Derived Products When The Contactor is Assembled With Following Accessory Module
Derived products Contactor Accessorial modular Picture
Reversing
contactor
Auxiliary Contact
Dust cover
Electromagnetic
Starter
AC(V) 50Hz
AC(V) 60Hz
AC(V) 50/60Hz
DC(V)
24 36 48 110 127 220 380 415
24 36 48 110 127 220 380 415
24 36 48 110 127 220 380 415
12 24 36 48 110 127 220 -
UNAC-M
Rated impulse withstand voltage correction factor
Altitude (m)
Rated operation current correction factor
2000
1
3000
0.88
4000
0.78
1 0.92 0.90
Ambient temperature (℃) 55 60 65 70
Correction factor 1 0.93 0.875 0.75
www.unionele.com I 48
UNION ELECTRICS
AC Contactor
Type Amax Bmax Cmax a b
91
Installation and overall dimensions of UNAC-M06/N~M16/N series AC contactor
Dmax Φ
59 58 94 80±0.35 50±0.48 4.2
91 59 70 106 35±0.35 50±0.48 4.2
UNAC-M06/N-M16/N
UNAC-M06/Z/N-M16/Z/N
Type
Number of N/O contact
Configuration of contacts
F4-M Auxiliary contact group
Number of N/C contact
F4-M20
F4-M11
F4-M02
2
1
0
4
3
2
1
0
0
1
2
0
1
2
3
4
Product
F4
F4-M31
F4-M22
F4-M13
F4-M04
-M40
FS-M Surge suppression module
FS-M
Product
Model of Surge
Suppression Module
Control Voltage
AC/DC:24V-48V
AC/DC:380V-440V
AC/DC:110V-240V
47 I www.unionele.com
a
Amax
b Bmax
Cmax
Dmax(F4-M)
UNION ELECTRICS
AC Contactor
UNION ELECTRICS
Modular Contactors
www.unionele.com I 50
Modular contactors can be used to remote control applications in alternative
networks:
lighting, heating, ventilation, roller blinds. sanitary hot water mechanical
ventilation systems, etc load-shedding of non-priority circuits
Indication O+F
This auxiliary allows indication or control of the open
\"or\"closed\"postition of the contactor power contacts
Contactors Contactors Auxiliaries
This auxiliary allows indication or control of the
\"open\"or\"closed\" position of the contactor
power contacts
Used to control a contactor in impulse-type
mode or to combine latched or impulse-type
control orders
230VAC
24VAC
Dual control BACTc Indication BACTs
Modular
The breadth of the ICT modular contactor range satisfies most application requirements. These modular contactors can be combined
with auxiliary control, protection, and indication functions.
The range covers 1P, 2P, 3P, and 4P types, with rated operational currents from 16 A up to 100 A, providing reliable performance under
both AC7a (resistive load) and AC7b (inductive load) conditions.
Contactors
Motor power kW
380V/400V 660V/690V
2.2 3
2.2
4
4
5.5
5.5
3
4
4
4
4
Maximum operation current A
(AC-3 380V/400V)
Number of contacts contained in the contactor body
NO NC
Contactor model
UNAC-M0610
UNAC-M0601
UNAC-M0910
UNAC-M0901
UNAC-M1210
UNAC-M1201
UNAC-M1204
UNAC-M1208
2.2 3
2.2 3
UNAC-M0604
UNAC-M0608
6 1 0
6 0 0
6 0 0
6 0 1
4
4
4
4
UNAC-M0904
UNAC-M0908
1 0
0 0
0 0
0 1
9
9
9
9
12
12
12
12
5.5
5.5
4
4
1 0
0 0
0 0
0 1
1 0
0 0
0 0
0 1
7.5
7.5
7.5
7.5
4
4
4
4
16
16
16
16
UNAC-M1610
UNAC-M1601
UNAC-M1604
UNAC-M1608
UNAC-M
49 I www.unionele.com
UNION ELECTRICS
AC Contactor
UNION ELECTRICS
Modular Contactors
www.unionele.com I 50
Modular contactors can be used to remote control applications in alternative
networks:
lighting, heating, ventilation, roller blinds. sanitary hot water mechanical
ventilation systems, etc load-shedding of non-priority circuits
Indication O+F
This auxiliary allows indication or control of the open
\"or\"closed\"postition of the contactor power contacts
Contactors Contactors Auxiliaries
This auxiliary allows indication or control of the
\"open\"or\"closed\" position of the contactor
power contacts
Used to control a contactor in impulse-type
mode or to combine latched or impulse-type
control orders
230VAC
24VAC
Dual control BACTc Indication BACTs
Modular
The breadth of the ICT modular contactor range satisfies most application requirements. These modular contactors can be combined
with auxiliary control, protection, and indication functions.
The range covers 1P, 2P, 3P, and 4P types, with rated operational currents from 16 A up to 100 A, providing reliable performance under
both AC7a (resistive load) and AC7b (inductive load) conditions.
