51
51
52 Convenient Installation and Maintenance
110m
100m
40m
The biggest
drop when
ODU on the top The biggest
drop when ODU
at the bottom
Maximum
drop of IDU
120m
Furthest IDU
Nearest IDU IDU
5.1 1100m Super Long Piping Design
The industry-leading piping length, with a total length of 1100m, makes floor design more flexible.
The max distance between the IDU and the ODU (the higher ODU) is 100m. The max distance between the IDU and
the ODU (the lower ODU) is 110m.
The maximum distance between indoor units is 40m.
The maximum actual single pipe length is 220m.
The maximum equivalent single tube length is 240m.
The equivalent length from first indoor distributor to last indoor unit 120m.
53
5.2 130Pa external static pressure
Engineered with advanced fan blades and a high-performance inverter motor, the system delivers a
superior external static pressure of 130Pa*. This ensures reliable and efficient heat dissipation.
* Note: 130Pa static pressure needs to be customized
Better heat dissipation, better refrigeration effect
MAX 130Pa
VRF static pressure contrast diagram
TMV6+
Ordinary
VRF
TmvS
Non-polar CAN bus communication technology
TMV6+ adopts CAN bus communication technology, which is a communication technology applied in the field of
automobile and military industry.
5.3
TMV6 VRF(CAN communication) Other similar products in the industry(RS 485
communication)
Reliability High reliability and stable network The reliability is unstable and easy to be paralyzed
Communication
efficiency Up to 100kbs About 10kbs
Communication distance About 2000m About 1000m
Communication line
polarity No polarity, easy to debug Polarities need to be distinguished for installation
Scalability Easy to plug and play To add new device, the software must be changed,
and the scalability is poor
Wire control
Remote control
Packet controller
Centralized controller
Network centralized
control system
Separate billing s
ystem
Intelligent building
control system
BMS
Intelligence
development
54 Convenient Installation and Maintenance
One-touch commissioning function
You can choose to debug on the outdoor unit side or remotely through the monitoring software to realize the cooling
and heating trial operation, no need opening the indoor units one by one, which is convenient for on-site debugging
and improves the quality of construction at the project site.
5.4
5.6 360°pipe connection design
These units allow the freedom to connect the piping in multiple
directions, such as front side, left side , right side and back side ,
making installation easier.
One button commissioning via commissioning software.
One button commissioning from outdoor unit.
Software PCB of ODU
5.5 Non-polarity communication connection
CAN bus communication mode is applied between indoor and outdoor unit, no need to distinguish between
positive and negative poles, and the installation is simpler and more efficient.
communication wire
ODU IDU ODU IDU
A B A B A B A B
55
5.9 Auto-addressing function
Commissioning software supports local analysis for
convenient debugging and easy troubleshooting.
The system can realize the automatic allocation of indoor unit address. There is no need to dial code during
commissioning, which avoids the trouble of manual setting one by one. It is more intelligent and convenient.
5.8 Commissioning software
5.7
If an indoor unit requires power outage for maintenance due to a malfunction, it can be independently powered off
for repair without affecting the operation of the entire system. Other indoor units within the system can continue to
operate normally.
Emergency power-off function for IDU maintenance
Under repair Other indoor units
operate asusual.
56 ODU lineup 925mm 845mm1780mm
8 to 16HP
1340mm 845mm1780mm
18 to 24HP
1760mm 845mm1780mm
1900mm 845mm1780mm
26 to 32HP 34 to 36HP
The outdoor unit module has only 3 basic structures with the same height, which simplifies the design process and
improves the flexibility of the system.
Product Specifications
57
ODU Specifications (8-36HP)
Capacity Range 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP
Model:
TMV-VED+(**)W/AS-D(EC) 252 280 335 400 450 504 560 615 680 730 785 850 900 950 1010
Power Supply V~,Hz,Ph 380-415V, 50/60Hz, 3N
Cooling
Capacity kW 25.2 28.00 33.50 40.00 45.00 50.40 56.00 61.50 68.50 73.00 78.50 85.00 90.00 95.20 101.00
Input kW 5.27 6.44 8.09 9.76 11.25 13.06 15.14 17.67 20.03 20.28 21.93 24.15 26.71 28.94 32.48
Current A 8.41 10.27 12.91 15.56 17.94 20.82 24.14 28.19 31.94 32.34 34.97 38.51 42.59 46.15 51.80
EER W/W 4.78 4.35 4.14 4.10 4.00 3.86 3.70 3.48 3.42 3.60 3.58 3.52 3.37 3.29 3.11
Heating
Capacity kW 27.0 31.50 37.50 45.00 50.00 56.50 63.00 69.00 75.00 81.50 87.50 95.00 100.00 106.00 112.00
Input kW 4.89 5.83 7.08 9.09 10.75 13.29 15.33 16.91 19.23 19.88 21.60 24.68 26.88 28.96 32.84
Current A 7.80 9.30 11.28 14.50 17.15 21.20 24.45 26.97 30.67 31.70 34.46 39.35 42.87 46.19 52.38
COP W/W 5.52 5.40 5.30 4.95 4.65 4.25 4.11 4.08 3.90 4.10 4.05 3.85 3.72 3.66 3.41
Max. Input
Consumption kW 11.30 12.43 13.73 16.50 18.70 21.39 23.70 26.07 29.68 31.49 33.27 33.47 34.59 39.44 41.25
Max. Current A 20.03 22.03 24.33 28.80 32.80 37.90 42.00 46.20 52.60 55.80 58.95 59.31 61.29 69.90 73.10
Outdoor Fan Motor
(Output Power x Fan
quantity)
W 560 920 560 920
Air Flow Volume m3
/h 11000 11000 11500 13500 14000 15500 19000 19000 20000 26000 26000 27000 27000 29000 29000
Noise Level dB(A) 56 57 58 59 60 61 61 62 63 63 64 65 65 66 66
Dimension
(W×D×H)
Net mm 925×845×1780 1340×845×1780 1760×845×1780 1900×845×1780
Packing mm 1000×925×1940 1415×925×1940 1835×925×1940 1975×925×1940
Weight
Net kg 215 215 215 230 230 270 315 315 320 380 380 420 420 455 455
Gross kg 225 225 225 240 240 290 335 335 340 405 405 445 445 480 480
Refrigerant
type/
Quantity
Type / R410A
Charged
Volume kg 9 9.00 9.00 9.00 9.00 12.00 14.00 14.00 16.00 18.00 18.00 25.00 25.00 28.00 28.00
Design Pressure MPa 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5 4.3/1.5
Refrigerant
Piping
Liquid
Side mm φ9.52 φ9.52 φ12.7 φ12.7 φ12.7 φ15.9 φ15.9 φ15.9 φ15.9 φ19.1 φ19.1 φ19.1 φ19.1 φ19.1 φ19.1
Gas Side mm φ19.1 φ22.2 φ25.4 φ25.4 φ28.6 φ28.6 φ28.6 φ28.6 φ28.6 φ31.8 φ31.8 φ34.9 φ34.9 φ38.1 φ38.1
Max.
Length m 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100
Max.
