Chapter 5 : Installation and Wiring
51
Step 4
Make sure that the Input Switch (Q1), Bypass Switch (Q2), Manual Bypass Switch (Q3)
and the Output Switch (Q4) are in the OFF position.
Step 5
Make sure that each external battery cabinet’s breaker (Q5) is in the OFF position.
Step 6
Follow Table 5-2 to select proper input, output, and battery cables.
Step 7
Connect the cables of the main AC source, output and external battery cabinet(s) to
the UPS. Please refer to Table 5-3, 5.6 External Battery Cabinet Connection Warnings
and the following diagram to perform wiring.
Figure 5-6: Single Unit Single Input Wiring Diagram
Step 8
Follow the table below to select proper Protective Earth (PE) cables to ground the UPS,
external battery cabinet(s) and connected critical loads. The table is in accordance
with IEC 60364-5-54 (Article 543 and Table 54.2). The grounding diagram below is for
reference.
Main AC Source
Loads
Connect to the Same Model of
UPS(s) for Parallel Application
Input Switch (Q1)
Manual Bypass
Switch (Q3)
Output Switch
(Q4)
AC Input Terminals
(L1/ L2/ L3/ N)
UPS Output Terminals
(L1/ L2/ L3/ N)
Battery Input
Terminals (+/ -/ N)
External Battery Cabinet
Bypass Switch (Q2) Bypass Input Terminals
(L1/ L2/ L3/ N)
Delta UPS DPH 60-400/ 500/ 600 kVA 52
DPH Series
UPS Capacity 400kVA/ 400kW 500kVA/ 500kW 600kVA/ 600kW
Suggested
PE Cable
Size
Input
240 mm2 × 1 PC
(500 kcmil × 1 PC)
300 mm2 × 1 PC
(600 kcmil × 1
PC)
240 mm2 × 2 PCS
(500 kcmil × 2 PCS)
Bypass
185 mm2 × 1 PC
(400 kcmil × 1 PC)
240 mm2 × 1 PC
(500 kcmil × 1 PC)
185 mm2 × 2 PCS
(400 kcmil × 2 PCS)
Output
185 mm2 × 1 PC
(400 kcmil × 1 PC)
240 mm2 × 1 PC
(500 kcmil × 1 PC)
185mm2 × 2 PCS
(400 kcmil × 2 PCS)
Battery
300 mm2 × 1 PC
(600 kcmil × 1 PC)
240 mm2 × 2 PCS
(500 kcmil × 2
PCS)
240 mm2 × 2 PCS
(500 kcmil × 2 PCS)
Maximum Cable Lug
Width 50 mm (1.97\")
Cable Lug Gap/ Inner
Diameter 44.5mm (1.75\") / 14mm (0.55\")
Screw Size M12
Tightening Torque M12 = 500 ± 10 kgf-cm (434 ± 8.7 lb-in)
Terminal Type*1 TLAPH-2A
NOTE:
*1
The suggested manufacturer is K.S. TERMINALS INC. You may use
equivalent terminals provided by other manufacturers
Figure 5-7: Grounding Diagram_ Single Unit
Load Load External Distribution
Panel
Load Grounding
External
Battery
Cabinet
Load Grounding
UPS Grounding
External Battery
Cabinet Grounding
Protective Earthing
Chapter 5 : Installation and Wiring
53
5.5.3.2 Dual Input (Single Unit)
When there are two AC power sources, single unit wiring procedures are as follows.
Step 1
Follow 5.5.2 Single Input to Dual Input Modification to modify the UPS from single input
to dual input.
Step 2
The UPS ONLY allows top cable entry. Please leave adequate space above the UPS.
Step 3
Remove the upper back panel, you can see the wiring terminals. Please refer to Figure
2-6.
Step 4
Remove the top covers (1, 2, 3, 4) shown in the following figure
Figure 5-8: Location of the Top Covers
Remove the Top
Covers (1, 2, 3 & 4)
Delta UPS DPH 60-400/ 500/ 600 kVA 54
Step 5
Make sure that the Input Switch (Q1), Bypass Switch (Q2), Manual Bypass Switch (Q3)
and the Output Switch (Q4) are in the OFF position.
Step 6
Make sure that each external battery cabinet’s breaker (Q5) is in the OFF position.
Step 7
Follow Table 5-2 to select proper input, output, and battery cables.
Step 8
Connect the cables of the main AC source, bypass source, output and external battery
cabinet(s) to the UPS. Please refer to Table 5-3, 5.6 External Battery Cabinet
Connection Warnings and the following diagram to perform wiring.
Figure 5-9: Single Unit Dual Input Wiring Diagram
Step 9
Refer to Figure 5-7 to ground the UPS, external battery cabinet(s) and connected
critical loads.
Main AC Source
Loads
Connect to the Same Model of
UPS(s) for Parallel Application
Input Switch
(Q1)
Manual Bypass
Switch (Q3)
Output Switch
(Q4)
AC Input Terminals
(L1/ L2/ L3/ N)
UPS Output Terminals
(L1/ L2/ L3/ N)
Battery Input
Terminals (+/ -/ N)
External Battery Cabinet
Bypass AC Source Bypass Switch
(Q2)
Bypass Input Terminals
(L1/ L2/ L3/ N)
Chapter 5 : Installation and Wiring
55
5.5.4 Parallel Units Wiring
NOTE:
1. Up to eight UPS units can be paralleled for redundancy and capacity
expansion. Only the UPSs with the same capacity, voltage, frequency and
version can be paralleled. Please only use the provided parallel cable to
parallel the UPS units. Otherwise, parallel functions will fail.
