MODELIMPLICATION
| Model | GN30-12/400-12.5 | GN30-12/630-20 | GN30-12/1000-31.5 | GN30-12/1250-31.5 | |
| Item Data | GN30-12D/400-12.5 | GN30-12D/630-20 | GN30-12D/1000-31.5GN30-12D/1250-31.5 | ||
| RatedVoltage(KV) | 12 | ||||
| RatedCurrent(A) | 400 | 630 | 1000 | 1250 | |
| Ratedshort-timewithstandcurrent(KA) | 12.5 | 20 | 31.5 | ||
| Rated short-circuit duration(S) | 4 | ||||
| Rated peakwithstand current(KA) | 31.5 | 50 | 80 | ||
| Rated insulting level | Lightning impulse withstand voltage(KV) | Phasetophase/toearth:75、acrossopencontacts:85 | |||
| 1 min.PF withstand voltage(KV) | Phasetophase/toearth:42、acrossopencontacts:48 | ||||
OVERALLDIMENSION
| GN30-12 | GN30-12D/1250 | |||||||||||||
| 400A 630A | 1000A | 1250A | 400A 630A | 1000A | 1250A | |||||||||
| A | C | A | C | A | C | A | B | C | A | B | C | A | B | C |
| ~560 | ~315 | ~580 | ~332 | ~580 | ~295 | ~550 | ~610 | ~240 | ~575 | ~615 | ~245 | ~580 | ~600 | ~295 |
GN19-12M Inidcor High Volitahe
SPECIFICATION
GN19-12 series indoor high voltage disconnect switch belong to high voltage switch equipments, applies to power system of rated voltage 12KV, AC50Hz and less than it system, it is equipped with CS6-1 manual operating mechanism and is used to break and make circuit under no-load but withvoltage.There are additional pollution abatement type,high altitude type and electrifieddisplay.
AMBIENTCONDITION
1.Thealtitude:under1000M;
2.Theambienttemperature: -25°C-+40°C
3.Therelativehumidity of air:monthly {\lesssim}90% daily \lesssim95%
4. The wind pressure: \L\Lleftarrow700\rho_{\mathsf{A}} (withspeed 34m/s)
5.Ampitude:Earthquakedegree8;
6.Applicationoccasionsshouldfreefromfire,inflammables,
explosives,corrosivesandseverevibration.
PRODUCTFEATURE
1.Scientific and reliable design.
2. Large clearance between gaps.
3.Small operating power and steady performance.
MODELIMPLICATION
| Model | Rated Voltage(KV) | Rated Current(V) | 4sthermal stability current(Kv) | Dynamic current(KA) |
| GN19-12CM/400-12.5 | 12 | 400 | 12.5 | 31.5 |
| GN19-12CM/630-20 | 12 | 630 | 20 | 50 |
| GN19-12CM/1000-31.5 | 12 | 1000 | 31.5 | 80 |
| GN19-12CM/1250-40 | 12 | 1250 | 40 | 100 |
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
GN30-12M VeriesndsorRotaryiteHigh
SPECIFICATION
GN30-12M series rotary indoor high voltage disconnect switch is a new type of touch rotating knife type disconnect switch, the main structure in three phase chassis of the upper and lower two plat,fixed two set of insulator and contact, by rotating contactor,realizethedivideandcombinetheswitch.
GN30-12MseriesswitchisonthebasisofGN30-12switchincreaseswiththeformofearthingknife,canmeet theneeds of different power systems.This product design is compact, small footprint, insulating ability is strong,easy to install, the performancemeetGB198589<ACHighVoltageIsolatingSwitchandEarthSwitch>requirements.Also,theswitchapplicableto ratedvoltage10KVAC50HZand thefollowing indoorsystems,asinthecaseswithvoltagewithout load,foropening andclosing current.It canbeusedwithhighvoltageswitchcabinet,andalsocanbeused alone.
AMBIENTCONDITION
MODELIMPLICATION
1.Scientificdesignand innovativestructure.
2.Contacting points distribute on two planes, small operating moment, and release pressure to small and easy adjustment.
3.Improved driving and conducting part.
4. Column moving contact that can decrease operating strength and ensurereliabilityof circuit conduction.
GN30-12M
| Model | GN30-12M/400-12.5 | GN30-12M/630-20 | GN30-12M/1000-31.5 | GN30-12M/1250-31.5 | |
| Item Pecificatio | GN30-12DM/400-12.5 GN30-12DM/630-20 GN30-12DM/1000-31.5GN30-12DM/1250-31.5 | ||||
| Ratedvoltage(KV) | 12 | ||||
| Ratedcurrent(A) | 400 | 630 | 1000 | 1250 | |
| Ratedshort-timewithstandcurrent(KA) | 12.5 | 20 | 31.5 | ||
| Rated short-circuitdurations(S) | 4 | ||||
| Ratedpeakwithstand current(KA) | 31.5 50 | 80 | |||
| Rated insulating level | Lightningmpulse withstandvotage(KV) | Phasetophase/toearth:75/acrossopencontacts:85 | |||
| 1min. PF withstand voltage(KV) | Phasetophase/toearth:42/acrossopencontacts:48 | ||||
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
GNF38-12/630A Inidcor High Vwltaghe
SPECIFICATION
The GNF38-12KV series indoor isolating switch, in order to meet fixed -pressure cabinet, RMU to require a compact, compact design and manufacture of development,it has three-position structure,fully insulated bottom plate, and is equipped with a coaxial lock and perfect mechanical interlocking structure,compact size, is a compact box-type switchgear best equipped Switch.
AMBIENTCONDITION
MODELIMPLICATION
1.the altitude: Under 2000M;
2.the ambient temperature: -25°C-+40°C
3.the relative humidity of air:monthly {\lesssim}90% daily \lesssim95%
4.Application occasions should free from fire,inflammables,
explosives,corrosivesandeseverevibration.
| NO. | Item | Units | Parameters | |
| 1 | RatedVoltage | kV | 12 | |
| 2 | Ratedfrequency | Hz | 50 | |
| 3 | RatedCurrent | A | 630 | |
| 4 | Ratedshort-timewithstandcurrent(4S) | KA | 25,31.5 | |
| 5 | Ratedpeakwithstand current(KA) | KA | 63,80 | |
| 6 | Rated insulation level | 1minfrequencywithstand | kV | Phasetophase/toearth:42、acrossopencontacts:48 |
| Lightningimpulsewithstand | Phasetophase/toearth:75、acrossopencontacts:85 | |||
OVERALLDIMENSION
GN24-12D InidoorACHighiVoltage
SUMMARY
GN24-12D(III), GN24-12D(III)C series disconnect switch is an indoor electric apparatus of rated voltage 12KV, threephaseAC50Hz.