Height m 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100 110\\100
Ambient Temp
(Cooling/Heating) °C Cooling: -15~56
Heating: -30~28
Notes:
1. Cooling conditions: Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
58 Space Saving Combination
Product parameters
2 ODUs HP 38 40 42 44 46 48 50 52 54
Recommended
combination 16+22 18+22 20+22 22+22 22+24 24+24 22+28 24+28 26+28
Model:
TMV-VED+**W/AS-D(EC) 1065 1119 1175 1230 1295 1360 1400 1465 1515
Naminal cooling*1 kW 45+61.5 50.4+61.5 56+61.5 61.5+61.5 61.5+68 68+68 61.5+78.5 68+78.5 73+78.5
Naminal heating*2 kW 50+69 56.5+69 63+69 69+69 69+75 75+75 69+87.5 75+87.5 81.5+87.5
Rated cooling
power input kW 26.39 30.73 32.81 35.34 37.70 40.06 39.60 41.96 42.21
Rated heating
power input kW 26.08 30.20 32.24 33.82 36.14 38.46 38.51 40.83 41.48
Power supply / 380V~3N 50Hz/60Hz
Compressor type - DC Inverter Scroll
Dimension
(W×D×H) mm 925×845×1780+1900×845×1780 1340×845×1780+11340×845×1780
Motor
Type DC Inverter
Air volume m³/h 33000 34500 38000 38000 39000 40000 45000 46000 52000
Drive type Direct
Net weight kg 230+315 270+315 315+315 315+315 315+320 320+320 315+380 320+380 380+380
HP 56 58 60 62 64 66 68 70
Recommended combination 28+28 26+32 28+32 30+32 32+32 30+36 32+36 34+36
Model:TMV-VED+**W/AS-D(EC) 1570 1630 1685 1750 1800 1860.00 1910.00 1960.00
Naminal cooling*1 (kW) 78.5+78.5 73+90 78.5+90 85+90 90+90 85+101 90+101 95+101
Naminal heating*2 (kW) 87.5+87.5 81.5+100 63+100 95+100 100+100 95+112 100+101 106+112
Rated cooling
power input (kW) 43.86 46.99 48.48 50.86 53.42 56.63 59.19 61.42
Rated heating
power input (kW) 43.20 46.76 46.71 51.56 53.76 57.52 59.72 61.80
Power supply / 380V ~ 3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Net dimension (W×D×H) (mm) 1760×845×1780+1760×845×1780 1760×845×1780+1900×845×1780
Motor
Type / DC Inverter
Air volume m³/h 52000.00 53000.00 53000.00 54000.00 54000.00 56000.00 56000.00 58000.00
Drive type / Direct
Net weight kg 380+420 380+315 380+420 380+420 420+420 380+455 420+455 455+455
Notes:
1. Cooling conditions: Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
59
Space Saving Combination
3 ODUs
HP 88 90 92 94 96
Recommended combination 28+28+32 26+32+32 28+32+32 30+32+32 32+32+32
Model:TMV-VED+**W/AS-D(EC) 2470 2530 2585 2650 2700
Naminal cooling*1 kW 78.5+78.5+90 73+90+90 78.5+90+90 85+90+90 90+90+90
Naminal heating*2 kW 87.5+87.5+100 81.5+100+100 87.5+100+100 95+100+100 100+100+100
Rated cooling power input kW 70.57 73.70 75.35 77.57 80.13
Rated heating power input kW 70.08 73.64 75.36 78.44 80.64
Power supply / 380V~3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Net dimension (W×D×H) mm 1760×845×1780+1760×845×1780+1760×845×1780
Motor
Type / DC Inverter
Air volume m³/h 79000 80000 80000 81000 81000
Drive type / Direct
Net weight kg 380+380+420 380+420+420 380+420+420 420+420+420 420+420+420
HP 72 74 76 78 80 82 84 86
Recommended
combination 24+24+24 22+24+28 24+24+28 22+28+28 24+28+28 26+28+28 28+28+28 26+28+32
Model:
TMV-VED+**W/AS-D(EC) 2040 2080 2145 2185 2250 2300 2355 2415
Naminal cooling*1 kW 68+68+68 61.5+68+78.5 68+68+78.5 61.5+78.5+78.5 68+78.5+78.5 73+78.5+78.5 78.5+78.5+78.5 73+78.5+90
Naminal heating*2 kW 75+75+75 69+75+87.5 75+75+87.5 69+87.5+87.5 75+87.5+87.5 81.5+87.5+87.5 87.5+87.5+87.5 81.5+87.5+100
Rated cooling
power input kW 60.09 59.63 61.99 61.53 63.89 64.14 65.79 68.92
Rated heating
power input kW 57.69 56.02 60.06 60.11 62.43 63.08 64.80 68.36
Power supply / 380V~3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Dimension
(W×D×H) mm
1340×845×1780+
1340×845×1780+
1340×845×1780
1340×845×1780+
1340×845×1780+
1760×845×1780
1340×845×1780+
1760×845×1780+
1760×845×1780
1760×845×1780+1760×845×1780+1760×845×1780
Motor
Type / DC Inverter
Air
volume m³/h 57000 65000 66000 71000 72000 72000 78000 79000
Drive
type / Direct
Net weight kg 315+315+315 315+320+380 320+320+380 315+380+380 320+380+380 380+380+380 380+380+380 380+380+420
Notes:
1. Cooling conditions: Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
60 Space Saving Combination 4 ODUs HP 98 100 102 104 106 108 110
Recommended
combination 24+24+24+26 24+24+26+26 24+26+26+26 24+26+26+28 26+26+26+28 26+26+28+28 26+28+28+28
Model:
TMV-VED+**W/AS-D(EC) 2770 2820 2870 2925 2975 3030 3085
Naminal cooling*1 kW 68+68+68+73 68+68+73+73 68+73+73+73 68+73+73+78.5 73+73+73+78.5 73+73+78.5+78.5 73+78.5+78.5+78.5
Naminal heating*2 kW 75+75+75+81.5 75+75+81.5+81.5 75+81.5+81.5+81.5 75+81.5+81.5+87.5 81.5+81.5+81.5+87.5 81.5+81.5+87.5+87.5 81.5+87.5+87.5+87.5
Rated cooling
power input kW 80.37 80.06 80.87 82.12 82.77 84.02 85.87
Rated heating
power input kW 77.57 78.22 78.87 80.59 81.24 82.96 84.48
Power supply / 380V ~ 3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Dimension
(W×D×H) mm
1340×845×1780+
1340×845×1780+
1340×845×1780+
1760×845×1780
1340×845×1780+
1340×845×1780+
1760×845×1780+
1760×845×1780
1340×845×1780+
1780×845×1780+
1760×845×1780+
1760×845×1780
1340×845×1780+
1760×845×1780+
1760×845×1780+
1760×845×1780
1760×845×1780+
1760×845×1780+
1760×845×1780+
1760×845×1780
Motor
Type / DC Inverter
Air volume m³/h 33000 34500 38000 38000 39000 40000 45000
Drive type / Direct
Net weight kg 230+315 270+315 315+315 315+315 315+320 320+320 315+380
HP 112 114 116 118 120 122
Recommended
combination 28+28+28+28 26+28+28+32 28+28+28+32 26+28+32+32 28+28+32+32 26+32+32+32
Model:
TMV-VED+**W/AS-D(EC) 3140 3200 3255 3310 33700 3430
Naminal cooling*1 kW 78.5+78.5++78.5+78.5 73+78.5+78.5+90 78.5+78.5+78.5+90 73+78.5+90+90 78.5+78.5+90+90 73+90+90+90
Naminal heating*2 kW 87.5+87.5++87.5+87.5 81.5+87.5+87.5+100 87.5+87.5+87.5+100 81.5+87.5+100+100 87.5+87.5+100+100 81.5+100+100+100
Rated cooling
power input kW 87.72 90.85 92.50 95.63 97.28 100.38
Rated heating
power input kW 86.40 89.96 91.68 96.96 78.44 100.52
Power supply / 380V~3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Dimension(W×D×H) mm 1760×845×1780+1760×845×1780+1760×845×1780+1760×845×1780
Motor
Type / DC Inverter
Air volume m³/h 104000 105000 105000 106000 106000 107000
Drive type / Direct
Net weight kg 380+380+380+380 380+380+380+420 380+380+380+420 380+380+420+420 380+380+420+420 380+420+420+420
Product parameters
Notes:
1. Cooling conditions: Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
61
Space Saving Combination
4 ODUs
HP 124 126 128 130 132 134
Recommended
combination 28+32+32+32 30+32+32+32 32+32+32+32 34+32+32+32 34+34+32+32 34+34+34+32
Model:
TMV-VED+**W/AS-D(EC) 3485 3550 3600 3652 3704 3756
Naminal cooling*1 kW 78.5+90+90+90 85+90+90+90 90+90+90+90 95.2+90+90+90 95.2+95.2+90+90 95.2+95.2+95.2+90
Naminal heating*2 kW 87.5+100+100+100 95+100+100+100 100+100+100+100 106+100+100+100 106+106+100+100 106+106+106+100
Rated cooling
power input kW 101.40 104.28 106.84 109.07 111.28 113.53
Rated heating
power input kW 102.24 105.32 107.52 109.58 111.68 113.76
Power supply / 380V ~ 3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Dimension
(W×D×H) mm
1760×845×1780+
1760×845×1780+
1760×845×1780+
1760×845×1780
1900×845×1780+
1760×845×1780+
1760×845×1780+
1760×845×1780
1900×845×1780+
1900×845×1780+
1760×845×1780+
1760×845×1780
1900×845×1780+
1900×845×1780+
1900×845×1780+
1760×845×1780
Motor
Type / DC Inverter
Air volume m³/h 107000 108000 108000 110000 112000 114000
Drive type / Direct
Net weight kg 380+420+420+420 420+420+420+420 420+420+420+420 455+420+420+420 455+455+420+420 455+455+455+420
HP 136 138 140 142 144
Recommended
combination 34+34+34+34 36+34+34+34 36+36+34+34 36+36+36+34 36+36+36+36
Model:
TMV-VED+**W/AS-D(EC) 3808 3866 3924 3982 404
Naminal cooling*1 kW 95.2+95.2+95.2+95.2 101+95.2+95.2+95.2 101+101+95.2+95.2 101+101+101+95.2 101+101+101+101
Naminal heating*2 kW 106+106+106+106 112+106+106+106 112+112+106+106 112+112+112+106 112+112+112+112
Rated cooling
power input kW 115.76 119.30 122.84 126.38 129.92
Rated heating
power input kW 115.84 119.72 123.60 127.48 131.36
Power supply / 380V~3N 50Hz/60Hz
Compressor type / DC Inverter Scroll
Dimension(W×D×H) mm 1900×845×1780+1900×845×1780+1900×845×1780+1900×845×1780
Motor
Type / DC Inverter
Air volume m³/h 116000 116000 116000 116000 116000
Drive type / Direct
Net weight kg 455+455+455+455 455+455+455+455 455+455+455+455 455+455+455+455 455+455+455+455
Notes:
1. Cooling conditions: Indoor air temperature 27°C DB, 19°C WB; outdoor air temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
62 Mini VRF
Full DC Inverter MINI VRF Unit
Powerful High Effi ciency Comfortable Stable
63
64 High efficiency full DC inverter and twin rotary compressor
High efficiency DC fan motor Electrical control box refrigerant cooling technology
Strong Power, Stable Operation
Energy Saving And Environmental Friendly
TCL Mini VRF use full DC inverter twin rotary compressor, which has high- efficiency
both for full load condition and partial load condition, also leads to low noise, stable
and reliable operation.