Contactors
Motor power kW
380V/400V 660V/690V
2.2 3
2.2
4
4
5.5
5.5
3
4
4
4
4
Maximum operation current A
(AC-3 380V/400V)
Number of contacts contained in the contactor body
NO NC
Contactor model
UNAC-M0610
UNAC-M0601
UNAC-M0910
UNAC-M0901
UNAC-M1210
UNAC-M1201
UNAC-M1204
UNAC-M1208
2.2 3
2.2 3
UNAC-M0604
UNAC-M0608
6 1 0
6 0 0
6 0 0
6 0 1
4
4
4
4
UNAC-M0904
UNAC-M0908
1 0
0 0
0 0
0 1
9
9
9
9
12
12
12
12
5.5
5.5
4
4
1 0
0 0
0 0
0 1
1 0
0 0
0 0
0 1
7.5
7.5
7.5
7.5
4
4
4
4
16
16
16
16
UNAC-M1610
UNAC-M1601
UNAC-M1604
UNAC-M1608
UNAC-M
49 I www.unionele.com
UNION ELECTRICS
AC Contactor
The UNDW1 Series Intelligent Air Circuit Breaker (hereinafter referred to as circuit breaker) is designed for distribution networks with AC
50 Hz, rated working voltages of 400 V and 690 V, and rated currents up to 6300 A. It is used to distribute electrical energy and to protect
lines and equipment against overload, undervoltage, short circuit, grounding, and other faults.
The circuit breaker is equipped with an intelligent controller featuring precise selective protection and multifunctional capabilities,
ensuring comprehensive protection across electrical systems. It is particularly suitable for distribution networks where improved power
supply reliability and prevention of unnecessary outages are required.Among them, the 2H and 3H intelligent controllers feature
communication interfaces that allow easy connection with field bus systems.
They support four remote functions: telemetry, remote regulation, remote communication, and control, meeting the requirements of
modern control automation.
Leakage protection can be achieved by configuring a leakage current transformer together with the intelligent controller.
The circuit breaker with rated currents up to 1000 A can also be used for overload, short circuit, undervoltage, and ground fault
protection of motors in AC 50 Hz and 400 V networks, and is suitable for infrequent motor starting under normal conditions.
The UNDW1 Series is available in fixed type and withdrawable (drawable) type versions, offering flexibility for different installation and
maintenance requirements.
IEC 60947-1 General principles for low-voltage switchgear and controlgear.
IEC 60947-2 Low-voltage switchgear and controlgear, low-voltage circuit breakers.
IEC 60947-4-1 Low-voltage switchgear and controlgear, electromechanical contactors and motor starters.
Overview and guidelines for environmental testing of electrical and electronic products.
Climatic and environmental conditions for electrical products at different altitudes.
The Circuit Breaker Meets the Following Standards
Air
Circuit
Breaker
General
www.unionele.com I 52
UNION ELECTRICS
Intelligent Air Circuit Breaker
UNION ELECTRICS
Modular Contactors
51 I www.unionele.com
Technical Data
-5°C to +60°C
-40°C to +70°C
Treatment 2(relative humidity 95% at 55°C)
ELSV compliance(Extra Low Safety Voltage)for 12/24/48vac versions
The product control conforms to the SELV(safety extra low voltage)requirements
Power circuit
Voltage rating(Ue) 1P,2P
3P,4P
Frequency
Endurance(O-C)
Electrical
Maximum number of switching operation a day
Additional characteristics
Insulation voltage
Pollution degree
Rated impulse withstand voltage(Uimp)
Degree of protection(IEC 60529) Device only
Device in modular enclosure
Operating temperature
Storage temperature
Tropicalization(lEC 60068-1)
250V AC
400VAC
50Hz or 60Hz
100,000 cycles
100
500 V AC
2
2.5kV(4 kV for 12124/48V AC)
IP20
IP40
(1)In the case of contactor mounting in an enclosure for which the interior temperature is in the range between 50 C and 60 C, it is ° °
necessary to use a spacer, between each contactor.
(1)
Dimensions
The UNDW1 Series Intelligent Air Circuit Breaker (hereinafter referred to as circuit breaker) is designed for distribution networks with AC
50 Hz, rated working voltages of 400 V and 690 V, and rated currents up to 6300 A. It is used to distribute electrical energy and to protect
lines and equipment against overload, undervoltage, short circuit, grounding, and other faults.
The circuit breaker is equipped with an intelligent controller featuring precise selective protection and multifunctional capabilities,
ensuring comprehensive protection across electrical systems. It is particularly suitable for distribution networks where improved power
supply reliability and prevention of unnecessary outages are required.Among them, the 2H and 3H intelligent controllers feature
communication interfaces that allow easy connection with field bus systems.
They support four remote functions: telemetry, remote regulation, remote communication, and control, meeting the requirements of
modern control automation.
Leakage protection can be achieved by configuring a leakage current transformer together with the intelligent controller.
The circuit breaker with rated currents up to 1000 A can also be used for overload, short circuit, undervoltage, and ground fault
protection of motors in AC 50 Hz and 400 V networks, and is suitable for infrequent motor starting under normal conditions.
The UNDW1 Series is available in fixed type and withdrawable (drawable) type versions, offering flexibility for different installation and
maintenance requirements.
IEC 60947-1 General principles for low-voltage switchgear and controlgear.
IEC 60947-2 Low-voltage switchgear and controlgear, low-voltage circuit breakers.
IEC 60947-4-1 Low-voltage switchgear and controlgear, electromechanical contactors and motor starters.
Overview and guidelines for environmental testing of electrical and electronic products.
Climatic and environmental conditions for electrical products at different altitudes.