Structure
a,GN24-12D( I 1.2, Il 1.21)Q disconnect switch is dynamic or static contact side earthing type. The main and earthing knife is combination in whole frame; Type 1 is for left operation; type 2 for right operation; Q is the safe working condition product,andcanbeattachedwithelectricindicatingdevice.
b,GN24-12SD I、 Il ( C.1.2.3.) is the dynamic and static contact on both sides earthing disconnect swith, meanwhile the contact can be changed to wallbushing, the main and earthing knife is combination in the same frame, one set knife can operate independently,canalsobeoperatedbya machine at thesametime.
AMBIENTCONDITION
PRODUCTFEATURE
1. the altitude: {\lesssim}30000
2.the ambient temperature: -25°C-+40°C
3.therelativehumidityof air:monthly {\lesssim}90% daily \lesssim95%
4.ampitude:earthquakedegree8
5.Application occasions should free from inflammables,explosives,
corrosivesandseverevibration.
1.Reasonable and scientific design,innovative structure.
2.Contacting points distribute on two planes, small operation
moment,strongpressurereleasecapability,easyadjustment.
3.Improved driving and conducting parts.
4.Model implication
MODELIMPLICATION
OVERALLDIMENSION
| Size(mm) Current | 400A630A | 100A | 1250A | Mounting holespacing mm | |||||||||
| Model | A | B | C | D | A | B | C | D | A | B | C | D | |
| GN24-12DI | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | 700×300 |
| GN24-12DII | 890 | 660 | 450 | 125 | 890 | 690 | 480 | 125 | 890 | 700 | 500 | 125 | |
| GN24-12DI | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | |
| GN24-12DIIC | 890 | 660 | 450 | 240 | 890 | 690 | 480 | 350 | 890 | 700 | 500 | 350 | |
| GN24-12DI | 920 | 780 | 450 | 125 | 920 | 790 | 480 | 125 | 920 | 790 | 500 | 125 | |
| GN24-12DIC | 920 | 780 | 450 | 240 | 920 | 790 | 480 | 350 | 920 | 790 | 500 | 350 | |
GN27-40.5 VeriesIndsorHinect Switch
SPECIFICATION
GN27-40.5 indoor high voltage disconnect switch is an indoor electric apparatus used in rated voltage 35kV, three-phase AC 5012 system.It used for connect and switch the circuit with voltage without load. This disconnect switch equipped with CS6-2 manual/handle operating mechanism, D series equipped with CS6-1 manual/handleoperatingmechanism.
AMBIENTCONDITION
1. Altitude: <=slant1000m
2.Ambient temperature: -25°\;\;C^{-+40°C};
3.Relative humidity:daily average \lesssim95% monthlyaverage {\lesssim}90%
4.Earthquake intensity: \L{<=slant}8 degree;
5.Applicable occasions should free from inflammables,explosives, corrosivesandseverevibration.
6.steampressure:dailyaverage <=slant2.2^{*}10* -3MPa,monthly average <=slant1.8^{*}10 -3Mpa
PRODUCTFEATURE
1.Scientific design and innovative structure.
2.Multi contacts,rotary contacting, auto-cleaning capacity andeffectivecooling.
3.Contacting points distribute on two planes,small operating moment andgoodpressurewithstandcapacityaswell as easyofadjustment.
4.Applicable when creepage distance,insulating capacity and withstandvoltageareall on thehighest level.
5.Axletree is fabricated on the rotary axle so as to prolong lifetime of apparatus and to simplify operation.
MODELIMPLICATION
| Model | Rated voltage(KV)voltage(KV) | Max. | Rated current(A) | Ratedpeak withstandcurrent(kA) | 4sshort-time withstandcurrentKA |
| GN27-35(C)(D)/630 | 35 | 40.5 | 630 | 20 | 50 |
| GN27-35(C)(D)/1250 | 1250 | 31.5 | 80 | ||
| GN27-35(C)(D)/2000 | 2000 | 40 | 100 |
GN22-12 Series IndoorWighVoltage
SPECIFICATION
GN22-12 Disconnect switch is an indoor electric apparatus of rated voltage 12kV three-phase AC 50/60Hz. it is used to break,makeand transfer lines when theHV apparatus isunder situationswithvoltageand no-load.
AMBIENTCONDITION
MODELIMPLICATION
1.Altitude: <=slant1000m
2.Ambient temperature: -25°\;\subset-+40°\mathbb{C};
3.Relative humidity:daily average <=slant95% ,monthlyaverage {\lesssim}90%
4.Earthquake intensity: <=8 degree;
5.Applicableoccasions should freefrominflammables,explosives, corrosivesandseverevibration.
6. steam pressure: daily average ≤2.2× 10-3MPa,monthly average <=1.8x10^{-3}Mpa
PRODUCTFEATURE
1.Scientific and reliable design.
2.Large current capacity.
3.Easy maintenance and operation.
| Item | Units | Parameters | ||
| Ratedvoltage | KV | 12 | ||
| Ratedfrequency | Hz | 50 | ||
| Ratedcurrent | A | 1600-2000 2500-3150 | ||
| Ratedshort-circuitresistancecurrent | KA | 40 | 50 | |
| Ratedpeakwithstandcurrent | KA | 100 | 125 | |
| Ratedshort-circuitduration | S | 4 | ||
| Rated insulatinglevel | 1min.PFwithstandvoltage | KV | Phase to phase/to earth:42,across open contacts:49 | |
| Lightningimpulsewithstandvoltage(peak) | KV | Phase tophase/to earth:75,across opencontacts:85 | ||
| Model | A | B | C | D | E |
| GN22-12/1600-2000 | 255 | 305 | 527 | 490 | 50 |
| GN22-12/2500-3150 | 262 | 325 | 538 | 494 | 60 |
| GN22-12C/1600-2000 | 537 | 255 | 305 | 807 | 580 |
| GN22-12C/2500-3150 | 539 | 267.5 | 330 | 880 | 630 |
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
GW9 DustdooreHighVioltage
SPECIFICATION
The GW9 outdoor highvoltage disconnect switch is a type of HV electric apparatus of rated voltage 10KV,15KV,24KV,is usedtobreakandmakecircuitunderno-load.
Thisseriesdisconnect switchmeetGB1985<ACHIGH-VOLTAGEDISCONNECTORANDEARTHINGSWITCH>、 IEC60129<ACHIGH-VOLTAGEDISCONNECTORANDEARTHINGSWITCH>andGB/T1022<COMMONSPECIFICATIONS FORHIGH-VOLTAGESWITCHGEARANDCONTROLGEARSTANDARDS>etCStandardrules.
