex head cone point set bolts until heads bottom out. A minimum of 1\" (25mm)
pipe extension is recommended. Brace pipe can be installed on top or bottom of
pipe to be braced.
Approvals: Approved by Factory Mutual Engineering (FM). Included in our
Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to our
Seismic Engineering Guidelines, OPM-0052-13. For UL Listed information refer to
UL Listed page 66.
Finish: Plain, Electro-Galvanized or Hot Dip Galvanized. Contact customer service
for alternative finishes and materials.
Order By: Order by figure number, pipe size to be braced, followed by pipe size
used for bracing (1\" (25mm) or 11
⁄4\" (32mm)) , and finish.
Important Note: Fig. 1001 is precision manufactured to perform its function as
a critical component of a complete bracing assembly. To ensure performance,
the FM Approval requires that Fig. 1001 must be used only with other TOLCO™
bracing products. The Fig. 1001 is not intended for use with the Fig. 907
4-way Longitudinal Brace Attachment.
Designed to meet or exceed requirements of FM DS 2-8.
TOLCO Fig. 1001 - sway brace attachment (FM approved)
Set Bolts
Included
Design Load - For Sch. 7, Sch. 10, & Sch. 40 Pipe
Pipe Part Number & Approx. Wt./100 Allowable Horizontal Capacity (lbf) Per Installation1, 2, 3
Size 1\" (25mm) Brace Pipe 11
/4\" (32mm) Brace Pipe 30°-44° 45°-59° 60°-74° 75°-90°
in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
1\" (25) 1001-1 X 1 104.6 (47.4) 1001-1 X 11
/4 122.2 (55.4) 1800 (8.01) 2550 (11.34) 3120 (13.88) 3490 (15.52)
11
/4\" (32) 1001-11
/4 X 1 105.2 (47.7) 1001-11
/4 X 11
/4 122.6 (55.6) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.59)
11
/2\" (40) 1001-11
/2 X 1 107.0 (48.5) 1001-11
/2 X 11
/4 124.7 (56.6) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.59)
2\" (50) 1001-2 X 1 112.6 (51.1) 1001-2 X 11
/4 129.2 (58.6) 1230 (5.47) 1740 (7.74) 2140 (9.52) 2380 (10.59)
*21
/2\"(65) 1001-21
/2 X 1* 136.3 (61.8) 1001-21
/2 X 11
/4 * 154.4 (70.0) 800 (3.56) 1130 (5.03) 1380 (6.14) 1540 (6.85)
3\" (80) 1001-3 X 1 145.0 (65.8) 1001-3 X 11
/4 163.1 (74.0) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.30)
4\" (100) 1001-4 X 1 158.6 (71.9) 1001-4 X 11
/4 176.7 (80.1) 850 (3.78) 1200 (5.34) 1470 (6.54) 1640 (7.30)
5\" (100) 1001-5 X 1 173.2 (78.6) 1001-5 X 11
/4 191.4 (86.8) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40)
*6\" (150) 1001-6 X 1* 190.0 (85.2) 1001-6 X 11
/4* 206.0 (93.4) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40)
*8\" (200) 1001-8 X 1* 217.4 (111.5) 1001-8 X 11
/4* 265.3 (120.3) 510 (2.27) 730 (3.25) 890 (3.96) 990 (4.40)
1 FM Approved when used with 1 or 11
/4 inch NPS Schedule 40 GB/T 3091,EN 10255H, or JIS G3451 steel pipe as the brace member.
2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as “Schedule 7\". These ratings may also be
applied when EN 10220 and GB/T 8163 steel pipe.
3 Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H, or JIS G3454, FM Approved Thinwall, or Schedule
40 steel pipes.
Note: See UL load ratings in UL Listed Design
Load chart shown under drawing.
*Note: Metric sizes available for 65mm, 150mm, 200mm
pipe size with 25mm and 32mm brace pipe size.
Contact the factory.
OPM
Fig. 1001
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
68 Eaton B-Line series Fire Protection Solutions
Size Range: Pipe size to be braced: 1\" (25mm) thru 4\" (100mm) 40 IPS.
Pipe size used for bracing: 1\" (25mm) and 11
⁄4\" (32mm) Schedule 40 IPS.
For pipe sizes larger than 2\" (500mm) please refer to TOLCO™ Fig. 1001.
Material: Steel
Function: A restraint device intended for lateral bracing.
Features: Field adjustable, making critical pre-engineering of bracing pipe
unnecessary. Unique design requires no threading of bracing pipe. Steel leaf
spring insert provided to assure installer and inspector necessary minimum
torque has been achieved.
Installation: Fig. 1000 is the “braced pipe” attachment component of a lateral
sway brace assembly. It is intended to be combined with the “bracing pipe”
and TOLCO structural attachment component, Fig. 980, 910, 909 or other
approved TOLCO component to form a complete bracing assembly. Follow
NFPA 13 guidelines.
To Install: Place the Fig. 1000 over the pipe to be braced, insert bracing pipe
through opening leaving a minimum of 1\" extension. Brace pipe can be installed
on top or bottom of pipe to be braced. Tighten hex nuts until leaf spring is flat.
It is recommended that the brace angle be adjusted before hex nuts are fully
tightened.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL). Approved for use with engineered light wall sprinkler pipe up to 2\" as
a restraint device. Torque requirement is 6-8 ft./lbs. (8-10Nm). Included in our
Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to
our Seismic Engineering Guidelines, OPM-0052-13.
For FM Approval information refer to FM Approved page 69.
Application Note: Position Fast Clamp and tighten two hex nuts until leaf
spring flattens. A minimum of 1\" pipe extension beyond the Fig. 1000 is
recommended.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Order by figure number, pipe size to be braced, followed by pipe
size used for bracing (1\" (25mm) or 11
⁄4\" (32mm)) , and finish.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Lateral Brace
TOLCO Fig. 1000 - “Fast Clamp“ branch line restraint attachment (UL listed)
UL Listed Design Load
1\" (25mm) thru 2\" (50mm) pipe size 650 Lbs. (2.89kN)
Pipe Part Number & Approx. Wt./100
Size 1\" (24mm) Brace Pipe 11
/4\" (32mm) Brace Pipe
in. (mm) Lbs. (kg) Lbs. (kg)
1\" (25) 1000-1 X 1 71.6 (32.5) 1000-1 X 11
/4 75.8 (34.4)
11
/4\" (32) 1000-11
/4 X 1 74.8 (33.9) 1000-11
/4 X 11
/4 79.1 (35.9)
11
/2\" (40) 1000-11
/2 X 1 77.8 (35.3) 1000-11
/2 X 11
/4 82.1 (37.2)
2\" (50) 1000-2 X 1 84.1 (38.1) 1000-2 X 11
/4 88.4 (40.1)
Hardware
Included
OPM
Fig. 980
Fig. 1000
Seismic Bracing
Seismic Bracing
69 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: Pipe size to be braced: 1\" (25mm) thru 4\" (100mm) 40 IPS.
Pipe size used for bracing: 1\" (25mm) and 11
⁄4\" (32mm) Schedule 40 IPS.
For pipe sizes larger than 4\" (100mm) please refer to TOLCO™ Fig. 1001.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
Features: Field adjustable, making critical pre-engineering of bracing pipe
unnecessary. Unique design requires no threading of bracing pipe. Steel leaf
spring insert provided to assure installer and inspector necessary minimum
torque has been achieved.
Installation: Fig. 1000 is the “braced pipe” attachment component of a lateral
sway brace assembly. It is intended to be combined with the “bracing pipe”
and TOLCO structural attachment component, Fig. 980 or other approved
TOLCO seismic brace to form a complete bracing assembly. Follow NFPA 13
guidelines.
To Install: Place the Fig. 1000 over the pipe to be braced, insert bracing pipe
through opening leaving a minimum of 1\" extension. Brace pipe can be installed
on top or bottom of pipe to be braced. Tighten hex nuts until leaf spring is flat.
It is recommended that the brace angle be adjusted before hex nuts are fully
tightened.
Approvals: Approved by Factory Mutual Engineering (FM). Included in our
Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load,
spacing and placement information relating to OSHPD projects, please refer to
our Seismic Engineering Guidelines, OPM-0052-13. For UL Listed information
refer to UL Listed page 68.
Application Note: Position Fast Clamp and tighten two hex nuts until leaf
spring flattens. A minimum of 1\" pipe extension beyond the Fig. 1000 is
recommended.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Order by figure number, pipe size to be braced, followed by pipe
size used for bracing (1\" (25mm) or 11
⁄4\" (32mm)), and finish.
Designed to meet or exceed requirements of FM DS 2-8.
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Lateral Brace
TOLCO Fig. 1000 - “Fast Clamp‘’ sway brace attachment (FM approved)
Hardware
Included
1
FM Approved when used with 1, 11
/4, 11
/2, or 2 inch NPS Schedule 40 GB/T 3091,EN 10255H, or JIS G3451 steel pipe as the brace member.
2 Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as “Schedule 7\". These ratings may also be applied when
EN 10220 and GB/T 8163 steel pipe.
3
Load rating for Schedule 10 above may be applied to GB/T 3092,EN 10255M and H, or JIS G3454, FM Approved Thinwall, or Schedule 40 steel pipes.
Pipe Part Number & Approx. Wt./100 Design Load - Allowable Horizontal Capacity (lbf) Per Installation 1, 2, 3
Size 1\" (24mm) Brace Pipe 11
/4\" (32mm) Brace Pipe 30°-44° 45°-59° 60°-74° 75°-90°
in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
1\" (25) 1000-1 X 1 71.6 (32.5) 1000-1 X 11
/4 75.8 (34.4) 200 (0.89) 280 (1.24) 340 (1.51) 380 (1.69)
11
/4\" (32) 1000-11
/4 X 1 74.8 (33.9) 1000-11
/4 X 11
/4 79.1 (35.9) 200 (0.89) 280 (1.24) 340 (1.51) 380 (1.69)
11
/2\" (40) 1000-11
/2 X 1 77.8 (35.3) 1000-11
/2 X 11
/4 82.1 (37.2) 200 (0.89) 280 (1.24) 340 (1.51) 380 (1.69)
2\" (50) 1000-2 X 1 84.1 (38.1) 1000-2 X 11
/4 88.4 (40.1) 200 (0.89) 280 (1.24) 340 (1.51) 380 (1.69)
21
/2\" (65) 1000-21
/2 X 1 90.2 (40.9) 1000-21
/2 X 11
/4 94.6 (42.9) 200 (0.89) 280 (1.24) 340 (1.51) 380 (1.69)
3\" (80) 1000-3 X 1 97.3 (44.1) 1000-3 X 11
/4 101.7 (46.1) 230 (1.02) 320 (1.42) 400 (1.78) 450 (2.00)
31
/2\" (90) 1000-31
/2 X 1 104.0 (47.2) 1000-31
/2 X 11
/4 108.4 (49.2) 230 (1.02) 320 (1.42) 400 (1.78) 450 (2.00)
4\" (100) 1000-4 X 1 110.3 (50.0) 1000-4 X 11
/4 114.6 (52.0) 230 (1.02) 320 (1.42) 400 (1.78) 450 (2.00)
OPM
Fig. 980
Fig. 1000
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
70 Eaton B-Line series Fire Protection Solutions
Size Range: Pipe size to be braced: 21
⁄2\" (65mm) thru 8\" (200mm) all steel
schedules. Consult factory when bracing other than steel. The Fig. 2002
accepts brace pipes sizes 11
⁄2\" (40mm) and 2\" (50mm) steel schedule 40.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance. The
pipe attachment component of a sway brace system: Fig. 2002 is used in
conjunction with a TOLCO™ Fig. 980 sway brace attachment and joined
together with bracing pipe. Install per NFPA 13.
Features: Easy verification of proper installation by tightening bolts until
ears touch.
Installation: Place Fig. 2002 over pipe to be braced. Slide bracing pipe
through attachment and tighten hex nuts until ears touch.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL). UL Listed for the following sprinkler type pipes: Sch. 40 (and
as brace member), Sch. 10, Bull Moose Eddy Flow, Wheatland Mega Flow,
DIN 2448, KSD 3562 (and as brace member), KSD 3507. Ask the factory for
additional information as it may vary by product size.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, pipe size to be braced, pipe size used for bracing
(11
⁄2\" (40mm) or 2\" (50mm)) and finish.
TOLCO Fig. 2002 - sway brace attachment (UL listed)
Shown with
Fig. 980
Fig. 2002
1\" (25.4mm)
Min.
Pipe Part Number & Approx. Wt./100 Design
Size 11
/2\" (32mm) Brace Pipe 2\" (50mm) Brace Pipe Load
in. (mm) Lbs. (kg) Lbs. (kg) Lbs. (kN)
21
/2\" (65) 2002-21
/2 X 11
/2 260 (117.9) 2002-21
/2 X 2 283.3 (128.6) 2000 (8.89)
3\" (80) 2002-3 X 11
/2 276 (125.2) 2002-3 X 2 299.4 (135.8) 2000 (8.89)
4\" (100) 2002-4 X 11
/2 303 (137.4) 2002-4 X 2 326.8 (148.2) 2000 (8.89)
6\" (150) 2002-6 X 11
/2 361 (163.7) 2002-6 X 2 385.0 (174.6) 2000 (8.89)
8\" (200) 2002-8 X 11
/2 416 (188.7) 2002-8 X 2 439.7 (199.4) 2000 (8.89)
Hardware
Included
Seismic Bracing
Seismic Bracing
71 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Function: Three recommended applications for this product:
• May be used as a branch line restraint for structural attachment to
anchor bolt, beam clamp, etc.
