Automation Control Device
PEOPLE ELECTRIC PRODUCT SALES MANUAL
Providing Safer electrical products globally
COMPANY PROFILE
People Ele. Appliance Group was wholly owned company of People Holding Group, one of Chinese Top 500 Enterprise, and founded in the year 1996.
Industrial electrical products as the core business of People Ele. Appliance Group, People Electric owns Zhejiang, Shanghai, Nanchang , Fuzhou, Nantong and Zaozhuang six manufacturing bases, 35 wholly owned subsidiaries, 150 holding member enterprises, over 1500 cooperated processing enterprises and over 5000 sales companies.
The products are popularly sold to over 125 countries and regions, which are widely used in Pudong Airport, Beiing-Shanghai high-speed railway, Three Gorges Hydropower, Beijing Subway, Olympic venues, South North Water Transfer, Qinghai-Tibet Railway, Chang'e Lunar Exploration Project and Vietnam Taian hydropower project etc. major projects at home and abroad, which ranked among the World's Top 500 Machinery Enterprises.
Assess by the World's Brand Laboratory, the brand value reaches to RMB110.927 bilion Yuan.
Perfect industry chain and personalize solutions, Satisfying the different requirements of global customers
Power and energy
• Power
• Petroleum and petrochemical
• Transportation
Commercial
network
• Bank insurance
• Public construction
• Community facility
Indusry and machinery
• Mining / building materials
• Water / water treatment
• Car
Building
• Official building
• Industrial building
• Basic facility
Date center
·IT
• High technology
• Internet
Residence
• Residential construction
• Public construction
• Community facility
More safety
Ensure the safety of life and property
More reliale
Supply the power uninterruptedly
More efficient
Reducing the consumption of energy and the cost, shorten the time of supply
More economic
Optimize the process of the machinery and factory, improving the comfortability of use.
More ecofriendly
Supply the energy through the renewable energy, reducing the carbon emissions
Contents
AC CONTACTOR 01
CJX2-09\~95 01
CJX2-115\~780 04
CJX2-Z 07
CJX2-D 10
CJX2-K(PLC1-K) 14
Auxiliary contact block 15
CJX1 16
RDC5 20
RDC19B(CJ19) 23
CJX2-NC 25
JX1-N(P3TD) 28
RDCH8 29
STARTER 32
PLE1-D 32
QJX2 33
PGV2 & PGV3 36
RELAY 40
RDJ2 40
JRS2 44
SSR/JGX 49
JQX-13F 50
JQX-10F(JTX) 51
HH5-P 52
ST3P 53
KG316T/KG316TX 55
PUSH BUTTON 60
RDA2(PXB2) 60
RDA5(PXB5) 67
MP016S 73
RDA 77
RDD6 79
SWITCH 81
TME 81
TXCK-M 83
TXCK-P/TXCK-T 85
CWL 88
THL 91
CM 93
Toggle 96
PEY 98
UNIVERSAL CHANGEOVER SWITCH 99
LW26S 99
LW26GS 104
LW26S 105
KDH 107
HZ10D-□/E119 108
HZ10D 109
DISCONNECTOR 111
RDHG2B 111
HR17B 113
RDH5 114
RDH5R 122
RDT16(NT0) 125
RT0 128
CJX2-09\~95 Series AC Contactor
Application
CJX2 series AC Contactor is mainly used in the circuit of AC 50Hz or 60Hz, rated voltage up to 690V, rated current up to 95A, for the use of remotely connecting and breaking the circuit, it also can be directly combined with thermal relay into electromagnetic starter to protect the circuit that may have overloaded operations. Contactor can also be equipped with accessories such as the block type auxiliary contacts group, air delay contact, mechanical interlock mechanism, etc. to combine into delay contactor, directional contactor, and star-delta starter. It conforms to the standard IEC/EN60947-4-1.
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃.
3.2 Altitude: does not exceed 2000m.
3.3 Atmospheric condition: when the highest temperature is +40C, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3.
3.5 Installation category: III.
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ± 5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
Main technical parameter
table 1
| Conventional heating current(≤40℃) A | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | ||||||||||
| Rated current (A)when at 380V | AC-3 | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 | |||||||||
| AC-4 | 4 | 5 | 7 | 10 | 13 | 16 | 20 | 25 | 32 | 45 | ||||||||||
| Power of controllable | 110V | 0.4 | 0.5 | 0.75 | 1.1 | 1.5 | 1.5 | 2.2 | 3.7 | 1 | - | |||||||||
| single phase motor kW | 220V | 0.75 | 1.1 | 1.5 | 2.2 | 3 | 3.7 | 5.5 | - | - | - | |||||||||
| Power of controllable three-phase squirrel cage typemotor kW (when AC-3) | 220V | 2.2 | 3 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 25 | |||||||||
| 380V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | ||||||||||
| 440V | 4 | 5.5 | 7.5 | 11 | 15 | 22 | 30 | 37 | 45 | 45 | ||||||||||
| 660V | 5.5 | 7.5 | 9 | 15 | 18.5 | 30 | 33 | 37 | 45 | 45 | ||||||||||
| AC-1(≤40℃)A | 20 | 20 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | ||||||||||
| Connecting max. current A | 250 | 250 | 300 | 450 | 550 | 800 | 900 | 1000 | 1100 | 1200 | ||||||||||
| Breaking max. current A | 440V | 250 | 250 | 300 | 450 | 550 | 800 | 900 | 1000 | 1100 | 1200 | |||||||||
| 500V | 175 | 175 | 250 | 400 | 480 | 800 | 900 | 1000 | 1100 | 1200 | ||||||||||
| 660V | 85 | 85 | 120 | 180 | 200 | 400 | 500 | 630 | 640 | 700 | ||||||||||
| Operationfrequency | Electrical life | AC-4 | 300 | 300 | 300 | 150 | 150 | 150 | 150 | 150 | 150 | 150 | ||||||||
| AC-3 | 2400 | 2400 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 1200 | 600 | ||||||||||
| Mechanical life | (times/h) | 360 | 0 | |||||||||||||||||
| Electrical life (10000 times/h) | AC-4 | 20 | 20~15 | 20~7 | 15~7 | 15~7 | 10~7 | 7 | 7~6 | 7~5 | 7~5 | |||||||||
| AC-3 | 200 | 160 | ||||||||||||||||||
| Mechanical life (10000 times/h) | 2000 | 1000 | ||||||||||||||||||
| Rated control power voltage Us (V) | AC 36,48,110,220,380,415,440,660 | |||||||||||||||||||
| Pull-in voltage 50/60Hz V | (0.85~1.1)Us | |||||||||||||||||||
| Release voltage 50/60Hz V | (0.2~0.7)Us | |||||||||||||||||||
| 50Hz | Pull-in VA | 70 | 70 | 70 | 110 | 110 | 200 | 200 | 200 | 200 | 200 | |||||||||
| Hold VA | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||||||||||
| Coil power | 60Hz | Pull-in VA | 80 | 80 | 80 | 115 | 115 | 200 | 200 | 200 | 200 | 200 | ||||||||
| Hold VA | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||||||||||
| Power W | 1.8~2.7 | 1.8~2.7 | 1.8~2.7 | 3~4 | 3~4 | 6~10 | 6~10 | 6~10 | 6~10 | 6~10 | ||||||||||
| Powerfactor | Connecting | 0.8 | 0.6 | |||||||||||||||||
| Breaking | 0.3 | 0.3 | ||||||||||||||||||
| Pull-in time m s | 12~22 | 15~24 | 20~26 | 20~35 | ||||||||||||||||
| Release time m s | 4~12 | 5~19 | 8~12 | 6~20 | ||||||||||||||||
| Max. operating frequency | 3500 ti | mes/h | ||||||||||||||||||
| Pieces | 1 2 | 1 2 | 1 2 | 1 2 | 1 2 | 1 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | ||||||
| Flexible wire with cold-press terminal (mm²) | 2.5 | 2.5 | 4 | 4 | 6 | 10 | 16 | 6 | 16 | 6 | 50 | 25 | 50 | 25 | ||||||
| Flexible wire without cold-press terminal (mm²) | 4 | 4 | 6 | 10 | 6 | 10 6 | 16 | 25 | 16 | 25 | 16 | 50 | 35 | 50 | 35 | |||||
| Single hard wire | 4 | 4 | 6 | 6 | 10 | 10 | 25 | - | 25 | 1 | 50 | = | 50 | |||||||
| Weight (kg) | 0.32 | 0.32 | 0.35 | 0.49 | 0.55 | 1.07 | 1.07 | 1.10 | 1.44 | 1.44 | ||||||||||
| Suited fuse typeRated current (A)Auxiliary contacts | RDT16( | NT)-00 | ||||||||||||||||||
| 20 | 20 | 32 | 40 | 50 | 63 | 80 | 80 | 100 | 125 | |||||||||||
| Can be added with F4, LA2-D/LA3-D type air delay contacts | ||||||||||||||||||||
Dimensions
CJX2-115\~780
Series AC Contactor
Application
CJX2 series AC Contactor is mainly used in the circuit of AC 50Hz or 60Hz, rated operating voltage up to 690V, rated operating current up to 780A, for the use of remotely connecting and breaking the circuit, it also can be combined with thermal relay into electromagnetic starter to protect the circuit's overloaded operations. It conforms to the standard IEC/EN60947-4-1
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: III
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ±5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
Main technical parameter
4.1 Main specification
4.1.1 Rated current: 115, 150, 185, 225,265,330,400, 500, 630, 780A
4.1.2 Rated control power voltage of coil Us: AC 50Hz, 36, 48, 110, 220, 380, 415, 440, 660V
(special voltage can be customized).