AMBIENTCONDITION
MODELIMPLICATION
1.thealtitude:Under1000M 2.theambient temperature: -30°C^{-}+40°C alpineregion, -40°C 3.Application occasions should free fromfire,inflammables, explosives,corrosivesandeseverevibration.
| Item | Units | Parameters | |||||||
| RatedVoltage | KV | 10 | 15 | 24 | |||||
| Ratedworkvoltage | KV | 12 | 17.5 | ||||||
| Rated insulation level | 1minfrequency withstand | To earth | KV | 42 | 55 | 65 | |||
| Open contacts | KV | 48 | 65 | 79 | |||||
| Lightning impulse withstand | To earth | KV | 75 | 105 | 125 | ||||
| Open contacts | KV | 85 | 120 | 145 | |||||
| Ratedfrequency | HZ | 50 | |||||||
| Ratedcurrent | A | 200 | 400 | 630 | 1250 | 400 | 630 | ||
| Rated short-time withstand current(4S) | KA | 6.3 | 12.5 | 20 | 31.5 | 16 | 20 | ||
| Ratedpeakwithstandcurrent | KA | 16 | 31.5 | 50 | 80 | 40 | 50 | ||
| Creepagedistance | mm | 300 | 380 | ||||||
| Life | Times | 2000 | 2000 | 2000 | |||||
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
GW4-12(17.5-40.5) DustdooreHighWioltage
SPECIFICATION
The GW4-12(1735/40.5) series outdoor H.V.disconnect switch is applicable device in outdoorAC 50\ \mathsf{H z}. It isusedto make,breakand transferbetweenlinesundersituationwithvoltage17.5KV/40.5KVandno-load.It ismadeasperGB1985.
AMBIENTCONDITION
MODELIMPLICATION
1.Thealtitude: <=q1000\mathsf{M}
2.The ambient temperature:-30°℃-+40°C, alpine region, ≥- 40 °C
3.Air pressure: <=700\mathsf{P a}
4.Earthquake intensity: <=8 degree;
5.Icethickness: <=q10mm
6.Application occasions should free from fire,inflammables, explosives,corrosivesandeseverevibration.
| Classification | Model | Rated voltage (KV) | Rated current (A) | Disconnectswitch | Earthingswitch | |||||
| Rated peak | Rated short circuit withstandcurrentKAwithstandcurrentKA | Ratedpeak withstandcurrentKA | Ratedshort circuit withstandcurrentKA | |||||||
| General type (anti-pollution type) | GW4 | 12 | 600~630 | 80 | 31.5(4s) | 50 | 80 | 20 (4s) | 31.5 (4s) | No earthing、 singleearthing、 doubleearthing |
| 17.5 | 400~1000 | 50 | 20(4s) | |||||||
| 40.5 | 400~1250 | 80 | 31.5(4s) | |||||||
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
GW5 VertegeutdoorACHiwitch
SPECIFICATION
GW5series outdoor disconnect switchis themost common equipments in electric system.Itsmainfunction isisolating high voltagewhentheequipmentsorcircuitdothemaintenance,toensuresafety.GW5cannotbreaktheloadcurrentandshortcircuitcurrent,needtousecooperativelywithcircuitbreaker.Whenpowercutfirstlyseparatebreakerthenseparatedisconnect switch;whenpoweronfirstlyclosedisconnect switch,thenclosebreaker.
GW5seriesoutdoor disconnect switchbelong todoublecolumnV shape,horizontalopen-type.Eachsinglestage composed of substrate,supporting insulator,outlet power,contact,etc.It fixed bytwo 50° includedanglesubstrate,supporting insulatorandtwosupportinginsulatormaketheangletoeachother,and installthebearingofsubstrate,verticalwithsubstrate. Leadingelectricpartseparateinstallonthetwosupportinginsulator,makethe 90° rotatetogetherwiththesupportinginsulator.
AMBIENTCONDITION
1.Thealtitude:under1000-3000M;
2.Theambient temperature: -30°C-+40°C coldareas -40°C
3.Windpressure \L{<=slant}8
4.Ampitude:Earthquake degree 8;
5.Applicationoccasionsshouldfreefromfire,inflammables, explosives,corrosivesandseverevibration.
6.anti-pollutiontype suitableforseriouspolluted area,but should nothasthematerialwhichcancausefire/explode.
PRODUCTFEATURE
1.Complete inspecifications,hightechnicalparameters ishigh, widerange.Additional,widescopeofapplication,itcanbe usedforhighlayout.Installationwayisflexible.
2.PerfectsealingPerformanceand ResistantToRust
3.Simple,reliablemechanical rotating way.
4.Perfect dustproof, waterproof,and anti-corrosion ability.
5.Full set of steel galvanized foundationframe and thevertical andhorizontaldwangforoption.
MODELIMPLICATION
| Ratedvoltage(KV) | A | A1 | H | E | C | D |
| 40.5 | 1200 | 1075 | 1070 | 1400 | 240 | 300 |
| 72.5 | 1600 | 1285 | 1295 | 2200 | 240 | 300 |
| 123 | 2000 | 1660 | 1695 | 3000 | 240 | 300 |
OVERALLDIMENSION
Boxd BOXCTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
LW8-40.5 Outaforriltteaer
SPECIFICATION
LW8-40.5outdoorhighvoltageSF6circuitbreakerisathree-phaseAC 50\mathsf{H}z outdoorhigh-voltageelectricalequipment for control and protection of 35kVtransmissionand distribution systems,and can alsobe used to open and close contact breakerandcapacitorbanksoccasions.
LW8-40.5-breakerequippedwithCT14springoperatingmechanism.
Breakerin linewith national GB1984-89"AChighvoltage circuit breakers"and the International.