The stepless regulation of the fan motor
can meet the actual requirement of the
capacity output, efficiency of motor is
increased up to be 45%, higher efficiency
in low speed operation.
The refrigerant cooling technology can cool the PCBs in high ambient
temperature condition, which improves the reliability, effciency and
lifespan of the MINI VRF units.
80° C
60° C
Temperature
drop
Wide operation temperation range
The Mini VRF can operate under -20℃ to ensure the heating demand, operate up to 54℃ to make sure the cooling capcity
output with high effi ciency and stability.
MINI VRF
R410A High-efficiency and environmentally friendly refrigerant
RoHS Certification
R410A is an HFC refrigerant which does not damage the ozone layer. It is an energy
effi cient and environmentally friendly refrigerant.
The TCL mini VRF unit meets the RoHS enviromental
certifi cation, which is environmental friendly.
R410A is non-toxic and is a �non-fl ammable refrigerant�. The composition structure of
R410A is not easy to change and very stable.
7.1
7.2
65
Beautiful Appearance, Upgraded Structure Design
The top panel
Right front side plate
Grille
Right back plate
Footing
Seal plate
The front panel Lifting handle
No screw design to get high-quality structure
and improve the strength, more beautiful
Mold forming and integrated design
to make sure the strength of the panel
Grille adopts DOE simulation design, air
volume increased more than 7%
The mold is integrally formed and
the new designed diff user improves
the heat exchange effi ciency.
High strength foundation with rust - proof,
corrosion - proof, more stable and reliable. Ensure simple pipe connection.
Double 528mm wind wheel, larger air volume
and lower noise.
Upgraded handle design, easy to carry
Simple and elegant appearance
The front, side and back of the unit are
designed with knock-out holes, coper
pipes can be connected from various
directions, which is more convenient to
do the installation.
Sealing plate is combined with knock-out plate
Three side pipe connection design
Diff erent installation options
Three side direction pipe connection
7.3
66 Mini VRF Specifications
MINI VRF Specifications
8-12kW 14 -16kW
7.4
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB.
4. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
5. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
6. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
7. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
8. Due to ongoing product development, specifications are subject to change without notice.
Notes:
Items Unit
80 100 120 140 160
Model: TMV-Vd(**)W/N1-D(E)
Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1N
Cooling
Capacity W 8,000 10,000 12,000 14,500 16,000
Input W 2,550 2,750 3,050 4,100 4,800
Current A 11.6 12.5 13.9 18.6 21.8
EER W/W 3.14 3.64 3.93 3.54 3.33
Heating
Capacity W 10,000 12,000 14,000 16,000 18,000
Input W 2,850 3,050 3,350 3,800 4,700
Current A 13 13.9 15.3 17.3 21.4
COP W/W 3.51 3.93 4.18 4.21 3.83
Max. Input Consumption W 6,200 6,200 6,200 7,260 7,260
Max. Current A 28.2 28.2 28.2 33.0 33.0
Circuit Breaker A 40 40 40 40 40
Air Flow Volume m3
/h 4300 4300 4300 5300 5300
Noise Level dB(A) 54 55 56 56 56
Dimension
(W×D×H)
Net mm 910×359×803 1010×410×850
Packing mm 1022×480×835 1145×535×970
Weight
Net kg 52 52 52 75 75
Gross kg 55 55 55 87 87
Cooling
Operating
range
Outdoor side °C -20~55
Indoor side °C 16~32
Heating
Operating
Range
Outdoor side °C -20~24
Indoor side °C 15~31
67
18 KW 22.4-28 KW
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Heating: Indoor temperature 20°C DB/15°C WB,and outdoor temperature 7°C DB/6°C WB.
4. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
5. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
6. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
7. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
8. Due to ongoing product development, specifications are subject to change without notice.
Notes:
Items Unit
180 224 252 280
Model: TMV-Vd(**)W/N1-C(E)
Power Supply V~,Hz,Ph 220-240V,50/60Hz, 1N 380-415V, 50/60Hz, 3N
Cooling
Capacity W 18,000 22,400 25,200 28,000
Input W 5,250 7,200 8,250 9,100
Current A 23.9 11.5 13.2 14.5
EER W/W 3.43 3.11 3.05 3.08
Heating
Capacity W 20,000 24,500 27,000 30,800
Input W 5,200 7,100 8,000 8,500
Current A 23.6 11.3 12.8 13.6
COP W/W 3.85 3.45 3.38 3.62
Max. Input Consumption W 7,200 11,000 11,500 12,000
Max. Current A 33 17.6 18.5 19.2
Circuit Breaker A 40 25 25 25
Air Flow Volume m3
/h 7000 10500 10500 10500
Noise Level dB(A) 55 58 59 61
Dimension
(W×D×H)
Net mm 950×340×1330 1120×400×1560
Packing mm 1080×430×1480 1250×560×1721
Weight
Net kg 99 130 130 140
Gross kg 110 145 145 163
Cooling
Operating
range
Outdoor side °C -20~55
Indoor side °C 16~32
Heating
Operating
Range
Outdoor side °C -20~24
Indoor side °C 15~31
68 VRF systems, various combinations
In response to the different needs of building types for air-conditioning equipment, TCL provides four basic
outdoor unit modules, which can be freely combined in 2HP increments, and the maximum combination can reach
144HP, which can meet the high level design capacity differentiation, installation and transportation requirements
of large and medium-sized air-conditioning projects .
Recommended combination table
MINI VRF Specifications
Outdoor unit capacity
(HP) Combination (HP) Number of connected
indoor units
Outdoor unit capacity
(HP) Combination (HP) Number of connected
indoor units
8 8 13 78 22+28+28 80
10 10 16 80 24+28+28 80
12 12 19 82 26+28+28 80
14 14 23 84 28+28+28 80
16 16 26 86 26+28+32 80
18 18 29 88 28+28+32 80
20 20 33 90 26+32+32 80
22 22 36 92 28+32+32 80
24 24 39 94 30+32+32 80
26 26 43 96 32+32+32 80
28 28 46 98 30+32+36 80
30 30 50 100 32+32+36 80
32 32 53 102 30+36+36 80
34 34 56 104 32+36+36 80
36 36 59 106 34+36+36 80
38 16+22 63 108 36+36+36 80
40 18+22 66 110 26+28+28+28 80
42 20+22 69 112 28+28+28+28 80
44 22+22 72 114 26+28+28+32 80
46 22+24 75 116 28+28+28+32 80
48 24+24 78 118 26+28+32+32 80
50 22+28 80 120 28+28+32+32 80
52 24+28 80 122 26+32+32+32 80
54 26+28 80 124 28+32+32+32 80
56 28+28 80 126 30+32+32+32 80
58 26+32 80 128 32+32+32+32 80
60 28+32 80 130 30+32+32+36 80
62 30+32 80 132 32+32+32+36 80
64 32+32 80 134 30+32+36+36 80
66 30+36 80 136 32+32+36+36 80
68 32+36 80 138 30+36+36+36 80
70 34+36 80 140 32+36+36+36 80
72 36+36 80 142 34+36+36+36 80
74 22+24+28 80 144 36+36+36+36 80
74 24+24+28 80
69
IDU lineup
Series Fan motor Model
Capacity range(x100w)
18 22 25 28 32 36 40 45 50 56 63 71 80 90 100 112 125 140 160 180 220 280 450 560
360° Q8
cassette
DC TMV-V(**)Q8/
N1DY(E) ● ● ● ● ● ● ● ● ● ● ● ● ● ●
compact
cassette
DC TMV-V(**) Q4R/
N1D1Y (E) ● ● ● ● ● ● ● ● ● ●
Low ESP
Slim duct
DC TMV-V(**)F5/
N1DY(E) ● ● ● ● ● ● ● ● ● ● ● ● ●
Free static
pressure duct
DC TMV-V(**) F2/
N1DY(E) ● ● ● ● ● ● ● ● ● ● ● ● ●
Wall-mounted
(External EXV)
DC TMV-V(**)G/
N1DY-B(E) ● ● ● ● ● ● ● ● ● ●
Wall-mounted
(Built-in EXV)
AC TMV-V(**)G/
N1Y-B(E) ● ● ● ● ● ● ● ●
High static
pressure duct
AC TMV-V(**)F1/
N1Y(E) ● ● ● ●
Fresh air
duct
AC TMV-V(**) F1/
XFN1Y(E) ● ● ● ●
Celilling
& Floor
AC TMV-V(**) ZD/
N1Y(E) ● ● ● ● ● ● ● ● ● ● ●
One-way
cassette
DC TMV-V(**) Q1/
N1DY(E) ● ● ● ● ● ● ●
Two-way
cassette
AC TMV-V(**)Q2/
N1Y(E) ● ● ● ● ● ● ● ●
70 360° Q8 cassette
Technical characteristics
Recommended places
Office, restaurant, supermarket, shopping mall, lobby, etc
360° Airflow
Experience a gentle breeze in every corner. Our system ensures
uniform air distribution to eliminate hot and cold spots, maintaining a
consistently comfortable temperature throughout your space.