• May be used as an upper attachment with short hanger rod to omit
seismic bracing.
• May be used in a pitched or sloped roof application, to meet
requirements of NFPA 13 (2010) 9.1.2.6.
Refer to page 40 for more information and sizing.
TOLCO Fig. 75 - swivel attachment
Fig. 76 - TOLCO structural attachment for branch line restraint assembly (UL listed)
structural attachment for sway brace assembly (FM)
Function: Structural attachment for branch line restraint or sway brace assembly
Refer to pages 42 for UL Listed information and sizing.
Refer to pages 43 for FM information and sizing.
Fig. 77 - TOLCO structural attachment for branch line restraint assembly (UL listed)
structural attachment for sway brace assembly (FM)
Function: System attachment for branch line restraint or sway brace assembly
Refer to pages 44 for UL Listed information and sizing.
Refer to pages 45 for FM information and sizing.
TOLCO Fig. 3000 - CPVC sway brace attachment
Function: For bracing CPVC and steel pipe against sway and seismic
disturbance. The pipe attachment component of a sway brace system:
Fig. 3000 is used in conjunction with a Fig. 900 Series fitting and joined
together with bracing pipe per NFPA 13, forming a complete sway brace
assembly.
Refer to page 41 for more information and sizing.
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
72 Eaton B-Line series Fire Protection Solutions
TOLCO Fig. 98 - Rod Stiffener
TOLCO Fig. 98B - Rod Stiffener with Break-Off Bolt Head
Size Range: Secures 3
⁄8\"-16 thru 7
⁄8\"-9 hanger rod
Material: Steel
Function: Secures channel to hanger rod for vertical seismic bracing.
Approvals: Included in our Seismic Engineering Guidelines
approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to our Seismic
Engineering Guidelines OPM-0052-13.
Finish: Electro Galvanized. Contact customer service for alternative
finishes and materials.
Weight: Approx. Wt./100: Fig. 98 - 11.8 Lbs. (5.3kg)
Fig. 98B - 12.7 Lbs. (5.7kg)
Order By: Figure number
Notes:
1.) Rod stiffeners are required only on hanger and
trapeze assemblies that have seismic bracing
attached at or within 6\" (152.4mm) of the rod.
A minimum of two rod stiffeners (Figure 98, 98B,
or SC228) must be installed.
2.) Recommended torque on Figure 98 and SC228
is 8 ft-lbs. (10.8Nm) or finger tight and one full
turn with a wrench.
Figure 98B has the break off bolt head.
Rod Stiffener Requirements
Rod Maximum Rod Length Maximum Spacing Between
Size Without Rod Stiffener Rod Stiffeners
3/8\" 19\" (482mm) 13\" (330mm)
1/2\" 25\" (635mm) 18\" (457mm)
5/8\" 31\" (787mm) 23\" (584mm)
3/4\" 37\" (940mm) 28\" (711mm)
7/8\" 43\" (1092mm) 33\" (838mm)
1\"* 50\" (1270mm) 38\" (965mm)
11/4\"* 60\" (1524mm) 43\" (1092mm)
Fig. SC228 - Hanger Rod Stiffener
Size Range: Secures 3
⁄8\"-16 thru 5
⁄8\"-11 hanger rod
Material: Steel
Function: Secures channel to hanger rod for vertical seismic bracing.
Slight distortion of the channel (strut) may occur upon
installation of rod stiffeners.
Finish: Electro Galvanized. Contact customer service for alternative
finishes and materials.
Weight: Approx. Wt./100: 21.0 Lbs. (9.5kg)
Order By: Figure part number
Note: Order channel separately
11
/2\"
(63.5)
3/8\"-16
Threads
SC228B
SC228BS
N228WO
Fig. 98B
Fig. 98
OPM
* Use with SC228 only.
Seismic Bracing
Seismic Bracing
73 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
TOLCO Fig. 4A - Pipe Clamp for Sway Bracing
Size Range: 21
/2\" (65mm) thru 8\" (200mm) pipe. For sizes smaller than
21
/2\" (65mm) use Fig, 4LA.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada
(cUL) 21
/2\" (65mm) thru 8\" (200mm).
Installation Instructions: Fig. 4A is the “braced pipe” attachment component
of a longitudinal, lateral or riser brace assembly. It is intended to be combine
with the “bracing pipe” and TOLCO transitional and structural attachment
component(s) to form a complete bracing assembly. NFPA 13 guidelines
should be followed.
To Install: Place the Fig. 4A over the pipe to be braced. Attach TOLCO
transitional fitting, either Fig. 980, 910 or 909, to the clamp ears. Tighten bolts
and nuts; torque requirement is a minimum of 50 ft./lbs. (68Nm).
Transitional fitting attachment can pivot for adjustment to proper brace angle.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, pipe size and finish
Note: Please refer to Fig. 4LA for longitudinal brace applications for
1\" (25mm) - 12\" (300mm) pipe sizes.
C
D
A
B
Longitudinal Brace
For
Laterial Brace
Refer to 4LA
Hardware Included
Pipe Max. Horizontal Approx.
Part Size A C D Bolt Design Load (UL) Wt./100
No. in. (mm) in. (mm) in. (mm) in. (mm) Size lbs. (kN) lbs. (kg)
4A-21
/2 21
/2\" (100) 7\" (177.8) 211/16\" (68.3) 3\" (76.2) 1
/2\"-13 1000 (4.45) 134 (60.8)
4A-3 3\" (80) 71
/2\" (190.5) 3\" (76.2) 35
/16\" (84.1) 1
/2\"-13 1000 (4.45) 150 (69.0)
4A-4 4\" (100) 81
/2\" (215.9) 33
/8\" (85.7) 311/16\" (93.7) 1
/2\"-13 1600 (7.11) 221 (100.2)
4A-5 5\" (125) 93
/4\" (247.6) 37
/8\" (98.4) 43
/8\" (111.1) 1
/2\"-13 1600 (7.11) 253 (114.7)
4A-6 6\" (150) 111
/2\" (292.1) 5\" (127.0) 51
/8\" (130.2) 1
/2\"-13 2015 (8.96) 513 (232.7)
4A-8 8\" (200) 131
/4\"(336.5) 611/16\" (169.9) 61
/8\" (155.6) 1
/2\"-13 2015 (8.96) 601 (272.6)
Fig. 980 Fig. 980
Fig. 4A DISCONTINUED
Seismic Bracing
Seismic Bracing
All dimensions in charts and
on drawings are in inches.
Dimensions shown in
parentheses are in millimeters
unless otherwise specified.
74 Eaton B-Line series Fire Protection Solutions
TOLCO Fig. 4L - sway brace attachment (UL listed)
Size Range: 1\" (25mm) through 8\" (200mm) IPS. 10\" (250mm) and 12\" (300mm) not
UL listed
Material: Steel and stainless steel.
Function: For bracing pipe against sway and seismic disturbance.
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL) 1\"
(25mm) through 8\" (200mm) pipe. UL Listed for the following sprinkler type pipes:
Sch. 40, Sch. 10, Bull Moose Eddy Flow, Wheatland Mega Flow, DIN 2448, KSD
3562, KSD 3507. Ask the factory for additional information as it may vary by product
size. For FM Approval information refer to FM Approved page 75. Included in
our Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load, spacing
and placement information relating to OSHPD projects, please refer to our Seismic
Engineering Guidelines, OPM-0052-13.
Installation Instructions: Fig. 4L is the “braced pipe“ attachment component
of a longitudinal and lateral sway brace assembly. It is intended to be combined
with the “bracing pipe“ and TOLCO structural attachment component to form
a complete bracing assembly. NFPA 13 guidelines should be followed. (For
complete detailed instructions see instruction sheet IL309015EN).
To Install: Place the Fig. 4L over the pipe to be braced and tighten bolts. Then
engage “bracing pipe” into jaw opening and tighten set bolt until head snaps off.
Jaw attachment can pivot for adjustment to proper brace angle.
Finish: Plain, Electrogalvanized, Hot Dip Galvanized or Stainless Steel (only for
4\" & 6\" sizes).
Order By: Figure number, pipe size and finish.
Eaton’s B-Line series seismic bracing
components are designed to be
compatible only with other B-Line
series bracing components, resulting
in a listed seismic bracing assembly.
Eaton B-Line Division warranty for
seismic bracing components will
be the warranty provided in Eaton
B-Line Division standard terms and
conditions of sale made available by
Eaton, except that, in addition to the
other exclusions from Eaton B-Line
Division warranty, Eaton makes no
warranty relating to B-Line series
seismic bracing components that are
combined with products not provided
by Eaton.
D
A
CC
A
D
Set Bolt &
Hardware Included
OPM
Lateral
Brace
Longitudinal
Brace
With Plain &
Electrogalvanized Finish
With Hot Dip Galvanized &
Stainless Steel Finish
UL Max. Rec. Load PLN & EG.
Approx.
Part No.
Nom Pipe Size A (Max) C D Bolt Size Logitudinal Lateral
in. (mm) in. in. in. in. lbs. lbs. Wt./100 lbs.
4L-1 1 (25) 5 2 13
/8 1
/2-13 1000 1000 176
4L-11
/4 11
/4 (32) 52
/7 21
/16 15
/9 1
/2-13 1000 1000 182
4L-11
/2 11
/2 (40) 51
/2 21
/3 12
/3 1
/2-13 1000 1000 187
4L-2 2 (50) 62
/7 22
/3 2 1
/2-13 1600 1000 204
4L-21
/2 21
/2 — 67
/9 3 21
/3 1
/2-13 2000 1000 217
4L-65mm — (65) 67
/9 3 21
/3 1
/2-13 700 1000 214
4L-3 3 (80) 73
/7 31
/4 25
/8 1
/2-13 2000 1000 323
4L-31
/2 31
/2 (90) 8 31
/2 27
/8 1
/2-13 2000 1000 343
4L-4*** 4 (100) 83
/7 33
/4 31
/8 1
/2-13 2000** 1000 253
4L-5 5 — 95
/9 43
/8 35
/8 1
/2-13 2000** 1600* 314
4L-125mm — (125) 95
/9 43
/8 35
/8 1
/2-13 1200 1600* 314
4L-6*** 6 — 113
/7 51
/3 44
/7 1
/2-13 2000 1600* 540
4L-150mm — (150) 113
/7 51
/3 44
/7 1
/2-13 1200 1600* 538
4L-8 8 — 133
/5 62
/5 52
/3 1
/2-13 2000 2100* 645
4L-200mm — (200) 133
/5 62
/5 52
/3 1
/2-13 1400 2100* 643
4L-10**** 10 (254) 173
/5 81
/4 71
/4 1
/2-13 NA NA 1349
4L-12**** 12 (300) 193
/5 91
/4 81
/4 1
/2-13 NA NA 1526
* Only UL listed as a lateral brace for use with a 1\" (25mm) pipe as the brace member.
** Only UL listed as a longitudinal brace for use with a 1\" (25mm) thru 11
/2\" (40mm) pipe as the brace member.
*** Fig 4L-4 and Fig 4L-6 are only sizes available in stainless steel 316.
**** FM approved not UL listed.
Updated 4-2-21
Seismic Bracing
Seismic Bracing
75 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
TOLCO Fig. 4L - sway brace attachment (FM approved)
Size Range: 1\" (25mm) through 12\" (300mm) IPS.
Material: Steel.
Function: For bracing pipe against sway and seismic disturbance.
Approvals: Approved by Factory Mutual Engineering (FM), 1\" (25mm) through 12\"
(300mm) pipe. For UL Listed information refer to UL Listed page 74. Included in
our Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load, spacing
and placement information relating to OSHPD projects, please refer to our Seismic
Engineering Guidelines, OPM-0052-13.
Installation Instructions: Fig. 4L is the “braced pipe“ attachment component of a
longitudinal and lateral sway brace assembly. It is intended to be combined with the
“bracing pipe“ and TOLCO™ structural attachment component to form a complete
bracing assembly. NFPA 13 and/or FM guidelines should be followed.
To Install: Place the Fig. 4L over the pipe to be braced and tighten bolts. Then
engage “bracing pipe“ into jaw opening and tighten set bolt until head snaps off.
Jaw attachment can pivot for adjustment to proper brace angle. (For complete
detailed instructions see instruction sheet IL309015EN).
Finish: Plain, Electrogalvanized.
Order By: Figure number, pipe size and finish.
Designed to meet or exceed requirements of FM DS 2-8.
OPM
D
A
CC
D
Set Bolt &
Hardware Included
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components, resulting in a listed seismic bracing
assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty provided in Eaton B-Line Division standard terms and conditions of sale made
available by Eaton, except that, in addition to the other exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing
components that are combined with products not provided by Eaton.