The Circuit Breaker Meets the Following Standards
Air
Circuit
Breaker
General
www.unionele.com I 52
UNION ELECTRICS
Intelligent Air Circuit Breaker
UNION ELECTRICS
Modular Contactors
51 I www.unionele.com
Technical Data
-5°C to +60°C
-40°C to +70°C
Treatment 2(relative humidity 95% at 55°C)
ELSV compliance(Extra Low Safety Voltage)for 12/24/48vac versions
The product control conforms to the SELV(safety extra low voltage)requirements
Power circuit
Voltage rating(Ue) 1P,2P
3P,4P
Frequency
Endurance(O-C)
Electrical
Maximum number of switching operation a day
Additional characteristics
Insulation voltage
Pollution degree
Rated impulse withstand voltage(Uimp)
Degree of protection(IEC 60529)
Device only
Device in modular enclosure
Operating temperature
Storage temperature
Tropicalization(lEC 60068-1)
250V AC
400VAC
50Hz or 60Hz
100,000 cycles
100
500 V AC
2
2.5kV(4 kV for 12124/48V AC)
IP20
IP40
(1)In the case of contactor mounting in an enclosure for which the interior temperature is in the range between 50 C and 60 C, it is ° °
necessary to use a spacer, between each contactor.
(1)
Dimensions
Toroidal
Current
Transformer
The TTC series toroidal transformers allow the sense of leaking currents to earth, These transformers have been desiened to be coupled
to the ELR series earth leakage current relays.
TTC Type
Turns Ratio
System Voltage
System Frequency
Insulation Voltage
Distance Between CBCT and DELR
OperatingTemperature
Storage Temperature
Humidty
Measure of detecting Earth Leakge Currents single phase, three phase with or without neutral applications;
Hole diameters: Φ40 mm ;Φ80 mm ; Φ120 mm ; Φ160 mm; Φ210 mm;
Surface mounting with fixing slots;
Plug-in mounting for secondary terminals;
Fire Retardant insulated plastic Housing.
Main Features
Closed Toroid
200/1A
720V maximum
50 Hz or 60 Hz
3kV for 1 minute
<1 meters
0°C to +55°C
-25°C to +55°C
Up to 95% RH
Technical Data
Dimensions
A
B
C
D
E
F
G
TTC-210
211
262.5
248
40
4.3
186
40
TTC-160
161
212.5
188
40
4.3
146
40
TTC-40
41
88
74
40
4.3
42
40
A
B
C
D
E
F
G
TTC-80
81
133
120
40
4.3
85
40
TTC-120
121
172.5
158
40
4.3
110
40
Toroidal Current Transformer
Toroidal Current Transformer
www.unionele.com I 54
UNION ELECTRICS
Toroidal Current Transformer
Technical Parameters
Model
Frame current rating Inm(A)
Rated working current In (A)
Rated working voltage Ue (V)
Rated insulation voltage Ui(V)
Rated impulse withstand voltage Uimp (kV)
Power frequency withstand voltage U(V)1min
Pole number
Rated limit short circuit breaking capacity
(effective value)Icu(KA)
Rated short circuit breaking capacity
(effective value)lcs(KA)
Rated short time withstand current
(1s)(RMS)Icw(KA)
Total breaking time (without additional delay)(ms)
Closing time(ms)
400V
690V
400V
690V
400V
690V
Electrical life (times)
Maintenance free
With maintenance
Mechanical
life (times)
UNDW1
2000 3200 4000 6300
(400)630,800,1000
1200,1600,2000
2000,2500,2900
3200,4000
3200,3600
3900,4000
4000,5000
6300
AC50Hz 400V/690V
1000
12
AC2500V 50Hz
3P/4P
12~18
≤60
1000 500
2500
10000
100
65
65
65
65
65
100
65
85
65
85
65
AC50Hz 400V/690V
1000
12
AC2500V 50Hz
3P/4P
12~18
≤60
2500 200
2500 2000
10000 8000
138
105
138
105
138
105
138
105
138
105
138
105
Operational
performance
53 I www.unionele.com
UNION ELECTRICS
Intelligent Air Circuit Breaker
Toroidal
Current
Transformer
The TTC series toroidal transformers allow the sense of leaking currents to earth, These transformers have been desiened to be coupled
to the ELR series earth leakage current relays.
TTC Type
Turns Ratio
System Voltage
System Frequency
Insulation Voltage
Distance Between CBCT and DELR
OperatingTemperature
Storage Temperature
Humidty
Measure of detecting Earth Leakge Currents single phase, three phase with or without neutral applications;
Hole diameters: Φ40 mm ;Φ80 mm ; Φ120 mm ; Φ160 mm; Φ210 mm;
Surface mounting with fixing slots;
Plug-in mounting for secondary terminals;
Fire Retardant insulated plastic Housing.
