Other Specifications
| Operating Temp. | -40℃~75℃ |
| Storage Temp. | -40℃~85℃ |
| Relative Humidity | |
| Altitude | 4000m |
| IP Level | IP20 |
| Input Protection | 3KA lightning protection |
| Output Protection | Overvoltageshutdown,shortcircuit protection,output fuse protection. |
| Isolation | 1200VDC-input and output to earth |
| Cooling | One fan (front-to-back airflow) |
| Fan Speed | Temperatureand output current regulated |
| MTBF | > 500000 hours (T_ambient: 25℃) Telcordia SR-332 Issue 1 |
| Acoustic Noise | ≤55dB at100VDC input and full load (T_ambient: |
| Dimensions | 107Wx40.8Hx270D(mm) |
| Weight | 1.5Kg |
Applicable Standards
| Safety | IEC/EN62109-1 |
| EMC | EN55032 Class B (emission) IEC61000-4-2 (electrostatic discharge) IEC61000-4-3 (radiated immunity) IEC61000-4-4 (EFT) IEC61000-4-5 (surge immunity) IEC610o0-4-6 (conducted immunity) EN IEC 61000-6-4:2019 ENIEC61000-6-2:2019 |
| Environment | ETSI EN 300 019-2 (-1,-2,-3) ETSI EN 300 132-2 |
HPN48-220-3000
Introduction
HPN48-220-3000 is a digital inverter module.It is specially designed for telecom,network accessand energy storage system applications and so on. It can workwith outstanding reliability,efficiency and high power density. HPN48-220-3000 support parallel connection,also can be used in 3-phase Y-type system (by monitor setting).
Features
Digital control
Digital primary and secondary control,realizing excellent monitoring and regulation.
Highreliability design
One fan front-to-back airflow with latest thermal solution and experienced design.
ExcellentEMCperformance
Lower interference and excellent susceptibility give the module a better compatibility.
Globalapprovals Meet CE standard.
DC Input
| Input Voltage Range | 42-58VDC (Nominal: 53.5VDC) |
| Maximum Input Current | 75A |
Output
| Voltage | 200-230VAC (Nominal220/230VAC) |
| Rated Current | 10.9Aat220VAC,resistive load |
| Frequency | 50/60Hz |
| Freqnency Stability | ≤1% |
| Static Voltage Regulation | ≤1% |
| Dynamic Voltage Regulation | ≤10% (recovery time ≤60ms) |
| THDv | ≤3%,rated resistiveload ≤6%,rated non resistive load |
| LoadPower Factor Requirement | ≥0.8 |
| Efficiency | ≥94% @53.5Vin/220Vo/50%load |
| Current Sharing | ≤5% |
| Rated Output Power | 3000VA/2400W (46-58VDC) 2500VA/2000W (other input) |
| 46-58Vin Output Overload Capacity (Resistive load) | 105%≤Load≤125%,t>1min Load>125%,t≤1s |
| 42-46Vin Output Overload Capacity | 105%≤Load≤125%,t>10min 155%≤Load≤150%,t>10s Load>150%,t≤1s |
Other Specifications
| Operating Temp. | -20℃~75℃ |
| Storage Temp. | -40℃~85℃ |
| Relative Humidity | |
| Altitude | 4000m (Derating>2000m) |
| IPLevel | IP20 |
| Input Protection | Input fuse protection, Under/Overvoltageshutdown |
| OutputProtection | Under/Overvoltage shutdown,short circuit protection,output fuse protection,5KA lightning protection |
| Isolation | 4242VDC-input and output 2121VDC-outputand earth 707VDC-input and earth |
| Paralleling | Up to 12 modules in parallel |
| Fan Speed | Temperature and output current regulated |
| MTBF | ≥5000o0 hours(T_ambient:25℃) TelcordiaSR-332Issue1 |
| Acoustic Noise | ≤ 55dB at rated input and output, full load(T_ambient: |
| Dimensions | 107Wx40.8Hx270D(mm) |
| Weight | 2.0Kg |
Applicable Standards
| Safety | UL1741,EN/IEC 62477-1-2012,EN/IEC 62368-1 |
| EMC | EN55032ClassB (emission) ENIEC61000-6-4:2019,IEC 61000-6-4:2018 EN61000-3-12:2011,IEC61000-3-12:2011 ENIEC61000-3-11:2019,IEC61000-3-11:2017 ENIEC 61000-6-2:2019,IEC61000-6-2:2016 IEC61000-3-2IEC61000-3-3 IEC61000-4-2(electrostaticdischarge) IEC61000-4-3(radiated immunity) IEC61000-4-4(EFT)surge immunity) IEC61000-4-5 IEC61000-4-6(conducted immunity) IEC61000-4-8IEC61000-4-11 |
Diagrams
HPB48-48-5800
Introduction
HPB48-48-5800 is a non-isolated DC/DC converter which has battery charging and discharging management function.It can automatically adapt to different charging voltages,with fast chargingand long service life.Module can achieve the common use of batteries of different types,capacities,and manufacturers,adapting to the construction and maintenance needs of communication base stations.