Lateral
Brace
Longitudinal
Brace
With Plain &
Electrogalvanized Finish
Part No.
Nom Pipe
Size
in. (mm)
A
(Max)
in.
C
in.
D
in.
Bolt
Size
in.
FM Max. Rec. Load
Logitudinal
FM Max. Rec. Load
Lateral Approx.
30°-44°
lbs. (kN)
45°-59°
lbs. (kN)
60°-74°
lbs. (kN)
75°-90°
lbs. (kN)
30°-44°
lbs. (kN)
45°-59°
lbs. (kN)
60°-74°
lbs. (kN)
75°-90°
lbs. (kN)
Wt./100
lbs.
4L-1 1 (25) 5 2 13
/8 1
/2-13 1060 (4.72) 1160 (5.16) 1400 (6.23) 1500 (6.68) 1370 (6.10) 1940 (8.63) 2380 (10.59) 2650 (11.79) 176
4L-11
/4 11
/4 (32) 52
/7 21
/16 15
/9 1
/2-13 1060 (4.72) 1160 (5.16) 1400 (6.23) 1500 (6.68) 1370 (6.10) 1940 (8.63) 2380 (10.59) 2650 (11.79) 182
4L-11
/2 11
/2 (40) 51
/2 21
/3 12
/3 1
/2-13 740 (3.30) 1020 (4.54) 1250 (5.57) 920 (4.10) 1370 (6.10) 1940 (8.63) 2380 (10.59) 2650 (11.79) 187
4L-2 2 (50) 62
/7 22
/3 2 1
/2-13 740 (3.30) 1020 (4.54) 1250 (5.57) 920 (4.10) 1420 (6.32) 1990 (8.86) 2440 (10.86) 2720 (12.10) 204
4L-21
/2 21
/2 — 67
/9 3 21
/3 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 220
4L-65mm — (65) 67
/9 3 21
/3 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 218
4L-3 3 (80) 73
/7 31
/4 25
/8 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 323
4L-31
/2 31
/2 (90) 8 31
/2 27
/8 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 343
4L-4 4 (100) 83
/7 33
/4 31
/8 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 253
4L-5 5 — 95
/9 43
/8 35
/8 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 313
4L-125mm — (125) 95
/9 43
/8 35
/8 1
/2-13 520 (2.32) 650 (2.90) 790 (3.52) 1040 (4.63) 1410 (6.28) 1990 (8.86) 2440 (10.86) 2720 (12.10) 312
4L-6 6 — 113
/7 51
/3 44
/7 1
/2-13 870 (3.87) 1200 (5.34) 1460 (6.50) 1630 (7.26) 1560 (6.94) 2210 (9.84) 2710 (12.06) 3020 (13.44) 540
4L-150mm — (150) 113
/7 51
/3 44
/7 1
/2-13 870 (3.87) 1200 (5.34) 1460 (6.50) 1630 (7.26) 1560 (6.94) 2210 (9.84) 2710 (12.06) 3020 (13.44) 538
4L-8 8 — 133
/5 62
/5 52
/3 1
/2-13 1190 (5.30) 1440 (6.41) 1580 (7.03) 1750 (7.79) 1560 (6.94) 2210 (9.84) 2710 (12.06) 3020 (13.44) 645
4L-200mm — (200) 133
/5 62
/5 52
/3 1
/2-13 1190 (5.30) 1440 (6.41) 1580 (7.03) 1750 (7.79) 1560 (6.94) 2210 (9.84) 2710 (12.06) 3020 (13.44) 643
4L-10 10 (254) 173
/5 81
/4 71
/4 1
/2-13 1620 (7.21) 1660 (7.38) 1570 (6.98) 1740 (7.74) 1620 (7.21) 2300 (10.23) 2820 (12.54) 3140 (13.97) 1349
4L-12 12 (300) 193
/5 91
/4 81
/4 1
/2-13 1620 (7.21) 1660 (7.38) 1570 (6.98) 1740 (7.74) 1620 (7.21) 2300 (10.23) 2820 (12.54) 3140 (13.97) 1526
Updated 4-2-21
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
76 Eaton B-Line series Fire Protection Solutions
Size Range: 1\" (25mm) through 8\" (200mm) IPS.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
Approvals: For FM Approval information refer to FM Approved page 77.
Underwriters Laboratories Listed in the USA and Canada (cULus).
Included in our Seismic Engineering Guidelines approved by the State of
California Office of Statewide Health Planning and Development (OSHPD).
For additional load, spacing and placement information relating to OSHPD
projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13.
Installation Instructions: Fig. 4LA can be used as the system attachment
component of a longitudinal or lateral brace assembly. It is intended to be
combined with the “bracing member\" and TOLCO™ transitional attachment
and structural attachment to form a complete bracing assembly. For fire
sprinkler applications NFPA 13 guidelines should be followed.
To Install: Place the Fig. 4LA pipe clamp component over the pipe to be
braced and tighten down the break-off nuts until the hex head portion breaks
off to verify correct installation torque. Next engage brace member (pipe or
strut) with jaw component and tighten break-off head bolt until the hex head
breaks off to verify correct installation torque. Pivot jaw for correct angle and
attach to structure using TOLCO brand transitional attachment and structural
attachment.
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, pipe size and finish.
TOLCO Fig. 4LA - In-Line Sway Brace Attachment (UL Listed)
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Pipe UL Max. Rec. Load Approx.
Part Size A C D Bolt Size Longitudinal Lateral Wt./100
No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kg)
4LA-1 1\" (25) 319/32\" (91.2) 15/16\" (33.5) 15/16\" (33.5) 3/8\"-16 1000 (4.45) NA (NA) 119 (54.0)
4LA-11/4 11/4\" (32) 329/32\" (99.3) 13/8\" (35.3) 13/8\" (35.3) 3/8\"-16 1000 (4.45) NA (NA) 123 (55.8)
4LA-11/2 11/2\" (40) 45/32\" (105.7) 11/2\" (38.5) 11/2\" (38.5) 3/8\"-16 1000 (4.45) NA (NA) 127 (57.6)
4LA-2 2\" (50) 511/32\" (135.6) 21/32\" (51.9) 21/16\" (51.9) 3/8\"-16 1000 (4.45) NA (NA) 142 (64.4)
4LA-21/2 21/2\" (65) 527/32\" (148.7) 25/16\" (58.5) 25/16\" (58.5) 3/8\"-16 1000 (4.45) NA (NA) 173 (78.5)
4LA-3 3\" (80) 61/2\" (164.9) 25/8\" (66.6) 25/8\" (66.6) 3/8\"-16 1000 (4.45) 1000 (4.45) 187 (84.8)
4LA-31/2 31/2\" (90) 7.407\" (188.1) 27/8\" (73.1) 27/8\" (73.1) 3/8\"-16 1000 (4.45) 1000 (4.45) 198 (89.8)
4LA-4 4\" (100) 713/32\" (190.8) 31/8\" (79.5) 31/8\" (79.5) 3/8\"-16 1000 (4.45) 1000 (4.45) 209 (94.8)
4LA-6 6\" (150) 105/8\" (269.9) 49/16\" (115.9) 49/16\" (115.9) 1/2\"-13 1600 (7.12) 1600 (7.12) 521 (236.3)
4LA-8 8\" (200) 1213/16\" (325.5) 59/16\" (143.7) 521/32\" (143.7) 1/2\"-13 2015 (7.12) 2015 (7.12) 629 (285.3)
4LA-10* 10\" (250) 161/2\" (419.1) 71/4\" (184.2) 71/4\" (184.2) 1/2\"-13 NA (NA) NA (NA) 1320 (598.7)
4LA-12* 12\" (300) 181/2\" (469.9) 81/4\" (209.6) 81/4\" (209.6) 1/2\"-13 NA (NA) NA (NA) 1496 (678.6)
4LA-1 thru 4LA-4
4LA-6 thru 4LA-12
Longitudinal
Brace
Lateral Brace
C
A
D
C
A D
OPM
Fig. 980
Fig. 4LA
Fig. 980
Brace
Brace
Fig. 4LA
* FM Approved but not UL Listed.
DISCONTINUED
Seismic Bracing
Seismic Bracing
77 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Longitudinal
Brace
Lateral
Brace
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Size Range: 1\" (25mm) through 12\" (300mm) IPS.
Material: Steel
Function: For bracing pipe against sway and seismic disturbance.
Approvals: Approved by Factory Mutual Engineering (FM), 1\" (25mm)
through 12\" (300mm) pipe.
For UL Listed information refer to UL Listed page 76.
Included in our Seismic Engineering Guidelines approved by the State of
California Office of Statewide Health Planning and Development (OSHPD).
For additional load, spacing and placement information relating to OSHPD
projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13.
Installation Instructions: Fig. 4LA can be used as the system attachment
component of a longitudinal or lateral brace assembly. It is intended to be
combined with the “bracing member\" and TOLCO™ transitional attachment
and structural attachment to form a complete bracing assembly. For fire
sprinkler applications NFPA 13 guidelines should be followed.
To Install: Place the Fig. 4LA pipe clamp component over the pipe to be
braced and tighten down the break-off nuts until the hex head portion breaks
off to verify correct installation torque. Next engage brace member (pipe or
strut) with jaw component and tighten break-off head bolt
until the hex head breaks off to verify correct installation torque. Pivot jaw
for correct angle and attach to structure using TOLCO brand transitional
attachment and structural attachment.
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number, pipe size and finish.
TOLCO Fig. 4LA - In-Line Sway Brace Attachment (FM Approved)
4LA-1 thru 4LA-4
4LA-6 thru 4LA-12
Pipe FM Max. Rec. Load Approx.
Longitudinal & Lateral**
Part Size A C D Bolt Size 30°-44° 45°-59° 60°-74° 75°-90° Wt./100
No. in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kN) lbs. (kg)
4LA-1 1\" (25) 319/32\" (91.2) 15/16\" (33.5) 15/16\" (33.5) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 119 (54.0)
4LA-11/4 11/4\" (32) 329/32\" (99.3) 13/8\" (35.3) 13/8\" (35.3) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 123 (55.8)
4LA-11/2 11/2\" (40) 45/32\" (105.7) 11/2\" (38.5) 11/2\" (38.5) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 127 (57.6)
4LA-2 2\" (50) 511/32\" (135.6) 21/32\" (51.9) 21/16\" (51.9) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 142 (64.4)
4LA-21/2 21/2\" (65) 527/32\" (148.7) 25/16\" (58.5) 25/16\" (58.5) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 173 (78.5)
4LA-3 3\" (80) 61/2\" (164.9) 25/8\" (66.6) 25/8\" (66.6) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 187 (84.8)
4LA-31/2 31/2\" (90) 7.407\" (188.1) 27/8\" (73.1) 27/8\" (73.1) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 198 (89.8)
4LA-4 4\" (100) 713/32\" (190.8) 31/8\" (79.5) 31/8\" (79.5) 3/8\"-16 680 (3.02) 970 (4.31) 1190 (5.29) 1320 (5.87) 209 (94.8)
4LA-6 6\" (150) 105/8\" (269.9) 49/16\" (115.9) 49/16\" (115.9) 1/2\"-13 1620 (7.20) Note 1 Note 3 Note 5 521 (236.3)
4LA-8 8\" (200) 1213/16\" (325.5) 59/16\" (143.7) 521/32\" (143.7) 1/2\"-13 1620 (7.20) Note 2 Note 4 Note 6 629 (285.3)
4LA-10 10\" (250) 161/2\" (419.1) 71/4\" (184.2) 71/4\" (184.2) 1/2\"-13 1620 (7.20) Note 2 Note 4 Note 6 1320 (598.7)
4LA-12 12\" (300) 181/2\" (469.9) 81/4\" (209.6) 81/4\" (209.6) 1/2\"-13 1620 (7.20) Note 2 Note 4 Note 6 1496 (678.6)
** Longitudinal and Lateral Loads are the same except where noted in chart.
Note 1: Longitudinal Load 2260 lbs. (10.05kN) - Lateral Load 2300 lbs. (10.23kN)
Note 2: Longitudinal Load 1660 lbs. (7.38kN) - Lateral Load 2300 lbs. (10.23kN)
Note 3: Longitudinal Load 2010 lbs. (8.94kN) - Lateral Load 2820 lbs. (12.54kN)
Note 4: Longitudinal Load 1570 lbs. (6.98kN) - Lateral Load 2820 lbs. (12.54kN)
Note 5: Longitudinal Load 2220 lbs. (9.87kN) - Lateral Load 3140 lbs. (13.96kN)
Note 6: Longitudinal Load 1740 lbs. (7.74kN) - Lateral Load 3140 lbs. (13.96kN)
C
A
D
C
A D
OPM
Fig. 4LA
Fig. 4LA
Fig. 980 Fig. 980
Brace
Brace DISCONTINUED
Seismic Bracing
Seismic Bracing
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
78 Eaton B-Line series Fire Protection Solutions
Size Range: 3
⁄4\" (20mm) to 8\" (200mm) pipe
Material: Steel
Function: For bracing pipe against sway and seismic disturbance
Approvals: Included in our Seismic Engineering Guidelines approved by the State
of California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to our Seismic Engineering Guidelines, OPM-0052-13.