2. When the UPSs are paralleled, the length of each unit’s bypass input
cables plus output cables must be the same. This ensures that the
parallel UPSs can equally share the critical loads in Bypass mode.
3. Before wiring, please read 5.5 Wiring thoroughly and make sure that
relevant conditions have been met.
Step 1
For single input, follow Step 1 ~ Step 7 mentioned in 5.5.3.1 Single Input (Single Unit).
For dual input, follow Step 1 ~ Step 8 mentioned in 5.5.3.2 Dual Input (Single Unit).
Step 2
Use the provided parallel cables*1
to connect the parallel ports of the parallel units.
Please adopt the Daisy Chain method shown in the figure below. For the parallel port
location, refer to Figure 4-1.
NOTE:
*1
One parallel cable is provided in each UPS’s accessory package.
Delta UPS DPH 60-400/ 500/ 600 kVA 56
Figure 5-10: Parallel Port Connection_ Daisy Chain Method
Step 3
Follow the table below to select proper Protective Earth (PE) cables to ground the
parallel UPS units, external battery cabinet(s) and connected critical loads. The table
is in accordance with IEC 60364-5-54 (Article 543 and Table 54.2). The grounding
diagram below is for reference.
DPH Series
UPS Capacity 400kVA/ 400kW 500kVA/ 500kW 600kVA/ 600kW
Suggested
PE Cable
Size
Input
240 mm2 × 1 PC
(500 kcmil × 1
PC)
300 mm2 × 1 PC
(600 kcmil × 1 PC)
240 mm2 × 2 PCS
(500 kcmil × 2 PCS)
Bypass
185 mm2 × 1 PC
(400 kcmil × 1
PC)
240 mm2 × 1 PC
(500 kcmil × 1 PC)
185 mm2 × 2 PCS
(400 kcmil × 2 PCS)
Output
185 mm2 × 1 PC
(400 kcmil × 1
PC)
240 mm2 × 1 PC
(500 kcmil × 1 PC)
185mm2 × 2 PCS
(400 kcmil × 2 PCS)
Battery
300 mm2 × 1 PC
(600 kcmil × 1 PC)
240 mm2 × 2 PCS
(500 kcmil × 2 PCS)
240 mm2 × 2 PCS
(500 kcmil × 2 PCS)
Maximum Cable Lug
Width 50 mm (1.97\")
Cable Lug Gap/ Inner
Diameter 44.5mm (1.75\") / 14mm (0.55\")
Screw Size M12
Tightening Torque M12 = 500 ± 10 kgf-cm (434 ± 8.7 lb-in)
Terminal Type*1 TLAPH-2A
Parallel Cable
(1st UPS)
Parallel Ports
(Last UPS)
Parallel Ports
(Middle UPS(s))
Parallel Ports
Chapter 5 : Installation and Wiring
57
NOTE:
*1
The suggested manufacturer is K.S. TERMINALS INC. You may use
equivalent terminals provided by other manufacturers.
Figure 5-11: Grounding Diagram_ Parallel Units
WARNING:
Before start-up of the parallel units, qualified service personnel must set each
UPS’s 'Parallel Group ID' (1 or 2) and 'Parallel ID' (1 ~ 8) through the LCD.
Otherwise, the parallel UPSs cannot be started. Please refer to 7.6.5 Parallel
Setting.
5.6 External Battery Cabinet Connection Warnings
NOTE:
1. The information of the battery parameters in this chapter may not be
applicable to the lithium-ion batteries. For relevant information, please
refer to the manual of the lithium-ion batteries.
2. Whether you use the lead-acid batteries or the lithium-ion batteries,
please contact Delta service personnel for any battery/ battery cabinet’s
setup and configurations.
Load Load External Distribution
Panel
Load Grounding
External
Battery
Cabinet
Load Grounding UPS Grounding
External Battery Cabinet Grounding
Protective Earthing
External
Battery
Cabinet
External Battery Cabinet Grounding
UPS Grounding
Delta UPS DPH 60-400/ 500/ 600 kVA 58
WARNING:
1. Before performing battery/ battery cabinet installation, wiring and
replacement, please turn off each external battery cabinet’s breaker (Q5)
to completely disconnect the battery power from the UPS.
2. A battery can present a risk of electric shock and high short-circuit
current. Servicing of batteries and battery cabinets must be performed
or supervised by qualified service personnel knowledgeable in batteries,
battery cabinets and the required precautions. Keep unauthorized
personnel away from batteries and battery cabinets.
You should connect the UPS with at least one external battery cabinet to ensure that
the connected critical loads are protected when a power failure occurs. You can
connect up to four units of external battery cabinets to the UPS.
• To ensure that the batteries are fully charged, please charge the batteries for at
least 8 hours before initial use of the UPS. The charging procedures are as follows.
1. Connect the UPS to the main AC source and the external battery cabinet(s).
Please refer to 5.5 Wiring.
2. Follow 6. UPS Operation to turn on the external battery cabinet(s). After that,
the batteries will be automatically charged.
WARNING:
You can connect the critical loads to the external maintenance bypass
cabinet only after the batteries are fully charged. This guarantees that
the external maintenance bypass cabinet can provide sufficient
backup power to the critical loads connected when a power failure
occurs.
• To connect the external battery cabinet(s) to the UPS, please refer to 5.5 Wiring.