AMBIENTCONDITION
MODELIMPLICATION
1.Thealtitude:1000M-3000M
2.Theambient temperature: -30°C-+40°C alpineregion,≥- 40°C
3.Wind pressure:8degree;
4.Earthquake intensity: <=8 degree;
5.Flexible mounting site should not seriouslyaffect the isolation switch insulation and conductivity of gases,vapors,chemical deposition, salt spray,dust and other explosive,corrosive substances;
6.Applies to serious contamination and pollution prevention areas,but should not havecaused a fire and explosionand other substances;
| Item | Units | Parameters | |
| Ratedvoltage | KV | 40.5 | |
| Ratedinsulationlevel | 1minpowerwithstandvoltage | KV | 95 |
| Lightning impulsewithstandvoltage | KV | 185 | |
| Rated current | A | 1600/2000 | |
| Machanicallife | Time | 3000 | |
| SF6gasratedpressure(when20°℃thegaugepressure) | Mpa | 0.45 | |
| Closurepressure(when20°C thegaugepressure) | Mpa | 0.42 | |
| Thelowesttemperature | -30 | ||
| Rated short-circuit breaking current | KA | 20/25/31.5 | |
| Rated short-circuitclosing current(peak) | KA | 50/63/80 | |
| Rated shorttimewithstandcurrent(thermalcurrent) | KA | 20/25/31.5 | |
| Ratedpeakwithstandcurrent(dynamiccurrent) | KA | 63/80/100 | |
| Ratedoutofstepbreakingcurrent | KA | 63/80/100 | |
| Ratedshortduration | S | 4 | |
| Closing time(rated operatingvoltage) | S | ≤0.1 | |
| Operatingtime(ratedoperatingvoltage) | S | ≤0.07 | |
| Rated operating sequence | 0-0.3s-C0-180s-CO | ||
| Ratedcurrentopeningandclosingofasinglecapacitorcombination | A | 400 | |
| WeightofSF6 | kg | 8/5 | |
| Circuitbreakerweight(includingtheoperatingmechanism) | kg | 1400/1000 | |
OVERALLDIMENSION
FKN12-12RD SeriesIndoorHighVoltageAir-BlastTypeLoad BreakSwitch-FuseCombinationApparatus
SPECIFICATION
FKN12A-12DSeriesair-blast loadbreakswitch andFKRN12A-12Dseriesair-blast loadbreakswitch-fusecombination apparatusarenewseriesswitchgear appliesto three-phaseelectricdistributionsystemofrated12KV,actingasprotecting and controlapparatusfortransformers,cableandoverheadwiring.Theseseriesareespeciallyapplicableinrural,urbanterminal substationandprefabricatedsubstations,aswell asringnetworkpowersupply.
FKN12A-12DSeries air-blast load breakswitchcanbreakandmake load current and over-current. FKRN12A-12DSeriesair-blast load break switchcanbreak andmakeover-current,loadcurrentandshort-circuit current(limitedcurrentfuse).
This product is featured with impact structure, aesthetic appearance reliable interlock and high insulating level. In the spring storage operating mechanism,ON/OFFspeed is free from the influence of the manpower.For the arc-extinguish electric arcextinguish inside the insulating cover,thefree gas occurs at sparking donot causedescend of insulating levelbetween phases andphasetoearth.Theinsulating coverclapboard separates electrifiedpart thusboost protectiongrade of ring mainunit.The copper-tungsten contact and main contact brings alongreliableconductivity and long life.Thisproduct achievessound fame due toeasy maintenance and operations aswell asreliableperformance.It is in compliancewithper IEC62271-105.
AMBIENTCONDITION
1.Ambient temperature -25°C-+40°C
2.Elevation <=slant 1000m
3.Humidity:dailyaverage humidity \lesssim95% monthly {\lesssim}90%
4.The earthquake does not exceed degree8
5. No fire, explosion, chemical errosion.
6.Pollution: level 2
FKN12-12RD
SeriesIndoor HighVoltageAir-Blast Type Load BreakSwitch-Fuse Combination Apparatus
TECHNICALSPECIFICATION
OVERALLDIMENSION
| Size(MM) Model | A | H | C | D | E | F | K | J | L M | N | P | R | S | T | D | W | Z | Weight | |
| FKN12A-12D | 390 | 940 | 600 | 210 | 648 | 270 | 67 | 50 | 155 | 287 | 171 368 | 11 | 337 | 170 | 94 | 105 | 868 | 18070kg |
FZN25-12D
SeriesIndoorHighVoltage VacuumLoadSwitch
SPECIFICATION
FZN25,FZRN25 type vacuum load switch and composite apparatus,suitable for three-phase AC 501-12 ringnetworkor terminal power supplyand industrial electricalequipment,forload control and short circuit protection use,load switch open and close the closed loop current,no-load transformer and cable charging current,composite apparatus can break any current till rated short circuit current.Adopt the straight move orisolating fracture andvacuum interrupter linkage.Withfunction of manual andelectricoperation.
FZN25,FZRN25 special transmission structure design, arc extinguish chamber only withstand voltage in the moment of closingandbreaking,smallsize,Lightweight.
FZN25,FZRN25canrealize isolation fracture and arcextinguish chamber fracture disposable operating.
FZN25, FZRN25 has a grounding switch mutual linkage grounding valve between the static contact and mova conductive cylinder,ensuressafety andconvenientmaintenance.
AMBIENTCONDITION
1.Theambienttemperature: -25°C-+40°C ,alpine region, \gtrsim-40°C
2. The altitude: <=10000
3.Relativehumidity:dailyaveragevalue isnot greaterthan 95% monthlyaverageisnotgreaterthan 90%
4.Earthquakeintensity: {\lesssim}8 degree;
5.The surrounding air is not corrosive and flammable gas, steam and other significant pollution;
6.Contaminationgrade:ll class;
| NO. | Item | Units | Parameters FZRN25-12D/T125-31.5 | ||
| FZN25-12D/T630-20 | |||||
| 1 Rated voltage | KA | 12 | |||
| 2 | Rated frequency | HZ | 50 | ||
| 3 | Rated Current | A | 630 125 | ||
| 4 | Rated insulationlevel | 1min frequency voltage | KV | InterruptrFracture30.onthegroundwhite42solationFractur48 | |
| Lightningimpulsewithstandvoltage | KV | Ontheground,white75solationFracture85 | |||
| 5 | Rated dynamicstability current(peak) | KA | 50 | 一 | |
| 6 | 4Sthermalcurrent | KA | 20 | 一 | |
| 7 | Ratedactiveloadbreakingcurrent | A | 630 | 125 | |
| 8 | Ratedclosed-Loopbreakingcurrent | A | 630 | 125 | |
| 9 | Ratedcablechargingbreakingcurrent | A | 10 | 10 | |
| 10 | Breakingloadtransformer | KV | 1250 | 1250 | |
| 11 | Ratedshort-circuitbreaking current | KA | 一 | 31.5 | |
| 12 | Ratedtransfercurrent,ratedcurrenttransfer | A | 一 | 2000 | |
| 13 | Fuse Model | SDLAJ-12SFLAJ-12 | |||
| 14 | Impactenergyoutput | J | 2-5 | ||
| 15 | Ratedshortcircuit makingcurrent | KA | 50 | ||
| 16 | GroundswitchratedDynamiccurrent | KA | 50 | ||
| 17 | Groundingswitch2Sthermalcurrent | KA | 20 | ||
| 18 | SecondarycircuitRatedvoltage | V | AC/CD220;110 | ||
| 19 | Mechanical life | Times | 1000 | ||
FN7-12 SeriehdrinationApparatus
SPECIFICATION
FN7-12DRModel IndoorAC HV LoadSwitch is suitable in50Hz,rated voltage of 12Kv the three-phase AC power system asthebreaking load short-circuit current of thepowerand used the Closing,until the combination of electrical short-circuit currentcanbebreakinganycurrentcanbeusedasprotectionpurposes.