Standard Finish: Plain or Electro-Plated, Contact customer service for alternative
finishes and materials.
Ordering: Specify part number and finish.
Installation Instructions: Fig. 4B is the “braced pipe” attachment component of
a longitudinal or lateral sway brace assembly. It is intended to be combined with
the “bracing pipe” and transitional and structural attachment component(s) to form
a complete bracing assembly. OSHPD guidelines should be followed.
To Install: Place the Fig. 4B over the pipe to be braced. Attach other transitional
fitting, Fig. 909, 910, 980, or 990. Tighten bolts and nuts. Transitional fitting
attachment can pivot for adjustment to proper brace angle.
TOLCO Figure 4B pipe clamp
Pipe Size Rod Size B C D Bolt Size Approx. Wt./100
Part No. in. (mm) A in. (mm) in. (mm) in. (mm) Lbs. (kg)
4B-3
/4 3
/4\" (20) 3
/8\"-16 1\" (25.4) 27
/8\" (73.0) 25
/8\" (66.7) 5
/16\"-18 56 (25.4)
4B-1 1\" (25) 3
/8\"-16 1\" (25.4) 31
/4\" (82.5) 215/16\" (74.6) 5
/16\"-18 60 (27.2)
4B-11
/4 11
/4\" (32) 3
/8\"-16 1\" (25.4) 39
/16\" (90.6) 31
/4\" (82.5) 5
/16\"-18 74 (33.5)
4B-11
/2 11
/2\" (40) 3
/8\"-16 1\" (25.4) 313/16\" (96.8) 37
/16\" (87.3) 5
/16\"-18 79 (35.8)
4B-2 2\" (50) 3
/8\"-16 11
/2\" (38.1) 51
/8\" (130.2) 45
/8\" (117.5) 5
/16\"-18 156 (70.7)
4B-21
/2 21
/2\" (65) 1
/2\"-13 13
/4\" (44.4) 55
/8\" (142.9) 53
/8\" (136.5) 3
/8\"-16 176 (79.8)
4B-3 3\" (80) 1
/2\"-13 17
/8\" (47.6) 63
/4\" (171.4) 61
/8\" (155.5) 3
/8\"-16 198 (89.9)
4B-31
/2 31
/2\" (90) 1
/2\"-13 2\" (50.8) 71
/4\" (184.1) 63
/4\" (171.4) 3
/8\"-16 219 (99.3)
4B-4 4\" (100) 5
/8\"-11 2\" (50.8) 85
/8\" (219.1) 71
/4\" (184.1) 1
/2\"-13 288 (130.6)
4B-5 5\" (125) 5
/8\"-11 2\" (50.8) 97
/8\" (250.8) 85
/16\" (211.1) 5
/8\"-11 390 (176.9)
4B-6 6\" (150) 3
/4\"-10 21
/8\" (54.0) 1015/16\" (277.8) 91
/2\" (241.3) 5
/8\"-11 448 (203.2)
4B-8 8\" (200) 7
/8\"-9 21
/8\" (54.0) 137
/16\" (341.2) 111
/2\" (292.1) 3
/4\"-10 691 (313.4)
B
D
C
A
Fig. 980
Fig. 980
Fig. 4B
Hanger/Longitudinal Brace
OPM
Eaton’s B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
combined with products not provided by Eaton.
Refer to OPM-0052-13 for approved loads.
Concrete Anchors
79 B-Line series Fire Protection Solutions Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Concrete Anchors
Features:
• Fully threaded, torque-controlled, wedge anchor which is
designed for consistent performance in cracked and
uncracked concrete.
• For use in concrete, structural sand lightweight concrete,
and concrete over metal deck.
• Nominal drill bit size is the same as the anchor diameter.
• ICC-ES listed, ESR-2502, Category 1
• Zinc plated carbon steel body with stainless steel expansion
clip from premium performance.
• Qualified for seismic and wind loading.
Approvals: Included in our Seismic Engineering Guidelines approved by
the State of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information relating to
OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
ICC-ES Certified. See ICC-ESR-2502
UL (Underwriters Laboratories) Listed
FM (Factory Mutual) Approved
Refer to pages 11-20 through 11-23 in Seismic Engineering Guidelines
OPM-0052-13 for approval OSHPD structural attachment data.
AWSD Series - Power Stud+®†
SD2 seismic wedge anchors
Anchor Size
Wedge Anchor Diameter Length Thread Length Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kg)
AWSD-37-300 3
/8\" (9.5) 3\" (76.2) 13
/4\" (44.4) 11.4 (5.2)
AWSD-37-350 3
/8\" (9.5) 31
/2\" (88.9) 21
/4\" (57.1) 12.2 (5.5)
AWSD-37-375 3
/8\" (9.5) 33
/4\" (95.2) 21
/2\" (63.5) 13.2 (6.0)
AWSD-37-500 3
/8\" (9.5) 5\" (127.0) 33
/4\" (95.2) 16.0 (7.2)
AWSD-50-375 1
/2\" (12.7) 33
/4\" (95.2) 21
/8\" (54.0) 23.0 (10.4)
AWSD-50-450 1
/2\" (12.7) 41
/2\" (114.3) 27
/8\" (73.0) 26.6 (12.0)
AWSD-50-550 1
/2\" (12.7) 51
/2\" (139.7) 37
/8\" (98.4) 34.0 (15.4)
AWSD-50-700 1
/2\" (12.7) 7\" (177.8) 53
/8\" (136.5) 38.0 (17.2)
AWSD-62-475 5
/8\" (15.9) 43
/4\" (120.6) 27
/8\" (73.0) 50.3 (22.8)
AWSD-62-500 5
/8\" (15.9) 5\" (127.0) 31
/8\" (79.4) 52.0 (23.6)
AWSD-62-600 5
/8\" (15.9) 6\" (152.4) 41
/8\" (104.8) 58.8 (26.7)
AWSD-62-700 5
/8\" (15.9) 7\" (177.8) 51
/8\" (130.2) 65.2 (29.6)
AWSD-75-550 3
/4\" (19.0) 51
/2\" (139.7) 31
/4\" (82.5) 81.5 (36.9)
AWSD-75-625 3
/4\" (19.0) 61
/4\" (158.7) 4\" (101.6) 94.0 (42.6)
AWSD-75-700 3
/4\" (19.0) 7\" (177.8) 43
/4\" (120.6) 106.5 (48.3)
For loading information, refer to the ICC-ES ESR-2502 evaluation report.
Seismic Wedge Anchor - Data 3
/8\"-16 1
/2\"-13 5
/8\"-11 3
/4\"-10
ANSI Drill Bit Size (in. - mm) 3
/8\" - (9.5mm) 1
/2\" - (12.7mm) 5
/8\" - (15.9mm) 3
/4\" - (19.0mm)
Fixture Clearance Hole (in. - mm) 7
/16\" - (11.1mm) 9
/16\" - (14.3mm) 11/16\" - (17.5mm) 13/16\" - (20.6mm)
Minimum Hole Depth (in. - mm) 25
/8\" - (66.7mm) 23
/4\" - (69.8mm) 41
/4\" - (107.9mm) 5\" - (127.0mm)
Minimum Concrete Thickness (in. - mm) 4\" - (101.6mm) 41
/2\" - (114.3mm) 53
/4\" - (146.0mm) 7\" - (177.8mm)
Max. Tightening Torque (lbs-ft - N•m) 20 lbs-ft - (27.1N•m) 40 lbs-ft - (54.2N•m) 60 lbs-ft - (81.3N•m) 110 lbs-ft - (149.1N•m)
Min. Embedment Depth (in. - mm) 23
/8\" - (60.3mm) 21
/2\" - (63.5mm) 37
/8\" - (98.4mm) 41
/2\" - (114.3mm)
OPM
†
Power Stud+® SD2 is a registered trademark used by DeWalt.
Concrete Anchors
Concrete Anchors
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
80 Eaton B-Line series Fire Protection Solutions
TOLCO Fig. 109DD - DDI+™†
- concrete deck insert - hanger application
NOTES:
1. Mounting holes are standard. If the plate is not mechanically secured to the deck ribs, a jam nut is required to prevent the
anchor bolt from laying over when concrete is poured. There is no structural strength added from the use of a mechanical
fastener to hold the product in place before the pour.
2. Minimum spacing between inserts shall be not less than 3 times the embedment depth or 12 times the anchor diameter
(whichever is greater)
16\" (406mm) x Anchor Dia.
Minimum
‘D’ ‘D’ ‘D’
Edge of Concrete
Edge of Concrete
Edge of Concrete
Fig. 109DD Fig. 109DD Fig. 109DD
16\" (406mm) x Anchor Dia.
Minimum
3
/4\" (19.0mm)
Minimum
11
/4\" 31.8mm)
Minimum
3
/4\" (19.0mm)
Minimum
3
/4\" (19.0mm)
Minimum
16\" (406mm) x Anchor Dia.
Minimum
1î
A
Fig. 109DD
‘D’ 3
/4\" (19.0mm)
Minimum
Size Range: 3
/8\"-16 thru 7
/8\"-9 rod
Material: Steel
Function: For use in concrete filled metal deck (20 GA. min.)
assemblies (i.e. pan deck, Q-deck) applications. After installation, the
threaded male hanger of the insert protrudes below the surface of
the deck. The threaded bolt offers adjustability for precise height
requirements and guarantees the minimum embedment depth. The
longer plate enables a variety of installation locations across the deck.
Pre-mounted drill screws included for installation.
Approvals: International Code Council, Evaluation Service (ICC-ES),
ESR-3958 for concrete, for 3
/8\"-16 thru 5
/8\"-11\" anchor sizes.
Approved for seismic and wind loading.
UL (Underwriters Laboratories) Listed
FM (Factory Mutual) Approved
Finish: Plate: Plain Steel. Rod: Electro-Galvanized.
Order By: Figure number, rod size and finish.
Applications Per NFPA 13 (2010): UL Listed as a component of a
hanger assembly per Section 9.1.1.4.1
See dimensions and installation Detail below.
Note: Fig. 109DD replaces Fig. 109A which has been discontinued.
Bolt Length
8\" (203.2mm)
12\"
(304.8mm)
T
W
†
DDi+™ is a registered trademark used by DEWALT®
Rod Max. Vertical ‘D’ Min. Anchor Approx.
Size T W Load Embedment Depth Wt./100
Part No. in. (mm) in. (mm) lbs. (kn) in. (mm) lbs. (kg)
109DD-3
/8 3
/8\"-16 3
/16\" (4.7) 11
/4\" (31.7) 467 (2.08) 21
/2\" (63.5) 98.1 (44.5)
109DD-1
/2 1
/2\"-13 3
/16\" (4.7) 11
/4\" (31.7) 680 (3.02) 21
/2\" (63.5) 112.8 (51.1)
109DD-5
/8 5
/8\"-11 3
/16\" (4.7) 11
/4\" (31.7) 647 (2.88) 21
/2\" (63.5) 139.3 (63.2)
109DD-3
/4 3
/4\"-10 3
/8\" (9.5) 2\" (50.8) 612 2.72) 21
/2\" (63.5) 112.8 (153.6)
109DD-7
/8 7
/8\"-9 3
/8\" (9.5) 2\" (50.8) 577 (2.56) 21
/2\" (63.5) 381.2 (172.9)
Concrete Anchors
81 B-Line series Fire Protection Solutions Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Concrete Anchors
TOLCO Fig. 109DD-DDI+™†
- concrete deck insert - brace application
NOTES:
1. Mounting holes are standard. If the plate is not mechanically secured to the deck ribs, a jam nut is required to prevent the
anchor bolt from laying over when concrete is poured. There is no structural strength added from the use of a mechanical
fastener to hold the product in place before the pour.
2. Minimum spacing between inserts shall be not less than 3 times the embedment depth or 12 times the anchor diameter
(whichever is greater)
16\" (406mm) x Anchor Dia.
Minimum
‘D’ ‘D’ ‘D’ Edge of Concrete
Edge of Concrete
Edge of Concrete
Fig. 109DD Fig. 109DD Fig. 109DD
16\" (406mm) x Anchor Dia.
Minimum
3
/4\" (19.0mm)
Minimum
11
/4\" (25.4mm)
Minimum
3
/4\" (19.0mm)
Minimum
3
/4\" (19.0mm)
Minimum
16\" (406mm) x Anchor Dia.
Minimum
Detail 1 Detail 2 Detail 3
Size Range: 3
/8\"-16 thru 7
/8\"-9 rod
Material: Steel
Function: For use in concrete filled metal deck (20 GA. min.) assemblies (i.e.
pan deck, Q-deck) applications. After installation, the threaded male hanger of
the insert protrudes below the surface of the deck. The threaded bolt offers
adjustability for precise height requirements and guarantees the minimum
embedment depth. The longer plate enables a variety of installation locations
across the deck. Pre-mounted drill screws included for installation.
Approvals: International Code Council, Evaluation Service (ICC-ES),
ESR-3958 for concrete, for 3
/8\"-16 thru 5
/8\"-11\" anchor sizes.
Approved for seismic and wind loading.