• For the external battery cabinet’s grounding information, please refer to Figure 5-
7 and Figure 5-11.
• Battery Parameters
No. Item Description
1 Charge Voltage
Float charge voltage: 272 Vdc (default)
Equalized charge voltage: 280 Vdc (default)
2 Charge Current
Default: ±6A (per power module)
Maximum: ±15A (per power module)
3 Low Battery Shutdown Voltage 210 Vdc (default)
4 Battery Quantity 12V × 40 PCS (default)
Chapter 5 : Installation and Wiring
59
• The charge current is adjustable from 6A to the maximum, 1A per step.
• If you need to modify the default charge current setting and default low battery
shutdown setting, please contact your local dealer or service personnel.
• Follow on-site requirements to choose 12V × 30/ 32/ 34/ 36/ 38/ 40/ 42/ 44/ 46
PCS of batteries. Change of the battery quantity will influence the applied
specifications. For battery selection, installation and replacement, please contact
your local dealer or customer service.
• You must set up the ‘Battery Rating Voltage’, ‘Battery Strings’ and ‘Capacity’ on the
LCD according to on-site application. Otherwise, the batteries will be overcharged, not fully charged or even seriously damaged.
• Only use the same type of batteries from the same supplier. Never use old, new
and different Ah batteries at the same time.
• The number of batteries must meet the UPS requirements.
• Do not connect the batteries in reverse.
• Use a voltage meter to measure whether the total voltage is around 12.5 Vdc × the
total number of batteries after the batteries are connected in series.
• The default battery quantity is 40 PCS of 12V batteries connected in series. The
external battery cabinet’s neutral (N) is to be connected to the middle of the 20th
and 21st batteries.
Figure 5-12: External Battery Cabinet Connection
WARNING:
The electrolyte leakage of the batteries can lead to serious accidents. For
safety’s sake, you must insulate the batteries properly (using insulated
trays or boxes) from the metal cabinets and racks.
Delta UPS DPH 60-400/ 500/ 600 kVA 60
• Installation of the External Battery Cabinet’s Protective Device
Please follow your UPS’s rating to install an appropriate protective device for each
external battery cabinet. There are two installation methods for selection.
(1) A 4-pole DC circuit breaker or DC isolated switch connected in series with DC
fuses
(2) A 3-pole DC circuit breaker or DC isolated switch connected in series with DC
fuses
For relevant values, please refer to Table 5-4; for installation diagrams, please refer to
Figure 5-13 ~ Figure 5-14.
Table 5-4: External Battery Cabinet’s Protective Device (Default Battery Q’ty: 12 Vdc ×
40 PCS)
UPS Capacity Protective Device’s
Current Protective Device’s Voltage
400kVA/ 400kW 1000A • 4-pole DC isolated switch/
DC circuit breaker: voltage
per pole ≥ 250 Vdc.
• 3-pole DC isolated switch/
DC circuit breaker: voltage
per pole ≥ 500 Vdc
• DC fuse: voltage ≥ 500 Vdc
500kVA/ 500kW 1250A
600kVA/ 600kW 1600A
NOTE:
1. Table 5-4 is for 12 Vdc × 40 PCS of batteries (default). If you install a
different number of batteries, please contact Delta service personnel for
the protective device’s current and voltage.
2. If you need to parallel multiple units of external battery cabinets, please
contact Delta service personnel for relevant information.
3. To extend backup time, you can parallel up to four units of external
battery cabinets to the UPS. Please note that (1) the number of the
batteries in each paralleled external battery cabinet and (2) the cable
length of each battery string must be the same.
• When choosing the external battery cabinet’s protective device, please take the
following factors into consideration: (1) overcurrent between the UPS and battery
circuit, (2) short circuit current of the batteries, (3) wire/ cable materials, and (4)
local electrical regulations. If you have any questions about the external battery
cabinet’s protective device, please contact Delta service personnel.
Chapter 5 : Installation and Wiring
61
• The protective device is optional, and its type must be fast-acting DC circuit
breaker and/ or fast-acting DC fuse. If you want to buy any of them, please contact
Delta service personnel. When choosing the protective device, please follow the
instructions below.
(1) The protective device’s rated current must comply with the current values
shown in Table 5-4.
(2) The specifications of the protective device’s short-circuit protection (i.e. the
tripping current of the fast-acting DC circuit breaker and/ or the melting current
of the fast-acting DC fuse) must be 3 ~ 6 times the values shown in Table 5-4.
Besides, the response time of the protective device must be less than 20ms.
(3) For the choice of the fast-acting DC fuse mentioned above, the A50QS series
from the supplier Ferraz Shawmut is suggested. Please contact Delta customer
service for relevant information.
(4) The maximum tripping current of the fast-acting DC circuit breaker and/ or the
maximum melting current of the fast-acting DC fuse mentioned above are3 ~
8 times as much as the values shown in Table 5-4. These maximum values are
suggested for general applications only. For the actual maximum values, the
maximum short-circuit capacity of the on-site batteries must be taken into
consideration. Please contact Delta customer service for relevant information.
External Battery Cabinet’s Protective Device (Option 1)
Figure 5-13: Installation of a 4-pole DC Circuit Breaker or DC Isolated Switch
Connected in Series with DC Fuses
DC Fuses 4-Pole DC Circuit Breaker
or DC Isolated Switch
Delta UPS DPH 60-400/ 500/ 600 kVA 62
External Battery Cabinet’s Protective Device (Option 2)
Figure 5-14: Installation of a 3-pole DC Circuit Breaker or DC Isolated Switch
Connected in Series with DC Fuses
• Common Battery (Only for Parallel UPSs Sharing the Same External Battery
Cabinet(s))
To save on your costs and installation space, the parallel UPSs can share their
connected external battery cabinet(s). See Figure 5-15 for two parallel UPSs sharing
one external battery cabinet as an example.