Large Air Outlet Volume
Through the new DC inverter fan motor,
achieve 2100m³/h air outlet volume, and
improve the air Exchange efficiency by 30%
Soft Wind Panel
The optional Soft Wind Panel creates a 360° airflow for superior
comfort. Air is dispersed through 2,565 micro-holes, which break up the
direct airflow into a gentle, body-friendly breeze.
*This is optional
Built-in DC Drain Pump
The drain pump delivers a maximum lift height
of 1200 mm, simplifying installation and
enabling efficient condensate drainage from
the indoor unit.
Standard Float Switch, Timely Warning
Standard float switch, when the condensate
pump is faulty or the drainpipe is blocked,
timely warning, prevent the water tray inside
the machine overflow.
Ultra Low Noise
Using the advanced technology of threedimensional spiral blade design, can reduce the
air resistance, realize the machine low noise
operation, \"quiet\" enjoy a comfortable life.
27dB(A)
Clean Sterilization, Healthy Life
Standard health filter screen, effectively
remove large particles in the air, optional
silver ion purification module, adsorption of
formaldehyde and odor, eliminate germs.
DC Inverter Fan Motor Technology
Adoption DC inverter motor technology, to
improve the running efficiency by 15% and
reduce the operation noise (min 27dB)
IDU Lineup & Specifications
71
360° Q8 cassette
Specification
Items Unit 28 36 45 50 56 63 71 Indoor Model: TMV-V(**)Q8/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 10000 12000 15000 17000 19000 21000 24000
KW 2.8 3.6 4.5 5 5.6 6.3 7.1
Heating
Btu/h 11000 14000 17000 19000 21000 24000 27000
KW 3.2 4 5 5.6 6.3 7.1 8
Electric
Data
(T1)
Rated Cooling Power Input KW 0.02 0.025 0.035
Rated Heating Power Input KW 0.02 0.025 0.035
Rated Cooling Current A 0.09 0.11 0.16
Rated Heating Current A 0.09 0.11 0.16
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 800/750/700 900/800/700 1100/900/750
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 31/29/27 33/31/29 35/33/31
Net Dimension
(WxDxH) mm 840x840x245
Packing Dimension
(WxDxH) mm 920x920x270
Net Weight Kg 21.5 22
Gross Weight Kg 25 25.5
Panel
Net Dimension
(WxDxH) mm 950x950x50
Packing Dimension
(WxDxH) mm 1055x1055x90
Net weight Kg 6
Gross weight Kg 9
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Items Unit 80 90 100 112 125 140 160 Indoor Model: TMV-V(**)Q8/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 27000 30000 34000 38000 42000 48000 55000
KW 8 9 10 11.2 12.5 14 16
Heating
Btu/h 30000 34000 38000 42000 48000 55000 62000
KW 9 10 11.2 12.5 14 16 18
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.06 0.07 0.085 0.132
Rated Heating Power Input KW 0.04 0.06 0.07 0.085 0.132
Rated Cooling Current A 0.18 0.27 0.32 0.39 0.6
Rated Heating Current A 0.18 0.27 0.32 0.39 0.6
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 1300/1000/800 1500/1100/800 1600/1200/900 1800/1300/950 2100/1700/1200
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 38/35/33 39/36/33 40/37/34 43/38/35 47/42/37
Net Dimension
(WxDxH) mm 840x840x245 840x840x290
Packing Dimension
(WxDxH) mm 920x920x270 920x920x315
Net Weight Kg 22 22.5 25 27.5
Gross Weight Kg 25.5 26 28.5 31
Panel
Net Dimension
(WxDxH) mm 950×950×50
Packing Dimension
(WxDxH) mm 1055×1055×90
Net weight Kg 6
Gross weight Kg 9
Refrigerant
Pipe
Gas Side mm/in 15.88(5/8)
Liquid Side mm/in 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
72 Compact Cassette
Technical characteristics
Recommended places
Office, restaurant, supermarket, shopping mall, lobby, etc
Ultra Low Noise
Using the advanced technology of three-dimensional spiral blade
design, can reduce the air resistance, realize the machine low noise
operation, \"quiet\" enjoy a comfortable life.
Built-in DC Drain Pump
The drain pump delivers a maximum lift height of 1200 mm,
simplifying installation and enabling efficient condensate drainage
from the indoor unit.
DC inverter fan motor technology
Adoption DC inverter motor technology, to improve the running
efficiency by 15% and reduce the operation noise (min 25dB)
Compact design
It features a compact body size (570mm x 570mm) that allows it to fit
neatly within the space of standard architectural ceiling tiles.
IDU Lineup & Specifications
73
Items Unit
18 22 25 28 32 36 40 45 50 56
Indoor Model:TMV-V(**)Q4R/N1D1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 6000 7500 9000 10000 11000 12000 14000 15000 17000 19000
KW 1.8 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6
Heating
Btu/h 7500 9000 10000 11000 12000 14000 15000 17000 19000 21000
KW 2.2 2.5 2.8 3.2 3.6 4 4.5 5 5.6 6.3
Electric
Data
(T1)
Rated Cooling
Power Input KW 0.014 0.016 0.022 0.044 0.05
Rated Heating
Power Input KW 0.014 0.016 0.022 0.044 0.05
Rated Cooling
Current A 0.06 0.07 0.1 0.2 0.23
Rated Heating
Current A 0.06 0.07 0.1 0.2 0.23
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 520/390/260 560/410/280 620/460/300 750/560/310 800/590/330
Indoor sound
pressure
(Hi/Mi/Lo)
dB(A) 30/28/25 31/29/25 35/30/26 43/32/26 45/34/27
Net Dimension
(WxDxH) mm 570x570x245
Packing Dimension
(WxDxH) mm 718x657x301
Net Weight Kg 14.5 15
Gross Weight Kg 17 17.5
Panel
Net Dimension
(WxDxH) mm 650x650x57
Packing Dimension
(WxDxH) mm 734x734x95
Net weight Kg 2.7
Gross weight Kg 4.25
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2)
Liquid Side mm/in 6.35 (1/4)
Operation Temperature Range °C 16-31
1. Specifications are based on the following conditions:
2. Cooling: Indoor temperature 27°C DB/19°C WB,and outdoor temperature 35°C DB/24°C WB.
3. Equivalent piping length:5m; Level difference:0m; Voltage:230V.
4. Sound Level: Indoor unit sound pressure level,measured at a point 1.5m downward from the unit center.
5. Outdoor unit sound pressure level,measured at a point 1.0m in front of the unit.
6. Optional simple wired controller; Universal remote controller; auto-restart(optional); Timer:only one circle.
7. Due to ongoing product development, specifications are subject to change without notice.
Note:
Compact Cassette
Specification
74 IDU Lineup & Specifications
Recommended places
Office, conference room, hotel room, restaurant, living room, etc
Technical characteristics
Low ESP Slim Duct
Constant Air Volume
Fan motor automatically adjusts speed according to real-time wind
resistance. To provide stable air volume to rooms.
Ultra-thin Body Design, Fashion and Beautiful
The minimum height of the body is only 200mm, saving space.
Segmented Slide-out Filter Design (Optional)
The filter can be pulled out from either left or right side for replacement
or cleaning, even in confined spaces.
High ESP
ESP up to 80Pa supports longer air duct and fits with more installation
scenario.
Built-in DC Drain Pump
The drain pump delivers a maximum lift height of 1200 mm, simplifying
installation and enabling efficient condensate drainage from the indoor
unit.