| Ratedvoltage(KV) | 12 | ||
| Insulationlevel | 1minfrequencyvoltage(KV) | Phasetophase、toearth42 | lsolationfracture48 |
| Lightningimpulse withstandvoltageOkV | Phasetophase、toearth75 | lsolationfracture85 | |
| Rated current(A) | 400 | 630 | |
| 4SRatedthermalcurrent(KA) | 12.5 | 20 | |
| RatedactiveloadbreakingcurrentKA(Peak) | 31.5 | 50 | |
| Ratedshortcircuitmakingcurrent(KApeak) | 31.5 | 50 | |
FN7-12
TECHNICALSPECIFICATION
| NameModels | DS DX | R | RA | F | Jse | |||
| Groundingswitch incomingfedderside | Groundingswitch outgoingfedderside | Interlockdevice | Fuse | Impactfuse | Electricsub- gatedevices | |||
| Switches Load | FN7-12 | switch | ||||||
| FN7-12DSL | ||||||||
| fuse FN7-12DXL | △ | △ | peol Line | |||||
| impact FN7-12R | ||||||||
| Non FN7-12DSLR | △ | △ | Protection | |||||
| FN7-12DXLR | △ | Transformer | ||||||
| FN7-12RAF | △ | △ | ||||||
| FN7-12DSLRAF | Transformer Protection | |||||||
| impactfuse FN7-12DXLRAF | △ | △ | △ | △ | ||||
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
FN5-12 SewiendusrAcHihViotageLradBreak
SPECIFICATION
FN5-12R(L) model indoor AC HV load break switch-fuse combination apparatus is developed and designed based on international technology and national power supplyrequirement, it passed alltype tests and trial-operation inspections.The apparatuSconforms toIEC420:ACLOADBREAKSWITCHANDFUSECOMBINATIONAPPARATUS(1990EDITION)and GB3804:3-63KVACHVLOADBREAKSWITCHVOLUMEANDLIGHT WEIGHT.Compared to international product it keeps upwith technical level with small volume and light weight.It is applicable inring main unit and prefabricated substations as well as 12kv line and power distribution system.The product realizes three working positions: power making,power breaking and earth.It applies topower system of rated voltage 6-12kv,50/60HZ breaking load current ober load current and short-circuit current.
AMBIENTCONDITION
MODELIMPLICATION
1.The altitude:under 1000M;
2.The ambient temperature: -25°C-+40°C
3.Therelativehumidity of air:monthly {\lesssim}90% daily \Lleftarrow95%
4.Ampitude:Earthquake degree 8;
5.Application occasions should free from fire,inflammables,
explosives,corrosivesandseverevibration.
FN5-12
Series IndoorACHighVoltage Load Break Switch-Fuse Combination Apparatus
TECHNICALSPECIFICATION
| Rated voltageKV | 1min frequency voltage KV | Rated CurrentA | 4Sthermal currentA | Dynamic current (peak)KA | Rated breaking currentA | Shortcircuit closecurrent KA |
| 12 | 42 | 400 | 12.5 | 31.5 | 400 | 31.5 |
| 48 | 630 | 20 | 50 | 630 | 50 |
OVERALLDIMENSION
Left side: Load switch and
CS6-10 operating mechanism drawing
1.Loadswitch
2.Bend connection
3.3/4""Welded steel pipe”
4.Operating mechanism
IndoorAChighvoltageload switch
1.Bottombase 2.lnsulator
3.Fuse 4.Tripper gear
5.Movable contact
6.Arc-extinguishing tube
7.Guidance piece 8.Staticcontact
9.Switching mechanism
10.lnterlocking apparatus
11.Load switch operating mechanism
12.Earthing switch
| Model | Ratedvoltage(KV) | Rated current(A) | Fondant rated current(A) |
| SDLA*J | 12 | 50 | 6.3,1016,20,25,31,5,40, |
| SFLA*J | 12 | 100 | 50,63,71,80,100 |
| SKLA*J | 12 | 125 | 125 |
Boxd BOXCTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
JN15 Sertes IndartriAg Hivitch
SPECIFICATION
JN15-12series indoor highvoltage(HV)earthing switch absorbs advanced new technical from domestic and abroad.It confirmstoGB1985-89<ACHVDISCONNECTSWITCHANDEARTHSWITCH>,relative standardsIEC129 andpassKEMA test.The apparatus applies topower system of rating below 12kv,and AC 50/60Hz.It is suitablefor varioustypes HV switchgearforearthingprotection.Theholisticearthingswitchconsistsof basis,supportinginsulatormainaxismainbladefast spring,fixed and moving contact.Additional electronicdisplay is also availableaccording to theusers’s requirement.
AMBIENTCONDITION
MODELIMPLICATION
1. Altitude: <=slant1000m
2.Ambient temperature: -10°C^{-}+40°C
3.Humidity:dailyaverage humidity \lesssim95% monthly {\lesssim}90%
4.Earthquake doesnot exceed degree8;
5.No fire,explosion, chemical erosion.
PRODUCTFEATURE
1.Advanceddesignandsteadyperformance.
2.Simple structures,simplemounting and adjustment.
3.Quick breaking and making capability.
4.Handsome appearance and delicate manufacture technical.
5.Usable andscientific,availableoperation onboth two sides
(rightandleft).
| Item | Units | Parameters | ||
| Ratedvoltage | kV | 12 | ||
| Ratedshort-timewithstandcurrent | kV | 31.5 | ||
| Ratedshort-circuitduration | S | 4 | ||
| Ratedcircuit-timemakingcurrent | KA | 80 | ||
| Ratedpeakwithstandcurrent | KA | 80 | ||
| Centraldistancebetweenpoles | mm | 150,210,275 | ||
| Ratedinsultinglevel | 1min.PFwithstandvoltage | kV | Toearth,phasetophase/fracture | 42/48 42/48 |
| Lightingimpulsewithstandvoltage | ||||
OVERALLDIMENSION
| Model | L | E | C |
| JN15-12/31.5-210 | 655 | 210 | 516 |
| JN15-12/31.5-230 | 710 | 230 | 556 |
| JN15-12/31.5-250 | 760 | 250 | 596 |
| JN15-12/31.5-275 | 810 | 275 | 646 |
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
JN15-24/31.5 Herielntager Earthing Switch
SPECIFICATION
JN15-24/31.5indoorAVHVearthingswitch isthenewearthingswitchourBoxdcompanyresearchanddeveloped.It has the advanced design, simple and compact structure,reliable technicalperformance,etc.It according withGB 1985-2004AC HV disconnect switch and earthing switch,relative standards IEC62271-102: 2002.The apparatus applies to power system of rating below 24kV,and AC 50/60 Hz. It has short-circuit making capacity to protect other electrical equipment in the switching equipment,and alsobeused forearthing protectionwhen overhauling high-voltage electrical apparatus.