NOTE:
The following ‘common battery’ information is not applicable to the UPS using
lithium-ion batteries. For relevant information, please refer to the user manual
of the lithium-ion batteries. Whether you use the lead-acid batteries or the
lithium-ion batteries, please contact Delta service personnel for any battery/
battery cabinet’s setup and configurations.
For common battery application, please install a protective device between each
parallel UPS and its connected external battery cabinet(s). You have to use the LCD to
set each UPS’s ‘Float Charge Voltage’ (default: 544V) the same, ‘Equalized Charge
Voltage’ (default: 560V) the same, ‘Battery Strings’ even and ‘Charge Current (Max)’
even. Please refer to the examples below and 7. LCD Display & Settings.
Example I
When (1) two UPSs are paralleled and share one external battery cabinet, (2) lead-acid
batteries are used, (3) the battery capacity is 200AH, (4) there are a total of 4 battery
strings, and (5) the charge current is 80A, please use the LCD to set each UPS’s
‘Battery Type’ as ‘VRLA’, ‘Capacity’ as 200AH, ‘Battery Strings’ as 2, and ‘Charge Current
(Max)’ as 40A.
DC Fuses 3-Pole DC Circuit Breaker
or DC Isolated Switch
Chapter 5 : Installation and Wiring
63
Example II
When (1) three UPSs are paralleled and share one external battery cabinet, (2) leadacid batteries are used, (3) the battery capacity is 300AH, (4) there are a total of 3
battery strings, and (5) the charge current is 90A, please use the LCD to set each
UPS’s ‘Battery Type’ as ‘VRLA’, ‘Capacity’ as 300AH, ‘Battery Strings’ as 1, and ‘Charge
Current (Max)’ as 30A.
Figure 5-15: Common Battery Diagram
• External Battery Cabinet Alarm
When any external battery cabinet connected to the UPS has the following problems,
the UPS system will sound an alarm. Please see the table below.
No. External Battery Cabinet Status Alarm
1 Battery Abnormal - Reversed It sounds 50 ms every second.
2 Battery Ground Fault It sounds 50 ms every second.
3 Battery Over Temperature It sounds 50 ms every second.
BYPAS
MAIN
Static Switch
Rectifier Inverter
BYPAS
MAIN
Static Switch
Rectifier Inverter
LOAD
Batteries
Delta UPS DPH 60-400/ 500/ 600 kVA 64
No. External Battery Cabinet Status Alarm
4 Battery Under Temperature It sounds 50 ms every second.
5 Battery Breaker Off It sounds 50 ms every 3 seconds.
6 Battery Disconnected (Missing) It sounds once every second.
7 Battery Over Charged Long beep.
8 Battery Test Fail It sounds 50 ms every second.
9 Battery End of Discharge Imminent It sounds 50 ms every second.
10 Battery End of Discharge Long beep.
11 Battery Life Time Expired It sounds 50 ms every 3 seconds.
5.7 STS Module
The hot swappable STS module has been installed in the UPS by default. Please refer
to Figure 5-16 for its location.
Figure 5-16: STS Module Location
STS Module
Chapter 5 : Installation and Wiring
65
For STS module illustration, please refer to Figure 5-17.
Figure 5-17: STS Module
5.7.1 STS Module Installation
WARNING:
1. Only qualified service personnel can perform the following STS module
installation procedures.
2. The STS module is heavy (38.0 kg (83.78 lb)). At least two people are
required for handling.
Step 1
Confirm that the STS module’s switch is in the lower position ( ) and the pullers are
in the open status.
Figure 5-18: Confirm the STS Module’s Switch in the Lower Position
LED Indicator
Lower Handle
Lock
Upper Handle
Puller
Puller
Delta UPS DPH 60-400/ 500/ 600 kVA 66
Figure 5-19: Confirm the Pullers in the Open Status
Step 2
Two people work together to insert the STS module into the designed slot. After that,
one person holds the two pullers and push the two pullers inwards in order to push
the module into the end of the UPS cabinet until it snaps into place. Now, the pullers
are all in the closed status.
Figure 5-20: Insert the STS Module into the Slot
Puller
Puller
Open Status
Handle
Puller
Puller
Handle
Chapter 5 : Installation and Wiring
67
Step 3
Re-install the four screws (removed during the STS module removal process) to firmly
fix the STS module's ear brackets on the UPS cabinet.
Figure 5-21: Fix the STS Module on the UPS Cabinet
Step 4
Turn the STS module’s switch to the upper position ( ).
Figure 5-22: Turn the STS Module’s Switch to the Upper Position
Delta UPS DPH 60-400/ 500/ 600 kVA 68
5.7.2 STS Module Removal
WARNING:
1. Only qualified service personnel can perform the following STS module
installation procedures.
2. The STS module is heavy (38.0 kg (83.78 lb)). At least two people are
required for handling.
Step 1
Turn the STS module’s switch to the lower position ( ) and wait until the STS
module’s LED indicator becomes off.
Figure 5-23: Turn the STS Module’s Switch to the Lower Position
Step 2
Remove the four screws from the STS module.