MAX: 12M
75
Specification
Low ESP Slim Duct
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Items Unit
18 22 25 28 32 36
Indoor Model: TMV-V(**)F5/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 6000 7500 9000 10000 11000 12000
KW 1.8 2.2 2.5 2.8 3.2 3.6
Heating
Btu/h 7500 9000 10000 11000 12000 14000
KW 2.2 2.5 2.8 3.2 3.6 4
Electric
Data
(T1)
Rated Cooling Power Input KW 0.02 0.03
Rated Heating Power Input KW 0.02 0.03
Rated Cooling Current A 0.09 0.14
Rated Heating Current A 0.09 0.14
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 500/380/200 550/380/200
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 30/26/20 31/26/22
External Static Pressure
(Rated) Pa 20
External Static Pressure
(Range) Pa 0~50
Net Dimension (WxDxH) mm 700×450×200
Packing Dimension (WxDxH) mm 900×555×250
Net Weight Kg 15.5
Gross Weight Kg 18
Refrigerant
Pipe
Gas Side mm/in 9.52(3/8) 12.7(1/2)
Liquid Side mm/in 6.35(1/4)
Operation Temperature Range °C 16~31
Items Unit
40 45 50 56 63 71 80
Indoor Model: TMV-V(**)F5/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 14000 15000 17000 19000 21000 24000 27000
KW 4 4.5 5 5.6 6.3 7.1 8
Heating
Btu/h 15000 17000 19000 21000 24000 27000 30000
KW 4.5 5 5.6 6.3 7.1 8 9
Electric
Data
(T1)
Rated Cooling Power Input KW 0.05 0.054
Rated Heating Power Input KW 0.05 0.054
Rated Cooling Current A 0.23 0.25
Rated Heating Current A 0.23 0.25
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 850/580/310 1100/760/480
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 34/29/24 37/31/27
External Static Pressure
(Rated) Pa 20
External Static Pressure
(Range) Pa 0~50 0~80
Net Dimension (WxDxH) mm 920×450×200 1100×450×200
Packing Dimension (WxDxH) mm 1200×555×250 1290×565×245
Net Weight Kg 18 22.5
Gross Weight Kg 21 26
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
76 Recommended places
Office, conference room, hotel room, restaurant, living room, etc
Technical characteristics
Free Static Pressure Duct
Ceiling & Floor installation
Support both ceiling concealed and floor
concealed installation.
Built-in DC Drain Pump
The drain pump delivers a maximum lift height
of 1200 mm, simplifying installation and
enabling efficient condensate drainage from
the indoor unit.
Magnetic Filter (Optional)
Customizable magnetic filter, no screws
required for mounting, enabling easy removal
and cleaning.
Segmented Slide-out Filter Design
(Optional)
The filter can be pulled out from either left or
right side for replacement or cleaning, even in
confined spaces.
Fresh Air
Take in outdoor fresh air, ensure that the
indoor air is fresh and circulated. Max fresh air
volume 100m2
/h.
High ESP
ESP up to 200Pa* supports longer air duct
and fits with more installation scenario.
Constant Air Volume
Fan motor automatically adjusts speed
according to real-time wind resistance. To
provide stable air volume to rooms.
Slim Body 245mm
Duct are new designed body of 245mm
thickness which is convenient for concealed
installation.
2 Air Return Ways
There are two air return ways to be chosen
for installation: bottom air return and rear air
return.
IDU Lineup & Specifications
Recommended places
Office, conference room, hotel room, restaurant, living room, etc
77
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Free Static Pressure Duct
Specification
Items Unit
45 50 56 63 71 80 90 100 112 125 140 160 180
Indoor Model: TMV-V(**)F2/N1DY(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling
Btu/h 15,000 17,000 19,000 21,000 24,000 27,000 30,000 34,000 38,000 42,000 48,000 54,000 60,000
KW 4.5 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 17.5
Heating
Btu/h 17,000 19,000 21,000 24,000 27,000 30,000 34,000 38,000 42,000 48,000 55,000 61,000 66,000
KW 5.0 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 18.0 19.5
Electric
Data
(T1)
Rated Cooling Power
Input KW 0.072 0.125 0.18 0.23 0.28 0.33
Rated Heating Power
Input KW 0.072 0.125 0.18 0.23 0.28 0.33
Rated Cooling Current A 0.33 0.57 0.82 1.05 1.27 1.5
Rated Heating Current A 0.33 0.57 0.82 1.05 1.27 1.5
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 1000/650/480 1350/950/700 1900/1400/1000 2100/1400/1050 2500/1850/1250 2700/1950/1350
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 36/30/27 40/35/30 43/39/34 44/39/34 44/39/34 46/40/35
External Static Pressure
(Rated) Pa 40 50
External Static Pressure
(Range) Pa 0~160 0~200
Net Dimension
(WxDxH) mm 920×700×245 1200×700×245 1400×700×245
Packing Dimension
(WxDxH) mm 1140×830×290 1420×830×290 1620×830×290
Net Weight Kg 28 29 37 38 41 41
Gross Weight Kg 33 34 42 43 47 47
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
78 IDU Lineup & Specifications
High static pressure Duct
Recommended places
Workshop, hotel, restaurant, shopping mall, ballroom,
bar and other large space places
Technical characteristics
Various Forms of Air Outlets, Matching with Decoration
The indoor unit adopts a hoiden installation mode, which can be
equipped with appropriate air outlets to perfectly combine the air
conditioning.
Ultra-high Static Pressure Design to Meet Various Space
Requirements
Maximum static pressure 300Pa, can be long distance multi-point air
supply, fully meet the air conditioning needs of different Spaces.
Clean Sterilization, Healthy Life
Built-in coarse filter, PP filter screen, optional silver ion purification
module, effectively remove large particles in the air, absorb
formaldehyde and odor, eliminate germs.
79
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
High Static Pressure Duct
Specification
Items Unit
140 280 450 560
Indoor Model: TMV-V(**)F1/XFN1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 48000 95500 153000 191000
KW 15.5 28 45 56
Heating
Btu/h 34000 68000 95500 133000
KW 10 20 28 39
Electric
Data
(T1)
Rated Cooling Power Input KW 0.42 1.1 1.55 2.25
Rated Heating Power Input KW 0.42 1.1 1.55 2.25
Rated Cooling Current A 2 5.3 7.4 10.8
Rated Heating Current A 2 5.3 7.4 10.8
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 2050 3000 4000 6000
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 45 53 56 60
External Static Pressure
(Rated) Pa 196 200 300
Net Dimension (WxDxH) mm 1200×590×380 1366×758×520 1770×758×700
Packing Dimension (WxDxH) mm 1410×695×435 1620×975×740 2035×975×920
Net Weight Kg 58 120 220
Gross Weight Kg 60 145 245
Refrigerant
Pipe
Gas Side mm/in 15.88(5/8) 25.4(1) 28.69(9/8)
Liquid Side mm/in 9.52(3/8) 12.7(1/2)
Operation Temperature Range °C 16~31
80 IDU Lineup & Specifications
Recommended places
Cinemas, hotels, lobbies, dance halls, bars and other places
Technical characteristics
Note: The sum of the capacity of the processing unit and the indoors should be 50%~100% of the ODU capacity, and the capacity of the fresh air units does not exceed 30%.
Fresh Air Duct
Healthy Fresh Air
Through the fresh air unit, the outdoor healthy air can be introduced
into the room to keep the indoor healthy.
Ultra-high Static Pressure Design
The maximum static pressure is 300pa, which can meet longdistance air supply and different space requirements.
Simplify Air Exhaust System
Simplified air supply and exhaust system, stable and reliable.
Control Smart and Lower Cost
The fresh air unit can be controlled independently or connected to the
same outdoor unit system with the AC indoor unit, reducing costs and
installation space.
MAX: 12M
81
Items Unit
220 280 450 560
Indoor Model:TMV-V(**)F1/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 75000 96000 154000 191000
KW 22 28 45 56
Heating
Btu/h 85300 106000 171000 208000
KW 25 31 50 61
Electric
Data
(T1)
Rated Cooling Power Input KW 1.75 2.25
Rated Heating Power Input KW 1.75 2.25
Rated Cooling Current A 8.85 11.36
Rated Heating Current A 8.85 11.36
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 4500/3440/2910 7500/5730/4860
Indoor sound pressure (Hi/Mi/Lo) dB(A) 55/53/51 61/59/57
External Static Pressure (Rated) Pa 200
External Static Pressure (Range) Pa 100~300
Net Dimension (WxDxH) mm 1366×758×520 1770×758×700
Packing Dimension (WxDxH) mm 1620×975×740 2035×975×920
Net Weight Kg 120 220
Gross Weight Kg 145 245
Refrigerant
Pipe
Gas Side mm/in 22.2(7/8) 28.6(9/8)
Liquid Side mm/in 12.7(1/2)
Operation Temperature Range °C 16~31
Fresh Air Duct
Specification
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
82 IDU Lineup & Specifications
Wall mounted
Recommended places
Living room, study, reference room, negotiation room and
other places
Technical characteristics
Ultra-low Silent Operation
Adopt large-diameter blade, high-quality plastic-encapsulated motor,
and the noise is as low as 27dB(A).
Ultra-thin Body Design, Smart and Beautiful
The minimum thickness of the unit is only 294mm, which makes
installation more convenient.
Long-lasting Filter Design
The long-term filter design makes the air more heathy, reduces the
difficulty of maintenance.
Wide-angle Air Supply, More Comfortable
The upper and lower wind guide vanes make the airflow comfortable.
27dB(A)
83
Specification (50Hz, AC)
Wall mounted (Built-in EXV)
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
Specification (50/60Hz, DC)
Wall mounted (External EXV)
If the wall-mounted unit is installed in the
bedroom and you are sensitive to sounds (such
as the noise from the EXV adjustment), it is
recommended to use a external EXV kit wallmounted unit , and install the EXV kit outside the
bedroom, like in the corridor or inside the ceiling.
External EXV Kit Note: Maximum 9m if extending the EXV wire in field.