Main Features
Closed Toroid
200/1A
720V maximum
50 Hz or 60 Hz
3kV for 1 minute
<1 meters
0°C to +55°C
-25°C to +55°C
Up to 95% RH
Technical Data
Dimensions
A
B
C
D
E
F
G
TTC-210
211
262.5
248
40
4.3
186
40
TTC-160
161
212.5
188
40
4.3
146
40
TTC-40
41
88
74
40
4.3
42
40
A
B
C
D
E
F
G
TTC-80
81
133
120
40
4.3
85
40
TTC-120
121
172.5
158
40
4.3
110
40
Toroidal Current Transformer
Toroidal Current Transformer
www.unionele.com I 54
UNION ELECTRICS
Toroidal Current Transformer
Technical Parameters
Model
Frame current rating Inm(A)
Rated working current In (A)
Rated working voltage Ue (V)
Rated insulation voltage Ui(V)
Rated impulse withstand voltage Uimp (kV)
Power frequency withstand voltage U(V)1min
Pole number
Rated limit short circuit breaking capacity
(effective value)Icu(KA)
Rated short circuit breaking capacity
(effective value)lcs(KA)
Rated short time withstand current
(1s)(RMS)Icw(KA)
Total breaking time (without additional delay)(ms)
Closing time(ms)
400V
690V
400V
690V
400V
690V
Electrical life (times)
Maintenance free
With maintenance
Mechanical
life (times)
UNDW1
2000 3200 4000 6300
(400)630,800,1000
1200,1600,2000
2000,2500,2900
3200,4000
3200,3600
3900,4000
4000,5000
6300
AC50Hz 400V/690V
1000
12
AC2500V 50Hz
3P/4P
12~18
≤60
1000 500
2500
10000
100
65
65
65
65
65
100
65
85
65
85
65
AC50Hz 400V/690V
1000
12
AC2500V 50Hz
3P/4P
12~18
≤60
2500 200
2500 2000
10000 8000
138
105
138
105
138
105
138
105
138
105
138
105
Operational
performance
53 I www.unionele.com
UNION ELECTRICS
Intelligent Air Circuit Breaker
25 selectable sensitivity settings: 30 mA to 30 A
9 selectable time delays: 0 ms to 3s
Earth leakage level indicators
Detection of no connection to CT
Relay tripped indicator
Trip starting indicator
Protected against nuisance tripping
Features for ELR only*
50% pre-fault output contact
Remote test and remote reset functions
Features for ELR only***
UKM32Z with the use of
Remote test and remote reset functions
Main Features
Technical Data
Settings
Sensitivity adjustment
Accuracy
Time delay setting
Accuracy
Frequency
VA rating
Auxiliary supply
Time delay
Trip
Leakage current*
Remote test/ reset inputs
Sensor
Contacts (Trip / 50% pre-fault*)
Contact arrangement
Contact rating
Contact material
Operating time
Expected electrical life
Expected mechanical life
C pole output current
DC power output voltage
DC power output current
Mounting method
Weight
Supply voltage
Auxiliary supply
Indicators
Inputs
Outputs
NPN-type
transistor***
Mechanical
ELR Earth Leakage Relay
30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA,
750mA,1A, 1.25A, 1.5A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30A
+0%~-15%
Instantaneous, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s, 3s
±5%
110V AC±10% or 240V
90-120VAC
50 Hz or 60 Hz
Less than 3 VA
Green LED
Red LED
Red LED
5 red LED for leakage levels
N.O. dry contact*
CT
Change over
6A,250V AC (cos φ=1)
Silver alloy
15 ms max.
100,000 operations at rated current
5×106 operations
50mA
12V
50mA
Panel mounted, DIN rail mounted, Screws mounted
0.3kg
Leakage
Relay
Earth
UNION ELECTRICS
Earth Leakage Relay
www.unionele.com I 56
UNION ELECTRICS
Toroidal Current Transformer
E 1 N E 3
1 2
single-phase 3 phases
without neutral
N
E 3
1 2 E
N
3
1 2
3 phases
with neutral
3 phases
with neutral
L1
L2
L3
N
E C.T.
E
1-Phase,2-wire 3-Phase,3-wire 3-Phase,4-wire
C.T. C.T.
E E
Wiring
55 I www.unionele.com
25 selectable sensitivity settings: 30 mA to 30 A
9 selectable time delays: 0 ms to 3s
Earth leakage level indicators
Detection of no connection to CT
Relay tripped indicator
Trip starting indicator
Protected against nuisance tripping
Features for ELR only*
50% pre-fault output contact
Remote test and remote reset functions
Features for ELR only***
UKM32Z with the use of
Remote test and remote reset functions
Main Features
Technical Data
Settings
Sensitivity adjustment
Accuracy
Time delay setting
Accuracy
Frequency
VA rating
Auxiliary supply
Time delay
Trip
Leakage current*
Remote test/ reset inputs
Sensor
Contacts (Trip / 50% pre-fault*)
Contact arrangement
Contact rating
Contact material
Operating time
Expected electrical life
Expected mechanical life
C pole output current
DC power output voltage
DC power output current
Mounting method
Weight
Supply voltage
Auxiliary supply
Indicators
Inputs
Outputs
NPN-type
transistor***
Mechanical
ELR Earth Leakage Relay
30mA, 50mA, 75mA, 100mA, 125mA, 150mA, 200mA, 250mA, 300mA, 500mA,
750mA,1A, 1.25A, 1.5A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5A, 15A, 20A, 25A, 30A
+0%~-15%
Instantaneous, 50ms, 100ms, 150ms, 250ms, 350ms, 500ms, 1s, 3s
±5%
110V AC±10% or 240V
90-120VAC
50 Hz or 60 Hz
Less than 3 VA
Green LED
Red LED
Red LED
5 red LED for leakage levels
N.O. dry contact*
CT
Change over
6A,250V AC (cos φ=1)
Silver alloy
15 ms max.