Figure 5-24: Remove the Four Screws
Chapter 5 : Installation and Wiring
69
Step 3
Pull out the STS module from the slot. When the STS module cannot be pulled out any
more, press the lock on the top side of the STS module to continuously pull out the
module from the UPS cabinet.
Figure 5-25: Remove the STS Module
Handle
Puller
Puller
Handle
Delta UPS DPH 60-400/ 500/ 600 kVA 70
5.7.3 STS Module’s LED Indicator
The STS module’s LED indicator shows its operation status. Please refer to the
following table.
Figure 5-26: Location of the STS Module’s LED Indicator
LED Indicator Description
OFF The STS module is OFF.
ON (yellow) The STS module is working in Bypass mode,
ECO mode, or energy recycle mode.
Flashing (yellow)_ on for 0.3
seconds and off for 3 seconds The STS module is abnormal.
NOTE:
In bypass mode, if you turn the STS module’s switch to the lower position
( ), the STS module will shut down, and its output and LED indicator will be
off.
LED Indicator
Chapter 5 : Installation and Wiring
71
5.8 Power Module (Optional)
The power module is optional. Each capacity is 60kVA/ 60kW.
Figure 5-27: Power Module (Optional)
Please see the table below for the power module’s packing list.
No. Item Q’ty
❶ Power Module 1 PC
❷ Ear Bracket 2 PCS
❸ M6 Screw 4 PCS
❹ M4 Screw 8 PCS
LED Indicator
Handle
Handle
Switch Fans
Delta UPS DPH 60-400/ 500/ 600 kVA 72
5.8.1 Power Module Installation
After firmly installing the UPS on the designed installation area according to the
instruction stated in 5.4 UPS Installation, continue with the following steps to install
the power module (optional) into the UPS.
WARNING:
1. Only qualified service personnel can perform the following installation
procedures.
2. The power module is heavy (36 kg (79.37 lb)). At least two people are
required for handling.
3. Please follow your UPS capacity to install the correct number of power
modules.
DPH Series
UPS Capacity 400kVA/
400kW
500kVA/
500kW
600kVA/
600kW
Power Module Q’ty 7 9 10
4. Please install the power modules from the top layer of the power module
slot to the bottom layer of the power module slot in sequence.
Step 1
Confirm that the power module’s switch is in the lower position ( ).
Figure 5-28: Confirm the Power Module’s Switch in the Lower Position
Step 2
Take out the two bracket ears, four M6 screws and eight M4 screws from the power
module’s package
Chapter 5 : Installation and Wiring
73
Step 3
Use the eight M4 screws to fix the two ear brackets on the two sides of the power
module.
Figure 5-29: Install the Two Ear Brackets
Step 4
Insert the power module into the power module slot until it snaps into place. Two
people are required.
Figure 5-30: Insert the Power Module into the Slot
Delta UPS DPH 60-400/ 500/ 600 kVA 74
Step 5
Use the four M6 screws to firmly fix the power module on the UPS cabinet.
Figure 5-31: Fix the Power Module on the UPS Cabinet
Step 6
Turn the power module’s switch to the upper position ( ).
Figure 5-32: Turn the Power Module’s Switch to the Upper Position
Chapter 5 : Installation and Wiring
75
5.8.2 Power Module Removal
WARNING:
1. Before removing any power module, make sure that the remaining power
module(s) can support the connected critical loads.
2. Only qualified service personnel can perform the following power module
removal procedures.
3. The power module is heavy (36 kg (79.37 lb)). At least two people are
required for handling.
Step 1
Turn the power module’s switch to the lower position ( ) and wait until the power
module’s LED indicator becomes off.
Figure 5-33: Turn the Power Module’s Switch to the Lower Position
Step 2
Remove the four screws from the power module.
Figure 5-34: Remove the Four Screws
Delta UPS DPH 60-400/ 500/ 600 kVA 76
Step 3
Pull out the power module from the slot (Two people are required). When the power
module cannot be pulled out any more, press the lock on the left side of the power
module to continuously pull out the module from the UPS cabinet.
Figure 5-35: Remove the Power Module
Figure 5-36: Press the Lock of the Power Module
Press the Lock
Chapter 5 : Installation and Wiring
77
5.8.3 Power Module’s LED Indicator
The power module’s LED indicator shows its operation status. Please refer to the
following table.
Figure 5-37: LED Indicator of the Power Module
LED Indicator Description
OFF The power module is OFF.
ON (green)
1. The power module is running in On-Line
mode or Battery mode.
2. The power module’s inverter starts up.
3. The power module’s PFC starts up.
Flashing (green)_ on for 2 seconds
and off for 1 second
The power module is under discharging
process.
Flashing (green)_ on for 0.3 seconds
and off for 3 seconds The power module is abnormal.
NOTE:
In online mode, if you turn the power module’s switch to the lower position
( ), the power module will shut down its output and discharge the DC BUS
voltage until the voltage reaches to a safety level. After that, the power
module’s LED indicator will be off.
LED
Delta UPS DPH 60-400/ 500/ 600 kVA 78
5.9 Installation of Rodent Shields
Table 5-8: Rodent Shields Quantity
Rodent Shields Type A B C D
Quantity 1 PC 1 PC 1 PC 1 PC
Step 1
Install the Rodent Shield A at the front bottom of the UPS and the Rodent Shield B at
the right bottom of the UPS.
Figure 5-38: Install the Rodent Shields A & B
Rodent Shield A
M4 Screw × 6 PCS
Rodent Shield B
M4 Screw × 6 PCS
Chapter 5 : Installation and Wiring
79
Step 2
Install the Rodent Shield C at the rear bottom of the UPS and the Rodent Shield D at
the left bottom of the UPS.