Max.3.5m
External EXV Kit
Items Unit 22 28 36 45 50 56 71 80 90 100 Indoor Model:TMV-V(**)G/N1DY-B(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50/60Hz, 1Ph
Capacity
Cooling Btu/h 7500 10000 12000 15000 17000 19000 24000 27000 30000 34000
KW 2.2 2.8 3.6 4.5 5 5.6 7.1 8 9 10
Heating Btu/h 9000 11000 14000 17000 19000 21000 27000 30000 34000 41000
KW 2.5 3.2 4 5 5.6 6.3 8 9 10 12
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.045 0.055 0.09
Rated Heating Power Input KW 0.04 0.045 0.055 0.09
Rated Cooling Current A 0.19 0.2 0.25 0.4
Rated Heating Current A 0.19 0.2 0.25 0.4
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 550/450/330 650/550/360 800/700/500 1500/1200/800
Indoor sound pressure
(S/M/Mute) dB(A) 37/29/22 39/31/27 45/38/34 47/41/36
Net Dimension (WxDxH) mm 910×206×294 1010×220×315 1186×258×360
Packing Dimension (WxDxH) mm 977×276×367 1094×300×386 1260×328×430
Net Weight Kg 9.5 12 16.5
Gross Weight Kg 12 14.5 21
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Items Unit 22 28 36 45 50 56 71 80 Indoor Model:TMV-V(**)G/N1Y-B(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 24000 27000
KW 2.2 2.8 3.6 4.5 5 5.6 7.1 8
Heating
Btu/h 9000 11000 14000 17000 19000 21000 27000 30000
KW 2.5 3.2 4 5 5.6 6.3 8 9
Electric
Data
(T1)
Rated Cooling Power Input KW 0.04 0.045 0.07
Rated Heating Power Input KW 0.04 0.045 0.07
Rated Cooling Current A 0.19 0.2 0.32
Rated Heating Current A 0.19 0.2 0.32
Indoor
Unit
Indoor Air Flow
(Hi/Mi/Lo) m³/h 550/450/350 650/580/400 800/700/550
Indoor sound pressure
(S/M/Mute) dB(A) 38/30/27 42/38/29 44/38/35
Net Dimension (WxDxH) mm 910×206×294 1010×220×315
Packing Dimension
(WxDxH) mm 977×276×367 1094×300×386
Net Weight Kg 10 13
Gross Weight Kg 12.5 16
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
84 Ceiling & floor Recommended places
Living room, study, reference room, negotiation
room and other places
Technical characteristics
Ultra-thin Design
Compact design which fits for various room styles.
Detachable Plastic Blowers
Universal designed parts and assemblies applied, which is easy for
maintenance.
Flexible Installation
Wire Control (Optional)
Two ways of installation available, ceiling suspended and floor standing.
Wire control is available, especially for hotel rooms, offices, etc.
Wide Range of Air Flow
The air supply angle is from 0 to 110°, making the indoor temperature
more uniform and more comfortable.
Dual Direction of Drainage
Condensing water can be drained both from left and right side.
110°
IDU Lineup & Specifications
85
Ceiling & floor
Specification
Items Unit
45 50 56 63 71 80 90 100 112 125 140
Indoor Model: TMV-V(**)ZD/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 15000 17000 19000 21000 24000 27000 30000 34000 38000 42000 48000
KW 4.5 5 5.6 6.3 7.1 8 9 10 11.2 12.5 14
Heating
Btu/h 17000 19000 21000 24000 27000 30000 34000 38000 42000 48000 55000
KW 5 5.6 6.3 7.1 8 9 10 11.2 12.5 14 16
Electric
Data
(T1)
Rated Cooling Power Input KW 0.102 0.149 0.158 0.235
Rated Heating Power Input KW 0.102 0.149 0.158 0.235
Rated Cooling Current A 0.46 0.68 0.72 1.07
Rated Heating Current A 0.46 0.68 0.72 1.07
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 960/870/680 1200/1100/820 1600/1440/1280 2000/1910/1590
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 44/42/38 46/44/40 50/48/44 52/50/46
Net Dimension (WxDxH) mm 1055×675×235 1055×675×235 1275×675×235 1635×675×235
Packing Dimension (WxDxH) mm 1131×753×313 1351×753×313 1711×753×313
Net Weight Kg 24 25 29 38
Gross Weight Kg 27 28 35 46
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
86 One-way Cassette
Recommended places
Living room, dining room, office, lobby, etc
IDU Lineup & Specifications
Technical characteristics
Stronger Airflow
1100m3
/h large-circulation air volume ensuresrapid whole-room cooling
by circulating andspreading cool air evenly.
T-Al Energy-Saving
Using Al algorithm and tempature prediction
models, T-Al dynamically adjusts the compressor
frequency to regulate room temperature-saving
energy while keeping comfort.
High-lift Drain Pump
The drain pump with a 1200mm lifting head which is as standard,
simplifying installation of the drain pipes.
Easy Disassembly & Easy Cleaning
A simple pull-down releases the snap-fit panel
for easy maintenance and cleaning.
130mm Slim Design
Fits ceiling space as limited as 150 mm, Saves
wall-mount space, Blends in with integrated
home-style design.
10.5m Long-distance
AirflowSuitable for narrow and high-depthspaces.
Wi-Fi & OTA
Easily control your air conditioner anytime,
anywhere with just a mobile phone and update
software APP. No need to manipulate on electrical
controlboard, convenient for afterservice.
120° Wide Airflow
Full-Room Airflow adapts to diverseroom
shapes,delivering coolingcomfort that reaches
every corner.
87
One-way Cassette
Specification
Items Unit
TMV-V22Q1/
N1DY(E)
TMV-V28Q1/
N1DY(E)
TMV-V36Q1/
N1DY(E)
TMV-V45Q1/
N1DY(E)
TMV-V56Q1/
N1DY(E)
TMV-V63Q1/
N1DY(E)
TMV-V71Q1/
N1DY(E)
Indoor Model /
Power Supply V~,Hz,Ph 220-240V~50/60Hz
Capacity
Cooling kW 2.2 2.8 3.6 4.5 5.6 6.3 7.1
Heating kW 2.5 3.2 4.0 5.0 6.3 7.1 8.0
Electrical
Data
Rated Cooling Power Input W 25 25 28 30 35 45 55
Rated Heating Power Input W 25 25 28 30 35 45 55
Rated Cooling Current A 0.16 0.16 0.19 0.20 0.23 0.30 0.37
Rated Heating Current A 0.16 0.16 0.19 0.20 0.23 0.30 0.37
Indoor
Unit
Indoor Air Flow m³/h
600/550/520/
480/450/420/
390
600/550/520/
480/450/420/
390
640/590/560/
530/490/430/
400
880/790/740/
700/650/610/
570
900/820/780/
730/680/640/
590
1050/980/880/
830/740/650/
610
1100/1000/980/
880/790/700/
650
Indoor Sound Power
(Standard rating conditions) dB(A) 51/50/48/46/
44/43/42
51/50/48/46/
44/43/42
52/51/49/47/
45/44/43
53/51/50/49/
47/46/45
54/53/52/51/
49/46/45
56/55/53/51/
50/48/46
58/57/55/53/
51/49/47
Indoor Sound Pressure
(Standard rating conditions) dB(A) 37/36/34/32/
30/29/28
37/36/34/32/
30/29/28
38/37/35/33/
31/30/29
39/37/36/35/
33/32/31
40/39/38/37/
35/32/31
42/41/39/37/
36/34/32
44/43/41/39/
37/35/33
Net Dimension (WxDxH) mm 1020×450×185 1365×450×185
Net Dimensions
(no water tray) (WxDxH) mm 1020×450×130 1365×450×130
Packing Dimension (WxDxH) mm 1185×535×240 1470×540×230
Net Weight/Gross Weight kg 11.0/14.5 13.5/17.5
Panel
Net Dimension (WxDxH) mm 1180×500×90 1480×500×90
Packing Dimension (WxDxH) mm 1275x565x140 1585x575x140
Net Weight/Gross Weight kg 5.0/7.5 6.0/10.0
Refrigerant
Pipe
Gas Side mm/inch Ф9.52 (3/8'') Ф9.52 (3/8'') Ф9.52 (3/8'') Ф12.7 (1/2'') Ф12.7 (1/2'') Ф15.88 (5/8'') Ф15.88 (5/8'')
Liquid Side mm/inch Ф6.35 (1/4'') Ф6.35 (1/4'') Ф6.35 (1/4'') Ф6.35 (1/4'') Ф6.35 (1/4'') Ф9.52 (3/8'') Ф9.52 (3/8'')
Drain Pipe (External dia.) mm O.D 25
Maximum Allowable Pressure MPa 4.5
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
88 Recommended places
Sitting room, study, dining room, small meeting room, etc
Technical characteristics
Two-way Cassette
IDU Lineup & Specifications
Ultra-thin Body, Lightweight Design
Super Wide Angle Air Supply
Ultra-thin body (290mm), requires less installation space, even in the
narrow low ceiling, still can be easily installed, more flexible collocation
decoration style.
Panel swing motor system adopts high-precision stepper motor, panel
up and down risk control system is more intelligent, to achieve ultrawide Angle and large range of air supply.