100,000 operations at rated current
5×106 operations
50mA
12V
50mA
Panel mounted, DIN rail mounted, Screws mounted
0.3kg
Leakage
Relay
Earth
UNION ELECTRICS
Earth Leakage Relay
www.unionele.com I 56
UNION ELECTRICS
Toroidal Current Transformer
E 1 N E 3
1 2
single-phase
3 phases
without neutral
N
E 3
1 2 E
N
3
1 2
3 phases
with neutral
3 phases
with neutral
L1
L2
L3
N
E C.T.
E
1-Phase,2-wire 3-Phase,3-wire 3-Phase,4-wire
C.T. C.T.
E E
Wiring
55 I www.unionele.com
Thermal
Relay
The UNTR1 Series Thermal Relays (UNTR1-25, UNTR1-36, UNTR1-93, UNTR1-150, UNTR1-200, UNTR1-630) are suitable for use in circuits
with rated voltages up to 660 V
and rated currents up to 93 A, at AC 50/60 Hz, providing reliable overcurrent protection for AC motors.
These relays feature a differential mechanism and temperature compensation, ensuring stable performance under varying operating
conditions. The UNTR1 relays can also be directly
mounted onto CJX2 series AC contactors, allowing convenient assembly and enhanced motor protection.
The product conforms to IEC 60947-4-1 standard.
General
Motion Characteristic: Three-phase Balance Motion Time
No Times of the setting current(A) Motion time Start condition Ambient temperature
>2h
<2h
<4min
1
2
3
4
Cold state
Heat state(Following the No.1 test)
Cold state
20±5℃
1.05
1.2
1.5
7.2
≤10A 2s<Tp≤10s ≤63A
>10A 4s<Tp≤10s >63A
Phase-losing Motion Characteristic
No
Times of the setting current(A)
Start condition Ambient temperature Motion
time
1
2
Cold state
20±5℃
1.0
1.15
>2A
<2A
Any two phases Another phase
0.9
0 Heat state(Following the No.1 test)
www.unionele.com I 58
UNION ELECTRICS
Thermal Relay
Typical Application Diagram
Case Dimensions
UNION ELECTRICS
Earth Leakage Relay
57 I www.unionele.com
ELR1E ELR1Z
ELR1
ELR02
Thermal
Relay
The UNTR1 Series Thermal Relays (UNTR1-25, UNTR1-36, UNTR1-93, UNTR1-150, UNTR1-200, UNTR1-630) are suitable for use in circuits
with rated voltages up to 660 V
and rated currents up to 93 A, at AC 50/60 Hz, providing reliable overcurrent protection for AC motors.
These relays feature a differential mechanism and temperature compensation, ensuring stable performance under varying operating
conditions. The UNTR1 relays can also be directly
mounted onto CJX2 series AC contactors, allowing convenient assembly and enhanced motor protection.
The product conforms to IEC 60947-4-1 standard.
General
Motion Characteristic: Three-phase Balance Motion Time
No Times of the setting current(A) Motion time Start condition Ambient temperature
>2h
<2h
<4min
1
2
3
4
Cold state
Heat state(Following the No.1 test)
Cold state
20±5℃
1.05
1.2
1.5
7.2
≤10A 2s<Tp≤10s ≤63A
>10A 4s<Tp≤10s >63A
Phase-losing Motion Characteristic
No
Times of the setting current(A)
Start condition Ambient temperature Motion
time
1
2
Cold state
20±5℃
1.0
1.15
>2A
<2A
Any two phases Another phase
0.9
0 Heat state(Following the No.1 test)
www.unionele.com I 58
UNION ELECTRICS
Thermal Relay
Typical Application Diagram
Case Dimensions
UNION ELECTRICS
Earth Leakage Relay
57 I www.unionele.com
ELR1E ELR1Z
ELR1
ELR02
Outline and Mounting Dimension
UNTR1-36 UNTR1-93
UNTR1-200 UNTR1-630
UNTR1-25
Accessories
Pic
Description
Application
UNTR1-25 mounting base
Assembled with UNTR1-25
to form a complete set
UNTR1-36 mounting base
Assembled with UNTR1-36
to form a complete set
UNTR1-93 mounting base
Assembled with UNTR1-93
to form a complete set
www.unionele.com I 60
UNION ELECTRICS
Thermal Relay
5.5~8
7~10
9~13
12~18
17~25
23~32
30~40
17~25
23~32
30~40
37~50
48~65
55~70
63~80
80~93
80~104
95~120
110~140
UNTR1-36
UNTR1-93
90~150
30~50
48~80
60~100
90~150
132~220
200~330
300~500
380~630
UNTR1-630
UNTR1-200
UNTR1-150
59 I www.unionele.com
UNTR1 Series Thermal Relay
0.1~0.16
0.16~0.25
0.25~0.4
0.4~0.63
0.63~1
1~1.6
1.6~2.5
2.5~4
4~6
Type Setting range(A)
UNTR1-25
UNION ELECTRICS
Thermal Relay
Outline and Mounting Dimension
UNTR1-36 UNTR1-93
UNTR1-200 UNTR1-630
UNTR1-25
Accessories
Pic
Description
Application
UNTR1-25 mounting base
Assembled with UNTR1-25
to form a complete set
UNTR1-36 mounting base
Assembled with UNTR1-36
to form a complete set
UNTR1-93 mounting base
Assembled with UNTR1-93
to form a complete set
www.unionele.com I 60
UNION ELECTRICS
Thermal Relay
5.5~8
7~10
9~13
12~18
17~25
23~32
30~40
17~25
23~32
30~40
37~50
48~65
55~70
63~80
80~93
80~104
95~120
110~140
UNTR1-36
UNTR1-93
90~150
30~50
48~80
60~100
90~150
132~220
200~330
300~500
380~630
UNTR1-630
UNTR1-200
UNTR1-150
59 I www.unionele.com
UNTR1 Series Thermal Relay
0.1~0.16
0.16~0.25
0.25~0.4
0.4~0.63
0.63~1
1~1.6
1.6~2.5
2.5~4
4~6
Type Setting range(A)
UNTR1-25
UNION ELECTRICS
Thermal Relay
UNION ELECTRICS
Automatic transfer switch
Structure and Wiring instructions
Backup power neutral wire
Backup power live wire
common power neutral wire
Backup power closing mechanical in dication
Common power closing mechanical indication
Backup power auto/manua switch
Backup power supply with electricitydication
Common power supply with electricity indicatior
Common power auto/nanua switch
Load output live wire
common power live wire
Operation handle
The temperature range of the operating environment is -5℃~+40℃, an d the average temperature within 24 hours shall be lower than
+35℃ , and the temperature range of the storage environmentis -25℃~+55℃, which can be reached+70℃ in a short time (within 24
hours).