Figure 5-39: Install the Rodent Shields C & D
Rodent Shield C
M4 Screw × 6 PCS
Rodent Shield D
M4 Screw × 6 PCS
Delta UPS DPH 60-400/ 500/ 600 kVA 80
Chapter 6 : UPS Operation
6.1 Pre Start-up & Pre Turn-off Warnings
NOTE:
1. All LCD diagrams in the user manual are for reference only. The display is
subject to the actual status of the UPS.
2. For information about the LCD touch panel and tri-color LED indicator,
please refer to 2.8 Tri-color LED Indicator & Buzzer and 7. LCD Display &
Settings.
3. If the ON/ OFF Button ( ) does not appear on the screen, please log in
as Administrator first, and then go to → General Setting → User →
On/ Off Button Access to change the setting.
4. The external battery cabinet’s breaker (Q5) shown on the LCD is always
ON by default. To enable the detection of the Q5 status via the LCD,
please contact Delta customer service for additional configurations.
Single Unit
• Pre Start-up Warnings
1. Before UPS operation, ensure that installation and wiring have been completely
done according to 5. Installation and Wiring, and relevant precautions and
instructions have been followed. Make sure that the AC power’s voltage,
frequency, phase sequence and battery type meet the UPS’s requirements.
2. Make sure that all the switches and breakers, including every external battery
cabinet’s breaker (Q5), are in the OFF position.
3. Make sure that the UPS’s voltage difference between the Neutral (N) and
Ground ( ) is < 3V.
ON/ OFF
Button
Chapter 6 : UPS Operation
81
4. Check if all power modules are properly installed and every power module’s
switch is in the upper position ( ). Please refer to 5.8 Power Module (Optional)
for more information.
• Pre Turn-off Warnings
If you perform turn-off procedures for single unit, all power will be completely cut off.
Please make sure the critical loads connected to the UPS have already been safely
shut down before you perform the turn-off procedures.
Parallel Units
• Pre Start-up Warnings
1. You can parallel a maximum of eight UPS units.
2. For parallel units, ensure that each parallel cable (provided) is connected well.
3. Make sure that all the switches and breakers, including every external battery
cabinet’s breaker (Q5), are in the OFF position.
4. Make sure that the UPS’s voltage difference between the Neutral (N) and
Ground ( ) is < 3V.
5. Check if the wiring is correct. Ensure that the AC power’s voltage, frequency,
phase sequence and battery type meet the UPS’s requirements.
6. Check if all power modules are properly installed and every power module’s
switch is in the upper position ( ). Please refer to 5.8 Power Module (Optional)
for more information.
7. For parallel units, ensure that every operation procedure is synchronized to all
parallel UPSs.
8. For parallel application, if you just want to operate a specific UPS but not all
parallel ones, please contact service personnel.
• Pre Turn-off Warnings
1. If you want to turn off one of the parallel UPSs, please check whether the
remaining parallel units’ total capacity exceeds the total critical loads. If the
remaining parallel units’ total capacity is less than the total critical loads, all
parallel units will shut down due to overload.
2. If you perform turn-off procedures for all parallel UPSs, all power will be
completely cut off. Please make sure that the critical loads connected to the
parallel UPSs have already been safely shut down before you perform the turnoff procedures.
Delta UPS DPH 60-400/ 500/ 600 kVA 82
6.2 Start-up Procedures
6.2.1 On-Line Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
Step 4
Tap the ON/ OFF Button ( ) on the LCD screen.
Step 5
After the inverter turns on, each power module will start up and perform selfinspection. At the same time, At the same time, the system begins synchronization
with the bypass AC source. After the self-inspection is completed, the UPS will
automatically transfer to run in On-Line mode, the tri-color LED indicator will illuminate
green and the following screen will appear.
Chapter 6 : UPS Operation
83
6.2.2 Battery Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5) and output Switch (Q4).
Step 3
Press any of the BATT. START buttons on the Communication Interfaces I for one
second.
Step 4
Tap the ON/ OFF Button ( ) on the LCD screen.
Step 5
After the inverter turns on, each power module will start up and perform selfinspection and the LED indicator of the power module will illuminate green. After the
self-inspection is completed, the UPS will automatically transfer to run in Battery
mode. At this moment, the tri-color LED indicator illuminates yellow and the following
screen appears.
Delta UPS DPH 60-400/ 500/ 600 kVA 84
6.2.3 Bypass Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5).
Step 3
Switch ON the Input Switch (Q1) and Bypass Switch (Q2).
Step 4
For parallel application, please check each parallel UPS’s parallel settings. Please note
that each parallel UPS’s parallel ID No. must be different, and parallel group ID No.,
input, output and battery settings must be the same.
Step 5
For parallel application, tap the icon ( ) located in the upper left corner of the screen
and check if the parallel group ID No. and parallel ID No. of the parallel UPSs are
correct. The UPS with the smallest parallel ID No. is defined as the master unit. Please
refer to below Figure.
Parallel Group
ID No.
Parallel ID No.
Chapter 6 : UPS Operation
85
Step 6
For single unit, turn ON the Output Switch (Q4).
For parallel units, ensure that the output voltage difference between each parallel UPS
is below 3V. If larger than 3V, it is abnormal; please contact service personnel
immediately. If below 3V, turn ON each parallel UPS’s Output Switch (Q4).