4.2 Main parameter and technical performance index of contactor to see table 1
table 1
| Model | CJX2-115 C | JX2-150 C | JX2-185 | CJX2-225 | CJX2-265 | CJX2-330 C | JX2-400 C | JX2-500 C | JX2-630 C | JX2-780 | ||||
| Maincont-actsCoil | Conventional heating current(≤40℃) IthA | 200 | 200 | 275 | 275 | |||||||||
| 315 | 380 | 450 | 630 | 800 | 1500 | |||||||||
| Rated current (A) | AC-3 | 380V | 115 | 150 | 185 | 225 | 265 | 330 | 400 | 500 | 630 | 780 | ||
| Max. power ofcontrollable three-phase squirrel cagetype motor kW | 380V | 63 | 80 | 100 | 110 | 140 | 180 | 200 | 250 | 335 | 400 | |||
| 660V | 80 | 100 | 110 | 129 | 160 | 220 | 280 | 335 | 450 | 470 | ||||
| 1000V | 63 | 75 | 100 | 132 | 160 | 200 | 250 | 300 | 450 | 450 | ||||
| Operation frequency times/h (AC-3) | 1200 | 600 | ||||||||||||
| Electrical life (100000 times/h)(AC-3) | 120 | 100600 | ||||||||||||
| Mechanical life (10000 times/h) | 1000 | |||||||||||||
| Control voltage Us | AC 36,48,110,220,380,415,440,660V | |||||||||||||
| Pull-in voltage 50/60Hz V | (0.85~1.1)Us(0.2~0.7)Us | |||||||||||||
| Release voltage 50/60Hz V | ||||||||||||||
| Coil power | 50Hz | Pull-in VA | 660 | 660 | 966 | 966 | 840 | 840 | 1380 | 1380 | 2076 | 2100 | ||
| Hold VA | 54 | 54 | 66 | 66 | 12 | 12 | 22 | 24 | 30 | 50 | ||||
| Suited fuse (SCPD)Auxiliary contacts | RDT16(NT)-1 | RDT16(NT)-1 | RDT16(NT)-2 | RDT16(NT)-2 | RDT16(NT)-2 | RDT16(NT)-3 | RDT16(NT)-3 | |||||||
| 200 | 250 | 315 | 315 | 400 | 500 | 500 | 500 | 630 | 1000 | |||||
| Can be added with F4, LA2-D/LA3-D type air delay c | ontacts | |||||||||||||
Dimensions
| mm | CJX2-115 | CJX2-150 | CJX2-185 | CJX2-225 | CJX2-265 | CJX2-330 | CJX2-400 | CJX2-500 | CJX2-630 | |||||||||
| 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | 3P | 4P | |
| A max | 167 | 204 | 167 | 204 | 170 | 211 | 170 | 211 | 202 | 247 | 218 | 261 | 215 | 261 | 235 | 288 | 310 | 389 |
| B max | 163 | 163 | 171 | 171 | 175 | 175 | 175 | 175 | 203 | 203 | 210 | 210 | 210 | 210 | 240 | 240 | 304 | 304 |
| C max | 172 | 172 | 172 | 172 | 183 | 183 | 183 | 183 | 215 | 215 | 223 | 223 | 223 | 223 | 235 | 235 | 257 | 257 |
| P | 37 | 37 | 40 | 40 | 40 | 40 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 48 | 55 | 55 | 80 | 80 |
| S | 20 | 20 | 20 | 20 | 20 | 20 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 25 | 30 | 30 | 40 | 40 |
| ∅ | M6 | M6 | M8 | M8 | M8 | M8 | M10 | M10 | M10 | M10 | M10 | M10 | M10 | M10 | M10 | M10 | M12 | M12 |
| f | 131 | 131 | 131 | 131 | 131 | 131 | 131 | 131 | 147 | 147 | 147 | 147 | 147 | 147 | 150 | 150 | 181 | 181 |
| M | 147 | 147 | 150 | 150 | 154 | 154 | 172 | 172 | 178 | 178 | 181 | 181 | 181 | 181 | 208 | 208 | 264 | 264 |
| H | 124 | 124 | 124 | 124 | 127 | 127 | 127 | 127 | 147 | 147 | 158 | 158 | 158 | 158 | 172 | 172 | 202 | 202 |
| L | 107 | 107 | 107 | 107 | 113.5 | 113.5 | 113.5 | 113.5 | 141 | 141 | 145 | 145 | 145 | 145 | 146 | 146 | 155 | 155 |
| X1 200~500V | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 10 | 15 | 15 | 15 | 15 | 20 | 20 |
| X1 660~1000V | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 15 | 20 | 20 | 20 | 20 | 30 | 30 |
| Ga | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 80 | 96 | 96 | 96 | 96 | 80 | 80 | 80 | 80 | 180 | 180 |
| Ha | 106~ | 119 | 106~ | 119 | 106~ | 119 | 106~ | 119 | 106~ | 119 | 106~ | 119 | 170~ | 180 | 170~ | 180 | 180~ | 190 |
2. X1: the arcing distance which is determined by the rated voltage and breaking capacity.
CJX2-Z
Series DC operated AC Contactor
Application
CJX2-Z series DC operated AC contactor is mainly used in the circuit of AC 50Hz or 60Hz, rated voltage up to 690V, rated current up to 95A, for the use of remote frequently connecting and breaking the circuit, it can control the motor, also can control the electric welder, capacitor group, electric heating device, lighting equipment and other loads. It conforms to the standard IEC/EN60947-4-1
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: II
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ± 5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
Main technical parameter
table 1
| Model | CJX2-09ZC | JX2-12ZC | JX2-18Z CJX2-25ZCJX2-32Z CJX2-40Z CJX2-50ZCJX2-65Z CJX2-80ZCJX2-95Z | ||||||||||||||||||||
| Maincont-acts | Rated current le A | AC-3 | 380V | 9 | 12 | 18 | 25 | 32 | 40 | 50 | 65 | 80 | 95 | ||||||||||
| 660V | 6.6 | 8.9 | 12 | 18 | 21 | 34 | 39 | 42 | 49 | 49 | |||||||||||||
| Rated control power (kW) | AC-3 | 380V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 45 | |||||||||||
| 660V | 5.5 | 7.5 | 10 | 15 | 18.5 | 30 | 37 | 37 | 45 | 45 | |||||||||||||
| Conventional heating current Ith (A) | 25 | 25 | 32 | 40 | 50 | 60 | 80 | 80 | 125 | 125 | |||||||||||||
| Rated voltage Ue (V) | 660 | ||||||||||||||||||||||
| Rated insulation voltage Ui (V) | 690 | ||||||||||||||||||||||
| Electrical life (104 times) | AC-3 | 100 | 100 | 100 | 100 | 80 | 80 | 60 | 60 | 60 | 60 | ||||||||||||
| Operation frequency h-4 | 1200 | 1200 | 1200 | 1200 | 600 | 600 | 600 | 600 | 600 | 600 | |||||||||||||
| Electrical life (104 times) | AC-4 | 20 | 20 | 20 | 20 | 20 | 20 | 15 | 15 | 10 | 10 | ||||||||||||
| Operation frequency h-4 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | 300 | |||||||||||||
| Mechanical life(104 times) | 1000 | 1000 | 1000 | 800 | 800 | 800 | 800 | 800 | 800 | 600 | |||||||||||||
| Coil | Rated control voltage Us | DC:24V,48V, 110V,220V | |||||||||||||||||||||
| Pull-in voltage | 85%~110% Us | ||||||||||||||||||||||
| Release voltage | 0.1~0.70 Us | ||||||||||||||||||||||
| Coil power (W) less than | 11 | 11 | 11 | 13 | 13 | 22 | 22 | 22 | 22 | 22 | |||||||||||||
| Term-als | Pieces of wire | 1 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | |||
| Flexible wire | 2.52.5 | 2.5 | 2.5 | 4 | 4 | 4 | 4 | 6 | 6 | 10 | 10 | 16 | 16 | 16 | 16 | 50 | 25 | 50 | 25 | ||||
| Hard wire | 4 | 4 | 4 | 4 | 6 | 6 | 6 | = | 10 | 10 | 10 | 10 | 25 | 25 | 50 | – | 50 | ||||||
| Auxiliary contacts | Can be added with F4, LA2-D/LA3-D type air delay contacts | ||||||||||||||||||||||
Dimensions
| a max | b max | c max | G | C1 | C2 | H | |
| CJX2-09-12Z | 45 | 75 | 115 | 35 | 145 | 172 | 50~60 |
| CJX2-18Z | 45 | 75 | 120 | 35 | 150 | 177 | 50~60 |
| a max | b max | c max | G | C1 | C2 | H | |
| CJX2-25Z | 58 | 80 | 130 | 40~50 | 160 | 187 | 50~60 |
| CJX2-32Z | 58 | 80 | 136 | 40~50 | 166 | 193 | 50~60 |
| CJX2-40/50/65Z | a max | b max | c max | G | H |
| 79 | 128 | 172 | 40 | 50~60 | |
| CJX2-80/95Z | 86 | 128 | 182 | 40 | 50~60 |
Wiring diagram
CJX2-D Series AC Contactor
Application
CJX2-D series AC Contactor is mainly used in the circuit of AC 50Hz or 60Hz, rated voltage up to 690V, rated current up to 620A, for the use of remotely connecting and breaking the circuit, it also can be directly combined with thermal relay into electromagnetic starter to protect the circuit that may have overloaded operations. Contactor can also be equipped with accessories such as the block type auxiliary contacts group, air delay contact, mechanical interlock mechanism, etc. to combine into delay contactor, directional contactor, and star-delta starter. It conforms to the standard IEC/EN60947-4-1.
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: III
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ± 5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration
AC CONTACTOR
Main technical parameter
table 1
| Model | CJX2-D09 | CJX2-D12 | ||||||||||||
| CJX2-D18CJX2-D25CJX2-D32CJX2-D38CJX2-D40CJX2-D50CJX2-D65CJX2-D80CJX2-D95 | ||||||||||||||
| Rated Insulation voltage V | 690 | |||||||||||||
| Conventional heating current Ith(≤40℃) A | 20 | 32 | 40 | 50 | 50 | 60 | 80 | 80 | 80 | 125 | 125 | |||
| Rated current le (A) | AC-3 | 9 | 12 | 18 | 25 | 32 | 38 | 40 | 50 | 65 | 80 | 95 | ||
| Power of controllable three-phase | 220V | 2.2 | 3 | 4 | 5.5 | 7.5 | 9 | 11 | 15 | 18.5 | 22 | 25 | ||
| squirrel cage type motor(kW) (AC-3) | 380V | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 18.8 | 22 | 30 | 45 | 45 | ||
| 660V | 5.5 | 7.5 | 10 | 15 | 18.8 | 18.5 | 30 | 33 | 37 | 45 | 45 | |||
| Control voltage of coil Us (V) | AC 36,48,110,220,380,415,440,660V | |||||||||||||
| Pull-in voltage 50/60Hz V | (0.85~1.1)Us(0.2~0.7)UsRDT16(NT)-0040 50 63 63 80 80 100 125 | |||||||||||||
| Release voltage 50/60Hz V | ||||||||||||||
| Suited fuse (SCPD) | Model | |||||||||||||
| Rated current (A) | ||||||||||||||
| Auxiliary contacts | 3P+1NO+1NC, Can be added with F4, LA2-D/LA3-D type air delay contacts | |||||||||||||
| Model | CJX2-D115 | CJX2-D150 | CJX2-D170 | CJX2-D205 | CJX2-D245 | CJX2-D300 | CJX2-D410 | CJX2-D475 | CJX2-D620 | |||
| Rated Insulation voltage V | 1000 | |||||||||||
| Conventional heating current Ith(≤40℃)A | 200 | 200 | 200 | 275 | 275 | 380 | 450 | 580 | 800 | |||
| Rated current le (A) | 380V | AC-3 | 115 | 150 | 170 | 205 | 245 | 300 | 410 | 475 | 620 | |
| AC-4 | 50 | 65 | 70 | 80 | 100 | 124 | 150 | 185 | 225 | |||
| 660V | AC-3 | 86 | 107 | 118 | 130 | 170 | 225 | 235 | 290 | 360 | ||
| AC-4 | 25 | 32 | 35 | 40 | 47 | 60 | 72 | 85 | 100 | |||
| Power of controllable three-phasesquirrel cage type motor(kW)(AC-3) | 380V | 55 | 75 | 85 | 90 | 110 | 160 | 200 | 250 | 335 | ||
| 660V | 80 | 90 | 100 | 110 | 129 | 220 | 280 | 330 | 450 | |||
| Electrical | AC-3 | 600 | 300 | 300 | 600 | 600 | 600 | 300 | 300 | 300 | ||
| Operation frequency(times/h) | life | AC-4 | 300 | 300 | 300 | 150 | 150 | 150 | 150 | 150 | 150 | |
| Mechanical life | 2400 | 2400 | 2400 | 2400 | 2400 | 2400 | 1200 | 1200 | 1200 | |||
| Electrical life (10000 times/h) | AC-3 | 40 | 40 | 40 | 50 | 50 | 50 | 30 | 30 | 20 | ||
| AC-4 | 2 | 2 | 2 | 10 | 10 | 10 | 8 | 8 | 5 | |||
| Mechanical life (10000 times/h) | 300 | 300 | 300 | 300 | 300 | 300 | 100 | 100 | 100 | |||
| Control voltage of coil Us (V) | AC 36,48,110,220,380,415,440,660(0.85~1.1)Us(0.2~0.7)Us | |||||||||||
| Pull-in voltage 50/60Hz V | ||||||||||||
| Release voltage 50/60Hz V | ||||||||||||
| Average powerconsumption (VA) | 50Hz | Pull-in | 300 | 300 | 300 | 800 | 800 | 1200 | 1200 | 1250 | 1250 | |
| Hold | 22 | 22 | 22 | 55 | 55 | 13 | 20 | 24 | 22 | |||
| Suited fuse type | Model | RDT16(NT) -1 | RDT16(NT) -1 | RDT16(NT) -2 | RDT16(NT) -2 | RDT16(NT) -2 | RDT16(NT) -3 | RDT16(NT) -3 | RDT16(NT) -3 | RDT16(NT) -3 | ||
| Rated current (A) | 160 | 200 | 250 | 315 | 315 | 400 | 500 | 630 | 630 | |||
| Auxiliary contacts | Can be ad | ded with F4, | LA2-D/LA3-D t | ype air dela | y contacts | |||||||
Dimensions
6.1 Overall dimensions and installation dimensions to see fig 1\~6 and table 3\~6
table3
| L | W | H | C1 | C2 | ∅D | |
| CJX2-D09~18 | 45 | 77 | 86 | 50~60 | 35 | 4.5 |
| CJX2-D25~38 | 45 | 88 | 92 | 50~60 | 35 | 4.5 |
table4
| L | W | H | C1 | C2 | ∅D | |
| CJX2-D40~65 | 75 | 127 | 119 | 100~110 | 40 | 6.5 |
| CJX2-D80~95 | 85 | 127 | 130 | 100~110 | 40 | 6.5 |
table5
| a max | b max | cmax | dmax | e max | f max | a | b | 0 | |
| CJX2-D115~170 | 120 | 162 | 133 | 155 | 173 | 130 | 95~110 | 6.5 |
| Model | Amax | Bmax | Cmax | P | S | ∅ | f | M | H | L | X1≤500V | X1>500V | Ga | Ha |
| CJX2-D205 | 170 | 175 | 183 | 40 | 20 | M8 | 131 | 154 | 127 | 113.5 | 10 | 15 | 80 | 106~119 |
| CJX2-D245 | 170 | 175 | 183 | 48 | 25 | M10 | 131 | 172 | 127 | 113.5 | 10 | 15 | 80 | 106~119 |
| CJX2-D300 | 218 | 210 | 223 | 48 | 25 | M10 | 147 | 181 | 158 | 145 | 10 | 15 | 96 | 106~119 |
| CJX2-D410 | 218 | 210 | 223 | 48 | 25 | M10 | 147 | 181 | 158 | 145 | 15 | 20 | 80 | 170~180 |
| CJX2-D475 | 235 | 240 | 235 | 55 | 30 | M10 | 150 | 208 | 172 | 146 | 15 | 20 | 80 | 170~180 |
| CJX2-D620 | 310 | 304 | 257 | 80 | 40 | M12 | 181 | 264 | 202 | 155 | 20 | 30 | 180 | 180~190 |
CJX2-K(PLC1-K)
Series AC Contactor
Application
CJX2-K series AC contactor is mainly used for AC 50Hz or 60Hz, rated working voltage to 690V, rated current circuit to 9A, for the use of remotely connecting and breaking the circuit. It also can be combined with suitable thermal relay into electromagnetic starter to protect the circuit that may have overloaded operations. It conforms to the standard IEC/EN60947-4-1.