The altitude of the installation site should be lower than 2000m.
The relative humidity at the installation site shall not exceed 50% when the ambient air temperature is +40℃, Higher relative humidity
is possible at lower temperatures. For example: when the average minimum temperature of the wettest month is +20℃, the monthly
average maximun relative humidity of that month can reach 90%Appropriate measures should be taken to prevent condensation due
to temperature changes.
Pollution level 3 (conductive pollution, or dry non-conductive pollution becomes conductive due to condensation)ATS can be installed
vertically or horizontally in the cabinet, if there are special installation requirements, contact US.
The protection grade of ATS case is lp30
Over voltage category
Main circuit category III; control auxiliary circuit category II.
Working conditions
Note:
◇ Terminal wiring area: fit for (1~25)mm²
◇ Wre connection screwis M5,torque:3.0N.m
Overall and installation dimension
www.unionele.com I 62
The UATA Automatic Transfer Switch (ATS) is a PC-class infrequent change-over switch with a two-station design (commonly used for
main power supply A and backup power supply B). It is suitable for AC systems with AC 50–60 Hz and rated currents from 6 A to 63 A.
The main function of the ATS is to ensure continuous operation. When the main power supply (A) fails, the ATS automatically switches to
the backup power supply (B) within 50 milliseconds, effectively preventing power outages and ensuring reliable system operation.
General
Automatic
Transfer
Switch
Operating environment temperature: -5 °C to +40 °C; The 24-hour average temperature must not exceed +35 °C.
Storage environment temperature: -25 °C to +55 °C (can reach up to +70 °C in a short period, within 24 hours).
Altitude: Installation site must be below 2000 m.
Relative humidity: Must not exceed 50% when ambient temperature is +40°C. Higher relative humidity is possible at lower
temperatures (e.g., at +20 °C, monthly average maximum relative humidity may reach 90%). Appropriate measures must be taken to
prevent condensation caused by temperature changes.
Pollution level: Class 3 (conductive pollution, or dry non-conductive pollution becoming conductive due to condensation).
Installation method: The ATS can be mounted vertically or horizontally inside a cabinet. For special installation requirements, please
contact us.
Protection grade: Ip30.
Overvoltage category: Main circuit -Category III; Control and auxiliary circuits -Category II.
Working Conditions
Rated operating current le(A)
Rated insulation voltage Ul
Rated impulse withstand voltage Uimp
Rated working voltage Ue
Rated frequency
Class
Pole number
Rated short-circuit current lq
Short circuit protection device (fuse)
Rated impulse withstand voltage
Control circuit
Auxiliary circuit
Contactor change-over time
Operation change-over time
Return change-over time
Power off time
Change-over operation time
Mechanical life
Electrical life
Usage category
Main technical parameters
6A/10A/16A/20A/25A/32A/40A/50A/63A
690V
8kV
AC220V/AC110V
50/60Hz
PC class: can be switched on and loaded without generating short-circuit current
2P 4P
50kA
RT16-00-63A
8kV
Rated control voltage Us: AC220V, 50Hz Normal working conditions: 85%Us-110%Us
AC220V/110V 50Hz le=5A
<50ms
<50ms
<50ms
<50ms
<50ms
>26000 times
>1500 times
AC-31B
UNION ELECTRICS
Automatic transfer switch
UATS4063
61 I www.unionele.com
UNION ELECTRICS
Automatic transfer switch
Structure and Wiring instructions
Backup power neutral wire
Backup power live wire
common power neutral wire
Backup power closing mechanical in dication
Common power closing mechanical indication
Backup power auto/manua switch
Backup power supply with electricitydication
Common power supply with electricity indicatior
Common power auto/nanua switch
Load output live wire
common power live wire
Operation handle
The temperature range of the operating environment is -5℃~+40℃, an d the average temperature within 24 hours shall be lower than
+35℃ , and the temperature range of the storage environmentis -25℃~+55℃, which can be reached+70℃ in a short time (within 24
hours).
The altitude of the installation site should be lower than 2000m.
The relative humidity at the installation site shall not exceed 50% when the ambient air temperature is +40℃, Higher relative humidity
is possible at lower temperatures. For example: when the average minimum temperature of the wettest month is +20℃, the monthly
average maximun relative humidity of that month can reach 90%Appropriate measures should be taken to prevent condensation due
to temperature changes.