Now, the tri-color LED indicator illuminates yellow and the LCD shows the following
screen.
6.2.4 Manual Bypass Mode Start-up Procedures
WARNING:
1. Before turning on/ off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions
have been followed.
2. In Manual Bypass Mode, make sure that all of the switches/ breakers
(except for Manual Bypass Switch (Q3)) are in the OFF position before
working on the UPS’s internal circuits to prevent electric shock. DO NOT
touch any external maintenance bypass cabinet’s terminal and bus bar
which may carry high-voltage electricity.
• From On-Line Mode to Manual Bypass Mode
Step 1
Tap the ON/ OFF Button ( ) on the LCD screen to shut down the inverter.
Step 2
Ensure that the UPS runs in Bypass mode. After confirmation, turn ON the Manual
Bypass Switch (Q3).
Delta UPS DPH 60-400/ 500/ 600 kVA 86
Step 3
Switch OFF the Output Switch (Q4), Input Switch (Q1) and Bypass Switch (Q2). After
that, the LCD screen shows as follows.
Step 4
When the UPS performs DC BUS discharging, each power module’s LED indicator
flashes green. After discharging, each power module’s LED indicator will be off. About
three minutes later, the UPS will shut down, and the LCD and the tri-color LED will be
off.
Step 5
Switch OFF every external battery cabinet’s breaker (Q5).
• From Manual Bypass Mode to On-Line Mode
Step 1
Switch ON every external battery cabinet’s breaker (Q5).
Step 2
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
Step 3
Switch OFF the Manual Bypass Switch (Q3).
Step 4
Tap the ON/ OFF Button ( ) on the LCD screen.
Chapter 6 : UPS Operation
87
Step 5
After the inverter turns on, the UPS will run in On-Line mode, the LCD screen will show
as below, and the tri-color LED indicator will illuminate green.
6.2.5 ECO Mode Start-up Procedures
WARNING:
Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
If the bypass input is within the normal range, the UPS will run in Bypass mode.
Delta UPS DPH 60-400/ 500/ 600 kVA 88
Step 4
Log in as Administrator. For the Administrator password, please contact service
personnel.
Step 5
Go to SETUP → Mode Setting → Select ECO.
Step 6
Tap the icon ( ) to go back to the Main Screen and tap the ON/ OFF Button ( ).
Administrator Login
Chapter 6 : UPS Operation
89
Step 7
After the inverter turns on and the system confirms that the bypass voltage is normal,
the UPS will automatically transfer to ECO mode to let the bypass supply power, the
LCD screen will show as below, and the tri-color LED indicator will illuminate green.
6.2.6 Frequency Conversion Mode Start-up Procedures
WARNING:
1. Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions
have been followed.
2. Frequency Conversion mode is only applicable to single UPS but not to
parallel UPSs.
3. When the UPS runs in Frequency Conversion mode, once the inverter
becomes off, there is no bypass power supplying to the loads.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
If the bypass input is within the normal range, the UPS will run in Bypass mode.
Delta UPS DPH 60-400/ 500/ 600 kVA 90
Step 4
Log in as Administrator. For the Administrator password, please contact service
personnel.
Step 5
Go to SETUP → Mode Setting → Select Frequency Conversion.
WARNING:
Once you select 'Frequency Conversion' mode, the UPS will run in Standby
mode and the output will be terminated.
Step 6
Tap the icon ( ) to go back to the Main Screen and tap the ON/ OFF Button ( ).
ON/ OFF
Button
Administrator Login
Chapter 6 : UPS Operation
91
Step 7
After the inverter turns on, the UPS will run in Frequency Conversion mode, the output
frequency will be the same as the setup value, the LCD screen will show as below, and
the tri-color LED indicator will illuminate green.
6.2.7 Green Mode Start-up Procedures
WARNING:
1. Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions
have been followed.
2. For parallel units, ensure that every operation procedure mentioned
below is synchronized to all parallel UPSs.
Step 1
Ensure that the Manual Bypass Switch (Q3) is in the OFF position.
Step 2
Switch ON every external battery cabinet’s breaker (Q5).
Step 3
Switch ON the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
If the bypass input is within the normal range, the UPS will run in Bypass mode.
Delta UPS DPH 60-400/ 500/ 600 kVA 92
Step 4
Log in as Administrator. For the Administrator password, please contact service
personnel.
Step 5
Go to SETUP → Mode Setting → Select Green.
Step 6
Tap the icon ( ) to go back to the Main Screen and tap the ON/ OFF Button ( ).
Step 7
Now, the UPS automatically transfers to run in Green mode and the system automatically
detects the output status (i.e. total load capacity %) to decide which specific power
module(s) should be fully powered on or idle in order to achieve higher efficiency of the
UPS. The LCD screen shows as below, and the tri-color LED indicator illuminates green.
Administrator Login
Chapter 6 : UPS Operation
93
6.2.8 Energy Recycle Mode Start-up Procedures
WARNING:
Energy Recycle mode is only applicable to single input and single unit
application.
Step 1
Ensure that the Manual Bypass Switch (Q3), Output Switch (Q4) and every external
battery cabinet’s breaker (Q5) are in the OFF position.
Step 2
Switch ON the Input Switch (Q1) and Bypass Switch (Q2).
Step 3
Log in as an Administrator. For the Administrator password, please contact service
personnel. Administrator Login
Delta UPS DPH 60-400/ 500/ 600 kVA 94
Step 4
Go to SETUP → Mode Setting → select Energy Recycle.