| CJX2-K-06 | CJX2-K-08 | |||
| Rated working current(A) | 380V | 6 | 9 | |
| AC-3/AC-4 | 660/690V | 3.8 | 5 | |
| Rated insulation voltage(V) | 690 | 690 | ||
| Conventional heatingcurrent Ith (A) | 20 | 20 | ||
| Controllable three-phase cage | 220V | 1.5 | 2.2 | |
| Motor power(kW) | 380V | 2.2 | 4 | |
| AC-3 | 660V/690V | 3 | 4 | |
| Operating frequency(h1) | Electrical life | AC-3 | 12000 | 12000 |
| AC-4 | 300 | 300 | ||
| Mechanical life | 3600 | 3600 | ||
| Electrical life (10000times) | AC-3 | 120 | 120 | |
| AC-4 | 2.5 | 2.5 | ||
| Mechanical life (10000times) | 1000 | 1000 | ||
| Fuse Specification | RDT16-16 | RDT16-20 | ||
| Coil power(VA) | Pull in | 30 | 30 | |
| Hold | 4.5 | 4.5 | ||
Structure characteristics
1.The utility model has the advantages of advanced structure, small size, light weight, low power consumption, long operation life, safety and reliability, high technical performance etc..
2.It can be assembled by block type, equipped with auxiliary contact group, thermal relay and other accessories, combined into a variety of derivative products
3.The contactor not only can be installed by screw, but also can be installed with 35mm standard rail. 4.The contact direction of the iron core and the contact of the contactor is parallel to the mounting surface.
Auxiliary contact blocks
table 1
| Model | Group of contact | Rated insulationvoltage V | Conventionalheating current A | Electrical life(10⁶times) | Mechanical life(10⁴4 times) | Max. operatingfrequency (t/s) | Connectablemin. load | Sketch picture |
| F4-11 | 1NO+1NC | 10 | 0.5~5 | 3 | 6V 10mA | ![]() | ||
| F4-20 | 2NO | 690 | ||||||
| F4-02 | 2NC | |||||||
| F4-22 | 2NO+2NC | 1000 | ![]() | |||||
| F4-40 | 4NO | |||||||
| F4-04 | 4NC | |||||||
| F4-31 | 3NO+1NC | |||||||
| F4-13 | 1NO+3NC |
table 2
| Model | Ratedinsulationvoltage V | Conven-tionalheatingcurrentA | Charac-teristicsof delay | Scope ofdelay (s) | Delayrepeatederror | Delaystabilityerror | Temper-atureerror(%C) | Group ofcontacts | Electricallife (times) | Mechanical life | Max.operationfrequency(times/s) | Connect-able min.load | Sketchpicture |
| LA2-D20 | 10 | Delay | 0.1~3 | NO+NC | 0.5~5×10 | 2.5×10 | 3 | 6V10mA | ![]() | ||||
| LA2-D22 | 690 | when | 0.1~30 | ||||||||||
| LA2-D24LA3-D20 | power on | 10~180 | ±5 | ±30* | ±25 | ||||||||
| Delay | 0.1~3 | ||||||||||||
| LA3-D22 | whenpower off | 0.1~30 | |||||||||||
| LA3-D24 | 10~180 |
table 3
| Model | Group of contact | Rated insulationvoltage V | Conventionalheating current A | Electrical life(10° times) | Mechanical life(10{ times) | Max. operatingfrequency (t/s) | Connectablemin. load |
| LA8-11 | 1NO+1NC | 1000 | 3 | 6V 10mA | |||
| LA8-20 | 2NO | 690 | 10 | 0.5~5 | |||
| LA8-02 | 2NC |
Application
CJX1 Series AC contactor is suitable for the circuit of AC 50Hz or 60Hz, rated operating voltage up to 690V. The rated current up to 400A when the usage category of AC-3, and rated operating voltage is 380V, for remotely connecting and breaking the circuit, and it can be combined with JRS2 (3UA) into electromagnet starter to protect the circuit over load produced by operation. This product conforms to:IEC/EN60947-4-1 standards.
| Code for auxiliary contact | 22 | 33 | 44 | |
| Quantity of contact | NO | 2 | 3 | 4 |
| NC | 2 | 3 | 4 | |
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: III
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ± 5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
Main technical parameter
Main technique parameter of contactor to see table 1
table 2
| Model | CJX1-9 | CJX1-12 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | CJX1 | ||
| -16 | -22 | -32 | -45 | -63 | -75 | -85 | -110 | -140 | -170 | -205 | -250 | -300 | -400 | |||||
| Rated insulation voltage Ui V | 690 | |||||||||||||||||
| Ratedoperatingcurrent le (A) | AC-3 | 380V | 9 | 12 | 16 | 22 | 32 | 45 | 63 | 75 | 85 | 110 | 140 | 170 | 205 | 250 | 300 | 400 |
| 660V | 7.2 | 9.5 | 13.5 | 13.5 | 18 | 45 | 63 | 75 | 75 | 110 | 110 | 170 | 170 | 200 | 250 | 320 | ||
| AC-4 | 380V | 3.3 | 4.3 | 7.7 | 8.5 | 12 | 24 | 28 | 34 | 42 | 54 | 68 | 75 | 96 | 110 | 125 | 150 | |
| 660V | 1.4 | 1.9 | 3.5 | 4 | 7.5 | 12 | 14 | 17 | 21 | 27 | 35 | 42 | 67 | 95 | 110 | 115 | ||
| Control power | AC-3 | 380V | 4 | 5.5 | 7.5 | 11 | 15 | 22 | 30 | 37 | 45 | 55 | 75 | 90 | 110 | 132 | 160 | 200 |
| 660V | 5.5 | 7.5 | 11 | 11 | 15 | 37 | 55 | 55 | 55 | 90 | 90 | 160 | 160 | 185 | 220 | 315 | ||
| Pe (kW) | AC-4 | 380V | 1.5 | 2.5 | 4 | 4 | 5.5 | 11 | 15 | 18.5 | 22 | 30 | 37 | 37 | 45 | 55 | 55 | 75 |
| 660V | 1.1 | 1.5 | 3 | 4 | 7.5 | 11 | 11 | 15 | 18.5 | 22 | 30 | 37 | 55 | 75 | 90 | 110 | ||
| Conventional thermal current≥Ith | A | 20 | 3 | 0 | 45 | 70 | 90 | 150 | 170 | 205 | 250 | 300 | 400 | |||||
| Rated operation frequency | AC-3 | 1200 | 600 | 300 | ||||||||||||||
| times/h | AC-4 | 300800 | 150 | |||||||||||||||
| Mechanical life (10000 times) | 1000 | 6010 | ||||||||||||||||
| Electrical life (10000 times) | AC-3 | 100 | 80 | |||||||||||||||
| AC-4 | 20 | 15 | ||||||||||||||||
| Suited fuse specification (RDT16) A | 16 | 20 | 25 | 32 | 50 | 80 | 100 | 125 | 160 | 200 | 200 250 | 250 | 300 400 500 | |||||
4.4.Rated insulation voltage of auxiliary circuit (Ui) is 380V, conventional thermal current (Ith) is 10A,
table 3
| Usage category | Rated operating voltage Ue V | Rated operating current le A | Rated control power | |||
| AC VA | DC W | |||||
| AC-15 | 36 | 10 | 360 | |||
| 110 | 3.2 | |||||
| 220 | 1.64 | |||||
| 380 | 0.95 | |||||
| 48 | 0.69 | |||||
| DC-13 | 110 | 0.3 | 33 | |||
| 220 | 0.15 | |||||
Dimensions
Overall and installation dimension for CJX1-9\~32 to see fig 1 and table 4
table 4
| Model | a max | b | c max | d | e max | g | φ |
| CJX1-9/12 | 79 | 60±0.60 | 46 | 35±0.50 | 106 | 8 | $4 . 8 _ { 0 } ^ { + 0 . 4 8 }$ |
| CJX1-16/22 | 89 | 75±0.60 | 46 | 35±0.50 | 116 | 8 | |
| CJX1-32 | 90 | 75±0.60 | 74 | 35±0.50 | 109 | 8 | $5 _ { 0 } ^ { + 0 . 4 8 }$ |
Overall and installation dimension for CJX1-45\~140 to see fig 2 and table 5
| Model | a max | b | c max | d | e max | f | φ |
| CJX1-45/63 | 120 | 100±0.70 | 92 | 70±0.60 | 125 | 20 | $5 _ { 0 } ^ { + 0 . 4 8 }$ |
| CJX1-75/85 | 135 | 110±0.70 | 105 | 80±0.60 | 145 | 20 | $5 . 5 _ { 0 } ^ { + 0 . 4 8 }$ |
| CJX1-110/140 | 158 | 130±0.80 | 125 | 100±0.70 | 155 | 20 | $6 . 5 _ { 0 } ^ { + 0 . 4 8 }$ |
Overall and installation dimension for CJX1-170\~475
table 6
| Model | a max | b | c max | d | e max | g | φ |
| CJX1-170/205 | 180 | 160 | 163 | 135 | 185 | 28 | 8 |
| CJX1-250/300 | 200 | 145 | 172 | 120 | 198 | 30.5 | 10.5 |
| CJX1-400/475 | 200 | 160 | 187 | 130 | 222 | 39 | 10.5 |
RDC5 Series AC Contactor
Application
RDC5 series AC Contactor is mainly used in the circuit of AC 50Hz or 60Hz, rated voltage up to 690V, rated current up to 95A, for the use of remotely connecting and breaking the circuit, it also can be directly combined with thermal relay into electromagnetic starter to protect the circuit that may have overloaded operations. Contactor can also be equipped with accessories such as the block type auxiliary contacts group, air delay contact, mechanical interlock mechanism, etc. to combine into delay contactor, directional contactor, and star-delta starter. It conforms to the standard IEC/EN60947-4-1.