AMBIENTCONDITION
MODELIMPLICATION
1. Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:daily average humidity <=slant 95%,monthly {\lesssim}90%
4.Earthquake does not exceed degree 8;
5.No fire,explosion, chemical erosion;
6.Pollution:level 2.
PRODUCTFEATURE
1. Altitude less than 1000m.
2.Ambient air temperature:up to + 40 °C ,thelowerlimitof -25degree
3.The daily average relativehumidity of 95% is not dry, on average less than 90%
4. Filthy rating: Il.
| NO. | Item | Units | Parameters | ||
| 1 | Ratedcurrent | KA | 24 | ||
| 2 | Ratedshort-timewithstandcurrent | KA | 31.5 | ||
| 3 | Ratedcircuit-timemakingcurrent | KA | 80 | ||
| 4 | Ratedpeakwithstandcurrent | KA | 80 | ||
| 5 | Ratedshort-circuitduration | S | 4 | ||
| 6 | Ratedinsultinglevel | 1min.PFwithstandvoltage | kV | To earth, Phasetophase | 65 |
| Lightingimpulsewithstandvoltage | 125 | ||||
| 7 | Mechanicallife | 次 | 2000 | ||
OVERALLDIMENSION
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
JN22B-40.5/31.5 SertasgIndarthing Hiwitch
SPECIFICATION
JN22B-40.5/31.5seriesindoorhighvoltage(HV)earthingswitchabsorbsadvancednewtechnicalfromdomesticand abroad.It confirmsto GB1985-2004<AC HV DISCONNECT SWITCHAND EARTH SWITCH> standard.And applies to threephase rated voltage 405kV,AC50/60Hz power system.It can support the use of KYN61-405 HV switch panel and other models,thefoundationisprotect theHVelectricequipmentswhenrepairormaintenance.JYN22-40.5/31.5seriesHVearthing switch isrevised and update on thebase of the abovemodel, its structure ismore simple and compact,best performance and easy operate with smallangle.It is same with JN15-12, the connect and driving medium are in common use.
AMBIENTCONDITION
MODELIMPLICATION
1.Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:dailyaveragehumidity \lesssim95% monthly {\lesssim}90%
4.Earthquake does not exceed degree8;
5.No fire,explosion, chemical erosion.
OVERALLDIMENSION
MOUNTINGCUTOUTFIGURE
| Model | E | G | L | D |
| JN22B-40.5/31.5-280 | 280 | 290 | 1010 | 656 |
| JN22B-40.5/31.5-300 | 300 | 340 | 1100 | 696 |
| JN22B-40.5/31.5-350 | 350 | 340 | 1200 | 796 |
| JN22B-40.5/31.5-360 | 360 | 320 | 1200 | 816 |
| JN22B-40.5/31.5-400 | 400 | 340 | 1300 | 896 |
Boxd BOXDTRIC HIGHVOLTAGETOCREATE HIGH-PERFORMANCE
JN22-40.5/31.5 Sertag Indartring Hivitch
SPECIFICATION
JN22B-40.5/31.5 series indoor high voltage(HV) earthing switch absorbs advanced new technical from domestic and abroad. It confirms to GB1985-2004 <AC HV DISCONNECT SWITCH AND EARTH SWITCH> standard. And applies to threephase rated voltage 405kV, AC50/60Hz power system. It can support the use of KYN61-405 HV switch panel and other models, the foundation is protect the HV electric equipments when repair or maintenance.
AMBIENTCONDITION
MODELIMPLICATION
1. Altitude: <=slant1000m
2.Ambient temperature: -25°C-+40°C
3.Humidity:dailyaveragehumidity \lesssim95% monthly {\lesssim}90%
4.Earthquake does not exceed degree8;
5.No fire,explosion, chemical erosion.
TECHNICALSPECIFICATION
| NO. | Item | Units | Parameters | ||
| 1 | Ratedvoltage | kV | 40.5 | ||
| 2 | Ratedshort-timewithstandcurrent | KA | 31.5 | ||
| 3 | Ratedcircuit-timemakingcurrent | KA | 80 | ||
| 4 | Ratedpeakwithstandcurrent | KA | 80 | ||
| 5 | Ratedshort-circuitduration | S | 300、350、400 | ||
| 6 | Rated insultinglevel | 1min.PFwithstandvoltage | kV | 95 To earth, phasetophase | |
| Lightingimpulsewithstandvoltage | 185 | ||||
OVERALLDIMENSION
MOUNTINGCUTOUTFIGURE
| Model | E | G | L | D |
| JN22-40.5/31.5-280 | 280 | 290 | 1010 | 656 |
| JN22-40.5/31.5-300 | 300 | 340 | 1100 | 696 |
| JN22-40.5/31.5-350 | 350 | 340 | 1200 | 796 |
| JN22-40.5/31.5-360 | 360 | 320 | 1200 | 816 |
| JN22-40.5/31.5-400 | 400 | 340 | 1300 | 896 |
SPECIFICATION
This products can be used in indoor system of 50Hz and rated voltage of 12KV, 24KV, 36KV.it can be used together with other switch facilities such as loading switches, vacuum contactors. lt can protect electric transformers and other electric facilities against overload orcircuit breaker.It is also a necessary qeuipment for high voltage switch box,circular circuit cabinet high/lowvoltagetop-loading transformersubstation.