Features
Highefficiencyand high powerdensity 9 8 % efficiencyand 80.6W/in? power density. ·Digital control Digital control,realize excellent monitoring and regulation. High reliabilitydesign One fan front-to-back air flow with latest thermal solution and experienced design. Excellent EMC performance Lower interference and excellent susceptibility give module better compatibility. Globalapprovals Meet CE,ULandTUVstandard.
Charging Mode
| Bus Bar (Input) | |
| Voltage range | 43.2-58VDC |
| Rated voltage | 53.5VDC |
| Input Current | |
| Battery (Output) | |
| Voltage range | 43.2-57.6VDC |
| Ratedvoltage | 48VDC |
| Power | 5760W |
| Max. Current | 100A |
| Static Voltage Regulation | |
| Ripple | |
| Startup Time | 3-8s |
| Efficiency | 98% |
Discharging Mode
| Battery (Input) | |
| Voltage range | 43.2-57.6VDC |
| Rated voltage | 48VDC |
| Input Current | |
| Bus Bar (Output) | |
| Voltage range | 43.2-58VDC |
| Rated voltage | 53.5VDC |
| Power | 5830W |
| Max. Current | 110A at 53VDC |
| Stic Volthage | |
| Line Regulation | |
| Load Regulation | |
| Temperature Coefficient | |
| Dynamic Voltage Regulation | |
| Psophometric | |
| Ripple | |
| Startup Time | 3-8s |
| Efficiency | 98% |
Other Specifications
| Operating Temp. | -40℃~75℃ |
| Storage Temp. | -40℃~85℃ |
| Relative Humidity | |
| Altitude | 4000m |
| IP Level | IP20 |
| Input Protection | 5kA lightning protection |
| Output Protection | Overvoltage shutdown,short circuit protection,output fuse protection. |
| Isolation | 707VDC-input and output to earth |
| Cooling | One fan (front-to-back airflow) |
| Fan Speed | Temuparature and output current |
| MTBF | > 500000 hours (T_ambient:25℃) Telcordia SR-332 Issue 1 |
| Acoustic Noise | ≤55dBat48VDCinputandfull load (T_ambient: |
| Dimensions | 107Wx40.8Hx270D(mm) |
| Weight | 1.8Kg |
Applicable Standards
| Safety | IEC62368-1,UL62368-1,EN62368-1 |
| EMC | EN55032 ClassA (emission) EN 61000-3-12:2011 EN IEC 61000-3-11:2019 EN 55035:2017+A11:2020 IEC61000-3-2C61000-3-3 IEC61000-4-2 (electrostatic discharge) IEC61000-4-3 (radiated immunity) IEC61000-4-4EFT) IEC61000-4-5 (surge immunity) IEC61000-4-6 (conducted immunity) IEC61000-4-8 |
| Environment | ETSI EN 300 019-2 (-1.-2,-3) ETSIEN300 132-2 |
Diagrams(Charging Mode)
Diagrams(Discharging Mode)
QUALITYSYSTEM
"Three phases,nine steps." Triple-valida tion protocols,multi-tiered gatekeeping to secure optimal suppliers.
Phase 1 Phase 2 Phase 3 SupplierSelection > Process Control IntegratedManagement · Supplier Qualification Screening · Technical Sustaining ·StateControlTower · Compliance Auditing ·Process Control · Risk ldentification ·QMSCertification • NPI、DVT、MP、Logistics Performance Governance QMSCertification Process Verification ProductVerification Verifythesupplier'scertifications Comprehensivecertification Rigorousqualitymanagement inquality,viroment,oial ofsuppliers'manufacturing systemcertificationofsuppliers ponsibility,cybersecurityand info and testing processes. products. rmationsecuritysystem.
PRODUCTIONTESTING
Contactus
YourTrusted PowerSolutions Partner
围 □ \~ 0
I Hanertek ElectricalCo.,Ltd.
I www.hanertek.com info@hanertek.com +86 755-27900696
Funing Hi-techInd'lPark,Bao'an Dist.Shenzhen,Guangdong,P.R.C