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: +5℃\~+40℃, average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: III
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ±5°
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
AC CONTACTOR
Main technical parameter
| Model | RDC5-06RDC5-09RDC5-12RDC5-18RDC5-25RDC5-32RDC5-38 RDC5-40RDC5-50 RDC5-65RDC5-80RDC5-953 poles690380/400,660/690 | ||||||||||||||||||||||||
| Number of pole | |||||||||||||||||||||||||
| Rated insulation Voltage (Ui)V | |||||||||||||||||||||||||
| Rated operating voltage (Ue) V | |||||||||||||||||||||||||
| Conventional h | eating current (Ith) A | 16 | 20 | 20 | 25 | 32 | 40 | 40 | 50 | 60 | 80 | 110 | 110 | ||||||||||||
| Rated current | AC-3 | 380/400V | 6 | 9 | 12 | 18 | 25 | 32 | 38 | 40 | 50 | 65 | 80 | 95 | |||||||||||
| 660/690V | 3.8 | 6.6 | 8.9 | 12 | 18 | 22 | 22 | 34 | 39 | 42 | 49 | 49 | |||||||||||||
| (le) A | AC-4 | 380/400V | 2.6 | 3.5 | 5 | 7.7 | 8.5 | 12 | 14 | 18.5 | 24 | 28 | 37 | 44 | |||||||||||
| 660/690V | 1 | 1.5 | 2 | 3.8 | 4.4 | 7.5 | 8.9 | 9 | 12 | 14 | 17.3 | 21.3 | |||||||||||||
| Rated Power | AC-3 | 380/400V | 2.2 | 4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 18.5 | 22 | 30 | 37 | 45 | |||||||||||
| 660/690V | 3 | 5.5 | 7.5 | 10 | 15 | 18.8 | 18.5 | 30 | 33 | 37 | 45 | 45 | |||||||||||||
| (Pe) kW | AC-4 | 380/400V | 1.1 | 1.5 | 2.2 | 3.3 | 4 | 5.4 | 5.5 | 7.5 | 11 | 15 | 18.5 | 22 | |||||||||||
| 660/690V | 0.75 | 1.1 | 1.5 | 3 | 3.7 | 5.5 | 6 | 7.5 | 10 | 11 | 15 | 18.5 | |||||||||||||
| Mechanical li | fe (10000 times/h) | 1200 | 1000 | 900 | 650 | ||||||||||||||||||||
| Electrical life | AC-3 (10000 times/h) | 110 | 90 | 65 | |||||||||||||||||||||
| AC-4 (10000 times/h) | 22 | 22 | 17 | 11 | |||||||||||||||||||||
| Operation | AC-3 (times/h) | 1200 | 600 | ||||||||||||||||||||||
| frequency | AC-4 (times/h) | 300AC 24,36,48,110,127,220/230,240,380/400,415,440 | |||||||||||||||||||||||
| Coil | Rated control voltage Us (V) | ||||||||||||||||||||||||
| Pull-in voltage 50/60Hz V | (0.85~1.1)Us | ||||||||||||||||||||||||
| Release voltage 50/60Hz V | (0.2~0.7)Us | ||||||||||||||||||||||||
| Coil | Pull-in VA | 50 | 60 | 70 | 200 | 200 | |||||||||||||||||||
| powerconsum- | Hold VA | 6~9 | 6~9.5 | 6~9.5 | 15~20 | 15~20 | |||||||||||||||||||
| ption | Power W | 1~3 | 1~3 | 1~3 | 6~10 | 6~10 | |||||||||||||||||||
| Terminals | Pieces mm² | 1 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | 1 | 2 | |
| Flexible wire withterminal mm² | 42.5 | 4 | 2.5 | ||||||||||||||||||||||
| 4 | 2.5 | 4 | 2.5 | 6 | 4 | 6 | 4 | 6 | 4 | 25 | 10 | 25 | 10 | 25 | 10 | 50 | 16 | 50 | 16 | ||||||
| Flexible wire withoutterminal mm² | 4 4 | 4 | 4 | 4 | 4 | 4 | 4 | 6 | |||||||||||||||||
| 6 | 6 | 6 | 6 | 6 | 25 | 16 | 25 | 16 | 25 | 16 | 50 | 25 | 50 | 25 | |||||||||||
| Hard wire mm² | 4 4 | 4 | 4 | 4 | 4 | 6 | 6 | 6 | 6 | 10 | 6 | 10 | 6 | 25 | 10 | 25 | 10 | 25 | 10 | 50 | 25 | 50 | 25 | ||
| Tighteningtorque | (N·m) | 1.2 | 1.8 | 5 | 9 | ||||||||||||||||||||
| Suited fusetype | Model | RDT16 ( | NT)- | 00 | |||||||||||||||||||||
| Rated current (A) | 16 | 20 | 20 | 32 | 40 | 50 | 63 | 63 | 80 | 80 | 100 | 125 | |||||||||||||
| Suited thermal relay | RDR5-25 | RDR5-25R | DR5-25 R | DR5-25R | DR5-25 | RDR5-25 | RDR5-25 R | DR5-93R | DR5-93 R | DR5-93 | RDR5-93 R | DR5-93 | |||||||||||||
| RDR5-36 | RDR5-36 | ||||||||||||||||||||||||
| Auxiliary contacts | be added with F4, LA8 auxi | Can be added with F4, LA8 auxiliary contacts, LA2-D/LA3-D type air delay contacts | |||||||||||||||||||||||
| Model | Amax | Bmax | B1max | B2max | Cmax | C1max | C2max |
| RDC5-06,09,12,18 | 74.5 | 45.5 | 58 | 71 | 82.5 | 114.5 | 139.5 |
| RDC5-25,32,38 | 83 | 56.5 | 69 | 82 | 97 | 129 | 154 |
| RDC5-40,50,65 | 127.5 | 74.5 | 88 | 101 | 117 | 148.5 | 173.5 |
| RDC5-80,95 | 127.5 | 85.5 | 99 | 112 | 125.5 | 157 | 182 |
| Note: | B1max=contactor+LA8; B2max=contactor+2× LA8; C1max=contactor+F4; C2max=contactor+LA2(3)D | ||||||
| Model | a | b | C | d | e | f |
| RDC5-06,09,12,18 | 35 | 50/60 | 一 | 一 | ||
| RDC5-25,32, 38 | 40 | 50/60 | - | - | ||
| RDC5-40,50,65 | 105 | 40 | 100/110 | 59 | ||
| RDC5-80,95 | 105 | 40 | 100/110 | 67 |
RDC19B(CJ19)
Series Switch-over Capacitor Contactor
Application
RDC19B (CJ19) series switch-over capacitor contactor is suitable for the power circuit of AC50/60Hz, rated power voltage up to 660V and below, for the use of low voltage reactive power compensation equipment added-in or remove the low voltage shunt capacitor. This contactor is equipped with a surge suppression device, and it can effectively restrain the impact of closing inrush current on capacitor and reduce the breaking instantaneous overload voltage without adding the current limiting reactor. It conforms to the standard IEC/EN60947-4-1
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: + 5 ^ { \circ } \mathsf { C } ~ + 4 0 ^ { \circ } \mathsf { C } , average temperature within 24h does not exceed +35℃
3.2 Altitude: does not exceed 2000m
3.3 Atmospheric condition: when the highest temperature is +40℃, the relatively humidity does not exceed 50%; it can allow relatively high humidity when it is at relatively low temperature, for instance, it reaches 90% when it is at +20℃, it should take measurement when there have condensation occurred due to the temperature variation.
3.4 Pollution grade: 3
3.5 Installation category: III
3.6 Installation position: the gradient of the mounting surface to the vertical surface does not exceed ± { } 5 ^ { \circ } { }
3.7 Impact and vibration: product should be installed and used at the places without obvious shake, impact and vibration.
Wiring principle
Main technical parameter
| Model | RDC19-25/□□B | RDC19-32/□□B | RDC19-43/□□B | RDC19-63/□□B | RDC19-80/□□B | RDC19-95/□□B | |
| Controllable capacitor | 220V | 6 | 9 | 10 | 15 | 22 | 22 |
| capacity Kvar | 380V | 12 | 18 | 20 | 30 | 40 | 50 |
| Rated insulation voltage V | 660 | ||||||
| Rated voltage V | 220/380 | ||||||
| Conventional heating current A | 25 | 32 | 43 | 63 | 87 | 108 | |
| AC-6b Rated current A | 17 | 23 | 29 | 43 | 58 | 72 | |
| Auxi. Wire/Rated current of capacitor A | 20le | ||||||
| Control voltage V | 48,110,127,220,3806 | ||||||
| Conventional heating current of auxiliarycontact A | |||||||
| Operation frequency (times/h) | 120110 | ||||||
| Electrical life (10000 times) | |||||||
| Mechanical life (10000 times) | |||||||
| Tightening torque of terminal (N•m) | 0.8 | 1.2 | 1.2 | 6.0 10.0 | 10.0 | ||
Dimensions
Contactor can be installed by screw, and it also can be installed by DIN rail. Overall and installation dimension of RDC19B to see fig 2 and table 2
| Model | Overall dimension | Installation dimension | ||||||
| A | B | C | D | a | b | ∅ | Din rail | |
| RDC19-25/□□B | 84 | 56 | 130 | 140 | 40 | 50/60 | 4.5 | 35 |
| RDC19-32/□□B | 87 | 58 | 136 | 140 | 40 | 50/60 | 4.5 | 35 |
| RDC19-43/□□B | 87 | 58 | 136 | 140 | 40 | 50/60 | 4.5 | 35 |
| RDC19-63/□□B | 127 | 79 | 150 | 180 | 40 | 100/110 | 6.5 | |
| RDC19-80/□□B | 127 | 85 | 160 | 200 | 40 | 100/110 | 6.5 | 35 or 75 |
| RDC19-95/□□B | 127 | 85 | 160 | 200 | 40 | 100/110 | 6.5 | |
Auxiliary contacts
Code for the auxiliary contacts to see table 3
| Specification | Code for auxiliary contact | Number of auxiliary contacts | Marking | ||
| NO | NC | ||||
| 25A, 32A, 43A | 20 | 2 | 0 | 20E | 13,14;23,24 |
| 02 | 0 | 2 | 02E | 11,12;21,22 | |
| 11 | 1 | 1 | 11E | 13,14;21,22 | |
| 63A, 80A,95A | 21 | 2 | 1 | 21E | 13,14;21,22;33,34 |
| 12 | 1 | 2 | 12E | 13,14;21,22;31,32 | |
CJX2-N
Mechanical Interlocking Contactor
Application
CJX2-N mechanical interlocking contactor is suitable for using in the circuits up to the rated voltage 660V, for controlling the motor. This mechanical interlocking device ensures contact changeover of the two convertible contactors. It conforms to lEC60947-4-1.