High-lift Drain Pump
Standard Float Switch, Water Level Monitor
A drain pump with a 700mm raise height is fitted as standard,
simplifying installation of the drain piping.
Equipped with float switch, which will automatically send alarm when
malfunction of drain pump or stuck of drain pipe occur.
Three-speed Adjustment
New winding motor, with scroll fan technology,
wider air volume regulation, quieter operation,
unique intimate wind gear design. High,
medium and low three speed adjustment,
strong refrigeration and heating, to create a
quiet and comfortable temperature.
High Ceiling Design, Direct Air Flow to
the Ground
High ceiling design, suitable for ceiling height
up to 3m space.
Quiet Design, Quiet and Comfortable
Centrifugal wind wheel, axial air inlet, through
rotation to form a certain wind pressure, small
blade area, large number, uniform air, noise
greatly reduced, for you to create a quiet and
comfortable environment.
3m
89
Two-way Cassette
Specification
Items Unit
22 28 36 45 50 56 63 71
Indoor Model: TMV-V(**)Q2/N1Y(E)
IDU Power Supply V~,Hz,Ph 220-240V, 50Hz, 1Ph
Capacity
Cooling
Btu/h 7500 10000 12000 15000 17000 19000 21000 24000
KW 2.2 2.8 3.6 4.5 5 5.6 6.3 7.1
Heating
Btu/h 9000 11000 14000 17000 19000 21000 24000 27000
KW 2.5 3.2 4 5 5.6 6.3 7.1 8
Electric
Data
(T1)
Rated Cooling Power Input KW 0.064 0.07 0.11
Rated Heating Power Input KW 0.064 0.07 0.11
Rated Cooling Current A 0.27 0.31 0.49
Rated Heating Current A 0.27 0.31 0.49
Indoor
Unit
Indoor Air Flow (Hi/Mi/Lo) m³/h 580/460/380 680/660/520 850/660/520 1360/1180/970
Indoor sound pressure
(Hi/Mi/Lo) dB(A) 42/35/32 43/38/35 44/38/35 46/39/36
Net Dimension(WxDxH) mm 1140×575×290
Packing Dimension (WxDxH) mm 1305×755×370
Net Weight Kg 32 33 34
Gross Weight Kg 38 39 40
Panel
Net Dimension (WxDxH) mm 1240×680×30
Net weight Kg 5.56
Refrigerant
Pipe
Gas Side mm/in 12.7(1/2) 15.88(5/8)
Liquid Side mm/in 6.35(1/4) 9.52(3/8)
Operation Temperature Range °C 16~31
Remark:The above designs and specifications are subject to change of product improvement without prior notice.
90 Non-polar CAN bus
communication
technology
TCL remote intelligent
service center
BMS gateways
Multiple control solutions
TCL CAC
management system
AHU connection kit
INTELLIGENT - OPERATION AND
MAINTENANCE CONTROL
CAN
AHU BMS
TCL's full DC inverter VRF systems are equipped with intelligent
operation and maintenance capabilities. This integrated solution
ensures energy-efficient operation, high performance, and intelligent
management for buildings.
90
91
91
92 Intelligent - Operation and Maintenance Control
Remote Controller
Wired Controller
· Cooling / dehumidification / fan / heating /
automatic and other operation settings
· Temperature / fan speed setting
· Sleep/timer/swing/turbo and other functions
· Cooling / dehumidification / fan / heating / automatic and other operation
settings
· Temperature / fan speed setting
· Sleep / timer / swing / turbo and other function settings
· Monitoring function, big LCD screen displays the operation status of the unit
· Remote control signal available
Multiple control solutions
TMV6+ provides a variety control solutions for customers to choose .
6.1
Central Controller
6.2 VRF WiFi & APP control solution
WiFi module
Connect the WiFi module with the air-conditioning system, and then match
the WiFi module with the wireless router through the mobile phone APP,
and the air-conditioning equipment is networked, so that the cell phone APP
can realize remote control of the air-conditioning system from a different
place and enjoy the convenience interconnection; KZH- D1
Intelligent APP
After the unit is networked, the air conditioning system can be controlled
through the Tsmart mobile APP, which can realize:
-Mode control of air conditioner cooling/heating/dehumidifying/air supply;
-Setting temperature, wind speed, timer on/off function settings;
-Single unit, group, cluster, all control;
52E 58E 85T
86J1 86N3 86V
86B1
· 10 inches and colorful screen display, beautiful appearance, touch screem,
easy operation.
· A variety of combinations, single or multiple machines can be operated
simultaneously.
· It also has the schedule setting and historical fault query function.Up to
32 refrigerant systems and 1024 IDUs can be connected, easy to set indoor
units parameters 10'' Central Controller
93
6.4 Intelligent Control System
AHU Connection KIT
Solution to extend TCL VRF technology to
third party Air Handling Units.
√ Easy for connecting to third party AHU
√ Setting capacity by DIP
√ Remoter or wire controller can be chosen
√ 3 steps fan motor speed, Low/Mid/High
√ Error status: No error or error occurred
6.3
Communication wire Refrigerant pipe
AHU
AHU KIT
Type Condition Model Name Cooling Capacity Range
AHU
Kit
For room
return air
TMV-AK1 2.8-14kW
TMV-AK2 16-28kW
TMV-AK3 30-56kW
For outside
fresh air
TMV-AKF1 2.8-14kW
TMV-AKF2 16-28kW
TMV-AKF3 30-56kW
For room return air &
outside fresh air
TMV-BK1(F) 2.2-8kW
TMV-BK2(F) 9-16kW
TMV-BK3(F) 18-38kW
TMV-BK4(F) 40-58kW
TMV-BK5(F) 60-80kW
TMV-BK6(F) 82-112kW
94 Installation options
Front Front
Front Front
More than
More than
More than
IDU
ODU
First diverging pipe
IDU IDU
Guide plate
>
> >
>
>
The space shown in the figure needs to be reserved
for the installation of the ODU, and the power
supply equipment should be installed separately.
When a system has more than two outdoor
units, it is necessary to install the units as the
followings:
The outdoor units are arranged in descending
order(for example, in the right picture, ODU
capacity A ≥ ODU capacity B ≥ ODU capacity C)
and the ODU A should install at the brance pipe.
If there are stacks around the outdoor unit, the height
should be less than 800mm from the top of the
outdoor unit. If it is less than the size,a mechanical
exhaust device must be installed.
To ensure the heat dissipation of the outdoor unit,
there should be no obstacles above the outdoor
unit. If it cannot be avoided, a deflector should be
installed.
Fluorine filing valve
Liquid-side stop valve
Gas-side stop valve
(used to detect the pressure/add refrigerant
vacuumize at the time of maintenance)
Location of refrigerant pipes
Installation space for ODU
Arrangement sequence of ODU
95
Dimension of ODU
Requirements for ODU installation
Model A B
TMV-VED+(252-450)W/AS-D(EC) 724 754
TMV-VED+(504-680)W/AS-D(EC) 1140 754
TMV-VED+(730-900)W/AS-D(EC) 1560 754
TMV-VED+(950-1010)WIAS-D(EC) 1700 754
TMV-VED+(730-900)W/AS-D(EC)
TMV-VED+(252-450)W/AS-D(EC)
1780 17801780 1780
925
1760 1900
1340
845
845 845 845
TMV-VED+(950-1010)W/AS-D(EC)
TMV-VED+(504-680)W/AS-D(EC)
A shock absorber or shock pad should be installed between the unit and the foundation.
The unit and the foundation should be released tightly, otherwise there will be a lot of noise and vibration.
The outdoor unit must be grounded reliably.
It is forbidden to open the valves of the liquid pipe, gas pipe and oil balance pipe of the unit before commission.
The installation should ensure that there is enough space for maintenance.