UL (Underwriters Laboratories) Listed
FM (Factory Mutual) Approved
Finish: Plate: Plain Steel. Rod: Electro-Galvanized.
Order By: Figure number, rod size and finish.
Applications Per NFPA 13 (2010): UL Listed as a component of a hanger
assembly per Section 9.1.1.4.1
See dimensions and installation Detail below.
Note: Fig. 109DD replaces Fig. 109A which has been discontinued.
†
DDi+™ is a registered trademark used by DEWALT®
Bolt Length
8\" (203.2mm)
12\"
(304.8mm)
T
W
Seismic bracing design load calculated in compliance with the requirements of IBC 2015 / CBC 2016.
Details 1 & 2 Detail 3
Rod T W Max. Horizontal Load Max. Horizontal Load ‘D’ Min. Anchor Approx.
Size Brace At 45° Brace At 45° Embedment Depth Wt./100
Part No. in. (mm) in. (mm) lbs. (kN) lbs. (kN) in. (mm) lbs. (kg)
109DD-3
/8 3
/8\"-16 3
/16\" (4.7) 11
/4\" (31.7) 311 (1.38) 257 (1.14) 21
/2\" (63.5) 98.1 (44.5)
109DD-1
/2 1
/2\"-13 3
/16\" (4.7) 11
/4\" (31.7) 424 (1.89) 332 (1.48) 21
/2\" (63.5) 112.8 (51.1)
109DD-5
/8 5
/8\"-11 3
/16\" (4.7) 11
/4\" (31.7) 482 (2.14) 363 (1.61) 21
/2\" (63.5) 139.3 (63.2)
109DD-3
/4 3
/4\"-10 3
/8\" (9.5) 2\" (50.8) 482 (2.14) 363 (1.61) 21
/2\" (63.5) 338.7 (153.6)
109DD-7
/8 7
/8\"-9 3
/8\" (9.5) 2\" (50.8) 482 (2.14) 363 (1.61) 21
/2\" (63.5) 381.2 (172.9)
Concrete Anchors
Concrete Anchors
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
82 Eaton B-Line series Fire Protection Solutions
Features:
• Wood-Knocker™ II concrete inserts are installed onto wooden
forms used to support newly poured concrete floor slabs, roof
slabs or walls.
• When the forms are stripped, the color-coded flange is
visibly embedded in the concrete surface.
• The unique, six sided impact plate offers resistance to rotation
within the concrete as threaded rod is being installed.
• Suitable for overhead installations such as suspending cable
tray, pipe hangers, strut and conduit.
• Color coded by size for all trades.
• UL and FM approved.
• Lowest installation cost.
Approvals: Qualified for static, wind, and seismic loading in concrete.
Included in our Seismic Engineering Guidelines approved by the State
of California Office of Statewide Health Planning and Development
(OSHPD). For additional load, spacing and placement information
relating to OSHPD projects, please refer to our Seismic Engineering
Guidelines, OPM-0052-13.
ICC-ES Certified. See ICC-ESR-3657
UL (Underwriters Laboratories) Listed
FM (Factory Mutual) Approved
Refer to pages 11-26 through 11-27 in Seismic
Engineering Guidelines OPM-0052-13 for approval OSHPD
structural attachment data.
ACPW Series - Wood-Knocker™†
II
* Based on normal weight concrete with minimum compression strength of 3000 psi.
Allowable load capacities are calculated using applied safety factor of 4.0.
For additional loading information contact factory.
Minimum embedment depth is 2\".
Wood Knocker™ - Data 1
/4\" 3
/8\" 1
/2\" 5
/8\" 3
/4\"
Insert Thread Length (in.) 3
/8 5
/8 11/16 15/16 11
/8
Plastic Flange Diameter (in.) 13
/8 13
/8 13
/8 15
/8 15
/8
Thread Size (UNC) 1
/4\"-20 3
/8\"-16 1
/2\"-13 5
/8\"-11 3
/4\"-10
Overall Length (in.) 17
/8 17
/8 17
/8 17
/8 17
/8
Min. Insert Spacing (in.) 9 9 9 12 12
Min. End Distance (in.) 6 6 6 9 9
Load Capacity Tension (lbs) * 930 1200 1200 1160 1160
Load Capacity Shear (lbs) * 370 1330 1840 2800 2800
Catalog Rod Color
Number Diameter
ACPW-25-2 1
/4\" Brown
ACPW-37-2 3
/8\" Green
ACPW-3750-2 3
/8\"-1
/2\" Gray
ACPW-50-2 1
/2\" Yellow
ACPW-62-2 5
/8\" Red
ACPW-75-2 3
/4\" Purple
†
Wood-Knocker™ is a registered trademark used by DeWalt.
ACPW-50
shown
OPM
Concrete Anchors
83 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Concrete Anchors
Features:
• Bang-It™+ concrete inserts are designed for installation in and through metal
composite deck used to support newly poured concrete floors or roof slabs.
• After installation, the protective sleeve of the insert protrudes below the
surface of the deck, allowing overhead attachment of threaded rod.
• The unique, six sided impact plate offers resistance to rotation within the
concrete as threaded rod is bing installed.
• Suitable for overhead installations such as suspending cable tray,
pipe hangers, strut and conduit.
• Color coded by size for all trades.
• Lowest installation cost.
Approvals: Qualified for static, wind, and seismic loading in concrete. Included in
our Seismic Engineering Guidelines approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional load, spacing
and placement information
relating to OSHPD projects, please refer to our Seismic Engineering Guidelines,
OPM-0052-13.
ICC-ES Certified. See ICC-ESR-3657
UL (Underwriters Laboratories) Listed
FM (Factory Mutual) Approved
Refer to pages 11-28 through 11-32 in Seismic Engineering Guidelines
OPM-0052-13 for approval OSHPD structural attachment data.
ACPD Series - Bang-It™†
+ anchors
* Based on sand lightweight and normal weight concrete with minimum compression strength of 3000 psi over steel deck.
Allowable load capacities are calculated using applied safety factor of 4.0.
For additional loading information contact factory.
Minimum insert spacing of 6\", minimum end spacing 6\".
Bang-It™ - Data 1
/4\" 3
/8\" 1
/2\" 5
/8\" 3
/4\"
Metal Hole Saw Diameter (in.) 13/16 13/16 13/16 13
/16 13
/16
Drilling Speed (rpm) 700-900 700-900 700-900 500-700 500-700
Insert Thread Length (in.) 3
/8 5
/8 11/16 15/16 11
/8
Length of Sleeve (in.) 33
/8 33
/8 33
/8 33
/8 33
/8
Thread Size (UNC) 1
/4\"-20 3
/8\"-16 1
/2\"-13 5
/8\"-11 3
/4\"-10
Embedment Depth (in.) 2 2 2 2 2
Upper Deck Tension Load (lbs) * 1115 1915 2370 2935 2935
Lower Deck Tension Load (lbs) * 830 830 830 930 990
Upper Deck Shear Load (lbs) * 835 1115 1115 1115 1115
Lower Deck Shear Load (lbs) * 625 840 840 840 840
Catalog Rod Color
Number Diameter
ACPD-25 1
/4\" Brown
ACPD-37 3
/8\" Green
ACPD-3750-2 3
/8\"-1
/2\" Gray
ACPD-50 1
/2\" Yellow
ACPD-62 5
/8\" Red
ACPD-75 3
/4\" Purple
Catalog
Number Description
ACPD-HS813-2 13/16\" Carbide Hole Saw for 1
/4\", 3
/8\", 1
/2\"
ACPD-HS1188-2 13
/16\" Carbide Hole Saw for 5
/8\", 3
/4\"
†
Bang-It™ is a registered trademark used by DeWalt
OPM
Concrete Anchors
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
84 Eaton B-Line series Fire Protection Solutions
Concrete Anchors
Features:
• For use in normal-weight concrete, structural sand lightweight concrete and concrete over metal deck.
• Anchor design allows for shallow embedment and mechanically interlocks with base material.
• Internally threaded anchor for easy adjustment and removability of threaded rod or bolt.
• Fast anchor installation with a powered impact wrench.
• Suitable for overhead applications such as suspending cable tray, strut, pipe hangers and conduit.
• Made of Zinc Plated carbon steel.
• Setting tool included.
• Approvals: ICC-ES certified. See ICC-ESR-2272.
FM (Factory Mutual) Approved
ATM Series - self-tapping machine screw anchors
Self-Tapping Machine Screw Anchor - Data 3
/8\"
ANSI Drill Bit Size (in. - mm) 1
/2\" - (12.7mm)
Minimum Concrete Thickness (in. - mm) 4\" - (101.6mm)
Max. Tightening Torque (lbs-ft - N•m) 8 lbs-ft - (10.8N•m)
Min. Embedment Depth (in. - mm) 13
/8\" - (41.3mm)
Load Capacity Tension (lbs - kN)** 540 lbs - (2.40kN)
Load Capacity Shear (lbs - kN)** 825 lbs - (3.67kN)
**Based on concrete compression strength of 4000 psi
in uncracked concrete using applied safety factor of
4.0. For additional loading information contact factory.
For ultimate strength design data in cracked and
uncracked concrete, refer to ICC-ES ESR-2272
evaluation report.
Anchor Thread Size Thread Length Wt./100
Part No. in. (mm) lbs. (kg)
ATM-37 3
/8\"-16 11/16\" (17.6) 5.2 (2.3)
Features:
• For use in racking, shelving, material handling, structural anchorage, masonry AND food
& beverage facilities.
• One piece heavy-duty anchor with a finished hex-head.
• Fits standard fixture hole dimensions in fabricated steel.
• Fast installation and immediate loading reduces downtime.
• For proper performance, screw anchors must be installed with the corresponding bits.
The bits have a matched tolerance range designed to provide optimum performance.
ACB Series - concrete screw bolts
* Based on concrete compression strength of 4000 psi in uncracked concrete using applied safety factor of
4.0. For additional loading information contact factory.
For ultimate strength design data in cracked and uncracked concrete, refer to ICC-ES ESR-3889 evaluation report.
Concrete Bolt Diameter Length Thread Length Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kg)
ACB-25-175-2 1
/4\" (6.3) 13
/4\" (44.4) 15
/8\" (41.3) 3.5 (1.6)
ACB-25-225-2 1
/4\" (6.3) 21
/4\" (57.1) 2\" (50.8) 4.2 (1.9)
ACB-25-300-2 1
/4\" (6.3) 3\" (76.2) 23
/4\" (69.8) 5.0 (2.3)
ACB-37-175-2 3
/8\" (9.5) 13
/4\" (44.4) 11
/2\" (38.1) 7.8 (3.5)
ACB-37-250-2 3
/8\" (9.5) 21
/2\" (63.5) 21
/4\" (57.1) 10.2 (4.6)
ACB-37-300-2 3
/8\" (9.5) 3\" (76.2) 23
/4\" (69.8) 11.6 (5.3)
ACB-37-400-2 3
/8\" (9.5) 4\" (101.6) 33
/4\" (95.2) 14.8 (6.7)
Concrete Screw Bolts - Data 1
/4\" 3
/8\"
ACB Drill Bit Size (in. - mm) 1
/4\" - (6.3mm) 3
/8\" - (9.5mm)
Concrete Screw Tolerance Range (in. - mm) 0.255\" - 0.259\" - (6.5mm - 6.6mm) 0.385\" - 0.389\" - (9.8mm - 9.9mm)
Min. Embedment Depth (in. - mm) 1\" - (25.4mm) 11
/2\" - (38.1mm)
Load Capacity Tension (lbs - kN) * 335 lbs. - (1.49kN) 630 lbs. - (2.80kN)
Load Capacity Shear (lbs - kN) * 520 lbs. - (2.31kN) 1170 lbs. - (5.20kN)
Brackets
85 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Brackets
B3065 - Welded bracket - light duty
Max. Recommended Load: 275 lbs. (1.22kN)
Material: Steel
Function: Recommended for supporting pipe on top or
hanging through support bracket outward from mounting
surface.
Approvals: Conforms to Federal Specification WW-H-171E
& A-A-1192A, Type 32 and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 31.
Finish: Plain
Note: Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By: Figure number and finish
1\"
(25.4)
C
A
B
B3068 - Welded bracket - light duty
Material: Steel
Function: Recommended for suspending pipe outward from
mounting surface.
Approvals: Conforms to Federal Specification WW-H-171E &
A-A-1192A, Type 32 and Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 31.
Finish: Plain or Electro-Galvanized.
Contact customer service for
alternative finishes and materials.
Order By: Part number, hole size ‘H’, and finish
A B C Design Load * Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3065-1 13\" (330.2) 9\" (228.6) 111
/2\" (292.1) 275 (1.22) 571 (259.0)
B3065-2 17\" (431.8) 13\" (330.2) 151
/2\" (393.7) 275 (1.22) 769 (348.8)
B3065-3 23\" (584.2) 19\" (482.6) 211
/2\" (546.1) 275 (1.22) 1057 (479.4)
B
1
1
/2\"
(38.1)
H Dia.
Specify
C
A
A
9
/16\" Dia.
(14.3)
2 Holes
9
/16\" Dia.