Table 1
| Type | Rated currentAC-3(A) | controlled power(KW) | ||||
| 220V | 380V | 415V | 440V | 660V | ||
| CJX2-09N | 9 | 2.2 | 4 | 4 | 4 | 5.5 |
| CJX2-12N | 12 | 5.5 | 5.5 | 5.5 | 5.5 | 7.5 |
| CJX2-18N | 18 | 7.5 | 7.5 | 9 | 9 | 10 |
| CJX2-25N | 25 | 5.5 | 11 | 11 | 11 | 15 |
| CJX2-32N | 32 | 7.5 | 15 | 15 | 15 | 18.5 |
| CJX2-40N | 40 | 18.5 | 18.5 | 22 | 22 | 30 |
| CJX2-50N | 50 | 15 | 22 | 25 | 25 | 33 |
| CJX2-65N | 63 | 18.5 | 30 | 37 | 37 | 37 |
| CJX2-80N | 80 | 22 | 37 | 45 | 45 | 45 |
| CJX2-95N | 95 | 22 | 45 | 45 | 45 | 41 |
| CJX2-115N | 115 | 30 | 55 | 59 | 59 | 80 |
| CJX2-150N | 150 | 40 | 75 | 80 | 80 | 100 |
| CJX2-170N | 170 | 55 | 90 | 100 | 100 | 110 |
| CJX2-205N | 205 | 63 | 110 | 110 | 110 | 129 |
| CJX2-245N | 245 | 75 | 132 | 132 | 132 | 160 |
| CJX2-300N | 300 | 100 | 160 | 200 | 200 | 220 |
| CJX2-410N | 410 | 110 | 220 | 250 | 250 | 280 |
| CJX2-475N | 475 | 147 | 265 | 280 | 280 | 355 |
| CJX2-620N | 620 | 200 | 335 | 400 | 400 | 450 |
| Type | Number of poles | Rated currentAC-3(A) | Rated currentIn/A | controlled power(KW) | |
| 220V | 380V | ||||
| CJX2-F115N | 3P | 115 | 250 | 200 | 55 |
| CJX2-F1154N | 4P | 115 | 250 | 200 | 55 |
| CJX2-F150N | 3P | 150 | 355 | 250 | 75 |
| CJX2-F1504N | 4P | 150 | 355 | 250 | 75 |
| CJX2-F185N | 3P | 185 | 425 | 275 | 90 |
| CJX2-F1854N | 4P | 185 | 425 | 275 | 90 |
| CJX2-F225N | 3P | 225 | 500 | 315 | 110 |
| CJX2-F2254N | 4P | 225 | 500 | 315 | 110 |
| CJX2-F265N | 3P | 265 | 630 | 350 | 132 |
| CJX2-F2654N | 4P | 265 | 630 | 350 | 132 |
| CJX2-F330N | 3P | 330 | 800 | 400 | 160 |
| CJX2-F3304N | 4P | 330 | 800 | 400 | 160 |
| CJX2-F400N | 3P | 400 | 800 | 500 | 200 |
| CJX2-F4004N | 4P | 400 | 800 | 500 | 200 |
| CJX2-F500N | 3P | 500 | 1000 | 700 | 250 |
| CJX2-F5004N | 4P | 500 | 1000 | 700 | 250 |
| CJX2-F630N | 3P | 630 | 1250 | 1000 | 335 |
| CJX2-F6304N | 4P | 630 | 1250 | 1000 | 335 |
| CJX2-F800N | 3P | 800 | 1250 | 1000 | 400 |
Table 3
| CJX2-N | a | b | C | e1(3P) | e2(4P) | G |
| 09N,12N | 105 | 74 | 84 | 7 | 6 | 95 |
| 18N | 106 | 74 | 92 | 8 | - | 95 |
| 25N | 127 | 84 | 99 | 8 | 7 | 111 |
| 32N,38N | 127 | 84 | 117 | 10 | - | 111 |
Table 4
| CJX2-N(3-pole) | a | b | C | e1 | GG | 1 |
| 40N,50N,55N | 165 | 127 | 142 | 5 | 50 | 90 |
| CJX2-N(4-pole) | a | b | C | e1 | GG | 1 |
| 40N,65N | 182 | 127 | 133 | 11 | 57 | 97 |
c.e1 and e2 including cabing
| CJX2-N(3-pole) | a | b | C | e1 | GG | 1 |
| 80N,95N | 182 | 127 | 158 | 13 | 57 | 90 |
| CJX2-N(4-pole) | a | b | C | e1 | GG | 1 |
| 80N | 207 | 127 | 158 | 20 | 71 | 11 |
| CJX2-N(3-pole) | Amax | J | P1 | f | b | φ | Cmax |
| CJX2-F115N | 350 | 71 | 77 | 131 | 330 | 6.5 | 182 |
| CJX2-F1154N | 425 | 105 | 77 | 131 | 370 | 6.5 | 182 |
| CJX2-F150N | 350 | 71 | 71 | 131 | 330 | 6.5 | 182 |
| CJX2-F1504N | 425 | 105 | 71 | 131 | 370 | 6.5 | 182 |
| CJX2-F185N | 350 | 78 | 71 | 130 | 330 | 6.5 | 193 |
| CJX2-F1854N | 430 | 114 | 70 | 130 | 370 | 6.5 | 193 |
| CJX2-F1225N | 350 | 78 | 55 | 130 | 330 | 6.5 | 193 |
| CJX2-F2254N | 430 | 118 | 54 | 130 | 370 | 6.5 | 193 |
| CJX2-F265N | 450 | 109 | 96 | 147 | 428 | 6.5 | 225 |
| CJX2-F2654N | 546 | 157 | 100 | 147 | 485 | 6.5 | 225 |
| CJX2-F330N | 450 | 124 | 112 | 147 | 428 | 6.5 | 232.5 |
| CJX2-F3304N | 546 | 166 | 107 | 147 | 485 | 6.5 | 232.5 |
| CJX2-F400N | 485 | 157 | 110 | 146 | 460 | 8.5 | 232.5 |
| CJX2-F4004N | 485 | 157 | 107 | 146 | 485 | 8.5 | 232.5 |
| CJX2-F500N | 485 | 156 | 115 | 150 | 460 | 8.5 | 245.5 |
| CJX2-F630N | 650 | 139 | 140 | 181 | 625 | 10.5 | 268.5 |
| CJX2-F6304N | 810 | 139 | 137 | 181 | 785 | 10.5 | 268.5 |
| Model | H | H | H1 | H1 |
| Min | Max | Min | Max | |
| CJX2-F115N, CJX2-F150N | 200 | 310 | 80 | 190 |
| CJX2-F185N, CJX2-F225N | 220 | 310 | 100 | 190 |
| CJX2-F265N | 250 | 380 | 130 | 260 |
| CJX2-F330N | 260 | 380 | 60 | 200 |
| CJX2-F400N | 280 | 380 | 100 | 200 |
| CJX2-F500N | 300 | 380 | 120 | 200 |
| CJX2-F630N | 380 | 380 | 200 | 200 |
CJX1-N(P3TD)
Mechanical Interlocking Contactor
Application
CJX1-N Series mechanical interlocking contactor is suitable for the circuit of AC 50Hz or 60Hz, rated operating voltage to 690V-1000V. Under the AC-3 class, the rated operating voltage is 9A-475V when the rated working voltage is 380V, which is mainly used to control the positive and negative rotation of AC motors.
Model No.
Main technical parameter
| Type | Auxiliary contact | Rated | Controllable motor power AC-3 | Relay type | Fuse type | ||||||
| NO | NC | workingcurrent(380V) | 230/200VKW | 400/380VKW | 500VKW | 690/660VKW | 1000VKW | Type 1 (A) | Type 2 (A) | ||
| CJX1-9/22N | 2 | 2 | 9 | 2.4 | 4 | 5.5 | 5.5 | = | 3UA50 | 35 | 25 |
| CJX1-12/22N | 2 | 2 | 12 | 3.3 | 5.5 | 7.5 | 7.5 | = | 3UA50 | 35 | 25 |
| CJX1-16/22N | 2 | 2 | 16 | 4 | 7.5 | 9 | 11 | - | 3UA52 | 35 | 25 |
| CJX1-22/22N | 2 | 2 | 22 | 5.5 | 11 | 11 | 11 | = | 3UA52 | 35 | 25 |
| CJX1-32/22N | 2 | 2 | 32 | 8.5 | 15 | 21 | 23 | - | 3UA55 | 35 | 25 |
| CJX1-38/22N | 2 | 2 | 38 | 11 | 18.5 | 25 | 23 | = | 3UA55 | 35 | 25 |
| CJX1-45/22N | 2 | 2 | 45 | 15 | 22 | 30 | 39 | = | 3UA58 | 160 | 100 |
| CJX1-63/22N | 2 | 2 | 63 | 18.5 | 30 | 41 | 55 | - | 3UA58 | 160 | 125 |
| CJX1-75/22N | 2 | 2 | 75 | 22 | 37 | 50 | 67 | 39 | 3UA58 | 250 | 160 |
| CJX1-110/22N | 2 | 2 | 110 | 37 | 55 | 76 | 100 | 65 | 3UA60 | 315 | 250 |
| CJX1-170/22N | 2 | 2 | 170 | 55 | 90 | 118 | 156 | 90 | 3UA62 | 355 | 250 |
| CJX1-250/22N | 2 | 2 | 250 | 78 | 132 | 178 | 235 | 132 | 3UA66 | 500 | 315 |
| CJX1-400/22N | 2 | 2 | 400 | 125 | 200 | 284 | 375 | 250 | 3UA66 | 800 | 500 |
| CJX1-745/22N | 2 | 2 | 745 | 148 | 252 | 342 | 432 | 250 | 3UA66 | 800 | 500 |
RDCH8
Household AC contactor
Description
RDCH8 series AC contactor, is mainly applied to circuit of 50Hz or 60Hz, rated operational volteage up to 400V, Rated operational current up to 63A, to control the household appliance and the low induction load, and also can control the household motor load, the control power should decreased accordingly.This production can be used in the household, hotel, apartment those place to realize automation, and also can used in the other appliances. This production conforms to the standard of IEC61095.
Model No.
Normal working condition and Installation environment
3.1 Temperature: -5°+40°, the average temperature of 24 hours should not exceed 35C.
3.2 Altitude : should not exceed 2000m.
3.3 The relative humidity: no more than 50%, when Temperature is +40°C. The product can withstand the higher humidity under lower temperature, for instance, when temperature at +20°C, the product can withstand 90% relative humidity.
3.4 Pollution class: 2 class
3.5 Installation type: Il class
3.6 Installation codition: the angle between the prodouct and vertical plane should not exceed 5°.
3.7 Installation methods: adopt 35mm DIN-Rail
3.8 Protection class: IP20.
Main Technical parameter
4.1 Poles: 1P, 2P, 3P, 4P
4.2 The specification see Table 1, Table 2
| Model No. | Rated current(pole) | Using type | Rated operationalcurrent(A) | Rated insulationvoltage (V) | Control power(kW) | Connectiontype | |
| 16 (1P/2P) | AC-7a | 16 | 500 | 3.5 | |||
| AC-7b | 7 | 500 | 1.0 | ||||
| RDCH8-25 | 20 (1P/2P) | AC-7a | 20 | 500 | 4 | With soft-cable: | |
| AC-7b | 8.5 | 500 | 1.2 | With hard-cable: | |||
| 25 (1P/2P) | AC-7a | 25 | 500 | 5.4 | 6mm² | ||
| AC-7b | 9 | 500 | 1.4 | ||||
| 25 (3P/4P) | AC-7a | 40 | 500 | 16 | |||
| RDCH8-63 | 32 RP) | AC-7a | 32 | 500 | 7.2 | ||
| 32 (3P/4P) | AC-7a | 32 | 500 | 21 | With soft-cable:2×10mm²With hard-cable:25mm² | ||
| 40 (2P) | AC-7a | 40 | 500 | 8.6 | |||
| 40 (3P/4P) | AC-7a | 40 | 500 | 26 | |||
| 63 (2P) | AC-7a | 63 | 500 | 14 | |||
| 63 (3P/4P) | AC-7a | 63 | 500 | 40 | |||
| Pole | Rated current (A) | Rated voltage (V) | NO NC |
| 1P | 16~25 | 220/230 | 10 |
| 2P | 16~25 | 220/230 | 20 |
| 40~63 | 02 | ||
| 3P | 25 | 380/400 | 30 |
| 40~63 | |||
| 4P | 25 | 380/400 | 40 |
| 40~63 | 04 |
it should release and break between 75% and 20%(2P) or 10%(1P) of the rated control power voltage Us.