≥200
96 Installation options
Design of refrigerant piping
Branch pipe specifications
Refrigerant pipe lengthand height
Admissible
value Pipes
Lengthof
supporting
pipe
Total lengthof Refrigerant pipes
(Total extended length) 1100m L1+(L2+L3+L4+L5+L6+L7+L8+L9+L10+L11
+L12)×2+a+b+c+d+e+f+g+h+i+j+k+l+m
Lengthof the farthest
supporting pipe(L)
True length 220m
L1+L7+L8+L9+L10+i
Equivalent length 240m
Lengthof the supporting pipe furthest from the
first branch pipe(L)* 120m L7+L8+L9+L10+i
Height
Height difference between
indoor and outdoor units (H)
ODU up 100m
ODU down 110m
Height between indoor units (h) 40m
Assembly Include parts Assembly Include parts
BY01 Branch pipe parts G01、L01 BY05 Branch pipe parts G04、L03
BY02 Branch pipe parts G02、L01 BY06 Branch pipe parts L01、L01
BY03 Branch pipe parts G02、L02 BY07 Branch pipe parts L01、L02
BY04 Branch pipe parts G03、L02 BY08 Branch pipe parts G05、G02
* Note: Refer to relevant technical documents or consult technical person
120m
100m
240m
40m
First branch pipe
Between IDU & ODU Height difference Between IDU & ODU Height difference
Equivalent pipe lengthfarthest from
the first branch pipe
Equivalent lengthof farthest piping of IDU
97
Branch pipe specifications
98 Piping classification
Piping classification
Pipe dimension of indoor unit(NO.:a,b,c,d,… m)
Allowable lengthand height difference of refrigerant piping
IDU main piping and branch pipe assembly(Number: L2,L3,L4...L12,A,B,C...L)
Name of supporting pipe Connection position of supporting pipe Assembly
Main pipe Pipe between the outdoor unit and the first branch L1
Main pipe of indoor unit Pipe behind the first indoor branch which do not connect
to indoor unit L2,L3,L4,... L12
Slave pipe of indoor unit Pipes between the branch and indoor unit a,b, c, d,... m
Indoor unit branch assembly Pipes to the master pipe and slave pipes A, B, C,D,E,F,G,H, I,J,K,L
Outdoor unit branch assembly Pipes to the outdoor unit and main pipe L,Mg
Outdoor unit connecting pipe Pipe between outdoor and outdoor branch 1,g2, g3, g4, G1, G2
Indoor Unit Model Gas side Liquid side
Capacity: 1800~2200W φ9.52(flared nut) φ6.35(flared nut)
Capacity: 2800~5600W φ12.7(flared nut) φ6.35(flared nut)
Capacity: 6300~14000W φ15.9(flared nut) φ9.52(flared nut)
Capacity of
downstream
Indoor unit
A(×100w)
Dimension of
Master pipe
(Gas/Liquid)
Applicable brance
pipe
(Gas/Liquid) A(×100w)
Dimension of master
pipe
(Gas/Liquid)
Applicable brance
pipe
(Gas/Liquid)
A < 63 φ12.7/φ6.35 BY06(L01/L01) 63 ≤ A < 168 φ15.9/φ9.52 BY07(L02/L01)
168 ≤ A < 224 φ19.1/φ9.5 BY07(L02/L01) 224 ≤ A < 330 φ22.2/φ12.7 BY01(G01/L01)
330 ≤ A < 470 φ25.4/φ12.7 BY01(G01/L01) 470 ≤ A < 710 φ28.6/φ15.9 BY03(G02/L02)
710 ≤ A < 1040 φ31.8/φ19.1 BY03(G02/L02) 1040 ≤ A < 1540 φ38.1/φ19.1 BY04(G03/L02)
1540 ≤ A < 1800 φ41.2/φ22.2 BY05(G04/L02) 1800 ≤ A < 2500 φ44.5/φ25.4 BY05(G04/L03)
2500 ≤ A φ54.0/φ28.6 BY08(G05/G02)
Installation options
99
Diameter of outer connecting pipe
ODU Main pipe and branch pipes
Remark:
1. Please select the main pipe diameter of the outdoor unitfollow the above table. If the main pipe is larger ,
choose the main pipe according to larger one.
2. If the system is more than 108HP,please consult technical personnel.
ODU stop valve port diameter(Number: g1,g2,g3,g4)
Outdoor unit Model (Capacity) Gas-side Liquid-side Oil balance-side
25200W Φ19.1(welding) Φ9.52(welding) Φ9.52(welding)
28000W Φ22.2(welding) Φ9.52(welding) Φ9.52(welding)
33500/40000W Φ25.4(welding) Φ12.7(welding) Φ9.52(welding)
45000W Φ28.6(welding) Φ12.7(welding) Φ9.52(welding)
50400/56000/61500/68000W Φ28.6(welding) Φ15.9(welding) Φ9.52(welding)
73000W Φ31.8(welding) Φ19.1(welding) Φ9.52(welding)
85000/90000W Φ34.9(welding) Φ19.1(welding) Φ9.52(welding)
95000/101000W Φ38.1(welding) Φ19.1(welding) Φ9.52(welding)
Capacity of Outdoor
Units (HP)
Dimensions of Master Pipe, when the equivalent length
of all supporting pipes is less than 90 meters
Dimensions of Master Pipe, when the equivalent length of
all supporting pipes is 90 meters at least
Gas/Liquid-side Indoor Branch Pipe 1
(Gas/Liquid-side) Gas/Liquid-side Indoor Branch Pipe 1
(Gas/Liquid-side)
8HP Φ19.1/Φ9.52 Assembly BY01(G01/L01) Φ22.2/Φ12.7 Assembly BY01(G01/L01)
10HP Φ22.2/Φ9.52 Assembly BY01(G01/L01) Φ25.4/Φ12.7 Assembly BY01(G01/L01)
12~14HP Φ25.4/Φ12.7 Assembly BY01(G01/L01) Φ28.6/Φ15.9 Assembly BY03(G02/L02)
16HP Φ28.6/Φ12.7 Assembly BY02(G02/L01) Φ31.8/Φ19.1 Assembly BY03(G02/L02)
18~24HP Φ28.6/Φ15.9 Assembly BY03(G02/L02) Φ31.8/Φ19.1 Assembly BY03(G02/L02)
26~28HP Φ31.8/Φ19.1 Assembly BY03(G02/L02) Φ38.1/Φ22.2 Assembly BY04(G03/L02)
30~32HP Φ34.9/Φ19.1 Assembly BY04(G03/L02) Φ38.1/Φ22.2 Assembly BY04(G03/L02)
34~48HP Φ38.1/Φ19.1 Assembly BY04(G03/L02) Φ41.2/Φ22.2 Assembly BY05(G04/L03)
50~54HP Φ38.1/Φ19.1 Assembly BY04(G03/L02) Φ44.5/Φ22.2 Assembly BY05(G04/L03)
56~66HP Φ41.2/Φ22.2 Assembly BY05(G04/L03) Φ44.5/Φ22.2 Assembly BY05(G04/L03)
68~72HP Φ44.5/Φ22.2 Assembly BY05(G04/L03) Φ50.8/Φ25.4 Assembly BY08(G05/G02)
74~84HP Φ50.8/Φ22.2 Assembly BY05(G04/L03) Φ50.8/Φ25.4 Assembly BY08(G05/G02)
86~96HP Φ50.8/Φ25.4 Assembly BY08(G05/G02) Φ54.0/Φ28.6 Assembly BY08(G05/G02)
98~108HP Φ54.0/Φ28.6 Assembly BY08(G05/G02) Φ63.0/Φ28.6 Assembly BY08(G05/G02)
100 Remark :1.The wire diameter and continuous lengthin the table are applicable to a maximum distance of 20 meters. If the power wiring exceeds
20 meters and the voltage drop exceeds the range of 2%, please choose a wire diameter with a larger cross-sectional area.
2.The selection of the power cord is based on the ambient temperature of 40°C.
3.The wire current carrying capacity in the attached table is only for the user's reference. The actual interception capacity of the wire
varies depending on the type and lengthof the cable, the way of pipe penetration, and the actual laying environment, and the correction
factor is different.
Distribution transformer
Outdoor power
Ground1 Ground2 Ground3
Building
Lightning
arrester Ground wire
Junction box
Leakage protector
Manual switch
Electrical system and installation
Please design the dedicated power supply for IDU and ODU separately.
In order to reduce interference, it is recommended to use two-core shielded cables for the signal cables of the IDU and
ODU. Please do not use multi-core cables without shielding.
The power supply should be equipped with a leakage protector and a manual switch.
During installation, the communication line and the power line must not be intertwined, and must be routed separately,
and the minimum distance should be greater than 20CM, otherwise the communication of the unit may be abnormal.
Power wiring must be entrusted to professional electricians.
The power supply, leakage protector and manual switch of the IDU connected to the same ODU are required to be
universal. (Please use the same circuit for the IDU power supply of the same system. And it must be turned on and off at
the same time, otherwise it will seriously affect the service life of the system, and unpredictable situations may occur. )
Please integrate the IDU and ODU connection wiring system and refrigerant piping system into the same system.
Electrical wiring precautions
ODU power wiring
ODU power connection
Installation options
L1
L2
L3
N
PE
(a)
Item (Capacitiy) Power Minimum Wire Diameter
Current (A)
Copper Core PVC Insulated
Wire BVV(mm²)
Copper Core XLPE
Insulated Wire YJV (mm²)
Manual Switch
Capacity (A)
Electric
Leakage
Protector
25200W
380-415V
3N~ 50Hz
20.03 4.0×5 2.5×5 25
No more
than 100mA
0.1sec
28000W 22.03 4.0×5 2.5×5 25
33500W 24.33 6.0×5 4.0×5 32
40000W 28.8 6.0×5 4.0×5 32
45000W 32.8 10.0×5 6.0×5 40
50400W 37.9 10.0×5 6.0×5 50
56000W 42 16.0×5 10.0×5 50
61500W 46.2 16.0×5 10.0×5 63
68000W 52.6 16.0×5 10.0×5 63
73000W 55.8 16.0×5 10.0×5 63
78500W 58.95 16.0×5 10.0×5 63
85000W 59.31 25.0×3+16.0×2 16.0×5 80
90000W 61.29 25.0×3+16.0×2 16.0×5 80
95000W 69.9 25.0×3+16.0×2 16.0×5 80