(14.3)
2 Holes
A B C H Dia. Design Load * Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3068-1 9\" (228.6) 8\" (203.2) 61
/2\" (165.1) Specify (Specify) 275 (1.22) 360 (163.3)
B3068-2 13\" (330.2) 12\" (304.8) 101
/2\" (266.7) Specify (Specify) 275 (1.22) 582 (264.0)
B3068-3 19\" (482.6) 18\" (457.2) 161
/2\" (419.1) Specify (Specify) 275 (1.22) 860 (390.1)
* Design load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
* Design load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
Brackets
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
86 Eaton B-Line series Fire Protection Solutions
Brackets
B3064 - Adjustable strut bracket
Material: Steel
Function: Designed for supporting pipe from walls or
structures where lateral adjustment is required.
Standard Finish: Plain or Electro-Galvanized
Order By: Part number and finish.
A B Design Load * Approx. Wt./100
Part No. in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3064-1 15\" (381.0) 12\" (304.8) 590 (2.62) 660 (299.4)
B3064-2 21\" (533.4) 18\" (457.2) 310 (1.38) 1004 (455.4)
B3064-3 27\" (685.8) 24\" (609.6) 170 (0.75) 1346 (610.5)
9
/16\" Dia. (14.3)
2 Holes
3
/8\"
(9.5)
2\"
(50.8)
B22 Channel
B32 Channel
B
1
1
/4\"
(31.7)
1
1
/4\"
(31.7)
1
5
/8\"
(41.2)
45°
A
B3066 - Welded bracket - medium duty
Max. Recommended Load: 800 lbs. (3.56kN)
Material: Steel
Function: Recommended for supporting pipe on
top or hanging through support bracket outward
from mounting surface.
Approvals: Conforms to Federal Specification
WW-H-171E & A-A-1192A, Type 33 and
Manufacturers Standardization Society
ANSI/MSS SP-69 & SP-58, Type 32.
Finish: Plain. Contact customer service for
alternative finishes and materials.
Order By: Figure number and finish
B
C
A
1\"
(25.4)
13/16\" Dia.
(20.6)
2 Holes
A B C Design Load * Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3066-0 18\" (457.2) 12\" (304.8) 151
/2\" (393.7) 800 (3.56) 1577 (715.3)
B3066-1 24\" (609.6) 18\" (457.2) 211
/2\" (546.1) 800 (3.56) 2578 (1169.4)
B3066-2 30\" (762.0) 24\" (609.6) 271
/2\" (698.5) 800 (3.56) 4446 (2016.7)
* Design load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
* Design load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
Brackets
Brackets
87 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3067 - Welded bracket - heavy duty
Mtg. Hole H A B C D
Part No. in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3067-0 11
/8\" (28.6) 18\" (457.2) 12\" (304.8) 151
/4\" (387.3) ** **
B3067-1 11
/8\" (28.6) 24\" (609.6) 18\" (457.2) 211
/4\" (539.7) 21
/2\" (63.5)
B3067-2 11
/8\" (28.6) 30\" (762.0) 24\" (609.6) 271
/4\" (692.1) 21
/2\" (63.5)
B3067-3 11
/8\" (28.6) 36\" (914.4) 30\" (762.0) 33\" (838.2) 21
/2\" (63.5)
B3067-4 11
/8\" (28.6) 42\" (1066.8) 36\" (914.4) 39\" (990.6) 31
/2\" (88.9)
B3067-5 11
/8\" (28.6) 50\" (1270.0) 42\" (1066.8) 46\" (1168.4) 31
/2\" (88.9)
Design Load * Approx. Wt./100
Part No. Lbs. (kN) Lbs. (kg)
B3067-0 1850 (8.23) 2195 (995.6)
B3067-1 1850 (8.23) 4398 (1994.9)
B3067-2 1850 (8.23) 6294 (2854.9)
B3067-3 1850 (8.23) 7196 (3264.1)
B3067-4 1850 (8.23) 13197 (5986.2)
B3067-5 1850 (8.23) 15795 (7164.6)
B
H
3 Holes
Only one hole in top for B3067-0
C
A
D
Max. Recommended Load: 3000 lbs. (13.34kN)
Material: Steel
Function: Recommended for supporting pipe on top or
hanging through support bracket outward from mounting
surface.
Approvals: Conforms to Federal Specification WW-H-171E
& A-A-1192A, Type 33 and Manufacturers Standardization
Society ANSI/MSS SP-69 & SP-58, Type 33.
Finish: Plain or Electro-Galvanized. Contact customer
service for alternative finishes and materials.
Order By: Part number and finish
** One Hole
1\"
(25.4)
B3067-0
Shown
* Design load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
Brackets
Brackets
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
88 Eaton B-Line series Fire Protection Solutions
B3069W - Welded knee bracket
Size Range: 1
/2\" (15mm) thru 8\" (200mm) pipe
Material: Steel
Function: Recommended for suspending pipe outward from mounting surface.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes
and materials.
Note: Maximum “L” dimension 16\" (406.4mm).
Order By: Figure number, pipe size, (**) “L” dimension and finish
Pipe Size Hole Size H Max. Rec. Load ***
Part No. in. (mm) in. (mm) Lbs. (kN)
B3069W-1
/2-** 1
/2\" (15) 9
/16\" (14.3) 450 (2.00)
B3069W-3
/4-** 3
/4\" (20) 9
/16\" (14.3) 450 (2.00)
B3069W-1-** 1\" (25) 9
/16\" (14.3) 450 (2.00)
B3069W-11
/4-** 11
/4\" (32) 9
/16\" (14.3) 450 (2.00)
B3069W-11
/2-** 11
/2\" (40) 9
/16\" (14.3) 450 (2.00)
B3069W-2-** 2\" (50) 9
/16\" (14.3) 450 (2.00)
B3069W-21
/2-** 21
/2\" (65) 9
/16\" (14.3) 450 (2.00)
B3069W-3-** 3\" (80) 9
/16\" (14.3) 450 (2.00)
B3069W-31
/2-** 31
/2\" (90) 9
/16\" (14.3) 450 (2.00)
B3069W-4-** 4\" (100) 11/16\" (17.5) 450 (2.00)
B3069W-5-** 5\" (125) 11/16\" (17.5) 450 (2.00)
B3069W-6-** 6\" (150) 11/16\" (17.5) 450 (2.00)
B3069W-8-** 8\" (200) 11/16\" (17.5) 450 (2.00)
H
L
B3069E - “O” Bracket
Size Range: 1
/2\" (15mm) thru 8\" (200mm) pipe
Material: Carbon Steel
Function: Recommended for suspending pipe outward from mounting surface.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Note: Maximum “L“ dimension 16\" (406.4mm).
Order By: Figure number, pipe size, (**) “L” dimension and finish
Pipe Size Hole Size H Max. Rec. Load ***
Part No. in. (mm) in. (mm) Lbs. (kN)
B3069E-1
/2-** 1
/2\" (15) 9
/16\" (14.3) 65 (0.29)
B3069E-3
/4-** 3
/4\" (20) 9
/16\" (14.3) 65 (0.29)
B3069E-1-** 1\" (25) 9
/16\" (14.3) 65 (0.29)
B3069E-11
/4-** 11
/4\" (32) 9
/16\" (14.3) 65 (0.29)
B3069E-11
/2-** 11
/2\" (40) 9
/16\" (14.3) 65 (0.29)
B3069E-2-** 2\" (50) 9
/16\" (14.3) 65 (0.29)
B3069E-21
/2-** 21
/2\" (65) 9
/16\" (14.3) 65 (0.29)
B3069E-3-** 3\" (80) 9
/16\" (14.3) 65 (0.29)
B3069E-31
/2-** 31
/2\" (90) 9
/16\" (14.3) 65 (0.29)
B3069E-4-** 4\" (100) 11/16\" (17.5) 65 (0.29)
B3069E-5-** 5\" (125) 11/16\" (17.5) 65 (0.29)
B3069E-6-** 6\" (150) 11/16\" (17.5) 65 (0.29)
B3069E-8-** 8\" (200) 11/16\" (17.5) 65 (0.29)
H
L
** Length to be specified as shown on the drawing.
** Length to be specified as shown on the drawing.
*** Load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
*** Load based on a safety factor of 5 and reduced by 250 lbs per NFPA.
Upper Attachments
89 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Upper Attachments
Part No. Pipe Size A B C Hole Dia. D Thread Size Approx. Wt./100
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) E Lbs. (kg)
78-3
/8 1
/2\" - 2\" (15 - 60) 3\" (76.2) 21
/8\" (54.0) 11
/8\" (28.6) 5
/16\" (7.9) 3
/8\"-16 15 (6.8)
Size Range: 3
/8\"-16 rod
Material: Pre-Galvanized Steel
Function: Attachment to wood beams, ceilings, metal decks
or walls. Can also be welded to steel beams.
Approvals: Underwriters Laboratories Listed in the USA (UL)
and Canada (cUL). Additionally, UL has listed the Fig. 78 with
fasteners as shown in the table below.
Finish: Plain or Electro-Galvanized. Contact customer service
for alternative finishes and materials.
Order By: Figure number, rod size and finish
Patent #5,702,077
UL Listed Fastener Table
Pipe Size Qty Fastener Type Material
1
/2\" - 2\" 2 #14 x 11
/4\" A-point hex-washer-head sheet metal screw Wood
21
/2\" - 4\" 2 1
/4\" x 11
/2\" wood screws* Wood
1
/2\" - 2\" 2 1
/4\" x 1\" tek screws Metal (18 gauge)
1
/2\" - 2\" 2 #14 x 11
/4\" A-point hex-washer-head sheet metal screw Wood
1
/2\" - 2\" 2 #14 x 2\" A-point-hex-washer-head sheet metal screw Wood thru 5
/8\" gyp board
* No pre-drilling
TOLCO Fig. 78 - all steel ceiling plate
A B
C
D
(2 Holes)
E
TOLCO Fig. 51 - side beam bracket for NFPA rod & fastener sizing
Size Range: 3
/8\"-16 thru 1
/2\"-13 rod, 1
/2\" (15mm) thru 8\" pipe (200mm)
Material: Steel
Function: Recommended for attaching hanger rod to side of beams or walls.
Designed to accommodate current rod schedule and fastener requirements per
National Fire Protection Association (NFPA) Pamphlet 13.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL), and Factory Mutual Engineering approved.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number and finish
Part No. Pipe Size Rod A B C Hole 1 Hole 2 Approx. Wt./100
in. (mm) Size in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
51NFPA-3
/8x3
/8 1
/2\" - 2\" (15 - 60) 3
/8\"-16 2\" (50.8) 3
/4\" (19.0) 2\" (50.8) 7
/16\" (11.1) 7
/16\" (11.1) 35 (15.9)
51NFPA-3
/8x1
/2 21
/2\" - 4\" (65 - 100) 3
/8\"-16 2\" (50.8) 3
/4\" (19.0) 2\" (50.8) 9
/16\" (14.3) 7
/16\" (11.1) 34 (15.4)
51NFPA-1
/2x1
/2 5\" - 6\" (125 - 150) 1
/2\"-13 21
/2\" (63.5) 3
/4\" (19.0) 21
/2\" (63.5) 9
/16\" (14.3) 9
/16\" (14.3) 71 (32.2)
51NFPA-1
/2x5
/8 8\" (200) 1
/2\"-13 21
/2\" (63.5) 3
/4\" (19.0) 21
/2\" (63.5) 11/16\" (17.5) 9
/16\" (14.3) 70 (31.7)
Hole 1
Hole 2
B
B
C
A
A
Larger pipe sizes can be hung with reduced spacing.
Upper Attachments
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
90 Eaton B-Line series Fire Protection Solutions
Upper Attachments
Size Range: 3
/8\"-16 thru 7
/8\"-9 rod
Material: Steel
Function: Recommended for attaching hanger rod to side of beams or walls.
Approvals: 3
/8\"-16 - Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL), and Factory Mutual Engineering (FM) approved.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, rod size and finish
Size Range: 1
/2\" (15mm) thru 4\" (100mm) pipe (3
/8\"-16 rod)
Material: Stainless Steel Type 304 or 316
Function: Recommended for attaching hanger rod to steel or wood
beams. Tapped hole allows easy adjustment of hanger rod.
Approvals: Underwriters Laboratories Listed in the USA (UL) and
Canada (cUL), and Factory Mutual Engineering (FM) approved for 1
/2\"
(15mm) thru 4\" (100mm) pipe.
Order By: Figure number
Note: Available only in Stainless Steel materials.
Per NFPA 13: 1
/2\" (15mm) thru 2\" (50mm) pipe use 3
/8\"-16 fastener;
21
/2\" (65mm) thru 4\" (100mm) pipe, use 1
/2\"-13 fastener.