4.4 Mechanical life: no less than 1 million times.
4.5 Electrical life: no less than 100 thousands times.
4.6 Wiring diagram: see Flg1 to Fig5
| Model No. | Rated current(Poles) | D | L | L1 | L2 | H | H1 | H2 | H3 |
| RDCH8-25 | 16/25 1P,2P | 18 | 85 | 35.5 | 45.5 | 66 | 61 | 45 | 23 |
| 16/25 3P,4P | 36 | 85 | 35.5 | 45.5 | 66 | 61 | 45 | 23 | |
| RDCH8-63 | 40/63 2P | 36 | 85 | 35.5 | 45.5 | 66 | 61 | 45 | - |
| 40/63 3P,4P | 54 | 85 | 35.5 | 45.5 | 66 | 61 | 45 | - |
PLE1-D
Series Magnetic Starter
Application
PLE1-D magnetic starter is applied to circuit of AC 50/60Hz, voltage up to 660V, current up to 95A, used for directly starting or stopping the motor. The starter (assembled with thermal overload relay) could protect motor against overload or phase loss.
Structure characteristic
1. The starter is protected by enclosure (plastic enclosure for PLE1-D09\~PLE1-D32; metal enclosure for PLE1-D40\~PLE1-D95). The best protective grade of enclosure could be IP65. 2. Operating mechanism is the manual pushbutton: START (green) and STOP (red). PLE1-D is nonreversing starter, equipped with thermal overload relay.
Main technical parameter
1. Main technical parameter and component parts please see Table 1.
2. Rated control circuit voltage (Us) of the starter is: AC50/60Hz, 24V, 42V, 110V, 220/230V, 240V,
380V/400V, 415V, 440V, 480V, and 600V.
3. Operation range:
Pull-in voltage: (50/60Hz) 80%Us-110%Us; (50/60Hz) 85%Us-110%Us;
Release voltage: (50/60Hz) 20%Us-75%Us.
4. The actuation range of starter (assembled with thermal overload relay), has the action characteristics of thermal relay.
5. The operation frequency of starter (assembled with thermal overload relay) is 30 times/hour.
| Item No. | Ratedthermalcurrent Ith | Ratedinsulationvoltage Ui | Rated working current (A) | Rated power in ca | tegory AC-3 (kW) | Assembled | Current | AssembledAC contactormodel No. | |||||||
| AC-3 | AC-4 | 220V | 380V | 415V | 440V | 500V | 660V690V | relaymodel No. | setttingrate (A) | ||||||
| 380V | 660V | 380V | 660V | 230V | 400V | ||||||||||
| 0.37 | 0.37 | 0.37 | 0.37 | RDJ2-25 | 0.63-1 | ||||||||||
| 0.37 | 0.55 | 0.55 | 0.55 | 0.55 | RDJ2-25 | 1-1.6 | |||||||||
| 0.75 | 0.75 | 1.1 | 1.1 | 1.1 | 1.1 | RDJ2-25 | 1.6-2.5 | ||||||||
| PLE1-D09 | 20A | 9 | 6.6 | 3.5 | 1.5 | 1.1 | 1.5 | 1.5 | 1.5 | 2.2 | 2.2 | RDJ2-25 | 2.5-4 | CJX2-09 | |
| 1.5 | 2.2 | 2.2 | 2.2 | 3.7 | 3.7 | RDJ2-25 | 4-6 | ||||||||
| 2.2 | 3 | 3.7 | 3.7 | 4 | 4 | RDJ2-25 | 5.5-8 | ||||||||
| 2.2 | 4 | 4 | 4 | 5.5 | 5.5 | RDJ2-25 | 7-10 | ||||||||
| PLE1-D12 | 20A | 12 | 8.9 | 5 | 2 | 3 | 5.5 | 5.5 | 5.5 | 7.5 | 7.5 | RDJ2-25 | 9-13 | CJX2-12 | |
| PLE1-D18 | 32A | 18 | 10.6 | 7.7 | 3.8 | 4 | 7.5 | 9 | 9 | 10 | 10 | RDJ2-25 | 12-18 | CJX2-18 | |
| PLE1-D25 | 40A | 25 | 18 | 8.5 | 4.4 | 5.5 | 11 | 11 | 11 | 15 | 15 | RDJ2-25 | 17-25 | CJX2-25 | |
| PLE1-D32 | 50A | 32 | 21 | 12 | 7.5 | 7.5 | 15 | 15 | 15 | 18.5 | 18.5 | RDJ2-25 | 23-32 | CJX2-32 | |
| PLE1-D40 | 60A | 40 | 34 | 18.5 | 9 | 11 | 18.5 | 22 | 22 | 22 | 30 | RDJ2-93 | 30-40 | CJX2-40 | |
| PLE1-D50 | 80A | 50 | 39 | 24 | 12 | 15 | 22 | 25 | 30 | 30 | 33 | RDJ2-93 | 37-50 | CJX2-50 | |
| PLE1-D65 | 80A | 65 | 42 | 28 | 14 | 18.5 | 30 | 37 | 37 | 37 | 37 | RDJ2-93 | 55-70 | CJX2-65 | |
| PLE1-D80 | 100A | 80 | 49 | 37 | 17.3 | 22 | 37 | 45 | 45 | 55 | 45 | RDJ2-93 | 63-80 | CJX2-80 | |
| PLE1-D95 | 100A | 95 | 49 | 44 | 21.3 | 25 | 45 | 45 | 55 | 55 | 45 | RDJ2-93 | 80-93 | CJX2-95 | |
QJX2
Series Star-delta Starter
Application
QJX2 series star-delta starter is applied for circuit of AC50/60Hz, voltage up to 660V, current up to 95A, used for motor starting in category AC-3. The starter (assembled with timer) could transfer “Star-Delta” automatically, to reduce the motor starting voltage and current.
Model No.
Normal operating condition and installation condition
1. Altitude: ≤2000m;
2. Ambient temperature: -5℃\~+40℃, average value≤ +35℃ (in 24 hours);
3. Humidity: air relative humidity is lower than 50% at +40℃, higher relative humidity is permitted at lower temperature. Take special measures to condensation, which is caused by temperature change. 4. The installation and operation location has no obvious shake, impact or vibration.
5. Mounting condition: the gradient between mounting surface and vertical plane is not bigger than ± 5°
Main technical parameter
1. QJX2 Series AC Star-Delta starter is suitable to control delta connection motor. When the motor is transforming Star-Delta, star starting current is 1.8\~2.6 times of motor rated current, however, while running delta connection, the current is 0.58 time of motor rated current.
2. QJX2 series Star-Delta starter technical data please see Table 1
| Star-Delta starter | 380V squirrel cage motor | Matchedthermalrelaymodel | Currentadjustrange(A) | Matchedfuse ratedcurrent(A) | |||||
| Model No. | Product composition | Rated | 0.58 | Controlpower (kW) | |||||
| KM2 | KM3 | KM1 c | urrent In (A) | In (A) | |||||
| QJX2-12 | 18.5 | 9 | 10.7 | JRS1-12 | 10-13 | 20 | |||
| CJX2-12 | CJX2-12 | CJX2-09 | 20 | 10 | 11.6 | JRS1-12 | 10-13 | 20 | |
| 22 | 11 | 12.8 | JRS1-12 | 10-13 | 25 | ||||
| QJX2-18 | CJX2-18 | CJX2-18 | CJX2-09 | 30 | 15 | 17.4 | JRS1-25 | 13-18 | 32 |
| 37 | 18.5 | 21.5 | JRS1-25 | 18-25 | 40 | ||||
| QJX2-25 | CJX2-25 | CJX2-25 | CJX2-09 | 37 | 21.5 | 18.5 | JRS1-25 | 18-25 | 40 |
| QJX2-32 | CJX2-32 | CJX2-32 | CJX2-25 | 44 | 25.5 | 22 | JRS1-32 | 23-32 | 50 |
| 52 | 30.2 | 25 | JRS1-32 | 23-32 | 63 | ||||
| QJX2-40 | CJX2-40 | CJX2-40 | 44 | 25.5 | 22 | JRS1-40 | 23-32 | 50 | |
| 52 | 30.2 | 25 | JRS1-40 | 23-32 | 63 | ||||
| CJX2-25 | 60 | 34.8 | 30 | JRS1-40 | 30-40 | 63 | |||
| 68 | 39.5 | 33 | JRS1-63 | 38-50 | 80 | ||||
| 72 | 41.8 | 37 | JRS1-63 | 38-50 | 80 | ||||
| QJX2-50 | CJX2-50 | CJX2-50 | CJX2-40 | 79 | 45.8 | 40 | JRS1-63 | 38-50 | 80 |
| 85 | 49.3 | 45 | JRS1-63 | 48-57 | 100 | ||||
| 98 | 56.8 | 51 | JRS1-63 | 48-57 | 100 | ||||
| 105 | 60.9 | 55 | JRS1-63 | 57-66 | 125 | ||||
| QJX2-80 | CJX2-80 | CJX2-80 | 112 | 65 | 59 | JRS1-63 | 57-66 | 125 | |
| CJX2-50 | 117 | 67.9 | 63 | JRS1-80 | 63-80 | 160 | |||
| 138 | 80 | 75 | JRS1-80 | 63-80 | 160 | ||||
| QJX2-95 | CJX2-95 | CJX2-95 | CJX2-50 | 147 | 85.3 | 80 | JRS1-F105 | 75-105 | 160 |
The control motor power (under different voltage) of QJX2 Series (Star-Delta Starter), and other technical data, please see Table 2.