MODELIMPLICATION
| Type | Counterpart | Rated voltage | Ratedcurrent ofthefuse(A) | Ratedcurrent ofthefuselink(A) |
| XRNT-12 | SDLAJ | 12 | 40 | 3.15、6.3、10、16、20、25、31.5、40 |
| XRNT-12 | SDLAJ | 12 | 100 | 50、63、71、80、100、(125) |
| XRNT-12 | SDLAJ | 12 | 125 | 125、160、200、250 |
| XRNT-24 | 24 | 200 | 3.15、6.3、10、16、20、25、31.5、40、50、 63、80、100、125、160、200 | |
| XRNT-40.5 | 40.5 | 125 | 80、100、125、160、2003.15、6.3、10、16、 20、25、31.5、40、50、63、 |
12KV-15KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) (BIL) | Impulse voltage withstand | Power frequency | Creepage distance (KG) (MM) | Weight | Dimension (CM) |
| RH-33 | 15 | 100 | 10000 | 100 | voltage 40 | 250 | 7.5 | 40×34.5 |
| RH-33 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 | ×11 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (KG) (MM) | Weight | Dimension (CM) |
| Rw10 | 15 | 100 | 10000 | 100 | voltage 40 | 250 | 7.5 | 48×34.5× |
| Rw10 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 | 11 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RD-24 | 24 | 100 | 8000 | 150 | 65 | 530 | 12 | 48×34.5× |
| RD-24 | 24 | 200 | 10000 | 150 | 65 | 530 | 12 | 14 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage withstand (BIL) | Power frequency | Creepage distance | Weight | Dimension (KG) (CM) |
| RH-C | 11 | 100 | 10000 | 110 | voltage 40 | (MM) 250 | 7.5 | 40×34.5 ×11 |
| RH-C | 11 | 200 | 12000 | 110 | 40 | 250 | 7.5 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) (BIL) | Impulse voltage | Power frequency withstand | Creepage distance (KG) | Weight | Dimension (CM) |
| PD | 11 | 100 | 6000 | 110 | voltage 42 | (MM) 340 | 7.5 | 49×27 X11.5 |
| PD | 11 | 200 | 8000 | 110 | 42 | 340 | 7.5 |
12KV-15KV
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| FSC-23 | 33 | 100 | 8000 | 170 | voltage 70 | 820 | 27.5 | 68×17 ×15 |
| FSC-23 | 33 | 200 | 10000 | 170 | 70 | 820 | 27.5 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW11 | 12 | 100 | 6300 | 100 | 42 | 230 | 7.8 | 48×12× 31 |
| RW11 | 12 | 200 | 8000 | 110 | 42 | 230 | 7.8 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| Rw10 | 15 | 100 | 10000 | 100 | 40 | 250 | 7.5 | 48×34.5× 11 |
| Rw10 | 15 | 200 | 12000 | 110 | 40 | 250 | 7.5 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| Rw10-10F | 12 | 100 | 6300 | 110 | voltage 42 | 260 | 7.5 | 53×32× 12 |
| Rw10-10F | 12 | 200 | 8000 | 110 | 42 | 260 | 7.5 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW3 | 10 | 100 | 6300 | 100 | voltage 42 | 230 | 6.2 | 48×27× 12 |
| RW3 | 10 | 200 | 8000 | 110 | 42 | 230 | 6.2 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage withstand (BIL) | Power frequency | Creepage distance (KG) (MM) | Weight | Dimension (CM) |
| HRW11 | 12 | 100 | 6300 | 100 | voltage 42 | 350 | 3.8 | 42×35× 11 |
| HRW11 | 12 | 200 | 8000 | 110 | 42 | 350 | 3.8 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency distance withstand | Creepage (MM) | Weight (KG) | Dimension (CM) |
| SHY5WS | 3 | 100 | 6300 | 100 | voltage 42 | 350 | 3.8 | 42×35× 11 |
| SHY5WS | 9 | 100 | 8000 | 110 | 42 | 350 | 3.8 | |
| SHY5WS | 10 | 150 | 6300 | 100 | 42 | 350 | 3.8 | |
| SHY5WS | 10 | 150 | 8000 | 110 | 42 | 350 | 3.8 |
| Item | Rated voltage (KV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power frequency withstand voltage | Creepage distance (MM) | Weight (KG) | Dimension (CM) |
| RW7 | 10 | 100 | 6300 | 110 | 42 | 230 | 6.2 | 48×27× |
| RW7 | 10 | 200 | 8000 | 110 | 42 | 230 | 6.2 | 12 |
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Lightning impulse current peak value(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | |
| Low voltage | HY1.5W-0.28/1.3 | 0.25 | 0.22 | 0.24 | than(kv) 0.6 | 1.30 | 50 | 25 | 50 | |
| HY1.5W-0.5/2.6 | 0.50 | 0.38 | 0.42 | 1.20 | 2.60 | |||||
| HY1.5W-0.8/3.9 | 0.8 | 0.66 | 0.72 | 1.80 | 3.90 |
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue e(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Capacitance | HY0.1W-14R | 1.4 | 1.14 | 1.20 | 2.6 | 9.45 | 6.85 | 3.85 | 250 | 40 | 50 |
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | impulse current | LightingOperating impulse current | |||||||||
| Power distribution (S) | HY5WS-3.8/15 | 3.8 | 3 | 2.0 | 7.5 | 17.3 | 15.0 | 12.8 | 75 | 40 | 50 |
| HY5WS-5/15 | 5 | 3 | 4.0 | 7.5 | 17.3 | 15.0 | 12.8 | ||||
| HY5WS-7.6/30 | 7.6 | の | 4.0 | 15.0 | 34.6 | 30.0 | 25.6 | ||||
| HY5WS-10/30 | 10 | 6 | 8.0 | 15.0 | 34.6 | 30.0 25.6 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | HY5WZ-3.8/13.5 | 3.8 | (kV) 3 | 2.0 | 7.2 | 15.5 | 13.5 | 11.5 | 150 | 40 | 50 |
| HY5WZ-5/13.5 | 5 | 3 | 4.0 | 7.2 | 15.5 | 13.5 | 11.5 | ||||
| HY5WZ-7.6/27 | 7.6 | 6 | 4.0 | 14.4 | 31.0 | 27.0 | 23.0 | ||||
| HY5WZ-10/327 | 10 | 9 | 8.0 | 14.4 | 31.0 | 27.0 23.0 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power distribution (S) | HY5WS-12.7/50 | 12.7 | (kV) 10 | 6.6 | 25 | 57.5 | 50 | 42.5 | 75 | 40 | 50 |
| HY5WS-16.5/50 | 16.5 | 10 | 12.7 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17/50 | 17 | 10 | 13.6 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17.5/50 | 17.5 | 10 | 13.6 | 25 | 57.5 | 50 42.5 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | HY5WZ-12.7/45 | 12.7 | 10 | 6.6 | 24 | 51.8 | 45 | 38.3 | 150 | 40 | 50 |
| HY5WZ-16.5/45 | 16.5 | 10 | 12.7 | 24 | 51.8 | 45 | 38.3 | ||||
| HY5WZ-17/45 | 17 | 10 | 13.6 | 24 | 51.8 | 45 | 38.3 | ||||