Pollution level 3 (conductive pollution, or dry non-conductive pollution becomes conductive due to condensation)ATS can be installed
vertically or horizontally in the cabinet, if there are special installation requirements, contact US.
The protection grade of ATS case is lp30
Over voltage category
Main circuit category III; control auxiliary circuit category II.
Working conditions
Note:
◇ Terminal wiring area: fit for (1~25)mm²
◇ Wre connection screwis M5,torque:3.0N.m
Overall and installation dimension
www.unionele.com I 62
The UATA Automatic Transfer Switch (ATS) is a PC-class infrequent change-over switch with a two-station design (commonly used for
main power supply A and backup power supply B). It is suitable for AC systems with AC 50–60 Hz and rated currents from 6 A to 63 A.
The main function of the ATS is to ensure continuous operation. When the main power supply (A) fails, the ATS automatically switches to
the backup power supply (B) within 50 milliseconds, effectively preventing power outages and ensuring reliable system operation.
General
Automatic
Transfer
Switch
Operating environment temperature: -5 °C to +40 °C; The 24-hour average temperature must not exceed +35 °C.
Storage environment temperature: -25 °C to +55 °C (can reach up to +70 °C in a short period, within 24 hours).
Altitude: Installation site must be below 2000 m.
Relative humidity: Must not exceed 50% when ambient temperature is +40°C. Higher relative humidity is possible at lower
temperatures (e.g., at +20 °C, monthly average maximum relative humidity may reach 90%). Appropriate measures must be taken to
prevent condensation caused by temperature changes.
Pollution level: Class 3 (conductive pollution, or dry non-conductive pollution becoming conductive due to condensation).
Installation method: The ATS can be mounted vertically or horizontally inside a cabinet. For special installation requirements, please
contact us.
Protection grade: Ip30.
Overvoltage category: Main circuit -Category III; Control and auxiliary circuits -Category II.
Working Conditions
Rated operating current le(A)
Rated insulation voltage Ul
Rated impulse withstand voltage Uimp
Rated working voltage Ue
Rated frequency
Class
Pole number
Rated short-circuit current lq
Short circuit protection device (fuse)
Rated impulse withstand voltage
Control circuit
Auxiliary circuit
Contactor change-over time
Operation change-over time
Return change-over time
Power off time
Change-over operation time
Mechanical life
Electrical life
Usage category
Main technical parameters
6A/10A/16A/20A/25A/32A/40A/50A/63A
690V
8kV
AC220V/AC110V
50/60Hz
PC class: can be switched on and loaded without generating short-circuit current
2P 4P
50kA
RT16-00-63A
8kV
Rated control voltage Us: AC220V, 50Hz Normal working conditions: 85%Us-110%Us
AC220V/110V 50Hz le=5A
<50ms
<50ms
<50ms
<50ms
<50ms
>26000 times
>1500 times
AC-31B
UNION ELECTRICS
Automatic transfer switch
UATS4063
61 I www.unionele.com
Outline dimension
1 3
2 4
5 7
6 8
9 11
10 12
13 15
14 16
1P 18
2P 36
3P 54
4P 72
Technical Parameters
UNION ELECTRICS
Manual Changeover Switch
MCB-CO
www.unionele.com I 64
Changeover
Switch
Product advantage
Product model MCB-CO
Technical Parameters
Manual
The Manual Changeover Switch can switch on, carry load, and break the circuit under normal conditions, functioning as a switch
disconnector.
UNION ELECTRICS
Manual Changeover Switch
63 I www.unionele.com
Outline dimension
1 3
2 4
5 7
6 8
9 11
10 12
13 15
14 16
1P 18
2P 36
3P 54
4P 72
Technical Parameters
UNION ELECTRICS
Manual Changeover Switch
MCB-CO
www.unionele.com I 64
Changeover
Switch
Product advantage
Product model MCB-CO
Technical Parameters
Manual
The Manual Changeover Switch can switch on, carry load, and break the circuit under normal conditions, functioning as a switch
disconnector.
UNION ELECTRICS
Manual Changeover Switch
63 I www.unionele.com
Some electrical appliances used in homes and workplaces need to operate periodically at certain times during the day (for example, floor heaters,
electric water heaters and storage water heaters, lighting fixtures, or other similar devices). To meet such needs, programmable time switches using
electro-mechanical technology have been designed and manufactured.
Our Union brand time switches have the following features:
Equipped with a servomotor, offering precise timing capability.
Reserve function allows programs to continue for up to 100 hours during power cuts.
Operates with 220 V / 50 Hz supply voltage.
Independent auxiliary contact, usable in both AC and DC circuits up to 400 V.
96 notches on the programming disc, each corresponding to 15 minutes.
24 hours of the day are displayed on the same disc.
Can operate in two modes: manual and automatic.
Mounted on a standard 36 mm rail (per En50022).
Due to the small and sensitive servomotor, it should not be installed next to contactors or similar devices.
Must be protected by an independent thermal-magnetic circuit breaker (automatic fuse).