Table 2
| Model No. | Rated workvoltage | Rated workcurrent(AC-3) | 3-phase motor power | Electrical life | Operationfrequency(times/h) | Mechanical life(10times) | Time delayelectrical life(104 times) | Maximumstartingtime (s) | |||
| Category | AC-3 (kW) | (10times) | |||||||||
| 220V | 380V | 415V | 440V | ||||||||
| QJX2-12 | 12A | 5.5 | 11 | 11 | 11 | 100~200 | 500 | 30 | |||
| QJX2-18 | 18A | 11 | 18.5 | 22 | 22 | 20 | |||||
| QJX2-25 | 25A | 11 | 18.5 | 22 | 22 | (AC-3) | |||||
| QJX2-32 | 32A | 15 | 25 | 25 | 25 | 30 | |||||
| QJX2-40 | 660V | 40A | 18.5 | 37 | 37 | 37 | |||||
| QJX2-50 | 50A | 25 | 55 | 59 | 59 | 1 | |||||
| QJX2-80 | 80A | 37 | 75 | 75 | 75 | (AC-4) | |||||
| QJX2-95 | 95A | 45 | 80 | 80 | 80 | ||||||
Dimensions
The outline and installation dimension of QJX2 Series (Star-Delta Starter) please see fig. 1\~3 and Table 3
| Model No. | Overall and installation dimensions (mm) | ||||||
| A | B | C | D | E | F | φ | |
| QJX2-12 | 140 | 124 | 140 | 90 | 110 | 10 | 4-φ6.3 |
| QJX2-18 | 140 | 124 | 140 | 90 | 110 | 10 | 4-φρ6.3 |
| QJX2-25 | 170 | 124 | 149 | 90 | 110 | 10 | 4-φρ6.3 |
| QJX2-32 | 170 | 124 | 149 | 90 | 110 | 10 | 4-φ6.3 |
PGV2 & PGV3
Manual Motor Starter
Application
1.1 Standard: IEC / EN 60947-4-1, IEC 60947-2
1.2 Protection class: IP20
1.3 Electric rating: AC 50/60Hz, AC 690V
Normal operating condition and installation condition
2.1 Ambient air temperature: -5...+ 40℃
2.2 Relative humidity: ≤90%
2.3 Pollution degree: III
2.4 Product should be installed and operated at a place without obvious shake, impact or vibration.
Main technical parameter
3.1 Rated insulation voltage Ui: 690V
3.2 Rated operating voltage Ue: 230/240V, 400/415V, 440V, 500V, 690V
3.3 Rated impulse withstand voltage Uimp: 8000V
3.4 Rated current: up to 32A for PGV2; up to 80A for PGV3
3.5 Protection reference to see below:
| No. | Appliedcurrent | Initial status | Time | Expectedresults | Ambienttemperature | |
| 1 | 1.05 In | cold status | t≥2 hours | no tripping | ||
| 2 | 1.20 In | heat status(right after test No.1) | t<2 hours | +20℃±2℃ | ||
| 3 | 1.50 ln | heat status(right after test No.1) | trippingclass | (10A) t<2 min | tripping | |
| (10A) t<4 min | ||||||
| 4 | 7.20 In | cold status | trippingclass | (10A) 2 s<t ≤10 s | ||
| (10A)4 s<t ≤10 s | ||||||
Table 2
| No. | Applied | current | Initial status | Time | Expectedresults | Ambienttemperature |
| any 2 phase | Other phases | |||||
| 1 | 1.0 | 0.9 | cold status | t≥2 hours | no tripping | +20℃±2℃ |
| 2 | 1.15 | 0 | heat status(right after test No.1) | t<2 hours | tripping |
| No. | Appliedcurrent | Initial status | Time | Expected results | Ambienttemperature |
| 1 | 1.0 ln | cold status | t≥2 hours | no tripping | |
| 2 | 1.20 ln | heat status(right after test No.1) | t<2 hours | tripping | +40℃±2℃ |
| 3 | 1.05 ln | cold status | t≥2 hours | no tripping | |
| 4 | 1.30 In | heat status(right after test No.1) | t<2 hours | tripping | -5℃±2℃ |
Table 4
| Model | Range ofsetting current (A) | Ratedcurrent (A) | Electromagnetictripping current (A) | Matched three phase motor | ||||
| 220V | 400V | 440V | 500V | 690V | ||||
| PGV2-M01 | 0.10~0.16 | 0.16 | 1.50 | -- | - - | - - | -- | - - |
| PGV2-M02 | 0.16~0.25 | 0.25 | 2.40 | -- | - - | -- | -- | -- |
| PGV2-M03 | 0.25~0.40 | 0.40 | 5.00 | -- | -- | -- | -- | -- |
| PGV2-M04 | 0.40~0.63 | 0.63 | 8.00 | -- | -- | -- | -- | 0.37 |
| PGV2-M05 | 0.63~1.00 | 1.00 | 13.0 | - - | -- | 0.37 | 0.37 | 0.55 |
| PGV2-M06 | 1.00~1.60 | 1.60 | 22.5 | - - | 0.37 | 0.55 | 0.75 | 1.10 |
| PGV2-M07 | 1.60~2.50 | 2.50 | 33.5 | 0.37 | 0.75 | 1.10 | 1.10 | 1.50 |
| PGV2-M08 | 2.50~4.00 | 4.00 | 51 | 0.75 | 1.50 | 1.50 | 2.20 | 3.00 |
| PGV2-M10 | 4.00~6.30 | 6.30 | 78 | 1.10 | 2.20 | 3.00 | 3.70 | 4.00 |
| PGV2-M14 | 6.00~10.00 | 9.00 | 138 | 2.20 | 4.00 | 4.00 | 5.50 | 7.50 |
| PGV2-M16 | 9.00~14.00 | 13.00 | 170 | 3.00 | 5.50 | 7.50 | 7.50 | 9.00 |
| PGV2-M20 | 13.00~18.00 | 17.00 | 223 | 4.00 | 7.50 | 9.00 | 9.00 | 11.00 |
| PGV2-M21 | 17.00~23.00 | 21.00 | 327 | 5.50 | 11.00 | 11.00 | 11.00 | 15.00 |
| PGV2-M22 | 20.00~25.00 | 23.00 | 327 | 5.50 | 11.00 | 11.00 | 15.00 | 18.50 |
| PGV2-M32 | 24.00~32.00 | 24.00 | 416 | 7.50 | 15.00 | 15.00 | 18.50 | 26.00 |
| Model | Rated ultimate short-circuitbreaking capacity Icu (kA) | Rated service short-circuitbreaking capacity Ics (kA) | Fuse | ||||||||||||
| 220V | 400V | 440V | 500V | 690V | 220V | 400V | 440V | 500V | 690V | 220V | 400V | 440V | 500V | 690V | |
| PGV2-M01 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | * | * | * | * |
| PGV2-M02 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | * | * | 大 | * |
| PGV2-M03 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | * | * | 大 | * |
| PGV2-M04 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | * | * | * | * |
| PGV2-M05 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | 大 | * | * | 大 |
| PGV2-M06 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | 100 | * | * | * | * | * |
| PGV2-M07 | 100 | 100 | 100 | 100 | 3 | 100 | 100 | 100 | 100 | 2.25 | * | 大 | * | 大 | 20 |
| PGV2-M08 | 100 | 100 | 100 | 100 | 3 | 100 | 100 | 100 | 100 | 2.25 | * | * | * | * | 32 |
| PGV2-M10 | 100 | 100 | 100 | 100 | 3 | 100 | 100 | 50 | 50 | 2.25 | * | * | 63 | 63 | 40 |
| PGV2-M14 | 100 | 100 | 100 | 100 | 3 | 100 | 100 | 15 | 10 | 2.25 | * | * | 63 | 63 | 40 |
| PGV2-M16 | 100 | 15 | 8 | 6 | 3 | 100 | 7.50 | 4 | 4.50 | 2.25 | * | 80 | 63 | 63 | 50 |
| PGV2-M20 | 100 | 15 | 8 | 6 | 3 | 100 | 7.50 | 4 | 4.50 | 2.25 | * | 80 | 63 | 63 | 50 |
| PGV2-M21 | 50 | 15 | 6 | 4 | 3 | 50 | 6 | 3 | 3 | 2.25 | 100 | 100 | 80 | 63 | 50 |
| PGV2-M22 | 50 | 15 | 6 | 4 | 3 | 50 | 6 | 3 | 3 | 2.25 | 100 | 100 | 80 | 63 | 50 |
| PGV2-M32 | 30 | 10 | 6 | 4 | 3 | 30 | 10 | 4.50 | 3 | 2.25 | 100 | 100 | 80 | 63 | 50 |
Table 6
| Model | Range ofsetting current (A) | Ratedcurrent (A) | Electromagnetic | Matched three phase motor | ||||
| tripping current (A) | 220V | 400V | 440V | 500V | 690V | |||
| PGV3-M06 | 1.00~1.60 | 1.6 | 19.2 | -- | 0.37 | 0.55 | 0.75 | 1.10 |
| PGV3-M07 | 1.60~2.50 | 2.5 | 30 | 0.37 | 0.75 | 1.10 | 1.10 | 1.50 |
| PGV3-M08 | 2.50~4.00 | 4 | 48 | 0.75 | 1.50 | 1.50 | 2.20 | 3.00 |
| PGV3-M10 | 4.00~6.00 | 6 | 72 | 1.10 | 2.20 | 3.00 | 3.70 | 4.00 |
| PGV3-M14 | 6.00~10.00 | 10 | 120 | 2.20 | 4.00 | 4.00 | 5.50 | 7.50 |
| PGV3-M20 | 10.00~16.00 | 16 | 192 | 4.00 | 7.50 | 7.50 | 10.00 | 11.00 |
| PGV3-M25 | 16.00~25.00 | 25 | 300 | 5.50 | 11.00 | 11.00 | 15.00 | 18.50 |
| PGV3-M40 | 25.00~40.00 | 40 | 480 | 11.00 | 22.00 | 22.00 | 25.00 | 33.00 |
| PGV3-M63 | 40.00~63.00 | 63 | 756 | 15.00 | 33.00 | 33.00 | 40.00 | 55.00 |
| PGV3-M80 | 56.00~80.00 | 80 | 960 | 22.00 | 45.00 | 45.00 | 55.00 | 63.00 |
| Model | Rated ultimate short-circuitbreaking capacity Icu (kA) | Rated service short-circuitbreaking capacity Ics (kA) | Fuse | ||||||||||||
| 220V | 400V | 440V | 500V | 690V | 220V | 400V | 440V | 500V | 690V | 220V | 400V | 440V | 500V | 690V | |
| PGV3-M06 | 100 | 60 | 60 | 20 | 3 | 75 | 30 | 30 | 10 | 1.5 | * | * | * | * | 火 |
| PGV3-M07 | 100 | 60 | 60 | 20 | 3 | 75 | 30 | 30 | 10 | 1.5 | * | 大 | * | * | 10 |
| PGV3-M08 | 100 | 60 | 60 | 20 | 3 | 75 | 30 | 30 | 10 | 1.5 | * | * | * | * | 32 |
| PGV3-M10 | 100 | 60 | 60 | 20 | 3 | 75 | 30 | 30 | 10 | 1.5 | * | * | 63 | 63 | 40 |
| PGV3-M14 | 100 | 60 | 60 | 20 | 3 | 75 | 30 | 30 | 10 | 1.5 | * | * | 63 | 63 | 40 |
| PGV3-M20 | 100 | 35 | 25 | 10 | 4 | 75 | 17.5 | 12.5 | 5 | 2 | 火 | 80 | 63 | 63 | 63 |
| PGV3-M25 | 100 | 35 | 25 | 8 | 4 | 75 | 17.5 | 12.5 | 4 | 2 | 大 | 80 | 63 | 63 | 50 |
| PGV3-M40 | 100 | 35 | 25 | 8 | 4 | 75 | 17.5 | 12.5 | 4 | 2 | * | 315 | 315 | 200 | 200 |
| PGV3-M63 | 100 | 35 | 25 | 8 | 4 | 75 | 17.5 | 12.5 | 4 | 2 | * | 400 | 400 | 250 | 250 |
| PGV3-M80 | 100 | 35 | 25 | 8 | 4 | 75 | |||||||||
| 17.5 | 12.5 | ||||||||||||||
| 4 | 2 | * | 400 | 400 | 250 | 250 | |||||||||
Accessories
| Model | Rated insulationvoltage Ui (V) | Conventional thermalcurrent Ith (A) | Configuration |
| PGV2-AE11 | 250 | 2.50 | 1 NO + 1 NC |
| PGV2-AE20 | 250 | 2.50 | 2 NO |
| PGV2-AN11 | 690 | 6.0 | 1 NO + 1 NC |
| PGV2-AN20 | 690 | 6.0 | 2 NO |
| PGV3-A01 | 690 | 6.0 | 1 NO + 1 NC |
| PGV3-A02 | 690 | 6.0 | 2NO |
| Model | Rated insulationvoltage Ui (V) | Voltage range of operation | Specification |
| PGV2-AU115 | 690 | 0.35-0.7Ue | 110-115V/50Hz |
| PGV2-AU115 | 690 | 0.35-0.7Ue | 127V/60Hz |
| PGV2-AU225 | 690 | 0.35-0.7Ue | 220-240V/50Hz |
| PGV2-AU225 | 690 | 0.35-0.7Ue | 380-440V/50Hz |
| PGV2-AU385 | 690 | 0.35-0.7Ue | 440V/60Hz |
| Model | Rated insulationvoltage Ui (V) | Voltage range of operation | Specification |
| PGV2-AS115 | 690 | 0.70-1.1Ue | 110-115V/50Hz |
| PGV2-AS115 | 690 | 0.70-1.1Ue | 127V/60Hz |
| PGV2-AS225 | 690 | 0.70-1.1Ue | 220-240V/50Hz |
| PGV2-AS225 | 690 | 0.70-1.1Ue | 380-440V/50Hz |
| PGV2-AS385 | 690 | 0.70-1.1Ue | 440V/60Hz |
| Model | Rated insulation voltage Ui (V) | Conventional thermal current Ith (A) | Configuration | |
| Auxiliary contact | Fault signal contact | |||
| PGV2-AD0110 | 690 | 6.0 | 2.5 | $1 N C + 1 N O$ |
| PGV2-AD0101 | 690 | 6.0 | 2.5 | 1 NC + 1 NC |
| PGV2-AD1010 | 690 | 6.0 | 2.5 | 1 NO + 1 NO |
| PGV2-AD1001 | 690 | 6.0 | 2.5 | 1 NO +1 NC |
Dimensions
RDJ2
Series Thermal Over-load Relay
Usage and its scope of application
RDJ2 (LR2) series bimetal type thermal over-load relay is suitable for the circuit of AC50Hz/60Hz, rated operating voltage Ue:660V, rated current 0.10\~630 (A), as the use of over-load, break phase and protection of motor and circuit.