Step 5
Tap the icon ( ) to go back to the Main Screen and tap the ON/ OFF Button ( ).
Step 6
After the inverter turns on, the UPS will run in Energy Recycle mode and perform selfaging test. The LCD screen shows as below, and the tri-color LED indicator illuminates
yellow.
Chapter 6 : UPS Operation
95
6.3 Turn-off Procedures
6.3.1 On-Line Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Tap the ON/ OFF Button ( ) to shut down the UPS’s inverter. After that, the UPS will
let the bypass AC source supply power. At the moment, if the bypass is abnormal,
there is a risk of output interruption.
Step 2
Switch OFF the external maintenance bypass cabinet’s Input Breaker or Switch (Q1)
and Bypass Breaker or Switch (Q2). After that, the UPS will transfer to Standby mode.
Step 3
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD screen and tri-color LED indicator
will be off.
6.3.2 Battery Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Tap the ON/ OFF Button ( ) to shut down the UPS’s inverter. Note that once you turn
off the inverter, all the output power will be completely cut off, and the UPS will transfer
to Standby mode.
Step 2
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4).
Step 3
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD and tri-color LED indicator will be
off.
Delta UPS DPH 60-400/ 500/ 600 kVA 96
6.3.3 Bypass Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). After
that, the UPS will run in Standby mode.
Step 2
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD and tri-color LED indicator will be
off.
6.3.4 Manual Bypass Mode Turn-off Procedures
WARNING:
1. Ensure that the LCD, all LED indicators and fans are OFF.
2. Check that all the switches, breakers and power are OFF.
In Manual Bypass mode, the LCD and tri-color LED indicator are both OFF. To
completely shut down the UPS, switch OFF the Manual Bypass Switch (Q3).
6.3.5 ECO Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Tap the ON/ OFF Button ( ) to shut down the UPS’s inverter. After that, the UPS will
let the bypass AC source supply power. At the moment, if the bypass is abnormal,
there is a risk of output interruption.
Step 2
Log in as an Administrator. For the Administrator password, please contact service
personnel.
Chapter 6 : UPS Operation
97
Step 3
Go to SETUP → Mode Setting → On-Line.
Step 4
Switch OFF the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). After
that, the UPS will run in Standby mode.
Step 5
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD and tri-color LED indicator will be
off.
6.3.6 Frequency Conversion Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Please make sure that the critical loads connected to the UPS have already been safely
shut down. After confirmation, tap the ON/ OFF Button ( ) to shut down the UPS’s
inverter. Note that once you turn off the inverter, all the output power will be
completely cut off, and the UPS will transfer to Standby mode. Now, the power
modules keep charging the batteries.
Step 2
Switch OFF the Output Switch (Q4).
Delta UPS DPH 60-400/ 500/ 600 kVA 98
Step 3
Log in as an Administrator. For the Administrator password, please contact service
personnel.
Step 4
Go to SETUP → Mode Setting → On-Line.
Step 5
Switch OFF the Input Switch (Q1) and Bypass Switch (Q2) and the UPS will transfer
to Standby mode.
Step 6
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD and tri-color LED indicator will be
off.
6.3.7 Green Mode Turn-off Procedures
WARNING:
Before turning off the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions have
been followed.
Step 1
Please make sure that the critical loads connected to the UPS have already been safely
shut down. After confirmation, tap the ON/ OFF Button ( ) to shut down the UPS’s
inverter. After that, the UPS will let the bypass AC source supply power. At the
moment, if the bypass is abnormal, three is a risk of output interruption.
Step 2
Switch OFF the Output Switch (Q4).
Chapter 6 : UPS Operation
99
Step 3
Log in as an Administrator. For the Administrator password, please contact service
personnel.
Step 4
Go to SETUP → Mode Setting → On-Line.
Step 5
Switch OFF the Input Switch (Q1) and Bypass Switch (Q2). After that, the UPS will
run in Standby mode.
Step 6
Wait for the UPS to complete the DC BUS discharging. After that, switch OFF each
external battery cabinet's breaker (Q5), and the LCD and tri-color LED indicator will be
off.
6.3.8 Energy Recycle Mode Turn-off Procedures
WARNING:
1. Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions
have been followed.
2. Energy Recycle mode is only applicable to single input and single unit
application.
Step 1
Tap the ON/ OFF Button ( ) to shut down the UPS’s inverter. After that, the UPS will
stop self-aging test and transfer to run in Bypass mode.
Delta UPS DPH 60-400/ 500/ 600 kVA 100
Step 2
Please log in as an Administrator. For the Administrator password, please contact
service personnel.
Step 3
Go to SETUP → Mode Setting → On-Line.
Step 4
Switch OFF the Input Switch (Q1) and Bypass Switch (Q2). After that, the UPS will be
off and the LCD and tri-color LED indicator will be off.
6.4 Start-up & Turn off Procedures for Parallel Units
WARNING:
1. Before turning on the UPS, please read 6.1 Pre Start-up & Pre Turn-off
Warnings thoroughly and ensure that the precautions and instructions
have been followed.
2. Ensure that every operation procedure is synchronized to all parallel
UPSs. If you just want to operate a specific UPS but not all the parallel
ones, please contact service personnel.
• Start-up Procedures (Parallel Units)
Step 1
Ensure that each parallel cable (provided) is connected well.
Step 2
Perform the first few steps following your chosen mode’s section in 6.2 Start-up
Procedures until there is power supplying to the UPS (after switching ON Q1/ Q2 or
pressing the BATT. START button).