TOLCO Fig. 50 - side beam bracket
C
A
A
B
H
H
B
3
/8\"-16
2
5
/8\"
(66.7)
1\"
(25.4)
1
1
/4\"
(31.7)
7
/16\"
(11.1)
9
/16\"
(14.3)
Part No. Rod A B C Hole Size H Approx. Wt./100
Size in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kg)
50-3
/8 3
/8\"-16 2\" (50.8) 3
/4\" (19.0) 2\" (50.8) 7
/16\" (11.1) 35 (15.9)
50-1
/2 1
/2\"-13 2\" (50.8) 3
/4\" (19.0) 2\" (50.8) 9
/16\" (14.3) 35 (15.9)
50-5
/8 5
/8\"-11 2\" (50.8) 3
/4\" (19.0) 2\" (50.8) 11/16\" (17.5) 32 (14.5)
50-3
/4 3
/4\"-10 21
/2\" (63.5) 3
/4\" (19.0) 21
/2\" (63.5) 13/16\" (20.6) 110 (49.9)
50-7
/8 7
/8\"-9 21
/2\" (63.5) 3
/4\" (19.0) 21
/2\" (63.5) 15/16\" (23.8) 100 (45.3)
Material: Steel
Function: — Recommended for supporting pipe at various distances
from wall or column.
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number and finish
B3061 - Angle bracket
A
B
Part No. Size A B Hole Size Max. Rec. Load Approx. Wt./100
in. (mm) Size in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B3061-1 1 3\" (76.2) 2\" (50.8) 7
/16\" (11.1) 180 (0.80) 46 (20.8)
B3061-2 2 4\" (101.6) 3\" (76.1) 7
/16\" (11.1) 180 (0.80) 65 (29.5)
B3061-3 3 3\" (76.2) 2\" (50.8) 9
/16\" (14.3) 390 (1.73) 85 (38.5)
B3061-4 4 4\" (101.6) 3\" (76.1) 9
/16\" (14.3) 390 (1.73) 115 (52.1)
Part No. Approx. Wt./100
Lbs. (kg)
56 20 (9.1)
TOLCO Fig. 56 - tapped side beam connector (stainless steel)
Upper Attachments
Upper Attachments
91 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 rod, pipe sizes 1
/2\" (15mm) thru 4\" (100mm)
Material: Pre-Galvanized Steel
Function: Practical and economical bracket used to support piping from wood, concrete
or steel beams.
Features: Unique design allows rod to be easily threaded into bracket. Offset design
permits unlimited rod adjustment. Center mounting hole will accept 3
/8\" and 1
/2\" fastener
bolts. Per NFPA 13: 1
/2\" (15mm) thru 2\" (50mm) pipe requires 3
/8\" fastener, 21
/2\" (65mm)
thru 4\" (100mm) pipe requires 1
/2\" fastener.*
Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL), and
Factory Mutual Engineering approved thru 4\" (100mm) pipe.
Finish: Pre-Galvanized
Order By: Figure number and finish
*Note: Additionally UL has listed the Fig. 58 with fasteners as shown in table below.
TOLCO Fig. 58 - threaded side beam bracket
A
C
2 - 1
/4\" x 2\" Lag Bolts
(No Pre-Drilling
Up to 4\" (100mm) pipe
Per NFPA
1 - 3
/8\" or 1
/2\" Lag Bolts
Up to 4\" (100mm) pipe
2 - #16 x 2\"
Drive Screws 1
/2\" (15mm) - 4\" (100mm) pipe
Bolt & Hex Nut
Up to 4\" (100mm) pipe
2 - #14 x 1\"
Tek Type Screws
Into Min. 16 Gauge Steel
Up to 4\" (100mm) pipe
B
UL Listed Fastener Table
Pipe Size Qty Fastener Type Material
2\" 2 #16 x 2\" Drive screws Wood
2\" 1 3
/8\" Lag bolt Wood
21
/2\" - 4\" 1 1
/2\" Lag bolt Wood
31
/2\" 2 1
/4\" x 11
/2\" Lag bolts Wood
4\" 2 1
/4\" x 2\" Lag bolts ** Wood
4\" 2 1
/4\" x 1\" Tek screws Metal (15 gauge)
4\" 2 1
/4\" x 1\" Tek screws Metal (16 gauge)
** No pre-drilling
Part No. Pipe Size Rod A B C Approx. Wt./100
in. (mm) Size in. (mm) in. (mm) in. (mm) Lbs. (kg)
58 1
/2\" - 4\" (15 - 100) 3
/8\"-16 23
/4\" (69.8) 11
/2\" (38.1) 11
/8\" (28.6) 14 (6.3
Larger pipe sizes can be hung with reduced spacing.
Threaded Accessories
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
92 Eaton B-Line series Fire Protection Solutions
B3200 - Weldless Eye Nut
Size Range: 3
/8\"-16 thru 21
/2\"-41
/2 machine thread.
Material: Forged Steel
Quality Assurance: Conforms to the requirements of NCA 3800.
Threads: Tapped UNC Class 2B. Right hand threads are standard. Left
hand threads supplied upon request (B3200L).
Function: Used on piping installations where high strength and swivel
action are required. Left hand tap is also available.
Approvals: Approvals: Included in our Seismic Engineering Guidelines
approved by the State of California Office of Statewide Health Planning
and Development (OSHPD). For additional load, spacing and placement
information relating to OSHPD projects, please refer to our Seismic
Engineering Guidelines, OPM-0052-13.
Conforms to Federal Specification WW-H-171E & A-A-1192A, Type 17 and
Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 17.
Finish: Plain. Contact customer service for alternative finishes and
materials.
Order By: Figure number and finish.
A
(Rod Size)
Hanger Rod Not
Included
E
F
B
C
F
A
D
Rod Size B C D E F G
Part No. A in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
B3200-3
/8 3
/8\"-16 11
/2\" (38.1) 13
/16\" (30.2) 1
/2\" (12.7) 2\" (50.8) 13
/8\" (34.9) 11/16\" (17.5)
B3200-1
/2 1
/2\"-13 11
/2\" (38.1) 13
/16\" (30.2) 1
/2\" (12.7) 2\" (50.8) 13
/8\" (34.9) 11/16\" (17.5)
B3200-5
/8 5
/8\"-11 11
/2\" (38.1) 13
/16\" (30.2) 1
/2\" (12.7) 2\" (50.8) 13
/8\" (34.9) 11/16\" (17.5)
B3200-3
/4 3
/4\"-10 11
/2\" (38.1) 13
/16\" (30.2) 1
/2\" (12.7) 2\" (50.8) 13
/8\" (34.9) 11/16\" (17.5)
B3200-7
/8 7
/8\"-9 2\" (50.8) 111/16\" (42.9) 3
/4\" (19.0) 25
/8\" (66.7) 115/16\" (49.2) 1\" (25.4)
Design Load
650°F (343°C) 750°F (399°C) Approx. Wt./100
Part No. Lbs. (kN) Lbs. (kN) Lbs. (kg)
B3200-3
/8 610 (2.71) 540 (2.40) 63 (28.6)
B3200-1
/2 1130 (5.02) 1010 (4.49) 60 (27.2)
B3200-5
/8 1810 (8.05) 1610 (7.16) 59 (26.7)
B3200-3
/4 2710 (12.05) 2420 (10.76) 56 (25.4)
B3200-7
/8 3770 (16.77) 3360 (14.94) 170 (77.1)
For larger sizes consult full line pipe hanger catalog.
OPM
Threaded Accessories
Threaded Accessories
93 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B501 - Light weight u-bolt with 2 hex nuts
A
B
D
C
Hex Nuts
Included
Design Load
Size Range: Size 1
/2\" (15mm) thru 8\" (200mm) pipe
Material: Carbon Steel
Function: Recommended for supporting or anchoring light pipe loads.
Maximum Temperature: 650°F (343°C)
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number and finish.
Note: When furnished in Hot-Dip Galvanized finish, oversize
tapped hex nuts must be used.
A B C D Design Load Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
B501-1
/2 15/16\" (23.8) 13
/4\" (44.4) 11
/2\" (38.1) 5
/16\"-18 600 (2.67) 12 (5.4)
B501-3
/4 11
/8\" (28.6) 13
/4\" (44.4) 15
/8\" (41.3) 5
/16\"-18 600 (2.67) 13 (5.9)
B501-1 13
/8\" (29.9) 17
/8\" (47.6) 15
/8\" (41.3) 5
/16\"-18 900 (4.00) 14 (6.3)
B501-11
/4 123/32\" (43.6) 13
/4\" (44.4) 115/32\" (37.3) 5
/16\"-18 900 (4.00) 15 (6.8)
B501-11
/2 2\" (50.8) 13
/4\" (44.4) 17
/16\" (36.5) 5
/16\"-18 900 (4.00) 16 (7.2)
B501-2 27
/16\" (61.9) 21
/16\" (52.4) 17
/8\" (47.6) 3
/8\"-16 1200 (5.34) 27 (12.2)
B501-21
/2 215/16\" (74.6) 21
/16\" (52.4) 113/16\" (46.0) 3
/8\"-16 1200 (5.34) 32 (14.5)
B501-3 39
/16\" (90.5) 2\" (50.8) 13
/4\" (44.4) 3
/8\"-16 1800 (8.00) 36 (16.3)
B501-31
/2 43
/32\" (94.6) 2\" (50.8) 123/32\" (43.6) 3
/8\"-16 1800 (8.00) 38 (17.2)
B501-4 419/32\" (116.7) 21
/4\" (57.1) 121/32\" (50.0) 3
/8\"-16 1800 (8.00) 42 (19.0)
B501-5 521/32\" (143.6) 21
/4\" (57.1) 2\" (50.8) 1
/2\"-13 2400 (10.70) 92 (41.7)
B501-6 63
/4\" (171.4) 25
/8\" (66.7) 23
/8\" (60.3) 5
/8\"-11 2400 (10.70) 176 (79.8)
B501-8 83
/4\" (222.2) 25
/8\" (66.7) 23
/8\" (60.3) 5
/8\"-11 2400 (10.70) 191 (86.6)
B
Thread Length
Threaded Accessories
Threaded Accessories
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
94 Eaton B-Line series Fire Protection Solutions
Threaded Accessories
B3188 - Standard U-bolt with 4 hex nuts
B3188C - Standard plastic coated U-bolt
Size Range: Size 1
/2\" (15mm) thru 30\" (900mm) pipe
Material: Steel
Function: Recommended for support, anchor or guide of pipe.
Approvals: Underwriters Laboratories Listed 3
/4\" (20mm) thru 12\"
(300mm). Conforms to Federal Specification WW-H-171E & A-A-1192A,
Type 24 and Manufacturers Standardization Society ANSI/MSS SP-69 &
SP-58, Type 24.
Maximum Temperature: 750°F (399°C)
Finish: Plain or Electro-Galvanized. Contact customer service for
alternative finishes and materials.
Order By: Figure number and finish. U-bolt can be furnished with longer
tangents “D” or with longer threads “E”. Consult factory.
Note: When furnished in Hot-Dip Galvanized finish, oversize tapped hex
nuts must be used. B3188NS - Non-standard (NS) U-bolts are available
upon request. Specify dimensions other than standard. B3188DI - For
ductile iron pipe.
TL
Thread Length
A
Thread Size
B
E
TL
Design
Load 2
Design
Load 3
Design
Load 1
D
C
Hex Nuts Included
Pipe Size Thread Size Thread Length TL B
Part No. in. (mm) in. (mm) in. (mm)
B3188-1
/2 1
/2\" (15) 1
/4\"-20 21
/8\" (54.0) 15/16\" (23.8)
B3188-3
/4 3
/4\" (20) 1
/4\"-20 21
/8\" (54.0) 11
/8\" (28.6)
B3188-1 1\" (25) 1
/4\"-20 21
/8\" (54.0) 13
/8\" (34.9)
B3188-11
/4 11
/4\" (32) 3
/8\"-16 21
/8\" (54.0) 111/16\" (42.9)
B3188-11
/2 11
/2\" (40) 3
/8\"-16 21
/2\" (63.5) 2\" (50.8)
B3188-2 2\" (50) 3
/8\"-16 21
/2\" (63.5) 27
/16\" (61.9)
B3188-21
/2 21
/2\" (65) 1
/2\"-13 3\" (76.2) 215/16\" (74.6)
B3188-3 3\" (80) 1
/2\"-13 3\" (76.2) 39
/16\" (90.5)
B3188-31
/2 31
/2\" (90) 1
/2\"-13 3\" (76.2) 41
/16\" (103.2)
B3188-4 4\" (100) 1
/2\"-13 3\" (76.2) 49
/16\" (115.9)
B3188-5 5\" (125) 1
/2\"-13 3\" (76.2) 521/32\" (143.6)
B3188-6 6\" (150) 5
/8\"-11 33
/4\" (95.2) 63
/4\" (171.4)
B3188-8 8\" (200) 5
/8\"-11 33
/4\" (95.2) 83
/4 “ (222.2)
B3188-10 10\" (250) 3
/4\"-10 4\" (101.6) 107
/8\" (276.2)
B3188-12 12\" (300) 7
/8\"-9 41
/4\" (107.9) 127
/8\" (327.0)
B3188-14 14\" (350) 7
/8\"-9 41
/4\" (107.9) 141
/8\" (358.8)
B3188C
Plastic Coated
For larger sizes consult full line pipe hanger catalog.