The structure and main technique performance index of this thermal relay is the same with LR2 series thermal relay, therefore, LR2 series thermal relay can be entirely replaced by RDJ2 series thermal relay.
Thermal relay with the functions and characteristics of break phase protection temperature compensation, setting current adjusting, optional selection of auto-reset and manual reset, action indication signal, insulation separation of NO, NC auxiliary contacts, small installation section, and various installation mode. Moreover, it has the testing and stop push-buttons,and it can be inspected the action flexibility, has the protective cover that prevent the hand get shocked, safe to use, with the locking device to prevent mis-operation etc.
This product conforms to : IEC60947-4-1 standards.
Model No.
Rated operating current (A)
Design serial No.
Thermal over-load relay
Enterprise code
Normal operating and installation conditions
3.1 Ambient temperature: -5℃\~+40℃, and the average value within 24h does not exceed +35℃
3.2 Altitude of the installation place does not exceed 2000m;
3.3 Atmosphere condition: The relative humidity does not exceed 50% when it is at +40℃, it allowed relatively high humidity at the relatively low temperature, for example, the relative humidity reaches 90% when +20℃, and it should take special measurements when there produced the condensation on the product due to the temperature variation.
3.4 It should be at the no explosion danger medium, and the medium without the gas that cannot corrode the metal and damage the insulation as well as the places that without conductive dust.
3.5 Grade of pollution: 3
3.6 Installation category: III
3.7 Installation position: installed at the normal position, the gradient between the installation side and the vertical side does not exceed ±5°, and without obvious vibration and impact.
3.8 Protection grade: IP 20.
Main technical parameter
Rated operating current, setting current adjusting scope, suited AC contactor model and recommended fuse model for thermal relay to see table 1
| No | Model | Rated current A | Setting currentadjusting scope A | Suited ACcontactor model | Suited fuse model | Cross section ofconductor mm² |
| 1 | 0.1-0.16 | |||||
| 2 | 0.16-0.25 | |||||
| 3 | 0.25-0.4 | RDT16-00-2 | ||||
| 4 | 0.4-0.63 | |||||
| 5 | 0.63-1 | |||||
| 6 | RDJ2-25 | 25 | 1-1.6 | CJX2-09-32 | RDT16-00-4 | 1 |
| 7 | 1.25-2 | |||||
| 8 | 1.6-2.5 | RDT16-00-6 | ||||
| 9 | 2.5-4 | RDT16-00-10 | ||||
| 10 | 4--6 | RDT16-00-16 | ||||
| 11 | 5.5-8 | |||||
| 12 | 7--10 | RDT16-00-20 | 1.5 | |||
| 13 | 9--13 | RDT16-00-25 | 2.5 | |||
| 14 | RDJ2-25 | 25 | 12--18 | RTD16-00-40 | ||
| 15 | 17-25 | CJX2-25,CJX2-32 | RDT16-00-50 | 4 | ||
| 16 | RDJ2-36 | 36 | 23-32 | RDT16-00-63 | 6 | |
| 17 | 28-36 | CJX2-32 | RDT16-00-80 | 10 | ||
| 18 | 23-32 | CJX2-40-95 | RDT16-00-63 | 6 | ||
| 19 | 30-40 | RDT16-00-80 | ||||
| 20 | 37-50 | RDT16-00-100 | ||||
| 21 | RDJ2-93 | 93 | 48-65 | RDT16-00-125 | 16 | |
| 22 | 55-70 | CJX2-63-95 | RDT16-00-160 | 25 | ||
| 23 | 63-80 | CJX2-80,CJX2-95 | ||||
| 24 | 80-93 | CJX2-95 | RDT16-1-200 | 35 | ||
| 25 | 80-125 | RDT16-1-250 | 50 | |||
| 26 | RDJ2-200 | 200 | 100-160 | CJX2-115,150, | RDT16-1-315 | 70 |
| 27 | 125-200 | 185,225 | RDT16-2-400 | 95 | ||
| 28 | 160-250 | RDT16-3-500 | 120 | |||
| 29 | 200-320 | CJX2-185,225, | RDT16-3-630 | 185 | ||
| 30 | RDJ2-630 | 630 | 250-400 | 265,330,400 | RDT16-4-800 | 240 |
| 31 | 315-500 | RDT16-4-1000 | 2X150 | |||
| 32 | 400-630 | CJX2-500,630 | RDT16-4-1000 | 2X185 |
Rated insulation voltage of auxiliary circuit Ui 380V; Rated frequency 50, 60Hz; Usage category, rated operating voltage, rated operating current and rated thermal current to see table 2
table 2
| Usage category | AC-15 | DC-13 | |
| Rated operating voltage V | 220 | 380 | 220 |
| Rated operating current A | 1.64 | 0.95 | 0.15 |
| Setting thermal current A |
Multiple of setting current Map 1 Action scope curve
table 3
| No. | Multiple of setting current | Action time | Initial status | Ambient temperature℃ | ||
| 1 | 1.05 | >2h | Cool status | 20±5℃ | ||
| 2 | 1.20 | < 2h | Thermal status(after serial No.1) | |||
| 3 | 1.50 | Grade of | 10A | <2min | ||
| 10 | <4min | |||||
| 4 | 7.20 | releasing | 10A | 2s < top≤10s | Cool status | |
| 10 | 4s <top≤10s | |||||
table 4
| No. | Multiple of setting current | Action time | Initial status | Ambient temperature℃ | |
| Any two phases | Another phase | ||||
| 1 | 1.00 | 0.90 | >2h | Cool status | 20±5℃ |
| 2 | 1.15 | 0 | ≤2h | Thermal status(after serial No.1) | |
Time-current characteristics curve of thermal relay to see map 1
A. Three phase balance, unbalance, starting by cool status;
B. Three phase balance, break phase, starting by thermal status
External and installation dimension
External and installation dimension of thermal relay to see map 2\~9
JRS2
Series Thermal Over-load Relay
Usage and its scope of application
JRS2 Series Thermal Relay is suitable for the power system of AC50Hz/60Hz, rated voltage Ue: 690V, current 0.1\~630 (A) as the use of over-load and break-phase protection of AC motor or circuit. Thermal relay has the functions of break phase protection, temperature compensation, optional selection of manual reset and auto-reset, inspection of action flexibility, and manually break the NC contacts and NO contacts.
This product conforms to: IEC60947-4-1 etc. standards.
Model No.
Normal operating condition and installation condition
3.1 Ambient temperature: -5℃\~+40℃, average value within 24h does not exceed +35℃;
3.2 Height of altitude: does not exceed 2000m,
3.3 Atmosphere: when highest temperature is +40℃, the relative humidity does not exceed 50%; it allowed the relatively high humidity when it is under the relatively low temperature, for example, it reaches 90% when +20C; It should take special measurements if there produced condensation that is due to the temperature variation.
3.4 Grade of pollution: 3
3.5 Installation category: III
3.6 Position of installation: the gradient between the installation side of relay and the vertical side is not more than ±5°
3.7 Impact and vibration: product should be installed and used at the places of no obvious shake, impact and vibration.
3.8 Installation mode:
JRS2-12.5, 25, 32, 45, 80 has three kinds of installation mode: combination installation, screw installation, 35mm standard rail installation.
JRS2-63, 135, 150, 180, 400, 630 has two kinds of installation mode: screw installation, 35mm standard rail installation.
3.9 Protection grade: IP00
| Model | Setting current adjustable scope A | Recommended SCPD model,specification | Conductor's cross section formain circuit mm |
| JRS2-63、80 | 40-57 | RDT16-00-125 | 16 |
| 50-63 | |||
| JRS2-135、150、180 | 55-80 | RDT16-1-160 | 25 |
| JRS2-80 | 57-70 | ||
| 63-80 | |||
| JRS2-80 | 77-88 | RDT16-1-160 | 35 |
| JRS2-135、150、180 | 63-90 | RDT16-1-200 | |
| 80-110 | |||
| JRS2-400 | 80-125 | RDT16-1-250 | 50 |
| JRS2-135、150、180 | 90-120 | ||
| 110-135 | RDT16-2-315 | ||
| JRS2-150、180 | 120-150 | ||
| JRS2-400 | 125-200 | RDT16-2-400 | 95 |
| JRS2-180 | 135-160 | RDT16-2-315 | 70 |
| 150-180 | RDT16-2-400 | 95 | |
| 160-250 | RDT16-3-500 | 120 | |
| JRS2-400 | 200-320 | RDT16-3-630 | 185 |
| 250-400 | RDT16-4-800 | 240 | |
| JRS2-630 | 320-500 | RDT16-4-1000 | 2×150 |
| 400-630 | 2×185 |
table 3
| Model | Multiple ofsetting current | Action time | Predict results | Initial status | Ambienttemperature℃ | ||
| 1 | 1.05 | >2h | No action | Cool status | 20±5℃ | ||
| 2 | 1.20 | <2h | Action | Thermal status(after serial No.1) | |||
| 3 | 1.50 | Grade of | 10A | <2min | Action | ||
| 10 | <4min | Action | |||||
| 4 | 7.50 | releasing | 10A | 2s < top≤10s | Action | Cool status | |
| 10 | 4s < top≤10s | Action | |||||
Action scope of thermal relay when two poles electrified to see table 4
| No. | Multiple of setting current | Action time | Initial status | Ambient temperature℃ | |
| Any two phases | Another phase | ||||
| 1 | 1.00 | 0.90 | >2h | Cool status | |
| 2 | 1.15 | 0 | ≤2h | Thermal status(after serial No.1) | 20±5℃ |
table 5
| Rated insulation voltage Ui (V) | 380 | ||
| Setting thermal current Ith (A) | 6 | ||
| Usage category | AC-15 | AC-13 | |
| Rated operating voltage Ue (V) | 220 | 380 | 220 |
| Rated operating current le (A) | 1.9 | 1.1 | 0.2 |
| Suited fuse (RDT16 type) specification A | 6 | ||