Main Features
Analog Timer Relay
Analog timer relays have a wide range of applications. They are used in all systems that require operation at specific times and deactivation after a
defined period. Typical applications include:
Park irrigation systems
Road lighting systems
Agricultural irrigation systems
School bells
Heating and cooling systems
Analog
Timer
Product advantage
This ensures that these systems operate automatically and only for the desired period of time, without requiring user intervention.
www.unionele.com I 66
UNION ELECTRICS
Analog Timer
UNION ELECTRICS
Motor Protection Switches
SPM Series Motor Protection Switches
The SPM Series Electric Motor Protection Circuit Breakers use a modular design with a compact structure. They feature reliable breaking
and protection functions, integrated with a thermal relay. The design ensures strong functionality, high versatility, and convenient
operation.
The SPM series conforms to IEC 60947-2, IEC 60947-4-1, and EN 60947-1 standards. The switch and contact device can be used for direct
motor starting.
The UV2/UV3 series outer covering provides a protection rating of up to IP65.
This series includes three product types:
SPM25 0.16A Motor Protection Switch
SPM25 0.25A Motor Protection Switch
SPM25 0.4A Motor Protection Switch
SPM25 0.63A Motor Protection Switch
SPM25 1A Motor Protection Switch
SPM25 1.6A Motor Protection Switch
SPM25 2.5A Motor Protection Switch
SPM25 4A Motor Protection Switch
SPM25 6.3A Motor Protection Switch
SPM25 10A Motor Protection Switch
SPM25 14A Motor Protection Switch
SPM25 18A Motor Protection Switch
SPM25 23A Motor Protection Switch
SPM25 25A Motor Protection Switch
SPM25 32A Motor Protection Switch
SPM80 40A Motor Protection Switch
SPM80 50A Motor Protection Switch
SPM80 63A Motor Protection Switch
SPM80 80A Motor Protection Switch
Description
Motor
Protection
Switches
SPM with button control: Thermo-magnetic motor protection circuit breaker with integrated button operation.
SPM with change-over switch control (with thermal protection): Thermomagnetic motor protection circuit breaker controlled by a
change-over switch.
SPM with change-over switch control (magnetic only): Magnetic motor protection circuit breaker controlled by a change-over switch
(without thermal protection).
65 I www.unionele.com
General
Product Photo
SPM80
Some electrical appliances used in homes and workplaces need to operate periodically at certain times during the day (for example, floor heaters,
electric water heaters and storage water heaters, lighting fixtures, or other similar devices). To meet such needs, programmable time switches using
electro-mechanical technology have been designed and manufactured.
Our Union brand time switches have the following features:
Equipped with a servomotor, offering precise timing capability.
Reserve function allows programs to continue for up to 100 hours during power cuts.
Operates with 220 V / 50 Hz supply voltage.
Independent auxiliary contact, usable in both AC and DC circuits up to 400 V.
96 notches on the programming disc, each corresponding to 15 minutes.
24 hours of the day are displayed on the same disc.
Can operate in two modes: manual and automatic.
Mounted on a standard 36 mm rail (per En50022).
Due to the small and sensitive servomotor, it should not be installed next to contactors or similar devices.
Must be protected by an independent thermal-magnetic circuit breaker (automatic fuse).
Main Features
Analog Timer Relay
Analog timer relays have a wide range of applications. They are used in all systems that require operation at specific times and deactivation after a
defined period. Typical applications include:
Park irrigation systems
Road lighting systems
Agricultural irrigation systems
School bells
Heating and cooling systems
Analog
Timer
Product advantage
This ensures that these systems operate automatically and only for the desired period of time, without requiring user intervention.
www.unionele.com I 66
UNION ELECTRICS
Analog Timer
UNION ELECTRICS
Motor Protection Switches
SPM Series Motor Protection Switches
The SPM Series Electric Motor Protection Circuit Breakers use a modular design with a compact structure. They feature reliable breaking
and protection functions, integrated with a thermal relay. The design ensures strong functionality, high versatility, and convenient
operation.
The SPM series conforms to IEC 60947-2, IEC 60947-4-1, and EN 60947-1 standards. The switch and contact device can be used for direct
motor starting.
The UV2/UV3 series outer covering provides a protection rating of up to IP65.
This series includes three product types:
SPM25 0.16A Motor Protection Switch
SPM25 0.25A Motor Protection Switch
SPM25 0.4A Motor Protection Switch
SPM25 0.63A Motor Protection Switch
SPM25 1A Motor Protection Switch
SPM25 1.6A Motor Protection Switch
SPM25 2.5A Motor Protection Switch
SPM25 4A Motor Protection Switch
SPM25 6.3A Motor Protection Switch
SPM25 10A Motor Protection Switch
SPM25 14A Motor Protection Switch
SPM25 18A Motor Protection Switch
SPM25 23A Motor Protection Switch
SPM25 25A Motor Protection Switch
SPM25 32A Motor Protection Switch
SPM80 40A Motor Protection Switch
SPM80 50A Motor Protection Switch
SPM80 63A Motor Protection Switch
SPM80 80A Motor Protection Switch
Description
Motor
Protection
Switches
SPM with button control: Thermo-magnetic motor protection circuit breaker with integrated button operation.
SPM with change-over switch control (with thermal protection): Thermomagnetic motor protection circuit breaker controlled by a
change-over switch.
SPM with change-over switch control (magnetic only): Magnetic motor protection circuit breaker controlled by a change-over switch
(without thermal protection).
65 I www.unionele.com
General
Product Photo
SPM80
UNION ELECTRICS
www.unionele.com I 68
UNION ELECTRICS
67 I www.unionele.com
UNION ELECTRICS
www.unionele.com I 68
UNION ELECTRICS
67 I www.unionele.com