| Using area | Product model | Rating voltage virtual value | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | impulse current | LightingOperating impulse current | |||||||||
| Electric rotating machinery | HY2.5W-3.8(5)/9.5 | (kv) 3.8(5) | (kV) | 2.0(3.0) | than(kv) 5.7 | 10.7 | 9.5 | 7.6 | 40 | ||
| HY2.5W-7.6(8)19.0 | 7.6(8) | 4.0(6.3) | 11.2 | 21.0 | 19.0 | 15.0 | |||||
| The motor neutral point | HY1.5W-2.4/6 | 2.4 | 1.9 | 3.4 | 6.0 | 5.0 | 200 | 40 | 50 | ||
| HY1.5W-4.8/12 | 4.8 | 3.8 | 6.8 | 12.0 | 10.0 | ||||||
| Capacitor (R) | HY5WR-3.8(5)/13.5 | 3.8(5) | 3 | 2.0(4.0) | 7.2 | 13.5 | 10.5 | 400 | 65 | ||
| HY5WR-7.6(10)/27.0 | 7.6(10) | 6 | 4.0(8.0) | 14.4 | 27.0 | 20.8 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u | Max.leaking current simpulse under current 0.75DCref. peak value(kA) voltage (uA) | ||
| Teep wave impulse current | Lighting Operating impulse impulse current current | ||||||||||
| Capacitor (R) | HY5WR-12.7/45 | 12.7 | (kV) 10 | 6.6 | than(kv) 23.0 | 45.0 | 35.0 | 400 | 65 | 50 | |
| HY5WR-16.5/45 | 16.5 | 10 | 12.7 | 23.0 | 45.0 | 35.0 | |||||
| HY5WR-17/45 | 17 | 10 | 13.6 | 24 | 45.0 | 35.0 | |||||
| Electric rotating machinery | HY2.5W-12.7/31.0 | 12.7 | 10.5 | 18.9 | 34.7 | 31.0 | 25.0 | 200 | 40 | ||
| HY2.5W-17.5/40.0 | 14.5 | 13.8 | 24.4 | 44.8 | 40.0 | 32.0 | |||||
| HY2.5W-20.0/45.0 | 20.0 | 15.8 | 28.0 | 50.4 | 45.0 | 36.0 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | |||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | ||||||||||
| Power distribution (S) | HY5WS-3.8/15L | 3.8 | (kV) 3 | 2.0 | than(kv) 7.5 | 17.3 | 15.0 | 12.8 | 75 | 40 | 50 | |
| HY5WS-5/15L | 5 | 3 | 4.0 | 7.5 | 17.3 | 15.0 | 12.8 | |||||
| HY5WS-7.6/30L | 7.6 | 9 | 4.0 | 15.0 | 34.6 | 30.0 | 25.6 | |||||
| HY5WS-10/30L | 10 | 9 | 8.0 | 15.0 | 34.6 | 30.0 | 25.6 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless than(kv) | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power distribution (S) | HY5WS-12.7/50L | 12.7 | 10 | 6.6 | 25 | 57.5 | 50 | 42.5 | 75 | 40 | 50 |
| HY5WS-16.5/50L | 16.5 | 10 | 12.7 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17/50L | 17 | 10 | 13.6 | 25 | 57.5 | 50 | 42.5 | ||||
| HY5WS-17.5/50L | 17.5 | 10 | 13.6 | 25 | 57.5 | 50 42.5 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | HY5WZ-42/134 | 42 | (kV) 35 | 23 | than(kv) 73 | 154 | 134 | 114 | 150 | 65 | 50 |
| HY5WZ-51/134 | 51 | 35 | 40.8 | 73 | 154 | 134 | 114 | ||||
| HY5WZ-52.7/134 | 52.7 | 35 | 40.8 | 73 | 154 | 134 | 114 | ||||
| HY5WZ-54/134 | 54 | 35 | 41 | 73 | 154 | 134 114 | |||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | impulse current | Lighting Operating impulse current | |||||||||
| Power station (Z) | HY5W-75/215 | 75 | (kV) 66 | 60 | than(kv) 123 | 248 | 215 | 183 | 400 | 65 | 50 |
| HY5W-90/224 | 90 | 66 | 72.5 | 130 | 258 | 224 | 190 | ||||
| HY10W-75/250 | 75 | 66 | 60 | 127 | 288 | 250 | 213 190 | 600 | 100 | 50 | |
| HY10W-75/223 HY10W-75/230 | 75 75 | 66 | 60 | 127 | 256 | 223 | |||||
| 66 | 60 | 127 | 265 230 | 196 | |||||||
| HY10W-90/224 | 90 | 66 | 72.5 | 130 | 258 | 224 190 | |||||
| HY10W-90/232 | 90 | 66 | 72.5 | 130 | 266 | 232 198 | |||||
| HY10W-90/235 | 90 | 66 | 72.5 | 130 | 270 | 235 | 201 | ||||
YHW-110KV
| Using area | Product model | Rating voltage virtual value (kv) | System nomina voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5W-100/260 | 100 | (kV) 110 | 78 | than(kv) 145 | 299 | 260 | 221 | 400 | 65 | 50 |
| YH5W-102/266 | 102 | 110 | 79.6 | 148 | 305 | 266 | 226 | ||||
| YH5W-108/281 | 108 | 110 | 84 | 157 | 323 | 281 | 239 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000u square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH10W-100/260 | 100 | (kV) 110 | 78 | than(kv) 145 | 291 | 260 | 221 | 600 | 100 | 50 |
| YH10W-102/266 | 102 | 110 | 79.6 | 148 | 297 | 266 | 226 | ||||
| YH10W-108/281 | 108 | 110 | 84 | 157 | 315 | 281 | 239 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value (kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH10W-200/520 | 200 | (kV) 220 | 156 | than(kv) 290 | 582 | 520 | 442 | 600 | 100 | 50 |
| YH10W-204/532 | 204 | 220 | 159 | 296 | 594 | 532 | 452 | ||||
| YH10W-216/562 | 216 | 220 | 168.5 | 314 | 630 | 562 | 478 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value(kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5WX1-51/134L | 51 | (kV) 35 | 40.8 | than(kv) 73 | 154 | 134 | 114 | 400 | 100 | 50 |
| YH5WX1-54/142L | 54 | 35 | 43.2 | 77 | 163 | 142 | 121 | ||||
| YH5WX1-57/170L | 57 | 35 | 45.6 | 80 | 195 | 170 | 145 | ||||
| Using area | Product model | Rating voltage virtual value (kv) | System nominal voltage virtual value (kV) | Continuous working voltage virtual value(kv) | DC(U1 mA) Ref. Voltage noless | Max.residualvoltage peakvalue(kv) | 2000μ square waveflux capacity (A) | 4/10u simpulse current peak value (kA) | Max.leaking current under 0.75DCref. voltage (uA) | ||
| Teep wave impulse current | Lighting impulse current | Operating impulse current | |||||||||
| Power station (Z) | YH5WX2-51/134L | 51 | 35 | 40.8 | than(kv) 73 | 154 | 134 | 114 | 400 | 100 | 50 |
| YH5WX2-54/142L | 54 | 35 | 43.2 | 77 | 163 | 142 | 121 | ||||
| YH5WX2-57/170L | 57 | 35 | 45.6 | 80 | 195 | 170 | 145 | ||||
Complete Accessories
Sensor,live display series
6-35KVlive displayDXN-V(GL-3)
Insulating cylinderseries
VS1Insulating cylinder JS2-10Q/1600A\~4000A
Contact/Contactarmseries