Threaded Accessories
Threaded Accessories
95 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
C Tangent D E Approx. Wt./100
Part No. in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3188-1
/2 13
/16\" (30.2) 23
/4\" (69.8) 25
/16\" (58.7) 10 (4.5)
B3188-3
/4 13
/8\" (34.9) 23
/4\" (69.8) 27
/32\" (56.3) 11 (5.0)
B3188-1 15
/8\" (41.3) 23
/4\" (69.8) 23
/32\" (53.2) 11 (5.0)
B3188-11
/4 23
/32\" (53.2) 27
/8\" (73.0) 21
/32\" (51.6) 28 (12.7)
B3188-11
/2 23
/8\" (60.3) 3\" (76.2) 21
/16\" (52.4) 29 (13.1)
B3188-2 213/16\" (71.4) 31
/4\" (82.5) 21
/16\" (52.4) 31 (14.0)
B3188-21
/2 37
/16\" (87.3) 33
/4\" (95.2) 25
/16\" (58.7) 72 (32.6)
B3188-3 41
/16\" (103.2) 4\" (101.6) 21
/4\" (57.1) 79 (35.8)
B3188-31
/2 49
/16\" (115.9) 41
/4\" (107.9) 21
/4\" (57.1) 84 (38.1)
B3188-4 51
/16\" (128.6) 41
/2\" (114.3) 21
/4\" (57.1) 94 (42.6)
B3188-5 65
/32\" (156.3) 5\" (127.0) 27
/32\" (56.3) 104 (47.2)
B3188-6 73
/8\" (187.3) 61
/8\" (155.6) 213/16\" (71.4) 203 (92.1)
B3188-8 93
/8\" (238.1) 71
/8\" (181.0) 213/16\" (71.4) 241 (109.3)
B3188-10 115
/8\" (295.3) 83
/8\" (212.7) 31
/4\" (82.5) 412 (186.9)
B3188-12 133
/4\" (349.2) 95
/8\" (244.5) 31
/4\" (82.5) 661 (299.8)
B3188-14 15\" (381.0) 101
/4\" (260.3) 3\" (76.2) 707 (320.7)
Design Load 1 Design Load 2 Design Load 3
650°F (343°C) 750°F (399°C) 650°F (343°C) 650°F (343°C)
Part No. Lbs. (kN) Lbs. (kN) Lbs. (kN) Lbs. (kN)
B3188-1
/2 580 (2.58) 454 (2.02) 145 (0.64) 180 (0.80)
B3188-3
/4 580 (2.58) 454 (2.02) 145 (0.64) 300 (1.33)
B3188-1 580 (2.58) 454 (2.02) 145 (0.64) 480 (2.13)
B3188-11
/4 1460 (6.49) 1144 (5.09) 365 (1.62) 600 (2.67)
B3188-11
/2 1460 (6.49) 1144 (5.09) 365 (1.62) 600 (2.67)
B3188-2 1460 (6.49) 1144 (5.09) 365 (1.62) 720 (3.20)
B3188-21
/2 2700 (12.01) 2114 (9.40) 675 (3.00) 720 (3.20)
B3188-3 2700 (12.01) 2114 (9.40) 675 (3.00) 900 (4.00)
B3188-31
/2 2700 (12.01) 2114 (9.40) 675 (3.00) 900 (4.00)
B3188-4 2700 (12.01) 2114 (9.40) 675 (3.00) 900 (4.00)
B3188-5 2700 (12.01) 2114 (9.40) 675 (3.00) 1080 (4.80)
B3188-6 4320 (19.21) 3382 (15.04) 1080 (4.80) 1080 (4.80)
B3188-8 4320 (19.21) 3382 (15.04) 1080 (4.80) — —
B3188-10 6460 (28.73) 5060 (22.50) 1615 (7.18) — —
B3188-12 9960 (44.30) 7016 (31.21) 2490 (11.07) — —
B3188-14 9960 (44.30) 7016 (31.21) 2490 (11.07) — —
B3188 - Standard U-Bolt with 4 Hex Nuts cont’d.
For larger sizes consult full line pipe hanger catalog.
Threaded Accessories
Threaded Accessories
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
96 Eaton B-Line series Fire Protection Solutions
B3205 - Threaded rod (right-hand threads - both ends)
B3205L - Threaded rod (right & left hand threads)
ATR - All threaded rod - 120\" (3.05m) lengths
TOLCO Fig. 99 - all threaded rod cut to length
Size Range: 3
/8\"-16 thru 7
/8\"-9 rod
Material: Steel
Function: Recommended for use as a hanger support in hanger assemblies.
Rod is threaded on both ends with right hand threads of the length shown. Also
available with left and right hand threads - specify Fig. B3205L when ordering.
Maximum Temperature: 750°F (399°C)
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, rod size, length and finish
Size Range: 1
/4\"-20 thru 7
/8\"-9 rod in 120\" lengths or cut to length
Material: Steel
Maximum Temperature: 750°F (399°C)
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes
and materials.
Approvals: Included in our Seismic Engineering Guidelines approved by the State
of California Office of Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relating to OSHPD projects,
please refer to our Seismic Engineering Guidelines, OPM-0052-13.
Order By: Figure number, rod size, length and finish
A
Thread Size
TL
TL
Specify Length
‘L’
Standard Design Load
Thread Size Thread Length TL 650°F (343°C) 750°F (399°C)
Part No. A in. (mm) Lbs. (kN) Lbs. (kN)
B3205-3
/8 x ‘L’ 3
/8\"-16 21
/2\" (63.5) 730 (3.25) 572 (2.54)
B3205-1
/2 x ‘L’ 1
/2\"-13 21
/2\" (63.5) 1350 (6.00) 1057 (4.70)
B3205-5
/8 x ‘L’ 5
/8\"-11 21
/2\" (63.5) 2160 (9.61) 1692 (7.52)
B3205-3
/4 x ‘L’ 3
/4\"-10 3\" (76.2) 3230 (14.37) 2530 (11.25)
B3205-7
/8 x ‘L’ 7
/8\"-9 31
/2\" (88.9) 4480 (19.93) 3508 (15.60)
Part No. - Size x Length Threads Recommended Load Approx. Wt./100 Ft.
ATR Fig. 99 Per Inch Lbs. (kN) Lbs. (kg)
ATR 1
/4\" x 120 99-1
/4\" x length 20 240 (1.07) 12 (5.44)
ATR 3
/8\" x 120 99-3
/8\" x length 16 730 (3.24) 29 (13.15)
ATR 1
/2\" x 120 99-1
/2\" x length 13 1350 (6.00) 53 (24.04)
ATR 5
/8\" x 120 99-5
/8\" x length 11 2160 (9.60) 89 (40.37)
ATR 3
/4\" x 120 99-3
/4\" x length 10 3230 (14.37) 123 (55.79)
ATR 7
/8\" x 120 99-7
/8\" x length 9 4480 (19.93) 170 (77.11)
For larger sizes consult full line pipe hanger catalog.
For larger sizes consult full line pipe hanger catalog.
OPM
Threaded Accessories
Threaded Accessories
97 Eaton
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
B-Line series Fire Protection Solutions
B3214 - Tie bolt
Material: Steel
Function: Recommended for securing the connection of steel pipe to
ductile pipe first attach tie bolts to pipe flanges then connect tie rods. May
be used in vertical or horizontal applications.
Approvals: As shown in NFPA Pamphlet 24, Installation of Private Fire
Service Maintenance 4\" (100mm) - 12\" (300mm) pipe size.
Finish: Plain. Contact customer service for alternative finishes and materials.
Order By: Figure number, length and finish.
Custom lengths for thicker flange available.
Size Range: 3
/8\"-16 rod thru 1
/2\"-13 rod
Material: Steel
Function: Typically used to suspend pipe from wood joists.
Machine threaded on one end and lag threaded on the other
end. It is recommended that pilot holes be pre-drilled to prevent
beam from splitting and to aid in starting lag threads.
Approvals: Conforms to the requirements of NFPA13.
Finish: Plain. Contact customer service for alternative
finishes and materials.
Order By: Figure number, rod size, length and finish
B3213 - Coach screw rod
*3
/8 x 31
/2 and 1
/2 x 31
/2 will have a coach screw thread length of 2\" (50.8) and a rod thread length of 1\" (25.4).
Design Load is based on proper installation and solid wood.
A
Thread Size
B
C
Specify L
Size Specify
4\" (101.4mm) or 41
/2\"
(114.3mm)
Steel Pipe Riser
Adapter
Ground Level
All Threaded Rod
Ductile Iron Riser
Typical Application
Under Ground Pipe
1\" (25.4mm)
Max.
3
/4\" (19.0mm)
Dia.
Thread Coach Screw Rod Thread Design
Size Standard Rod Lengths L Thread Length B Length C Load
Part No. A in. (mm) in. (mm) in. (mm) Lbs. (kg)
B3213-3
/8 x ‘L’ 3
/8\"-16 *31
/2\", 8\" (88.9, 203.2) 2\" (50.8) 2\" (50.8) 390 (1.73)
B3213-1
/2 x ‘L’ 1
/2\"-13 *31
/2\", 8\" (88.9, 203.2) 21
/2\" (63.5) 21
/2\" (63.5) 640 (2.84)
Length Approx. Wt./100
Part No. in. (mm) Lbs. (kg)
B3214-4 4\" (101.6) 107.5 (48.5)
B3214-41
/2 41
/2\" (114.3) 113.7 (51.6)
Threaded Accessories
Threaded Accessories
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
98 Eaton B-Line series Fire Protection Solutions
Size Range: 3
/8\"-16 thru 7
/8\"-19 rod
Material: Steel
Function: Designed to be hooked or hung from beam flange or purlin.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative
finishes and materials.
Order By: Figure number, length and finish
B3212 - J-bolt
A
Thread Size
TL
Thread Length
Radius D
Specify Length L
Thread Size Thread Length TL Radius D Design Load
Part No. A in. (mm) in. (mm) Lbs. (kg)
B3212-3
/8 x ‘L’ 3
/8\"-16 2\" (50.8) 1
/2\" (12.7) 240 (1.07)
B3212-1
/2 x ‘L’ 1
/2\"-13 2\" (50.8) 5
/8\" (15.9) 440 (1.96)
B3212-5
/8 x ‘L’ 5
/8\"-11 21
/2\" (63.5) 3
/4\" (19.0) 705 (3.13)
B3212-3
/4 x ‘L’ 3
/4\"-10 21
/2\" (63.5) 7
/8\" (22.2) 1050 (4.67)
B3212-7
/8 x ‘L’ 7
/8\"-9 21
/2\" (63.5) 1\" (25.4) 1470 (6.54)
DS 16 x 2 - Drive screw
Material: Steel
Function: Equivalent to a nail, but has greater holding power
Finish: Plain and Electro-Galvanized
Order By: Figure number and finish
B3228 - Hex head lag bolt
Material: Steel
Function: Designed to fasten metal to wood. Lag screws are made with hex heads in lengths of 6\" (152.5mm)
or shorter and square heads in lengths longer than 6\" (152.5mm). Both types have coarse lag threads and gimlet points and are available in diameters of 1
/4\"(6.3mm) to 5
/8\"(15.9mm) inclusive. Square-head lag screws are
also available in 3
/4\"(19.0mm), 7
/8\"(22.2mm) and 1\"(25.4mm) diameters.
Approvals: Qualified for static, wind, and seismic loading in concrete. Included in our Seismic Engineering
Guidelines approved by the State of California Office of Statewide Health Planning and Development (OSHPD).
For additional load, spacing and placement information relating to OSHPD projects, please refer to our Seismic
Engineering Guidelines, OPM-0052-13.
Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes and materials.
Order By: Figure number, bolt size, length and finish
Bolt Diameter and Wt./C
Length 1
/4\" (6.3) 3
/8\" (9.5) 1
/2\" (12.7) 5
/8\" (15.9) 3
/4\" (19.0)
11
/2\" (38.1) 2.3 (1.0) 6.0 (2.7) 11.8 (5.3) 19.4 (8.8) 32.3 (14.6)
2\" (50.8) 2.8 (1.3) 7.0 (3.2) 14.4 (6.5) 23.2 (10.5) 38.3 (17.4)
21
/2\" (63.5) 3.3 (1.5) 8.3 (3.7) 16.2 (7.3) 27.0 (12.2) 44.0 (19.9)
3\" (76.2) 3.9 (1.7) 9.8 (4.4) 18.6 (8.4) 31.0 (14.0) 47.7 (21.6)
31
/2\" (88.9) 4.4 (2.0) 11.4 (5.2) 21.2 (9.6) 34.8 (15.8) 56.3 (25.5)
4\" (101.6) 5.0 (2.2) 12.5 (5.7) 23.3 (10.5) 37.6 (17.0) 58.5 (26.5)
41
/2\" (114.3) 5.7 (2.6) 14.0 (6.3) 26.1 (11.8) 42.6 (19.3) 64.0 (29.0)
5\" (127.0) 6.3 (2.8) 15.4 (7.0) 29.0 (13.1) 45.5 (20.6) 68.0 (30.8)
51
/2\" (139.7) 7.0 (3.2) 16.4 (7.4) 31.5 (14.3) 49.3 (22.3) 74.0 (33.5)
6\" (152.4) 7.4 (3.3) 18.3 (8.3) 34.0 (15.4) 53.0 (24.0) 77.0 (34.9)
OPM